MGE UPS Esprit 3, Esprit 4 User Manual

Page 1
Made in USAMade in USA
Slim Line Rack UPS
User’s Manual
Models 3 & 4
www.mgeups.com
Page 2
For service call: 1-800-438-7373
1660 Scenic Avenue
Costa Mesa, CA 92626
(714) 557-1636
www.mgeups.com
Revision History
Esprit Rack UPS User's Manual
86-153301-03
Copyright © 2000 MGE UPS Systems
All rights reserved. Printed in USA
Revision A00 New Release 10/00
Page 3
Important Safety Instructions. Save These Instructions.
This manual contains important safety instructions for the Esprit Models 3 and 4 that should be followed during installation and maintenance of the UPS and Batteries.
Caution: Risk of electric shock, even with the unit disconnected from the AC power source. Hazardous voltages still may be present thr ough operation from the battery. The battery supply should be disconnected by unplugging the battery cord from the UPS when maintenance or service work inside the UPS is necessary.
The UPS and battery module contains voltages which are potentially hazardous. All repairs should be performed by qualified service personnel only.
Do not attempt to power the UPS from any receptacle other than a 2-pole, 3-wire grounded
receptacle for models 3 and 4.
To reduce the risk of fire, connect Esprit to a circuit provided with the following maximum branch
circuit protection in accordance with NEC, ANSI/NFPA70:
Model 3: 30 ampere branch circuit protection; Model 4: 50 ampere branch circuit protection.
Do not place Esprit near water or in an environment of excessive humidity. Do not allow liquids or foreign objects to get inside Esprit. Do not block air vents in front, on top, or on bottom of Esprit. Do not plug any household appliances such as hair dryers into Esprit receptacles. Do not place Esprit in direct sunlight or close to heat emitting sources. The AC power receptacle should be near the equipment and easily accessib le. To isolate Esprit
from AC input, remove the input cord from the AC power receptacle.
Esprit contains lead-acid batteries that should be disposed of or recycled in accordance with
local applicable laws.
Prior to installation, store Esprit in a dry location. Storage temperatures must be between -4° to +113°F (-20° to +45°C); Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions to handle high voltages. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and type of batteries:
12 each, 12V - 5 Ahr. • For model 3, use MGE P/N: 031-000003-0000
• For model 4, use MGE P/N: 031-000004-0000
~
: alternating current supply symbol
: direct current supply symbol
: risk of electric shock symbol
Safety
i
Page 4
ii
Caution: Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate
the batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic. A battery
can present a risk of electric shock and high short circuit current.
The following precautions should be observed when working with batteries:
Remove watches, rings, or other metal objects. Use tools with insulated handles. Do not lay tools or metal parts on top of batteries.
Disconnect the charging power source prior to connecting or disconnecting battery terminals.
Wear rubber gloves, boots, and safety glasses. Determine if the battery is inadvertently grounded. Please dispose of the packaging in accordance with applicable laws.
Federal Communication Commission (FCC) Statement
Note: This equipment has been tested and found to comply with Class A limits of Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when equipment is operated in an industrial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits.
Page 5
iii
Contents
Quick Start ..........................................................insert
Important Safety Instructions ....................................i
1. Introduction........................................................1—1
MGE UPS Systems ......................................................................................1—1
Why the Need for Uninterruptible Power?....................................................1—1
Theory of Operation......................................................................................1—1
Make Sure You Have the Following: ............................................................1—1
2. Getting to Know Your Esprit Rack UPS ..........2—1
2A. Product Features & Benefits ................................................................2—1
2B. UPS Model and Battery Identification
(dimensions/weights and part numbers) ..............................................2—1
2C. Esprit Rack UPS Product Views With Rack Kit ....................................2—2
3. Installation..........................................................3—1
3A. Storing the UPS and Recharging the Batter y ......................................3—1
3B. Unpacking the UPS ..............................................................................3—1
3C. Placement of the UPS ..........................................................................3—1
Rack Mounting ..............................................................................3—1
3D. Optional Accessories ............................................................................3—1
3E. Connecting the Optional Extended Battery ..........................................3—2
3F. Disconnecting the UPS & Battery to Take Out of Service....................3—2
3G. Connecting to the Communication Ports ..............................................3—2
3H. Connecting the UPS to the Utility ........................................................3—3
3I. Connecting the Loads ..........................................................................3—3
3J. Solution-Pac Software ..........................................................................3—4
4. Startup and Shutdown ......................................4—1
4A. UPS Star tup..........................................................................................4—1
4B. Initial Star tup Tests and Diagnostics ....................................................4—1
4C. Battery Operation..................................................................................4—2
4D. UPS Shutdown......................................................................................4—2
4E. Front Panel Display Functions ..............................................................4—2
LED Operation ..............................................................................4—2
Button Operation............................................................................4—4
4F. Fault Alarms..........................................................................................4—5
5. Performance and Product Specifications........5—1
Sizing Guide and Battery Runtimes ..............................................5—2
Extended Battery Runtime ............................................................5—2
Page 6
iv
6. Advanced Configuration ..................................6—1
6A. Entering/Exiting Configuration Mode ....................................................6—1
6B Using Configuration Mode ....................................................................6—1
6C Configuration Options ..........................................................................6—2
7. Service & Maintenance......................................7—1
7A. Maintenance ..........................................................................................7—1
Maintenance Log ..........................................................................7—1
Places to Contact for Service and Questions ................................7—1
7B. Recycling Y our UPS ..............................................................................7—2
8.T roubleshooting ................................................8—1
Other Fine MGE Products........................................................inside back cover
Figures
2a. Rear View of Models 3 and 4
With Rack Kit and Extended Batteries ..................................................2—2
2b. Optional Rack Mounting Kit ..................................................................2—2
2c. Typical Front Views of Models 3, 4, Extended Battery, Label
Placement ............................................................................................2—2
3a. RS232, Contact Closures and Remote Shutdown................................3—2
3b. Communication Ports (USB and RS232 serial por t) ............................3—3
3c. AC Line Cord of the Extended Battery ................................................3—3
4a. Front Panel Indicators and Controls......................................................4—1
Tables
3a. UPS Wiring Information ........................................................................3—3
5a. Esprit Models 3 and 4 Rack UPS Specifications..................................5—1
Page 7
1—1
Thank you for your purchase of the Esprit rack "UPS" from MGE. The Esprit "UPS" will provide many years of, trouble-free power protection for critical high availability servers and other devices. Please read this manual fully, to familiarize yourself with the safety instructions and Esprit features.
MGE UPS Systems
MGE, one of the largest UPS manufacturers in the world, has a power protection solution for every power problem. Our product range includes UPSs from 250 VA to over 4.5 MVA in single and three phase configurations. Other products include Power Management Software, DC to AC inverters, line conditioners and isolation transformers. Contact your sales representative today for additional information about MGE’s other fine products.
Why the Need for Uninterruptible Power?
Servers and other electronic devices do not store sufficient energy to overcome the power outages and short interruptions that occur on a daily basis. Any interruption of the utility power may stop the operation of a computer and cause loss of data, potential hardware damage, and inconvenience.
A "UPS" is an uninterruptible power supply. The UPS has an internal battery to provide power back-up if the utility power is lost or a short
outage
occurs. In addition, the Esprit UPS provides
surge protection from indirect lightning strikes, power surges and short high voltage transients (spikes) created by machinery or other common equip­ment.
Theory of Operation
Esprit normally operates in the bypass mode. Surge suppression and filtering are also provided in this mode.
The UPS instantly transfers the load to the battery when a power failure occurs. If the power returns before the battery is exhausted, the operation returns to normal and the batter y is recharged.
The Esprit UPS is comprised of three major systems: the inverter, the battery/battery charger and the bypass.
All logic and supervision in the UPS is provided by a state-of-the-art micro-controller.
Inverter
The inverter is the heart of the UPS and inverts direct current (DC) from the battery into alternating current (AC) at 120 volts. The DC voltage from the batteries is converted into a pseudo-sine wave by a pulse width modulated (PWM) inverter. This unique MGE technique, eliminates all bulky 60 HZ components, reduces heat, and greatly enhances reliability.
Battery
The battery provides the energy source for back-up when a power failure occurs. The battery is a recombinant, sealed, lead acid-type battery which provides the high current required for UPS use and long life. It requires no addition of water during its life.
Battery Charger
The battery charger maintains the battery. The battery charger converts 120 volt AC utility power to filtered and regulated DC current specific for battery charging.
Bypass
The bypass is the electro-mechanical hardware providing a transfer to or from the in verter. This is done rapidly and synchronized to the utility power sine wave in order to pro vide contin uity to the critical device and not cause a re-boot.
Make Sure You Have the Following:
Esprit Rack UPS MGE P3 PolicySolution Pac CD ROM ◗ Warranty CardCables (RS232 & USB) ◗ Warranty StatementQuick Star t Guide ◗ Esprit LabelStabilizing Feet (2) ◗ Rack “ears” (2)Mounting Screws & Nuts
1. Introduction
Page 8
1—2
Page 9
2. Getting to Know Your Esprit Rack UPS
2A. Product Features & Benefits
Features Benefits Comments
Plug in operation Low installation costModular concept Greater flexibility Add batteries as neededHigh efficiency Longer life and back-up time Up to 93% on battery,
98% on utility
2/3 components reduction Longer life, higher reliability Unique MGE designMany user selectable Tailor the UPS to Front panel button accessible
parameters environment
Built-in receptacles Easier to specify Most common NEMA
receptacles are included
Quiet operation Allows placement in "library Small fan only runs while in
type" environments battery mode
Standard HID Provides the latest and fastest Other communications optional
communications communications possible
Networ k-based power Multiple server shutdown and
management software super vision
Web management New standard for web Easier to use than HTML and
via XML management provides additional features
Extended distr ibution Provides additional Optional
options receptacles for critical loads Call factory for availability
2B. UPS Model and Battery Identification
(US and Canadian Models)
Dimensions/Weights and Part Numbers
Model Dimensions (H W D) Weight (lbs.) Part Number UPC
Esprit 3 SLR 5.25 x 17 x 20 75 ESP030 635760894318 Esprit 4 SLR 5.25 x 17 x 20 75 ESP040 635760894455 SLR Extended Battery 5.25 x 17 x 20 60 ESP001 635760894004 Rack rail kit 5 x 5 x 17 6 ESP104 635760894042 AS/400 DB9 cable 12 x 12 x 1 1 ESP105 635760894059 AS/400 DB15 cable 12 x 12 x 1 1 ESP107 635760894073
2—1
Page 10
2—2
2C. Esprit Rack UPS Product Views With Rack Kit
Figure 2a. Rear View of Models 3 and 4 With Rack Kit and Extended Batteries
Model 3 Model 4
Figure 2b. Optional Rack Mounting Kit Figure 2c. Typical Front Views of Models
(ESP104) 3, 4, Extended Battery, Label
Placement
!
Extended Battery
Extended Battery
Vdc In/Ue/Entrada
Out/US
Ausg/Salida
144 VDC Amp hr: 5
Continuous Amps: 33
Do not disconnect
under load
In/Ue
Eing/Entrada
COM1 USB
SW4
Eing/Entrada
Utilization en atmosphere controlee Intended for use in a controlled environment Utilización preuista en un amblento controlado.
Vdc In/Ue/Entrada
Do not disconnect under load
144Vdc / 4 Amp hr. Continuous amps: 25
Vdc Out/Us/Salida
Intended for computer loads only
Vac
In/Ue
CAUTION: Batteries inside. Risk of electric shock even when input
power is removed. Do not remove cover. No user serviceable parts inside. Refer to qualified service personnel.
15A/120Vac
15A/120Vac
Overload
Overload
protection,
protection,
push to reset
push to reset
ATTENTION: Contiant batteries. Risque de choc electrique milime apreis
deparition tanaion d entrada. Ne pas enlevar le capot. Absence de piécede recharge à l'intérievr de l'appareil. Appeler personnel de meinlenance qualifié.
Vdc In/Ue/Entrada
Out/US
Ausg/Salida
144 VDC Amp hr: 5
Continuous Amps: 33
Do not disconnect
under load
In/Ue
Eing/Entrada
COM1 USB
SW4
Vdc In/Ue/Entrada
Do not disconnect under load
Continuous amps: 33.3
In/Ue
Eing/Entrada
Utilization en atmosphere controlee Intended for use in a controlled environment Utilización preuista en un amblento controlado.
144Vdc / 5 Amp hr.
Vdc Out/Us/Salida
Intended for computer loads only
Vac
CAUTION: Batteries inside. Risk of electric shock even when input
power is removed. Do not remove cover. No user serviceable parts inside. Refer to qualified service personnel.
15A/120Vac
15A/120Vac
Overload
Overload
protection,
push to reset
15A/120Vac
protection,
push to reset
15A/120Vac
ATTENTION: Contiant batteries. Risque de choc electrique milime apreis
deparition tanaion d entrada. Ne pas enlevar le capot. Absence de piécede recharge à l'intérievr de l'appareil. Appeler personnel de meinlenance qualifié.
Models 3 and 4
Extended Battery
Rack "ears"
(included)
mounting
screws & nuts
(included)
Page 11
3A. Storing the UPS and Recharging the Battery
Always store the equipment in its original packaging. The battery is of the sealed lead-acid type. Battery recharge requires that the battery module be
plugged into an energized NEMA 5-15 receptacle for 6-8 hours. The battery may be charged in the box by pulling the AC cord out through the bottom.
Battery storage or prolonged shutdown should never exceed 6 months or 68°F (20°C), for a battery initially at 100% charge. The battery warranty is void if the 6 month recharge interval is not adhered to.
3B. Unpacking the UPS
It is recommended that the equipment be unpacked in an area close to its installation location.
Caution:
The UPS and extended batteries weigh up to 75 pounds each.
Two people are required to lift the unit.
Remove the Solution-P ac CD, RS232 cable, and USB cable from the bo x and set aside f or later use . Fold the box flaps outw ard. Gently rotate the box on its side and slide the unit out of the box. Gently rotate the unit upright and then remove the packing material. Save packaging for future shipment of UPS to MGE for recycling.
3C. Placement of the UPS
Choose a location out of direct sunlight with adequate ventilation. The operating ambient temperature range is 32° to 104°F (0° to 40°C). Temperatures above 77°F (25°C) should be avoided as battery life is reduced.
Ensure that there is clearance around the intake vents in the front of the UPS and that the rear is unob­structed. Six inches of clearance at the rear of the unit is required. Units may be placed vertically or hor­izontally with zero clearance. Use the supplied stabilizing feet when vertically mounting the UPS and/or extended battery.
Rack Mounting
Optional rack mounting hardware is available for rack mounting. Instructions for their use are included in the rack kit. See Figure 2a.
3D. Optional Accessories
The following accessories are available for use with your equipment. Refer to each accessories' manual for full installation, operation and maintenance instructions.
Rack Rail Kit AS/400 Cables (for contacts)Multi-slot Communication Cabinet Extended distributionExtended batteries (no additional manual necessary)
3. Installation
3—1
Page 12
3E. Connecting the Optional Extended Battery
Plug the DC battery cable into the UPS module as shown in Figure 2a. The cable plug is keyed, so make sure to align the plug properly to the receptacle. Do not force the cable on, nor attempt to reverse the connection. To do so, will damage the equipment and void the warranty. Plug the AC line cord into an AC line receptacle. See Figure 3f.
3F. Disconnecting the UPS & Battery to Take Out of Service
Turn off the UPS module by depressing the “Off” red button if the “inverter on” or "utility power present" (bottom LED) is lit. Unplug the AC line cord for the battery module. Unplug the DC battery cord. For extended batteries unplug AC line cord and DC battery cord.
3G. Connecting to the Communication Ports
If you plan to utilize Solution-P ac HID ("human interface de vice" protocol), read the Solution-P ac HID manual on the Solution-Pac CD for a full description of its features.
To connect to your computer, you will need the RS232 serial por t or a USB (Universal Serial Bus) port. The connection will be made between your computer’s serial or USB por t and the serial or USB port on the rear of the UPS module as shown in Figure 3d. Cables are supplied for this purpose.
A slide switch is provided for either RS232 or USB communication. The slide switch (shown in
Figure 3d)
is preset for RS232. Push the switch down for USB communication.
If communication does not operate, check the position of the slide switch.
The RS232 port also contains two low voltage (24 VDC)/low current (5MA) contact closures. See
Figure 3d
below. To use these an optional cable is available. These can be used by AS/400
computers or for special uses.
Figure 3a. RS232, Contact Closures and Remote Shutdown
1. Open
2. RTXD transmit (TX)
3. RRXD receive (RX)
4. OPEN
5. LOGIC RETURN (OV)
6. PNP (plug and play, do not use)
7. ALARM - Contact closure through a transistor from pin 7 to pin 5 when "low battery".
8. RPO - A logic high will activate an output shutdown.
9. INVO - Contact closure through a transistor from pin 9 to pin 5 when the unit is on Inverter.
3—2
5
9
4 3 2 1
8 7 6
OV
PNP
OV
RX
+8 to
+15VDC
TX
OV
Page 13
The transistor resistance is 27 ohms and the maximum current allowed is 140mA AC or DC with ambient temperature of up to 40°C.
In order to get a "logic low" you have to limit the current to: logic low voltage required divided by 27, logic low voltage = 0.5V. I max = 0.5/27=0.0185A=18mA.
If you intend to use other forms of communication, an optional Multi-slot Communication is available that will convert the RS232 serial commands into the following formats:
Ethernet, SNMP J-Bus/RS422 High voltage/current relay contacts
Figure 3b. Communication Ports (USB and RS232 serial port)
3H. Connecting the UPS to the Utility
Plug the AC line cord of the UPS module into an AC 2-pole, 3-wire grounded receptacle for models 3 and 4. There should be no other loads on this branch circuit. To do so may result in a circuit overload. Refer to National Electrical Code (NEC) specifications for requirements in your area or ask your electrician.
Table 3a. UPS Wiring Information Figure 3c. AC Line Cord of the Extended Battery
Model Plug Amp rating
3 L5-30 30 4 5-50 50
3I. Connecting the Loads
Utilize the receptacles on the rear of the UPS module to connect your critical loads. If you need more, you may want to consider the addition of MGE's optional distribution extension.
Caution: Never plug a surge suppressor into the output of a UPS. Most UPSs do not produce the proper output wave shape for surge suppressor use. Improper use and resultant damage is not covered by warranty.
r n
u
3—3
G
W
W
G
Vac In/Ue/Entrada
Vdc In/Ue/Entrada
CAUTION:
Batte power is removed. Do Refer to qualified serv
ATTENTION:
Con
deparition tanaion d entra recharge à l'intérievr de l
144Vdc / 5 Amp hr. Continuous amps: 25
Utilization en atmosphere controlee Intended for use in a controlled environment Utilización preuista en un amblento controlado.
Do not disconnect under load
Vdc In/Ue/Entrada
RS232
Serial Port
Slide
Switch
COM1 USB
SW4
Vdc In/Ue/Entrada
Do not disconnect under load
USB
Port
Utilization en atmosphe Intended for use in a co Utilización preuista en
Page 14
3—4
Caution: Connect only computer-type loads to the Esprit UPS. Warranty is void if non­computer-type loads are connected to the UPS.
3J. Solution-Pac Software
Solution Pac software allows you to interface your computer with the UPS. The software is loaded on your computer and through the communication port, can access and react to status information from the UPS. Refer to the Solution Pac manual on the CD for a full description of its operation.
Page 15
4. Startup and Shutdown
4A. UPS Startup
You are ready to start the equipment after installing the UPS module, optional battery module(s), any options, and the communication cable (if used).
Follow these simple steps:
1. Connect your computer equipment.
2. Depress the green "ON" button. You will hear an audible beep, and the “Utility Power Present” LED " " will be green. See Figure 4a.
3.
Turn on any computer equipment.
Your UPS has auto-frequency and voltage sensing and will automatically configure itself to 120, 50 or 60 Hz.
Your equipment is now receiving
protected power from the UPS.
Figure 4a. Front Panel Indicators and Controls
LED operation is described fully in section 4E.
4B. Initial Startup Tests and Diagnostics
Your UPS will perform internal diagnostics as well as check utility power. After depressing the green "On" button and starting your UPS for the first time, you will hear an
audible "beep" confirming the button has been depressed, and your UPS will perform the following diagnostic tests:
1. All front-panel LEDs will light, allowing visual confirmation that LEDs function properly.
2. UPS will confirm the integrity of factory calibration settings. FAULT indicator illuminates " " if internal settings have been corrupted.
3. UPS will check utility input frequency and configure itself accordingly. If utility power is not present, the UPS configures itself to run at the last frequency it detected in a previous power-up operation.
!
g)
4—1
Control Buttons
OFF
6 Status LEDs
ON
Alarm
Silence
(Controls audible alarm
& alarm/fault handlin
1. 2. 3. 4. 5. 6.
1. Inverter ON
(UPS on battery power)
2. Utility Power Present
3. Output Overload
4. Battery Charging Indicator
!
5. Replace Battery
6. Fault Detected
Page 16
4—2
If desired, the UPS can be set up to operate at a known, fixed frequency regardless of the detected utility frequency. Fixed-frequency operation is often desirable in installations that make use of cold-start capability. Discussion on this is in the Advanced Configuration Section (section 6) of this manual.
If utility power is present and within specifications, your UPS will start up in bypass mode. Power will be supplied to your computer loads and will be protected from a utility loss. The utility power present, green indicator " ", will be lit.
If utility power is not present, your UPS will start on battery until utility power is restored. No diagnostics will be performed in this case.
4C. Battery Operation
Battery Mode: Utility power is outside specifications and computer loads are now powered
On by UPS battery source.
Bypass Mode: Utility power is present and within specification limits.
On
Inverter On Mode: Utility power is available but is outside specification limits.
On Flashes
Battery Low:
A low battery warning will sound. Acknowledge the alarm by depressing the
Flashes
grey push button. Immediately save your work and shut down connected computer loads to prevent data loss. The actual time to reach "low batter y" can vary significantly depending on the critical loads and condition of the batteries.
4D. UPS Shutdown
At any time, your UPS may be shut down by depressing the "Off" red button. Make sure to hold
the button down for 2 seconds (prevents accidentally turning off your UPS). You will hear an audible "beep" confirming the button has been depressed.
4E. Front Panel Display Functions
LED Operation
There are six status LEDs, arranged in a vertical column just above the control buttons. Icons to the right of each indicator indicate the function. The status indicated by each LED is listed below, in the order that they appear on the front panel (top to bottom):
!
Page 17
4—3
Off Flashing On
1. Fault The UPS is operating The UPS has detected a The UPS has detected an
Detected normally. No faults new operating fault. The operating fault that has been (yellow) have been detected. FAULT indicator will continue acknowledged by the user.
to flash until the fault has been acknowledged by pressing the grey silence alarm button.
2. Replace The UPS batter y is O.K. The result of the last battery
Battery test indicates that the UPS (red) battery cannot provide at least
half of its rated run time. The battery should be replaced. This could also indicate an inverter problem.
3. Battery The UPS battery is The charger is not operating The UPS battery is not yet
Charging charged within 80% of properly. Check that the fully charged and cannot Indicator its full capacity. battery module power cord deliver its full rated run time if (green) is plugged into a source a power failure occurs.
other than the UPS itself.
4. Output The UPS is capable of The UPS is heavily The UPS is slightly over-loaded.
Overload supporting the load overloaded. Automatic The UPS will continue to sup­(yellow) connected to it. shutdown is imminent. port the load but it may not be
able to provide its full rated run time if the UPS has to run on battery power. Reduce the load.
5. Utility Utility power is not Utility power is present but Utility power is present, stable
Power connected to the UPS. is either unstable or the line and within acceptable voltage Present voltage is too high or too low limits. In this state, the UPS (green) to allow operation in utility will be operating on utility
power mode. In this state, power mode. the UPS will normally be operating on battery power.
6. Inverter The UPS is not The UPS is operating on The UPS is operating on
on/UPS operating on battery battery power and battery power. The inverter on battery power. The inverter is performing its periodic is running. power turned off. inverter/battery test. The (green) battery test is started once
every 28 days of operation and lasts for up to 60 seconds.
!
Page 18
4—4
The "Fault Detected" LED turns on and acts as described above for ANY system alar m, including those that have their own status indicators (e.g. overload, replace batter y).
Button Operation
There are 3 buttons present on the front panel:
The grey, " " top button controls the audible alarm and alarm/fault handling.The green, " " center button turns the UPS on.
The red " ", bottom button turns the UPS off.
The internal microprocessor can directly read the state of the top (alarm silence) and bottom (power off) buttons. The UPS is capable of distinguishing between a “short” and “long” depression and can perform different actions based on how long a button or combination of buttons is depressed. A “short” button press is defined as pressing and releasing a button within a 2-second time frame. A “long” button press is recognized if a button is pressed and held for more than 2 seconds.
When a button is pressed, the UPS responds by beeping the horn. If the button is held down longer than 2 seconds the UPS responds by beeping the horn again. The action assigned to a short button press is carried out AFTER the button is released. Actions assigned to a long button press are carried out immediately after the 2-second timeout, even if the button is not released after this time.
The UPS is capable of decoding six distinct “button states”:
1. Short Top button press: Silences the alarm beeper if it is active. If a new alarm/fault is
detected after a silence operation, the beeper will be re-activated to issue the new alert. This button sequence can be thought of as an "alarm/fault acknowledge" function. By pressing it, the user acknowledges the presence of the then-active system alarms. After an acknowledge sequence, any new alarms that occur will be brought to the user's attention by re-activating the alert beeper.
2. Long Top button press: Clears all active alarms and attempts to re-start the UPS on utility
power. If the UPS is already operating on utility power, or operating on inverter because utility
power is not present or not usable, then the alarms will be cleared but the restart-on-utility request will be ignored. If the condition(s) that caused an alarm persist after alarm(s) are cleared, the UPS will re-issue the alarm after a short delay.
3. Short Bottom button press: No UPS activity is associated with this button combination.
4. Long Bottom button press: Powers down the UPS. This is the "off switch". When the UPS
is powered down, neither utility or inver ter power is provided to the load.
5. Short Top + Bottom button press: The UPS will perform a battery testIF the UPS is running
on Utility power, and the batter y is at least 80% charged (charger indicator on). If these two conditions are not met, the test will be postponed until they are met.
6. Long Top + Bottom button press: The UPS will enter configuration mode. In this mode,
various operational parameters may be changed b y the user. To exit configuration mode, press the top and bottom buttons again.
Page 19
4—5
Although six button states are detectable, not every button combination has an assigned task. button states/combinations that have no assigned task will simply be ignored.
The “Utility Power Present” does NOT reflect the state of the UPS output. If, for example, the UPS has shut down due to an output overload, the Utility Power Present LED may be solidly ON but the UPS output could be turned off (due to the overload).
4F. Fault Alarms
LED Status Audible Alarm Pattern UPS Action
Fault " " LED flashes until Low Run time Warning Warning when there is less than alarm is acknowledged or (shor t-long-shor t beep) 3 minutes of back-up time cleared. remaining.
Fault " " LED flashes until Low Battery Warning/Shutdown Occurs within 1 minute of UPS alarm is acknowledged or (shor t-long-long beep) shutdown. Could also indicate cleared. a faulty battery charger.
Fault " " LED flashes until High Battery Warning There is a problem with the alarm is acknowledged or (shor t-shor t-short-long beep) battery system. problem is corrected.
Fault " " LED and Charge Charger Problem Warning
The battery system
may not be
" " LED flashes until alarm (long-short-long-short beep) plugged into an AC source or is acknowledged or problem there is a charger problem. is corrected.
Fault " " LED Battery Fail Battery/Inverter Test Failure Indicates failed battery/inverter " " LED flashes until alarm (long-short-short-short beep)
test performed every 28 days.
is
acknowledged or cleared.
Clear
fault and recharge battery
for 8
hours. Manually initiate test
again. I
f fault recurs, call for
service.
Fault " " LED flashes until Output Voltage Low Output shuts down to protect alarm is acknowledged or (on inverter, load from low voltage. cleared. short-long-shor t-shor t beep)
Fault " " LED flashes until Output Voltage High Output shuts down to protect alarm is acknowledged or (on inverter, load from high voltage. cleared. short-shor t-shor t-short beep)
Fault " " LED and Overload Output Overload Flashes when load exceeds " " LED flashes until alarm Warning/Shutdown 105%, solid when overload is
is acknowledged or problem (long-long-long beep) 101-105%, automatically clears corrected, flashes when when load is reduced. shutdown is imminent, and solid if warning only.
!!!!!!!
!
Page 20
4—6
Page 21
5.
Performance & Product Specifications
5—1
Table 5a. Esprit Models 3 and 4 Rack UPS Specifications
Item Specification Comment
Output V A 2880/4000 Output W 2016/3150 Surge protection, joule rating 420 joules per system Each battery cabinet adds 210 joules Waveform Stepped approximation of sine wave Pseudo-sine wave on back-up only Nominal input voltage 120 VAC (opt.100 or 127 VAC) +10%, -15% Maximum input voltage (VAC) 140 Low voltage transfer (VAC) 102 Adjustable to 96 Low line return (VAC) 109 Adjustable to 99 High line transfer (VAC) 132 High line return (VAC) 126 Input current (A) 24/33 maximum Input frequency (HZ) 50 or 60 + or - 2.5 HZ Auto-select at start-up Input protection Customer provided, branch Transfer time 4-8 ms. To or from battery Overload protection, line mode Output disabled at >120% load Overload protection, battery mode Output disabled at >120% load Efficiency, on utility >98% Efficiency, on battery >93% Battery mode voltage 120 VAC + or - 5% (120 VAC mode) Battery life expectancy 3-5 years Output frequency regulation Nominal + or - 0.5 HZ On battery Battery mode output protection Electronic current limit Self-protected Battery 12 each 5 Ah 144 VDC nominal bus Maximum charge current 0.7 A With 100% discharge Float voltage 2.25 VDC/cell (162 VDC) Backup time 5 minutes 100% load Battery protection Current limiting fuses 1 internal, 1 w/extended battery Recharge time 8 hrs..to 90%, 4 hrs.. to 80% Full discharge Battery charger ripple current 0.05C maximum Low battery alarm level 1.75 v/cell, no load (126 VDC) Low battery shutdown level 1.65 v/cell, full load (119 VDC) Faulty battery alarm level 1.8 v/cell (130 VDC) Low battery alarm level 3 minutes before end of discharge Charger protection Overload, current protected Max. # of extended batteries Unlimited Controls Start, stop, alarm reset switches Communications RS232 or USB + two contact HID on RS232 or USB
closures included (selectable RS232 or USB) Temperature 0-40 C Air flow 30 CFM on battery Heat: ESP030 40-141W Humidity 0-95% non-condensing Heat: ESP040 60-211W Noise 45 dBA maximum
Page 22
Table 5a. Esprit Models 3 and 4 Rack UPS Specifications (Continued)
Item Specification Comment
Design standards Safety; UL, cUL 1778, Emissions;
FCC A, Surge protection; ANSI C62.41, Transportation; (drop test), IEC 68 level 1, (vibration), IEC
68.2-6 level 3, testing;PowerCet
tested Input connection NEMA 5-30/50 w/ six foot cord Output connections 1 NEMA 5 30/50 and 4 5-15 Auxiliary DC input 1 each special female connector on Provides additional battery time
UPS (18" cord and male connector
on optional battery) Size 1 each (UPS, battery) 5.25" X 7.25" X 19" Weight 65/70 lbs.. total MTBF 200K hours
Sizing Guide and Battery Runtimes (In minutes, 0.62 PF)
Unix Server 1 2 3 4
server servers ser vers servers
PC Server 1 2 3 4 5 6 7 8
server servers servers servers servers ser vers servers servers VA 500 1000 1500 2000 2500 3000 3500 4000 Esprit 3 SLR 90 40 28 19 11 6 Esprit 3 SLR + 1 Ext. Batt. 240 90 40 28 19 15 Esprit 3 SLR + 2 Ext. Batt. 360 150 90 60 45 38 Esprit 4 SLR 120 50 30 20 15 12 9 7 Esprit 4 SLR + 1 Ext. Batt. 240 100 72 45 35 28 24 18 Esprit 4 SLR + 2 Ext. Batt. 360 180 110 75 55 45 35 29
Extended Battery Runtime (internal plus extended battery, in minutes, 0.7 PF)
Extended Batteries (Qty.) 1 2 3 4 Model Esprit 3 12 30 45 60 Esprit 4 15 25 38 49
Note: All battery times above are typical.
5—2
Page 23
6. Advanced Configuration890-=qwertyuio
Esprit Front Panel Configuration Mode Usage and Instructions For advanced users only!
The Esprit UPS is shipped from the factory with a configuration that is suitable for most applications. However, there are some circumstances where modification of the UPS operating parameters is required. A special configuration mode, accessible from the front panel, has been provided for this purpose. This section of the manual describes how to use the front panel configuration mode and describes the UPS parameters that can be changed by the user.
Caution: Configuration mode can only be entered when the Esprit is operating on utility power. Attempts to enter configuration mode when the UPS is operating on battery power will be ignored.
Caution: When the Esprit is in configuration mode, transfers to battery power are inhibited. The load connected to the UPS will not be protected while the Esprit is in this mode. Normal UPS operation will resume upon exit from configuration mode.
6A. Entering/Exiting Configuration Mode
The Esprit front panel configuration mode is entered by simultaneously depressing the top (Alarm silence) and bottom (Pow er OFF) b uttons for approximately 1-2 seconds. The Esprit will acknowledge entry into configuration mode by sounding the buzzer and slowly flashing the AC PRESENT indicator. The AC PRESENT indicator blinks slowly during the time that the Esprit is in configuration mode.
To exit configuration mode, press and hold both top and bottom buttons again. The AC PRESENT indicator will stop flashing, and the remaining indicators will resume their normal function. Any changes to the Esprit configuration made by the user will be permanently saved.
The Esprit incorporates a timer that automatically terminates configuration mode if no activity is detected for 30 seconds. This feature prev ents the unit from remaining in the vulner ab le offline state for a long period if the configuration mode is accidentally entered.
6B. Using Configuration Mode
When configuration mode is activated, the usage of the front panel status indicators changes. The top 4 indicators (GENERAL FAULT, BATTERY FAULT, BATTERY CHARGING, and OVERLOAD) are no w used to indicate the internal feature being vie w ed or modified. The AC PRESENT indicator blinks slowly to indicate that the Esprit is in configuration mode. The bottom-most ON BATTERY indicator shows the state (on/enabled or off/disabled) of the currently active feature.
In configuration mode, the topmost button (Alarm silence) is used to advance to the next configuration setting. The top 4 indicators, which light in unique patterns to indicate which option is being viewed/modified, cycle forw ard each time the top b utton is pressed. The bottom button (power off) is used to toggle the current option ON or OFF. The ON BATTERY indicator toggles on and off each time the bottom button is pressed.
6—1
Page 24
6—2
It is possible to cycle backward through the configuration options by pressing and holding the top button. A given option setting can be forced to its factory default state by pressing and holding the bottom button.
The middle (Power ON) button is not used in configuration mode. To leave configuration mode, simultaneously depress and hold in both the top and bottom
buttons until the buzzer sounds and the AC PRESENT indicator stops flashing. Any changes made to the Esprit configuration will now be permanently saved.
6C. Configuration Options
The table below lists the options that can be changed by the user in configuration mode, and shows which front panel indicators will be on for each option.
Option Indicators
Number Fault Batt Fail Charge
Overload
Option affected
0 ————Extended Battery switch A 1
*
———Extended Battery switch B
2
*
——Extended Battery switch C
3
**
——Operating voltage switch A
4 ——
*
Operating voltage switch B
5
*
*
Input voltage tolerance switch A
6
**
Input voltage tolerance switch B
7
***
Test alarm
8 ———
*
Limit run time on battery power
9
*
——
*
Cold start enable
10
*
*
Auto restart after low battery shutdown
11
**
*
UPS mode (On=Normal, Off=Line condition)
12 ——
**
Automatic frequency detect on powerup
13
*
**
Operating frequency (0=50 Hz, 1=60 Hz)
14
***
Comm port mode (0=Normal, 1=Tuning/factor y)
15
****
Power-on inverter test
Indicators: (
*
) = Option On/illuminated, ( ) = Option Off/dark
Page 25
6—3
Options 0, 1, 2 – Extended Battery Configuration
These three option switches should be changed as shown in the table below when new battery cabinet(s) are added to the UPS. The standard setting for these options are all OFF, selecting the single/internal battery module option.
Option Setting Number of battery cabinets installed
0 (A) 1 (B) 2 (C) Esprit 3 & 4
(SlimLine)
—— — Internal only
*
—— 1
*
2
**
3
——
*
4
*
*
5
**
6
** *
7
Indicators: (
*
) = Option On/illuminated ( ) = Option Off/dark
Options 3, 4 – Operating voltage selection
These two options select the nominal operating voltage of the UPS as shown in the tab le below. The factory setting is 3=Off, 4=Off, which configures the Esprit for 120V (230V) operation.
Switch Setting Nominal Operating Voltage
3 (A) 4 (B) Low Voltage
—— 120 V
*
100 V
*
127 V
**
Custom
Indicators: (
*
) = Option On/illuminated ( ) = Option Off/dark
Do not select the "Custom" setting (Option 3 & 4 both ON) unless you are instructed to do so by MGE service.
Page 26
6—4
Options 5, 6 – Input Voltage Tolerance
Use these two option switches to select the Esprit’ s sensitivity to low/high input voltage conditions . The Esprit will switch to battery power when the utility voltage falls outside the range selected. The percentages shown in the table below are subtracted/added to the nominal voltage setting as set by options 4, 5. The factory setting is 5=OFF, 6=OFF which selects the –15/+10% range.
Switch Setting Input Voltage Tolerance
5 (A) 6 (B) Low limit High limit
—— - 15% + 10%
*
- 20% + 15%
*
- 10% + 10%
**
Custom
Indicators: (
*
) = Option On/illuminated ( ) = Option Off/dark
Do not select the "Custom" setting (Option 5 & 6 both ON) unless you are instructed to do so by MGE service.
Option 7 – Test Alarm
The normal state of this option is OFF. Turning it on will instruct the Esprit to issue a "User Test Fault". This condition does NOT affect the UPS operation in any way, but it does close the Low Battery contact on the DB9 communication port, and activates the FAULT indicator and audible alarm (pattern shor t-shor t-long). You can use this option switch to test hardware connected to the Low Battery contact without actually running the Esprit batter y down.
To clear the User Test Fault, set this option to OFF, or follow the "Alarm Clear" procedure. Press and hold the top button.
Option 8 – Limit run time on battery power
The normal setting for this option is OFF, which allows the UPS to operate on battery for the maximum time possible. The Esprit run time on battery is limited only by the capacity of it’s battery system and the battery state of charge.
If Option 8 is turned on, the Esprit will run a maximum of 15 minutes on battery power before turning itself off. Actual run time may be less, depending on size of battery system and load.
Option 9 – Cold Start (allow UPS to run on battery power on startup)
When Option 9 is turned ON (factory setting), the UPS is allowed to start up on battery power if the AC input voltage is not present or not of satisfactor y quality. The ability to run on battery power immediately upon startup is known as "cold start" capability.
If this option is turned OFF, the UPS will start up with its output OFF if input AC is not present or usable. The output will not be turned on until input AC is present and usable. Once the UPS turns on it’s output, a subsequent loss/disturbance of input AC will cause the UPS to run on battery power as usual.
Page 27
6—5
Option 10 – Automatic UPS restart after Low Battery shutdown
The factory setting for this option is ON, which allows the UPS to automatically turn its output back on following a Low Batter y shutdown once input AC is present. This setting is the usual one for applications where the UPS is connected to automated or unattended equipment that is capable of restarting itself without direct human intervention.
If the load connected to the UPS requires special attention when it is powered up, this option should be turned OFF. When Auto Restart is turned off, the UPS output will stay turned off until it is manually restarted by pressing and holding the top silence/restart button on the front panel.
Option 11 – Automatic UPS mode
The default setting for Option 11 is ON, which allows the Esprit to act like a typical UPS. The UPS will automatically switch from utility to backup power as needed.
If this option is turned off, the Esprit acts like a line conditioner. The battery backup system is disabled. If the input utility power is acceptable, the Esprit will pass it through to the load. If the input power is unacceptably low or high, the load power is removed. The Esprit will NOT operate on battery power if Option 11 is turned off!
Option 12 – Automatic Frequency Detect
When this option is set the factory default ON setting, the Esprit will analyze the input power when it is turned on, and configure itself to operate at the proper frequency (50 or 60 Hz). If utility power is not present when the Esprit is turned on, it will configure itself based on the frequency setting in place when the unit was last turned off (see option 13 setting).
If this option is turned OFF, the Esprit will configure itself to operate using a utility power frequency set by Option 13. Power-up input AC frequency analysis is not performed.
Option 13 – Operating Frequency selection
This option setting is only effective if Option 12, Automatic Frequency Detect is turned off. If Option 12 is turned off, this option (13) setting can be used to select the Esprit’s nominal oper­ating frequency. If this option is OFF, 50 Hz operation is selected. If ON, 60 Hz operation is selected.
The factory setting for this option is ON, selecting 60 Hz operation at startup. Note, however, that the setting of this option is overwritten by the UPS logic if option 12 (Automatic Frequency Detect) is enabled. If the Espr it is powered up from a 50 Hz source with option 12 enabled, the setting of this option (13) will be forced to OFF.
Option 14 – Communication Mode Selection
This option should be left in it’s factor y-standard OFF setting unless you are instructed to turn it ON by MGE Service. If this option is inadvertently turned ON, the Esprit may be rendered incapable of operating with UPS monitoring and control software, including MGE’s Solution-Pac software.
Page 28
6—6
Option 15 – Power-On Inverter Test (POIT)
When this option is set to the factory default ON setting, the Esprit will perform a short battery/inverter test shortly after it is tur ned on. This test is only performed only if the UPS is able to power up the load from utility power first.If the POIT is enabled, the UPS will power up the load from utility power, then briefly switch to battery power approximately 5-7 seconds after it is powered up. The UPS runs on battery for only 3-5 seconds, so no significant drain on the battery will occur.
The POIT is disabled if this option is turned OFF. The setting of this option has no effect on the scheduling and execution of the monthly inverter/battery test, which runs less frequently than the POIT but is considerably more exhaustive.
Page 29
7—1
7. Service & Maintenance
7A. Maintenance
Clean the UPS with a dry cloth after turning off all power to the UPS and switching off the power switch.
The UPS performs monthly automatic battery tests. Howev er , it is recommended that a 6 month test be performed on the UPS for battery condition. Perform all tests off peak hours with applications shut down.
1.Turn off power to the UPS via the branch circuit breaker to the UPS. It is not recommended to disconnect the plug from the UPS to the utility power due to disconnection of the safety ground.
2.Allow the UPS to run on batter y power for 1 minute. Monitor the UPS for any fault LEDs and if none are observed, return power to UPS and log results below in the maintenance log. If battery fault LED is lit, call for service.
Maintenance Log
UPS serial number Date of installation Location Notes
Date Check Comments
6th month 12th month 18th month 24th month 30th month 36th month 42nd month 48th month 54th month 60th month
Places to Contact for Service and Questions
In USA or Canada, call 1-800-438-7373 M - F 24 hours. For service outside USA or Canada, call your local distributor . You may also visit our web site at: www.mgeups.com
Page 30
7—2
7B. Recycling Your UPS
In USA or Canada, call 1-714-557-1636, M - F, 6:00 A.M.to 5:00 P.M.PST. Ask for a return goods authorization for free UPS or battery recycling. MGE does not cover return freight charges for recycling and will not accept items without a return goods authorization number.
Page 31
8—1
8. Troubleshooting
Problem Possible cause
Required User Action
UPS does not tur n on. UPS is not plugged in. Plug UPS into a working outlet.
Wall socket is dead.
Test wall socket, repair as required.
UPS has not been activated. Press Output ON (1) button for
one second, then release.
There is no power to Confirm that the UPS is on. See above.
the computer load. Output circuit breaker is Disconnect load and check. If
tripped. okay, reset circuit breaker.
Load plugs are not seated Remove and reseat plugs.
properly.
Batter y Online indicator Utility line is out of Test wall socket, repair as
remains on, even though specification. required. line voltage is present.
UPS beeps occasionally. UPS is on battery. None - UPS is protecting your
system.
UPS does not provide Battery capacity is low. Allow battery to charge for 24
the expected backup time. hours, then retest.
Protected equipment power Reduce load, then retest.
requirements exceed UPS capacity.
Overload indicator flashes. Protected equipment power Reduce the load.
requirements exceed UPS capacity.
Batter y Fault indicator is lit. Battery is weak or charger is Make sure batter y is connected.
faulty. If battery is proper ly connected,
allow the battery to charge for 24 hours. Retest. Have batteries replaced if condition persists. Make sure battery charger is plugged into a functioning outlet.
Page 32
Notes
8—2
Page 33
Other Fine MGE Products
Eclipse Surge Suppressors Ellipse
300-1200 VA
ESV+ UPS ESV+ Rack UPS
780-2200 VA 780-2200 VA
EX UPS EX Rack UPS
700-3000 VA 700-3000 VA
Call MGE for many more power solutions:
(714) 557-1636 or (800) 523-0142
US
MGE GREEN SWEEP
Call MGE to return your UPS for free recycling to a US EPA-certified recycling center and help protect our environment.
Esprit UPS
3 - 13.5 kVA
Page 34
MGE UPS SYSTEMS
USA (headquarters)
1660 Scenic Avenue Costa Mesa, CA 92626 tel: (800) 523-0142
(714) 557-1636 fax: (714) 557-9788 www.mgeups.com