MGE UPS Systems GALAXY PW 225KVA User Manual

Page 1
Galaxy PW
100 to 225kVA
Uninterruptible Power Systems
Installation and User Manual
86-133060-00 A00
www.mgeups.com
Features
Single and Parallel UPSs
Maintenance Bypass
Optional Up-link to an
IBM AS4000
Page 2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains important instructions for the Galaxy PW™ that must be
followed during operation of the equipment.
WARNING Opening enclosures expose hazardous voltages. Always refer service to
qualified personnel only.
ATTENTION L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous tou-
jours que le service ne soit fait que par des personnes qualifiees.
WARNUNG! Das öffnen der Gehäuse legen gefährliche Spannungen bloss. Service sollte
immer nur von qualifizierten Personal durchgeführt werden.
WARNING As standards, specifications, and designs are subject to change, please ask for
confirmation of the information given in this publication.
ATTENTION Comme les normes, spécifications et produits peuvent changer, veuillez
demander confirmation des informations contenues dans cette publication.
WARNUNG! Normen, Spezifizierungen und Pläne unterliegen Anderungen. Bitte verlangen
Sie eine Bestätigung über alle Informationen, die in dieser Ausgabe gemacht wurden.
NOTE This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equip­ment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user's own expense.
Certification Standards
IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability
FCC rules and regulations of Part 15, Subpart J, Class A
UL listed under 1778-ULC, Standards for Uninterruptible Power Supply Equipment
NEMA PE 1 (National Electrical Manufacturers Association) - Uninterruptible Power Systems
NEMA 250 (National Electrical Manufacturers Association)
– Enclosures for Electrical Equipment (1000 Volts Maximum)
NFPA 70 – National Electrical Code
ISO 9001
Occupational Safety & Health Administration (OSHA)
Galaxy PWUPS 100 to 225kVA
Important Safety Information and Standardsii 86-133060-00 A00
Page 3
How To Use This Manual and Symbol Usage iii86-133060-00 A00
WARNING To reduce the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area free of conductive contaminants.
This equipment is intended only for installations in a RESTRICTED ACCESS LOCATION.
ATTENTION Pour réduire le riske d'inccendie ou d'électrocution, installer dans une enciente
intérieure contrôlée en température et humidité et sans contaminants conducteurs.
Ce matériel est destiné seulement pour des installations dans un EMPLACE­MENT RESTREINT d'cAccès.
WARNUNG! Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das
Gerät in einem temperatur - und feuchtigkeitskontrollierten Raum, frei von leitungsfähigen Verunreinigungen, installiert werden. Dieses Gerät ist nur für die Installation an einem Ort mit eingeschränkter Zugangserlaubnis vorgesehen.
Diese Ausrüstung ist nur für Anlagen in einem EINGESCHRäNKTEN ZUGRIFF STANDORT bestimmti.
WARNING HIGH LEAKAGE CURRENT. Earth connection essential before connecting
supply.
ATTENTION COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant
le raccordement au reseau.
WARNUNG! Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverbindung herstellen.
How to Use This Manual and Symbol Usage
This manual is designed for ease of use and easy location of information.
Locate specific topics in the Table of Contents.
For terms used in the text refer to the Glossary.
Typographical conventions use single quote marks in procedures to denote a prompt for User action:
For example:
1. After the selections are complete, click on the “Save” button.
This manual uses four icon symbols with text to convey important information and tips.
WARNING indicates information provided to protect the user and service personnel against
safety hazards and/or possible equipment damage.
CAUTION indicates information provided to protect the user and service personnel against
possible equipment damage.
IMPORTANT indicates information provided as an operating instruction, or as an operating tip.
NOTE indicates information provided as an operating tip or an equipment feature.
Installation and User Manual
Page 4
iv 86-133060-00 A00
Galaxy PWUPS 100 to 225kVA
CAUTION: Record All Serial Numbers!
RECORD ALL SERIAL NUMBERS FOR THE GALAXY PWAND COMPONENTS.
THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.
KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL
NUMBERS IF SERVICE IS REQUIRED!
UPS SINGLE SERIAL NUMBER: ___________________________________________________
UPS PARALLEL SERIAL NUMBER: _________________________________________________
BATTERY CABINET SERIAL NUMBER: ______________________________________________
MBP SERIAL NUMBER: ___________________________________________________________
ADDITIONAL MODULE SERIAL NUMBERS:
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
CAUTION: Record All Serial Numbers
Page 5
Installation and User Manual
Galaxy PW
100 to 225kVA
Installation and User Manual
Revision History
Galaxy PW™ 100 to 225kVA Installation and User Manual 86-133060-00 A00
Revision: X1 Initial Release 06/2003
A00 ECN#: 003469 02/2006
Copyright © 2006 MGE UPS SYSTEMS, INC. All rights reserved. Printed in U.S.A.
MGE UPS SYSTEMS, INC.
1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636
Technical Support: 1-800-
523-0142 (during business hours)
Customer Care Center: 1-800-438-7373
(Hours: 24/7)
v86-133060-00 A00
Page 6
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
vi 86-133060-00 A00
Page 7
Contents
Contents
c i86-133060-00 A00
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
Certification Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
How to Use This Manual and Symbol Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iv
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v
Section 1 Introduction
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1
1.1 Section Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1
1.2 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 2
1.3 System Major Power Components . . . . . . . . . . . . . . . . . . . . . . . .1 — 3
1.4 Different Types of Galaxy PW™ Systems . . . . . . . . . . . . . . . . . .1 — 4
1.4.1 Single UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1.4.2 Parallel UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1.5 System Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5
1.5.1 Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5
1.6 Electrical Parameters for Selecting Protective Devices . . . . . . . .1 — 6
1.6.1 Normal AC Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
1.6.2 Bypass AC Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
1.7 Recommended Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8
1.7.1 Protection Upstream of Galaxy PW™ . . . . . . . . . . . . . . . . . . . . .1 — 8
1.7.2 Protection Downstream of Galaxy PW™ . . . . . . . . . . . . . . . . . . .1 — 8
1.8 Parallel Connected UPS Units . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9
Section 2 System Setup
2.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
2.0.1 First steps by an on-site qualified Technical Engineer . . . . . . . .2 — 1
2.0.2 Final steps by MGE Field Service Engineer . . . . . . . . . . . . . . . . .2 — 1
2.0.3 Required Equipment and Tools . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
2.1 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2
2.1.1 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2
2.1.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 3
2.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
Page 8
Galaxy PWUPS 100 to 225kVA
Contentsc ii 86-133060-00 A00
Section 2 System Setup (continued)
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
2.3 Galaxy PW™ Cabinet Major Components . . . . . . . . . . . . . . . . . .2 — 5
2.4 Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 6
2.5 Remote External Maintenance Bypass Cabinet . . . . . . . . . . . . . .2 — 7
2.6 General Instructions for Screens . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8
2.6.1 Control Panel Indicators and Definitions . . . . . . . . . . . . . . . . . . .2 — 8
2.7 System Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 10
2.7.1 Single UPS unit or Redundant Parallel UPS . . . . . . . . . . . . . . .2 — 10
2.8 Parallel UPS Unit for Increased Output . . . . . . . . . . . . . . . . . . .2 — 11
Section 3 Installation
3.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1
3.1 Optional Communications Card Installation . . . . . . . . . . . . . . . . .3 — 1
3.2 Notes on Connection of Power Circuits . . . . . . . . . . . . . . . . . . . .3 — 1
3.3 Power-Circuit Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2
3.4 Hot Swap Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2
3.5 Connections Between Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4
3.5.1 Connections Between UPOZ Boards . . . . . . . . . . . . . . . . . . . . . .3 — 4
3.5.2 Connections Between UPS Cabinets and the
Remote External Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4
3.5.3 Connections Between MUSI Boards . . . . . . . . . . . . . . . . . . . . . .3 — 5
3.6 Environmental Signal of the Media Contacts 11 Board . . . . . . . .3 — 7
3.6.1 Signal Reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7
3.6.2 Signal Transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7
3.7 "Media Contacts 11" Standard Auxiliary Circuits Connection . . . .3 — 9
3.7.1 Battery Circuit Breaker "QF1" Connection . . . . . . . . . . . . . . . . .3 — 10
3.8 Installation of the "Temperature Monitor" in the
Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10
3.8.1 "Temperature Monitor" installation in a Battery Room . . . . . . . .3 — 11
3.8.2 Connection of the Battery "Temperature Monitor" . . . . . . . . . . .3 — 12
3.9 About Final Installation Steps . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 14
Section 4 Operation
4.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
4.1 Start-up of a Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
4.1.1 Start-up of an Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
4.1.2 Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
4.1.3 Single UPS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2
4.1.4 Parallel UPS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2
4.2 Operation in On-line Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 3
4.2.1 Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 3
4.2.2 Operation with the Normal AC Source Down . . . . . . . . . . . . . . . .4 — 4
4.3 Operation with the Normal AC Source Restored . . . . . . . . . . . . .4 — 5
Page 9
Installation and User Manual
Section 4 Operation (continued)
section description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
4.4 Operation with Engine Generator Set . . . . . . . . . . . . . . . . . . . . .4 — 6
4.5 Battery Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 7
4.6 Inverter Shutdown or Overload . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 7
4.6.1 Single UPS Unit (On-line mode) . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 8
4.6.2 Parallel UPS Without Redundancy . . . . . . . . . . . . . . . . . . . . . . . .4 — 8
4.6.3 Parallel UPS With Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 9
4.7 Output Voltage Quality and Continuity . . . . . . . . . . . . . . . . . . . .4 — 9
4.7.1 Steady State Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . .4 — 10
4.7.2 Transient Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 10
4.8 Measurement System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 11
4.8.1 Voltage Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 12
4.8.2 Current Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 12
4.8.3 Power and Frequency Measurements . . . . . . . . . . . . . . . . . . . .4 — 12
4.8.4 Battery Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 12
4.9 Selections and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 13
4.10 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 16
4.11 Maintenance Bypass Option . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 16
4.12 Logging and Time-Stamping . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 17
4.12.1 Event Time-Stamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 17
4.12.2 Consulting Logged (time-stamped) Events . . . . . . . . . . . . . . . .4 — 17
4.13 Setting the Date and Time for the UPS - Utilization
Via the Galaxy PW™ Display . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 18
4.14 Consulting Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 19
4.14.1 Consulting Recorded Measurements . . . . . . . . . . . . . . . . . . . . .4 — 21
Section 5 Maintenance
5.0 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1
5.1 Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1
5.2 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
5.2 Maintenance Isolation Procedures . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
5.2.1 Single UPS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2
5.3 Steps for Parallel UPS Redundancy to Increase Output . . . . . . .5 — 4
5.4 Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 6
5.5 Visual Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 6
5.6 Functional System Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 6
5.7 Testing Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7
5.7.1 Galvanic Isolation and Voltage Matching Transformers . . . . . . . .5 — 7
5.8 Management of Computer Networks . . . . . . . . . . . . . . . . . . . . . .5 — 7
5.8.1 Integrated SNMP Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7
5.8.2 Two-channel Network Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7
Contents c iii86-133060-00 A00
Page 10
Appendices
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
Appendix A
Front Control Panel Display Definitions . . . . . . . . . . . . . . . . . . . . . . . . . .A — 1
Display of Primary and Secondary Messages . . . . . . . . . . . . . . . . . . . . .A — 4
Primary Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 5
Secondary Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 6
Appendix B
Monitoring - Electrical Supervision Options . . . . . . . . . . . . . . . . . . . . . .A — 11
"Teleservice" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11
Utilization Via Teleservice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11
GTC Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11
GTC + Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 11
Appendix C
Link to an IBM AS/400® Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . .A — 13
Connect and Configure the AS400 Link . . . . . . . . . . . . . . . . . . . . . . . . .A — 13
MGE Warranty & Proprietary Rights for Three Phase Products
MGE Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—1
Proprietary Rights Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—1
MGE Customer Care Center
Technical Support and Product Services . . . . . . . . . . . . . . . . . . . . . . . . .W—3
Who To Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—3
Scheduling Field Service Engineer Support . . . . . . . . . . . . . . . . . . . . . . .W—3
Return Policy for Repair (RMA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W—3
Glossary
Term and Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G — 1
Reorder Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RO—1
Galaxy PWUPS 100 to 225kVA
Contentsc iv 86-133060-00 A00
Page 11
Installation and User Manual
Figures
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1: Galaxy PW™ System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 2
1-2: Galaxy PW™ Single UPS System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
1-3: Fuse Curve Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
2-1: Handling Cabinet From the Bottom or Rolling on Bars. . . . . . . . . . . . . . .2 — 3
2-2: Dismantling Leg Supports and Attaching Spacers to Cabinet. . . . . . . . .2 — 4
2-3: Layout of the Major Cabinet Components. . . . . . . . . . . . . . . . . . . . . . . .2 — 5
2-4: Component Layout in a Battery Cabinet or a
Battery Circuit-breaker Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 6
2-5: 350A and 1200A Maintenance Bypass Cabinet. . . . . . . . . . . . . . . . . . . .2 — 7
2-6: Control Panel Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8
2-7: Single UPS Unit Start-up Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 10
2-9: Parallel UPS Unit for Increased Output. . . . . . . . . . . . . . . . . . . . . . . . . .2 — 11
3-1: Galaxy PW™ Single UPS Unit Wire Diagram. . . . . . . . . . . . . . . . . . . . . .3 — 2
3-2: Single UPS Unit Power Circuit Connections. . . . . . . . . . . . . . . . . . . . . . .3 — 2
3-3: Parallel UPS Unit Power Circuit Diagram. . . . . . . . . . . . . . . . . . . . . . . . .3 — 3
3-4: Connections Between UPOZ Boards. . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4
3-5: Two Parallel UPS Units Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
3-6: Three Parallel UPS Units Connections. . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
3-7: Four Parallel UPS Units Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
3-8: Standard Auxiliary Circuits Connections. . . . . . . . . . . . . . . . . . . . . . . . . .3 — 9
3-9: Installing the "Temperature Monitor" in a Battery Cabinet. . . . . . . . . . .3 — 10
3-10: Temperature Monitor" Base. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 11
3-11: Single UPS Unit Connection of the Battery "Temperature Monitor". . . .3 — 12
3-12: Connection of the Battery "Temperature Monitor."
(In Parallel UPS Units with Batteries in Same Room.) . . . . . . . . . . . . .3 — 13
3-13: Connection to the "Media Contacts 11" Board. . . . . . . . . . . . . . . . . . . .3 — 14
4-1: Control Panel and Circuit Breaker Diagram. . . . . . . . . . . . . . . . . . . . . . .4 — 1
4-2: Single UPS Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2
4-3: Parallel UPS Two Parallel Connected UPS Units. . . . . . . . . . . . . . . . . . .4 — 2
4-4: Parallel UPS Two to Four Parallel Connected UPS Units. . . . . . . . . . . .4 — 2
4-5: Normal Operation Indicator Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 3
4-6: Normal AC Source Indicator Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 4
4-7: Normal Operation Mode Indicator Diagram. . . . . . . . . . . . . . . . . . . . . . .4 — 5
4-8: Battery Charge Cycle Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 6
4-9: Installation with an Engine Generator Set. . . . . . . . . . . . . . . . . . . . . . . . .4 — 6
4-10: Operating in On-line Mode Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 7
4-11: Overload Curve Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 9
4-12: Measurement System Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 11
4-13: Display of Alarm Messages.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 16
5-1: UPS Isolation Diagram for Normal AC Bypass Source. . . . . . . . . . . . . . .5 — 3
5-2: Panel Procedures for UPS Isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 3
5-3: Start-up After Isolation Procedure is Completed. . . . . . . . . . . . . . . . . . . .5 — 3
5-4: Isolate All UPS’s Procedures Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 4
Contents c v86-133060-00 A00
Page 12
Figures (continued)
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
5-5: Start-up Procedure After Isolation Diagram. . . . . . . . . . . . . . . . . . . . . . .5 — 5
5-6: Redundancy for Increased Output Diagram. . . . . . . . . . . . . . . . . . . . . . .5 — 5
5-7: MAC Address Sticker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 7
Tables
table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1: Electrical Parameters for Normal AC Source. . . . . . . . . . . . . . . . . . . . . .1 — 6
1-2: Electrical Parameters for Bypass AC Source. . . . . . . . . . . . . . . . . . . . . .1 — 7
1-2A: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
1-3: Rating Recommended for Devices Upstream of Single UPS. . . . . . . . . .1 — 8
1-4: Rating Recommended for Devices Downstream of Single UPS. . . . . . .1 — 8
1-5: Parameters for Bypass AC Source and
Load Cables for a Parallel UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9
Galaxy PWUPS 100 to 225kVA
Contentsc vi 86-133060-00 A00
Page 13
Introduction
1.0 Scope
Introduction is a general description and overview of Galaxy PW™ 100 to 225kVA components, its intended use, environment, and applicable specifications, power input/output requirements, and system characteristics for different system configurations.
1.1 Section Descriptions
1 Introduction
Introduction is a general description and overview of the Galaxy PW™ 100 to 225kVAcomponents, its intended use, environment, and applicable specifications, power input/output requirements, and system characteristics for different system configurations.
2 System Setup
System Setup describes receiving and handling of the Galaxy PW™ 100 to 225kVA, a description of major compo­nents, the battery cabinet, and definition of the control panel indicators. Includes electrical, mechanical and environmental specifications.
3 Installation
Installation guides the User through single and parallel UPS unit power cable connections, hot swap options, connections between cabinets, communication card connections, battery temperature monitoring. Wire diagrams are included for configuring the unit to specifications.
4 Operation
Operation describes the theory of operation, start-up for single and parallel units, modes of operation, normal speci­fications for operating the Galaxy PW™ 100 to 225kVA. The User procedures include display messages, measurement systems, alarms, battery cabinet, and log time-stamping procedures.
5 Maintenance
Maintenance procedures for isolation for maintenance, startup for single and parallel units, functional and visual checks, software configurations, and testing scenarios.
Appendices
A List of primary and secondary display messages.
B Electrical supervision options. (Teleservice and GTC Cards)
C Instructions of the optional IBM AS400 up link process.
1 — 186-133060-00 A00 Introduction
Page 14
1.2 General Description
The cabinets are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged through the roof, which means the cabinets can be positioned against the back wall.
Connections are made through the bottom. (Connections through the top are an available option.)
The connection cables may be run in three ways:
In a trench running under the cabinets.
Under a false floor.
On the floor under the cabinets, in the free space equal to the height of the feet; in this case the cables
should be run side by side to avoid blocking the flow of air for ventilation.
The cables for connections are between:
The battery and UPS cabinets (power and control cables).
The bypass AC-source transformer in an auxiliary cabinet and the UPS cabinet.
Only the wires for the inter cabinet control connections between parallel-connected UPS units are supplied.
The other power cables for connections between cabinets are not supplied.
Figure 1-1: Galaxy PW™ System.
Galaxy PWUPS 100 to 225kVA
Introduction1 — 2 86-133060-00 A00
Page 15
Installation and User Manual
1.3 System Major Power Components
Rectifier/charger module (A) Converts 3-phase AC power from the normal AC source supply (1) into DC power
for the normal inverter input and float charges or recharges the battery.
Battery unit (D) Provides backup power for the inverter in the event of a voltage drop or a normal AC
source failure.
Inverter module (B) Converts the DC power supplied by the rectifier/charger module or the battery unit
into 3-phase AC power for the load.
Static bypass module (C) Ensures the instantaneous transfer of the load to the bypass AC source input in the
event of an inverter shutdown (initiated by the user or by a protective device) or a sudden overload.
Maintenance Bypass Isolates the UPS for maintenance and transfers the load to bypass AC source input
without interrupting the supply of power. The maintenance bypass is made up of three manual switches (Q3BP, Q4S and Q5N).
External Bypass Option for parallel UPSs and Hot-Swapping.
Q5N: Isolation of the inverters of all the parallel UPS systems from the load.
Q3BP: Bypass for maintenance.
The normal AC input and the bypass AC input have different functions and, depending on the installation, may be protected differently upstream and/or come from different sources.
When increased power is required, several Galaxy PW™ units may be connected in parallel (up to four, refer to section 4.0). In this configuration, an "isolation" function is added for the UPS system as a whole for maintenance purposes, without interrupting the supply of power to the load.
Introduction 1 — 386-133060-00 A00
Page 16
1.4 Different Types of Galaxy PW™ Systems
1.4.1 Single UPS System
Figure 1-2: Galaxy PW™ Single UPS System.
Note: *The Fuse is to protect against catastrophic rectifier/inverter semiconductor failure.
1.4.2 Parallel UPS System
Parallel UPSs can be utilized when increased power is required (two to four parallel units), or an external bypass must be added.
CAUTION PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-
nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is open, each UPS control panel display will show a message “LOAD PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the critical load is not protected because it is supplied by the maintenance bypass power.
Legend: Q1 (Molded CB NA): Isolation of
the rectifier/charger (A) from the normal AC source (1); rectifier/charger (A) start-up.
QF1 (circuit breaker): Battery (D)
protection and isolation.
Q5N (switch): Isolation of the UPS
(B) from the load.
Q4S (switch): Isolation of the static
bypass (C) from the bypass AC source (2).
Q3BP (switch): Bypass switch for
maintenance.
FUE (fuses): Protection of the
rectifier/charger (A) from the normal AC source.
FUS (fuses): Protection of the
inverter (B) from the load. Switch Q3BP is lock on open position on parallel UPS systems constituted to increase available power.
maintenance bypass:
Q3BP
inverter (B):
DC to AC power
isolation:
Q4S
isolation and protection:
Q5N
rectifier/ charger (A):
AC to DC power
QF1: isolation and protection
normal AC input
load
battery (D):
backup power
static bypass (C):
bypass AC input
Q1
isolation and protection
(1)
(2)
harmonic fliter
*FUSE
*FUSE
Galaxy PWUPS 100 to 225kVA
Introduction1 — 4 86-133060-00 A00
Page 17
1.5 System Specifications
1.5.1 Electrical Characteristics
Installation and User Manual
Introduction 1 — 586-133060-00 A00
UPS power rating in kVA 100 130 150 180 200 225 Normal AC input
number of conductors 3 phases rated voltage and tolerances 480 V ± 10% (adjustable to ± 15%) rated frequency and tolerances 60 Hz / ± 10% THDI < 14% < 11% < 10% < 8% < 7.6% < 7.5% power factor up to 0.9
Bypass AC input
number of conductors 3 phases 3 phases + neutral rated voltage and tolerances 480 V / ± 10% rated frequency and tolerances 60 Hz / ± 10%
Load
number of conductors 3 phases 3 phases + neutral Ph/Ph voltages 480 V Ph/N voltages 277 V voltage fluctuations (Ph/Ph,Ph/N) ± 1% adjustable frequency and tolerances (on battery power) 60 Hz ± 0.05 Hz synchronization with bypass ± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz) transient voltage variation for 0 to 100% load step change
± 2% (with battery), +2%/-6% (without battery) permissible overloads 150% for 1 minute, 125% for 10 minutes Isc Ph/Ph (% of I rated) 4.7 3.6 3.2 2.6 2.4 2.1 Isc Ph/N (% of I rated) 7.4 5.7 5 4.1 3.7 3.3 THDU Ph/Ph and Ph/N for linear load < 1.5% Ph/Ph, < 2% Ph/N THDU Ph/Ph and Ph/N for non-linear load < 2% Ph/Ph, < 3% Ph/N
(at 80% of Pn)
Battery
voltage floating 512V to 561V standard battery type gas-recombination sealed lead-acid battery
UPS characteristics
active power (kW) 100 130 150 180 200 202.5* efficiency at 50% load (%) 90.5 91 92 92.5 92.5 93 (values ± 1%) efficiency at 100% load (%) 92.5 93 93 93 93.5 93.5 (values ± 1%) heat losses (1) in KW 8.1 9.8 11.3 13.5 13.9 14.1
in cal./s 1940 2350 2700 3240 3340 3380
storage temperature range ºF (ºC) -13 to 158 (-25 to 70) dry heat — unit without battery
-4 to 113 (-20 to 45) — unit with battery operating temperature range ºF (ºC) 32 to 95, 104 for 8 hours (0 to 35, 40 for 8 hours) relative humidity 95% maximum non condensing at ambient temperature maximum operating altitude without derating, FT(m)
< 3280 (< 1000) noise level (dBA) 62 63 64 65 67 68 dimensions, in. (mm) width 47.8 (1215)
depth 33 (840)
height 74.8 ± .39 (1900 ± 10) weight lbs (kg) 3050 (1388) standards design NFPA / NEC / NEMA / OSMA
product and safety UL 1778 - ULC electromagnetic compatibility FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41
(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system. * pf of 225kVA unit has 0.9 and remaining units have 1.0.
Page 18
1.6 Electrical Parameters for Selecting Protective Devices
1.6.1 Normal AC Source
The parameters given in Table 1-1 can be used to determine the required rating of the upstream protective circuit breaker on the normal AC input for one single-UPS or parallel-UPS unit.
Normal and Bypass AC Input:
number of conductors 3 phases
rated voltage and tolerances 480 V ± 10% (adjustable to ± 15%)
rated frequency and tolerances 60 Hz / ± 10%
IMPORTANT It is essential to choose the type of circuit breaker according to its breaking
capacity and the prospective short-circuit current at its place of installation. This choice must also be made so as to protect the static-switch semicon­ductors with respect to the maximum permissible currents and ensure discrimination between the UPS output fuses and the downstream protection devices.
Table 1-1: Electrical Parameters for Normal AC Source.
Electrical parameters for the normal AC source
rated current normal AC source UPS rated current In for unit: for 25% for 50% output with battery at start without battery (2) overload (3) overload (3) in kVA of charge cycle (1) 100 166 159 199 239 130 214 205 256 308 150 245 236 295 354 180 295 283 354 425 200 328 316 395 474 225 332 320 400 480
(1) The rated normal AC source currents (In) have been determined for a rated phase-to-phase voltage of 480 V,
a battery with a 10 minute backup time at the beginning of its charge (412 x 1, 2 = 494 Volts) and full rated load with a power factor of 0.9.
(2) The rated normal AC source currents (In) have been determined for float charging voltage and full rated load
with a power factor of 0.9
(3) The normal AC source currents given for an overload of 25% or 50% are maximum values. They have been
determined for a battery with float charging voltage and a load power factor of 0.9. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the values in the overload columns.
Galaxy PWUPS 100 to 225kVA
Introduction1 — 6 86-133060-00 A00
Page 19
Installation and User Manual
1.6.2 Bypass AC Source
The parameters given in Table 1-2 and 1-2A can be used to determine the required rating of the upstream protec­tive circuit breaker on bypass AC input.
NOTE If the installation includes a transformer on the bypass AC input, allow for the
inrush current caused by magnetization of the transformer windings.
Table 1-2: Electrical Parameters for Bypass AC Source.
Electrical parameters for bypass AC source (480 V)
rated UPS current bypass AC source (1) output rated current In for unit: for 25% for 50% in kVA overload overload (3) 100 120 150 180 130 156 205 234 150 180 236 270 180 217 283 325 200 241 316 362 225 271 320 407
(1) The bypass AC source currents have been determined for a rated phase-to-phase voltage of 480 V, a load
power factor of 0.9 and for full rated load as well as overloads of 25% or 50%. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the data in the overload columns. See table and chart below.
Table 1-2A:
UPS output maximum permissible current in kVA
100 50 In for 20 ms 130 38 In for 20 ms 150 33 In for 20 ms 180 27 In for 20 ms 200 25 In for 20 ms 225 22 In for 20 ms
Figure 1-3: Fuse Curve Chart.
10
4
t(s)
I(A)
10
3
10
2
10
1
1
10-
1
10-
4
10-
3
10-
2
10
2
10
3
10
4
Introduction 1 — 786-133060-00 A00
Page 20
1.7 Recommended Protection
1.7.1 Protection Upstream of Galaxy PW™
The information provided here is purely indicative, for a single UPS unit. Check that all the criteria mentioned in the previous section are taken into account (short-circuit current and protection of the static switch semiconductors on the bypass AC input).
Table 1-3: Rating Recommended for Devices Upstream of Single UPS.
Ratings
rated UPS CB on normal CB on bypass output AC input AC input in kVA circuit breaker control unit circuit breaker control unit
100 125A 125A 125A 125A 130 160A 160A 160A 160A 150 250A 200A 250A 200A 180 250A 250A 250A 250A 200 400A 400A 400A 400A 225 400A 400A 400A 400A
1.7.2 Protection Downstream of Galaxy PW™
These protection devices ensure discrimination for each of the Galaxy PW™ output circuits. If the recommended downstream protection is not installed and a short-circuit occurs, the result may be a break longer than 20-min on all the other output circuits.
Table 1-4: Rating Recommended for Devices Downstream of Single UPS.
Ratings
rated UPS downstream circuit output breaker(s) in kVA circuit breaker control unit
100 to 225kVA 100A 63A curve C
100A curve B
Galaxy PWUPS 100 to 225kVA
Introduction1 — 8 86-133060-00 A00
Page 21
Installation and User Manual
1.8 Parallel Connected UPS Units
For installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected UPS units, one being redundant, only 2 UPS units are used to determine bypass AC source and load currents and cable cross-sections).
Table 1-5 serves as an example for a parallel connected installation comprising up to four UPS units.
Table 1-5: Parameters for Bypass AC Source and Load Cables for a Parallel UPS.
Parameters
rated unit number of total UPS bypass AC output parallel- rated output source or load in kVA connected in kVA line current
units in Amps
100 2 200 240
3 300 360 4 400 480
130 2 260 312
3 390 468 4 520 624
150 2 300 360
3 450 540 4 600 720
180 2 360 434
3 540 651 4 720 868
200 2 400 482
3 600 723 4 800 964
225 2 450 542
3 675 813 4 900 1084
Introduction 1 — 986-133060-00 A00
Page 22
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
Introduction1 — 10 86-133060-00 A00
Page 23
System Setup
2.0 Scope
System Setup describes receiving and handling of the Galaxy PW™ 100 to 225kVA, a description of major compo­nents, the battery cabinet, and definition of the control panel indicators, which includes electrical, mechanical and environmental specifications.
MGE also recommends obtaining an MGE field service engineer for final installation and basic startup for single and parallel units.
CAUTION Scheduling of the MGE Field Service Engineers typically should be done 7 to
10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE toll free telephone number at
1-800-438-7373 for assistance.
The MGE Field Service Engineers will
insure a
quick installation for the initial safe startup and configuration of your Galaxy PW™.
Final installation and start-up should be completed by a qualified MGE Field Service Engineer.
2.0.1 First steps by an on-site qualified Technical Engineer
Step 1. Unpack and position the unit.
Step 2. Connect the main (utility) power.
Step 3. Connect the power circuits.
2.0.2 Final steps by MGE Field Service Engineer
Step 4. Call MGE and wait for the MGE Field Service Engineer to complete the installation.
Step 5. The MGE Field Service Engineer finalizes installation and the startup process.
Optional: Procedure for temporary power prior to the final startup.
2.0.3 Required Equipment and Tools
The following equipment and tools are recommended for on-site installation:
Digital volt meter (DVM)
1/8 inch slotted screwdriver
Pallet jack/forklift
Conduit installation tools
Nut driver set
2 — 186-133060-00 A00 System Setup
Page 24
2.1 Receiving
On delivery, check that the equipment has not been damaged in transport (declare any damage to the carrier in accordance with customary claim procedures).
Also check that the characteristics noted in the test report for the equipment correspond to those specified on the order form. In the event of a non-conforming item, quote the delivery note reference number when making your claim.
2.1.1 Handling
The cabinets are delivered on pallets, equipped with a shock absorbing system. Ideally, the equipment should be unpacked just before installation (see "unpacking" section below). Cabinet weights and dimensions are specified on the packaging. Cabinets may be handled in one of the following ways (see Figure 2-1):
Rolling on Bars (B)
Do not mount the foot pads, but place the cabinet on the rollers (at least three). The cabinet may be pulled on rollers using a sling positioned horizontally. This technique should only be used when absolutely necessary (narrow doorway or corridor, preventing the use of a fork-lift or pallet-mover).
From the Bottom (A)
The cabinets can be moved from the front or the rear (715 mm wide cabinets) using a pallet truck or fork-lift truck, or on the 4 surfaces (1015 mm and 1215 mm wide cabinets) using a fork-lift truck.
Fork tunnel height: 140 ±10 mm.
Fork opening: 560, 650 or 700 mm according to cabinets width.
The 715 mm wide cabinets are designed to pass through 715 mm wide openings, and the other cabinets are designed to pass through 825 mm wide openings. For narrow openings, (follow the instructions below) cabinets are normally 825 mm deep.
This depth can be reduced to:
817 mm by removing rear panels.
805 mm by removing doors.
800 mm by removing doors and door hinges.
unpack the cabinet, refer to section 2.2 ‘Unpacking’, page 4. The cabinet can then be handled by lifting machines on all surfaces after the pallets have been dismantled by removing the rear panels, and remove the fixing screws using a "torx" screwdriver.
Removing the doors:
1. Open the door(s).
2. Disconnect the door earth connection from the frame.
3. For cabinets fitted with a control panel, carefully disconnect the ribbon cables from the panel circuit boards located on the inside of the door.
4. Knock out the hinge pins from below.
5. Remove the door(s).
Removing the door hinges:
1. Remove the screws holding the side panels to the hinges.
2. Remove the central screw holding the hinge.
Galaxy PWUPS 100 to 225kVA
System Setup2 — 2 86-133060-00 A00
Page 25
Installation and User Manual
Figure 2-1: Handling Cabinet From the Bottom or Rolling on Bars.
2.1.2 Storage
The equipment must be stored in a dry and well-aired location, sheltered from rain, water sprays or splashes and all chemical agents. Storage in original packing is recommended, since this packaging is designed to provide maximum protection during storage and handling. If the unit must be unpacked prior to final installation, cover the equipment with a shroud providing protection against dust, debris, or paint.
Please dispose of the packaging in accordance with the applicable legislation.
IMPORTANT Transport: the temperatures must remain within the -30° to +50°C range and the
duration should not exceed 30 days.
Storage: the battery is of the sealed lead-acid or vented lead-acid type and should not be stored for more than six months at 20°C without recharging for batteries that are initially fully charged (for partially charged batteries, the storage time should be reduced). After the recommended maximum storage time, the battery must be charged, requiring partial start-up of the equipment (rectifier-charger).
The battery cells can be stored at a temperature between -20°C and +45°C if delivered in their initial packing.
The ideal battery storage temperature is between 15° and 25°C (higher temperatures result in reduced storage life or downgraded technical characteristics). If higher temperatures cannot be avoided during transport or storage, please consult us.
System Setup 2 — 386-133060-00 A00
A
From Bottom
B
On Rollers
Page 26
2.2 Unpacking
1. Remove the packing box and the document holder on the top of the cabinet; raise the cabinet.
2. Dismantle the blocks fixed beneath the cabinet by M12 screws, see Figure 2-2 (A or B), according to the width of the cabinet);
3. Dismantle the 4 M12 screws screwed on the 4 leg supports (C).
4. Withdraw the "hexagonal spacer + leg" assemblies delivered inside the document holder.
5. Screw the spacers onto the cabinet frame (C).
6. Lock these spacers in position using a 24 mm flat wrench, and fit the cabinet on its legs.
7. Adjust cabinet height and verticality by screwing or unscrewing the legs using a 13 mm flat wrench.
Figure 2-2: Dismantling Leg Supports and Attaching Spacers to Cabinet.
Galaxy PWUPS 100 to 225kVA
System Setup2 — 4 86-133060-00 A00
A B C
Page 27
Installation and User Manual
2.3 Galaxy PW™ Cabinet Major Components
Legend:
AA: cross-sectional view of the cabinet,
B: front view of the cabinet,
C: front panel,
D: rear panel,
1: normal AC input connection,
2: bypass AC input connection,
E: load connection,
F: battery connection,
G: air inlets,
H: air outlets,
I: cable exit through the bottom,
J: trough, if applicable,
K: rectifier/charger module,
L: inverter module,
M: static-bypass module,
Figure 2-3: Layout of the Major Cabinet Components.
System Setup 2 — 586-133060-00 A00
H
G
G
H
F
E
1
P
2
G
Y
Q1
Q4S
Q5NQ3BP
L1
L2
L3
L1L2L3
L1
L2
L3
GND
N
M
Q Z
S
L
A
B
M
N 3
T
W
U
R
A
X
J
I
1, 2, E,F
D
C
AA
K
O
V
N: rack containing electronic boards,
O: Media Contacts 11 board,
P: slot for communications boards,
Q: FUE input fuses,
R: FUS output fuses,
S: RALI board,
T: UPOZ /UCOZ board,
U: MUSI board,
V: backfeed protection (contactor),
W: control wire routing,
X: fuses for overvoltage protection RC circuit on bypass,
Y: control-wire connection (auxiliary "Media Contacts 11" circuits and
communications options).
z: EP0I Board
3: VETI Board
Page 28
2.4 Battery Cabinet
Legend:
AA: cross-sectional view of the cabinet,
B: front view of the cabinet,
C: front panel,
D: rear panel,
E: cable ties to duckboard shelf,
F: cable exit through the bottom,
G: trough, if applicable,
H: connection of exposed conductive parts to duckboard shelf,
I: cable exit to battery connection point in UPS cabinet,
J: cable exit to an additional battery cabinet, if applicable,
K: cable ties to duckboard shelf,
L: fixture locking circuit breaker "QF1" in the open position.
Figure 2-4: Component Layout in a Battery Cabinet or a Battery Circuit-breaker Enclosure.
Galaxy PWUPS 100 to 225kVA
System Setup2 — 6 86-133060-00 A00
XR1
QF1
+
+
D
C
A
A
LK
I
J
F
G
E
H
BAA
Page 29
Installation and User Manual
2 — 786-133060-00 A00
2.5 Remote External Maintenance Bypass Cabinet
350A and 1200A (See Figure 2-5)
Refer to “Installation Instructions” 90-133056-01 for detailed information about 350A cabinet.
Refer to Installation drawing 90-133077-00 for detailed information about 1200A cabinet.
If your installation is custom designed, a separate installation drawing may apply to your system.
All external wiring are provided and installed by the user.
Transfer instructions can be found in front of the cabinet including the proper operation of the kick key interlock.
Figure 2-5: 350A and 1200A Maintenance Bypass Cabinet.
1200A
NEURTRAL (NOT SHOWN)
CRITICAL LOAD
DISPLAY METER
T1
MAINTENANCE
BYPASS
GROUND
REMOVABLE
PANELS
FOR POWER
CONDUIT ENTRY
SEISMIC
MOUNTING
CUTOUTS
SEISMIC HOLE
LOCATION
FORKLIFT OPENINGS
(LEFT & RIGHT SIDE TYPICAL)
MULTI CIRCUIT MONITOR BOARD
MULTI CIRCUIT MONITOR BOARD
F1, F2 F3 TO F8
TRANSFER INITIATE (SI)
ELECTRIC INTERLOCK (KA)
TB2
CB2
CB1
UPS OUTPUT
TB1
CONTROL WIRE ROUTING
REMOVABLE PANEL FOR CONTROL AND POWER CONDUIT ENTRY
F1, F2
TRANSFER INITIATE (SI)
ELECTRIC INTERLOCK (KA)
350A
CRITICAL LOAD
TB1
MBP
TERMINALS
NEUTRAL
CB2 UPS ISOLATION
CB1 MAINTENANCE BYPASS
UPS TERMINALS
GROUND
System Setup
Page 30
2.6 General Instructions for Screens
To display the desired information and enter commands using the ▲, ▼ and ø keys:
1. Press the key to exit the time-stamping consultation mode and return to the main menu. If no commands are entered for five minutes, the system automatically returns to the normal display mode.
To scroll through the screens displaying information:
1. Press the
and keys to scroll up and down through the screens.
For time-stamped events, the display begins with the last event logged. To access older events, press the
key.
If during consultation, you wish to review more recent events, press the
key.
2.6.1 Control Panel Indicators and Definitions
The control panel on the Galaxy PW™UPS comprises the basic controls and indications required to check the general status of the system. See Figure 2-6.
Located in the upper right part of the cabinet front, the control panel is designed to provide an easy and rapid overview of system status. See Figure 2-6.
Interpretation of symbols is very simple and requires no particular training. The information concerns only the cabinet on which the panel is located. Refer to Appendix A for a complete List of Primary and Secondary display messages.
The panel indicates:
Normal operation (load protected).
Operation with load on battery power.
Abnormal situations (operating problem).
Dangerous situations (load not protected).
Figure 2-6: Control Panel Indicators.
1
2
VAW.Hz
fault
18
17
8
7
643 521
22
2119 20
16
9 10 11 12 13 1514 15
Galaxy PWUPS 100 to 225kVA
System Setup2 — 8 86-133060-00 A00
Page 31
Installation and User Manual
Control Panel Alphanumeric Legend:
1 "Rectifier/charger" light Indicates on/off and charging activity.
2 "Battery light" Indicates battery status.
3 "Static-bypass" light Indicates static bypass tolerance status.
4 "Inverter" light Indicates inverter on/off status.
5 "Load" light Indicates Load supplied and not supplied.
6 Buzzer The buzzer sounds in load operating situations.
7 "Inverter ON" button This button is used to start the inverter locally.
8 "Inverter OFF" button This button turns the inverter off locally.
9 -10 Keys These keys are used to select commands in the main menu and access the secondary
messages.
11 Key This key is used to validate the user’s choice.
12
øø
Key This key is used to access the main menu: display language, display-contrast setting,
sound level of the buzzer, lamp test, date and time settings, inverse-video and event log.
13 "V" Key This key is used to access voltage measurements.
14 "A" Key This key is used to access current measurements.
15 "W.Hz" Key This key is used to access other measurements:
16 "Anomaly" light This indicator light indicates the presence of anomalies.
17
Key This key is used to access the primary messages.
18
ıı
"Battery" Key This key is used to access battery measurements:
19 "Forced-transfer" This key is used to voluntarily transfer the load to the inverter or from the inverter to the
static bypass (return transfer).
20 "Alarm reset" This key is used to reset stored alarms. The system accepts resetting only when alarms
have been cleared.
21 "Buzzer reset" This key is used to stop the buzzer. However, new alarms set the buzzer off again.
22 Display The display continuously indicates the system operating status.
System Setup 2 — 986-133060-00 A00
Page 32
2.7 System Start-up
2.7.1 Single UPS unit or Redundant Parallel UPS
Proceed in the following order: See Figure 2-7.
1. Close the upstream switches supplying normal and bypass AC source power (on the LV switchboard).
2. Close normal AC input switch Q1. The system powers up:
- the rectifier/charger automatically starts.
- green light 1 on the control panel goes on.
- light 2 turns red.
3. Close bypass AC input switch Q4S:
- green lights 3 and 5 on the control panel go on.
4. Close inverter output switch Q5N.
5. Close battery circuit breaker QF1:
- light 2 goes off.
6. Open maintenance bypass switch Q3BP.
7. Press the "inverter on" button 7 on the control panel:
- the green "inverter" light 4 flashes.
- the inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the inverter if the on-line mode is selected.
- the green "static-bypass" light 3 goes off.
- the green "inverter" light 4 shines for on-line mode.
Figure 2-7: Single UPS Unit Start-up Diagram.
Q5NQ1 Q4S
QF1
0
I
3
1
2
1
0
1
0
1
0
1
0
1
0
Q3BP
1
0
1
0
1
0
1
0
1
0
1
0
1
0
5
4
6
1
0
1
0
1
0
1
0
7
8
1
2
8
7
643 521
22
Galaxy PWUPS 100 to 225kVA
System Setup2 — 10 86-133060-00 A00
Page 33
Installation and User Manual
2.8 Parallel UPS Unit for Increased Output
Proceed in the following order: See Figure 2-8.
1. Check that all load devices are off or that the load is disconnected.
2. Close the upstream switch supplying normal AC source power (on the LV switchboard).
3. Close the normal AC input circuit breakers Q1 on the UPS units. The system powers up:
- the rectifier/chargers automatically start,
- the green "rectifier/charger" lights 1 in the control panels go on,
- lights 2 turn red.
4. Close the battery circuit breakers QF1.
- lights 2 go off.
- green lights 3 and 5 on the control panels go on.
5. Close Main 2 input switch Q4S for the units.
6. Close output switches Q5N for the inverters and in the external bypass unit.
7. Open maintenance bypass switch Q3BP in the external bypass unit.
8. Press the "inverter on" button 7 on each control panel:
- the green "inverter" lights 4 flash.
9. When a sufficient number of inverters are ready, the inverter-output contactors close:
- the green "inverter" lights 4 shine permanently green.
- the "static-bypass" lights 3 go off.
Figure 2-8: Parallel UPS Unit for Increased Output.
3
1
2
1
0
1
0
7
Q5N
1
0
Q4S
Q1
Q5N
1
0
Q4S
Q1
QF1
0
I
1
0
1
0
Q1
1
0
1
0
1
0
7
8
1
2
8
7
643 521
22
5 6 7
4
Q5N
Q3BP
external bypass
1
0
1
0
1
0
1
0
System Setup 2 — 1186-133060-00 A00
Page 34
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
2 — 12 86-133060-00 A00
Page 35
3 — 186-133060-00 A00
Installation
3.0 Scope
Installation guides the User through single and parallel UPS unit power cable connections, hot swap options, connections between cabinets, communication card connections, battery ‘temperature monitoring’ installation. Wire diagrams are included for configuring the unit to specifications.
MGE recommends obtaining an MGE field service engineer for final installation and basic startup for single and parallel units. Final installation and start-up should be completed and performed by a qualified MGE Field
Service Engineer.
3.1 Optional Communications Card Installation
Three slots are available on the "Media Contacts 11" board for optional communications. See the position of these slots marked "P" in Figure 2-3, page 2—5.
Installation of Boards setup notes:
Boards may be installed with the UPS on, without removing the protective covers.
Boards must be pushed to the end of the slots to ensure correct installation.
Board front plates must be screwed to the protective "Media Contacts 11" board cover.
Wire routing holes are provided in the support for the "Media Contacts 11" board for tying down the wires;
The control wires must then be routed through the cableway marked "W" in figure 2-3, page 2—5.
3.2 Notes on Connection of Power Circuits
Open the doors and remove the lower terminal shields (secured by screws to the cabinet chassis) of the
UPS cabinets, connect the power cables, each cabinet must be grounded.
All the cabinets must be interconnected for equipotential bonding, forming a mesh which is itself connect-
ed to the building structure and earthing electrode.
The connection drawings hereafter show the cabinets with doors open and terminal shields removed.
CAUTION Before making connections, check that switches Q1, Q4S, Q3BP, Q5N and QF1 are
in the "open" position.
IMPORTANT For parallel UPS with an external bypass unit, the power connections between
each UPS cabinet and the external bypass unit must imperatively be of the same length. Outside the cabinets, separate the auxiliary wiring from the power cables.
Installation
Page 36
3.3 Power-Circuit Wiring Diagrams
The single UPS wire diagram is for typical UPS installations shown in Figure 3-1. The heavy lines represent the cables that must be connected (F), refer to section 3.5 ‘Connections Between Cabinets’ for more detail on cables.
Figure 3-1: Galaxy PW™ Single UPS Unit Wire Diagram.
Legend:
1: Normal AC source,
2: Bypass AC source,
A: Rectifier/charger module,
B: Inverter module,
C: Static-bypass module,
D: Battery cabinet next to the
Galaxy PW™ UPS cabinet,
E: Additional battery cabinets,
F: The equipotential-bonding
connection between cabinets.
3.4 Hot Swap Options
The external bypass may be used to construct a bypass outside the UPS, thus making it possible to shutdown the UPS for maintenance purposes.
The option may be used for single UPS units and redundant parallel UPS. For the power-circuit connections of a single UPS unit see Figure 3-2, for the power-circuit connections of parallel UPS see Figure 3-3.
Power cables for UPS-to-bypass connections are not supplied.
Figure 3-2: Single UPS Unit Power Circuit Connections.
Legend:
1: Normal AC source.
2: Bypass AC source.
A: Rectifier/charger module.
B: Inverter module.
C: Static-bypass module.
D: Battery cabinet next to the
Galaxy PW™ UPS cabinet.
E: Additional battery cabinets.
F: The equipotential-bonding
connection between cabinets.
Galaxy PWUPS 100 to 225kVA
Installation3 — 2 86-133060-00 A00
C
B
A
Q4S
Q1 Q5N
Galaxy PW
Q3BP
2
1
D
+
+
E
F
QF1
F
Q4S
2
Q3BP
Q5N
( )
( )
( )
( )
2
1
C
B
A
Q4S
D
+
+
E
F
QF1
Q1 Q5N
Galaxy PW
F
Q3BP
( )
( )
Page 37
Installation and User Manual
Figure 3-3: Parallel UPS Unit Power Circuit Diagram.
Legend:
1: Normal AC source,
2: Bypass AC source,
A: Rectifier/charger module,
B: Inverter module,
C: Static-bypass module,
D: Battery cabinet next to the
Galaxy PW™ UPS cabinet,
E: Additional battery cabinets,
F: The equipotential-bonding
connection between cabinets.
Installation 3 — 386-133060-00 A00
Galaxy PW
2
1
D
+
+
E
F
QF1
F
2
1
D
+
+
E
F
QF1
F
Galaxy PW
2
Q3BP
Q5N
2
C
B
A
Q4S
Q1 Q5N
( )
( )
C
B
A
Q4S
Q1 Q5N
( )
( )
( )
Page 38
3.5 Connections Between Cabinets
These connections are made on the UPOZ board (marked T) and MUSI board (marked U). See Figure 2-3, page 2—5.
3.5.1 Connections Between UPOZ Boards
These connections are made using the cables (A) supplied, see Figure 3-4.
The purpose of the connection is to make a loop. Connector XM137 on the UPOZ board of one UPS unit must be connected to connector XM136 on the UPOZ board of the next UPS unit and so on until the first board is returned to origin.
Figure 3-4: Connections Between UPOZ Boards.
3.5.2 Connections Between UPS Cabinets and the Remote External Bypass
Refer to the installation drawing included with the Maintenance Bypass Cabinet for control and power connections. These connections are provided and installed by the user.
'UPOZ'
Galaxy PWTM 1
'UPOZ'
Galaxy PWTM 2
'UPOZ'
Galaxy PWTM 3
XM137
XM138
XM137
XM138
XM137
XM138
A
Galaxy PWUPS 100 to 225kVA
Installation3 — 4 86-133060-00 A00
Page 39
Installation and User Manual
3.5.3 Connections Between MUSI Boards
These connections are made using the special cables (A) supplied, see Figures 3-5.
1. Connectors XM5, XM6 and XM7 on the MUSI board are used to transmit signals.
2. Connectors XM10, XM11 and XM12 on the MUSI board are used to receive signals.
3. Connector XM5 is associated with connector XM10 for communication with one UPS unit; similarly, XM6 is associated with connector XM11 for communication with a second UPS unit and XM7 is associated with connector XM12 for communication with a third UPS unit.
For connection with two parallel UPS units, see Figure 3-5.
For connection with three parallel UPS units, see Figure 3-6, page 3—6.
For connection with four parallel UPS units, see Figure 3-7, page 3—6.
IMPORTANT Outside the cabinets, group the "UPOZ" inter-board and "MUSI" inter-board
connections with the inter-cabinet auxiliary connections, and separate this assembly using power cables.
Figure 3-5: Two Parallel UPS Units Connections.
'MUSI'
Galaxy PW
TM 1
'MUSI'
Galaxy PW
TM 2
A
XM10
XM11
XM12
XM5
XM6
XM7
XM10
XM11
XM12
XM5
XM6
XM7
Installation 3 — 586-133060-00 A00
Page 40
Figure 3-6: Three Parallel UPS Units Connections.
Figure 3-7: Four Parallel UPS Units Connections.
'MUSI'
Galaxy PW
TM 1
'MUSI'
Galaxy PW
TM 2
A
XM5
XM6
XM7
XM5
XM6
XM7
'MUSI'
Galaxy PW
TM 3
XM5
XM6
XM7
'MUSI'
Galaxy PW
TM 4
XM5
XM6
XM7
XM10
XM11
XM12
XM10
XM11
XM12
XM10
XM11
XM12
XM10
XM11
XM12
'MUSI'
Galaxy PW
TM 1
'MUSI'
Galaxy PW
TM 2
A
XM5
XM6
XM7
XM5
XM6
XM7
'MUSI'
Galaxy PWTM 3
XM5
XM6
XM7
XM10
XM11
XM12
XM10
XM11
XM12
XM10
XM11
XM12
Galaxy PWUPS 100 to 225kVA
Installation3 — 6 86-133060-00 A00
Page 41
Installation and User Manual
3.6 Environmental Signal of the Media Contacts 11 Board
Terminals XR2, XR3, XR4 and XR5 on the "Media Contacts 11" board of each type of unit can be used to receive signals from the operating environment and to transmit signals concerning the operating status of the UPS, see Figure 2-3, page 2—5 for the position of the board, item 1 and 2).
3.6.1 Signal Reception
The signals should be provided by volt-free contacts.
Emergency off: An NC contact causes shutdown of the inverter and the rectifier/charger, opening of
the battery circuit breaker, blocking of the static bypass and activation of a relay contact on the "Media Contacts 11" board.
Battery room ventilation fault: A ‘NO’ contact causes shutdown of the rectifier/charger.
Battery circuit breaker QF1 closed: A ‘NO’ contact prevents inverter start-up if the circuit breaker is open.
Battery temperature: A PC-board, placed near the battery, supplies information on the battery tempera-
ture, thus enabling the rectifier/charger to regulate the battery voltage.
"Auxiliary" signals: Depending on the selected settings, these signals may be used to provoke:
- forced shutdown of the inverter (whatever the status of the bypass AC source),
- protected shutdown of the inverter (load transfer to the bypass AC source).
- limiting of the current drawn by the rectifier/charger (programmable value) when supplied by an engine generator set with an insufficient power rating. The additional power required by the inverter is supplied by the battery which discharges,
- limiting of the battery charge current (programmable value) if the normal AC source is replaced by an engine generator set with an insufficient power rating.
3.6.2 Signal Transmission
An auxiliary 24 V power supply: Isolated and backed up, is used to supply:
- the undervoltage release of the battery circuit breaker(s) QF1.
- the board that measures the temperature in the battery room.
"low battery" warning signal: (Volt-free changeover contact) indicating that battery time is about to run out.
The warning threshold may be personalized.
"load on UPS" signal: (Volt-free changeover contact) indicating that the load is supplied by the
inverter. For a single-UPS unit, one volt-free changeover contact may be used to indicate that the load is supplied by the bypass AC source.
Installation 3 — 786-133060-00 A00
Page 42
"load on battery power" signal: (Volt-free changeover contact) indicating that the inverter is supplied
by the battery in the following cases:
- normal AC source outage or voltage drop.
- rectifier/charger shutdown.
- rectifier/charger current limiting.
This signal, which may be used to initiate process saving and shutdown procedures, is time-delayed 30 seconds to avoid unnecessary operations following micro-breaks.
"Maintenance position" signal: (Volt-free changeover contact) indicating that:
- maintenance bypass switch Q3BP is closed,
- bypass AC source input switch Q4S is open,
- inverter output switch Q5N is open,
- battery circuit breaker QF1 is open.
Signal to open battery
circuit breaker(s) QF1: In the event the "emergency off" button is pressed or to avoid an excessive
battery discharge (lasting more than three times the rated backup time plus two hours).
Repo Contact: (Volt-free changeover contact) used to trip switching devices in the event of an
emergency shutdown.
"General Alarm" information: (Volt-free changeover contact) which includes:
- internal faults.
- information on temperatures outside tolerances in the battery room (optional).
- overload information (> In).
- static-switch ventilation and power-supply faults.
NOTE The maximum breaking capacity of the changeover contacts is 5A at 250V.
Galaxy PWUPS 100 to 225kVA
Installation3 — 8 86-133060-00 A00
Page 43
Installation and User Manual
3.7 "Media Contacts 11" Standard Auxiliary Circuits Connection
Connecting the auxiliary circuits to the three connectors on the "Media Contacts 11" board in the Galaxy PW™ UPS cabinet, see the position of this board, marked "O", see Figure 2-3, page 2—5.
Recommended cable cross-section: 1 mm
2
. The male connectors that fit the female connectors on the board (XR2 to XR5) are supplied. The contacts are volt-free and are shown in the diagram under the following conditions: UPS on, contact at rest. Contact breaking capacity: 250 V, 5 A.
Figure 3-8: Standard Auxiliary Circuits Connections.
Installation 3 — 986-133060-00 A00
Media Contacts 11 Board
12 11 10
9
8
7 6 5 4 3 2 1
10
9
8
7 6 5 4 3 2 1
-12V
-12V
24V CC
-12V
XR3 connector
AC AC AC
power supply
input or output signals:
input or output signals:
emergency shutdown breaker circuit REPO (jumper Y
XR2 connector
harmonic filter
battery cubicle
XA13 terminal block
correction with optional electric boad for measuring battery temperature
temperature
signal
OF1 battery circuit-breaker opening command
harmoni
cs over-temperature fault
battery-room ventilation fault
-12V +12V
QF1 battery
circuit breaker closed
QF1 battery circuit breaker opening command
XA1 terminal block
output signals:
EPO
XR2 XR3 XR4 XR5
12 - - - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1
circuit
thermal measuring of the harmoinc-filter circulator
10
9
8
7 6 5 4 3 2 1
XR4 connector
output signals:
load or battery
10
9
8
7 6 5 4 3 2 1
XR4 connector
low-battery shutdown warning
load or inverter
AC
AC
2 1
2 1
2 1
AC
Optional alarm
free auxilary contact
XR2
XR3
XR4
XR5
XR1
12 - - - - - - - - - -110- - - - - - - - - 1 10- - - - - - - - - 1 10- - - - - - - - - 1
Page 44
3.7.1 Battery Circuit Breaker "QF1" Connection
Connect the cable from connector XR3 (pins 2 to 8) on the "Media Contacts 11" board in the UPS cabinet to connector XR1 in the battery cabinet containing battery circuit breaker QF1.
IMPORTANT
In the case of a complex installation with parallel units, there should be only one emergency shutdown pushbutton and this pushbutton must interrupt all the units. This pushbutton must therefore have as many contacts as there are units in the installation. The emergency shutdown pushbutton turns off the rectifier/ chargers and inverters, opens the battery circuit breakers (QF1), the input circuit breaker (Q1) on the normal source, the backfeed protection contactor (K4S) on the bypass AC source, blocks the static switches and activates a contact on the "Media Contacts 11" board (terminals 1 to 3 on connector XR4).
3.8 Installation of the "Temperature Monitor" in the Battery Cabinet
The "Temperature Monitor" unit is placed inside the battery cabinet housing circuit-breaker QF1. See Figure 3-9.
1. Open the unit cover, and before fixing, break the self-cleaving seal on the base of the unit for insertion of the connecting cable.
2. Fix the unit on the plate using the self-adhesive sticker and a screw (nut and washer combination, diameter 4 mm, length 16 mm, not supplied).
3. Connect and put back the cover. The temperature sensor MUST be placed at the top of the cabinet to work properly.
4. Tie the connecting cable to the cabinet upright so that it does not pull on the unit.
Figure 3-9: Installing the "Temperature Monitor" in a Battery Cabinet.
Battery Cabinet
Temperature Monitor unit
Tie the cable to the cabinet upright
to UPS Cabinet
QF1
Galaxy PWUPS 100 to 225kVA
Installation3 — 10 86-133060-00 A00
Page 45
Installation and User Manual
3.8.1 "Temperature Monitor" installation in a Battery Room
The "Temperature Monitor" should be secured against a wall or any vertical support. See Figure 3-10.
1. Choose a location near the batteries and away from draughts which adversely affect the accuracy of
temperature measurements. Dimensions: 75 x 75 x 21 mm.
2. Use the holes provided in the base plate to screw the unit to the vertical support, unless the connecting cable
runs on the surface, break the knock-out in the unit base plate provided for cable entry. Secure the cable by suitable means so that it does not pull on the unit.
Figure 3-10: Temperature Monitor" Base.
Mounting Hole
Cable Entry
Mounting Hole
Dimensions: 75 x 75 x 21 mm
board
Installation 3 — 1186-133060-00 A00
Page 46
3.8.2 Connection of the Battery "Temperature Monitor"
This unit must be connected to the XR2 connector on the remote indications "Media Contacts 11" board of the UPS cabinets. For the location of the "Media Contacts 11" board, marked "O" see Figure 2-3, page 2—5.
Use a shielded cable made up of 2 twisted telephone pairs with a conductor cross-section of at least 0.1 mm
2
, not
longer than 100 m in length. Do not forget to connect the cable shield to ground pin 12 on connector XR2;
In the case of a parallel UPS configuration, the connections between cabinets may be made by means of a shielded cable made up of 1 or 2 twisted telephone pairs. In this case, the total length of all the connecting cables must not exceed 100 m;
A "Temperature Monitor" unit can be connected to several UPS cabinets only when the batteries of these cabinets are located in the same room at the same ambient temperature.
Figure 3-11: Single UPS Unit Connection of the Battery "Temperature Monitor".
Refer to Appendix C for link-up options using an IBM AS400 computer for additional monitoring capability.
+12
(unit shown open)
XR2
XR1
-12
DC-
DC +
12 11 10
9
8
7 6 5 4 3 2 1
power supply
XR2 connector on 'Media Contacts 11' Board:
temperature signal
-12V +12V
each
DC + DC -
Shielded cable (2 twisted telephone pairs)
Battery Temperature Monitor
Galaxy PWUPS 100 to 225kVA
Installation3 — 12 86-133060-00 A00
Page 47
Installation and User Manual
Figure 3-12: Connection of the Battery "Temperature Monitor." (In Parallel UPS Units with Batteries in Same Room.)
+12
(unit shown open)
XR2
XR1
-12
DC-
DC +
12 11 10
9 8 7 6 5 4 3 2 1
power supply
XR2 connector on 'Media Contacts 11' Board in Galaxy PW unit 1:
temperature signal
-12V +12V
each
DC + DC -
Shielded cable (2 twisted telephone pairs)
Battery Temperature Monitor
12 11 10
9 8 7 6 5 4 3 2 1
XR2 connector on 'Media Contacts 11' Board in Galaxy PW unit 2:
temperature signal
each
DC + DC -
12 11 10
9 8 7 6 5 4 3 2 1
XR2 connector on 'Media Contacts 11' Board in Galaxy PW unit n:
temperature signal
each
DC + DC -
Shielded cable (1 or 2 twisted telephone pairs)
Installation 3 — 1386-133060-00 A00
Page 48
Figure 3-13: Connection to the "Media Contacts 11" Board.
3.9 About Final Installation Steps
After making the connections, install the front and rear base plates of the cabinets, clipping them to the feet of the cabinets (unless the connecting cables are fed through these openings), and refit the terminal shields of the terminal blocks, switches and circuit breakers.
Media Contacts 11 Remote Indicators Board
XR2 XR3 XR4 XR5
12 - - - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1
XR2
XR3
XR4
XR5
XR1
12 - - - - - - - - - -110- - - - - - - - - 1 10- - - - - - - - - 1 10- - - - - - - - - 1
output signals:
load or battery (utility failure)
10
9
8
7 6 5 4 3 2 1
XR's connector
low-battery shutdown warning (low battery)
load or inverter (ON)
load on bypass (bypass active)
commond W (system ground)
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Galaxy PW
IBM AS400
male 9-pin SUB-D connector
male 15-pin SUB-D connector
NOTE: the corresponding IBM AS400 signal names
are given in parapharase.
Galaxy PWUPS 100 to 225kVA
Installation3 — 14 86-133060-00 A00
Page 49
Operation
4.0 Scope
Operation describes the start-up for single and parallel units, modes of operation, normal specifications for operating the Galaxy PW™ 100 to 225kVA, including display messages, measurement systems, alarms, batteries, and log time stamping operations.
WARNING Rectifier/charger start-up is automatic when normal AC input circuit breaker Q1
is closed. DC voltage is present in the DC bus.
4.1 Start-up of a Module
Rectifier/charger start-up is automatic when the normal AC input circuit breaker Q1 is closed. The green "rectifier/charger" light 1 on the control panel goes on. Close battery circuit breaker QF1.
Figure 4-1: Control Panel and Circuit Breaker Diagram.
4.1.1 Start-up of an Inverter
When the rectifier/charger is on, press the "inverter ON" button 7 on the control panel. The green "inverter" light 4 flashes.
4.1.2 Emergency Power Off (EPO)
The UPS emergency shutdown function is generally wired to a "mushroom-head" type emergency-off pushbutton. In case of its use, the pushbutton contact has to reset.
IMPORTANT After EPO/REPO, unit has to be reset by opening M2 feed (switch Q4S). Open
switch Q5N also, and then follow the procedure of single UPS for single unit or parallel UPS for parallel units to start-up the system.
1
2
VA
W.H z
fault
18
17
8
7
643 521
22
2119 20
16
9 10 11 12 13 1514 15
maintenance bypass:
Q3BP
inverter (B):
DC to AC power
isolation:
Q4S
isolation and protection:
Q5N
rectifier/ charger (A):
AC to DC power
QF1: isolation and protection
normal AC input
battery (D):
backup power
static bypass (C):
bypass AC input
Q1
isolation and protection
(1)
(2)
harmonic fliter
*FUSE
*FUSE
Operation 4 — 186-133060-00 A00
Page 50
4.1.3 Single UPS Unit
The inverter starts, then, if the bypass AC source transfer conditions are satisfied, the load is transferred to the inverter, if the on-line mode is selected.
For on-line mode:
The green "inverter" light 4 remains on.
The "static-bypass" light 3 goes off.
Figure 4-2: Single UPS Diagram .
4.1.4 Parallel UPS Unit
The inverter starts and awaits the start of the other inverters. When they are all on or enough have been started to supply the rated load power, the output switch for each running inverter closes and the load is supplied with power:
The green "static-bypass" light 3 goes off.
The green "inverter" light 4 on the control panels of the running inverters goes on.
Figure 4-3: Two Parallel Connected UPS Units.
Figure 4-4: Four Parallel Connected UPS Units.
2
1
Q3BP
Galaxy 1
Galaxy 2
2
1
Galaxy 3
2
1
Galaxy 4
2
2
Q5N
1
2
1
Q3BP
S
Galaxy 1
Galaxy 2
2
2
Q5N
1
1
2
AB
C
D
Galaxy PWUPS 100 to 225kVA
Operation4 — 2 86-133060-00 A00
Page 51
Installation and User Manual
4.2 Operation in On-line Mode
4.2.1 Normal Operation
Normal AC source power is available, see Figure 4-5.
Lights 1 , 4 and 5 shine green on the control panel.
-The power necessary for the load is provided by the normal AC source (1) through the rectifier/charger (A) and the inverter (B). The rectifier/charger (A) also supplies the power to float charge and recharge the battery if any.
The output voltage (DC) is regulated to supply:
The float-charging or the recharging voltage for vented lead-acid or Ni/Cd batteries.
- a single charge voltage for sealed lead-acid batteries.
The voltages depend on the number of battery cells and the battery manufacturer. Factory set, they may also be adjusted by support technicians.
An electronic board continuously measures the battery temperature and automatically adjusts the voltages.
NOTE In parallel Galaxy PW™ systems, the power drawn by the load is equally shared
between the different units.
Figure 4-5: Normal Operation Indicator Diagram.
1
2
AB
C
D
2
1
4
5
1
Operation 4 — 386-133060-00 A00
Page 52
4.2.2 Operation with the Normal AC Source Down
In the event of a normal AC source failure or voltage outside specified tolerances of ±10% in amplitude (±15% optionally), the rectifier/charger (A) stops and the battery (D) supplies the necessary backup power to the load via the inverter (B).
The battery, float-connected between the rectifier/charger and the inverter, discharges during this operating mode:
lights 2 , 4 and 5 shine green.
The user is warned of battery operation by the slow beeping of the buzzer 6 , see Figure 4-6, and the message "LOAD PROTECTED, BATTERY DISCHARGING", followed by the remaining backup time and the percent load.
This information is also available via volt-free changeover contacts for remote control devices.
Figure 4-6: Normal AC Source Indicator Diagram.
2
1
4 52
1
2
AB
C
D
Galaxy PWUPS 100 to 225kVA
Operation4 — 4 86-133060-00 A00
Page 53
Installation and User Manual
4.3 Operation with the Normal AC Source Restored
When normal AC source power (1) is restored or its voltage returns to within specified tolerances, the system automatically returns to its normal operating mode described above (on the condition it did not reach the end of battery power). If the end of battery power was reached (with the resulting inverter shutdown), the rectifier/charger (A) restarts automatically, but the inverter (B) must be restarted manually.
The rectifier/charger recharges the battery (D) which was discharged during the mains outage. During battery charging, light 2 flashes green.
The message "BATTERY CHARGING" is displayed, together with the value of the recharging current and battery voltage.
Figure 4-7: Normal Operation Mode Indicator Diagram.
The battery charge cycle takes place in two steps: See Figure 4-8.
step 1: the battery is recharged at a constant current limited to 0.1C10 (i.e. 1/10th of the battery capacity specified
for a 10 hour discharge). The DC voltage increases with the battery charge until the charge level is reached.
step 2: the battery is recharged at constant voltage equal to the charge level. The charging current gradually
decreases until reaching a specified low value (floating current).
For vented lead-acid batteries, the rectifier/charger supplies the charging voltage for 0 to 255 hours (parameter defined by the after-sales support department) and then the floating voltage. For sealed lead-acid batteries, the charging and floating voltages are the same.
NOTE
If the normal AC source failure is shorter than 0 to 255 seconds (default value = 30 seconds) (parameter defined by after-sales support department), the charger automatically supplies the floating voltage given the low battery discharge.
1
2
AB
C
D
2
1
4 521
Operation 4 — 586-133060-00 A00
Page 54
Figure 4-8: Battery Charge Cycle Chart.
4.4 Operation with Engine Generator Set
If a stand-by generator is included in the installation, it is generally started automatically in the event of a normal AC source failure and connected to the main low voltage switchboard. It is disconnected when normal AC source power is restored.
With such a system, the required battery time may be reduced to the time necessary for starting and bringing on line the stand-by generator. The battery (D) supplies power to the inverter (B) during the transfers:
Normal AC source to the generator.
Generator to the normal AC source.
The transfer sequences described above (normal AC source battery, battery generator, generator battery, and battery normal AC source) are fully automatic. They in no way affect the load and require no manual operation by the user.
NOTE To avoid load surges on the generator, the rectifier/charger is started with a 10
second maximum current consumption walk-in (lasting 3 to 10 seconds, depending on the percent load).
To avoid overloading an undersized engine generator set, it is possible to set a maximum power level drawn by the normal AC input. Any additional power required is supplied by the battery. This modification can be made on site by an MGE UPS SYSTEMS field engineer
Figure 4-9: Installation with an Engine Generator Set.
HV system
Mains 2
Mains 1
Galaxy PW
G
A
B
D
C
generator
main LV switchboard
U/I
current limiting
0,1 C10
constant voltage decreasing current
voltage
current
t
U charge/floating (sealed batteries)
U "floating" (vented batteries)
Galaxy PWUPS 100 to 225kVA
Operation4 — 6 86-133060-00 A00
Page 55
Installation and User Manual
4.5 Battery Time
The available battery time during a normal AC source outage depends on the:
Rated capacity of the battery.
Power consumed by the load.
Temperature of the battery.
Age of the battery.
The specified battery time corresponds to a minimum duration at full rated load.
The actual backup time can therefore be greater if the system operates below its full rated load during the normal AC source outage. Operation on battery power can be extended beyond the specified time by reducing the load power consumption (by disconnecting non-critical loads).
A "low battery" warning signal is sent via volt-free changeover contacts for remote control devices when the battery voltage reaches a level slightly above the minimum level. This signal warns the user of the imminent end of battery power. On the device itself, the buzzer beeps rapidly.
The message "LOW-BATTERY SHUTDOWN WARNING" is displayed, followed by the remaining backup time and the percent load. Light 2 turns red and flashes.
Battery power stops when the voltage supplied by the battery reaches the minimum threshold. This results in inverter shutdown and transfer of the load without interruption to the bypass AC source. Light 2 shines red (not flashing). The message "LOAD NOT PROTECTED, ON-LINE MODE" is displayed and the buzzer sounds continuously.
If the bypass AC source also fails, the load is no longer supplied. The inverter automatically shuts down when the time on battery power exceeds three times the specified backup time.
NOTE The "low battery shutdown" warning signal can be sent with an adjustable time
delay prior to the effective end of battery power.
4.6 Inverter Shutdown or Overload
Devices or installations operating in on-line mode with a Bypass AC source.
Figure 4-10: Operating in On-line Mode Diagram.
2
1
1
2
AB
C
D
3 5
Operation 4 — 786-133060-00 A00
Page 56
4.6.1 Single UPS Unit (On-line mode)
In the event of a UPS shutdown (initiated by the user or by an internal protective device), the load is automatically transferred to the bypass AC source. If transfer conditions are satisfied, transfer takes place instantly, without inter­ruption to the load.
NOTE Transfer conditions are not satisfied when bypass AC source characteristics are
outside tolerances (voltage: ±10%. frequency as per personalization. phase sync with inverter ±3°).
In the event of a major transient overload (greater than 1.65 In), immediate transfer takes place as above, without interruption to the load.
The return to the inverter is automatic when the overload disappears if the number of possible returns has not been reached (0 to 255, programmable by personalization). If this number has been reached, the load continues to be supplied by the bypass AC source. This operating mode allows start-up of load devices causing high inrush currents.
This system requires satisfied transfer conditions. If the conditions are not satisfied, the inverter will current limit to 165% of its rated current for 1 second before stopping.
In the event of a small but extended overload (i.e. a continuous level of power exceeding the full rated load), the inverter will continue to supply power for a period depending on the magnitude of the overload (10 minutes for a 125% overload, 1 minute for a 150% overload). See the overload curve in Figure 4-11.
In all the above cases, inverter shutdown and supply of the load via the bypass AC source results in the
following on the control panel:
- light 4 goes off,
- activation of the buzzer (continuous beep),
- light 3 shines green,
- the message "LOAD NOT PROTECTED, ON-LINE MODE" is displayed.
4.6.2 Parallel UPS Without Redundancy
WARNING During maintenance operation, when CB1 (MBP) is closed and CB2 (UPS
ISOLATION) is open, each UPS control panel display will show a message “LOAD PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the critical load is not protected because it is supplied by the mainte­nance bypass power.
Galaxy PWUPS 100 to 225kVA
Operation4 — 8 86-133060-00 A00
Page 57
Installation and User Manual
The shutdown of one inverter results in overload on the other inverters in operation. Two cases may then arise:
A) if the overload on each remaining inverter is > than 1.65 in, the load is immediately transferred to the bypass
AC source.
B) if the overload is less than 1.65 in, the remaining inverters support the overload (see curve in Figure 4-11), and
the load is transferred to the bypass AC source.
After this transfer:
- the light 4 goes off,
- the buzzer is activated and sounds continuously,
- the light 3 goes on and turns green,
- the message "LOAD NOT PROTECTED, PARALLEL ON-LINE MODE" is displayed.
Figure 4-11: Overload Curve Diagram.
4.6.3 Parallel UPS With Redundancy
The shutdown of one UPS unit is of no consequence for the load. The others each take up an equal amount of load power and the load continues to be supplied normally.
Unit shutdown results in the following on the control panel:
- Lights 4 and 5 go off,
- Activation of the buzzer (continuous beep),
- The message "LOAD NOT PROTECTED, PARALLEL ON-LINE MODE" is displayed.
- In the event of an overload, the system only loses its redundancy as long as the overload is less than the total rated power of the functioning units. If the overload is greater, the operating mode is that previously described for systems without redundancy.
4.7 Output Voltage Quality and Continuity
The output voltage is stable in amplitude and frequency and is free of interruptions or transients outside specified tolerances, irrespective of normal AC source or load disturbances (outages, load step changes, etc.).
I
12345678910
(min)
1,5 In
1,35 In
1,25 In
1,15 In
1,10 In
1,05 In
In
t
30 120
Operation 4 — 986-133060-00 A00
Page 58
4.7.1 Steady State Voltage Regulation
For stable or slowly varying load conditions, the inverter output voltage is regulated to within ±0.5% in amplitude.
The frequency of the output voltage can theoretically be regulated to within 0.1% of the rated value, however the output frequency range may be intentionally extended to a maximum of ±2 Hz so that the inverter can remain synchronized with the bypass AC source and its inherent frequency fluctuations, thus enabling transfer of the load to the bypass line at any time.
When the bypass AC source frequency returns to within the specified tolerances, the inverter is gradually re­synchronized to the bypass line at a rate of 0.5 Hz to 2 Hz/s (as per the value personalized by the after-sales support department), thus avoiding exposing the load to sudden frequency variations.
4.7.2 Transient Voltage Regulation
The inverter output voltage is not notably affected by instantaneous major variations in load characteristics.
This is made possible by the PWM (Pulse Width Modulation) chopping technique and the microprocessor-based regulation system that instantly compensates for any variation. In particular, the inverter output voltage remains within +/- 2% of the rated voltage for load step changes of 0 to 100% or of 100 to 0%.
The battery charge cycle takes place in two steps:
step 1: The battery is recharged at a constant current limited to 0.1C10 (i.e. 1/10th of the battery capacity specified
for a 10 hour discharge). The DC voltage increases with the battery charge until the charge level is reached.
step 2: The battery is recharged at constant voltage equal to the charge level. The charging current gradually
decreases until reaching a specified low value (floating current).
For vented lead-acid batteries, the rectifier/charger supplies the charging voltage for 0 to 255 hours (parameter defined by the after-sales support department) and then the floating voltage. For sealed lead-acid batteries, the charging and floating voltages are the same.
Galaxy PWUPS 100 to 225kVA
Operation4 — 10 86-133060-00 A00
Page 59
Installation and User Manual
Operation 4 — 1186-133060-00 A00
4.8 Measurement System
The display may be used to read a number of input and output measurements made at different points in the system. See Figure 4-12.
Normal AC source 1 Inverter output 4
- phase-to-phase voltages, - frequency
- currents of the three phases,
Total load 6
- frequency. - phase-to-neutral voltage.
Bypass AC source 2 - phase-to-phase voltages.
- phase-to-neutral voltage, - currents of the three phases.
- phase-to-phase voltages, - frequency.
- frequency, - active and apparent power.
- currents of the three phases.
Battery 3
- voltage.
- charge or discharge current.
- remaining battery time (for the UPS unit concerned).
- battery temperature.
Figure 4-12: Measurement System Diagram.
1
2
Q1
Q5N
QF1
U - V - I - F
U - I - F
U - I
F
U - V - I - F - P
AB
C
D
Q4S
6431
2
Page 60
4.8.1 Voltage Measurements
These measurements may be accessed by pressing the "V" key 13 . The following data is displayed.
Note:
M1: normal AC source
M2: bypass AC source
4.8.2 Current Measurements
These measurements may be accessed by pressing the "A" key 14 . The following data is displayed.
Note:
CF: crest factor
4.8.3 Power and Frequency Measurements
These measurements may be accessed by pressing the "W.HZ" key 15 .
The following data is displayed.
Note:
PF: power factor
4.8.4 Battery Measurements
These measurements may be accessed by pressing the "battery" key 18 . The following data is displayed.
RMS M1 M2 LOAD RMS M2 LOAD
U12 ---- ---- ---- V1 ---- ----
U23 ---- ---- ---- V2 ---- ----
U31 ---- ---- ---- V3 ---- ----
RMS M1 M2 LOAD RMS M2 LOAD
U12 ---- ---- ---- V1 ---- ----
U23 ---- ---- ---- V2 ---- ----
U31 ---- ---- ---- V3 ---- ----
RMS M1 M2 LOAD RMS M2 LOAD
U12 ---- ---- ---- V1 ---- ----
U23 ---- ---- ---- V2 ---- ----
U31 ---- ---- ---- V3 ---- ----
RMS M1 M2 LOAD RMS M2 LOAD
U12 ---- ---- ---- V1 ---- ----
U23 ---- ---- ---- V2 ---- ----
U31 ---- ---- ---- V3 ---- ----
Galaxy PWUPS 100 to 225kVA
Operation4 — 12 86-133060-00 A00
Page 61
Installation and User Manual
Operation 4 — 1386-133060-00 A00
4.9 Selections and Settings
These selections and settings may be accessed by pressing the "contrast" key 12 .
The following menu is displayed:
Selecting the language:
Adjusting the display contrast:
Adjusting the buzzer volume:
BUZZER VOLUME SETUP
CHOOSE WITH KEYS
OR
VALIDATE WITH KEY ø
DISPLAY CONTRAST SETUP
CHOOSE WITH KEYS
OR
VALIDATE WITH KEY ø
FRENCH SPANISH
ENGLISH DUTCH
GERMAN SWEDISH
ITALIAN PORTUGUESE
CHOOSE LANGUAGE DATE AND TIME
CONTRAST SETUP INVERSE VIDEO
BUZZER SETUP PAST EVENTS
LAMP TEST BATTERY TEST
Page 62
Lamp test:
When this function is selected, all the lights shine orange for three seconds.
Set Date and Time:
Use the "▲▼" keys to enter the data and confirm using the "ø " key.
Inverse Video:
When this function is selected, the text and background colors are reversed (white text on black or black text on white).
Past Events:
See section 3.15 "logging and Time-Stamping" for event details.
Battery test:
the screen opposite is displayed when a battery test is requested. It indicates the battery charge status and the remaining service life. A manual or automatic test may be requested.
- this screen is displayed during a battery test, whether manual or automatic,
TESTING BATTERY
U BATTERY = --- V
CHARGE LEVEL = -- %
REMAINING SERVICE LIFE = -- MONTH
MANUAL TEST press key ø
AUTO TEST press key ø
DATE AND TIME SETUP
YEAR ---- MONTH --
DAY -- HOURS --
MINUTES -- SECONDS --
Galaxy PWUPS 100 to 225kVA
Operation4 — 14 86-133060-00 A00
Page 63
Installation and User Manual
- this screen is displayed following a positive, manual battery test:
- this screen is displayed following a negative, manual battery test:
- this screen is displayed following a positive, automatic battery test. It indicates the time since the last test and provides access to test settings:
- this screen is displayed following a negative, automatic battery test. It indicates the time since the last test and provides access to test settings,
- this screen is displayed when the user requests access to the automatic test settings. It is possible to modify the interval between two automatic tests,
- this screen is displayed when the battery test cannot be completed.
TEST INTERRUPTED
CHECK PRESENCE OF THE BATTERY
CHECK ALARMS
SELECT TIME OF NEXT TEST WITH KEYS ▲▼
CHANGE UNITS WITH ø
WEEK -- DAY -- HOUR --
confirm with key
TIME SINCE LAST TEST
WEEK -- DAY -- HOUR --
LAST BATTERY TEST RESULT NOT OK
NEW PARAMETERS YES = NO =
TIME SINCE LAST TEST
WEEK -- DAY -- HOUR --
LAST BATTERY TEST RESULT OK
NEW PARAMETERS YES = NO =
BATTERY TEST RESULT NOT OK
BATTERY TEST RESULT OK
Operation 4 — 1586-133060-00 A00
Page 64
4.10 Alarms
The auto diagnostic system considers any system status other than normal as a problem.
Before taking any action, note down the messages displayed on the control panel.
Certain problems may prevent the control panel from functioning.
In this case, it is strongly recommended to call the MGE UPS SYSTEMS Customer Support Service
at:
1-800-438-7373
.
A) If the load is still correctly supplied with power, it has probably been transferred to the bypass AC source (static
bypass) and is therefore no longer protected (if the system is in on-line mode).
B) If the load is no longer supplied with power, transfer it manually to the maintenance bypass.
Figure 4-13: Display of Alarm Messages..
4.11 Maintenance Bypass Option
The Maintenance bypass option provides a direct bypass AC input source (mains 2) that can be used to supply the critical load while the UPS is being serviced.
This operation is possible only if the system includes a bypass AC source. It results in the load being directly supplied by the Bypass AC source via Maintenance Bypass switch Q3BP, thus ensuring a higher level of security in the event of a malfunction.
Switching procedures are explained on drawings next to each switch in the UPS cabinet and the External Bypass unit.
(ALARM MESSAGE N° 2)
(LAST ALARM MESSAGE)
primary message
main screen
(ALARM MESSAGE N° 1)
Galaxy PWUPS 100 to 225kVA
Operation4 — 16 86-133060-00 A00
Page 65
Installation and User Manual
4.12 Logging and Time-Stamping
4.12.1 Event Time-Stamping
Time-stamping of events by Galaxy PW™ makes it possible to:
Log the events.
Consult the last 500 events that occurred on the Galaxy PW™ UPS.
Consult general statistical data on UPS operation.
Consult measurement records for a number of physical values concerning system operation.
The time-stamping information may be accessed via the Galaxy PW™ keypad and display (standard equipment). This information may also be forwarded for the Teleservice function using the JBUS RS232/485 communications board. When the optional JBUS RS232/485 communications board is installed, the time-stamped information can be sent to the Teleservice center. Refer to Utilization of Teleservice Card options Appendix B.
4.12.2 Consulting Logged (time-stamped) Events
When the PAST EVENTS command is selected, the system displays a screen indicating the last event logged. Log screens are very similar to those displayed for current events. However, log screens include a line indicating the corresponding date and time with the mention "Appearance of" or "Disappearance of", followed by the standard text for the event (see example opposite). Consult the user manual for indications on the meaning of events.
The complete log may comprise up to 500 events. If over 500 events have occurred, only the last 500 may be consulted:
1. Press the
key to display the event that occurred just before the displayed event. If the displayed event is the
oldest in the list, the display is not modified.
2. Press the
key to display the event that occurred just after the displayed event. If the displayed event is the
most recent in the list, the display is not modified.
Example:
Note: numerical values are never indicated in screens for time-stamped events.
Example:
03/09/1997 15:30:23 Disappearance:
OVERLOAD
RATED CURRENT PER PHASE = _ _ _ A
CHECK LOAD LEVEL
02/09/1997 07:25:03 Appearance:
MAINS 2 INPUT SWITCH Q4S IS OPEN
Operation 4 — 1786-133060-00 A00
Page 66
4.13 Setting the Date and Time for the UPS - Utilization Via the Galaxy PW™ Display
The time and date can be set for the UPS via the main menu on the display (see below), using the DATE AND TIME command. The time-stamping information, statistics and measurement records are also available via the same menu, using the PAST EVENTS command.
Simply select the desired command with the ">" sign that can be moved using the
and keys. The selected
command can be confirmed by pressing the key.
When the DATE AND TIME command is selected, the date and time is displayed in the order of year, month, day, hours, minutes, and seconds. When you leave this command, the date and time is displayed in the reverse order.
The current values are automatically displayed.
Modify any of the displayed values by:
1. Position the ">" sign opposite the value to be modified. Then press the ø key.
2. Use the
and keys to modify the value.
3. Use the
key to increment the value by one.
4. Use the
key to decrement the value by one.
The selected value can be confirmed by pressing the ø key. A second value may then be selected for modification, again using the
and keys. Modifications are made and confirmed value by value.
5. Press the key at any time to exit the DATE AND TIME function.
That is the only means to leave the function. If no modifications to values are confirmed, exiting the function corresponds to cancelling the request.
DATE AND TIME SETUP
>YEAR 1997 MONTH 9
DAY 8 HOURS 8
MINUTES 11 SECONDS 42 ▲▼
Galaxy PWUPS 100 to 225kVA
Operation4 — 18 86-133060-00 A00
Page 67
Installation and User Manual
4.14 Consulting Statistics
Legend:
total backup time (h): This is the total time of operation on battery power since initial startup of the UPS. It
is expressed in hours.
total time on static This is the total time of operation on the static switch since initial startup of the UPS. switch (h): It is expressed in hours.
total time on UPS (d): This is the total time that the load has been supplied by the UPS since initial startup.
It is expressed in days.
total time with This is the total time of operation with the battery temperature greater than 25°C Tbatt > 25°C (h): since initial startup of the UPS. It is expressed in hours.
last reset: This is the date that the information was last set to zero by the Teleservice function.
elapsed backup This is the total time of operation on battery power since the last reset. It is expressed time (min): in minutes.
FIGURES SINCE COMMISSIONING
total backup time (h): 0
total time on static switch (h): 0
total time on UPS (d): 3627
total time with Tbatt >25°C (h): 1
FIGURES SINCE RESET
last reset: 05/09/1997
elapsed backup time (min): 0
Operation 4 — 1986-133060-00 A00
Page 68
Legend:
nb of backups: This is the number of times the load was supplied by the UPS from battery power
since the last reset.
nb of backups < 1 min: This is the number of times the load was supplied by the UPS from battery power for
less than one minute, since the last reset.
1 min < nb of This is the number of times the load was supplied by the UPS from battery power
backups < 3 min: for more than one minute and less than three minutes, since the last reset.
nb of backups > 3 min: This is the number of times the load was supplied by the UPS from battery power for
more than three minutes, since the last reset.
nb of overloads < 5’s: This is the number of times the UPS was overloaded (output current greater than In)
for less than five seconds, since the last reset.
nb of overloads > 5’s: This is the number of times the UPS was overloaded (output current greater than In)
for more than five seconds, since the last reset.
nb of times This is the number of times the battery temperature was measured at over 25°C,
TBatt. > 25°C: since the last reset.
FIGURES SINCE RESET
nb of backups: 0
nb of backups < 1 min: 0
1 min < nb of backups < 3 min: 0
nb of backups > 3 min: 0
nb of overloads < 5 s: 0
nb of overloads > 5 s: 0
nb of times TBatt. > 25°C: 0
Galaxy PWUPS 100 to 225kVA
Operation4 — 20 86-133060-00 A00
Page 69
Installation and User Manual
4.14.1 Consulting Recorded Measurements
Recorded measurements are presented in the same manner (see below):
the lists indicate the last 30 measurements recorded for the given parameter. The chronological order of
the measurements is indicated in the Figure opposite.
the most recent measurement is presented first, in the upper left-hand corner of the list. The following
measurement is listed just below, and so on until the 30th value listed in the bottom right-hand corner of the list.
the period T between two successive measurements is 30 days. The displayed measurements are instan-
taneous values.
NOTE when this screen is selected, approximately ten seconds are required to call up
and display the information. If the number of measurements is greater than 30, only the last 30 (the most recent) are displayed.
PARAMETER NAME (units) T=30 days
last read: 05/09/1997
M(t+29T)|M(t+23T)|M(t+17T)|M(t+11T)|M(t+05T)
||||
M(t+28T)|M(t+22T)|M(t+16T)|M(t+10T)|M(t+04T)
||||
M(t+27T)|M(t+21T)|M(t+15T)|M(t+09T)|M(t+03T)
||||
M(t+26T)|M(t+20T)|M(t+14T)|M(t+08T)|M(t+02T)
||||
M(t+25T)|M(t+19T)|M(t+13T)|M(t+07T)| M(t+T)
||||
M(t+24T)|M(t+18T)|M(t+12T)|M(t+06T)| M(t)
Operation 4 — 2186-133060-00 A00
Page 70
The battery capacity is the value measured by the UPS microprocessor. It is expressed in Ampere-hours. This value changes over time depending on the parameters of the battery itself and its environment. This measurement is used to check that the battery is capable of supplying the rated power in the event of a mains outage.
The backup time is the value calculated by the UPS microprocessor on the basis of measurements carried out on the battery. It is expressed in minutes. The calculation uses the percent load and the battery charge status at the time of the measurement.
The load level is the ratio between the power supplied by the UPS to the load at the time of the measurement and the rated output of the UPS. It is expressed as a percentage.
OUTPUT LOAD LEVEL(%) T=30 days
last read: 05/09/1997
63|0|0|0|0 52|0|0|0|0 63|0|0|0|0 63|0|0|0|0
0| 0| 0| 0| 0 0| 0| 0| 0| 0
BACKUP (min) T=30 days
last read: 05/09/1997
120|0|0|0|0 115|0|0|0|0 110|0|0|0|0 105|0|0|0|0
0| 0| 0| 0| 0 0| 0| 0| 0| 0
BATTERY CAPACITY (Ah) T=30 days
last read: 05/09/1997
97|0|0|0|0 96|0|0|0|0 95|0|0|0|0 94|0|0|0|0
0| 0| 0| 0| 0 0| 0| 0| 0| 0
Galaxy PWUPS 100 to 225kVA
Operation4 — 22 86-133060-00 A00
Page 71
Maintenance
5.0 Scope
Maintenance procedures include preventive maintenance, isolation procedures for maintenance, startup for single and parallel units after isolation, functional and visual checks, software options and configurations, and testing scenarios.
5.1 Preventive Maintenance
The following preventive maintenance routines should be considered the minimum requirements; your installation and site may require additional preventive maintenance to assure optimal performance from your installed Galaxy PW™ and associated equipment. These routines should be performed twice a year (more often if required). We strongly recommend contracting MGE Customer Support Services for preventive and remedial maintenance.
The technician or electrician performing preventive maintenance on the UPS must read thoroughly this manual Galaxy PW™ Installation and Users Manual (MGE PN 86-133060-00) and be familiar with the indicators, controls, and operation of the UPS prior to maintenance.
Technician or Engineer checks for preventive maintenance:
a. Isolate and de-energize all Galaxy PW™ equipment for all maintenance operations.
b. Ensure that all equipment is clean and free of loose dust, dirt, and debris. The exterior of the enclosures may
be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.
c. Inspect the air intake and exhaust plates and clean as required. Verify that air flows freely through the
equipment. Clean the air intake and exhaust plates, and the enclosure interior, with a vacuum cleaner.
d. The Galaxy PW™ module is equipped with air filters that should be changed at regular intervals. Inspect the
filters regularly to determine how long the filters will last in your installation.
e. Initiate the start-up procedure, as described in the Installation and Users Manual section 2.7 System Start-up,
page 2—10.
f. Test the main operating sequences as applicable to your equipment configuration and installation.
5 — 186-133060-00 A00 Maintenance
Page 72
5.2 Replacement Parts
There are no user replaceable parts inside the Galaxy PW™.
Three levels of replacement parts are available for the Galaxy PW™ UPS. The three levels are designated A, B, and C. The level that you should keep on hand for your installation will vary depending on the type of maintenance planned on site, and the configuration of your UPS system. Having the replacement parts on hand will prevent any unacceptable delays (due to time involved obtaining spare parts) during critical periods, such as system start-up.
Any items used during start-up will be replaced by MGE at no charge. Contact MGE Customer Support Services for specific recommendations.
A description of each level is provided below:
Level Description
A This level of replacement parts consists of consumable items, specifically fuses and air filters. It is
recommended to have these items on hand during installation of the UPS systems, including initial start-up.
B This level of replacement parts is recommended when the user can tolerate short-duration UPS down-
time to obtain replacement parts in the event of a major UPS failure. This level of replacement parts consists of consumable items, specifically fuses, air filters, an inverter leg, and the most critical circuit board assemblies.
C This level of replacement parts is recommended when the user can tolerate only a minimum of down-
time in the event of a major UPS failure. This level of replacement parts consists of consumable items, specifically fuses, air filters, an inverter leg, and a complete set of circuit board assemblies.
5.2 Maintenance Isolation Procedures
CAUTION PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-
nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is open, each UPS control panel display will show a message “LOAD PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the critical load is not protected because it is supplied by the maintenance bypass power.
5.2.1 Single UPS Unit
During maintenance, the UPS must be isolated from the normal and bypass AC source, the battery and the load.
UPS Isolation
Proceed in the following order: (see Figure 5-2):
1. Shut down the inverter (press the "inverter OFF" button 8 for three seconds),
2. Close bypass switch Q3BP,
3. Open isolating switches Q5N, Q4S, QF1 and Q1.
The UPS is powered down once the capacitors have discharged (a few minutes).
Galaxy PWUPS 100 to 225kVA
Maintenance5 — 2 86-133060-00 A00
Page 73
Installation and User Manual
Start-up
Following servicing, proceed in the following order: (See Figure 5-3)
1. Close switch Q1, then after approximately ten seconds, switches QF1, Q5N and Q4S,
2. 0pen bypass switch Q3BP,
3. Start the inverter (press the "inverter ON" button 7 ).
Figure 5-1: UPS Isolation Diagram for Normal AC Bypass Source.
Figure 5-2: Panel Procedures for UPS Isolation.
Figure 5-3: Start-up After Isolation Procedure is Completed.
FF
1
0
1
0
1
0
1
0
Q5NQ1 Q4S
3
1
2
Q3BP
1
0
5
4
6
1
0
1
0
1
0
1
0
1
0
1
0
1
0
QF1
0
I
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
Q5NQ1 Q4S
3
1
2
1
0
Q3BP
1
0
1
0
5
4
6
QF1
0
I
1
0
1
0
1
0
1
0
7
8
Q1
Q5N
QF1
Q3BP
Q4S
AB
C
D
1
2
Maintenance 5 — 386-133060-00 A00
Page 74
CAUTION Work should be carried out in accordance with applicable safety regulations. to
avoid interrupting the load, the various switching operations must be carried out in the correct order. Operations are explained in diagrams placed next to the switches. the system cabinet is only partially powered down. The load is still supplied via the bypass AC source and switch Q3BP.
5.3 Steps for Parallel UPS Redundancy to Increase Output
CAUTION
PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte­nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is open, each UPS control panel display will show a message “LOAD PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the critical load is not protected because it is supplied by the maintenance bypass power.
First Isolate all UPSs: (Refer to section 5.2, page 5—2)
See Figure 5-6.
Proceed in the following order: (See Figure 5-4)
1. Shut down the inverters (press the "inverter OFF" buttons 8 for three seconds).
2. Close switch Q3BP and open switch Q5N in the external bypass unit.
3. Open switches Q1, QF1, and Q5N on the UPS units.
Figure 5-4: Isolate All UPS’s Procedures Diagram.
2 3 4
1
0
1
0
1
0
1
0
Q5N
Q3BP
Q5NQ1 Q4S
QF1
0
I
external bypass
4
5
1
Galaxy PW
1
0
1
0
1
0
1
0
1
0
6
1
0
1
0
7
8
Galaxy PWUPS 100 to 225kVA
Maintenance5 — 4 86-133060-00 A00
Page 75
Installation and User Manual
Start-up
Following servicing, proceed in the following order: (see Figure 5-5)
1. Close switches Q5N on the UPS units.
2. Close switch Q5N in the external bypass unit.
3. Open switch Q3BP in the parallel-connection unit.
4. Close switches Q1 and QF1 on the UPS units.
5. Start the inverters (press the "inverter ON" buttons 7 ).
Figure 5-5: Start-up Procedure After Isolation Diagram.
Figure 5-6: Redundancy for Increased Output Diagram.
2
1
Q3BP
Galaxy 1
Galaxy 2
2
1
Galaxy 3
2
1
Galaxy 4
2
Q5N
1
2
Q1
QF1
Q5N
Q4S
2 3 4
1
0
1
0
Q3BP
Q5N
Q1
Q4S
QF1
0 1
Q5N
Q5N
Q1
Q4S
external bypass
4
5
1
0
1
0
1
0
1
0
1
0
1
6
1
0
7
8
1
0
1
0
1
0
Maintenance 5 — 586-133060-00 A00
Page 76
5.4 Battery Maintenance
Consult the instructions supplied by the battery manufacturer. Below are a few general indications:
Sealed lead-acid Batteries:
- these batteries require no maintenance, but check the terminals of each cell from time to time and clean if necessary.
Vented lead-acid Batteries:
- check the electrolyte level regularly and add water if necessary,
- check the voltage of each cell to determine if it is necessary to equalize the battery,
- check the terminals of each cell and clean if necessary.
5.5 Visual Check
Power down the system prior to any maintenance operations.
NOTE In redundant parallel UPS systems the check may be carried out successively on
each UPS unit without interrupting the load. In other configurations, the load must be supplied via the maintenance bypass (see "maintenance bypass" in the "Alarm" section).
1. Clean the system regularly, particularly the air filter inlet and outlet grills. Check that the air circulates freely in the cabinets. Use a vacuum cleaner if necessary.
2. Check that nothing hinders the ventilation at the top and at the back of the system.
5.6 Functional System Checks
1. Check that lights 1 , 2 and 3 on the control panel are not red, to avoid an interruption in the supply of power to the load due to incorrect transfer conditions or a battery problem.
2. Press the "inverter OFF" button and check that the buzzer and control panel lights function correctly (see the section on operating modes in the introduction).
3. Press the "inverter ON" button and check again that the control panel lights function correctly.
4. Run a transfer to battery test. With the inverter on, open input circuit breaker Q1. The orange "battery" light on the control panel should light. After two minutes on battery power, close input circuit breaker Q1. The rectifier/charger should automatically restart and the orange "battery" light on the control panel should go off.
Galaxy PWUPS 100 to 225kVA
Maintenance5 — 6 86-133060-00 A00
Page 77
Installation and User Manual
5.7 Testing Parallel Systems
5.7.1 Galvanic Isolation and Voltage Matching Transformers
The UPS can be equipped with an isolation or auto transformer on both the input and output to provide galvanic isolation or voltage step-up or step-down as required.
5.8 Management of Computer Networks
5.8.1 Integrated SNMP Agent
This electronic board, installed in the UPS system, enables direct connection to all Ethernet networks using TCP/IP.
The UPSs may then be supervised via the computer network. Furthermore, they can be used to close system files without having to add an external SNMP agent.
This board is fully compatible with "Solution Pac™" software.
The RJ45 connector of the communications option delivers information using the SNMP protocol. The sticker located on the board indicates the UPS MAC address.
Figure 5-7: MAC Address Sticker.
The MAC address is written in the following way: 0080C8 ZZ XX YY.
The default IP address is 168.8.xx.yy (xx and yy are decimal values of XX and YY).
For example, MAC address 00 80 C8 AB AA 01 is related to IP address 168.8.170.1.
Please refer to the "userman.doc" user manual contained in the directory "emb/galaxy/snmp/release3.xx" of the Solution-Pac CD-ROM in order to discover the management capabilities of your SNMP Galaxy PW™ UPS.
Please contact your sales representative for more detailed information.
5.8.2 Two-channel Network Board
This electronic board comprises two ports, each of which may be user set, either for the U-Talk protocol or as a relay contact.
A) U-Talk is the protocol required to establish contact with the communications software.
B) Relay contacts may be used for specific network applications (IBM AS400, Novell, etc.).
0080C8ABAA01
Maintenance 5 — 786-133060-00 A00
Page 78
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
5 — 8 86-133060-00 A00
Page 79
Appendices
Appendix A
Front Control Panel Display Definitions
1 "Rectifier/charger" light
light off: rectifier/charger OFF.
light shines green: rectifier/charger ON.
light shines red: rectifier/charger fault, the stored alarm indicates one or several of the following faults:
- input circuit breaker Q1 open,
- protection fuse at the rectifier/charger input (FUE) blown,
- abnormally high internal rectifier/charger temperature,
- abnormally high battery charge current,
- abnormally high battery voltage,
- fault, non-calibration or non-personalization of the electronic control board for the rectifier/charger,
- fault on the electronic power-supply board,
- abnormally high temperature in the harmonic filter inductor.
2 "Battery light"
light off: battery float charging.
light flashing green: battery recharging.
light shines green: load on battery power.
light flashing red: low-battery shutdown warning.
light shines red: battery at end of backup time and circuit breaker QF1 open, or battery fault.
3 "Static-bypass" light
light off: bypass AC source within specified tolerances and static bypass open.
light shines green: static bypass closed.
light shines red: the stored alarm indicates one or several of the following faults:
- bypass AC source voltage or frequency outside specified tolerances,
- static-bypass fault,
- abnormally high internal static-bypass temperature,
- static-bypass ventilation fault,
- power-supply fault for the static-bypass control function,
- fault on the electronic board controlling the transfer function,
- non-calibration or non-personalization of the electronic control board for the inverter,
- fault on the electronic power-supply board,
- fault on monitoring the "inverter ready" response channels (parallel UPS system).
Appendices A — 186-133060-00 A00
Page 80
4 "Inverter" light
light off: inverter OFF.
light flashing green: inverter starting, inverter ON but not connected to the load.
light shines green: normal inverter operation.
light shines red: inverter fault, the stored alarm indicates one or several of the following faults:
- inverter shutdown due to inverter output voltage outside specified tolerances,
- protection fuse at the inverter output (FUS) blown,
- abnormally high inverter-output transformer temperature,
- abnormally high inverter temperature,
- output-voltage fault (amplitude or phase) (parallel UPSs),
- fault, non-calibration or non-personalization of the electronic control board for the inverter,
- fault on the electronic power-supply board.
5 "Load" light
light off: load not supplied.
light shines green: load supplied via the inverter or the bypass AC source (via the static bypass).
6 Buzzer
The buzzer sounds in the following situations:
load supplied by the bypass AC source.
load on battery.
operating problems.
It sounds slowly and discontinuously for a minor problem or when the inverter is on battery power.
When the alarm "LOW BATTERY SHUTDOWN" is activated, the buzzer sounds more rapidly. Finally, if the inverter shuts down, the beep is loud and continuous. The buzzer may be reset by pressing a button. If the buzzer is reset, a higher level alarm will set it off again.
7 "Inverter ON" button This button is used to start the inverter locally.
8 "Inverter OFF" button This button turns the inverter off locally.
9 -10 Keys These keys are used to select commands in the main menu and access the secondary
messages.
11 Key This key is used to validate the user’s choice.
12 Key
øø
This key is used to access the main menu: display language, display-contrast setting, sound level of the buzzer, lamp test, date and time settings, inverse-video and event log.
Galaxy PWUPS 100 to 225kVA
AppendicesA — 2 86-133060-00 A00
Page 81
Installation and User Manual
13 "V" Key
This key is used to access voltage measurements:
normal AC source phase-to-phase voltages.
bypass AC source phase-to-phase and phase-to-neutral voltages.
load phase-to-phase and phase-to-neutral voltages.
14 "A" Key
This key is used to access current measurements:
normal AC source, bypass AC source and load currents.
percent load.
load crest factor.
15 "W.Hz" Key
This key is used to access other measurements:
normal AC source, bypass AC source and inverter frequencies.
level of active and apparent power drawn by the load.
load power factor.
inverter load level (percent).
16 "Anomaly" indicator light This indicator light indicates the presence of anomalies.
17 Key
This key is used to access the primary messages.
18 "Battery" Key
ıı
This key is used to access battery measurements:
battery voltage (or the DC voltage on frequency converters without a battery).
battery current (charge or discharge).
battery temperature.
available battery backup time.
inverter load level (percent).
19 "Forced-transfer"
This key is used to voluntarily transfer the load to the inverter or from the inverter to the static bypass (return transfer). Transfer and return transfer are carried out only following confirmation requested by the display and a warning as to the risk of an interruption in the supply of power to the load.
20 "Alarm reset" This key is used to reset stored alarms. The system accepts resetting only when alarms
have been cleared.
21 "Buzzer reset" This key is used to stop the buzzer. However, new alarms set the buzzer off again.
22 Display The display continuously indicates the system operating status.
Appendices A — 386-133060-00 A00
Page 82
Display of Primary and Secondary Messages
The display is structured around primary and secondary messages, measuring tables and setting screens. As a rule, the message displayed on the screen is always a primary one. The secondary messages, if any, are accessed by pressing keys 9 and 10 . See Figure 2-6, page 2—8.
The presence of secondary messages is indicated by the arrow Ø at the end of the primary message. Return to the primary messages is automatic if the keypad is not used for 2 minutes, or direct by pressing key 17 The display screen lights up when a key is pressed, and goes off if no key is pressed for 5 minutes.
NOTE Most functions may be directly accessed. For example, when voltagemeasure-
ments are currently displayed, it is possible to directly access current measurements by pressing the "A" button.
In addition to keypad operations, the graphical display brings up a window giving the overall device status. The message displayed is then said to be primary (see list in the paragraph below). A primary message can be used to access the measuring tables using keys 13 , 14 , 15 and 18 on the keypad The configuration screens can be accessed by pressing key 12 .
A flashing arrow appears at the end of a primary message if there is a problem or an alarm. secondary messages can be accessed by pressing key 9 on the keypad (see the list of secondary messages). The presence of another message is indicated by the arrows Ø and at the end of the secondary message. They can be accessed by pressing keys 9 and 10 on the keypad.
The return to the primary message is automatic after a 2 minute time delay or by pressing key 17 on the keypad.
IMPORTANT Select English U. S. as the display language to match the displays as presented
in this manual.
Galaxy PWUPS 100 to 225kVA
AppendicesA — 4 86-133060-00 A00
Page 83
Installation and User Manual
Primary Messages
LOAD PROTECTED
ON-LINE MODE
This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter, in on-line mode.
LOAD PROTECTED
PARALLEL ON-LINE MODE
This is the normal display when there are no alarms or problems and the load is correctly supplied by the inverter in a parallel UPS system, in on-line mode.
LOAD NOT PROTECTED
ON-LINE MODE Ø
This display indicates that the load is not supplied by the inverter, or that there is no battery backup. The arrow Ø indicates the presence of one or more problems specified in secondary messages.
The buzzer sounds continuously.
LOAD NOT PROTECTED
PARALLEL ON-LINE MODE Ø
Situation identical to that in the previous screen, but for parallel UPS systems.
LOAD PROTECTED
BATTERY DISCHARGING
Remaining battery time (min) = XX
% kW used = XXX
The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied by the battery.
This message indicates the remaining battery time in minutes prior to inverter shutdown and the percent load. The battery time calculation takes into account:
The percentage of full rated load power currently being drawn.
The type of battery.
Battery temperature.
Battery age.
The buzzer sounds slowly and discontinuously.
LOAD PROTECTED
LOW-BATTERY SHUTDOWN WARNING
Remaining battery time (min) = XX
% kW used = XXX
This message replaces the preceding if the power outage persists and the warning level has been reached.
The user is warned that the battery is about to shut down.
The buzzer sounds rapidly and discontinuously.
Appendices A — 586-133060-00 A00
Page 84
LOAD PROTECTED
ECO MODE
This is the normal display when there are no problems: the load is supplied by the inverter or the bypass AC source, and battery backup is available.
LOAD NOT PROTECTED
ECO MODE
Ø
This display indicates that the load is supplied but has no battery backup. The arrow Ø indicates the presence of one or more problems specified in secondary messages.
The buzzer sounds continuously.
LOAD FORCED TO INVERTER
ECO MODE
The load has been transferred to the inverter following a specific request by the user.
Secondary Messages
LOAD ON MAINS 2
The load has been transferred to the bypass AC source (M2) and is no longer protected (only in on-line mode). The buzzer sounds continuously.
MAINS 2 OUTSIDE TOLERANCES
TRANSFER DISABLED
CHECK MAINS 2
The bypass AC source (M2) frequency or voltage is outside tolerances and the inverter is unable to synchronize.
Transfer of the load from the inverter to the bypass AC source (M2) or vice-versa will result in an interruption of the supply of power to the load. The buzzer sounds slowly and discontinuously.
BATTERY OVER TEMPERATURE,
CHECK VENTILATION
The battery temperature is outside tolerances. The buzzer sounds slowly and discontinuously
BATTERY ROOM VENTILATION FAULT, CHECK VENTILATION
A fault requiring servicing has occurred in the battery room ventilation system. The rectifier/charger shuts down after a 30-second time delay.
The user must take steps to re-establish correct operation of the ventilation system.
This message also signals an abnormally high temperature in the filter inductor.
The buzzer sounds slowly and discontinuously.
MAINS 1 OUTSIDE TOLERANCES
CHECK MAINS 1
The normal AC source (M1) frequency or voltage is outside specified tolerances and the rectifier/charger has shut down. The inverter is on battery power.
MAINS 1 INPUT SWITCH Q1
IS OPEN
The normal AC input (M1) switch Q1 is open. It must be closed for rectifier/charger start-up. The buzzer sounds slowly and discontinuously.
Galaxy PWUPS 100 to 225kVA
AppendicesA — 6 86-133060-00 A00
Page 85
Installation and User Manual
INTERNAL UPS FAULT
LOAD TRANSFER FAULT,
CALL MAINTENANCE
A fault has occurred in the static switch that transfers the load between the inverter and the bypass AC source (M2). Servicing by the after-sales support department is required. The buzzer sounds continuously.
OVERLOAD
RATED CURRENT PER PHASE = XXXA
CHECK LOAD LEVEL
This display informs the user that load current is greater than rated current, and gives the value. The buzzer sounds continuously.
UPS SHUTDOWN DUE T AN OVERLOAD
CHECK LOAD LEVEL
This message follows the preceding when the overload persists. The UPS has shut down and the buzzer sounds continuously.
INVERTER NOT IN PHASE WITH MAINS 2
TRANSFER DISABLED,
CHECK MAINS 2
The phase difference between the inverter and the bypass AC source (M2) is outside tolerances. Transfer of the load between the inverter and the bypass AC source (M2) will result in an interruption in the supply of power to the load.
For parallel UPSs, this message should be interpreted as meaning the phase difference between the inverter for which the message is displayed and the other inverters is outside tolerances.
UPS SHUTDOWN
BY AN EXTERNAL COMMAND
The inverter has received a command to shut down. The command is in the form of a signal from received the remote-indications relay board which has been set for this function.
The inverter is started again.
MAINS 2 INPUT SWITCH Q4S IS OPEN
The bypass AC source (M2) input switch Q4S is open, i.e. backup power for the load via the bypass AC source (M2) is not available.
INVERTER OUTPUT SWITCH Q5N IS OPEN
Inverter output switch Q5N is open, i.e. the load cannot be supplied via the inverter.
BYPASS SWITCH Q3BP IS CLOSED
Maintenance bypass switch Q3BP is closed. The system is in maintenance configuration and the load is supplied by the bypass AC source.
STATIC SWITCH (M2) OFF
DUE TO AN OVERLOAD
The load is no longer supplied by the bypass AC source (M2), due to an extended overload. The buzzer sounds continuously.
Appendices A — 786-133060-00 A00
Page 86
BATTERY CHARGING
I BAT.=XXX A U BAT. = XXX V
The battery is currently be recharged.
BATTERY AT END OF SERVICE LIFE CALL MAINTENANCE
The battery is nearing the end of its estimated service life. This information is based on average service-life calcu­lations since its initial installation. The buzzer sounds slowly and discontinuously.
EMERGENCY OFF
This message is displayed when the external emergency-off pushbutton is pressed. The result is:
Shutdown of the inverter.
Shutdown of the rectifier/charger.
Opening of the battery circuit breaker.
Blocking of the static bypass.
Opening of the backfeed protection contactor (M2),
Opening of the Q1 circuit breaker (M1),
Activation of a relay contact on the remote-indications relay board.
Servicing by the after-sales support department is required.
The buzzer sounds discontinuously.
THE BATTERY C.B. QF1 IS OPEN,
CHECK THE INSTALLATION
Battery circuit breaker QF1 is open. The load is no longer protected because battery power is no longer available in the event of a normal AC source outage. The buzzer sounds continuously.
LOW BATTERY SHUTDOWN
The inverter has shut down at the end of battery power. The buzzer sounds continuously.
INTERNAL UPS FAULT,
INVERTER FAULT,
CALL MAINTENANCE
A fault has occurred in the inverter. Servicing by the after-sales support department is required. The buzzer sounds continuously.
INTERNAL UPS FAULT,
CHARGER FAULT,
CALL MAINTENANCE
A fault has occurred in the rectifier/charger. Servicing by the after-sales support department is required.
The buzzer sounds slowly and discontinuously.
FORCED TRANSFER TO INVERTER REQUESTED,
POWER TO LOAD MAY BE INTERRUPTED,
CONFIRM YOUR REQUEST WITH KEY ø
The requested transfer to the inverter may provoke an interruption in the supply of power to the load if Mains 2 characteristics are not within the specified tolerances.
Galaxy PWUPS 100 to 225kVA
AppendicesA — 8 86-133060-00 A00
Page 87
Installation and User Manual
THE NUMBER OF UPS READY IS INSUFFICIENT,
LOAD TRANSFER IN STANDBY
This message may be displayed in non-redundant, parallel UPS systems, when the number of ready inverters in not sufficient to supply the load.
INVERTER NOT CONNECTED
This message may be displayed in parallel UPS systems, when the inverter is not connected to the load.
PARALLEL UPS,
FORCED TRANSFER INHIBITED
This message is displayed when forced connection is requested on a parallel UPS system for a power extension.
INTERNAL UPS FAULT,
SELF-TEST FAULT
Communication between the system and the display is faulty. The buzzer sounds slowly and discontinuously.
FORCED TRANSFER TO M2 REQUESTED, POWER TO LOAD MAY BE INTERRUPTED
CONFIRM YOUR REQUEST WITH KEY ø
This message is displayed following pressing of the "forced-transfer" key 20, when the load is supplied via the inverter.
UPS SUPPLIED BY A GENERATOR SET
This message informs the user that the UPS has received the order to limit the current drawn by the rectifier/charger. It is displayed when the corresponding signal is transmitted by the remote indications board which must be conFigure d for this function.
VENTILATION FAULT
This message is displayed when a fault occurs on a fan.
Appendices A — 986-133060-00 A00
Page 88
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
AppendicesA — 10 86-133060-00 A00
Page 89
Installation and User Manual
Appendix B
Monitoring - Electrical Supervision Options
"Teleservice"
"Teleservice" is a contract offering continuous remote supervision and maintenance of UPS systems via a modem. Real-time communication is established with our "Teleservice" centre for communication of all alarms and events occurring in the installation.
Utilization Via Teleservice
When the optional JBUS RS232/485 communications board is installed, the time-stamped information can be sent to the Teleservice center.
The center can remotely consult the same information and carry out the same modifications as the user locally on the display. Note that only the Teleservice centre can reset the counters for the statistical data.
GTC Board
This electronic board provides user access to the J-Bus communications protocol. Using the data and address tables provided, the user can customize his installation.
GTC + Software
The user has access to the J-Bus protocol and, in addition, the associated software acquires system parameters (measurements, status conditions) and transforms them into diagrams, alarm messages and tables. With the click of a mouse, the user can locally or remotely supervise the UPS system (comprising one or many UPS units).
Appendices A — 1186-133060-00 A00
Page 90
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
AppendicesA — 12 86-133060-00 A00
Page 91
Installation and User Manual
Appendix C
Link to an IBM AS/400®Computer
The Galaxy PW™ can dialogue with an IBM AS/400®computer via a link in compliance with IBM communications recommendations, thus enhancing the protection provided by your Galaxy PW™.
The IBM AS/400®computer must be configured for the link. This section describes the physical connections required as well as the system values that must be modified on the AS/400®. For further information, consult the following IBM documents:
"Planning Guide, Appendix E" concerning physical connections.
"Back-up and Recovery Guide", chapter 7 "Power Loss Recovery" concerning configuration of the AS 400
®
.
Connect and Configure the AS400 Link
Connections are made to the female client connector XR5 on the "Media Contacts 11" board. The corresponding male connector is supplied; see Figure 3-12 below for the wiring diagram. A five-wire cable (not supplied) is required.
1. On the AS/400®side, use a 9 or 15-pin SUB-D connector. (Depending on the type of AS/400®.)
2. Certain values on the AS/400®must be configured to enable operation of the Galaxy PW™ — AS/400®link.
The values requiring modification and the corresponding procedures are presented in chapter 7 "Power Loss Recovery" of the "Back-up and Recovery Guide" for the AS/400®.
Configuration values:
QUPSMSGQ: UPS message queue;
QUPSDLYTIM: Uninterruptible power supply delay time;
QPWRRSTIPL: Power restore IPL.
Appendices A — 1386-133060-00 A00
Page 92
(This page left blank intentionally)
Galaxy PWTMUPS 100 to 225 kVA
A — 14 86-133060-00 A00
Page 93
MGE Warranty & Proprietary Rights for Three Phase Products
MGE Warranty
The liability of MGE UPS SYSTEMS, INC. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS, INC.’s factory or on the job site at MGE UPS SYSTEMS, INC.’s option, any part or parts which are defective, including labor, for a period of 12 months from the date of purchase. The MGE UPS SYSTEMS, INC. shall have the sole right to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to MGE UPS SYSTEMS, INC. for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, INC.’s Return Materials Authorization prior to returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, INC. will not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item, or for damage due to accident, abuse, or Act of God.
In no event shall the MGE UPS SYSTEMS, INC. be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS, INC. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. MGE UPS SYSTEMS, INC. is not liable for and Purchaser waives any right of action it has or may have against MGE UPS SYSTEMS, INC. for any consequential or special damages arising out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, INC. will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE UPS SYSTEMS, INC.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS SYSTEMS, INC. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the MGE UPS SYSTEMS, INC.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of the MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser but to no one else. Accessories supplied by MGE UPS SYSTEMS, INC., but manufactured by others, carry any warranty the manufacturers have made to MGE UPS SYSTEMS, INC.. and which can be passed on to Purchaser.
MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent. Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to Purchaser’s specific design.
Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS SYSTEMS, INC. be responsible for consequential damages or for any damages except as expressly stated herein.
Proprietary Rights Statement
The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in which MGE UPS SYSTEMS, INC., retains any and all patent rights, including exclusive rights of use and/or manufac­ture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, INC.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.
June 2004 Rev A01
Page 94
Galaxy PWTMUPS 100 to 225 kVA
86-133060-00 A00
Page 95
MGE Customer Care Center
Technical Support and Product Services
Technical questions? If you encounter a problem while following the instructions in
this manual, or have
questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS
SYSTEMS, INC.
Customer Care Center or visit our web site www.mgeups.com for complete service information.
To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial
number of the unit and include them in any discussions or correspondence.
Part Number: _____________________________________________________________________
Assembly Number: _____________________________________________________________________
Serial number: _____________________________________________________________________
Who To Contact
Technical Support:
1-800-
523-0142 (during business hours)
Customer Care Center:
1-800-438-7373
(Hours: 24/7)
Customer FAQ or
International calls:
1-714-557-1636
Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that will provide responses to any questions that you might have.
Scheduling Field Service Engineer Support
Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE toll free telephone number at
1-800-438-7373, to insure a safe installation and startup that will maintain
the MGE warranty and insure smooth performance
Return Policy for Repair (RMA)
Should you require factory service for your equipment, contact MGE’s Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RMA.
Date: ______________________________________________________
RMA Number: ______________________________________________________
Contact Name: ______________________________________________________
?
Page 96
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
W—4 86-133060-00 A00
Page 97
Glossary
Term used Definition/Meaning
@ At.
/ And/or.
+/- Plus or Minus.
Equal to or less than.
# Number.
°C Degree Celsius.
°F Degree Fahrenheit.
Ø Phase angle.
Ω Ohm. unit of resistance.
® Trade Mark.
2nd Second.
AC or ac Alternating current, also implies root-mean-square (rms).
Ambient Temp. Temperature of surrounding air.
Ambient noise Acoustical noise of surrounding environment.
ANSI American National Standard Institute.
AWG American Wire Gauge.
Breaker Electrical circuit interrupter.
BTU or Btu British thermal unit. Defined as the amount of heat required to raise the temperature of one
pound of water by 1°F.
BYPASS See “Static Transfer switch”.
BYPASS mode See “off-line mode”.
Carrier The company or individual responsible for delivering goods from one location to another.
C Common.
CB Circuit breaker.
cm Centimeter.
dB Decibels.
Glossary G — 186-133060-00 A00
Page 98
DC Direct current.
Conduit A flexible or rigid tube enclosing electrical conductors.
C.S.S. Customer Support Service.
Current rating The maximum current that a conductor or equipment can carry reliably without damage.
dBA Decibel Adjusted.
dBrnC Decibel above reference noise.
DC or dc Direct current, or voltage.
Digital Meter The LCD display on the front panel of inverter system.
Earth ground A ground circuit that has contact with the earth.
Electrician Refers to an installation electrician qualified to install heavy-duty electrical components in
accordance with local codes and regulations. Not necessarily qualified to maintain or repair electrical or electronic equipment.
FET Field effect transistor.
Freq. Frequency.
Frequency slew rate The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).
GND Ground (safety).
Hz Hertz, frequency measurement unit, 1Hz is one cycle per second.
Inverter mode See “on-line” mode.
I Current.
IEC International Electrotechnical Commission.
IEEE Institute of Electrical and Electronic Engineers.
Input branch circuit The input circuit from the building power panel to the equipment.
Inverter An electrical circuit that generates an AC voltage source from a DC voltage source.
IGBT Insulated gate bipolar transistors
kVA KiloVolt-Ampere. is equal to 1000 Volt-Ampere.
L Line.
LCD Liquid-Crystal Display unit.
LED Light Emitting Diode.
Mains or Mains 1 Main AC input source.
Mains 2 Bypass AC input source.
mA Milliampere.
MAX. Maximum.
Galaxy PWUPS 100 to 225kVA
GlossaryG — 2 86-133060-00 A00
Page 99
Glossary G — 386-133060-00 A00
MCM Thousand circular mil. standard wire sizes for multiple stranded conductors over 4/0
AWG in diameter. M is from Roman numerical system indicating 1000.
Module Refers to individual power inverter module.
N Neutral.
NC Normally close.
NO Normally open.
NEC National Electrical Code.
NFPA National Fire Protection Association.
NO. or No. Part number.
On-line mode Inverter output power is the primary energy source to load.
Off-line mode Inverter output is off, and the load connected at the inverter output receives power
from utility line via a static transfer switch or maintenance bypass relay.
OSHA Occupational Safety and Health Agency.
PCB Printed circuit assembly.
PCB Printed circuit board.
PWM Pulse Width Modulation.
SCR Silicon controlled rectifier.
Shipping damage Any damage done to an article while it is in transit.
SPDT Single Pole Double Throw.
Static Transfer An solid state switching mechanism electronically controlled to pass AC power direct-
ly from the utility to an output load.
Technician Refers to an electronic technician qualified to maintain and repair electronic equip-
ment. Not necessarily qualified to install electrical wiring.
Test connector DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer
Support Service technician to access programmable and diagnostic features of the system.
V Volts
VA Volt amperes
VA Volt-amps, unit for apparent power measurement, equal V x I.
VAC or Vac Voltage of AC type.
VDC or Vdc Voltage of DC type.
ve Battery voltage.
Via By way of.
Installation and User Manual
Page 100
(This page left blank intentionally)
Galaxy PWUPS 100 to 225kVA
G — 4 86-133060-00 A00
Loading...