MGE 3000 VA, 2000 VA, 1500 VA, 2500 VA User Manual

Pulsar EXtreme
1500/2000 VA 2500/3000 VA
installation and user manual
French
German
Spanish
Netherlands
5103321100/AA - Page 1
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar EXtreme a reference in environmental protection include:
the eco-design approach used in product development; production in an ISO 14001 certified factory; recycling of Pulsar EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EXtreme range, we invite you to visit our web site at Erreur! Signet non défini. or contact your MGE UPS SYSTEMS representative.
Page 2 - 5103321100/AA
Safety rules
Safety of persons
A UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed. If it is connected to the AC-power source via a wall outlet, measurements are required to ensure that the total leakage current of the UPS and the protected equipment does not exceed 3.5 mA. If the total leakage current exceeds this value, the INSTALL version is mandatory and the earth wire must be connected to the input terminal block.
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed.
Never operate the UPS if the ambient temperature and relative humidity are higher than the levels
specified in the documentation.
Never burn the battery (risk of explosion).Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).Comply with all applicable regulations for the disposal of the battery.
Product safety
UPSs connected to the AC-power source via a wall outlet must remain in the immediate vicinity of the outlet. The outlet must be easily accessible. For UPSs connected to the AC-power source via a terminal block, a protection circuit breaker must be installed upstream and be easily accessible. The UPS can be disconnected from the AC-power source by removing the power cord or the UPS power cable.
Never install the UPS near liquids or in an excessively damp environment.Never let a liquid or foreign body penetrate inside the UPS.Never block the ventilation grates on the front or back of the UPS.Never expose the UPS to direct sunlight or a source of heat.
Safety
Special precautions
The UPS connection instructions contained in this manual must be followed in the indicated order. Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. If the UPS is positioned flat, check that not more than five modules are stacked on top of each other. If the UPS must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -40° C to +50° C.
If the UPS remains de-energized for a long period, we recommend that you energize the UPS for a period of 24 hours, at least once every month. This charges the battery, thus avoiding possible irreversible damage.
5103321100/AA - Page 3
Foreword
Using this document
Information may be found primarily by consulting:
the contents; the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Page 4 - 5103321100/AA
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Contents
1. Presentation
1.1 Pulsar EXtreme range................................................................................................................. 7
1.2 Connection modules .................................................................................................................. 8
Fault tolerant ................................................................................................................................... 8
Hot swap ......................................................................................................................................... 8
Install ............................................................................................................................................... 8
1.3 Back ............................................................................................................................................. 9
1.4 Control panel ............................................................................................................................... 10
2. Installation
2.1 Unpacking and checks ............................................................................................................... 11
"Tower" model ............................................................................................................................... 11
"Rack" model ................................................................................................................................ 11
2.2 Installation (rack version) .......................................................................................................... 13
2.3 Connection to the RS 232 communications port (optional) ................................................... 14
2.4 Installation of the communications-card option ...................................................................... 14
2.5 Securing and connecting the connection modules ................................................................. 15
Securing the connection modules .................................................................................................15
Fault tolerant ................................................................................................................................. 15
Hot swap ....................................................................................................................................... 16
Install ............................................................................................................................................. 17
3. Operation
3.1 Operating mode .......................................................................................................................... 18
ON-LINE mode ............................................................................................................................. 18
ECO mode .................................................................................................................................... 18
3.2 Start-up ........................................................................................................................................ 19
3.3 Bargraph indications .................................................................................................................. 19
5103321100/AA - Page 5
Contents
3.4 Failure of AC input power and operation on battery power.................................................... 20
Transfer to battery power .............................................................................................................. 20
Threshold for the low-battery shutdown warning .......................................................................... 20
End of backup time ....................................................................................................................... 20
Sleep mode ................................................................................................................................... 20
Return of AC input power .............................................................................................................. 20
3.5 Personalization ........................................................................................................................... 21
Function ........................................................................................................................................ 21
"ON / OFF conditions" tab ............................................................................................................. 21
"Battery" tab .................................................................................................................................. 22
"Output" tab ................................................................................................................................... 22
"By-pass" tab ................................................................................................................................ 22
"ECO mode" tab ............................................................................................................................ 23
3.6 Shutdown ..................................................................................................................................... 23
4. Maintenance
4.1 Troubleshooting .......................................................................................................................... 24
4.2 UPS replacement ........................................................................................................................ 26
Fault-tolerant connection module.................................................................................................. 26
Hot-swap and Install connection modules .................................................................................... 26
Page 6 - 5103321100/AA
5. Environment ..................................................................................................................................... 28
6. Appendices
6.1 Glossary ....................................................................................................................................... 29
6.2 Index ............................................................................................................................................. 31
1.1 Pulsar EXtreme range
Tower model
1. Presentation
Dimensions in mm
(H x W x D)
EXtreme 1500 to 3000
443 x 173 x 465
Weight in kg
Rack model
EXtreme 1500 to 2000
EXtreme 2500 to 3000
EXtreme 1500 to 3000
EXtreme 1500 to 2000
EXtreme 2500 to 3000
29
36
Dimensions in mm
(H x W x D)
177 (4U) x 483 x 462
Weight in kg
31
38
5103321100/AA - Page 7
1. Presentation
1.2 Connection modules
Fault tolerant
socket for connection to AC-power source.
1
outlets for direct connection to protected equipment.
2
manual bypass switch.
3
1
4
input terminal block with cable clamp.
Hot swap
Install
2
3
1
5
2
3
5
output terminal block with cable clamp.
Page 8 - 5103321100/AA
5
4
1.3 Back
1. Presentation
slot for communications-card option.
6
battery module connector.
7
6
battery circuit breaker.
8
10
11
7
8
9
rating plate.
9
connector for connection modules.
10
RS232 communications port.
11
5103321100/AA - Page 9
1. Presentation
1.4 Control panel
Alarms
14
UPS overload
electronics fault
15
16
battery fault
17
ambient temp.
> 40°C
hold down to display
18
percent load.
19
lamp test or buzzer OFF.
operation on manual bypass.
20
operation in ECO mode.
21
operation in ON-LINE mode.
22
operation on battery power.
23
ON/OFF.
24
% battery ␣ ␣ remaining
100%
80%
50%
20%
% load
100%
80%
50%
20%
Page 10 - 5103321100/AA
Loading...