mhouse WU2S User Manual

MhouseKit WU2
S
For power-operated swing gate
Installation instructions and warnings, and User Manual
IS0005A00EN_28-02-2011
English – 1
English
STEP 1 2
KNOWLEDGE OF THE PRODUCT AND PREPARATION FOR INSTALLATION
STEP 2 2
2.1 - PRODUCT DESCRIPTION AND INTENDED USE 2
2.2 - COMPONENTS USED TO SET UP A COMPLETE SYSTEM 3
PRELIMINARY CHECKS FOR INSTALLATION
STEP 3 3
3.1 - CHECKING SUITABILITY OF GATE TO BE AUTOMATED
AND RELATIVE ENVIRONMENT 3
3.2 - PRODUCT APPLICATION LIMITS 3
3.3 - PRODUCT DURABILITY 3
STEP 4 4
4.1 - PRELIMINARY CHECKS FOR INSTALLATION 4
4.2 - PREPARING ELECTRIC CABLES 4
INSTALLATION: ASSEMBLY AND CONNECTION OF COMPONENTS
STEP 5 6
5.1 - INSTALLING THE GEARMOTOR WU1SK 6
STEP 6 7
6.1 - INSTALLING CL2S 7
6.2 - INSTALLING AND CONNECTING PHOTOCELLS PH100 7
6.3 - INSTALLING AND CONNECTING THE FLASHING LIGHT FL100 7
6.4 - ELECTRICAL CONNECTION TO CONTROL UNIT CL2S 7
PROGRAMMING
STEP 7 13
7.1 - POWER SUPPLY CONNECTION 13
7.2 - INITIAL CHECKS 13
7.3 - LEARNING CONNECTED DEVICES 13
7.4 - LEARNING THE GATE LEAF OPENING AND CLOSING ANGLES 13
7.5 - CHECKING THE RADIO TRANSMITTERS 13
7.6 - SETTINGS 13
TESTING AND COMMISSIONING
STEP 8 15
8.1 - TESTING 15
8.2 - COMMISSIONING 15
MAINTENANCE
STEP 9 15
PRODUCT DISPOSAL 15
FURTHER INFORMATION
STEP 10 16
10.1 - ADVANCED SETTINGS 16
10.2 - OPTIONAL ACCESSORIES 17
10.3 - ADDING OR REMOVING DEVICES 19
10.4 - MEMORIZING RADIO TRANSMITTERS 20
10.5 - TROUBLESHOOTING 22
10.6 - DIAGNOSTICS AND SIGNALS 22
TECHNICAL SPECIFICATIONS OF PRODUCT COMPONENTS 25
APPENDIX 1 - EC declaration of conformity 28
USER’S GUIDE
STEP 11 29
11.1 - SAFETY INSTRUCTIONS 29
11.2 - GATE CONTROL 29
11.3 - MANUALLY RELEASING OR LOCKING THE GEARMOTOR 29
11.4 - MAINTENANCE OPERATIONS ADMISSIBLE TO THE USER 30
11.5 - REMOTE CONTROL BATTERY REPLACEMENT 30
11.6 - INSTALLING THE REMOTE CONTROL SUPPORT 30
APPENDIX 1 - EC declaration of conformity 31
CONTENTS
2 – English
English
GENERAL SAFETY WARNINGS AND PRECAUTIONS
• During installation, handle the automation with care, avoiding the risk of impact, dropping or contact with any type of liquid. Never place the pro ­duct near to sources of heat and never expose to naked flames. This may damage product components and cause malfunctions, fire or haz­ardous situations. If this occurs, suspend installation immediately and contact the MhouseTechnical Assistance.
• Never make modifications to any part of the product. Operations other than as specified can only cause malfunctions. The manufacturer declines all liability for damage caused by makeshift modifications to the product.
• If the power cable is damaged, it must be replaced exclusively by a qualified technician, to avoid potential risks.
• Connect the control unit to an electric power line equipped with an earthing system.
• The product should not be used by children or people with impaired physical, sensorial or mental capacities or who have not received ade­quate training in the safe use of the product.
• The key-operated selector switch must be positioned in sight of the automation, but far from moving parts and at a height of at least 1.5 m from the ground, not accessible by the public. If this is used in “hold-to­run” mode, ensure that there are no persons in the vicinity of the au ­tomation.
• In the vicinity of the automation children must be supervised to ensure that they do not play with it.
• Ensure that there are not points of entrapment or crushing with fixed parts when the gate leaf is in the maximum opening or closing position; protect parts if necessary.
• The product may not be considered an efficient system of protection against intrusion. If an efficient protection system is required, the au ­tomation must be integrated with other safety devices.
• The automation must not be used before performing the commissioning procedure as specified in the chapter “Testing and commissioning”.
• Check the automation frequently to ensure there is no imbalance, signs of wear or damage to electrical or mechanical parts. Do not use the automation if adjustments or repairs are necessary.
• In the event of long periods of disuse, to avoid the risk of leaks of harm­ful substances from the optional battery (PR1) disconnect it from the automation and store in a dry location.
• Do not allow children to play with fixed control devices. Keep remote control devices out of reach of children.
• The product’s packaging materials must be disposed of in full compli­ance with local regulations.
Operation warnings
• For cleaning the product surfaces, use a soft damp cloth. Use water only; never use detergents or solvents for cleaning.
––– STEP 1 –––
Safety warnings
• CAUTION! – This manual contains important instructions and warnings for personal safety. Incorrect installation could cause seri-
ous physical injury. Carefully read all parts of this manual before starting any work. If in doubt, suspend installation immediately and contact the Mhouse Technical Assistance.
• CAUTION! – Important instructions: keep this manual in a safe place to enable future product maintenance and disposal proce­dures.
• CAUTION! – According to the most recent European legislation, the production of a power-operated door or gate must comply with the standards envisaged in the Directive 2006/42/EC (Machinery Direc­tive) and in particular standards EN 12445; EN 12453; EN 12635 and EN 13241-1, which enable declaration of presumed conformity of the automation. In consideration of this, all mains connection, testing commissioning and maintenance operations must be per­formed exclusively by a qualified and skilled technician. All preliminary set-up, installation and programming operations may be performed by personnel with standard skills, provided that all instructions and the relative sequences in this manual are strictly observed, with particular reference to the warnings in this STEP 1.
Installation warnings
While reading this manual, take care to observe all instructions marked with the following symbol:
These symbols indicate subjects that may be the source of potential hazards and therefore the prescribed operations must be performed exclusively by qualified and skilled personnel, in observance of these instructions current safety standards.
• Before installation, ensure that this product is suitable for automation of your gate or door (see STEP 3 and chapter “Product Technical Specifi­cations”). If not suitable, do NOT proceed with installation.
• On the system power mains install a device for disconnection (not sup­plied), to guarantee a gap between contacts and complete disconnec­tion in the conditions of overvoltage category III.
All installation and maintenance operations must be performed with the automation disconnected from the power supply. If the power disconnect device is not visible from the location of the automa­tion, before work a notice should be affixed on the disconnect device, with the text “CAUTION! MAINTENANCE IN PROGRESS”.
CAUTION! - Never power up the motor before fully installed
on the column and leaf of the gate.
KNOWLEDGE OF THE PRODUCT AND PREPARATION FOR INSTALLATION
stated in this manual is to be considered improper and is strictly pro­hibited!
The main part of the automation comprises one control unit and two electromechanical gearmotors, each equipped with a 24 V DC motor, a worm reducer and a mechanical locking system with key to enable manu­al opening and closing of the gate in the event of a power failure. The control unit comprises a board and incorporated radio receiver which receives the commands sent by the user via a transmitter. It can memo­rise up to 256 GTX4 transmitters (if memorised in “Mode I”) and up to 6 pairs of PH100 photocells. Connection of the control unit with the various devices is by means of a single 2-wire cable (“ECSbus” system). The control unit can also be mains-powered (230 V) or alternatively by the Mhouse PF photovoltaic system. If powered from the mains, it can house a buffer battery (model PR1, optional accessory), which ensures that the automation can perform a number of manoeuvres for several hours in the event of a power failure. During the power failure, or at any other time, the gate leaf can be moved manually if required, by first releasing the gearmotor using the relative key (see chapter 11.3 - User’s Guide).
NOTES TO MANUAL
• This manual describes how to set up a complete and optimal automation, such as that shown in fig. 5, using all Mhouse devices that are part of the automation system named “WU2S”. Some of these devices are optional and may not be present in the kit. For a complete overview of the devices, refer to the MHouse product catalogue.
• This manual has been drawn up as a step-by-step guide
. There­fore, to ensure safe and facilitated assembly and programming procedures, perform all operations described in the same order as specified in this document.
––– STEP 2 –––
2.1 - PRODUCT DESCRIPTION AND INTENDED USE
The devices in this kit, plus other accessories (some optional and not included in the pack), form the automation system named “WU2S”, designed for the automation of a “residential” swing gate. Any other use
than as specified herein or in environmental conditions other than as
English – 3
English
2.2 - COMPONENTS USED TO SET UP A COMPLETE SYSTEM
Fig. 1 illustrates all components used to set up a complete system, such
as that shown in fig. 5. Components shown in Fig. 1: A - 2 electromechanical gearmotors WU1 with fixing/foundation plate and
slotted arms (*)
B - 3 release keys C - 1 pair of PH100 photocells (one TX and one RX) D - 2 GTX4 radio transmitters E - 4 nut caps F - 1 FL100 flashing light with integrated aerial G - 1 control unit CL2S H - Metal hardware
(*) the screws required for fixing the slotted arms are not supplied, as they depend on the material and thickness of the leaf.
Notes:
- Some devices and accessories specified in the manual are optional and may not be present in the kit. For a complete description, refer to the Mhouse product catalogue or visit the website www.mhouse.com.
- The limit switch stops are not supplied in the pack and are not part of the Mhouse product range.
––– STEP 3 –––
3.1 - CHECKING SUITABILITY OF GATE TO BE AUTOMAT-
ED AND RELATIVE ENVIRONMENT
• Ensure that the mechanical structure of the gate complies with current national standards and that it is suitable for automation. For this check, refer to the information specified on the gate dataplate. Important - This product cannot be used to automate a gate that is not already effi­cient and safe; furthermore it cannot solve defects caused by incorrect gate installation or poor maintenance.
• Manually move the gate leafs in both directions (opening/closing) and ensure that friction is constant throughout travel (there must be no points of increased or decreased force).
• If the leaf is fitted in a pedestrian pass door or a door onto the leaf movement area, ensure that this door does not obstruct normal travel, and install a suitable interlock device if necessary.
• Manually move the gate to any position; leave it stationary and ensure that it does not move when left.
• Ensure that the space around the site of gearmotor installation enables safe and easy manual gate release.
• Ensure that the selected surfaces for installation of the various devices are solid and guarantee a stable fixture; as regards photocells, select a flat surface that guarantees correct alignment between photocells (Tx and Rx).
• Ensure that all devices to be installed are in a sheltered location and protected against the risk of accidental impact.
• Ensure that there is sufficient space also when the gate is open (fig. 3).
• Verify the overall limits with reference to fig. 2-3 and the type of installa- tion: with gearmotor completely underground or surface-mounted.
• Whether the WU1SK gearmotor is underground or surface-mounted, the positions specified in Table 1 must be observed.
The most important value is ”A”: if possible choose the 1stline; after fixing “A”, the minimum and maximum values “B” and “ C” can be calculated with reference to the table.
In all cases a leaf opening angle of at least 100° is guaranteed. If a greater angle is required, up to 120° lower values should be selected for “B” and “C” should remain at the minimum envisaged value.
3.2 - PRODUCT APPLICATION LIMITS
Before proceeding with installation, perform the following checks in the specified sequence and ensure conformity both with the data in this para­graph and the technical data provided in the chapter “Technical Specifica­tions”.
1 - Ensure that the dimensions and weight of the gate leafs are within the
following limits of use:
- maximum length 1.8 m
- maximum weight 200 kg.
- opening angle up to 120°
The shape of the gate and weather conditions (such as the presence of strong winds) may reduce these maximum values; in this case the user must measure the torque required to move the leafs in the worst condi­tions, and compare this value with the technical specifications.
2 - Check the overall dimensions of the gearmotor (fig. 2). Note –
These measurements also serve as a reference to calculate the space occupied by the foundation pit for routing the electrical cable ducting.
3 - Ensure that the estimated lifetime is compatible with the intended use
(see paragraph 3.3).
4 - Ensure that all limitations, conditions and warnings in this manual can
be fully observed.
3.3 - PRODUCT DURABILITY
The lifetime is the average economic duration of the product. The value of lifetime is strongly influenced by the intensity of the manoeuvres, i.e. the sum of all factors that contribute to product wear, see Table 2. To estimate the durability of your automation, proceed as follows:
01. Add up all the values in the items of Table 2;
02. In Graph 1 from the value obtained above, trace vertical line until it
intersects the curve; from this point trace a horizontal line until it inter­sects the line of the “manoeuvre cycles”. The value obtained is the estimated lifetime of your product.
The lifetime values specified in the graph are only obtainable if the mainte­nance schedule is strictly observed (see chapter 9 - Maintenance sched­ule). The estimation of lifetime is made on the basis of design calculations and the results of tests performed on prototypes. As it is only an estima­tion, it does not represent any form of guarantee on the effective lifetime of the product.
Example of durability calculation: automation of a gate with a leaf length of
1.6 m with weight of 120 kg, for example, in a location subject to strong winds. Table 1 states the “severity index” values for this type of installa­tion: 25% (“Leaf length”), 10% (“Leaf weight”) and 15% (“Installation in windy areas”). These indexes must be added together to obtain the overall severity index, which in this case is 50%. With the value obtained (50%), check Graph 2 on the horizontal axis (“severity index”) and locate the correspon­ding value of “manoeuvre cycles” which this product is able to complete in its lifetime = approx. 40,200.
GRAPH 1
Severity index (%)
manoeuvre cycles
Ambient temperature over 40°C or lower than 0°C or humidity greater than 80%
Solid leaf Installation in windy zone
20%
15% 15%
TABLE 2
Severity index
1 - 1,5 m
1,5 - 1,8 m
> 100 kg > 150 kg
10% 25%
10% 25%
Leaf length
Leaf weight
TABLE 1 (expressed in millimetres)
ABC
1stchoice
2ndchoice
3rdchoice
4thchoice
0
from 10 to 30
from 31 to 50
from 51 to 60
from 0 to 80
from 0 to 80
from 0 to 70
from 0 to 60
from 160 to 170
from 180 to 190
from 200 to 210
from 210 to 240
90.000
80.000
70.000
60.000
50.000
40.000
30.000
20.000
10.000
0
4 – English
English
4.2 - PREPARING ELECTRIC CABLES
To prepare all connection cables, proceed as follows: a) - Refer to fig. 7 to check the connections of the various devices to the
control unit and terminals to be used for each connection. Important
- Only devices using “ECSbus” technology can be connected to the terminal “ECSbus”.
b) - Refer to fig. 6 to check positions of the electrical cables in the area.
Then draw a similar diagram on paper, adapting it to specific require­ments of your system. Note - This diagram will be useful to establish
the route of the raceways for cable ducting, and to draw up a com­plete list of the cables required.
c) - Read Table 3 to determine the type of cables to be used; then refer to
the diagram drawn above and on-site measurements to determine the length of each cable. Caution! - No cable must exceed the
specific maximum length stated in Table 3.
WARNING - “ECSbus” technology enables the interconnection of
devices using a single “bus” cable, with 2 internal electrical wires. Con­nection of several devices can be in the configuration “cascade”, “star” or the latter two “combined”.
––– STEP 4 –––
4.1 - PRELIMINARY CHECKS FOR INSTALLATION
4.1.1 - Establish the position of devices in the system
With reference to fig. 5 and 6, locate the approximate position for installa­tion of each device envisaged in the system. Fig. 5 shows a system made using this product and other optional accessories in the Mhouse range. These elements are positioned according to a typical standard layout. The components are:
[a] - 1 CL2S control unit. [b] - 1 FL100 Flashing light with integrated aerial [c] - 1 pair of PH100 photocells (one TX and one RX) [d] - 1 KS100 key-operated selector switch [e] - 2 photocell posts [f] - 2 limit switch stops [g] - 2 electromechanical gearmotors WU1SK [i] - junction box
WARNING! - Some of these devices are optional and may not be present in the kit (see Mhouse product catalogue).
WARNINGS:
The fixed control devices must be positioned:
- in sight of the automation;
- far from moving parts;
- at a height of at least 1.5 m from the ground,
- not accessible by the public.
4.1.2 - Establish the position of all connection cables
Refer to the instructions in paragraph 4.2 to establish the layout of the raceways for electric cable ducting.
4.1.3 - Ensure all equipment and materials for work are available
Before starting work, ensure that you have all equipment and materials required to complete the work. Ensure that all items are in good condition and comply with local safety standards.
4.1.4 - Completing the set-up work
Prepare the area for subsequent installation of the devices, completing all preliminary work, such as:
- digging of raceways for protection ducting of electric cables (external
ducting may be used as an alternative);
- laying of protection ducting and embedding in concrete;
- sizing of all electric cables to required length (see paragraph 4.2) and
routing in protection ducting. Caution! - In this phase, do not make
any electrical connections.
Warnings:
• The hoses and ducting serve to protect electrical cables and prevent accidental damage in the event of impact.
• When laying pipelines, take into account the risk of possible deposits of water in the branch wells, where condensate may form in the pipelines and the control unit with possible damage to the electronic circuits.
• Position the ends of the ducting at the points envisaged for fixture of the various components.
cascade star combined
TABLE 3 – Technical specifications of electric cables
Connection Type of cable (minimum section values) Max. admissible length
A - Power line cable 3 x 1.5 mm
2
30 m (note 1)
B - FLASH flashing light output cable 2 x 0.5 mm
2
20 m
C - Radio aerial RG58 shielded cable type 20 m (less than 5 m recommended) D - Input/output ECSbus cable 2 x 0.5 mm2 20 m (note 2) E - STOP input cable 2 x 0.5 mm2 20 m (note 2) F - OPEN input cable 2 x 0.5 mm2 20 m (note 2) G - Motor output M1 and M2 cable 3 x 1 mm2 10 m
Note 1 - If the power cable is longer than 30 m, a cable with a larger section is required (e.g. 3 x 2.5mm²) and safety earthing is necessary in the vicinity of the automation.
Note 2 - For cables of ECSbus and those of the STOP and OPEN inputs, a single cable with multiple internal wires may be used, to combine several connections: for example, the STOP and OPEN inputs can be connected to the KS100 selector switch with a cable of 4 x 0.5 mm2.
CAUTION! – The cables used must be suited to the installation environment: for example a cable type H03VV-F is recommended for indoor environments, and a cable type H07RN -F for outdoor environments is recommended.
English – 5
English
32 4
90
60
160
228,6
383,5
76
236
5
a
e f h
b c d
g
c
g
fi
e
6
A
D
B C
ED F
D
G G
1
B
F
D
C
E
A
H
G
6 – English
English
INSTALLATION: ASSEMBLY AND CONNECTION OF COMPONENTS
––– STEP 5 –––
WARNINGS
• Incorrect installation may cause serious physical injury to those
working on or using the system.
• Before starting automation assembly, make the preliminary checks
as described in STEP 3.
5.1 - INSTALLING THE GEARMOTOR WU1SK
WU1SK is an electromechanical gearmotor comprising a helical gear reducer and 24 V dc motor; it is fitted with a mechanical release with key, which enables manual movement of the gate in the event of a power fail­ure. The gearmotors can be anchored to the ground below the gate (if there is a clearance of at least 90 mm), or installed underground with the relative foundation plates. The slotted arm and relative fixing plate enable connection of the gearmo­tor to the gate leaf.
WU1SK gearmotors are designed for two types of installation:
A) Underground installation
(see paragraph 5.1.1).
B) Surface-mounted (see paragraph 5.1.2)
If there are problems inserting the gearmotor under the leaf, we recom­mend removing the leaf to facilitate work.
5.1.1 - Underground gearmotor installation
01. Prepare the foundation pit, observing the specifications in paragraph
3.1 “Preliminary checks”, and in particular positions “A” and “B” obtained from Table 1;
02. Lay the duct for routing the electric cable (fig. 7);
03. Separate the motor from the foundation plate;
04. Insert the four anchor bolts [B] in the foundation plate, securing the
above and below with two M8 nut types [A] and [C]; observe the maximum height from the protruding side as shown in fig. 8;
05. Cast concrete into the pit;
06. Embed the plate in the concrete, taking care to level it.
07. When the concrete is sufficiently dry (after a few days), remove the 4
internal nuts which will no longer be used;
08. Fix bracket [D] onto the slotted arm, inserting bush [F] and spacer
[E] on screw [G]; then tighten the screw and bracket fully down as shown in fig. 9;
09. Prepare the gearmotor inserting washer [L] in slotted arm [M], then
tighten fixing screws [I] fully down and close, inserting the cover [H] (fig. 10);
10. Using a slotted screwdriver, remove the two release covers [N] (fig. 11);
11. Tilt the gearmotor, rest it on the plate and tighten the 4 self-locking
nuts [R] and washers [S]. Seal off the lock nuts, at the rear by means of the nut caps [P] and at the front with the release covers [Q] (fig. 12);
12. Insert the electric cable through the duct until it reaches the control
unit. If necessary, use a junction box for connection of the gearmotor cable and cable to the control unit.
13. Refit the leaf if removed, and turn to the “gate closed” position.
14. Release the gearmotors by means of the relative release keys (see
paragraph “Releasing the gearmotor” on page 29) and turn the slot­ted arm until the fixing plate touches the leaf;
15. Position the fixing plate at the envisaged distance (position “C” of
Table 1 on page 3);
16. Provisionally secure the bracket to the leaf with a clamp; test a num-
ber of manoeuvres moving the gate by hand; check that the bracket slides smoothly in the slot of the arm and that there is always a mar­gin of at least 5 mm on the slot;
17. Fix the bracket permanently using screws suited to the leaf material;
18. Block the gearmotor again using the release keys (see paragraph
11.3 - User’s Guide) and close the release covers.
IMPORTANT!
- The following assembly phases show installation of a gearmotor model WU1SK.
- To ensure correct system operation, mechanical stops must be mounted on the floor or wall at the maximum leaf opening and closing points. Note - These stops are not supplied in the pack and are not part of the Mhouse product range.
5.1.2 - Surface-mounted gearmotor installation
01. Ensure that the fixing surface is perfectly smooth, level and sufficient­ly compact. WU1SK is not supplied with fixing devices, which must be chosen also on the basis of the fixing surface material.
02. Select the fixing position, observing the specifications in paragraph
3.1 “Preliminary checks”, and in particular positions “A” and “B” obtained from Table 1;
03. Lay the duct for routing the electric cable (fig. 14);
04. Separate the motor from the foundation plate;
05. Fix bracket [A] onto the slotted arm, inserting bush [C] and spacer
[B] on screw [D]; then tighten the screw and bracket fully down as shown in fig. 15;
06. Prepare the gearmotor inserting washer [G] in slotted arm [H], then tighten fixing screws [F] fully down and close, inserting the cover [E] (fig. 16);
07. Using a slotted screwdriver, remove the two release covers [I] (fig. 17);
08. Trace the drilling points at the envisaged location using the founda-
tion plate as a reference and using a drill to make the holes.
09. Insert the gearmotor on the plate, positioning the entire assembly over the holes, and secure permanently using screws suited to the type of fixing material;
10. Seal off the fixing points at the rear with the nut caps [L] (if possible; this depends on the type of fixture) and at the front with the release covers [M] (fig. 18);
11. Insert the electric cable through the duct until it reaches the control unit. If necessary, use a junction box for connection of the gearmotor cable and cable to the control unit.
12. Refit the leaf if removed, and turn to the “gate closed” position.
13. Release the gearmotors by means of the relative release keys (see
paragraph “Releasing the gearmotor” on page 34) and turn the slot­ted arm until the fixing plate touches the leaf.
14. Position the fixing bracket at the envisaged distance (position “C” of Table 1 on page 3);
15. Provisionally secure the bracket to the leaf with a clamp; test a num­ber of manoeuvres moving the gate by hand; check that the bracket slides smoothly in the slot of the arm and that there is always a mar­gin of at least 5 mm on the slot;
16. Fix the bracket permanently using screws suited to the leaf material;
17. Block the gearmotor again using the release keys (see paragraph
11.3 - User’s Guide) and close the release covers.
Make electrical connections. Refer to figure 23 and step 6.
English – 7
English
––– STEP 6 –––
6.1 - INSTALLING CL2S CONTROL UNIT
01. Select the installation position in an area protected against potential
impact and in the vicinity of the gate, to reduce the overall length of the cables;
02. Remove the cover, levering it off with a screwdriver from the opening on
the base; slide it by a few centimetres then lift it off the base (fig. 20);
03. Lay the duct for routing the electric cables so that they can be insert­ed from the lower section of the control unit;
04. Drill the lower side of the control unit and use special connectors for securing the ducts for routing electric cables, as shown in fig. 21;
05. On the base, use a screwdriver to punch through the two holes; trace the drilling points using the base as a reference (fig. 22);
06. Use a percussion drill to drill the wall, with a 6 mm tip, and insert 6 mm plugs;
07. Fix the base, using the relative screws [A];
08. Before closing the control unit, make the electrical connection with
reference to paragraph 6.6 and fig. 23.
09. To close the control unit, place the cover on the base by approx. 3 cm higher than the final position and push it downwards to engage it completely, as shown in fig. 25.
6.2 - INSTALLING AND CONNECTING PH100 PHOTOCELLS
(fig. 26)
Warning: all installation operations must be performed with the system disconnected from the power supply; if fitted, the PR1 backup battery must also be disconnected.
Warnings: Take care not to damage the o-ring fitted (fig. 26-3) [A].
Select the position of the two elements making up the photocell (TX and RX) observing the following:
• Place them at a height of 40-60 cm from the ground, to the sides of the
zone to be protected, and as close as possible to the edge of the gate, i.e. no further than 15 cm.
• There must be a raceway tube at the point envisaged for routing cables.
• Point the transmitter TX at receiver RX with a maximum tolerance of 5°.
01. Remove the front glass panel (fig. 26-1).
02. Position the photocell at the point where the cable routing tube
arrives.
03. Trace the drilling points using the base as a reference. Use a percus­sion drill to drill the wall, with a 5 mm tip, and insert 5 mm plugs.
04. Route the electric cables through the specific holes (pierce those required): see the two options in fig. 26-2.
05. Fix the base, using the relative screws [B] of fig. 26-3 ensuring that the hole on the base [C] of fig. 26-3 is aligned with the cable outlet. 2 self-tapping screws are also supplied for fixture on surfaces with a different density.
06. Connect the electrical cable in the relative terminals of both TX and RX (fig. 26-4). From an electrical point of view, TX and RX must be connected in parallel (fig. 26-5) and to the blue terminal on the con- trol board. No polarity needs to be observed
.
07. Fix the covering shell [D] of fig. 26-6 with the two screws [E] of fig. 29-6 using a Phillips screwdriver. Lastly, insert the external cover [F] in fig. 29-6 pressing it slightly to secure in place.
6.3 - INSTALLING AND CONNECTING THE FLASHING LIGHT
FL100 (fig. 27)
Select the position of the flashing light so that it is in the vicinity of the gate in a visible location; it can be fixed on either a horizontal or vertical surface. Fig. 27 shows the two options:
01. Remove the cover, unscrewing the screw if present.
02. Separate the base, unscrewing the screws present to route the elec-
tric cables.
03. Trace the drilling holes using the base as a reference and ensuring that the hole on the base is aligned with the cable outlet: vertical fix­ture (A) or horizontal fixture (B).
04. Use a percussion drill to drill the wall, with a 6 mm tip, and insert 6 mm plugs.
05. Fix the base, using the relative screws.
06. Connect the electric cables in the relative FLASH and “aerial” termi-
nals as shown in the figure: To facilitate operations, remove terminals, make connections, then refit the terminals. No polarity needs to be observed on the FLASH terminal, while in the case of the shielded cable connection of the aerial, the sheath must be connected.
07. Insert the lamp holder in the base, taking care to press it down so that it locks into place.
08. Secure the body of the flashing light to the fixing support and turn it left until it clicks into place, then secure by means of the screw.
6.4 - ELECTRICAL CONNECTION TO CONTROL UNIT CL2S
To make the electrical connection, at very low voltage, of the gearmotors and various devices, refer to fig. 23.
Caution! - If the length of the gearmotor cable is not sufficient, DO NOT REPLACE THE CABLE, but extend it by means of a suitable cable (see technical specifications in Table 3). The joining point of the two cables must be insulated and protected by means of a junction box (fig. 5-i).
Notes:
• The terminals have the same colour as the terminals on the correspon-
ding devices; for example the grey terminal (OPEN) of the KS100 key­operated selector switch must be connected to the grey terminal (OPEN) of the control unit;
• No polarity is needed for virtually any of the connections; only in the case
of the shielded cable of the aerial, the central core and sheath must be connected as shown in detail [A] of fig. 23.
Notes: - To facilitate connections, terminals can be removed as shown in fig. 24 - [A]; after making the connections, refit the terminals in their seats
- - At the end of connections, use cable ties to secure the electric cables
to the relative fixtures (fig. 24 - [B]).
8 – English
English
7 8
11 12
P
Q
P
Q
R
S
N
N
9 10
H
I
L
M
D
E
F
G
13 14
A
B
C
26 mm
English – 9
English
15 16
17 18
19
20
21
22
A
B
D
C
G
E
F
H
I
I
L
M
10 – English
English
23
24 25
C
B
FL100
PH100 KS100
WU1SK
M2
WU1SK
M1
blue
yellow/green
brown
blue
yellow/green
brown
A
B
TX RX
English – 11
English
27
AB
x4
A / BA/ B
A / BBBB
12
34
12
3
4
5
26
6
B
C
A
D
E
F
ECS bus
ECS bus
FLASH ECO bus STOP OPEN
12 – English
English
27
A / BA/BA/ BA/ B
A / BA/ B
5678
91112
10
A / BA/ B
Ø = 6 mm
x4
AA AA
4
English – 13
English
PROGRAMMING
––– STEP 7 –––
7.1 - POWER SUPPLY CONNECTION
WARNINGS – The power cable is in PVC and is designed for installation indoors. If installed outdoors, the entire cable must be covered with a protection ducting. Otherwise the cable can be replaced with a H07RN-F version. – Final connection of the automation to the electrical mains or replacement of the cable supplied must be made exclusively by a qualified and skilled electrician, in observance of the cur­rent safety standards and the following instructions.
• For automation operation tests and programming, use the
cable supplied, inserting the plug in an electrical socket. If the socket is far from the automation, an extension may be used in this phase.
• For the automation testing and commissioning phase the con­trol unit must be permanently connected to the power mains, replacing the cable supplied with one of adequate length. To connect the cable to the gearmotor control unit, proceed as follows:
WARNING!
The power line must be fitted with a disconnect device that ensures com­plete shut-off of power to the automation. The disconnect device must have contacts with a sufficient gap to ensure complete disconnection, in compliance with the overvoltage category III, according to the installation instructions. If necessary, this device guarantees quick and safe discon­nection from the mains power and therefore must be positioned in sight of the automation. If located in a concealed position, it must be equipped with a system that prevents inadvertent or unauthorised reconnection of power, to avoid potential hazards. The disconnect device is not supplied with the product.
01. To test, insert the CL2S plug in a power socket, using an extension if necessary.
7.2 - INITIAL CHECKS (fig. 28)
After powering up the control unit, perform the following checks:
01. Ensure that the LED “ECSBus” [A] (fig. 28) flashes regularly with the
frequency of 1 flash per second;
02. Ensure that the LED “SAFE” [B] (fig. 28) on the photocells is flashing
(both on TX and RX); the type of flash is not important, as this depends on other factors; it is important that it is not off or perma­nently lit.
03. Ensure that the night-time light [C] (fig. 28) on the KS100 key-operat-
ed selector switch is on.
04. If these events do not occur, disconnect the control unit from the
power supply and check the cable connections again with care. For other useful information, refer also to chapters 10.5 “Troubleshooting” and 10.6 “Diagnostics and signals”.
7.3 – LEARNING CONNECTED DEVICES (fig. 29)
On completion of initial checks, the control unit must be able to recognise the devices connected on the terminals “ECSBus” and “STOP”.
01. On the control unit, press and hold P2 [C] (fig. 29) for at least 3 sec- onds, then release.
02. Wait a few seconds for the control unit to complete the device learn­ing phase.
03. At the end of the learning phase the STOP LED [B] (fig. 29) must remain lit, while the LED P2 [C] (fig. 29) should turn off. If the LED P2 flashes it means there is an error; see paragraph 10.5 “Troubleshoot­ing”.
The phase for learning connected devices can be repeated at any time also after installation (for example if a photocell is added); simply repeat the procedure from point 01.
7.4 - LEARNING THE GATE LEAF OPENING AND CLOSING ANGLES
After learning devices, the control unit must recognise the opening angles of the leafs. In this phase the system reads the leaf opening angle from the mechanical closing stop through to the mechanical opening stop. The presence of fixed and sufficiently strong mechanical stops is essential.
01. Release the motors by means of the special keys (see paragraph
11.3 - User’s Guide) and move the leafs to mid-travel so that they are free to move in the opening and closing directions; then lock the motors.
02. Press and hold key P3 [B] (fig. 30) on the control unit. Wait for the
control unit to complete the device learning phase: closure of motor M1 through to the mechanical stop, closure of motor M2 through to the mechanical stop, opening of motor M2 and motor M1 through to the mechanical stop; complete closure of M1 and M2.
- If the first manoeuvre of one or both the leafs is not closure, press P3 to stop the learning phase, invert the polarity of the motor/s that opened the leaf, inverting the two brown and blue wires on the ter­minal.
- If the first motor to close is not M1, press P3 to stop the learning phase, and invert the motor connections on the terminals.
- During the learning phase, if any device trips (photocells, key-oper­ated selector switch, P3 pressed etc.), the learning phase is stopped immediately. In this case the entire learning phase must be repeated.
03. At the end of the learning the LED P3 [A] (fig. 30) should switch off.
see paragraph 10.5 “Troubleshooting”.
The phase for learning the opening angles can be repeated at any time
also after installation (for example if one of the opening stops is moved); simply repeat the procedure from point 1.
7.5 - CHECKING THE RADIO TRANSMITTERS
To check transmitters, simply press one of its 4 keys, ensure that the LED flashes and that the automation performs the associated command. The command associated with each key depends on the mode in which they were memorised (see paragraph 10.4 “Memorising radio transmit­ters”). The transmitters supplied are already memorised and the keys, when pressed, send the following commands (fig. 31):
Key T1 = “OPEN” Command
Key T2 = “Pedestrial opening “command
Key T3 = “Only open” command
Key T4 = “Only close” command
7.6 - SETTINGS
7.6.1 - Selecting the leaf speed .
Leaf opening and closing can be at two speeds: “high” and “low”. To change from one speed to another, briefly press key P2 [B] (fig. 32); the corresponding led P2 [A] (fig. 32) will turn on or off; when the led is off, the speed setting is “low”, when the led is on the speed setting is “high”.
7.6.2 - Selecting the operating cycle
Gate opening and closing can be performed in two different operating modes:
• Single cycle (semi-automatic): with one command, the gate opens and
remains open until the next command which activates closing.
• Complete cycle (automatic closure): with one command, the gate
opens and closes again automatically after a short interval (for the time interval, see paragraph 10.1 “Parameter settings via radio transmitter”).
To change from one mode to another, briefly press key P3 [B] (fig. 30); the
corresponding LED [A] (fig. 30) will turn on or off; when the led is off, the cycle is “single”, when the LED is on the cycle is “complete”.
14 – English
English
28
A
B
29
A
C
B
30
32
A
B
A
B
31
T1
T2
T3
T4
English – 15
English
TESTING AND COMMISSIONING
––– STEP 9 –––
Maintenance must be performed in strict observance of the safety provisions in this manual and according to current legislation and standards.
The automation devices do not require special maintenance. However a
check should be performed at least every six months to ensure complete efficiency of all devices. For this purpose, the tests and checks envisaged in paragraph 8.1 “Test­ing” should all be performed, as well as all procedure in the paragraph “Maintenance operations permitted for the user”. If other devices are present, follow the instructions in the relative mainte­nance schedule.
MAINTENANCE
8.2 - COMMISSIONING
Commissioning can only be performed after positive results of all test phases. Partial or “makeshift” commissioning is strictly prohibited.
01. Produce the technical documentation of the automation, which must
include at least the following documents: overall layout drawing (e.g. fig. 3), electrical wiring diagram (e.g. fig. 23), risk assessment and solutions adopted, manufacturer’s declaration of conformity for all devices used (use appendix 1).
02. Affix a dataplate on the door, specifying at least the following data:
type of automation, name and address of manufacturer (responsible for commissioning), serial number, year of construction and CE mark.
03. Permanently attach to the gate the label supplied in the pack, regard-
ing the procedure for manual locking/release of the gearmotor.
04. Compile and provide the automation owner with the declaration of
conformity (use appendix 2)
05. Prepare and provide the automation owner with the User’s guide; for
this purpose appendix 3 “User’s guide” may be used as an example (chapter 11.3).
06. Prepare and provide the owner with the form “Maintenance sched-
ule”, containing all maintenance instructions for all devices in the automation.
07. Before commissioning the automation, ensure that the owner is ade-
quately informed of all associated risks and hazards.
This product is an integral part of the automation and therefore must be disposed together with the latter.
As in installation, also at the end of product lifetime, the disassembly and scrapping operations must be performed by qualified personnel. This product is made of various types of material, some of which can be recycled while others must be scrapped. Seek information on the recy­cling and disposal systems envisaged by the local regulations in your area for this product category.
Caution! – some parts of the product may contain pollutant or hazardous
substances which, if disposed of into the environment, may cause serious damage to the environment or physical health. As indicated by the symbol alongside, disposal of this product in domestic waste is strictly prohibited. Separate the waste into categories for disposal, according to the methods envisaged by current legislation in your area, or return the product to the retailer when purchasing a new version.
Caution! – Local legislation may envisage serious fines in the event of abusive disposal of this product.
PRODUCT DISPOSAL
––– STEP 8 –––
These are the most important phases when setting up an automation, in order to guarantee maximum safety. Testing can also be used as a periodic check of devices in the automa­tion.
Testing of the entire system must be performed by skilled and quali­fied personnel, who are responsible for the tests required to verify the solutions adopted according to the risks present, and for ensur­ing observance of all legal provisions, standards and regulations, with particular reference to all requirements of the standard EN 12445 which establishes the test methods for testing automations for power-operated gates.
8.1 - TESTING
01. Ensure that all instructions and warnings in STEP 1 have been
strictly observed.
02. Using the selector or radio transmitter, test a gate closing and open­ing cycle and ensure that the leaf movement corresponds to specifi­cations. A number of tests should be performed to ensure that the gate moves smoothly and that there are no assembly defects, incor­rect settings, or any points of friction.
03. Check operation of all system safety devices one at a time (photo­cells, sensitive edges, etc.). In particular, each time a device trips, the “ECSBus” led on the control unit emits a longer flash to confirm con­trol unit recognition of the event.
04. To test photocells and in particular that there is no interference with other devices, pass a cylinder (fig. 33) (diameter 5 cm, length 30 cm) through the optic axis, first close to the TX and then the RX and then mid-way between the two. Ensure that in all cases the device engages, changing from the active status to alarm status and vice versa; then ensure that the action envisaged is performed on the control unit: during closure inverts movement.
05. Measure the force as specified in the standard EN 12445. If the motor force control is used as an auxiliary function for reduction of impact force, test and identify the setting that obtains the best results.
33
16 – English
English
FURTHER INFORMATION
––– STEP 10 –––
10.1 - ADVANCED SETTINGS
10.1.1 - Parameter settings via radio transmitter
The radio transmitter can be used to set a number of control unit operat­ing parameters: there are eight parameters.
1) Pause time: the time for which the leafs remain open (in the case of
automatic closure).
2) Pedestrian opening: pedestrian leaf opening mode.
3) Motor force: motor force over which the control unit recognises an
obstacle and inverts movement.
4) “OPEN” function: sequence of movements associated with each
“OPEN” command.
5) Level of discharge of motor 1 on closing: sets the duration of the “brief
inversion” of the motor after a closing manoeuvre, serving to reduce the final residual force.
6) Level of discharge of motor 1 on opening: sets the duration of the “brief
inversion” of the motor after an opening manoeuvre, serving to reduce the final residual force.
7) Level of discharge of motor 2 on closing: sets the duration of the “brief
inversion” of the motor after a closing manoeuvre, serving to reduce the final residual force.
8) Level of discharge of motor 2 on opening: sets the duration of the “brief
inversion” of the motor after an opening manoeuvre, serving to reduce the final residual force.
Parameters
Pause Time
Pedestrian opening
Motor force
“OPEN” function
NO.
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Action: operation to be performed at point 3 of the settings phase
Press T1 once Press T1 twice Press T1 three times Press T1 four times Press T2 once Press T2 twice Press T2 three times Press T2 four times Press T3 once Press T3 twice Press T3 three times Press T3 four times Press T4 once Press T4 twice Press T4 three times Press T4 four times
TABLE 4
Value
10s 20s (*) 40s 80s Opening of 1 leaf to mid-travel Total opening of 1 leaf (*) Partial opening of 2 leafs to 1/4 of travel Partial opening of 2 leafs to mid-travel Low Medium low (*) Medium high High “Open”, “Stop”, “Close”, “Stop” “Open”, “Stop”, “Close”, “Open” (*) “Open”, “Close”, “Open”, “Close” Opening only
(*) Factory setting
Parameters
Discharge on closing Motor 1
Discharge on opening Motor 1
Discharge on closing Motor 2
Discharge on opening Motor 2
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Actions to be performed
Press T1 once Press T1 twice Press T1 three times Press T1 four times Press T1 five times Press T1 six times Press T1 seven times Press T1 eight times Press T2 once Press T2 twice Press T2 three times Press T2 four times Press T2 five times Press T2 six times Press T2 seven times Press T2 eight times Press T3 once Press T3 twice Press T3 three times Press T3 four times Press T3 five times Press T3 six times Press T3 seven times Press T3 eight times Press T4 once Press T4 twice Press T4 three times Press T4 four times Press T4 five times Press T4 six times Press T4 seven times Press T4 eight times
TABLE 5
Value
No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum) No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum) No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum) No discharge (*)
0.1 s (Minimum)
0.4 s (Medium)
0.7 s (Maximum)
(*) Factory setting
English – 17
English
The parameter setting operation can be performed using any radio trans­mitter, provided that it is memorised in mode 1, in the same way as that supplied (see paragraph 10.4 “Memorisation mode 1”). If there is no transmitter memorised in mode 1 a single one may be mem­orised for this phase, after which it must be deleted immediately (see paragraph 10.4.4 “Deleting a radio transmitter”).
CAUTION! – When making settings via a transmitter, the control unit must be allowed sufficient time to recognise the command via radio; in practice the keys must always be pressed and released slowly, pressing for at least one second, releasing for one second and so on.
To program the parameters, see Table 4.
01. Press T1 and T2 simultaneously (fig. 34) on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 4
according to the parameter to be modified.
Example: to set the pause time at 40 s.
01. Press and hold the keys T1 and T2 simultaneously for at least 5 sec­onds.
02. Release T1 and T2
03. Press T1 three times
All parameters can be adjusted as required without any contraindications, only the “Motor force” setting may require special attention:
• Do not use force values to compensate for anomalous points of friction
on the gate. Excessive force settings may impair safety system opera­tion or cause damage to the gate.
• If the “Motor force control” is used in support of the system for impact
force reduction, after each adjustment the force measurement proce­dure must be performed, as envisaged by standard EN 12445.
• Weather conditions can influence gate movement; new adjustments
may be required periodically.
To program the parameters, see Table 5.
01. Press T1 and T3 simultaneously (fig. 35) on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 5
according to the parameter to be modified.
Example: to set discharge on closing of motor 2 on level 4.
01. Press and hold the keys T1 and T3 simultaneously for at least 5 s seconds
02. Release T1 and T3
03. Press T3 four times
10.1.2 - Checking settings via a radio transmitter
With a radio transmitter memorised in Mode 1 the user can check settings at any time for each parameter, as follows.
To display the parameters, see Table 6:
01. Press T1 and T2 simultaneously on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 6
according to the parameter to be modified.
04. Release the key when the flashing light starts to flash
05. Count the number of flashes and, according to the number, check
the corresponding value on Table 4.
Example: After pressing T1 and T2 for 5 s followed by T1, if the flashing light flashes three times, the pause time is set at 40 s.
To display the parameters, see Table 7.
01. Press T1 and T3 simultaneously on the radio transmitter for at least 5 s.
02. Release the two keys.
03. Within three seconds, complete the action as specified in Table 7
according to the parameter to be modified.
04. Release the key when the flashing light starts to flash.
05. Count the number of flashes and, according to the number, check
the corresponding value on Table 5.
10.2 - OPTIONAL ACCESSORIES
As well as the devices in WU2S, there are a number of optional acces­sories which may be used to integrate the automation system.
PR1: 24 V buffer battery; in the event of a mains power failure, this guar­antees at least 10 complete cycles.
PF: 24 V solar power system; useful in cases in which there is no electri­cal mains power.
PT50: Pair of columns (height 500 mm) with photocell
PT100: Pair of columns (height 1000 mm) with two photocells
For information on new accessories, consult the MHOUSE catalogue or visit the website www.mhouse.com.
10.2.1 - Installing the PR1 buffer battery (fig. 36)
CAUTION! - The electric connection of the battery to the control unit must only be made after completing all installation and programming phases, as the battery constitutes an emergency power supply.
To install and connect the buffer battery PR1 to the control unit, refer to fig. 36 and the PR1 instruction manual.
When the automation is powered by the buffer battery, 60 seconds after a manoeuvre is completed, the control unit automatically switches off the output “ECSbus” (and all connected devices), output Flash and all leds, with the exception of the ECSbus led, which flashes at slower intervals; this indicates the “Standby” function. When the control unit receives a command, it restores normal operation (with a short delay). This function is used to reduce consumption; an important factor when the unit is pow­ered by battery.
10.2.2 - Installing the PF solar power supply system (fig. 37)
CAUTION! - When the automation is powered exclusively by the solar power system “PF”, IT MUST NEVER BE POWERED at the same time by the mains.
To connect the PF solar power system to the control unit, refer to fig. 37 and the PF instruction manual.
When the automation is powered by the solar panel, 60 seconds after a manoeuvre is completed, the control unit automatically switches off the
34
T1
T2
Parameter
Pause Time
Pass door
Motor force
“OPEN” function
Action
Press and hold T1
Press and hold T2
Press and hold T3
Press and hold T4
TABLE 6
Parameter
Level of discharge of motor 1 on closing
Level of discharge of motor 1 on opening
Level of discharge of motor 2 on closing
Level of discharge of motor 2 on opening
Action
Press and hold T1
Press and hold T2
Press and hold T3
Press and hold T4
TABLE 7
35
T1
T3
18 – English
English
output “ECSbus” (and all connected devices), output Flash and all leds, with the exception of the ECSbus led, which flashes at slower intervals; this indicates the “Standby” function. When the control unit receives a
command, it restores normal operation (with a short delay). This function is used to reduce consumption; an important factor when the unit is pow­ered by photovoltaic panels.
10.2.3 - Maximum possible number of cycles per day
This product is specifically designed to operate also with the PF solar power supply system. Special technical provisions have been envisaged to minimise energy consumption when the automation is stationary, by turning off all devices not essential to operation (for example photocells and the key-operated selector switch). In this way all energy available and stored in the battery is used to move the gate.
Caution! - When the automation is powered by the solar power system “PF”, IT MUST NEVER BE POWERED at the same time by the mains.
Application limits:
maximum possible number of cycles per day within a
set period of the year.
The PF solar power system enables complete power autonomy of the automation, until the energy produced by the photovoltaic panel and stored in the battery remains above the amount consumed during gate manoeuvres. A simple calculation enables an estimate of the maximum number of cycles per day performed by the automation in a certain period of the year, provided that a positive energy balance is maintained.
The first step in calculating the energy available, is dealt with in the PF instruction manual; the second step in calculating the energy con- sumed and therefore the maximum number of cycles per day, is dealt with in this chapter.
Calculating the energy available
To calculate the energy available (refer also to the PF instruction manual) proceed as follows:
01. On the terrestrial map supplied in the PF kit instruction manual,
locate the point of system installation; then read the value Ea and the degrees of latitude of this location (E.g. Ea = 14 and degrees = 45°N)
02. On the graphs (North or South) supplied in the PF kit instruction man-
ual, locate the curve for the location’s latitude (e.g. 45°N)
03. Choose the period of the year on which to base the calculation, or select the lowest point of the curve to calculate the worst period of the year; then read the corresponding value Am (e.g. December, Jan­uary: Am= 200)
04. Calculate the value of energy available Ed (produced by the panel) multiplying Ea x Am = Ed (e.g.Ea = 14; Am = 200 therefore Ed =
2800)
Calculating the energy consumed
To calculate the energy consumed by the automation, proceed as follows:
05. On the table below, select the box corresponding to the intersection between the line with the weight and the column with the opening angle of the gate leaf. The box contains the value of the severity index (K) for each manoeuvre (e.g. WU2S with a leaf of 130 Kg and opening of 95°; K = 125).
Opening angle
Leaf weight 90° 90÷110° 110÷120°
< 75 Kg 71 92 125
75-120 Kg 84 110 168
120-160 Kg 101 125 240
160-200 Kg 130 168 330
36
1 2 3
37
2
B
B
1
English – 19
English
06. On the table A below, select the box corresponding to the intersec-
tion between the line with the Ed value and the column with the K val­ue. The box contains the maximum possible number of cycles per day (e.g. Ed = 2800 and K= 125; cycles per day ≈ 20)
If the number obtained is too low for the envisaged use or is located in the “area not recommended for use”, the use of 2 or more photovoltaic panels may be considered, or the use of a photovoltaic panel with a higher power. Contact the Mhouse technical assistance service for further information.
The method described enables the calculation of the maximum possible number of cycles per day that can be completed by the automation while running on solar power. The calculated value is considered an average val­ue and the same for all days of the week. Considering the presence of the battery, which acts as an energy “storage depot”, and the fact that the bat-
tery enables automation autonomy also for long periods of bad weather (when the photovoltaic panel produces very little energy) it may be possible to exceed the calculated maximum possible number of cycles per day, pro­vided that the average of 10-15 days remains within the envisaged limits.
Table B below specifies the maximum possible number of cycles, accord­ing to the manoeuvre’s severity index (K), using exclusively the energy stored by the battery. It is considered that initially the battery is complete­ly charged (e.g. after a prolonged period of good weather or recharging via the optional PCB power supply unit) and that the manoeuvres are per­formed within a period of 30 days.
When the battery runs out of the stored energy, the led starts to indicate the battery low signal by flashing briefly every 5 seconds, accompanied by a “beep”.
TABLE A - Maximum possible number of cycles per day
Ed K75 K=100 K=125 K=150 K=175 K=200 K=225 K=250 K=275 K=300 K325
9500 123 92 74 61 53 46 41 37 33 31 28 9000 116 87 70 58 50 44 39 35 32 29 27 8500 109 82 66 55 47 41 36 33 30 27 25 8000 103 77 62 51 44 39 34 31 28 26 24 7500 96 72 58 48 41 36 32 29 26 24 22 7000 89 67 54 45 38 34 30 27 24 22 21 6500 83 62 50 41 35 31 28 25 23 21 19 6000 76 57 46 38 33 29 25 23 21 19 18 5500 69 52 42 35 30 26 23 21 19 17 16 5000 63 47 38 31 27 24 21 19 17 16 14 4500 56 42 34 28 24 21 19 17 15 14 13 4000 49 37 30 25 21 19 16 15 13 12 11 3500 43 32 26 21 18 16 14 13 12 11 10 3000 36 27 22 18 15 14 12 11 10 9 8 2500 29 22 18 15 13 11 10 9 8 7 7 2000 23 17 14 11 10 9 8 7 6 6 5 1500 16 12 10 8 7 6 5 1000 97 6
TABLE B - Maximum number of cycles using exclusively battery power
K75 K=100 K=125 K=150 K=175 K=200 K=225 K=250 K=275 K=300 K325
741 556 445 371 318 278 247 222 202 185 171
Area of use not recommended
10.3 - ADDING OR REMOVING DEVICES
An automation using WU2S enables devices to be added or removed at any time.
Caution! – Do not add devices before ensuring that they are fully compatible with WU2S; for further details, contact the MHOUSE technical assistance.
10.3.1 - ECSBus
ECSBus is a system that enables connections of ECSBus devices using just two wires, which convey both electrical power and communication signals. All devices are connected in parallel on the same 2 wires of the ECSBus; each device is recognised individually as it is assigned a unique address during installation.
Photocells and other devices using this system can be connected to ECSBus, such as safety devices, control buttons, indicator lights etc. For information on ECSBus devices, refer to the MHOUSE catalogue or visit the website www.mhouse.com.
A special learning phase enables the control unit to recognise all connect­ed devices individually, and enables precise diagnostics procedures. For this reason, each time a device connected to ECSBus is added or removed, the learning phase must be performed on the control unit; see paragraph 10.3.3 “Learning other devices”.
10.3.2 - STOP Input
STOP is the input that causes immediate shutdown of the movement (fol­lowed by a brief inversion of the manoeuvre). This input can be connected to devices with contact types Normally Open (NO, as in the case of the KS100 selector switch), Normally Closed (NC) or devices with a constant resistance of 8.2 KΩ, such as sensitive edges. When set accordingly, more than one device can be connected to the STOP input, also different from one another; see Table 8.
Note 1. The NO and NC combination can be obtained by placing the two contacts in parallel, and placing an 8.2k
Ω
resistance in series with the NC
contact (it is, therefore, possible to combine 3 devices: NA, NC and 8,2k
Ω
).
Note 2. Any number of NO devices can be connected to each other in parallel.
Note 3. Any number of NC devices can be connected to each other in series.
Note 4. Only two devices with an 8.2 k
Ω
constant resistance output can be connected in parallel; multiple devices must be connected “in cas­cade” with a single 8.2 kΩ termination resistance.
Caution! – If the STOP input is used to connect devices with safety functions, only the devices with 8.2 kΩ constant resistance output will guarantee the fail-safe category 3.
As with the ECSBus, the control unit recognises the type of device con­nected to the STOP input during the learning phase; subsequently the control unit gives a STOP command when it detects a variation with respect to the learned state.
10.3.3 - Recognition of other devices
The learning operation of the devices connected to the ECSBus and STOP input is usually carried out during the installation phase; if devices are added or removed the learning operation can be carried out again as follows:
01. Press and hold key P2 [B] on the control unit for at least three sec-
onds (fig. 38), then release the key.
02. Wait a few seconds for the control unit to complete the device learn-
ing phase.
03. At the end of the learning the LED P2 [A] (fig. 38) should switch off. If
the LED P2 flashes it means there is an error; see paragraph 10.5 “Troubleshooting”.
04. After having added or removed a device the automation test must be
carried out again as specified in paragraph 8.1 “Testing”.
1stdevice type:
NO NC 8,2 KΩ
NO In parallel (note 2) (note 1) In parallel
NC (note 1) In series (note 3) In series
8,2KΩ In parallel In series (note 4)
TABLE 8
2
nd
device type:
20 – English
English
TABLE 9
Photocell h=50cm; triggered on closure
Photocell on right with acti­vation on opening
Photocell on left with acti­vation on opening
Photocell h=100cm; triggered on closure
Photocell h=100cm; triggered on opening and closure
Photocell
Jumpers
D
Photocell h=50cm; triggered on opening and closure
F
E
Photocell
Jumpers
10.4 - MEMORIZING ALL RADIO TRANSMITTERS
The control unit contains a radio receiver for GTX4 transmitters; the trans­mitter included in the box is already memorised and ready to use. There are two ways of memorising a new transmitter:
• Mode 1: in this “mode” the radio transmitter is used as a whole, i.e. all the keys carry out a preset command (the transmitters supplied with the WU2S are memorised using Mode 1). Obviously a radio transmitter in mode 1 can only control one single automation; that is:
• Mode 2: each key can be associated to one of the four commands available. If this mode is used appropriately 2 or more different automa-
A
B
C
tions can be controlled, for example:
Obviously each transmitter is treated separately and for one single control unit there can be some transmitters memorised in mode 1 and others in mode 2.
The overall maximum memory capacity is of 150 units; mode 1 memori­sation occupies one unit per transmitter while mode 2 occupies one unit per key.
Caution! – As memorisation procedures have a time limit (10 s), it is important to read the instructions in the next paragraphs before starting.
Key T1 “OPEN” Command
Key T2 “Pedestrial opening “command”
Key T3 “Only open” command
Key T4 “Only close” command
Key T1 “Only open” Automation N° 1 command
Key T2 “Only close” Automation N° 1 command
Key T3 “OPEN” Automation N° 2 command
Key T4 “OPEN” Automation N° 3 command
10.3.4 - Adding optional photocells
Additional photocells to those supplied with the WU2S can be installed at any time. On an automation for 2-leaf gates, these can be positioned as shown in fig. 39. In order for the control unit to correctly recognise the photocells they must be assigned with addresses using special electric jumpers. The address assignment operation must be carried out on both TX and RX (placing the electric jumpers in the same way) and it is important to check that there are not any other pairs of photocells with the same address. The photocell address assignment operation is necessary for them to be correctly recognised among the other devices of the ECSBus and to assign them their function.
01. Open the housing of the photocell.
02. Identify the position in which they are installed according to Figure 70
and place the jumper according to Table 9. Unused jumpers must be placed in the special compartment for
future use (fig. 40).
03. Carry out the learning phase as described in paragraph 10.3.3 “Recognition of other devices”.
38
B
A
40
39
TABLE 10
Once time “OPEN” Command Activates the automation as described in Table 4 (Open function)
Twice times “Pedestrial opening “command Activates partial opening of one or two leafs as described in Table 4
(Pedestrian opening)
Three times “Only open” command Activates opening of the leafs (open - stop - open etc.)
Four times “Only close” command Activates closing of the leafs (close - stop - close etc.)
Five times “Stop” command Stops the manoeuvre
Six times “Apartment block Open” command On opening the command has no effect, and on closing inverts movement,
i.e. opening of the leafs
Seven times “High priority open” command Gives command even when automation is blocked
Eight times “Pedestrial opening 2” command Activates partial opening of the leaf M2, equal to approx. mid-travel
Nine times “Pedestrial opening 3” command Activates partial opening of the two leafs, equal to approx. mid-travel
Ten times “Open + block automation” command It causes an opening manoeuvre, after which the automation is blocked;
the control unit accepts no further commands with the exception of “Open high priority” and “Release” automation
Eleven times “Close + block automation” command It causes a closure manoeuvre, after which the automation is blocked;
the control unit accepts no further commands with the exception of “Open high priority” and “Release” automation
Twelve times “Block automation” command It causes the manoeuvre to stop and the automation to block;
the control unit accepts no further commands with the exception of “Open high priority” and “Release” automation
Thirteen times “Unblock automation” command It causes the automation to be released and normal operation to resume
English – 21
English
10.4.1 - Memorisation mode 1
01. Press key P1 [B] (fig. 46) for at least 3 s. When the LED P1 [A] (fig.
46) switches on release the key.
02. Within 10 s press any one key on the transmitter for at least 3 s to memorise it. If the memorisation procedure is successful, the LED P1 will emit 3 flashes.
03. If there are other transmitters to be memorised repeat step 2 within the next 10 s otherwise the memorisation phase will end automati­cally.
10.4.2 - Memorisation mode 2
With Mode 2 transmitter memorisation each key can be associated with any one of the commands shown in table 10.
In Mode 2 each key requires its own memorisation phase.
01. If the transmitter to be memorised is already memorised (such as the transmitters supplied which are already memorised in mode 1) the transmitter must be deleted following the procedure described in: “10.4.4 - Deleting a radio transmitter”.
02. Press key P1 [B] (fig. 41) on the control unit the number of times equal to the required command, according to Table 10 (e.g. 3 times
for the “Only open” command).
03. Check that LED P1 [A] (fig. 41) flashes quickly for a number of times equal to the command selected.
04. Within 10 s press the required key on the radio transmitter for at least 2 s to memorise it. If the memorisation procedure is successful, the LED P1 will emit 3 slow flashes.
05. If there are other transmitters to be memorised for the same type of command, repeat step 03 within the next 10 s otherwise the memo­risation phase will end automatically.
10.4.3 - Remote memorisation
A new radio transmitter can be memorised on the control unit without having to use the unit itself. It is sufficient to have an “OLD” working and memorised radio transmitter. The “NEW” radio transmitter will “inherit” the characteristics of the OLD one; in other words if the OLD one is memo­rised in Mode 1 then the NEW one will also be memorised in Mode 1; in this case during the memorisation phase press any one key on the two transmitters. If the OLD radio transmitter is memorised in Mode 2 press the key with the required command on the OLD transmitter and press the key on the NEW transmitter with which you wish to associate the new command.
Take the two transmitters and position yourself within the action range of the automation and follow the following steps:
01. Press the key on the NEW radio transmitter for at least 5 s then release it.
02. Press the key on the OLD radio transmitter slowly 3 times.
03. Press the key on the NEW radio transmitter slowly once.
At this point the NEW radio transmitter will be recognised by the control unit and will take on the characteristics of the OLD one.
Repeat these steps for each new transmitter to be memorised.
10.4.4 - Deleting a radio transmitter
It is necessary to have a radio transmitter to delete it. If the transmitter is memorised in Mode 1 one single deletion phase is suf­ficient and at point 3 any key can be pressed. If the transmitter is memo­rised in Mode 2 a deletion phase must be carried out for each key.
01. Press and hold key P1 [B] (fig. 41) on the control unit.
02. Wait for the LED P1 [A] (fig. 41) to switch on and within three sec-
onds.
03. Press the key on the radio transmitter to be deleted for at least three seconds. If deletion is successful LED P1 will emit five quick flashes. If LED P1 emits one slow flash it means that the deletion has not been completed because the transmitter is not memorised.
04. To delete other transmitters keep key P1 pressed and repeat step 3 within 10 seconds otherwise the deletion procedure will end auto­matically.
10.4.5 - Deleting all radio transmitters
This procedure deletes all memorised transmitters.
01. Press and hold key P1 [B] (fig. 41) on the control unit.
02. Wait for LED P1 [A] (fig. 41) to switch on, then off and then flash 3
times.
03. Release P1 key precisely when the LED flashes the third time.
04. Wait about 4 s for deletion to be completed, during which the LED P1
will emit quick flashes.
If the pr
ocedure is successful after a few moments the LED P1 will emit 5
slow flashes.
41
B
A
22 – English
English
Symptoms
The radio transmitter does not emit any signal (the LED [A] does not light up)
The manoeuvre does not start and the LED “ECSBus” [B] does not flash
The manoeuvre does not start and the flashing light is off
The manoeuvre does not start and the flashing light flashes
The manoeuvre starts but is immediately followed by an inversion
The manoeuvre is carried out but the flashing light is not working
Probable cause and possible solution
• Check whether the batteries are flat and if necessary replace them (paragraph 11.5)
• Check that the power supply cable is correctly inserted in the mains socket
• Check that the fuses [E] and [F] have not been activated; if this is the case check the cause of the fault and replace them with other fuses with the same characteristics
• Check that the command is actually received. If the command reaches the OPEN input the relevant LED “OPEN” [D] should light up; if a radio transmitter is used the LED “ECSBus” should emit two long flashes
• Check that the STOP input is active, in other words that the LED “STOP” [C] is on. If this is not the case check the device connected to the STOP input.
• The photocell test carried out at the beginning of each manoeuvre is negative; check the photocells and refer to Table 12
• The force selected is too low to move the gate. Check for obstructions and if necessary select a higher force as described on page 10.1.1
• During the manoeuvre, ensure that there is voltage on the FLASH terminal of the flashing light (as this is intermittent, the voltage value is not significa
TABLE 11 (fig. 42)
10.5 - TROUBLESHOOTING
Table 11 gives possible indications on how to deal with malfunctions that may be met during installation or due to a fault.
42
E
A
CB
D
F
10.6 - DIAGNOSTICS AND SIGNALS
Some devices directly provide particular signals to describe the state of operation or eventually a malfunction.
10.6.1 - Photocells
The photocells contain a LED “SAFE” [A] (fig. 43) that provides informa­tion at any moment on the state of operation; see Table 12.
43
A
LED “SAFE”
Off
3 quick flashes and 1 second pause
1 very slow flash 1 slow flash 1 quick flash
1 very quick flash
Always lit
STATUS
The photocell is not powered or it is faulty
Device not recognised by the control unit
The RX receives an excellent signal The RX receives a good signal The RX receives a poor signal
The RX receives a bad signal
The RX does not receive any signal
ACTION
Check that the voltage on the photocell terminals is of about 8-12 Vdc; if the voltage is correct then the photocell is probably faulty
Repeat the learning procedure on the control unit. Check that all the photocell pairs on ECSBus have different addresses (see Table 9)
Normal operation Normal operation Normal operation but check TX-RX alignment and correct
cleaning of photocell lenses At the limit of normal operation; check TX-RX alignment and
correct cleaning of photocell lenses Check for any obstruction between TX and RX. Check that the
LED on the TX flashes slowly. Check TX-RX alignment
TABLE 12
Quick flashes
1 flash 1 second pause 1 flash
2 flashes 1 second pause 2 flashes
3 flashes 1 second pause 3 flashes
4 flashes 1 second pause 4 flashes
Status
ECSBus error
Photocell activated
“Gearmotor force” limiting device activated
STOP input activated
Action
At the beginning of the manoeuvre the devices present do not correspond with those recognised; check and eventually carry out the learning procedure (10.3.3 “Recognition of other devices”). One or more devices may be faulty; check and, if necessary, replace them.
At the start of the manoeuvre, one or more photocells do not enable move­ment; check to see if there are any obstructions. During the movement if there is an obstruction no action is required.
During the movement, the gate experienced excessive friction; identify the cause.
At the start of the manoeuvre or during the movement, the STOP input was activated; identify the cause.
TABLE 13
English – 23
English
LED STOP [B]
Off * ON
Status
STOP input activated Everything OK
Action
Check the devices connected to the STOP input STOP input active
LED OPEN [C]
Off On
Status
Everything OK OPEN input activated
Action
OPEN input not active This is normal only if the device connected to the OPEN input is
active
10.6.2 - Flashing light
During a manoeuvre the flashing light flashes every second; in case of anomalies the light flashes at more frequent intervals (half a second); the
flashes are repeated twice with an interval of one second; see Table 13.
10.6.3 - Control unit
The LEDs on the control unit provide particular signals to report on the normal operation and on possible faults; see Table 14.
44
D
E
F
C
B
A
LED ECSBus [A]
Off
On
One flash per second 2 long flashes
1 flash every 5 seconds
Series of flashes separated by a pause
Quick flash
Status
Fault
Serious fault
Everything OK Input status variation
Automation in “standby” mode
ECSBus short circuit
Action
Check that the unit is powered; check that the fuses have not been activated; if this is the case check the cause of the fault and replace them with other fuses with the same characteristics
There is a serious fault; switch off the control unit for a few sec­onds; if the status persists there is a fault and the electronic board must be replaced
Control unit works correctly A variation to the status of the inputs OPEN, STOP, activation of
the photocells, or when the radio transmitter is used, is normal Everything OK; when the control unit receives a command normal
operation is restored (with a short delay)
An overload has been detected therefore the power to the ECS­Bus switched off. Check by disconnecting the devices one at a time.
To restore power to the ECSBus simply send a command, for example with a radio transmitter
TABLE 14 (fig. 44)
The same signal as for the flashing light, see Table 13
24 – English
English
LED P1 [D]
Off * On
Series of quick flashes, from 1 to 4
5 quick flashes 1 slow flash 3 slow flashes 5 slow flashes
Status
Everything OK Memorisation mode 1
Memorisation mode 2
Deletion OK Wrong command Memorisation OK Deletion OK
Action
No memorisation underway This is normal during memorisation mode 1 which lasts maximum
10 s. This is normal during memorisation mode 2 which lasts maximum
20 s. Deletion of a transmitter successfully completed. Command received from a transmitter which is not memorised Memorisation successfully completed All radio transmitters successfully deleted
LED P2 [E]
Off * On 1 flash per second
2 flashes per second
Status
Everything OK Everything OK The learning phase has not been carried
out or there are errors in the memory data
Device learning procedure underwayo
Action
“Slow” speed selected “Fast” speed selected Some faulty devices may be present; check and if necessary
repeat the device learning phase (see paragraph 10.3.3 “Learning other devices”)
It shows that the search for connected devices is underway (it lasts maximum a few seconds)
LED P3 [F]
Off * On 1 slow flash
2 slow flashes
Status
Everything OK Everything OK There is no memorised opening angle
Opening angle learning phase in progress
Action
Cycle operation Complete cycle operation Perform the learning phase (see chapter 3.5.2 - Learning the leaf
opening and closing angles) Indicates that the opening angle learning phase is in progress
* or it could be in “Standby” mode
Model/type
PH100 photocells (optional)
Product Type
Adopted technology
Maximum start-up torque
Nominal torque
No-load speed
Speed at nominal torque
Maximum frequency of cycles
Maximum time continuous cycle
Application limits
Power supply
Rated current absorption
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
English – 25
English
Gearmotor with straight arm for WU1SK swing gates
Electromechanical gearmotor for automations of automatic gates and doors
24Vdc motor, helical gear reducer; mechanical release
150 Nm
50Nm
1.7 RPM
1.4 RPM
30 cycles/hour at 50 °C
About 10 minutes
The structural design of this product makes it suitable for use on gates with a weight up to 200 kg or leaf width up to 1.8 m and opening angle up to 120°
24Vdc
1.1A; on start-up the maximum absorbed current is 3.5 A for a maximum time interval of 2 s
-20 ÷ 50°C (gearmotor efficiency is reduced at low temperatures)
NO
Horizontal with special floor fixing plate or with housing in the underground configuration with foundation pit
IP67
384x236x76 mm (straight arm) / 7 kg
TECHNICAL SPECIFICATIONS OF PRODUCT COMPONENTS
The product WU2S is produced by Nice S.p.a. (TV) I, Mhouse is a company part of the NICE S.p.a. group.In order to improve its products, NICE S.p.a. reserves the right to modify the technical characteristics at any time without prior notice. In any case, the manufacturer guarantees their functionality and fitness for the intended purposes. Note: all technical specifications refer to a temperature of 20 °C.
Product Type
Adopted technology
Detection capacity
TX transmission angle
RX reception angle
Useful range
Power supply / output
Absorbed power
Max. cable length
Possibility of address assignment
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Presence detector for automations of automatic gates and doors (type D according to standard EN 12453) comprising a transmitter “TX” and receiver “RX
Optical, by direct interpolation of TX-RX with modulated infra-red rays
Opaque objects located on the optical axis between TX and RX, larger than 50 mm and moving slower than 1.6 m/s
20° approx.
20° approx.
10 m for maximum TX-RX misalignment ±5° (the device can signal an obstacle even in the event of particularly adverse weather conditions)
The device can only be connected to the “ECSBus” networks from which it receives mains power, and sends the output signals
1 ECSBus unit
Up to 20 m (observe warnings regarding the minimum section and type of cables)
UP to 7 detectors with protection function and 2 with opening command function Automatic synchronisation prevents interference between the various detectors
-20 ÷ 50°C
No
Vertical, wall-mounted
IP44
64 x 89,2 h 29 mm / 60 g
Product Type
Adopted technology
Maximum frequency of cycles
Mains power supply
Nominal absorbed power
Backup power supply
Motor ouputs
Flashing light output
ECSBus output
“OPEN” input
“STOP” input
Radio Aerial input
Max. cable length
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Possibility of remote control
Compatible GTX4 transmitters
GTX4 transmitter range
Programmable functions
Self-programmed functions
CL2S control unit
26 – English
English
Control unit for 1 or 2 24Vdc motors for automation of automatic gates or doors, complete with radio receiver for “GTX4” transmitters
Electronic board governed by 8-bit microcontroller with flash technology A transformer incorporated in the control unit, but separated from the board, reduces the mains voltage to the nominal 24 V voltage used in the whole automation system
30 cycles/hour at 50°C A
230Vac (+10% -10%) 50/60Hz
120 W; on start-up power is 310 W for a maximum time interval of 2s
For “PR1” buffer batteries
2, for 24 Vdc motors with nominal current of 1.1A, on start-up, maximum current is 3.5 A for a maximum time interval of 2 s
For flashing light with 12 V (maximum 21 W) bulb.
1 output with maximum load of 15 ECSBus units
For normally open contacts (closure of the contact prompts the “OPEN” command)
For normally open and/or 8,2kΩ constant resistance type contacts, or normally closed contacts with self-learning of the “normal” status (a variation with respect to the memorised status gener­ates a “STOP” command)
50 Ω for RG58 or similar type cable
Mains power-supply: 30 m; motor ouputs: 10 m; other inputs/outputs: 20 m with antenna cable preferably less than 5 m (observe warnings regarding the minimum section and type of cables)
-20 ÷ 50°C
No
Vertical, wall-mounted
IP44
180 x 240 h 110mm / 2,8kg
With “GTX4” transmitters, the control unit is set to receive one or more of the following commands: “OPEN”, “Partially open”, “Only open” and “Only close”
Up to 150 if memorised in mode 1
50-100 m. This distance may vary in the presence of obstacles and electromagnetic disturbance present, and is influenced by the position of the receiving antenna built into the flashing light
“Single cycle” or “Complete cycle” (automatic closure) operating mode Motor speed “low” or “high” Pause time in “complete cycle” selectable from 10, 20, 40, and 80 seconds Type of partial opening selectable from 4 modes Obstacle detection system sensitivity selectable on 4 levels “Open command” operating mode selectable on 4 modes
Self-learning of devices connected to the ECSBus output Self-learning of type of “STOP” device (NO, NC or 8.2 kΩ resistance contact) Self-learning of manoeuvre length for each motor Self-learning of automation with 1 or 2 motors
GTX4 Transmitters
KS100 Key-operated selector switch (optional)
FL100 indicator light (optional)
English – 27
English
Product Type
Adopted technology
Anti-intruder
Lock safety
Power supply / contacts
Max. cable length
Ambient operating temperature
Use in particularly acid, saline or po tentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Product Type
Adopted technology
Lamp
Power supply
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Assembly
Protection rating
Dimensions / weight
Flashing indicator light for automations of automatic gates and doors. The device incorporates a receiver antenna for remote control
Indicator light with 12V 21W lamp controlled by the control units for MHOUSE automations
12V 21W fitting BA15 (vehicle type lamp)
The device can only be connected to the terminals “FLASH” and “ANTENNA” of the MHOUSE automation control units
-20 ÷ 50°C
No
Horizontal on a flat surface or vertical wall-mounted
IP55
120 x 60 h 170mm / 285g
Double switch with key operation, suitable for controlling automations of automatic gates and doors. Equipped with lighting for night-time use
Activation protected by lock, insertion and clockwise rotation of the key closes a contact; anti­clockwise rotation closes a second contact, and in both cases a spring returns the key to the cen­tral position
The selector can only be turned on after insertion of the key and rotation on one of the two direc­tions
Key with 450 different codes
The device can only be connected to the terminals “OPEN” and “STOP” of the MHOUSE automa­tion control units to which it sends the command signals, and from which it receives the mains power for night-time lighting
Up to 20 m (observe warnings on the control units regarding the minimum section and type of cables)
-20 ÷ 50°
No
Vertical, wall-mounted
IP44
89 x 65 h 37mm / 120 g
Product Type
Adopted technology
Frequency
Encoding
Keys
Radiated power
Power supply
Battery life
Ambient operating temperature
Use in particularly acid, saline or potentially explosive atmospheres
Protection rating
Dimensions / weight
Radio transmitters for remote control of automations for automatic gates and doors
Encoded AM OOK radio modulation
433.92 MHz
64 Bit rolling code (18 billion billion combinations)
4, each key can be used for different commands of the same control unit or to control different control units
0.001 W approx.
3V; +20% -40%; with 1 lithium battery type CR2032
3 years, estimated on the basis of 10 commands/day lasting 1s at 20°C (battery efficiency is reduced at low temperatures)
-20 ÷ 50°C
No
IP 40 (use in the home or protected environments)
50 x 50 h 17mm / 16g
28 – English
English
ALLEGATO 2ANNEX 1
CE Declaration of Conformity
Declaration in accordance with the Directives: 1999/5/CE (R&TTE), 2004/108/CE (EMC);
2006/42/CE (MD) Appendix II, part B;
WU1SK, CL2S, GTX4, PH100 and FL100 are produced by Nice S.p.a. (TV) I; MHOUSE S.r.l . is a commercial trademark
owned by the group Nice S.p.a.
Note - The contents of this declaration correspond to declarations in the last revision of the official document deposited at the registered offices of Nice Spa available before this manual was printed. The text herein has been re-edited for editorial purpos­es. A copy of the original declaration can be requested from Nice S.p.a. (TV) I.
Number: 370/WU2S Revision: 0 Language: EN
Manufacturer’s Name: NICE S.p.A. Address: Via Pezza Alta 13, Z.I. Rustignè, 31046 Oderzo (TV) Italy Person authorised to compile the technical documentation:
Sig. Oscar Marchetto.
Product type: Electromechanical gearmotor and relative accessories Model / Type: WU1SK, CL2S, GTX4, PH100, FL100 Accessories:
The undersigned, Luigi Paro, in the role of Managing Director, declares under his sole responsibility, that the above mentioned product conforms to the requirements of the following directives:
• The products CL2S and GTX4 conform to the 1999/5/CE DIRECTIVE OF THE EUROPEAN PARLIAMENT AND COUNCIL of 9th March 1999 regarding radio equipment and telecommunications terminal equipment and the mutual recognition of their conformity, according to the following harmonised standards:
- Health protection (art. 3(1)(a)): EN 50371:2002
- Electric safety (art. 3(1)(a)): EN 60950-1:2006
- Electromagnetic compatibility (art. 3(1)(b)): EN 301 489-1 V1.8.1:2008, EN 301 489-3 V1.4.1:2002
- Radio spectrum (art. 3(3)): EN 300 220-2 V2.1.2:2007
In accordance with the directive 1999/5/EC (appendix V), the product is class 1 and marked:
• Models WU1SK, CL2S, PH100 and FL100 conform to DIRECTIVE 2004/108/CE/108/EC OF THE EUROPEAN PARLIAMENT AND COUNCIL of 15th December 2004 regarding the approximation of member state legislation related to electromagnetic compatibility, repealing directive 89/336/EEC, according to the following harmonised standards: EN 61000-6-2:2005, EN 61000-6-3:2007
In addition the product WU1SK and CL2S conform to the following directive according to the requirements for “partly complet-
ed machinery”:
2006/42/EC DIRECTIVE OF THE EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 regarding machinery, repealing
directive 95/16/EC
We hereby declare that the relevant technical documentation has been compiled in conformity with Annex VII B of directive 2006/42/EC and that the following essential requirements have been satisfied:
1.1- 1.1.2- 1.1.3- 1.2.1-1.2.6- 1.5.1-1.5.2- 1.5.5- 1.5.6- 1.5.7- 1.5.8- 1.5.10- 1.5.11
• The manufacturer undertakes to transmit, in response to a reasoned request by the national authorities, relevant information on the “partly completed machinery”, without prejudice to intellectual property rights of the manufacturer.
• Should the “partly completed machinery” be put into service in a European country with an official language different from the one of this dec­laration, the importer must attach the translation of this document to the declaration.
• The “partly completed machinery” must not be put into service until the final machinery into which it is to be incorporated has been declared in conformity with the provisions of directive 2006/42/EC.
In addition the product WU1SK and CL2S conform to the following directives: EN 60335-1:2002 + A1:2004 + A11:2004 + A12:2006 + A2:2006 + A13:2008 EN 60335-2-103:2003
The products WU1SK and CL2S also comply, within the constraints of applicable parts, with the following standards: EN 13241-1:2003, EN 12445:2002, EN 12453:2002, EN 12978:2003
Oderzo, 11thNovember 2010
Ing. Luigi Paro (Managing Director)
0682
English – 29
English
• With selector (optional accessory)
The selector has two positions with automatic return to the centre (fig. 46).
(*) This item must be compiled by the person who programmed the automation.
Control with safety devices out of service
In the event of safety devices malfunctioning or out of service, the door may still be moved.
01. Activates the gate command (with remote control or key­operated selector switch). The door will open normally if there is the consent of the safety devices, otherwise the command must be activated and held within 3 seconds.
02. After about 2 s the door will move in “hold-to-run” mode, in other words until the command is pressed the door will con­tinue to move; the door will stop as soon as the command is released.
In the event of safety devices out of service arrange for repairs to the automation immediately.
11.2 – Gate control
• With radio transmitter
The radio transmitter supplied is ready for use and the four keys have the following functions (fig. 45).
(*) This table must be compiled by the person who programmed the automation.
––– STEP 11 –––
This guide must be stored safely and be accessible to all automa­tion users.
11.1 – Safety instructions
• Keep at a safe distance from the moving door until it is completely open or closed; do not go through the door until it is completely open and has come to a standstill.
• Do not allow children to play near the door or with the con­trols.
• Keep the transmitters away from children.
• Suspend the use of the automation immediately as soon as
you notice something abnormal in the operation (noises or jolting movements); failure to follow this warning may cause serious danger and accidents.
• Do not touch moving parts.
• Regular maintenance checks must be carried out by quali-
fied personnel according to the maintenance plan.
• Maintenance or repairs must only be carried out by quali-
fied technical personnel.
USER’S GUIDE
45
T3
T4
T1
T2
Function (*)
Key T1
Key T2
Key T3
Key T4
46
Action
Turned right: “OPEN”
Turned left: “STOP”
Function
(*)
Stops movement of the sectional or up-and-over door
In case of fault of the gearmotor the motor release can be used to check whether the fault is in the release mechanism.
01. Open one of the two release covers of the gearmotor by pulling the relative tab.
02. Insert the key in the release pin.
03. Turn the key anti-clockwise by about 90° until the gate is
released.
04. Then move the gate manually.
11.3 – Manually releasing or locking the gearmo-
tor (fig. 47)
WU2S are equipped with a mechanical system that enables man­ual opening and closing of the gate (i.e. as if there is not a gear­motor).
The manual operation must be carried out in case of power failure or system malfunction. In case of power failure the buffer battery can be used (optional accessory PR1).
30 – English
English
05. To reset the automation turn the key clockwise and at the same time move the gate until you hear the carriage engage.
06. Remove the key and close the release cap cover.
11.4 – Maintenance operations admissible to the
user
The list of operations to be regularly carried out by the user is list­ed below.
• For cleaning the surfaces of the devices, use a slightly
damp (not wet) cloth. Never use substances containing alco­hol, benzene, diluents or other flammable substances. Use of these substances may damage the devices and cause fires or electric shocks.
• Disconnect the automation from the power supply before
removing leaves or stones to stop anyone activating the door.
• Regularly check the system, in particular the cables,
springs and supports and check for signs of unbalance, wear or damage. Do not use the automation if it needs to be repaired or adjusted as a fault or an incorrectly balanced door may cause injuries.
11.5 – Remote control battery replacement (fig. 48)
When the battery charge is low, the transmitter range is reduced significantly. When a key is pressed, if led L1 illuminates and then immediately fades and turns off, this means that the battery is completely discharged and must be replaced immediately.
Otherwise if led L1 illuminates briefly, this means that the battery charge is low; in this case press and hold the key for at least half a second to enable the transmitter to attempt delivery of the com­mand. In any event, if the battery charge is too low to complete a command (and wait for a response) led L1 fades and the trans­mitter turns off. In these cases, to restore normal operation of the transmitter, replace the old battery with a new version of the same type, taking care to observe the specified polarity. To replace the battery, proceed as shown in the figure below.
The batteries contain pollutant substances: do not dispose of them with normal waste material; follow the instructions foreseen by local regulations.
11.6 – Installing the remote control support
To install the remote control support, see fig. 49.
47
49
48
English – 31
English
CE DECLARATION OF CONFORMITY
In conformity with Directive 2006/42/EC, APPENDIX II, part A (EC declaration of conformity for machinery)
––––––––––––––––––––
The undersigned/company
(name or company name of the person responsible for commissioning of the power-operated gate: . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hereby declares under his/her sole responsibility that:
- The automation: power-operated swing gate
- Serial N°: . . . . . . . . . . . . . . . . . . .
- Year of manufacture: . . . . . . . . . . . . . . . . . . .
- Location (address): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Complies with the essential requirements of the following directives:
2006/42/CE “Machinery” Directive
2004/108/CEE Electromagnetic compatibility directive
2006/95/CEE “Low Voltage” Directive
1999/5/CE “R&TTE” Directive
and what is provided for by the following harmonised standards:
EN 12445 “Industrial, commercial and garage doors and gates. Safety in use of power operated doors - Test
methods”
EN 12453 “Industrial, commercial and garage doors and gates. Safety in use of power operated doors -
Requirements”
Name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date: . . . . . . . . . . . . . . . . . . . . . .
Place: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ANNEX 2
Mhouse is a commercial trademark owned by Nice S.p.a.
Nice S.p.a. Via Pezza Alta, 13 - Z.I. Rustignè
31046 Oderzo (TV), Italia Tel. +39 0422 85 38 38 Fax +39 0422 85 35 85
Loading...