MGE UPS Systems Pulsar Esprit 313.5 kVA User Manual

Page 1
Pulsar Esprit
3 –13.5 kVA
High Availability UPS for Internet Servers
MGE UPS SYSTEMS all new Pulsar Esprit has been specifically designed to meet the needs of Internet Service Providers & Application Service Providers. Esprit provides total power availability with redundant UPSs for the price of a regular, single UPS. This redundant combination, called Power Cluster, has been pioneered exclusively by MGE.
Pulsar Esprit has been designed with the Internet in mind:
For the first time, it is possible to remotely monitor an UPS using XML tags to perform automatic actions. This breakthrough technology is the result of MGE's heavy investment in research and development. They provide ISPs with the best combination of power availability and cost. With the revolutionary Esprit Power Cluster, MGE brings affordable, total power availability to smaller ISPs and mid-size businesses with 3 to 15 servers.
Pulsar Esprit World First. . .
First high availability UPS with maximum reliability
at an affordable cost (Power Cluster)
First UPS with infinitely expandable batteriesFirst UPS to provide “redundant hot swap” battery capability
First server-grade UPS with built-in USB communications First UPS in its class with HID protocol for seamless
integration with Windows 2000
First UPS managed with XML tags
Advanced Features
High availability power
+ maximum reliability = MGE Power Cluster
Web-based management
using XML
Standard USB
communications
Seamless integration
with Microsoft Windows 2000
Redundant battery
back-up potential
Redundant
battery chargers (with additional batteries)
Plug-in convenience
up to 8.5 kVA
Can be installed by
non-technical personnel
Capable of long
duration backup
Page 2
The Power Cluster Advantage
Traditional N+1 Redundant UPS
N+1
Redundant Server
MGE Esprit
Power Cluster
N+1
Redundant Server
A
B
A
B
UPSBatteries
Redundant DC
Power Supplies
CPUs
UPSBatteries
1
2
2
3
3
Redundant DC
Power Supplies
CPUs
Configuration Comments
Single point of failure Traditional redundant UPSs are paralleled at their outputs and provide
a worrisome single point of failure. Redundant power paths With Esprit, power sharing is achieved within each server on the DC bus. Redundant power sources Input power connections of servers will be connected to 2 (or 3) different Esprit
modules, providing 2 (or 3) different sources, eliminating a single point of failure. Esprit, for the first time, provides MGE’s advanced engineering & design significantly reduces the component
total power availability combined count for high availability and reliability at an affordable price. Traditional N+1 with maximum reliability UPS redundancy can provide power availability at the expense of reliability with
multiple sub-assemblies that increase the chance of costly failures.
Power redundancy for servers with multiple power supplies
Most servers provide multiple power supplies for N+1 redundancy. To maintain high availability of the system when considering power, a redundant configuration as offered with the Esprit Power Cluster is better than traditional N+1 redundant UPSs:
Maximum Availability and Reliability
1
2
3
Example of 5 PC servers with 3 redundant power supplies:
Select a 4.5 kVA Esprit Power ClusterConnect the first power supply of each server to the EspritConnect the second power supply of each server to the Esprit Connect the third power supply of each server to the Esprit Connect each Esprit to a separate wall outlet.
X
Y
Z
A
B
C
A
B C
A
B C
A
B C
A
B C
A
B C
X
Y
Z
Page 3
Esprit 4.5
(5-50)
Esprit 3.1
(L5-30)
Easy Connections and Installation
Electronic Module (Esprit 3.1)
Comprehensive Display and Controls
Versatile output receptacles
Various combinations of receptacles make it easy to connect any type of server to your Esprit
Multiple Communications ports
RS232 portUSB port
Plug-In convenience up to 9 kVA
Simple installation: simply plug the system in, up to 9 kVA
Esprit 6
(L14-30)
Esprit 9
(14-50)
Rack Mounting
Esprit’s unique design lets you stack up electronic and battery modules as you want (up to 3 max.). A 5U rack mount kit that can accommodate 2 modules is available as an option.
Redundant battery path
Each UPS is equipped with two battery connectors:
Battery modules are user
hot-swappable with no risk of power interruption during the exchange
Parallel battery modules avoid the
single point of failure generated by daisy-chained battery modules.
Multiple chargers
Each battery module includes its own internal charger:
Fast recharge for any
battery runtime
A faulty charger doesn't
prevent the recharge of the other battery strings.
Infinite battery runtime
You can “parallel daisy chain” as many battery modules as needed.
Fault detected
Replace battery
Battery charging
Overload
On Utility
On Battery
Alarm Reset
Enable UPS
Disable UPS
Battery Module
Stacking
Recessed front and back handles for easy installation
Page 4
Operating Systems Supported RS232 USB
Win 98 SE / Windows 2000
Win 95 OSR2 / NT 3.51 & 4
Linux RedHat 5.2 kernel 2.0.x
Linux RedHat 6.0 kernel 2.2
Netware 3.12, 4.12, 5.0 SCO 5.0x Unixware 7.x
SNMP Management
Enterprise users can take advantage of the extensive TCP/IP-based communications offering developed by MGE.
Features include:
Remote management from an NMS platform such as
HP OpenView, CA Unicenter TNG, SunNetManager and more
Shutdown of multiple servers running different operating systemsPerform automatic actions based on power events such as paging
the network administrator or sending an eMail
Reboot a locked up server remotely using the UM Switch power controller (option)Monitor the temperature and humidity of the computer room with the UM Sensor environmental module (option)
Connection to the network is achieved through an Ethernet/SNMP card that fits into the MultiSlot Communication Expander. The multiple slots available let you manage 2 or 3 redundant Esprit UPSs as one single system over the network.
Windows
MGE has been partnering for several years with Microsoft to co-develop power management interfaces for Windows products. As a result, Windows 2000 will ship with a dedicated power panel for MGE's Esprit product. Simply connect your UPS to the PC and Windows 2000 will install automatically all the drivers to secure your operating system and its files during a power failure.
MGE
power management software is available for
Windows 95/98/NT 4 and 2000 & is fully Plug & Play.
Esprit communication is based on the new Microsoft's HID protocol, which
will become the standard for any device interfaced with Windows
2000. By already implementing this industry standard, MGE offers seamless integration and faster, more reliable communications to its customers.
All Esprit models come standard with built-in communications capabilities using either an RS232 or USB port. UPS-to-server communications is essential to secure the operation of your operating system during an extended power failure. The UPS will signal the O/S when its batteries are almost depleted to launch an orderly, graceful shutdown process to make sure all files are protected. This feature is vital for systems running unattended, such as Web servers.
Web-based Management Using XML
MGE UPS SYSTEMS is currently chairing the W3C UPS industry workgroup, which will define an industry standard for power management over the Web. XML will quickly replace HTML as the protocol of choice for web-based management. HTML can only display information in a browser, it cannot easily send the data to another piece of software to perform an automatic action such as triggering a shut down command of the system or paging an administrator. MGE's XML -@gent runs on a Windows NT/2000 server and constantly monitors the status of the incoming power, publishing browser alerts during a power problem to all subscribing web-enabled nodes. MGE is the first UPS to offer Web-based management using the new XML/XSL (Extended Mark-up Language/Extended Style Language) specification for data communications
Internet-Grade Monitoring and Communications
Linux
MGE's popular Solution-Pac power management software is available for Linux. It provides a simple way to secure the operation of multiple Web servers during a power outage.
UM Switch
UM Sensor
MultiSlot Communication Expander
Page 5
Standard 2 Batteries 3 Batteries 4 Batteries 5 Batteries 6 Batteries
Standard 4 Batteries 6 Batteries 8 Batteries 10 Batteries 12 Batteries
13 30 54 75 108 126
8 22 34 42 54 72
13 30 54 75 108 126
8 22 34 42 54 72
* For servers with 3 redundant power supplies, add additional Esprit UPS.
Notes:1Example above requires adding one additional battery module to an Esprit 4.5 & will provide 22 minutes of runtime at full load. 2For Esprit 6 & 8.5 kVA, battery modules must be added in pairs.
Model Single UPS
Power Cluster
(for servers with 2 redundant power supplies*)
3-server protection 3-server protection
Esprit 3.1 3.0 kVA 3.0 kVA
5U (in rack) 10U (in rack)
Expand load to 6 kVA
(with no redundancy)
5-server protection 5-server protection
Esprit 4.5 4.5 kVA 4.5 kVA
5U (in rack) 10U (in rack)
Expand load to 9 kVA
(with no redundancy)
6-server protection 6-server protection
Esprit 6 6 kVA 6 kVA
10U (in rack) Expand load to 12 kVA
(with no redundancy)
Select the Esprit you need for your Web Servers
9-server protection 9-server protection
Esprit 9 8.5 kVA 8.5 kVA
10U (in rack) Expand load to 17 kVA
(with no redundancy)
15-server protection 15-server protection
Esprit 13.5 13.5 kVA 13.5 kVA
15U (in rack) Expand load to 27 kVA3 to 1 interface (with no redundancy)
3 to 1 interface
Scalable Battery Runtimes (in Minutes)
Esprit 3.1
Esprit 4.5
Esprit 6
Esprit 9
Page 6
©MGE UPS SYSTEMS, Inc. All specifications subject to change without notice. The MGE UPS SYSTEMS logo is a trademark of MGE UPS SYSTEMS.
CANADA
#9, 2798 Thamesgate Dr. Mississauga, ON L4T 4E8 tel (905) 672-0990
(877) 672-0990
fax (905) 672-7667
esprit 101 Effective: April 2000
USA (headquarters) 1660 Scenic Avenue Costa Mesa, CA 92626 tel (800) 523-0142
(714) 557-1636
fax (714) 557-9788
www.mgeups.com
info@mgeups.com
BRAZIL
Avenida Guido Caloi 1985 (GALPAO 23) Guarapiranga Sao Paulo - SP, CEP 05802 tel (55) 11-5890-3323 fax (55) 11-5890-3353
ARGENTINA
Thames 91 1609 San Isidro Prov de Buenos Aires tel (54) 11-4766-8777 fax (55) 11-4766-6008
MGE UPS SYSTEMS
MGE GREEN SWEEP
Call MGE to return your UPS for free recycling to a US EPA-certified recycling center and help protect our environment.
Characteristics
Esprit 3.1 Esprit 4.5 Esprit 6 Esprit 9
❊❊
Independent test lab report available on MGE’s web site
Dimensions
and Weights
Electrical
Power (VA/W) 3000/2016 4500/3150 6000/4032 8500/6000 Input voltage range
100/120/127 Volts +10% -15% 100/120/127 Volts +10% -15% 208/220/240 Volts+10%-15% 208/220/240 Volts+10%-15%
Output voltage range 100/120/127 Volts 100/120/127 Volts 100/120/127/200/208/220/240 Volts Output frequency regulation 50/60 Hz +/- 0.5 Hz Surge protection 420 joules 420 joules 630 joules 630 joules Efficiency (on battery) > 94% > 94% > 94% > 94% Waveform Compatible with multiple server-grade, Power Factor Corrected (PFC) power supplies
❊❊
Batteries
Number and type 12 x 12V/7Ah 12 x 12V/7Ah 24 x 12V/7Ah 24 x 12V/7Ah Recharge time 4 hours to 80% 4 hours to 80% 4 hours to 80% 4 hours to 80% Battery life expectancy 4-5 years 4-5 years 4-5 years 4-5 years
User connections
Input power cord 6 feet w/ L5-30P 6 feet w/ 5-50P 6 feet w/ L14-30P 6 feet w/ 14-50P Output receptacles
L5-30 & 4 x 5-15 5-50 & 4 x 5-15 L14-30, L6-30 & 6 x 5-15 14-50, L6-30 & 6 x 5-15 Communication ports 1xRS232 & 1xUSB Software included Solution-Pac Power Management suite
Environment
Safety UL, cUL 1778 Surge protection ANSI C62.41 Noise level 45 dBA max. Operating temperature 32-105 F Manufacturer certifications FCC, ISO 9001 Warranty 2 years, parts and labor electronics (battery modules:1year) Warranty extension (option) 3 years, parts and labor incl. batteries Environmental Recyclable components, packing & documentation, recycled materials, used battery recovery
3 PC 4 PC 5 PC 6 PC 2 RISC 9 PC 12 PC 15 PC servers servers servers servers servers servers servers servers
Esprit 3.1 17 Esprit 4.5 20 12 8 Esprit 6 45 26 18 15 13 Esprit 9 48 33 22 20 15 10 Esprit 13.5
100 70 55 47 40 25 18 13
Single UPS
Sizing Guide and Battery Runtimes
Single UPS Power Cluster (for servers with 2 redundant power supplies)
Model
Dimensions
Weight
Dimensions
Weight
WxHxD (in.) (lbs.) WxHxD (in.) each (lbs.) each
Esprit 3.1 Electronic 1 ea. 8.5" x 7.25" x 19" 20 2 ea. 8.5" x 7.25" x 19" 20
Battery 1 ea. 8.5" x 7.25" x 19" 80 2 ea. 8.5" x 7.25" x 19" 80
Esprit 4.5 Electronic 1 ea. 8.5" x 7.25" x 19" 20 2 ea. 8.5" x 7.25" x 19” 20
Battery 1 ea. 8.5" x 7.25" x 19" 80 2 ea. 8.5" x 7.25" x 19" 80
Esprit 6 Electronic 1 ea. 17" x 7.25" x 19" 40 2 ea. 17" x 7.25" x 19" 40
Battery 2 ea. 8.5" x 7.25" x 19" 80 4 ea. 8.5" x 7.25" x 19" 80
Esprit 9 Electronic 1 ea. 17" x 7.25" x 19" 40 2 ea. 17" x 7.25" x 19" 40
Battery 2 ea. 8.5" x 7.25" x 19" 80 4 ea. 8.5" x 7.25" x 19" 80
Esprit 13.5
Electronic 3 ea. 8.5" x 7.25" x 19" 20 6 ea. 8.5" x 7.25" x 19" 20 Battery 3 ea. 8.5" x 7.25" x 19" 80 6 ea. 8.5" x 7.25" x 19" 80 3 to1 Interface
1 ea. 19” x 4” x 5.1” 20 2 ea. 19” x 4” x 5.1” 20
Esprit 13.5 consists of 3 each Esprit 4.5 plus 1 3 to 1 interface
Pulsar Esprit
Specifications
Esprit 4.5
Esprit 13.5 Power Cluster
Note: In a Power Cluster configuration, the battery runtimes given above will double.