MGE UPS Systems EX15, EX10, EXB10, EX-7, EXB15 User Manual

Pulsar
TM
EX7 / EX10 / EX15 EXB10 / EXB15
Manuel d'utilisation User Manual Manual de instrucciones
!
+
… …
%
+
… …
%
MGE UPS SYSTEMS
Pulsar EX : 51032233XT/AC
Thank you for purchasing the EX Uninterruptible Power Supply. The EX has been designed to provide many years of trouble-free operation. Please review the manual which has been prepared to provide you with all the necessary information concerning the installation and use of your EX.
For service call 1-800-523-0142. Sincerely,
MGE UPS SYSTEMS
Federal Communications Commission (FCC) Statement
Note: this equipment has been tested and
found to comply with Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when equipment is operated in a residential environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits.
Nous vous remercions pour l’achat de l'Alimentation sans interruption EX. Nous vous invitons à lire ce manuel en souhaitant qu’il apporte tous les éléments nécessaires à l’installation et à l’utilisation de votre onduleur EX.
Appelez le numéro de téléphone 714­513-7349.
Nous vous prions d’agréer, Madame, Monsieur, nos sentiments les meilleurs.
MGE UPS SYSTEMS
Le agradecemos la compra del ondulador EX. Lo invitamos a leer este manual esperando que éste le brindará todos los elementos necesarios para la instalación y la utilización de su ondulador EX.
Contáctenos al siguiente número de teléfono 714-513-7349.
Le saludamos a Ud. muy cordialmente.
MGE UPS SYSTEMS
0
Pulsar EX : 51032233XT/AC
MGE UPS SYSTEMS
note
c this equipment has been tested and found to comply with Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
service and factory repair - call 1 - 800 - 523 - 0142
c direct questions about the operation, repair, or servicing of this equipment to MGE UPS SYSTEMS, Inc. Customer Support Services. Include the part number, assembly number, and serial number of the unit in any correspondence. Should you require factory service for your equipment, contact MGE UPS SYSTEMS, Inc. Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE UPS SYSTEMS, Inc. without first obtaining an RMA.
proprietary rights statement
c the information in this manual is the property of MGE UPS SYSTEMS, Inc., and represents a proprietary article in which MGE UPS SYSTEMS, Inc., retains any and all patent rights, including exclusive rights of use and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, Inc.; c IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.
two years warranty policy
c MGE UPS SYSTEMS, Inc. (herein after referred to as MGE) warrants Topaz and Pulsar equipment manufactured by MGE to be free from defects in materials and workmanship for a period of two years from date of purchase. If within such period purchaser discovers defective item and promptly notifies MGE in writing, MGE shall repair or replace the item at the Company's option. This warranty shall not apply:
v to equipment not manufactured by MGE, v to equipment repaired or altered by others than MGE, v to equipment subjected to negligence, accident, or damage by circumstances beyond MGE's control, or to improper operations, maintenance,
or storage, or to other than normal use or service. With respect to equipment not manufactured by MGE, the Warranty obligations of MGE shall in all respects conform and Warranties do not cover reimbursement for labor, transportation, removal, installation, or other expenses which may be incurred in connection with repairs or replacement. Except as may be expressly provided in an authorized writing by MGE, MGE shall not be subject to any other obligations or liabilities whatsoever with respect to equipment manufactured by MGE or service rendered by MGE. After Sales Service Support Line: 1-800-523-0142.
MGE UPS SYSTEMS
Pulsar EX : 51032233XT/AC
MGE UPS SYSTEMS, Inc.
Postal address:
1660 Scenic Avenue Costa Mesa, CA 92626 714-557-1636
51032233XT/AC
Pulsar EX : 51032233XT/AC
MGE UPS SYSTEMS
ENGLISH IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for Models EX7/EX10/EX15/EXB10/EXB15 that should be followed during installation and maintenance of the UPS batteries.
c This equipment can be operated by any individual, with no previous training; c CAUTION: Risk of electric shock, even with unit disconnected from AC power source. Hazardous voltage still may be present through operation from battery. The battery supply should be disconnected at the plus and minus terminals using the quick disconnect connectors of the battery when maintenance or service work inside the UPS is necessary.
c The UPS contains voltages which are potentially hazardous. All repairs should be performed by qualified service personnel only; c do not attempt to power the UPS from any receptacle other than a 2-pole 3-wire grounded receptacle;
c do not place Pulsar near water or in environment of excessive humidity; c do not allow liquids or any foreign objects to get inside Pulsar; c do not block air vents in the back of Pulsar; c do not plug household appliances such as hair dryers to Pulsar receptacles; c do not place Pulsar in direct sunlight or close to heat-emitting source;
MGE UPS SYSTEMS
c the AC power receptacle should be near the equipment and easily accessible. To isolate Pulsar from AC input, remove the input power cord from the AC power receptacle; c if Pulsar is to be stored for a long time, it is recommended to recharge the batteries (by connecting AC power source to Pulsar, switch "ON" or "OFF"), once a month for 24 hours to avoid a full batteries discharge; c Pulsar contains batteries that should be disposed of or recycled in accordance with local applicable laws; c prior to installation, store Pulsar in a dry location; c storage temperatures must be between –4°F (-20°C) and +113°F (+45°C); c servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries; c when replacing the batteries, use the same number and the following type of batteries:
v Pulsar EX7: 2 x 12V - 7.2Ah, v Pulsar EX10 : 3 x 12V - 7.2Ah, v Pulsar EX15 : 4 x 12V - 7.2Ah;
Pulsar EX : 51032233XT/AC
c ~ : alternating current supply symbol;
c CAUTION: do not dispose of battery or
batteries in a fire. The battery may explode; c CAUTION: do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes. It may be toxic; c CAUTION: a battery can present a risk of electric shock and high short circuit current. The following precautions should be observed when working with batteries: v remove watches, rings or other metal objects,
v use tools with insulated handles, v wear rubber gloves, boots and safety
glasses; c please dispose of the packaging in accordance with the applicable legislation.
i
ENGLISH introduction
In critical situations, count on MGE UPS SYSTEMS Pulsar EX7, EX10 and EX15 uninterruptible power supplies (UPS). Their protection keeps your data intact and accessible. Pulsar EX7, EX10 and EX15 UPSs ensure top quality power around the clock, and continue operations during power failures. An intelligent microprocessor detects any operating anomalies of the UPS and triggers an alarm if corrective action is necessary. In addition to the high-technology aspect of these UPSs, you can count on backup from our staff, a team of specialists, around the corner from you, throughout the world. It’s no accident that MGE UPS SYSTEMS is the world leader in UPS protection.
application of Pulsar EX7, EX10 and EX15:
Network servers and interconnection devices are very sensitive to electrical disturbances of all types, including outages, voltage sags, brownouts, spikes, etc. The origins of the disturbances also vary, ranging from atmospheric phenomena, to nearby devices generating interference such as elevators, photocopy machines and machine tools, not to mention human errors, like the accidental pulling out of power cords or tripping of circuit breakers. The consequences of these disturbances on computer systems range from data losses to hardware damage (power supplies, hard disks). Pulsar EX7, EX10 and EX15 are specially designed to protect network servers and all
other interconnection devices that are sensitive to electrical disturbances. Pulsar EX7, EX10 and EX15 add fault­tolerance to the utility supplying your sensitive equipment. Pulsar EX7, EX10 and EX15 are designed as compact units and feature very silent operation. They can be installed under a desk, and can also be installed in a rack (see "options"). Pulsar EX7, EX10 and EX15 provide a stable supply of clean power, long back-up time during a utility outage (see table) and vast information and control possibilities according to the configuration selected. Pulsar EX7, EX10 and EX15 On-Line technology provides maximum protection and availability of your workstations, server, and network communication devices. Pulsar EX7, EX10 and EX15 offer many functions and characteristics designed to simplify power management: c automatic battery test carried out periodically. In the event of a fault, a LED provides advance warning for battery replacement; c front panel LEDs signal all types of faults and alarms; c Bar graph continuously indicates the battery charge level or the critical load power level; c Pulsar EX7, EX10 and EX15 are environment friendly: all components are recyclable and an electronic power-saver device reduces power consumption if the UPS is not active for a period exceeding 5 minutes while on battery back-up; c EX Driver software provides rapid startup
of Pulsar EX7, EX10 and EX15 using the EX Tuner configuration module. This module adapts Pulsar EX7, EX10 and EX15 to user preferences (battery test frequency, startup and shutdown sequences, setting of battery thresholds, etc.). Operation and monitoring are ensured by the UPS Manager 3.1 module operating under Windows 3.1. EX Driver connects to the RS 232 port on the Pulsar EX7, EX10 and EX15 (see "communication" section for further details); c Solution-PacTM is a CD-ROM which contains all the tools needed to supervise your UPS.
iv
Pulsar EX : 51032233XT/AC MGE UPS SYSTEMS
options
c rack installation kit: this kit is used to install Pulsar EX7, EX10 and EX15 in a 19­inch rack. The kit is designed to receive two
Pulsar EX7, EX10 and EX15, or one Pulsar EX10/EX15 and a battery extension unit,
thus offering up to 3000 VA of power;
c UM Sensor environment measurement unit: compatible with SNMP and UPS
Manager 2 Unix and OS/2, or Solution PacTM, this unit measures the temperature and the relative humidity in the room where the Pulsar is installed. Eight relay contacts are provided to transmit signals to an administration platform, in the form of voltage free contacts to enable monitoring of (fire alarm, climate control fault, intrusion, etc.);
c battery extension module: Pulsar EXB10/EXB15 battery extension modules lengthen the battery time of the Pulsar EX10/EX15 to meet your requirements.
additional communications options:
c communication cables: these cables are used for the file-closing utilities offered by a number of network operating systems. They are available for Novell NetWare, Microsoft Lan Manager and Windows NT, IBM Lan Server, Artisoft LANtastic, Banyan Vines, Apple System 7, IBM AS400 and many others;
c UPS Manager 2 communication software: this software can be used for
automatic file closing on one or more servers, as well as for remote UPS shutdown and interrogation of all Pulsar EX7, EX10 and EX15 operating parameters. It is available for Novell NetWare, Microsoft Lan Manager, IBM Lan Server, the main Unix systems on the market (SCO, AIX, HP/ UX, OSF 1, etc.) VAX UMS and many others; c SNMP administration: MGE UPS SYSTEMS has the most complete offering for the administration of a group of UPSs using the SNMP protocol with different network-connection modules (UM Link adaptor or proxy UM Agent software), supervision modules (dedicated software under Windows UM View or application for NMS platforms such as HP OpenView or Novell NMS) and a file-closing module (UM Client). The MGE UPS SYSTEMS offering complies with RFC 1628 specifications (IETF) and was certified by the InterWorking
Labs during the Test Summit in June 1994; c SNMP card: this card, inserted into your unit, makes your UPS SNMP-compatible in any environment; c status information card: this option provides you with 5 voltage free contacts: on battery, on by-pass, low battery, load on UPS.
Contact your dealer for further information on these options.
MGE UPS SYSTEMS
Pulsar EX : 51032233XT/AC
v
software supplied with Pulsar EX7, EX10 and EX15
To meet the different operating environments of your UPS, Pulsar EX includes 2 MGE UPS SYSTEMS software programs: c EX-Driver software for Windows (on 3.5" diskettes);
c Solution-PacTM network software (on CD-
ROM).
EX-Driver for Windows
EX Driver for Windows provides communication with the UPS from a simple Windows workstation. EX-Driver is compatible with Windows 3.1x and Windows 95, for communication with the UPS via a serial connection for various needs:
c personalization of the UPS operating mode: the EX-Tuner utility, can be used to
change certain UPS operating parameters if the standard factory settings are not ideal for the operating conditions. It is possible to modify the output voltage, battery-test frequency, startup and shutdown sequences, operation of automatic by-pass, etc.;
c UPS monitoring from a Windows workstation and system safety:
EX-Driver, UPS Manager 3 software, can display the UPS status, warn the user if a problem arises, and provide automatic shutdown. The many possibilities available include: v supervision of operating parameters through a graphic interface (display of battery charge level, remaining battery time and UPS load level). These values can be recorded periodically in a log file, v messages to the user in case of power
outage or UPS problem and recording of events in a log file, v during long-term power outages, automatic shutdown of the system and of the UPS, followed by automatic restart of the UPS (system reboot) on return of utility power, v PowerShareTM functions.
Solution-PacTM for networks and multi-station systems
Novell Netware, Windows NT, OS/2 Lan Server, SCO Unix, etc.) Protection by UPS is only complete and effective if combined with powerful software functions which warn users and the operator of any power supply problem, automate system shutdown, supervise and remotely control the UPSs. MGE UPS SYSTEMS created Solution-PacTM for this purpose. Solution-PacTM combines all these functions in a single CD-ROM, usable in local or remote mode (SNMP), and covering the main network environments. Solution-PacTM is the ideal solution for protecting networks and multistation systems. Solution-PacTM on a single CD-ROM contains everything needed to safeguard one or more systems and to supervise one or more UPSs from a local or remote station. Solution-PacTM includes SNMP UM-Agent, UM-Client system shutdown software, and UM-Console supervision software. Solution-PacTM is a powerful and upgradable software tool which provides all the supervision, control and safety functions
associated with a UPS:
v graphic display of the UPS, v remote control of the UPS and output
receptacles,
v user alarm of problems, v recording of events in log files, v automatic system shutdown and restart, v local or remote supervision of UPSs and
ancillary devices, v transmission of UPS information and alarms to any SNMP supervisor.
vi
Pulsar EX : 51032233XT/AC MGE UPS SYSTEMS
general contents / sommaire général / sumario general
Pulsar presentation............................................................................................................................. 3
présentation de Pulsar presentación de Pulsar
english....................................................................................................................................................................... 11
getting started / operation
français.................................................................................................................................................................... 19
mise en service / exploitation
español..................................................................................................................................................................... 27
puesta en servicio / explotación
Pulsar EX7/EX10/EX15/EXB10/EXB15 presentation présentation de Pulsar EX7/EX10/EX15/EXB10/EXB15 presentación de Pulsar EX7/EX10/EX15/EXB10/EXB15
MGE UPS SYSTEMS
Pulsar EX : 51032233XT/AC
1
Pulsar EX : 51032233XT/ACMGE UPS SYSTEMS
2
Pulsar EX7/EX10/EX15 Pulsar EX7/EX10 front view / vue avant / vista delantera rear view / vue arrière / vista trasera
Pulsar EX15 Pulsar EXB10/EXB15 rear view / vue arrière / vista trasera rear view / vue arrière / vista trasera
… …
… … …
11
1a
11
8
Site wiring
U-Talk
fault
12
8
Site wiring
U-Talk
fault
T 20A 125V
6a
6b
1b
!
+
%
+
1c
1d
10
Vac OUT
1e
%
1f
2
3
6
9
4
T 15A 125V
I max 8.3A
Vac IN
13
10
Vac OUT
13
7
9
12
I max 12.5A
19
4 6
DC BREAKER
30A 65Vdc
20
MGE UPS SYSTEMS
ATTN: CUSTOMER SUPPORT SERVICES 1660 SCENIC AVENUE
COSTA MESA, CA 92626
21
I O
22
7
16
PLACE STAMP
14
solution-pac
HERE
17
5
5
18
23
6b
6a
3
Pulsar EX : 51032233XT/AC MGE UPS SYSTEMS
4
Pulsar EX : 51032233XT/AC
MGE UPS SYSTEMS

contents

getting started ..................................................................................................................12
location......................................................................................................................................12
preliminary checks .................................................................................................................... 12
connections ............................................................................................................................... 12
communication .......................................................................................................................... 13
operation .............................................................................................................................14
starting up with utility power present ......................................................................................... 14
starting up with out utility power ................................................................................................ 15
operation on battery ..................................................................................................................16
overload .................................................................................................................................... 17
operating anomalies..................................................................................................................17
MGE UPS SYSTEMS Pulsar EX: E-51032233XT/AC
11
OUT
e
s

getting started

location

c observe the safety rules indicated at the beginning of this document.

preliminary checks

c check that the "on/off" button " " on the front is not pushed in; c check that rating shown on the rating label corresponds to the input voltage specification and power requirement of the load.

connections

c use the AC input cord to supply input power to Pulsar as shown.
Connect the AC input cord between UPS utility power input receptacle, and utility power outlet.
s
s
e
r
p
?
r
e
s
t
e
T 15A 125V
Vac IN
4
I max 8.3A
utility power receptacle
c connect the computer loads to output sockets 7 .
Vac
7
s
s
r
e
0V
I max 8.3A
g
to computer
8
loads
Note 1: following connection, the battery automatically charges, whenever plugged in.
Note 2: the batteries will provide full back-up time after approximatively 8 hours of recharge time.
Note 3: the rating of input power cord must be not less than the nominal input rating of
Pulsar EX: use the supplied cord. Note 4: if site wiring fault LED 8 is lit and
buzzer sounds, line/neutral connections are reversed.
c connection of the Pulsar EXB10/EXB15 battery extension module (optional):
v check that the button "on/off" " " on the front of the Pulsar EX10/EX15 is not pushed in,
v disconnect the input connection cord, v flip the circuit-breaker of the battery unit to
the right (position "O"), v connect the battery connection cord to the DC connector of the battery module and connect to the Pulsar EX10/EX15, v if the installation has 2 battery modules, connect the second cord to the DC connector of the second module and to the first module, v the use of connectors is strictly limited to connecting the battery modules to the Pulsar EX10/EX15. Any other connection to these connectors is prohibited and risks damaging the battery, not covered by warranty, v to start, flip the battery circuit-breaker to the left (position "I"), v if your installation is operated with MGE UPS SYSTEMS software, update your battery configuration with EX Tuner.
12 Pulsar EX: E-51032233XT/AC MGE UPS SYSTEMS

communication

c the U-Talk communication port, at the rear of the Pulsar, delivers information in the form of an RS232 series link supported by the communication protocol exclusive to MGE UPS SYSTEMS. The Solution-PacTM programs use the data made available by this protocol.
standard port
0V
RD TD
5432
9876
1
11
option 1
c status information card: after the card is installed in the rear of the Pulsar, communication port transmits the status information on a SUB-D 9-pin female connector using the following pinouts:
1- ground, 4- normal operation, 5- common, 6 - operation on utility power, 7- low battery warning, 8- load supplied by UPS, 9- operation on battery.
optional port
option 2
c SNMP card: after the card is installed in the rear of the Pulsar, the communication port transmits information supported by the SNMP protocol on an RJ45 or BNC connector.
Contact your sales agent for further details.
With the EX Driver software program you can set up Pulsar EX to suit your user conditions (EX Tuner), supervise your UPS and safeguard your system (UPS Manager
0V
5432
9
1
876
3.1). To install EX Driver, connect the serial cable supplied to COM1 to COM4 (set up by EX Tuner) series port of your computer
n.c.
n.o.
n.o.
n.o.0Vn.o.
equipped with Windows 3.1 on the one end, and to the serial Pulsar EX connector on the other end. Insert the disk and type A:\Install.
0V
0V
0V
Follow the installation instructions on the screen. You may then use 2 software programs :
v EX Tuner to set up Pulsar EX, v UPS Manager 3.1 to supervise and
safeguard your system.
MGE UPS SYSTEMS Pulsar EX: E-51032233XT/AC
Relay breaking capacity: Vmax = 25V DC Imax = 10mA
n.o. : normally open, n.c. : normally closed.
12
13

operation

starting up with utility power present

indicator lights testpress button "on/off" :
automatic sequence:
1a to 1f on
1 s beep
output off output off
1a to 1f flashing
several beeps
device and battery test
to
1a
1e
1f
your load is supported by the battery
indicating the
1d
remaining battery time percentage (here 50%)
on on silence
normal operation
17 s7 s5 s0 s
1a
1e
1f
UPS is on utility power
to
1d
off on
silence
indicating the recharge percentage of the battery (here 50%)
14 Pulsar EX: E-51032233XT/AC MGE UPS SYSTEMS

starting up with out utility power

automatic sequence:
1a to 1f on
indicator lights testpress "on/off" button:
1a to 1f flashing
device and battery test
1a
1e
1f
1 s beep
output off output off
MGE UPS SYSTEMS Pulsar EX: E-51032233XT/AC
several beeps
your load is supported by the battery
to
indicating the
1d
remaining battery time percentage (here 50%)
on on 3 s beep
normal operation on battery
17 s7 s5 s0 s
1a
1e
1f
UPS is on utility power
indicating the
to
1d
remaining autonomy percentage (here 50%)
flashing on
1 beep every 10 s
15

operation on battery

no utility power
break in utility power
0 mn
1a
1e
1f
your load is supported by the battery
indicating the
to
1d
remaining battery time: here, between 75 and 87%
flashing on
1 beep every 10 s
warning alarm at low battery
x mn
1a
to off
1c
flashing
1d
flashing
1e
on
1f
1 beep every 3 s
you have less than 12% battery time remaining: power down your load, Pulsar will soon switch off automatically
Pulsar switches off automatically
x + ε mn
1a
1f
to off off
silence
UPS output "off"
if Pulsar is operating on battery without load: UPS switches off
5 mn
1a
to
1f
silence
load off
return of utility power load charge percentage
At whatever point the utility power returns, Pulsar switches to normal operation:
1a to 1d indicating the battery
1e indifferent 1f on
your load is supplied by the utility power (on line)
recharge percentage: here,
between 12 and 25%
silence
Note:
The alarm silence button is to deactivate or activate the audio warning device when operating on battery, or when site wiring fault occured.
If utility power is present, hold alarm silence button in:
1a to 1d indicating the load charge
1e off 1f on
percentage: here 50%
silence
16 Pulsar EX: E-51032233XT/AC MGE UPS SYSTEMS

overload

utility power present

operating anomalies

device fault
battery fault
1a flashing
1d flashing 1e off
1f on
1 beep every second
automatic load transfer to bypass
no utility power present
1a flashing
1e flashing 1f on
1 beep every second
Pulsar switches off automatically after a length of time which depends on the level of overload.
Note: overload occurs if the load
consumption is greater than the rated power of Pulsar. To acknowledge the fault, release the "on/ off" button, temporarily disconnected Pulsar from the wall socket (check input cord), disconnect loads and re-start Pulsar.
1b flashing
1d flashing 1e off
1f on
1 beep every second
vv
v automatic load transfer to bypass,
vv
vv
v switch off Pulsar (release "on/off" button),
vv
disconnect from the wall socket (check input cord), and check that Pulsar has not short­circuited (disconnect all loads),
vv
v if necessary, change the input fuse,
vv
vv
v re-start Pulsar.
vv
battery low
1a to 1f off
continuous beep
after the start-up sequence, if the audio warning device sounds continuously,
recharge your battery for 8 hours.
Note: if the previous symptoms persist,
contact technical support.
A battery test is carried out while Pulsar, is in start-up mode, then automatically every 7 days (interval times adjustable using EX Driver). If a battery fault is detected, the following occurs:
1c flashing
1e off 1f on
1 beep every second
recharge your battery for 8 hours.
operation on bypass
1a and 1b indifferents
1d flashing 1e off 1f on
1 beep every second
see "overload" and "device fault" section
Note:
This operating mode provides temporary inverter fault tolerance.
MGE UPS SYSTEMS Pulsar EX: E-51032233XT/AC
17
18 Pulsar EX: E-51032233XT/AC MGE UPS SYSTEMS