Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
PowerServices TelPac has been designed with the utmost care. It comes in 2 versions: card (ref. 66096) or external (ref. 66097 or 66098). The card version can be installed by the customer or by an MGE UPS SYSTEMS After Sales Service technician. The external version can only be installed by a specialised MGE UPS SYSTEMS After Sales Service technician. We recommend you take time to read this manual to take full advantage of the many features of this product.
To discover the entire range of MGE UPS SYSTEMS products, visit our Web site at www.mgeups.com or contact your nearest MGE UPS SYSTEMS representative.
Environment
MGE UPS SYSTEMS pays great attention to the environmental impact of its products during the design and manufacture stages and through to the end of its life cycle.
MGE UPS SYSTEMS products comply with the strictest regulations.They do not contain CFCs or HCFCs.
Recycling of packaging
Packaging has been designed to be recycled. Please make sure it is correctly recycled (in compliance with applicable regulations).
Recycling of products at the end of their life cycle
MGE UPS SYSTEMS undertakes to recycle all recovered products at the end of their life cycle in installations complying with applicable regulations. Please contact our sales office.
See the environment section on our Web site at www.mgeups.com.
Special precautions
If the card or external unit must be stored prior to installation, always store in a dry location.Storage temperature range: -10ºC to +70ºC.
Page 4
Page 4 - 34003602EN/AB
Foreword
EMC compatibility
The PowerServices TelPac card and external versions comply with the following standards, on condition that they are installed and used in compliance with their intended use and manufacturer’s instructions:
Safety standards for IT equipment: EN 60950/A11 (1998).EMC: EN 61000-6-2 (1999), EN 61000-6-3 (2002).
The PowerServices TelPac card and external versions comply with the following European directives:
Low voltage: 73/23/EEC and 93/68/EEC.EMC: 89/336/EEC and 93/68/EEC.
Radio and Telecommunications compatibility
The PowerServices TelPac card and external versions comply with the European R&TTE directive, on condition that they are installed and used in compliance with their intended use and manufacturer’s instructions.
Federal Communication Commission (FCC) statement
Part 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Part 68
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
Page 5
34003602EN/AB - Page 5
Foreword
Modem compatibility and supported countries
The modem integrated in the PowerServices TelPac card is compatible with European standard CTR21 (01.98) in accordance with Council Decision 98/482/EC.
Australia Austria Belgium Brazil Bulgaria Canada China Czechoslovakia
Denmark Finland France Germany Greece Hong Kong Hungary India
Ireland Israel Italy Japan Korea Luxembourg Malaysia Mexico
New Zealand Netherlands Norway Philippines Poland Portugal Russia Singapore
South Africa Spain Sweden
Switzerland Taiwan United Kingdom United States
List of countries supported by the modem
Page 6
Page 6 - 34003602EN/AB
Information and advice.
Visual indication.
Action.
Important instructions that must always be followed.
Pictogram symbols
UPS : Uninterruptible Power System.
The conventions used to represent indicator lights in the illustrations are as follows:
Indicator off.
Indicator on.
Flashing Indicator.
Foreword
Page 7
34003602EN/AB - Page 7
1. Presentation
1.1 Unpacking and checking the contents .......................................................................................................... 9
1.2 Overview ......................................................................................................................................................... 10
1.3 Functions ...................................................................................................................................................... 11
1.4 Technical data sheet....................................................................................................................................... 12
1.5 Indicator lights ................................................................................................................................................13
2. Installation
2.1 Procedure ........................................................................................................................................................ 14
2.2 Preliminary check ...........................................................................................................................................14
2.3 The various installation types ....................................................................................................................... 15
2.4 Recommendations ......................................................................................................................................... 16
2.5 Fitting the warning label ................................................................................................................................16
2.6 Setting up the RS485 link .............................................................................................................................. 18
General .............................................................................................................................................................18
"Single-unit" type installation ............................................................................................................................ 18
Impedance matching and bias settings ............................................................................................................ 19
Configuring the shielding terminal .................................................................................................................... 20
Configuring the RS485 card for Comet ............................................................................................................ 21
Configuring the RAUZ card for Galaxy ............................................................................................................ 22
2.7 Installing the PowerServices TelPac card .................................................................................................... 23
2.8 Installation of the PowerServices TelPac external unit for Comet UPSs .................................................. 24
2.9 Installing the PowerServices TelPac external unit for Galaxy UPSs ......................................................... 26
2.10 Connecting contact type inputs .................................................................................................................... 28
Contents
Page 8
Page 8 - 34003602EN/AB
Contents
3. Maintenance
3.1 Cable diagrams ............................................................................................................................................... 30
Serial cable diagrams (ref. 34003618) ............................................................................................................. 30
Modem cable (ref. 34003729) .......................................................................................................................... 30
Comet link cable (ref. 34003747) .....................................................................................................................30
Page 9
34003602EN/AB - Page 9
1. Presentation
1.1 Unpacking and checking the contents
Content of the card version
A: PowerServices TelPac communication
card.
B: cover plate specifically designed for Galaxy PW UPSs. C: 5m telephone cable equipped with RJ11
plugs. D: 2.5m serial communication cable used for configuration and maintenance operations.
E: 3 warning labels. F: this manual. G: information form needed to activate
Teleservice.
Content of the external version
A: PowerServices TelPac external
communication unit with its fixing kit. C: 5m telephone cable equipped with RJ11 plugs.
D: 2.5m serial communication cable. E: 3 warning labels. F: this manual. G: information form needed to activate
Teleservice.
H: UPS link cable and fixing accessories. I: cleaning kit. J: plug-in 5V DC power adapter.
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
PowerServices Telpac
Installation and user manual
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
MGE UPS SYSTEMSwww.mgeups.com
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable arrêté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable arrêté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable arrêté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
PowerServices Telpac
Installation and user manual
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
MGE UPS SYSTEMSwww.mgeups.com
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable arrêté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable arrêté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable arrêté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
A
B
C
D
E
F
G
A
C
D
E
G
H
F
I
J
66096
66097, 66098
H
Page 10
Page 10 - 34003602EN/AB
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
4 x Digital inputs
DC 5V
1. Presentation
1.2 Overview
Power supply connector (external unit).
Dip-switch to configure the RS485 link.
Extension port to connect the 4 additional contact inputs.
Shielding configuration jumper.
RS232 serial port for configuration or maintenance.
Card name.
RS485 terminal block for connection of MGE UPS SYSTEMS equipment.
Connection port for 2 contact inputs (A and B).
Modem connection status indicator.
Indicator for data flow with the UPS(s).
Modem connection port.
Modem.
Power input.
Cable entry to extension port.
Velcro system to attach the external unit.
1
3
2
12
4
7
8
6
5
9
10
11
14
15
13
Page 11
34003602EN/AB - Page 11
1. Presentation
1.3 Functions
PowerServices TelPac enables connection of one or more products to the MGE UPS SYSTEMS Teleservice centre via an analogue telephone line.
Several MGE UPS SYSTEMS products can be connected via a JBUS / RS485 connection.
Connection of other equipment not supplied by MGE UPS SYSTEMS is possible via a dry contact connection.
The card version is designed for insertion in a UPS with a specific communication card slot.
The external version is designed for installation in a UPS without a specific communication card slot.
Country Teleservice
Centre
MODEMS
Customer site
Customer site
Customer site
Customer site
Customer site
PowerServices Telpac
PowerServices Telpac
JBUS/RS485
Local public phone
network
Page 12
Page 12 - 34003602EN/AB
1. Presentation
1.4 Technical data sheet
Functions
RS232 Port
RS485 Port
Modem
Contact inputs
Power supply (external version)
Characteristics/Default values
9600 8 1 None
1200, 8, 1 None 2 wires Master With Without 0.08 - 0.6 mm
2
(28/20 AWG)
V.34/33.6 kbps Error correction: V.42 LAPM and MNP 2-4 Data compression: V.42b and MNP5 Works with 39 country profiles European CTR21 compatibility Line protection included
Normally open (NO)
0.08 - 0.6 mm2 (28/20 AWG)
2 (card version) 2+4 (external version) 0.08 - 0.5 mm
2
(28/20 AWG)
10m maximum5V DC
1A
Parameters
RateData bits Stop bitsParity
Rate, bits, stop Parity Mode Master / slave Bias Impedance matching Cable cross-section
Analogue
Country
ProtectionDry contacts
Number
DistanceVoltage
Current
Possible values
9600 8 1 Even, odd
See technical support
documentation
2 wires / 4 wires Master With / without With / without
NO / NC
0 to 2 0 to 6
Comment: only MGE UPS SYSTEMS can be connected to the RS485 link.
Page 13
34003602EN/AB - Page 13
1. Presentation
Green UPS indicator 10
Card version
1.5 Indicator lights
External version
Red CD indicator 9 Card version
External version
Self tests
Card fault
Waiting for UPS communication
Exchanging data with UPS
UPS communication fault
Card fault
Waiting for UPS communication
Exchanging data with UPS
Modem connected
Modem not connected. Communication with all remotely monitored UPSs OK
Communication with at least one of the remotely monitored UPSs NOK
Modem connected
Modem not connected. Communication with all remotely monitored UPSs OK
Communication with at least one of the remotely monitored UPSs NOK
Modem connecting
(1)
1 sec
Status
1
2
3
4
Status
1
2
3
4
(1): When status 3 and 4 are present at the same time, status 4 is indicated.
1 sec
Modem connecting
(1)
Page 14
Page 14 - 34003602EN/AB
2. Installation
2.1 Procedure
1 - Install the PowerServices TelPac kit using the present manual. 2 - Fill in the information form. 3 - Send the form to your Teleservice centre (by Fax or Internet). 4 - Your centre will activate this service. 5 - You receive an acknowledgement of receipt.
The information form must be sent back in order to trigger remote monitoring of your equipment.
2.2 Preliminary check
Before starting the installation:
Make sure that an analogue type telephone outlet with an RJ11 jack is available in the vicinity of the UPS.If the telephone outlet is not RJ11 type, use an adapter. The telephone line must be authorised to call the Teleservice
centre 7 days a week.
If no electrical outlet is available on the UPS on which the PowerServices TelPac is to be installed, connect the power
cord to an outlet protected by the UPS.
Page 15
34003602EN/AB - Page 15
2. Installation
2.3 The various installation types
Remote
monitoring
One UPS
Several UPSs or products
Installation
type
Single-unit
Multi-unit
UPS connected
to the telephone line
Galaxy PW Galaxy 3000 Pulsar/Comet EXtreme/EX RT Galaxy Comet S31 Others
Galaxy PW Galaxy 3000 Pulsar/Comet EXtreme/EX RT Galaxy Comet S31 Others
Version to be
installed
Card Card Card External unit External unit External unit
Card Card Card External unit External unit External unit
Other acces-
sories required
No No No Yes
(1)
Yes
(2)
Yes
(4)
Yes
(3)
Yes
(3)
Yes
(3)
Yes
(3)
Yes
(3)
Yes
(4)
Authorised
installer
Customer/MGE after sales Customer/MGE after sales Customer/MGE after sales MGE after sales MGE after sales MGE after sales
MGE after sales MGE after sales MGE after sales MGE after sales MGE after sales MGE after sales
(1): Galaxy must be equipped with at least one JBUS / RS485 communication card with a free port (COM2) (2): Comet S31 must be equipped with one JBUS / RS485 communication card. A protected and UPS-secured outlet (1A) must be available in the vicinity of the UPS. (3): Each additional UPS must be equipped with a JBUS / RS485 communication card and a converter. (4): The connection is made in this case via the contact type inputs.
There are two types of installation:
Single-unit: only one UPS is remotely monitored by PowerServices TelPac.Multi-unit: several UPSs are remotely monitored by one single PowerServices TelPac.
Multiple unit installation is not dealt with in this manual. It requires a special study taking into account the configurations existing on the site. SUBD9 / Terminal converters (Ref. 34003755) are available from the Logistics department (LDS) in order to simplify network cabling. For more information, please refer to the MGE UPS SYSTEMS technical support documentation.
Page 16
Page 16 - 34003602EN/AB
2. Installation
2.4 Recommendations
To ensure continuous remote monitoring of your equipment, the unit must remain permanently connected to the telephone network once installed. Regular checks should be made to ensure that it is working properly via the indicator light on the front of the card or external unit (see section 1.5 "Indicator lights").
When working on your installation, always disconnect the telephone line to avoid any unwanted alarms being sent to the Teleservice centre.
2.5 Fitting the warning label
A set of yellow warning labels is provided in the PowerServices TelPac kit. This label is designed to warn MGE UPS SYSTEMS field technicians that the equipment is being remotely monitored and that work on equipment connected to PowerServices TelPac must only be performed once the telephone line has been disconnected.
In the case of "Single-unit" remote monitoring (one product), the label is placed on this unit, near the control buttons (see illustration).
In the case of "Multi-unit" remote monitoring (several products), the labels are placed near the control buttons on each product .
Page 17
34003602EN/AB - Page 17
2. Installation
Galaxy PW Galaxy 3000
Galaxy
Pulsar / Comet EXtreme Comet EX RT
Comet EXtreme
Comet S31
!
!
f
a
u
l
t
ATTENTION : Onduleur sous Teleservice
WARNING: UPS under Teleservice
MGE
UPS SYSTEMS
Ne pas mettre hors tension sans avoir au préalable déconnecté la ligne téléphonique
Do not switch off without first disconnecting the telephone line
Page 18
Page 18 - 34003602EN/AB
2. Installation
2.6 Setting up the RS485 link
General
For UPSs equipped with the PowerServices TelPac external version (see table section 2.3 "The various installation types"), communication between the UPS and the external unit is achieved via a RS485 link in 2-wire mode. The link works using the master-slave mode, with the PowerServices TelPac always being the master. Standard practice is to add line bias at the network master and impedance matching at the end of the line on the slave side. The line must only be biased at one point.
The external unit is pre-configured to be directly operational. No special configuration is necessary for a "Single-unit" type installation of the external unit with a Galaxy or Comet type UPS. Configuration of communication parameters (mode, rate, etc.) is carried out on the RS485 cards on the respective UPSs (see "Configuring the RS485 card for Comet" or "Configuring the RAUZ card for Galaxy").
"Single-unit" type installation
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
!
!
f
a
u
l
t
The RS485 shielded 2-wire link
Slave number xWithout biasWith impedance matching1200,8,N,1
MasterWith biasWithout impedance matching1200,8,N,1
UPS with JBUS/ RS485 card
PowerServices Telpac
Page 19
34003602EN/AB - Page 19
2. Installation
Impedance matching and bias settings
If a specific adjustment is required on the RS485 link, see the settings on DIP switch SA1:
Switch number
1 2 3 4
Function
T+ to R+ connection T- to R- connection T+ 0V bias R+ R- impedance matching
Switch number
5 6 7 8
Function
R+ 0V bias T- +5V bias T+ T- impedance matching R- +5V bias
Default position
Master (fixed)Two-wire linkBiasWithout impedance
matching
Example:
SA1.6 = ON,
T- has a +5V bias,
SA1.6 = OFF,
T- does not have a +5V bias
.
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
SA1
OFF
ON
1
8
Page 20
Page 20 - 34003602EN/AB
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
2
1
3
2
1
3
2. Installation
Configuring the shielding terminal
When electrical measurements are to be made on the RS485 link, it is possible to configure the shielding terminal of terminal block 7 as a "0V" terminal. The holes above each terminal allow a measurement probe to be inserted.
Default position,
= "SHIELDING"
= "0V"
7
Terminal block for the RS485 serial link to MGE UPS SYSTEMS equipment.
Page 21
34003602EN/AB - Page 21
2. Installation
Configuring the RS485 card for Comet
XM1
XM2
JOJO 6761294
ON
OFF
XM5 XM3 XM4
The settings proposed below comply with the recommended configuration (see section "Single-unit type installation"). They must be made before installing and commissioning the PowerServices TelPac external unit. The slave number is set to 1 by default. Parameters may be set using UPS Tuner or Soft-Tunor.
Configuration for Comet
Page 22
Page 22 - 34003602EN/AB
2. Installation
Configuring the RAUZ card for Galaxy
The settings proposed below comply with the recommended configuration (see section "Single-unit type installation"). They must be made before installing and commissioning the PowerServices TelPac external unit. The serial link format and the slave number should be set using UPS Tuner or Soft-Tunor.
OPNM
K L J
HIGA
B
COM2 COM1
OUVERT-FERME
RAUZ 6739856
O P
NM
K L J
Also check that the XC11 jumper at the edge of the GTCZ (or GT2Z) card is mounted in the JBUS position. The card has a mark printed on it to identify the position.
Configuration for Galaxy
Default configuration of the card
Page 23
34003602EN/AB - Page 23
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
< 4m
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
U-Talk
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
2. Installation
2.7 Installing the PowerServices TelPac card
N.B.: For Galaxy PW UPSs, first attach the cover plate provided in the pack.
Installation (Illustrations show the Pulsar EXtreme UPS)
It is not necessary to shut down the UPS.
Unscrew and remove the cover plate of one of the free
communication card slots in the UPS.
Insert the card and secure it using the screws.
Check the indicator lights (see section 1.5 "Indicator lights")
Check the status of the UPS indicator light 10 :
- on steady for 5s (status 1 in the table),
- then regular flashing every second during the start-up phase (status 3 in the table),
- lastly, random flashing during data exchange with the UPS (status 4 in the table).
Check the status of the CD indicator light 9 :
- off for 5s,
- then flashing during the start-up phase (status 3 in the table),
- lastly, off (status 2 in the table).
Connection
Connect the telephone cable to the card’s phone port on one end
and the telephone outlet on the other. If the wall outlet is not compatible with the connector proposed on the cable, use an adapter.
Installation is now complete. PowerServices TelPac is operational. Move on to stage 2 (see section 2.1 "Procedure").
10
ASI
ASI
ASI
9
Page 24
Page 24 - 34003602EN/AB
< 4m
< 1m
2. Installation
2.8 Installation of the PowerServices TelPac external unit for Comet UPSs
For this installation it is necessary to de-energise the UPS. The various PowerServices TelPac components do not present an electrocution hazard for the installer. It is necessary to initially check:
That the UPS is equipped with a JBUS/RS485 communication card 16 in one of its slots situated at the back or that such
a card is available for installation (ref. 6761294 JOJO).
That a UPS-secured outlet is available near to the UPS (L < 1m) as well as a telephone outlet (L < 4m).
Comet S31 7.5/10KVA
Installation (UPS de-energised)
Clean the place where it is planned to fit the external unit using
the solvent cleaning kit (see figures).
Remove the protective adhesive under the external unit. Place the external unit as shown, according to the type of UPS. Press down hard for 10 seconds to fix the adhesive. Configure the JBUS / RS485 card as shown in section 2.6 and
place it in the recommended location.
Connections
Connect one end of the power supply adapter cord to the back of
the external unit (5V DC) and the other end to a UPS-secured outlet near to the UPS.
Connect the external unit to the JBUS / RS485 communication
card 16 using the supplied cable: wire T- on terminal T-, wire R+ on terminal R+, then the shielding.
Connect one end of the telephone cable to the "phone" port on
the external unit and the other end to the telephone outlet. If the wall outlet is not compatible with the connector on the cable, use an adapter.
Fix the cables to the back of the UPS using the attached
adhesive cable holders.
16
Page 25
34003602EN/AB - Page 25
300 mm
< 1m
< 4m
2. Installation
Comet S31 15/20KVA Checking the indicator light (see section 1.5 "Indicator lights")
Put the UPS back into operation. Check the status of the UPS green indicator light 10 :
- on steady for 5s (status 1 in the table),
- then regular flashing every second (status 3 in the table).
Check the status of CD indicator light 9 :
- off for 5s,
- then regular flashing (status 3 in the table).
PowerServices TelPac is now ready for the parameter setting stage that is necessary for Teleservice. Consult the Technical Support documentation. Lastly, proceed to step 2 (see section 2.1 "Procedure").
16
Page 26
Page 26 - 34003602EN/AB
XR11
1 2 4
XR11
2. Installation
Installation, connections
1 - Open the doors giving access to the switch handles, 2 - Carry out the UPS shut-down procedure and remove the three protective panels, 3 - Check:
that the UPS is equipped with at least one
GTCZ communication card 17 and one RAUZ card 18 .
that a protected and UPS-secured outlet
19 is available. 4 - Configure the RAUZ and GTCZ card as indicated in section 2.6. 5 - Connect the power supply adapter to the UPS-secured outlet 19 . Bring the power supply cord 20 out through the grommet in panel A. 6 - Connect, install then fix link cable 21 . Bring the other end of the cable out through the grommet in panel A. 7 - Replace the protective panels.
2.9 Installing the PowerServices TelPac external unit for Galaxy UPSs
Installation must be carried out by our technicians. Installation of the PowerServices TelPac external unit requires UPS shut down, load tranfer to bypass and removal of three protective panels. Refer to the UPS’s user manual to carry out shut-down procedures in full compliance with safety procedures and instructions. Non-compliance with these may lead to safety hazards for the people concerned.
Galaxy view with doors open and protective panels removed
19
17 18
RAUZ card
red
black brown
20
21
Page 27
34003602EN/AB - Page 27
< 3m
2. Installation
8 - Clean the planned location for the external unit using the cleaning kit provided (see figure). 9 - Remove the adhesive protection from under the external unit. 10 - Place the unit as shown. 11 - Press down hard for 10 seconds to fix the adhesive. 12 - Connect the power supply cord 20 to the back of the external unit (5V DC). 13 - Connect the one end of the telephone cable 22 to the "phone" port on the external unit and the other end to the telephone outlet. If the wall outlet is not compatible with the connector on the cable, use an adapter. 14 - Connect the cable 21 to the JBUS / RS485 terminal block on the card:
- wire T- on terminal T-,
- wire R+ on terminal R+,
- shielding.
(A)
Galaxy view with doors open and protective panels in place
22
22 20
21
Page 28
Page 28 - 34003602EN/AB
A
B
5V
U-Talk
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
< 10m
2. Installation
2.10 Connecting contact type inputs
Contact type inputs enable the connection of equipment without RS485 / JBUS links or equipment that is unknown to PowerServices TelPac. By default, closing of a contact causes an alarm to be sent to the Teleservice centre. The unit can also be configured to send an alarm when a contact opens. The connection cable is not supplied.
7
UPS
Checking the indicator lights (see section 1.5 "Indicator lights")
Put the UPS back into operation. Check the status of the green UPS indicator light 10 :
- on steady for 5s (status 1 in the table),
- then regular flashing every second (status 3 in the table).
Check the status of the CD indicator light 9 :
- off for 5s,
- then regular flashing (status 3 in the table). PowerServices TelPac is now ready for the parameter setting stage necessary for Teleservice. Consult the Technical Support documentation. Lastly move on to step 2 (see section 2.1 "Procedure").
PowerServices TelPac card (2 inputs)
Page 29
34003602EN/AB - Page 29
2. Installation
PowerServices TelPac external unit (2 inputs + 4 extensions)
Four similar inputs C, D, E, F are available inside the external unit on terminal block XM13. To connect contacts to these four inputs, proceed as follows:
Remove the cover (partly unscrew the
screws and pivot the cover).
Remove the card from the external unit (3
screws).
Feed the cable through the grommet. Connect the cable(s) to terminal block
XM13 as shown in the figure opposite.
Replace the card in the external unit and fix
it in place (3 screws).
Replace the cover.
PowerServices TelPac is now ready for the parameter setting stage required for Teleservice. Consult the Technical Support documentation. Lastly, move on to step 2 (see section 2.1 "Procedure").
Extension
C
D
E
F
Settings
JBUS / RS485
PowerServices TelPac
UPS
CD
Phone
A 5V B R+ R- T+ T-
A
B
5V
< 10m
Terminal block XM13
Page 30
Page 30 - 34003602EN/AB
3. Maintenance
3.1 Cable diagrams
Serial cable (ref. 34003618)
Modem cable (ref. 34003729)
Comet link cable (ref. 34003747)
red
black
brown
brown red black
DB9 female connector
DB9/RJ9 cable (2.5 m)
RJ9 male connector
4
1
DB9 female connector
RJ9 male connector
2 3 4
5 6 7 8
4
3
2
1
9
1
RJ45 male connector
RJ45/RJ11 cable (5 m)
RJ11 male connector
8
1
6
1
RJ45 male connector
5 6 7
1 2 3
8
4
4
3
2
1
RJ11 male connector
5 6
DB9 male connector
DB9/3-wire cable (0.9 m)
T-
R+
DB9 male connector
T-
5 6 7 8
4
3
2
1
9
R+
frame
Loading...