MGM GENERAL PURPOSE DRY Installation Manual

5701 S M IT H W A Y ST R E E T • C O M M E R C E , C A 9 0 0 40
(323) 726-0 8 8 8 • (800) 423-4366 • F A X (3 2 3 ) 7 2 6 -8224
w w w .m g m tr an sfor m e r.co m
GENERAL PURPOSE DRY - TYPE
DISTRIBUTION TRANSFORMER
INSTALLATION, OPERATION, AND
MAINTENANCE MANUAL
MGM 100-10A-04-2018
MGM 100
-
10A
WARNING
Electrical potentials hazardous to human life can exist within this equipment when it is energized. Disconnect all input power before opening the case or touching the internal parts
The information contained herein may not cover all variations in equipment supplied or provide for all contingencies that might arise during the installation, operation or maintenance for this equipment. If there is any question regarding the above items, contact your supplier.
IT IS E BY Q
XPECTED THAT ANY INSTALLATION OR MAINTENANCE WILL BE PERFORMED
UALIFIED PERSONNEL ACCORDING TO LOCAL
, S
TATE
, A
ND NATIONAL CODES
.
MGM 100
-
10A
Table of contents
General ...................................................................................................................... 3
Inspection upon Receipt ............................................................................................. 3
Handling ..................................................................................................................... 3
Storage ....................................................................................................................... 3
Installation Location .................................................................................................... 3
Room Requirements ................................................................................................... 3
Connections ............................................................................................................... 4
Grounding .................................................................................................................. 4
Reverse Feed or Step-up Operation ........................................................................... 4
Reducing Sound Levels .............................................................................................. 4
Prior To Energizing ..................................................................................................... 5
Maintenance ............................................................................................................... 5
Lighting Tap Applications ........................................................................................... 5
Dielectric Insulation .................................................................................................... 5
Ambient Temperature ................................................................................................. 5
Altitude ....................................................................................................................... 6
Single Phase Three Wire Operation ........................................................................... 6
References ................................................................................................................. 6
When you need Service ............................................................................................. 6
Terms and Conditions ................................................................................................ 6
Appendix A - Seismic Kit Installation Instructions (cases A, B, B+, C, C+)
Appendix B - Seismic Kit Installation Instructions (cases D & E)
Appendix C - Wall Mount Bracket Installation Instructions
Appendix D - Weatherproof Kit Installation Instructions
Appendix E - Rodent / Bird Screen Kit Installation Instructions
MGM 100-10A
3
General
Read the entire manual before attempting to perform installation of this transformer. Dry type transformers are suitable for indoor or outdoor use depending upon the construction of the enclosure as well as the ability to protect the transformer from unwarranted access to live parts. They are cooled by the free circulation of air through the enclosures, the average ambient temperature over 24 hours should not exceed 30° C (86°F), the maximum ambient temperature should not exceed 40° C (104°F) or as otherwise specified in the specification. Overheating may occur if the air flow is restricted, the transformer is overloaded, it is supplied with over or under voltage, or operated at other than rated frequency.
Inspection upon Receipt
Units are shipped in upright position and should arrive that way. Upon arrival, all units should be inspected for damage during shipment. Unpack and examine for broken or loose parts. Careful inspection should be made of transformer coils, wiring and insulators. What appears to be minor damage in these areas may result in an open or short circuit. Claims for damage should be filed with the transportation company and an MGM Transformer Company representative must be notified immediately. For superficial or minor case part damage, spare parts may be available, contact an MGM Transformer Company representative.
Handling
Lifting with hand trucks or fork lift trucks is permissible if the blades or forks are long enough to pass completely under the case. Since most general purpose transformers have a high center of gravity, extreme caution should be exercised when lifting or moving the units.
If it is necessary to move ventilated dry-type transformers during inclement weather then they should be thoroughly protected against the entrance of moisture.
Storage
Storage areas should be as clean and dry as possible without extreme temperature variations. Protective wrappings should be left intact until the transformer is moved to its permanent location. Dry type transformers stored under extremely wet or dusty conditions must have cleaning and drying operations performed before the unit can be energized. (See Maintenance Section.)
Installation Location
Factors to be kept in mind when choosing a location for dry type transformers are: accessibility, ventilation, environmental conditions, and noise (see ‘Reducing Sound Levels’). Installation should be made in an area reasonably free from dust, excessive moisture, fertilizers, chemicals and other corrosive fumes or vapors and separated from flammable materials in accordance with the NEC.
General purpose dry type transformers up to case GPC+ are supplied in dual rated enclosures suitable for indoor/outdoor installation and eliminates the need of a weather shield kit. Weather shield kits are for cases GPD and GPE which are available to convert these enclosures for UL listed outdoor NEMA 3R use. The appropriate kit can be obtained from a MGM Transformer representative. Even with a properly attached weathershield kit, no transformer should be hosed off, or placed in the catchment area of a water sprinkler. Wall-mount brackets are also available for units up to 75 KVA.
In all locations dry type transformers must be installed in the upright position in an area with free air circulation. Check NEC codes for minimum required clearances from adjacent structures. Fencing in the transformer to prevent unauthorized access is strongly recommended.
Room Requirements
Dry-type transformers located indoors should comply with the application requirements of NEC.
The room in which dry-type transformers are located should be sized to permit locating transformers with sufficient spacing between units and sufficient clearances to walls and other obstructions (as specified per NEC or as indicated below nameplate) to permit air circulation. Sufficient space should also be provided to permit routine inspection and maintenance.
Adequate ventilation is essential for the proper cooling of transformers. Clean, dry air is desirable. Filtered air at or above atmospheric pressure may reduce maintenance if dust or other contaminants present a particular problem. When transformers are located in rooms or other restricted spaces, sufficient ventilation should be provided to hold the air temperature within established limits when measured near the transformer inlets. This
will usually require approximately 100 ft3/min of air per kilowatt of transformer loss. The area of ventilating opening required depends upon the height of the room, the location of openings, and the maximum loads to be carried by the transformer. Room ventilation should not impede normal circulation of air through the transformer.
When possible, the air inlet to the room should be near the floor with the outlet in the opposite upper end of the room. The exhausting air should not exceed 15°C over the inlet air temperature. When necessary, forced air exhaust should be used to maintain this maximum differential.
FOR ADDITIONAL INFORMATION VISIT US ONLINE AT WWW.MGMTRANSFORMER.COM
BOLT
TYP TOL
ALUM
SIL BRONZE
STEEL
Connections
Cautions: Make only those connections shown on the
nameplate or connection diagram. Before energizing, check all tap jumpers for proper locations, and all bolted connections for tightness. All three sets of taps on a three phase transformer must be connected in the same location for each phase. For instructions on how to read nameplates and connection diagrams, please visit the documentation section of our website at: http://www.mgmtransformer.com .
All transformers, with bottom connections are designed for easy accommodation of cable sizes in accordance with NEC. Cables which will carry less than 100 amperes may have a 60° C temperature rating or higher, and cables which will carry 100 amperes or more must have a 75° C temperature rating or higher. All cables should be in the lower part of the transformer enclosure in accordance with markings on the enclosure.
Use 90° C cable sized to 75° C ampacity for the units having terminals located above the coils. After the first thirty days of service, re-tighten all connecting lugs and bolts. Depending on the kVA rating, the transformer may have flexible leads with bolted type wire terminals, copper/aluminum (CU/AL) lug connectors, or simply termination pads for mounting your own crimp or lug type terminations. The table below shows required torque for installing bolted wire connectors and cables in lug type connectors.
SIZE
1/4-20 +/- 20% 50 4 60 5 75 6
5/16-18 +/- 20% 85 7 110 9 135 11
3/8-16 +/-20 % 145 12 195 16 240 20
1/2-13 +/-15 % 300 25 420 35 540 45
5/8-11 +/-15 % 480 40 840 70 1080 90
3/4-10 +/-15 % 720 60 1200 100 1560 130
NOTES:
1. Always use two wrenches when tightening or loosening bolted connections to prevent damage.
2. Tighten, wait several seconds, then re-tighten all connecting lugs and bolts.
Minimum electrical clearances in the installation of lugs and cables must be per ANSI and NEMA Standards. All electrical clearances that are questionable must be insulated for the applied voltage. Particular care should be taken with shielded cables, so that the ground termi­nation of the cables has sufficient clearance from all the manufacturers installed live parts, including parts that appear to be insulated.
+/- NOM
In-
Lbs
Ft-
Lbs
In-
Lbs
Ft-
Lbs
In-
Lbs
FOR ADDITIONAL INFORMATION VISIT US ONLINE AT WWW.MGMTRANSFORMER.COM
Ft-
Lbs
MGM 100-10A
Grounding
It is the responsibility of the installer to ground the transformer enclosure assembly to the ground system in accordance with the latest revision of the NEC Section 450-10, NEC Article 250 and ANSI/IEEE Std. 144.
Reverse Feed or Step-up Operation
Step-down transformers may be reverse fed for step-up operation to increase voltage. This means that the incoming power is connected to the low voltage (X’s) and the load is connected to the high voltage (H’s). If the low voltage is wye, the X0 terminal must NOT be connected in any way. Likewise, if the low voltage is a delta with a 120 volt lighting tap (high-leg), the X4 terminal must NOT be connected in any way.
CAUTION: Much higher than normal inrush currents may occur with reverse feed operation and may cause nuisance fuse blowing or breaker tripping. For this reason, fuses and breakers with time-delay characteristics must be used.
If a breaker is used for incoming over-current protection, it must be a thermal-magnetic type breaker, not a magnetic­only type breaker. Tap Settings are for the high voltage side and when reverse fed the ability to adjust voltages is no longer available. This means some performance parameters may be affected.
Reducing Sound Levels
Transformer noise originates within the steel core. It is an inherent characteristic of all transformers and cannot be completely eliminated. Therefore, care should be exercised in the selection of the transformer location, particularly in buildings where the ambient sound level is quite low. A transformer's sound level is quite often unintentionally amplified by improper installation, which makes the transformer appear to be considerably louder than it actually is. Transformer sound levels are amplified by sound waves in the air being reflected from surrounding objects and resonance of mounting construction and electrical connections. This situation should be avoided wherever possible. Trans forme rs should be c onn ected f or and en ergiz ed at r at ed volta ge and fr equency at n o loa d t o de termi ne the corre ct noise l evel. Transformer sound level problems can also be further minimized by following these installation suggestions:
1. The case may be installed on vibration mounts for additional reduction of sound levels.
2. Flexible conduit couplings should be used to reduce vibration transfer from the case to the incoming and outgoing conduit.
3. The installation should be in an area where the sound will be least objectionable.
4. Avoid stairway and hall areas or reflecting objects which resonate or echo. Concrete or masonry walls, floors and ceilings are excellent sounding boards. If these and other reflecting surfaces cannot be avoided, acoustic absorbing materials should be used to cover them.
4
Loading...
+ 11 hidden pages