MGE UPS Systems EXB10Rack, EX15Rack, EX10Rack User Manual

Pulsar
TM
EX10
EXB10
User Manual
!
+
+
%
%
/ EX15
Rack
MGE UPS SYSTEMS
Pulsar EX
Rack
: 86-153522-00
www.mgeups.com
Thank you for purchasing the EX
Rack
Uninterruptible Po wer Supply. The EX
Rack
has been designed to provide many years of trouble-free operation. Please review the manual which has been prepared to provide you with all the necessary information concerning the installation and use of your EX
Rack
. For service call 1-800-523-0142. Sincerely,
MGE UPS SYSTEMS
Federal Communications Commission (FCC) Statement
Note: this equipment has been tested and
found to comply with Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when equipment is operated in a residential environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits.
Revision A00 ECN - 000071
Pulsar EX
Rack
: 86-153522-00
MGE UPS SYSTEMS
IMPORTANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS
This manual contains important instructions for Models EX10 should be followed during installation and maintenance of the UPS batteries.
Rack
/EX15
Rack
/EXB10
Rack
/EXB15 that
c This equipment can be operated by any individual, with no previous training; c CAUTION: Risk of electric shock, even with unit disconnected from AC power source. Hazardous voltage still may be present through operation from battery. The battery supply should be disconnected at the plus and minus terminals using the quick disconnect connectors of the battery when maintenance or service work inside the UPS is necessary.
c The UPS contains voltages which are potentially hazardous. All repairs should be performed by qualified service personnel only; c do not attempt to power the UPS from any receptacle other than a 2-pole 3-wire grounded receptacle;
c do not place Pulsar near water or in environment of excessive humidity; c do not allow liquids or any foreign objects to get inside Pulsar; c do not block air vents in the back of Pulsar; c do not plug household appliances such as hair dryers to Pulsar receptacles; c do not place Pulsar in direct sunlight or close to heat-emitting source;
MGE UPS SYSTEMS
c the AC power receptacle should be near the equipment and easily accessible. To isolate Pulsar from AC input, remove the input power cord from the AC power receptacle; c if Pulsar is to be stored for a long time, it is recommended to recharge the batteries (by connecting AC power source to Pulsar, switch "ON" or "OFF"), once a month for 24 hours to avoid a full batteries discharge; c Pulsar contains batteries that should be disposed of or recycled in accordance with local applicable laws; c prior to installation, store Pulsar in a dry location; c storage temperatures must be between –4°F (-20°C) and +113°F (+45°C); c servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries; c when replacing the batteries, use the same number and the following type of batteries:
v Pulsar EX10 v Pulsar EX15
Pulsar EX
Rack
: 3 x 12V - 7.2Ah,
Rack
: 4 x 12V - 7.2Ah;
Rack
: 86-153522-00
c ~ : alternating current supply symbol;
c CAUTION: do not dispose of battery or
batteries in a fire. The battery may explode; c CAUTION: do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes. It may be toxic; c CAUTION: a battery can present a risk of electric shock and high short circuit current. The following precautions should be observed when working with batteries: v remove watches, rings or other metal objects,
v use tools with insulated handles, v wear rubber gloves, boots and safety
glasses; c please dispose of the packaging in accordance with the applicable laws.
i
introduction
In critical situations, count on MGE UPS SYSTEMS Pulsar EX10
EX15
Rack
(UPS). Their protection keeps your data intact and accessible.
Pulsar EX10
ensure top quality power around the clock, and continue operations during power failures. An intelligent microprocessor detects any operating anomalies of the UPS and triggers an alarm if corrective action is necessary. In addition to the high-technology aspect of these UPSs, you can count on backup from our staff, a team of specialists, around the corner from you, throughout the world. It’s no accident that MGE UPS SYSTEMS is the world leader in UPS protection.
uninterruptible power supplies
Rack
uses of Pulsar EX10 EX15
Rack
Network servers and interconnection devices are very sensitive to electrical disturbances of all types, including outages, voltage sags, brownouts, spikes, etc. The origins of the disturbances also vary, ranging from atmospheric phenomena, to nearby devices generating interference such as elevators, photocopy machines and machine tools, not to mention human errors, like the accidental pulling out of power cords or tripping of circuit breakers. The consequences of these disturbances on computer systems range from data losses to hardware damage (power supplies, hard disks).
:
Rack
and EX15
and
Rack
Rack
UPSs
and
Pulsar EX10
specially designed to protect network servers and all other devices that are sensitive to electrical disturbances.
Pulsar EX10
tolerance to the utility supplying your sensitive equipment.
Pulsar EX10
designed as compact units and feature very quiet operation.
Pulsar EX10
stable supply of clean power, long back-up time during a utility outage (see table) and vast information and control possibilities according to the configuration selected.
Pulsar EX10
technology provides maximum protection and availability of your workstations, servers, and network communication devices.
Pulsar EX10
many functions and characteristics designed to simplify power management: c automatic battery test carried out periodically. In the event of a fault, a LED provides advance warning for battery replacement; c front panel LEDs signal all types of faults and alarms; c Bar graph continuously indicates the battery charge level or the critical load power level;
c Pulsar EX10
environment friendly: all components are recyclable and an electronic power-saver device reduces power consumption if the UPS is not active for a period exceeding 5 minutes while on battery back-up;
Rack
Rack
Rack
Rack
Rack
Rack
Rack
and EX15
and EX15
and EX15
and EX15
and EX15
and EX15
and EX15
Rack
Rack
Rack
Rack
Rack
Rack
Rack
are
add fault-
are
provide a
On-Line
offer
are
c EX Driver software provides rapid startup of Pulsar EX10 the EX Tuner configuration module. This module adapts Pulsar EX10
EX15
Rack
frequency, startup and shutdown sequences, setting of battery thresholds, etc.). See "communication" section for further details; c Solution-PacTM is a CD-ROM which contains all the tools needed to supervise your UPS. c Simply download the EX driver utility from the CD and Solution-Pac. The UPS must be serialy connected to a Windows PC.
Rack
and EX15
to user preferences (battery test
Rack
Rack
using
and
ii
Pulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
options
c UM Sensor environment measurement unit: compatible with SNMP or Solution
PacTM, this unit measures the temperature and the relative humidity in the room where the Pulsar is installed. Eight relay contacts are provided to transmit signals to an administration platform, in the form of voltage free contacts to enable monitoring of (fire alarm, climate control fault, intrusion, etc.);
c battery extension module: Pulsar EXB10
Rack
modules lengthen the battery time of the
Pulsar EX10
requirements. For rack installation of EXB15 order 19" rack kit P/N 8806U.
/EXB15 battery extension
Rack
/EX15
Rack
to meet your
additional communications options:
c SNMP administration: MGE has the most complete offering for the administration of a group of UPSs using the SNMP protocol with different network-connection modules (SNMP card or proxy software), supervision modules (application for NMS platforms such as HP OpenView or C.A. UNICENTER TNG) and a file-closing module (UM Client). c SNMP card: this card, inserted into your UPS, can establish a direct Ethernet network connection for your UPS. It can then be temporarily managed using SNMP or the various software modules of Solution-Pac. The MGE UPS SYSTEMS offering complies with RFC 1628 specifications (IETF) and was certified by the InterWorking Labs during the Test Summit in June 1994;
c status information card: this option provides you with 5 voltage-free contacts: on battery, on by-pass, low battery, load on UPS. This card can be used with the UPS driver of IBM AS/400.
Contact your dealer for further information on these options.
MGE UPS SYSTEMS
Pulsar EX
Rack
: 86-153522-00
iii
software supplied with Pulsar EX10 EX15
Rack
To meet the different operating environments of your UPS, Pulsar EX includes 2 MGE UPS SYSTEMS software programs:
c EX-Driver software for Windows; c Network based Solution-PacTM power
management software.
EX-Driver for Windows
EX Driver for Windows provides communication with the UPS from a simple Windows workstation. EX-Driver is compatible with Windows 3.1x and Windows 95/98, for communication with the UPS via a serial connection for various needs:
c personalization of the UPS operating mode: the EX-Tuner utility, can be used to
change certain UPS operating parameters if the standard factory settings are not ideal for the operating conditions. It is possible to modify the output voltage, battery-test frequency, startup and shutdown sequences, operation of automatic by-pass, etc.;
Rack
and
Rack
Solution-PacTM for networks and multi-server systems
Protection by UPS is only complete and effective if combined with powerful software functions which warn users and the operator of any power supply problem, automate system shutdown, supervise and remotely control the UPSs. MGE UPS SYSTEMS created Solution-PacTM for this purpose. Solution-PacTM combines all these functions in a single CD-ROM, usable in local or remote mode (TCP/IP and SNMP), and covering the main network environments. Solution-PacTM is the ideal solution for protecting networks and multiserver systems. Solution-PacTM on a single CD-ROM contains everything needed to safeguard one or more systems and to supervise one or more UPSs from a local or remote station. Solution-PacTM includes SNMP proxy agents, system shutdown software, and
supervision software. Solution-PacTM is a powerful and upgradable software tool which provides all the supervision, control and safety functions associated with a UPS:
v graphic display of the UPS, v remote control of the UPS and output
receptacles,
v user alarm of problems, v recording of events in log files, v automatic system shutdown and restart, v local or remote supervision of UPSs and
ancillary devices, v transmission of UPS information and alarms to any SNMP supervisor.
v paging / e-mail capabilities v multiple server shutdown in
heterogeneous environment.
Platforms supported:
Windows 3.1, 95, 98, NT, Novelle Netware, OS/2, Linus, Mac/OS, Sun Solaris, HP/UX, IBM Aix, Dec Unix and Open VMS, Silicon Graphics, IRIX.
iv
Pulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
general contents
Pulsar presentation............................................................................................................................. 3
getting started / operation....................................................................................................... 11
Pulsar EX10
Rack
/ EX15
Rack
/ EXB10
Rack
/ EXB15 presentation
MGE UPS SYSTEMS
Pulsar EX
Rack
: 86-153522-00
1
Pulsar EX
Rack
: 86-153522-00MGE UPS SYSTEMS
2
Pulsar EX10 EX15
Rack
front view
Rack
1f
1e
Pulsar EXB10
rear view
1c
2
!
+
3
%
+
%
1a
1b 1d
Rack
19
21
BATTERY CONNECTOR
Volt: 36Vdc = 20A
22
BATTERY CONNECTOR
Volt: 36Vdc = 20A
20
DC BREAKER
30A 65Vdc
I O
23
Pulsar EX10 EX15
Rack
rear view
3
Rack
7
13
Pulsar EX10
U-Talk
8
11
5
PLACE STAMP
HERE
MGE UPS SYSTEMS
ATTN: CUSTOMER SUPPORT SERVICES 1660 SCENIC AVENUE
COSTA MESA, CA 92626
4
6
Vac IN
12
9
10
14
6a 6b
Rack
: 86-153522-00 Pulsar EX10
MGE UPS SYSTEMS
4
solution-pac 98
17
Rack
: 86-153522-00
The indispensable companion sofware for your UPS
L'indispensable complément logiciel de votre onduleur
18
MGE UPS SYSTEMS
key to diagrams
yellow indicator LEDs 1a to 1d flashing quickly:
1a overload, 1b device fault, 1c battery fault, 1d operating on bypass (fault tolerant
mode),
yellow indicator LEDs 1a to 1d on continuously or flashing slowly: indicate
the battery charge level (if utility power present) or remaining battery time (if no utility power present). They may be on continuously or flash slowly during a transition period. By pressing the button marked "function" 2 when utility power is present, they indicate the load charge level.
1e green indicator LED flashing: operating
on battery,
1f green indicator LED on continuously:
load powered by UPS, green indicator light off: load no powered by UPS,
2 "function" button: switches off audio
warning device or measures load charge percentage (if utility power present),
3 "ON/OFF" switch:
button pushed in: ON button not pushed in: OFF,
4 input receptacle, 5 input cord (supplied, with ferrite for
Pulsar EX15
6 input fuse receptacle, 6a input fuse:
T 15A/125V for Pulsar EX10 T 20A/125V for Pulsar EX15
6b fuse holder, 7 output receptacles for connection of
computer loads to Pulsar EX 8 site wiring fault LED, 9 rating label,
Rack
)
Rack Rack
Rack
10 fan, 11 SUB-D 9 pin connector for RS232
communication port,
12 cover for optional communication cards, 13 connector for Pulsar EXB10
EXB15 battery extension module, 14 warranty card, 17 Solution-PacTM ,CD-ROM, EX Drive, 18 RS232 cable, 19 Pulsar EXB10
,
,
,
extension module,
20 battery circuit-breaker, 21 connector to Pulsar EX10
EX15
Rack
22 connector for second Pulsar
EXB10
module,
23 battery connection cord.
Rack
,
Rack
/EXB15 battery extension
Rack
/EXB15 battery
Rack
MGE UPS SYSTEMS
Pulsar EX
Rack
: 86-153522-00 5
technical data
c output power: v Pulsar EX10 v Pulsar EX15
c input voltage: v Pulsar EX10 v Pulsar EX15 v frequency (F): 47Hz to 53Hz or 57Hz to 63Hz
c battery: v type :
maintenance free sealed lead-acid Pulsar EX10
note: battery life (4 or 5 years) is halved every 10°C above 25°C
c output specifications: v voltage (V): single phase 120V ± 3% (can be adjusted from 100 to 127V using EX Driver)
v frequency (F): 50/60Hz ± 0.5% (frequency configuration using EX Driver) c environment:
v noise level: 40dBA (Pulsar EX10
v operating temperature: 0 to 35°C v relative humidity: 0 to 90%
c dimensions and weights: Pulsar EX10 v height H (inches): 3.46 3.46 3.46
v width W (inches): 19 19 19 v depth D (inches): 16.25 19.5 16.25 v weight lbs (kg) : 37 (17) 51 (23) 48 (22)
Rack
: 1000VA/700W
Rack
: 1500VA/1050W
Rack
voltage (V): a 80V to 138V single phase (60V to 138V at 1/3 Power, 70V to 138V at 2/3 Power)
Rack
voltage (V): a 90V to 138V single phase (70V to 138V at 1/3 Power, 80V to 138V at 2/3 Power)
+
Rack
: 3 x 12V - 7.2Ah
Rack
: 4 x 12V - 7.2Ah
H/2U
Rack
) or 50dBA (Pulsar EX15
Rack
) or 50dBA (Pulsar EX15
Rack
Pulsar EX15
Rack
Rack
a
/
/ a
Pulsar EX15
+
D
45dBA (Pulsar /EX10
non condensing
W
) for operation on utility power
Rack
) for battery backup mode
Pulsar EXB10
Rack
6
P-ulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
Pulsar EX10
Rack
battery back-up time Pulsar EX15
ATM switch 32 slots entry level mini-computer system 2 entry level servers
EX10 EX10 EX10
Rack Rack
+ EXB10
Rack
+ 2 EXB10
Rack
Rack
Rack
battery back-up time
ATM switch 32 slots entry level mini-computer system
EX15 EX15 EX15
Rack Rack
+ EXB15
Rack
+ 2 EXB15
2 entry level servers
tower server + external mass storage / ATM switch 16 slots tower server + modular hub tower server 100 lines PBX desktop server
0 50 100 150 200 012 3
MGE UPS SYSTEMS
t (min) t (h)
tower server + external mass storage tower server + modular hub tower server 100 lines PBX desktop server
0 80 160 240 320 012 34 5 6
Pulsar EX
Rack
: 86-153522-00 7
t (min) t (h)
8
P-ulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
contents
getting started ..................................................................................................................10
location...................................................................................................................................... 10
preliminary checks ....................................................................................................................10
connections ...............................................................................................................................10
communication ..........................................................................................................................11
operation ............................................................................................................................. 12
starting up with utility power present .........................................................................................12
starting up with out utility power ................................................................................................13
operation on battery .................................................................................................................. 14
overload .................................................................................................................................... 15
operating anomalies.................................................................................................................. 15
MGE UPS SYSTEMS Pulsar EX
Rack
: 86-153522-00
9
getting started
location
c observe the safety rules indicated at the beginning of this document.
preliminary checks
c check that button 3 " " on the front is not pushed in; c check that rating shown on identification plate 9 corresponds to the input voltage specification and power requirement of your application.
connections
c use your application cord to supply input power to Pulsar as shown.
Connect the computer cord 5 between UPS utility power receptacle 4 , and a nearby utility power outlet.
4
Vac IN
utility power outlet
5
c use IEC cords to connect your applications to output sockets 7 .
7
Vac IN
computer loads
Note 1:
Following connection, the battery automatically charges, whatever the position of the ON/OFF button 3 "" .
Note 2:
The batteries will provide full back-up time after approximatively 8 hours of recharge time.
Note 3:
The rating of input power cord must not be less than the nominal input rating of
Pulsar EX10
Rack
: Use the supplied cord.
c connection of Pulsar EXB10 battery extension module (optional):
v check that button 3 " " on the front of the Pulsar EX10 v disconnect the utility power connection cord 5 , v flip the circuit-breaker 20 of the unit to the right (position "O"), v connect the battery connection cord 23 to connector 21 of the module and connect 13 of the Pulsar EX10 v if the installation has 2 battery modules, connect the second cord 23 to connectors 21 of the second module and 22 of the first module, v the use of connectors 13 , 21 and 22 is strictly limited to connecting the battery modules to the Pulsar EX10 connection to these connectors is prohibited at the risk of damaging the battery and losing the warranty, v flip the battery circuit-breaker 20 to the left (position "I"), v if your installation is operated with MGE UPS SYSTEMS software, update your battery configuration with EX Tuner.
Rack
is not pushed in,
Rack
Rack
Rack
,
. Any other
10 Pulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
communication
c the U-Talk communication port, at the rear of the Pulsar, delivers information in the form of an RS232 series link supported by the communication protocol exclusive to MGE UPS SYSTEMS. The Solution-PacTM programs use the data made available by this protocol.
standard port
0V
RD TD
5432
9876
1
11
option 1
c status information card: after the card is installed in the rear of the Pulsar, communication port transmits the status information on a SUB-D 9-pin female connector using the following pinouts:
1- ground, 4- normal operation, 5- common, 6 - operation on utility power, 7- low battery warning, 8- load supplied by UPS, 9- operation on battery.
optional port
option 2
c SNMP card: after the card is installed in the rear of the Pulsar, the communication port transmits information supported by the TCP/IP andSNMP protocols on an RJ45 or BNC connector to any ethernet network.
Contact your sales agent for further details.
With the EX Driver software program you can set up Pulsar EX
Rack
to suit your user
0V
conditions (EX Tuner). To install EX Driver, connect the serial cable supplied to COM1 to COM4 (set up by EX Tuner) serial port of your computer equipped with Windows 3.1 or 95/98 on the one end, and to the serial
Pulsar EX
Rack
connector on the other end.
n.c.
n.o.
Insert the CD and type A:\Install. Follow the installation instructions on the screen.
Relay breaking capacity: Vmax = 25V DC Imax = 10mA
n.o. : normally open, n.c. : normally closed.
MGE UPS SYSTEMS Pulsar EX
0V
5432
9
876
n.o.
0V
Rack
: 86-153522-00
1
12
n.o.0Vn.o.
0V
11
operation
starting up with utility power present
indicator lights testpress button "on/off" :
automatic sequence:
1 s beep
output off output off
several beeps
12 Pulsar EX
device and battery test
indicating the remaining battery time percentage (here 50%)
silence
your load is supported by the battery
Rack
: 86-153522-00 MGE UPS SYSTEMS
normal operation
17 s7 s5 s0 s
indicating the recharge percentage of the battery (here 50%)
silence
UPS is on utility power
starting up with out utility power
indicator lights testpress "on/off" button:
automatic sequence:
1 s beep
output off output off
MGE UPS SYSTEMS Pulsar EX
several beeps
device and battery test
3 s beep
your load is supported by the battery
Rack
: 86-153522-00
indicating the remaining battery time percentage (here 50%)
normal operation on battery
17 s7 s5 s0 s
indicating the remaining autonomy percentage (here 50%)
1 beep every 10 s
UPS is on utility power
13
operation on battery
no utility power
break in utility power
indicating the remaining battery time: here, between 75 and 87%
1 beep every 10 s
your load is supported by the battery
warning alarm at low battery
x mn0 mn
1 beep every 3 s
you have less than 12% battery time remaining: power down your load, Pulsar will soon switch off automatically
Pulsar switches off automatically
x + ε mn
silence
UPS output "off"
return of utility power load charge percentage
At whatever point the utility power returns, Pulsar switches to normal operation:
silence
indicating the battery
recharge percentage: here, between 12 and 25%
Note:
The alarm silence button is to deactivate or activate the audio warning device when operating on battery, or when site wiring fault occured.
If utility power is present, hold alarm silence button in:
indicating the load charge percentage: here 50%
silence
your load is supplied by the utility power (on line)
14 Pulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
overload
utility power present
1 beep every second
operating anomalies
device fault
1 beep every second
battery fault
A battery test is carried out while Pulsar, is in start-up mode, then automatically every 7 days (interval times adjustable using EX Driver). If a battery fault is detected, the following occurs:
vv
v automatic load transfer to bypass,
automatic load transfer to bypass
no utility power present
vv
vv
v switch off Pulsar (release "on/off" button),
vv
disconnect from the wall socket (check input cord), and check that Pulsar has not short­circuited (disconnect all loads),
vv
v if necessary, change the input fuse,
vv
vv
v re-start Pulsar.
vv
battery low
1 beep every second
Pulsar switches off automatically after a length of time which depends on the level of overload.
Note: overload occurs if the load
consumption is greater than the rated power of Pulsar. To acknowledge the fault, release the "on/ off" button, temporarily disconnected Pulsar from the wall socket (check input cord), disconnect loads and re-start Pulsar.
MGE UPS SYSTEMS Pulsar EX
after the start-up sequence, if the audio warning device sounds continuously,
recharge your battery for 8 hours.
Note: if the previous symptoms persist,
contact technical support.
Rack
: 86-153522-00
continuous beep
1 beep every second
recharge your battery for 8 hours.
operation on bypass
1 beep every second
see "overload" and "device fault" section
Note:
This operating mode provides temporary inverter fault tolerance.
15
16 Pulsar EX
Rack
: 86-153522-00 MGE UPS SYSTEMS
service and factory repair - call 1 - 800 - 523 - 0142
c direct questions about the operation, repair, or servicing of this equipment to MGE UPS SYSTEMS, Inc. Customer Support Services. Include the part number, assembly number, and serial number of the unit in any correspondence. Should you require factory service for your equipment, contact MGE UPS SYSTEMS, Inc. Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE UPS SYSTEMS, Inc. without first obtaining an RMA.
proprietary rights statement
c the information in this manual is the property of MGE UPS SYSTEMS, Inc., and represents a proprietary article in which MGE UPS SYSTEMS, Inc., retains any and all patent rights, including exclusive rights of use and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, Inc.; c Trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.
two years warranty policy
c MGE UPS SYSTEMS, Inc. (herein after referred to as MGE) warrants Pulsar equipment manufactured by MGE to be free from defects in materials and workmanship for a period of two years from date of purchase. If within such period purchaser discovers defective item and promptly notifies MGE in writing, MGE shall repair or replace the item at the Company's option. This warranty shall not apply:
v to equipment not manufactured by MGE, v to equipment repaired or altered by others than MGE, v to equipment subjected to negligence, accident, or damage by circumstances beyond MGE's control, or to improper operations, maintenance,
or storage, or to other than normal use or service. With respect to equipment not manufactured by MGE, the Warranty obligations of MGE shall in all respects conform and Warranties do not cover reimbursement for labor, transportation, removal, installation, or other expenses which may be incurred in connection with repairs or replacement. Except as may be expressly provided in an authorized writing by MGE, MGE shall not be subject to any other obligations or liabilities whatsoever with respect to equipment manufactured by MGE or service rendered by MGE.
MGE UPS SYSTEMS
Pulsar EX
Rack
: 86-153522-00
MGE UPS SYSTEMS, Inc.
www.mgeups.com
Postal address:
1660 Scenic Avenue Costa Mesa, CA 92626 714-557-1636
86-153522-00
Pulsar EX
Rack
: 86-153522-00
MGE UPS SYSTEMS