MGE UPS Systems Galaxy PW 20 kVA, Galaxy PW 60 kVA, Galaxy PW 40 kVA, Galaxy PW 50 kVA, Galaxy PW 80 kVA Installation Manual

...
E-51028231XU/BH - 1
Installation manual
www.mgeups.com
MGE UPS SYSTEMS
Galaxy PW™
20 - 200 kVA
T
E
U
N
I
N
T
E
R
R
U
P
T
I
B
L
E
P
O
W
E
R
P
R
O
V
I
D
E
R
2 - E-51028231XU/BH
E-51028231XU/BH - 3
Contents
All products in the Galaxy PW range are protected by patents. They implement original technology not available to competitors of MGE UPS SYSTEMS.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by MGE UPS SYSTEMS.
This document may be copied only with the written consent of MGE UPS SYSTEMS. Authorised copies must be marked "Galaxy PW installation Manual, N° 51028231XU".
Characteristics
General characteristics of Galaxy PW UPSs ......................................................... 4
UPS cubicles........................................................................................................... 5
Empty battery cubicles ............................................................................................ 5
Electrical parameters for selecting protective devices ............................................ 5
Normal AC source ............................................................................................. 5
Bypass AC source............................................................................................. 6
Recommended protection ....................................................................................... 7
Protection upstream of Galaxy PW................................................................... 7
Protection downstream of Galaxy PW .............................................................. 7
Electrical parameters for determining cable cross-sections.................................... 7
Installation
Positioning the cubicles .......................................................................................... 9
Floor load ................................................................................................................ 9
Cubicle layout on a false floor or a normal floor...................................................... 9
Power-circuit wiring diagrams ................................................................................. 10
Connection of power circuits ................................................................................... 12
UPS cubicle....................................................................................................... 12
Battery cubicle................................................................................................... 15
Connection through the top ............................................................................... 16
External bypass cubicle 150 kVA ...................................................................... 17
External bypass cubicle 360 kVA ...................................................................... 18
External bypass cubicle 600 kVA ...................................................................... 19
Connection of the hot-swap option.................................................................... 20
Galaxy PW cubicle with a built-in harmonic filter .............................................. 20
Galaxy PW cubicle with a built-in bypass AC source isolation transformer...... 20
Bypass AC source isolation transformer in an auxiliary cubicle ........................ 21
THM filter........................................................................................................... 22
Connection of "Media Contacts 11" standard auxiliary circuits ............................... 23
Connection to battery circuit breaker "QF1" ...................................................... 23
Emergency power off ........................................................................................ 23
Connections between cubicles (parallel-connected configurations) ....................... 24
Connections between APOZ boards ................................................................. 24
Connections between MISI boards ................................................................... 24
Connections between UPS cubicles and the external bypass .......................... 25
Installation of communications options ................................................................... 25
Installation of boards ......................................................................................... 25
Passage of wires ............................................................................................... 25
Connection of the battery "Temperature Monitor"................................................... 26
Connections ...................................................................................................... 26
Installation of the "Temperature Monitor" in an MGE UPS SYSTEMS empty
battery cubicle ................................................................................................... 27
"Temperature Monitor" installation in a battery room ........................................ 27
Link to an IBM AS/400
®
computer........................................................................... 28
Connections ...................................................................................................... 28
Configuration of the AS/400
®
............................................................................. 28
Connection of the LED indications unit (optional) ................................................... 29
Final installation steps............................................................................................. 29
4 - E-51028231XU/BH
Characteristics
General characteristics of Galaxy PW UPSs
UPS power rating in kVA 20 30 40 50 60 80 100 120 160 200 Normal AC input
number of conductors 3 phases rated voltage and tolerances 380 V or 400 V or 415 V ± 10% (adjustable to ± 15%) rated frequency and tolerances 50 Hz or 60 Hz / ± 10% THDI with THM filter < 4% power factor with THM filter up to 0,96
Bypass AC input
number of conductors 3 phases + neutral rated voltage and tolerances 380 V or 400 V or 415 V / ± 10% rated frequency and tolerances 50 Hz or 60 Hz / ± 10%
Load
number of conductors 3 phases + neutral Ph/Ph voltages 380 V or 400 V or 415 V (according to setting) Ph/N voltages 220 V or 230 V or 240 V (according to setting) voltage fluctuations ± 1% adjustable frequency and tolerances (on battery power) 50 Hz or 60 Hz ± 0,05 Hz synchronisation with bypass ± 0,5 Hz (adjustable from ± 0,25 Hz to ± 2 Hz) voltage variation for 0 to 100% load step change ± 2% ((with battery) permissible overloads 150% for 1 minute, 125% for 10 minutes Isc Ph/Ph (% of I rated) 4.2 2.8 2.1 2.5 2.1 3.1 2.5 2.1 2.6 2.1 Isc Ph/N (% of I rated) 6.6 4.4 3.3 4 3.3 5 4 3.3 4 3.3 THDU Ph/Ph and Ph/N for linear load < 1,5% Ph/Ph, < 2% Ph/N THDU Ph/Ph and Ph/N for non-linear load < 2% Ph/Ph, < 3% Ph/N (at 80% of Pn) (1)
Battery
standard battery type gas-recombination sealed lead-acid battery
UPS characteristics
active power (kW) 16 24 32 40 48 64 80 96 128 160 efficiency at 50% load (%) 87.5 90.5 91.5 92.5 93 91 91.5 92 93 93.2 (values ± 1%) efficiency at 100% load (%) 91.5 92 91.5 93 92 92.5 92 91.5 92.8 92.5 (values ± 1%) heat losses (2) in KW 1.5 2.1 3.4 3.6 4.7 6.2 8.1 10.1 12.2 14.8
in cal./s 360 504 816 864 984 1488 1950 2420 2930 3550 storage temperature range -25 °C to +70 °C operating temperature range 0 °C to 35 °C (40 °C for 8 hours) relative humidity 95% maximum maximum operating altitude without derating < 1000 meters noise level (dBA) 58 58 58 60 60 62 64 65 67 68 dimensions (mm) width 715 1015 1215
depth 825
height 1400 or 1900 ± 10 1900 ± 10 weight (kg) (3) 450 450 450 490 490 800 800 800 1200 1200 recommended upstream earth-fault protection 1 A standards design IEC 146
product ENV 50091 safety IEC 950, ENV 50091 protection IEC 521 (cubicles 1400 mm high = IP 21, cubicles 1900 mm high = IP 20) electromagnetic compatibility IEC 62040, ENV 50091
(1): As per standards ENV 50091-3 / IEC 62040-3. (2): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system. (3): Not including any built-in options, such as harmonic filters or a bypass AC-source isolation transformer.
E-51028231XU/BH - 5
Empty battery cubicles
Characteristics of empty battery cubicles
Cubicle width Cubicle height Cubicle depth Maximum weight (1) in mm in mm in mm in kg
715 1400 ± 10 825 145
1900 ± 10 825 180
1015 1400 ± 10 825 185
1900 ± 10 825 230
Electrical parameters for selecting protective devices
Normal AC source
The parameters given in the table opposite can be used to determine the required rating of the upstream protective circuit breaker on the normal AC input for one single-UPS or parallel­UPS unit, a unit in economy mode or a frequency converter.
Important:
It is essential to choose the type of circuit breaker according to its breaking capacity and the prospective short­circuit current at its place of installation (see Schneider Electric LV documentation).
Note:
For normal AC source power supply voltages of 380, 400 and 415 V, the normal AC source current is the same because it is a function of the DC voltage.
Electrical parameters for the normal AC source
Rated Current normal AC source UPS Rated current In for unit: for 25% for 50% output with battery at start without battery (2) overload (3) overload (3)
in kVA of charge cycle (1)
20 36 33 41 50 30 53 49 62 74 40 71 66 83 100 50 88 83 103 124 60 107 100 125 150 80 142 133 166 200 100 179 166 208 249 120 214 199 249 299 160 282 262 329 397 200 358 329 414 501
UPS cubicles
Characteristics (cont.)
the cubicles are cooled by forced
ventilation. The air enters via the doors and grids at the bottom and is discharged through the back, or through the roof for the 1900 mm high cubicles (except the 160 and 200 kVA units from which the air is discharged through the roof only, which means the cubicles can be positioned against the back wall).
connections are made through the
bottom. Connections through the top are available on option for all 1900 mm high cubicles (except the 160 and 200 kVA units).
the connection cables may be run in
three ways:
in a trench running under the
cubicles,
under a false floor,on the floor under the cubicles, in the
free space equal to the height of the feet; in this case the cables should be run side by side to avoid blocking the flow of air for ventilation;
the cables for connections between:
the battery and UPS cubicles (power
and control cables);
the bypass AC-source transformer in
an auxiliary cubicle and the UPS cubicle can be supplied on option. Layout must comply with figures 5, 6 and 7. The other power cables for connections between cubicles are not supplied.
only the wires for the intercubicle
control connections between parallel­connected UPS units are supplied;
the cubicle doors are secured by
SOUTHCO locks (key CH751).
(1) the indicated weights are for the empty cubicles, without the batteries because the total battery weight may vary widely.
(1) the rated normal AC source currents (In) have been determined for a rated phase-to-phase voltage of 400 V, a battery with a 10 minute backup time at the beginning of its charge with 206 cells at 2 Volts per cell (412 Volts) and full rated load with a power factor of 0.8. (2) The rated normal AC source currents (In) have been determined for a minimum float charging voltage of 423 V and full rated load with a power factor of 0.8.
(3) the normal AC source currents given for an overload of 25% or 50% are maximum values. They have been determined for a battery with minimum float charging voltage and a load power factor of 0.8. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the values in the overload columns.
6 - E-51028231XU/BH
Electrical parameters for bypass AC source (415 V)
Rated UPS Current bypass AC source (1) output in kVA Rated current for 25% for 50%
In overload overload
20 29 36 43 30 43 53 64 40 58 73 87 50 72 90 108 60 87 108 130 80 116 145 174 100 144 180 216 120 174 218 261 160 231 289 347 200 289 362 434
Bypass AC source
The parameters given in the table opposite can be used to determine the required rating of the upstream protective circuit breaker on bypass AC input.
Important:
It is essential to choose the type of circuit breaker for bypass AC input according to its breaking capacity and the prospective short-circuit current at its place of installation (see Schneider Electric LV documentation). This choice must also be made so as to protect the static-switch semiconductors with respect to the maximum permissible currents (see table opposite) and ensure discrimination between the UPS output fuses (see the fuse curves in figures 1 and 2) and the downstream protection devices.
Remark:
If the installation includes a transformer on the bypass AC input, allow for the inrush current caused by magnetisation of the transformer windings.
UPS output Maximum permissible current in kVA
20 43 In for 20 ms 30 29 In for 20 ms 40 21 In for 20 ms 50 20 In for 20 ms 60 16 In for 20 ms 80 27 In for 20 ms 100 21 In for 20 ms 120 18 In for 20 ms 160 23 In for 20 ms 200 19 In for 20 ms
(1) the bypass AC source currents have been determined for a rated phase-to-phase voltage of 400 V, a load power factor of 0.8 and for full rated load as well as overloads of 25% or 50%. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the data in the overload columns.
For a bypass AC source voltage of 380 V, multiply the currents indicated in this table by 1.09. For a bypass AC source voltage of 400 V, multiply the currents indicated in this table by 1.04.
Fig. 1
Fig. 2
10
4
t(s)
I(A)
Galaxy PW 20 - 30 - 40 kVA
10
3
10
2
10
1
1
10-
1
10-
4
10-
3
10-
2
10210310
4
Galaxy PW 50 - 60 kVA
10
4
t(s)
I(A)
10
3
10
2
10
1
1
10-
1
10-
4
10-
3
10-
2
10210310
4
Galaxy PW 160 - 200 kVA
10
4
t(s)
I(A)
10
3
10
2
10
1
1
10-
1
10-
4
10-
3
10-
2
10210310
4
Galaxy PW 80 - 100 - 120 kVA
10
4
t(s)
I(A)
10
3
10
2
10
1
1
10-
1
10-
3
10-
2
10210310
4
10-
4
Characteristics (cont.)
E-51028231XU/BH - 7
Electrical parameters for determining cable cross-sections
Characteristics (cont.)
this table has been drawn up for
rated phase-to-phase AC source and load voltages of 400 V. For voltages of 380 V or 415 V, multiply the currents for the bypass AC source and the load by
1.05 and 0.96 respectively;
the current values and cable cross-
sections for the normal AC source are given for full rated load with a power factor of 0.8 and a battery consuming its minimum float charging voltage.
the battery current values and cable
cross-sections have been determined for a battery at the end of discharging;
the current values and cable sections
for the bypass AC source and load are given for full rated load with a power factor of 0.8. For frequency converters, the parameters concerning the bypass AC source are not applicable.
Parameters for cables for a single-UPS unit
Rated UPS Line currents absorbed in Amps Cross-sectional area of Cu cables in mm2 (2) output Normal AC source 400 V Battery Normal AC source 400 V Battery in kVA with or bypass AC with or without battery bypass AC
without battery (1) source and load source and load
20 33 29 52 16 16 16 30 49 43 72 25 25 25 40 66 58 103 35 35 35 50 83 72 128 50 35 50 60 100 87 154 50 50 70 80 133 116 205 95 or 2x50 70 95 or 2x50 100 166 144 256 95 or 2x50 70 2x70 120 199 174 308 95 or 2x50 70 2x70 160 262 231 410 95 95 2x95 200 329 289 512 120 120 2x95
(1) The rated normal AC source currents (In) have been determined for a minimum float charging voltage of 423 V and full rated load with a power factor of 0.8.
(2) the cable cross-sections are given for copper conductors (increase by 30% for aluminium conductors). They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m (AC circuits) or 25 m (DC circuits if cables not
Recommended protection
provided). For greater lengths, the cross-sections should be chosen to limit voltage drops to 3% (AC) or 1% (DC).
protection upstream of Galaxy PW
The information provided here is purely indicative, for a single-UPS unit supplied by a 380 to 415 V, 50 to 60 Hz distribution system. Check that all the criteria mentioned in the previous section are taken into account (short­circuit current and protection of the static-switch semiconductors on the bypass AC input).
Ratings of recommended protection devices upstream of a single-UPS unit (Merlin Gerin circuit breakers)
Rated UPS Circuit breaker on normal Circuit breaker on bypass output AC input AC input in kVA Circuit breaker Control unit Circuit breaker Control unit
20 NS 100N 3P TM 63D NS 100N 4P TM 63D 30 NS 100N 3P TM 63D NS 100N 4P TM 63D 40 NS 100N 3P TM 80D NS 100N 4P TM 80D 50 NS 100N 3P TM 100D NS 100N 4P TM 100D 60 NS 125E 3P TM 125D NS 125E 4P TM 125D 80 NS 160N 3P TM 160D NS 160N 4P TM 160D 100 NS 250N 3P TM 200D NS 250N 4P TM 200D 120 NS 250N 3P TM 250D NS 250N 4P TM 250D 160 NS 400N 3P STR 23 SE NS 400N 4P STR 23 SE 200 NS 400N 3P STR 23 SE NS 400N 4P STR 23 SE
Protection downstream of Galaxy PW
These protection devices ensure discrimination for each of the Galaxy PW output circuits. If the recommended downstream protection is not installed and a short-circuit occurs, the result may be a break longer than 20 ms on all the other output circuits.
Ratings of recommended protection devices downstream of a single-UPS unit (Merlin Gerin circuit breakers)
Rated UPS Downstream circuit output breaker(s) in kVA Circuit breaker Control unit
20 to 40 kVA C60N C 10A
B 20A
50 to 60 kVA C60N C 20A
B 32A
80 to 120 kVA C60N C 50A
NC100 B 63A
160 to 200 kVA NC100 C 63A
B 100A
8 - E-51028231XU/BH
Parameters for bypass AC source and load cables for a parallel UPS configuration
Rated unit Number of Total UPS Bypass AC Cable cross­output parallel- rated output source or load section (1) in kVA connected in kVA line current in mm
2
units in Amps
20 2 405835
3 608750 4 80 116 50
30 2 608650
3 90 129 70 4 120 172 70
40 2 80 116 50
3 120 174 70 4 160 232 120
50 2 100 144 70
3 150 216 95 4 200 288 150
60 2 120 174 70
3 180 261 120 4 240 348 185
80 2 160 232 120
3 240 348 185 4 320 464 2x95
100 2 200 288 150
3 300 432 185 4 400 576 2x120
120 2 240 348 185
3 360 522 2x120 4 480 696 2x150
160 2 320 462 2x95
3 480 693 2x150 4 640 924 3x120
200 2 400 578 2x120
3 600 866 2x185 4 800 1155 3x185
(1) cable cross-sections are given for copper conductors of the U1000 R02V type (increase by 30% for aluminium conductors). They are calculated according to permissible temperature rise and allow for line voltage drops over a
The table opposite serves as an example for a parallel-connected installation comprising up to four UPS units.
for installations with redundant units,
take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel­connected UPS units, one being redundant, only 2 UPS units are used to determine bypass AC source and load currents and cable cross­sections);
this table has been drawn up for
rated phase-to-phase bypass AC source and load voltages of 400 V and full rated load with a power factor of
0.8. For voltages of 380 V or 415 V, multiply the indicated currents by 1.05 and 0.96 respectively, then modify the cable cross-sections accordingly, if necessary. The cable cross-sections in this table concern the parts illustrated in bold in the simplified diagram in figure 3, where:
1: normal AC source, 2: bypass AC source, A: external bypass.
maximum length of 100 m. For greater lengths, the cross-sections should be chosen to limit voltage drops to 3%.
Fig. 3
A
2
1
2
1
2
1
2
Galaxy 2
Galaxy 3
Galaxy 1
Characteristics (cont.)
E-51028231XU/BH - 9
Installation
(qualified personnel only)
Positioning the cubicles
prior to moving the cubicles to their
final position, remove the packing material and the base panels which were shipped on top of the cubicle. The panels will be installed at the end of the installation procedure;
after moving them to their installation
location on their pallets, cubicles can be moved short distances using a forklift or pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 100 mm ±10 mm high openings;
adjust the front foot pads to make the
cubicle vertical and align the subsequent cubicles.
Note:
Dispose of packing materials in compliance with applicable legislation.
Floor loads
See figure 4, where:
A: the rear panel of the cubicle, B: the width of the cubicle, minus
139 mm (see page 5),
C: the four foot pads (diameter
40 mm),
D: the front panel of the cubicle.
to determine the stresses applied by
the cubicle on the floor, divide the cubicle weight (see the first 3 tables of this manual) by the total area of the 4 footpads (50 cm
2
).
Fig. 4
Cubicle layout on a false floor or a normal floor
see figure 5 for a single-UPS Galaxy
PW unit with a single battery cubicle;
see figure 6 for a single-UPS Galaxy
PW unit with several battery cubicles;
see figure 7 for two parallel-connected
Galaxy PW units with battery and auxiliary cubicles.
an overall clearance of 400 mm must
be left above the entire surface of the cubicles for ventilation;
in rooms with unrestricted access,
install a fire-protection system under the UPS cubicle.
Key for figures 5 to 7: A: the width W of the cubicle (see the
table in the Characteristics section on page 5),
B: the openings to be made for cables
coming up through a false floor: 65 x 430 mm for 20 to 60 kVA UPS, 200 x (L-160) mm for 80 to 200 kVA UPS,
C: the position of a trench under the
cubicles, if applicable,
D: front of cubicles E: back of cubicles 1: the battery cubicle containing circuit
breaker QF1,
2: a second battery cubicle, 3: the UPS cubicle, 4: an auxiliary cubicle, if applicable.
Fig. 5 Fig. 6
Fig. 7
69,5
676
B
C
82
6767
82
69,5
A
D
4
1
3413
E
D
2 13
E
D
(*) :
The Galaxy PW 20 to 120
kVA must be installed at a distance of at least 250 mm
from a wall;
Galaxy PW 160 and 200 may be
positioned against a wall;
It is advised that, whenever
possible, the units be installed at a distance of 400 mm from a wall, in order to facilitate their inspection during preventive maintenance.
(*)
1
A
80
825
> 850
A
3
B
C
E
D
10 - E-51028231XU/BH
2
1
C
B
A
Q4S
D
+
+
E
F
QF1
Q1 Q5N
Galaxy PW
F
G
Q3BP
Power-circuit wiring diagrams
The single-wire diagrams for typical UPS installations are given in figures 8 to 11. The heavy lines represent the cables that must be connected (see the table in the previous chapter for the required cross-sectional areas of the cables).
see figure 8 for a single-UPS
Galaxy PW unit;
see figure 9 for a two parallel Galaxy
PW units combined for redundancy.
see figure 10 for a two parallel Galaxy
PW units combined for higher output;
see figure 11 for a Galaxy PW
frequency converter without a battery;
Key for figures 8 and 9: 1: normal AC source, 2: bypass AC source, A: the rectifier/charger module, B: the inverter module, C: the static-bypass module, D: the battery cubicle next to the
Galaxy PW UPS cubicle, E: any additional battery cubicles, F: the equipotential-bonding
connection between cubicles, G: K3N contactor or output static-
switch module.
Fig. 8
Fig. 9
2
1
C
B
A
Q4S
D
+
+
E
F
QF1
Q1 Q5N
Galaxy PW
F
G
2
1
C
B
A
Q4S
D
+
+
E
F
QF1
Q1 Q5N
Galaxy PW
F
G
2
Q3BP
Q3BP
Galaxy PW single-UPS unit
Galaxy PW parallel connection for redundancy
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 11
Key for figures 9 and 10: 1: normal AC source, 2: bypass AC source, A: the rectifier/charger module, B: the inverter module, C: the static-bypass module, D: the battery cubicle next to the
Galaxy PW UPS cubicle, E: any additional battery cubicles, F: the equipotential-bonding
connection between cubicles, G: K3N contactor or output static-
switch module.
Fig. 11
Fig. 10
2
1
C
B
A
Q4S
D
+
+
E
F
QF1
Q1 Q5N
Galaxy PW
F
G
2
1
C
B
A
Q4S
D
E
F
QF1
Q1 Q5N
Galaxy PW
F
G
2
Q3BP
Q5N
Q4S
+
+
1
B
A
Q1 Q5N
Galaxy PW
G
Galaxy PW parallel connection for greater capacity
Galaxy PW frequency converter without a battery
Installation (cont.)
(qualified personnel only)
12 - E-51028231XU/BH
Connection of power circuits
Before making connections, check that switches Q1, Q4S, Q3BP, Q5N and QF1 are in the
"open" position.
General:
Remark. See page 4 for information on the supplied cables and wires.
open the doors and remove the lower
terminal shields (secured by screws to the cubicle chassis) of the UPS cubicles;
connect the power cables; each cubicle must be earthed; all the cubicles must be
interconnected for equipotential bonding, forming a mesh which is itself connected to the building structure and earthing electrode;
the connection drawings hereafter
show the cubicles with doors open and terminal shields removed.
Important:
For parallel UPSs with an external bypass unit, the power connections between each UPS cubicle and the external bypass unit must imperatively be of the same length. Outside the cubicles, separate the auxiliary wiring from the power cables.
UPS cubicle
See figure 12 for 20 to 60 kVA units, and figure 13 for 80 to 120 kVA units, and figure 14 for 160 to 200 kVA units. Battery + and - cables are connected by lugs on 8 mm diameter pins for 20 to 120 kVA units, or by lugs on 12 mm diameter holes for 160 to 200 kVA units. Normal/Bypass AC input and load cables are connected by tunnel terminals to the 20 to 60 kVA units, or by lugs on 10 mm diameter holes to the 80 to 120 kVA units. Elevation of connections from ground for 20 to 60 kVA units:
normal/bypass AC input and load: 310
mm;
battery: 280 mm.
Elevation of connections from ground for 80 to 120 kVA units:
normal/bypass AC input and load: 340
mm;
battery: 310 mm.
Elevation of connections from ground for 160 to 200 kVA units:
normal/bypass AC input and load: 410
mm;
battery: 410 mm.
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 13
1, 2, E
F
D
C
H
G
G
I J
H
F
L1L2L3N
E
L1L2 L3
1
K
N
O
P
2
L
M
A
A
W
S M
R
G
Q
V
Y
T
U
BAA
80 - 100 - 120 kVA
Q1
Q4S
Q5NQ3BP
X
L1L2L3N
Fig. 12
Key to figures 12 and 13: AA: cross-sectional view of the cubicle, B: front view of the cubicle, C: front panel, D: rear panel, 1: normal AC input connection, 2: bypass AC input connection, E: load connection, F: battery connection, G: air inlets, H: air outlets, I: cable exit through the bottom, J: trough, if applicable, K: rectifier/charger module, L: inverter module, M: static-bypass module, N: rack containing electronic boards, O: Media Contacts 11 board, P: slot for communications boards, Q: FUE input fuses, R: FUS output fuses, S: ETOI board (20 to 60 kVA UPS) or
RELI board (80 to 200 kVA UPS),
T: APOZ board, U: MISI board, V: modem socket switch, W: trough (20 to 60 kVA) or binding bar
(80 to 200 kVA) for fine wiring, X: fuses for overvoltage protection RC
circuit on bypass, Y: control-wire connection (auxiliary
"Media Contacts 11" circuits and
communications options).
Notes:
Figure 12. Switch Q3BP does not exist in parallel Galaxy PW cubicles interconnected for greater capacity. Figure 13. Switch Q3BP and "X" (protection fuses) do not exist in parallel Galaxy PW cubicles interconnected for greater capacity. The bypass AC source ("2") connects to switch Q4S.
Fig. 13
Installation (cont.)
(qualified personnel only)
Q1 Q5N
L1L2 L3N
L1L2L3
Q4S
L1L2 L3N
Q3BP
A
S
R
O P
T
U
N
W
V
BAA
20 - 30 - 40 - 50 - 60 kVA
C
G
1, 2, E
F G
H
H
D
G
F
E
1
2Y
K, L, M
A
Q
I J
Q1 Q5N
L1L2 L3N
L1L2L3
Q4S
L1 L2 L3
Q3BP
F
E
1
2Y
Galaxy PW cubicle with built-in bypass AC-input isolation transformer (option)
14 - E-51028231XU/BH
H
G
G
H
F
E
1
P
2
G
Y
160 - 200 kVA
Q1
Q4S
Q5NQ3BP
L1
L2L3N
L1L2L3
L1
L2L3N
M Q
S
L
A
B
M
N
T
W
U
R
A
X
J
I
1, 2, E,F
D
C
AA
K
V
O
Key to figure 14: AA: cross-sectional view of the cubicle, B: front view of the cubicle, C: front panel, D: rear panel, 1: normal AC input connection, 2: bypass AC input connection, E: load connection, F: battery connection, G: air inlets, H: air outlets, I: cable exit through the bottom, J: trough, if applicable, K: rectifier/charger module, L: inverter module, M: static-bypass module, N: rack containing electronic boards, O: Media Contacts 11 board,
Fig. 14
P: slot for communications boards, Q: FUE input fuses, R: FUS output fuses, S: ETOI board (20 to 60 kVA UPS) or
RELI board (80 to 200 kVA UPS),
T: APOZ board, U: MISI board, V: modem socket switch, W: trough (20 to 60 kVA) or binding bar
(80 to 200 kVA) for fine wiring,
X: fuses for overvoltage protection RC
circuit on bypass,
Y: control-wire connection (auxiliary
"Media Contacts 11" circuits and communications options).
Note:
Figure 14. Switch Q3BP does not exist in parallel Galaxy PW cubicles interconnected for greater capacity. The bypass AC source ("2") connects to switch Q4S.
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 15
Battery cubicle
See figure 15. The battery cubicle shown is an example only, given that characteristics of these cubicles vary greatly from one cubicle to another.
remove the cardboard covers and all
the hooping (used only for transport);
remove the terminal shield from the
battery circuit breaker "QF1" to make the connections to this circuit breaker;
in the case of installations having
several battery cubicles, the connections to be made between cubicles are indicated in the instructions accompanying the cubicles (or in the drawing file for complicated installations);
in the case of a UPS with a power
rating from 80 to 120 kVA and connection via the top, the battery cubicle containing circuit-breaker QF1 cannot be connected to the UPS cubicle via the bottom. A roof equipped with a cable gland can be installed on this battery cubicle in order to connect it directly via the top to the inverter cubicle. Please contact our after-sales service.
Important:
the cubicle is supplied with a fixture
locking circuit breaker "QF1"in the open position. Do not remove this fixture before commissioning. Accidental closing of "QF1" will power up the downstream circuits which could be hazardous for personnel and permanently damage the battery by deep discharge;
connections between battery cubicles
should be made in compliance with applicable regulations. Take all protective measures associated with working on live equipment and in particular use only qualified personnel equipped with gloves, protective
goggles, insulated tools, etc. Cables are connected to copper
terminals by lugs.
Note:
The optional "Temperature Monitor" unit is located at the top in one of the battery cubicles. The cubicles not fitted with a battery circuit breaker include an additional shelf for battery cells.
Key to figure 15: AA: cross-sectional view of the cubicle, B: front view of the cubicle, C: front panel, D: rear panel, E: cable ties to duckboard shelf, F: cable exit through the bottom, G: trough, if applicable, H: connection of exposed conductive
parts to duckboard shelf, I: cable exit to battery connection
point in UPS cubicle, J: cable exit to an additional battery
cubicle, if applicable,
K: cable ties to duckboard shelf, L: fixture locking circuit breaker "QF1"
in the open position.
Fig. 15
XR1
QF1
+
+
D
C
A
A
LK
I
J
F G
E
H
BAA
Installation (cont.)
(qualified personnel only)
16 - E-51028231XU/BH
Connection through the top
(20 to 120 kVA units) This type of connection is possible on
1900 mm high cubicles. See figure 16.
Key to figure 16: AA: cross-sectional view of the cubicle, B: front view of the cubicle, C: front panel, D: rear panel, 1: normal AC input connection, 2: bypass AC input connection, E: load connection, F: battery connection, I: air outlet grid, J: passageway for cables exiting
through the top (opening 460 x 197 mm with cable-gland plate),
K: top view of the cubicle. Note:
For 160 to 200 kVA units, this option is not available because air is discharged through the top. However, it is possible to run normal/bypass AC input and load cables through an auxiliary cubicle (empty or containing an optional harmonic filter or bypass AC-input isolation transformer). In this case, the cables enter through the standard opening in the top and exit through the bottom of the cubicle.
Fig. 16
AA
I
J
F
L+L-1L3L2 L1
2
L2L1 NL3
E
L2L1 NL3
F, 1, 2, E
A
B
K
20 - 30 - 40 - 50 - 60 - 80 - 100 - 120 kVA
DC
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 17
15,5
15
L1
L2
L3
N
L1
L2
L3
N
G
H
750
E
D
F
L1
L2
L3
N
800
857,5
XM8
"MISI" 1
1 2
Q3BP + Q3BP –
XM9
1 2
Q4S + Q4S –
XM8
"MISI" 2
1 2
Q3BP + Q3BP–
XM9
1 2
Q4S + Q4S –
"MISI" 3 "MISI" 4
Q4S
Q3BP
150 kVA
A
B
1000950 1057,5
120
303
317
1234
L1
L2
L3
N
Q4S
Q3BP
Q5N
C
317
56
Q5N
Fig. 17
External bypass cubicle 150 kVA
See figure 17.
Key to figure 17: A: bottom view of the unit, B: front view of the unit, C: passageway for cables
(317 x 120 mm), D: bypass AC input connection for the
UPS units, E: connections for auxiliary wiring
indicating the position of the Q4S
and Q3BP switches,
F: connection for the UPS-unit outputs, G: bypass AC input connection, H: load connection.
Installation (cont.)
(qualified personnel only)
18 - E-51028231XU/BH
Fig. 18
External bypass cubicle 360 kVA
See figure 18.
Key to figure 18: AA: cross-section AA of cubicle, B: cubicle front view, C: front panel, D: bypass AC input connection for the
UPS units,
E: connection of the auxiliary position
wires of switches "Q4S" and "Q3BP",
F: connection of UPS load outputs, G: bypass AC input connection, H: connection of load, I: air outlet grid, J: opening of 460 x 197 mm for cable
insertion,
K: fuses for overvoltage protection RC
circuit on bypass (to be replaced when the indicator light is on).
L: top view of cubicle
C
D
G
H
F
E
A
1900
A
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
L1
L2
L3
N
H
G
E
K
I
J
B AA
L
XM8
"MISI" 1
1 2
Q3BP + Q3BP -
XM9
1 2
Q4S + Q4S -
XM8
"MISI" 2
1 2
Q3BP + Q3BP -
XM9
1 2
Q4S + Q4S -
"MISI" 3 "MISI" 4
E
Q4S
Q3BP
1234
360 kVA
Q4S
Q3BP
Q5N
N
D
F
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 19
Fig. 19
External bypass cubicle 600 kVA
See figure 19.
Key to figure 19: AA: cross-section AA of cubicle, B: cubicle front view, C: front panel, D: bypass AC input connection for the
UPS units, E: connection of the auxiliary position
wires of switches "Q4S" and
"Q3BP",
C
D
E
AA
A
A
H
G
B
D
E
Q4S
Q3BP
Q5N
G
H
F
I
J
XM8
"MISI" 1
1 2
Q3BP + Q3BP -
XM9
1 2
Q4S + Q4S -
XM8
"MISI" 2
1 2
Q3BP + Q3BP -
XM9
1 2
Q4S + Q4S -
"MISI" 3 "MISI" 4
E
Q4S
Q3BP
1234
600 kVA
L
F
F: connection of UPS load outputs, G: bypass AC input connection, H: connection of load, I: air outlet grid, J: opening of 460 x 197 mm for cable
insertion,
L: top view of cubicle
Installation (cont.)
(qualified personnel only)
20 - E-51028231XU/BH
Connection of the Hot Swap option
The external bypass may be used to construct a bypass outside the UPS, thus making it possible to shutdown the UPS for maintenance purposes. The option may be used for single-UPS units and redundant parallel UPSs.
control-wire connections are not
required between the bypass unit and the UPS unit(s);
see figure 20 for the power-circuit
connections of a single-UPS unit and figure 21 for the power-circuit connections of redundant parallel UPSs. Power cables for UPS-to-bypass connections are not supplied.
Galaxy PW cubicle with built-in bypass AC-input isolation transformer
(20 to 60 kVA UPSs) For this option, the cubicle is 1900 mm
high. This isolation transformer is installed in the top part of the cubicle. Power connections are not modified by this option (see figure 22).
Installation (cont.) (qualified personnel only)
C
B
A
Q4S
Q1 Q5N
Galaxy PW
Q3BP
2
1
D
+
+
E
F
QF1
F
G
Q4S
2
Q3BP
Q5N
C
B
A
Q4S
Q1 Q5N
Galaxy PW
Q3BP
2
1
D
+
+
E
F
QF1
F
G
Q4S
2
Q3BP
Q5N
Fig. 20
Fig. 21
C
B
A
Q4S
Q1 Q5N
Galaxy PW
Q3BP
2
1
D
+
+
E
F
QF1
F
2
1
D
+
+
E
F
QF1
F
C
B
A
Q4S
Q1 Q5N
Galaxy PW
Q3BP
G
G
Q4S
2
Q3BP
Q5N
Fig. 22
E-51028231XU/BH - 21
Fig. 23
Mains 2 isolation transformer in an auxiliary cubicle
The cubicle is 1900 mm high. See figure 23 (20 to 120 kVA units) and figure 24 (160 to 200 kVA units).
Key to figures 23 and 24: AA: cross-sectional view of the cubicle, B: front view of the cubicle, C: front panel, D: rear panel, E: bypass AC input connection
(terminals A, B, C or A1, B1, C1
(+ 5%), F: bypass AC input connection to
UPS(s) - terminals n, a, b, c,
G: air inlets, H: air outlets, I: cable exit through the bottom, J: trough, if applicable, K: bypass AC input isolation
transformer,
L: passage of cables through the top, M: passageway for cables exiting
through the top (opening 460 x
197 mm with cable-gland plate),
N: air outlet grid, O: top view of the cubicle.
D
C
G
H
G
H
G
L
B
AA
O
I
J
L1L2 L3
L1L2L3N
E F
M N
A
715
K
20 - 30 - 40 - 50 - 60 80 - 100 - 120 kVA
A
Fig. 24
D
C
G
H
G
H
G
L
A
B
AA
O
I
J
FE
M
A
1015
K
160 - 200 kVA
L1L2 L3
L1L2L3N
N
E,F
Installation (cont.)
(qualified personnel only)
22 - E-51028231XU/BH
Fig. 25
THM filter
This option is installed on the normal AC input upstream of the Galaxy PW UPS cubicle. The cubicle is 1900 mm high.
20 to 120 kVA units, width of auxiliary
cubicle = 715 mm
160 to 200 kVA units, width of
auxiliary cubicle = 1015 mm For THM-filter installation and connections, see manual No. 51024338.
Key to figure 25: 1: normal AC input 2: bypass AC input A: Galaxy PW UPS cubicle B: THM filter.
1
2
A
Galaxy PW
THM
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 23
Fig. 26
Connection of "Media Contacts 11" standard auxiliary circuits
See figure 26 below for information on connecting the auxiliary circuits to the three connectors on the "Media Contacts 11" board in the Galaxy PW UPS cubicle. See the position of this board, marked "O" in figures 12 to 14.
recommended cable cross-section:
1mm2;
the male connectors that fit the female
connectors on the board (XR2 to XR5) are supplied;
the contacts are volt-free and are
shown in the diagram under the following conditions: UPS on, contact at rest;
contact breaking capacity: 250 V, 5 A.
Connection to battery circuit breaker "QF1"
connect the cable from connector
XR3 (pins 2 to 8) on the "Media Contacts 11" board in the UPS cubicle to connector XR1 in the battery cubicle containing battery circuit breaker QF1.
Emergency power off
The UPS emergency shutdown function is generally wired to a "mushroom­head" type emergency-off button.
Important:
In the case of a complex installation with a number of units, there should be only one emergency shutdown pushbutton and this pushbutton must interrupt all the active conductors of all the units. For the same reason, it is essential for the pushbutton to open the upstream protective circuit breakers on the normal and bypass inputs. Each type of unit (single UPS, parallel UPS, frequency converter) must have an independent, volt-free contact connected to the emergency shutdown pushbutton. This pushbutton must therefore have as many contacts as there are units in the installation, as well as the contact or contacts required to open the upstream protective circuit breakers on the normal and bypass inputs. The emergency shutdown pushbutton turns off the rectifier/ chargers and inverters, opens the battery circuit breakers and activates a contact on the "Media Contacts 11" board (terminals 1 to 3 on connector XR4). The emergency shutdown signal will be cleared when the emergency shutdown pushbutton contact has been reset.
Media Contacts 11" board
10
1
12
1
XR2 XR3
10
1
XR4
10
1
XR5
XR2
XR3
XR4
XR5
12
10
1
10
1
10
1
1
XR1
10
9 8 7 6 5
4 3 2 1
XR4 connector
output signals:
general alarm
NC
low-battery shutdown warning
10
9
8 7
6
5
4
3 2 1
XR5 connector
output signals:
load on battery
load on inverter
+12V
24V CC
–12 V
XR3 connector
input or output signals:
4 3
2
1
QF1 battery circuit-breaker closed
QF1 battery circuit-breaker opening command
battery cubicle
XR1 terminal block
10
9 8 7 6 5 4 3 2 1
free auxiliary contact
+12 V
NC
NC
QF1 battery circuit-breaker opening command
XR2 connector
input or output signals:
connection with optional electronic board for measuring battery temperature
battery-room ventilation fault
emergency-shutdown button contact (jumper if not used)
temperature signal
power supply
earth
NC NC
12
11
10
9 8 7 6 5 4 3 2 1
2 1
thermal monitoring of the harmonics-filter inductor
harmonic-filter cubicle
XR1 terminal block
and/or harmonics filter temperature fault
+12 V
NC
–12 V
complete system shutdown
maintenance position
NC
Installation (cont.)
(qualified personnel only)
24 - E-51028231XU/BH
Connections between cubicles (parallel-connected configurations)
These connections are made on the APOZ board (marked T in figures 12 to
14) and MISI board (marked U).
Important:
Outside the cubicles, group the "APOZ" inter-board and "MISI" inter­board connections with the inter-cubicle auxiliary connections, and separate
this assembly using power cables.
Connections between APOZ boards
See figure 27.
these connections are made using the
cables (A) supplied;
the purpose of the connection is to
make a loop. Connector XM137 on the APOZ board of one UPS unit must be connected to connector XM136 on the APOZ board of the next UPS unit and so on until the first board is returned to.
Connections between MISI boards
See figures 28, 29 and 30.
these connections are made using the
special cables (A) supplied;
connectors XM5, XM6 and XM7 on
the MISI board are used to transmit signals;
connectors XM10, XM11 and XM12
on the MISI board are used to receive signals;
connector XM5 is associated with
connector XM10 for communication with one UPS unit; similarly, XM6 is associated with connector XM11 for communication with a second UPS unit and XM7 is associated with connector XM12 for communication with a third UPS unit;
situation with two parallel UPS units:
see figure 28;
situation with three parallel UPS units:
see figure 29;
situation with four parallel UPS units:
see figure 30.
Fig. 27
Fig. 28
Fig. 29
XM137
XM136
XM137
XM136
XM137
XM136
"APOZ" Galaxy PW 1
"APOZ" Galaxy PW 2
"APOZ" Galaxy PW 3
A
"MISI" Galaxy PW 1
"MISI" Galaxy PW 2
A
XM5
XM6 XM7
XM10
XM11
XM12
XM5
XM6
XM7
XM10
XM11
XM12
"MISI" Galaxy PW 1
"MISI" Galaxy PW 2
XM5
XM6
XM7
XM10
XM11
XM12
XM5
XM6
XM7
XM10
XM11
XM12
"MISI" Galaxy PW 3
XM5
XM6
XM7
XM10
XM11
XM12
A
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 25
Fig. 30
Connections between UPS cubicles and the external bypass
the recommended cross-sectional
area of control wires is 1 mm
2
. Wires
are not supplied;
in non-redundant parallel UPS
systems (increased output), the UPS units must be connected to the external bypass unit (see figures 17, 18 and 19):
terminals 1 and 2 on connector XM8
of the MISI board of the UPS to terminals 1 and 2 on the external bypass for indications on the position of switch Q3BP,
terminals 1 and 2 on connector XM9
of the UPS to terminals 3 and 4 on the external bypass for indications on the position of switch Q4S.
Installation of communications options
Three slots are available on the "Media Contacts 11" board for communications options. See the position of these slots marked "P" in figures 12 to 14.
Installation of boards
boards may be installed with the UPS
on, without removing the protective covers;
boards must be pushed to the end of
the slots to ensure correct installation;
board front plates must be screwed to
the protective "Media Contacts 11" board cover.
Passage of wires
holes are provided in the support for
the "Media Contacts 11" board for tying down the wires;
the control wires must then be routed
through the cableway marked "W" in figures 12 to 14.
"MISI" Galaxy PW 1
"MISI" Galaxy PW 2
XM5
XM6
XM7
XM10
XM11
XM12
XM5
XM6
XM7
XM10
XM11
XM12
"MISI" Galaxy PW 3
XM5
XM6
XM7
XM10
XM11
XM12
"MISI" Galaxy PW 4
XM5
XM6
XM7
XM10
XM11
XM12
A
Installation (cont.)
(qualified personnel only)
26 - E-51028231XU/BH
Connection of the battery "Temperature Monitor"
Connections
This unit must be connected to the XR2 connector on the remote indications "Media Contacts 11" board of the UPS cubicles. See the location of the "Media Contacts 11" board, marked "O" in figures 12 to 14 in the Appendix.
use a shielded cable made up of 2
twisted telephone pairs with a conductor cross-section of at least
0.1 mm
2
, not longer than 100 m in
length;
do not forget to connect the cable
shield to ground pin 12 on connector XR2;
in the case of a parallel UPS
configuration, the connections between cubicles may be made by means of a shielded cable made up of 1 or 2 twisted telephone pairs. In this case, the total length of all the connecting cables must not exceed 100 m;
a "Temperature Monitor" unit can be
connected to several UPS cubicles only when the batteries of these cubicles are located in the same room at the same ambient temperature.
Connection of the battery "Temperature Monitor" (single-UPS unit)
Fig. 31
Fig. 32
Connection of the battery "Temperature Monitor" (n parallel UPS units with batteries in same room)
XR2 connector on "Media Contacts 11" board:
12 11 10
9 8 7 6 5 4 3
battery "Temperature Monitor"
XR2
XR1
(unit shown open)
–12 +12
BC+ BC–
shielded cable (2 twisted telephone pairs)
temperature signal
12V
+
12V
earth
BC
+
BC
power supply
2 1
temperature signal
earth
BC
+
BC
temperature signal
NC
BC + BC –
XR2 connector on "Media Contacts 11" board in Galaxy PW unit 1:
12 11 10
9
8 7 6
5
4
3
battery "Temperature Monitor"
XR2
XR1
(unit shown open)
–12 +12
BC+ BC–
shielded cable (2 twisted telephone pairs)
12
11 10
9 8 7
XR2 connector on "Media Contacts 11" board in Galaxy PW unit 2:
XR2 connector on "Media Contacts 11" board in Galaxy PW unit n:
12 11 10
9
8
7 6
5
4
3
temperature signal
–12V +12V
earth
NC
BC + BC –
power supply
6
2
1
5 4
3
2
1
shielded cable (1 or 2 twisted telephone pairs)
earth
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 27
QF1
to UPS cubicle
battery cubicle
tie the cable to the cubicle upright
"Temperature Monitor" unit
Installation of the "Temperature Monitor" in an MGE UPS SYSTEMS empty battery cubicle
The "Temperature Monitor" unit is placed inside the battery cubicle housing circuit-breaker QF1 (see figure
33):
open the unit cover; before fixing, break the self-cleavable
seal on the base of the unit for insertion of the connecting cable;
fix the unit on the plate using the self-
adhesive sticker and a screw (nut and washer combination, diameter 4 mm, length 16 mm, not supplied);
connect and put back the cover; the temperature sensor MUST be
placed at the top of the cubicle to work properly;
tie the connecting cable to the cubicle
upright so that it does not pull on the unit.
Installing the "Temperature Monitor" in a battery cubicle
Fig. 33
"Temperature Monitor" installation in a battery room
The "Temperature Monitor" should be secured against a wall or any vertical support.
choose a location near the batteries
and away from draughts which adversely affect the accuracy of temperature measurements;
use the holes provided in the base
plate to screw the unit to the vertical support (see figure 34);
unless the connecting cable runs on
the surface, break the knock-out in the unit base plate provided for cable entry,
secure the cable by suitable means
so that it does not pull on the unit.
"Temperature Monitor" base
dimensions du coffret : 75 x 75 x 21 mm
Fig. 34
board
oblong hole for fastening screw
knock-out for lateral cable entry
oblong hole for fastening screw
Installation (cont.)
(qualified personnel only)
28 - E-51028231XU/BH
Link to an IBM AS/400® computer
The Galaxy PW can dialogue with an IBM AS/400
®
computer via this link in compliance with IBM communications recommendations, thus enhancing the protection provided by your Galaxy PW. The IBM AS/400
®
computer must be configured for the link. This document presents the physical connections required as well as the system values that must be modified on the AS/400
®
. For further information, consult the following IBM documents:
"Planning Guide, Appendix E"
concerning physical connections;
"Back-up and Recovery Guide",
chapter 7 "Power Loss Recovery" concerning configuration of the AS 400
®
.
Connections
connections are made to the female
client connector XR5 on the "Media Contacts 11" board;
the corresponding male connector is
supplied;
see figure 35 below for the wiring
diagram. A five-wire cable (not supplied) is required;
on the AS/400
®
side, use a 9 or 15-pin SUB-D connector, depending on the type of AS/400
®
.
Configuration of the AS 400
®
Certain values on the AS/400® must be configured to enable operation of the Galaxy PW - AS/400
®
link. The values requiring modification and the corresponding procedures are presented in chapter 7 "Power Loss Recovery" of the "Back-up and Recovery Guide" for the AS/400
®
.
The values are the following:
QUPSMSGQ: UPS message queue; QUPSDLYTIM: Uninterruptible power
supply delay time;
QPWRRSTIPL: Power restore IPL.
Connection to the "Media Contacts 11" board
Fig. 35
10
9 8 7 6 5 4 3 2 1
XR5 connector
output signals:
low-battery shutdown warning
(low battery)
)
load on battery
(utility failure)
load on inverter
(ON)
load on bypass
(bypass active)
common 0 V
(system ground)
male 9-pin SUB-D connector
male 15-pin SUB-D connector
IBM AS/400
Galaxy PW
Note: the corresponding IBM AS/400® signal names are
given in parentheses.
2 3 4
6 7 8 9
1
2 3
4 5 6 7 8
9 10 11
2 3
12 13 14 15
"Media Contacts 11" remote indications board
10
1
12
1
XR2 XR3
10
1
XR4
10
1
XR5
XR2
XR3
XR4
XR5
12
1 10
1 10
1 10
1
XR1
1
5
Installation (cont.) (qualified personnel only)
E-51028231XU/BH - 29
Final installation steps
After making the connections:
install the front and rear base plates
of the cubicles, clipping them to the feet of the cubicles (unless the connecting cables are fed through these openings);
refit the terminal shields of the
terminal blocks, switches and circuit breakers.
Connection of the LED indications unit (optional)
This unit connects to the XR4 and XR5 connectors (see the position of the board in the figures in the "connection of "Media Contacts 11" standard auxiliary circuits" section). For information on unit installation and
details on connections to the unit, see the manual included with the LED indications unit, document No.
5102990400.
the recommended cable cross-
section is 1 mm2 .
Installation (cont.)
(qualified personnel only)
30 - E-51028231XU/BH
Loading...