MGE 3000 VA, 2000 VA, 1500 VA, 2500 VA User Manual

Page 1
Pulsar EXtreme
1500/2000 VA 2500/3000 VA
installation and user manual
French
German
Spanish
Netherlands
5103321100/AA - Page 1
Page 2
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar EXtreme a reference in environmental protection include:
the eco-design approach used in product development; production in an ISO 14001 certified factory; recycling of Pulsar EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EXtreme range, we invite you to visit our web site at Erreur! Signet non défini. or contact your MGE UPS SYSTEMS representative.
Page 2 - 5103321100/AA
Page 3
Safety rules
Safety of persons
A UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed. If it is connected to the AC-power source via a wall outlet, measurements are required to ensure that the total leakage current of the UPS and the protected equipment does not exceed 3.5 mA. If the total leakage current exceeds this value, the INSTALL version is mandatory and the earth wire must be connected to the input terminal block.
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed.
Never operate the UPS if the ambient temperature and relative humidity are higher than the levels
specified in the documentation.
Never burn the battery (risk of explosion).Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).Comply with all applicable regulations for the disposal of the battery.
Product safety
UPSs connected to the AC-power source via a wall outlet must remain in the immediate vicinity of the outlet. The outlet must be easily accessible. For UPSs connected to the AC-power source via a terminal block, a protection circuit breaker must be installed upstream and be easily accessible. The UPS can be disconnected from the AC-power source by removing the power cord or the UPS power cable.
Never install the UPS near liquids or in an excessively damp environment.Never let a liquid or foreign body penetrate inside the UPS.Never block the ventilation grates on the front or back of the UPS.Never expose the UPS to direct sunlight or a source of heat.
Safety
Special precautions
The UPS connection instructions contained in this manual must be followed in the indicated order. Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. If the UPS is positioned flat, check that not more than five modules are stacked on top of each other. If the UPS must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -40° C to +50° C.
If the UPS remains de-energized for a long period, we recommend that you energize the UPS for a period of 24 hours, at least once every month. This charges the battery, thus avoiding possible irreversible damage.
5103321100/AA - Page 3
Page 4
Foreword
Using this document
Information may be found primarily by consulting:
the contents; the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Page 4 - 5103321100/AA
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Page 5
Contents
1. Presentation
1.1 Pulsar EXtreme range................................................................................................................. 7
1.2 Connection modules .................................................................................................................. 8
Fault tolerant ................................................................................................................................... 8
Hot swap ......................................................................................................................................... 8
Install ............................................................................................................................................... 8
1.3 Back ............................................................................................................................................. 9
1.4 Control panel ............................................................................................................................... 10
2. Installation
2.1 Unpacking and checks ............................................................................................................... 11
"Tower" model ............................................................................................................................... 11
"Rack" model ................................................................................................................................ 11
2.2 Installation (rack version) .......................................................................................................... 13
2.3 Connection to the RS 232 communications port (optional) ................................................... 14
2.4 Installation of the communications-card option ...................................................................... 14
2.5 Securing and connecting the connection modules ................................................................. 15
Securing the connection modules .................................................................................................15
Fault tolerant ................................................................................................................................. 15
Hot swap ....................................................................................................................................... 16
Install ............................................................................................................................................. 17
3. Operation
3.1 Operating mode .......................................................................................................................... 18
ON-LINE mode ............................................................................................................................. 18
ECO mode .................................................................................................................................... 18
3.2 Start-up ........................................................................................................................................ 19
3.3 Bargraph indications .................................................................................................................. 19
5103321100/AA - Page 5
Page 6
Contents
3.4 Failure of AC input power and operation on battery power.................................................... 20
Transfer to battery power .............................................................................................................. 20
Threshold for the low-battery shutdown warning .......................................................................... 20
End of backup time ....................................................................................................................... 20
Sleep mode ................................................................................................................................... 20
Return of AC input power .............................................................................................................. 20
3.5 Personalization ........................................................................................................................... 21
Function ........................................................................................................................................ 21
"ON / OFF conditions" tab ............................................................................................................. 21
"Battery" tab .................................................................................................................................. 22
"Output" tab ................................................................................................................................... 22
"By-pass" tab ................................................................................................................................ 22
"ECO mode" tab ............................................................................................................................ 23
3.6 Shutdown ..................................................................................................................................... 23
4. Maintenance
4.1 Troubleshooting .......................................................................................................................... 24
4.2 UPS replacement ........................................................................................................................ 26
Fault-tolerant connection module.................................................................................................. 26
Hot-swap and Install connection modules .................................................................................... 26
Page 6 - 5103321100/AA
5. Environment ..................................................................................................................................... 28
6. Appendices
6.1 Glossary ....................................................................................................................................... 29
6.2 Index ............................................................................................................................................. 31
Page 7
1.1 Pulsar EXtreme range
Tower model
1. Presentation
Dimensions in mm
(H x W x D)
EXtreme 1500 to 3000
443 x 173 x 465
Weight in kg
Rack model
EXtreme 1500 to 2000
EXtreme 2500 to 3000
EXtreme 1500 to 3000
EXtreme 1500 to 2000
EXtreme 2500 to 3000
29
36
Dimensions in mm
(H x W x D)
177 (4U) x 483 x 462
Weight in kg
31
38
5103321100/AA - Page 7
Page 8
1. Presentation
1.2 Connection modules
Fault tolerant
socket for connection to AC-power source.
1
outlets for direct connection to protected equipment.
2
manual bypass switch.
3
1
4
input terminal block with cable clamp.
Hot swap
Install
2
3
1
5
2
3
5
output terminal block with cable clamp.
Page 8 - 5103321100/AA
5
4
Page 9
1.3 Back
1. Presentation
slot for communications-card option.
6
battery module connector.
7
6
battery circuit breaker.
8
10
11
7
8
9
rating plate.
9
connector for connection modules.
10
RS232 communications port.
11
5103321100/AA - Page 9
Page 10
1. Presentation
1.4 Control panel
Alarms
14
UPS overload
electronics fault
15
16
battery fault
17
ambient temp.
> 40°C
hold down to display
18
percent load.
19
lamp test or buzzer OFF.
operation on manual bypass.
20
operation in ECO mode.
21
operation in ON-LINE mode.
22
operation on battery power.
23
ON/OFF.
24
% battery ␣ ␣ remaining
100%
80%
50%
20%
% load
100%
80%
50%
20%
Page 10 - 5103321100/AA
Page 11
2.1 Unpacking and checks
Tower model
2. Installation
29
26
25 27 28
25
RS 232 communications cable.
26
"Solution Pac" CD ROM.
27
"UPS Driver" diskette for UPS personalization.
28
documentation.
29
electrical power cord (except INSTALL version).
5103321100/AA - Page 11
Page 12
2. Installation
Rack model
30
29
26
25 27 28
Page 12 - 5103321100/AA
25
RS 232 communications cable.
26
"Solution Pac" CD ROM.
27
"UPS Driver" diskette for UPS personalization.
28
documentation.
29
electrical power cord (except INSTALL version).
30
telescopic rails for mounting in 19" bay with mounting hardware.
Page 13
2.2 Installation (rack version)
Rack mounting diagram with rails.
3
3
2. Installation
1
3
4
3
2
The rails and the necessary mounting hardware are supplied with the UPS in the package.
5103321100/AA - Page 13
Page 14
2. Installation
2.3 Connection to the RS 232 communications port (optional)
1. Connect the RS 232 communications cable to the serial port on the computer.
2. Connect the RS 232 communications cable to the RS 232
11
OV
5 4 3 2 1
9 8 7 6
RD TD
communications port on the UPS.
The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.
Pin-out diagram for the RS 232 communications port on the UPS.
RTS
2.4 Installation of the communications-card option
25
25
11
Page 14 - 5103321100/AA
Slot for the communications-card option.
It is not necessary to shut down the UPS to install the communications card:
1. Remove the slot cover.
2. Insert the card in the slot.
3. Secure the card with the two screws.
Page 15
2.5 Securing and connecting the connection modules
Securing the connection modules
2. Installation
Fault tolerant
Insert the connection module in the connector .
10
31
31
Before carrying out any connections, check that the battery circuit breaker is OFF and that the
1. Secure the connection module to the UPS using the two screws .
31
8
10
electrical power cord to the AC-power source is disconnected.
Connection of equipment:
1. Connect the protected equipment directly to the outlets .
2
2
1
29
Connection to the AC-power source
1. Connect the electrical power cord to the socket
29
1
for connection to AC-power source.
2. Connect the other end of the electrical power cord to an AC-power outlet.
5103321100/AA - Page 15
Page 16
2. Installation
Hot swap
Before carrying out any connections, check that the battery circuit breaker is OFF
8
and that the electrical power cord to the AC-power source is disconnected.
Connection of equipment to outlets
Plug your equipment into the outlets .
2
2
Connection of equipment to a terminal block:
This type of connection must be carried out by qualified
8
electrical personnel.
1. Remove the terminal-block cover .
32
2. Insert the cable supplying the equipment through the cable
32
clamp .
33
3. Connect the three wires to the output terminal block .
33
Always connect the earthing wire first.
4. Remove the terminal-block cover.
5. Tighten the nut on the cable clamp .
33
The overall cable diameter and the cross-sectional area
5
Earthing wire
of the three wires depends on the UPS rating.
EXtreme 1500 to 2000
EXtreme 2500 to 3000
cable diameter (mm)
9 to 12
9 to 12
cross-sectional area of each wire (mm)
5
1 to 4
1,5 to 4
Page 16 - 5103321100/AA
1
29
Connection to the AC-power source:
1. Connect the electrical power cord to the socket
29 1
for connection to AC-power source.
2. Connect the other end of the electrical power cord to an AC-power outlet.
Page 17
Install
2. Installation
This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connections, check that the battery circuit breaker is OFF
8
and that the upstream protection devices (AC distribution system) are open (OFF).
The overall cable diameter and the cross-sectional area
8
32
of the three wires depends on the UPS rating.
cross-sectional area of each wire (mm)
EXtreme 1500 to 2000
EXtreme 2500 to 3000
cable diameter (mm)
9 to 12
9 to 12
Power and equipment connections:
1. Remove the terminal-block cover .
32
2. Insert the cable supplying the equipment and the power cable through the cable clamps .
33
3. Connect the three wires of the equipment cable to the output terminal block .
5
Always connect the earthing wire first.
4. Connect the three wires of the power cable to the input terminal block .
4
5. Refit the terminal_block cover.
33
6. Tighten the nut on the cable clamp .
33
1 to 4
1,5 to 4
Earthing wires
5
4
5103321100/AA - Page 17
Page 18
3. Operation
3.1 Operating mode
ON-LINE mode
ECO mode
The main advantage of this mode is that it reduces the consumption of electrical power. The protected equipment is supplied directly by the AC-power source as long as it remains within the tolerances set by the user.
ECO mode is selected and tolerance levels are set using the "UPS Driver" software for UPS personalization (see section 3.5).
This is the standard operating mode, set by default in the factory. It makes use of electronic double conversion of the input power.
Two possible cases:
22
22
LED is ON: AC input power is available. Power is drawn from the distribution system and supplied to the protected equipment via the UPS.
23
LED is ON: AC input power is not available. Power is drawn from the battery and supplied to the protected equipment.
23
27
Page 18 - 5103321100/AA
Three possible cases:
21
The AC-power source is within the set tolerances. The protected equipment is supplied directly by the AC-power source, via the automatic bypass. LED is ON.
21
The AC-power source is not within the set tolerances. The UPS automatically shifts to ON-LINE mode. LED is ON.
22
The AC-power source is not available. LED is ON.
22
23
The battery supplies power to the protected equipment.
23
Page 19
3.2 Start-up
3. Operation
The protected equipment connected to the UPS can be energized, whether AC input power is available or not.
Prior to initial start-up, check the UPS voltage settings. If the protected equipment voltage is other than 230 V / 50 Hz, the UPS settings must be modified using the "UPS Driver" software (see section 3.5).
27
If LEDs , and do not go ON or if LEDs , , or flash, there is a fault (see section 4.1).
21 22 23
3.3 Bargraph indications
14 17
LEDs to provide three different indications.
1. Set the battery circuit breaker(s) to ON.
8
2. Press the ON / OFF button .
8
24
All connected equipment is energized. The buzzer sounds.
21 22
LEDs , and go ON.
24
14 15
16
23
17
1. Remaining backup time in percent.
14
15
16
17
18
2. Percent load drawn by the protected equipment, when button is pressed.
18
3. Operating faults (flashing LED and beeps):
14
Overload.
15
UPS fault.
16
Battery fault.
17
Excessive ambient temperature.
5103321100/AA - Page 19
Page 20
3. Operation
3.4 Failure of AC input power and operation on battery power
AC input power is not available, the battery steps in to supply the protected equipment.
Transfer to battery power
The AC-power source is outside tolerances, LED is ON, the buzzer beeps three times.
23
Threshold for the low-battery shutdown warning
The low-battery shutdown warning threshold can be set by the user, with the "UPS Driver" software (see section 3.5).
23
LED flashes. The buzzer beeps every three seconds.
23
End of backup time
The buzzer sounds continuously.
19
Press button to turn the buzzer OFF.
23
There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is imminent.
19
The equipment is no longer supplied with power.
Sleep mode
This operating mode may be personalized using the "UPS Driver" software (see section 3.5). It saves battery power when no equipment is connected to the UPS. The UPS automatically restarts when the AC-power source returns to within tolerances.
Return of AC input power
If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.5).
Page 20 - 5103321100/AA
Page 21
3.5 Personalization
Function
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
3. Operation
Check that the RS 232 cable is correctly connected and that the battery circuit breaker is closed.
"UPS Driver" installation:
1. Insert the "UPS Driver" diskette in the drive of an IBM-compatible microcomputer.
2. Select the disk drive (A :\).
3. Double-click "upsdriv.exe".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters.
"ON / OFF conditions" tab
Personalizable function
Automatic start
Cold start (battery power)
Forced shutdown
Sleep mode
UPS ON / OFF via software
25
8
Default setting
Enabled
Enabled
Enabled
Disabled
Enabled
5103321100/AA - Page 21
Page 22
3. Operation
"Battery" tab
"Low-battery shutdown warning" threshold
"Output" tab
Rated AC-power source voltage (see figure 1)
Tolerance for AC-power source frequency (fig. 2)
"By-pass" tab
Personalizable function
"Battery test" intervals
Charger
Rated AC-power source frequency
Frequency-regulation rate
Seuil d'alarme surcharge utilisation
Redémarrage onduleur après court-circuit
Default setting
Every day
20% remaining battery
backup time
Standard
230 V
50 Hz
± 5%
Standard
100%
Disabled
Options
Once a week
Once a month
No test
40% remaining battery
backup time
CLA (2, 4 or 8 hours)
200 V-208 V-220 V-240 V
60 Hz
± 1% to ± 10% , in 1% steps
Redundancy (see section 6.1)
0 to 100%, in 10% steps
Enabled (click to add check)
Page 22 - 5103321100/AA
Authorized voltage range for transfer to bypass
(see figure 3) if fault or overload
Authorized frequency range for transfer to bypass
187 V to 265 V (for
230 V rated voltage)
± 10%
187 V to 265 V,
in 1V steps
± 1% to ± 10%, in 1% steps
(see figure 2) if fault or overload
Transfer to bypass if overload
Transfer to bypass following a fault, whatever
Enabled
Disabled
Disabled (click to remove check)
Enabled (click to add check)
the conditions on the AC-power source
The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).
Available power as a percentage of the rated power
Fig. 1 Fig. 2
Voltage in V
Authorized frequency range for transfer to bypass
Tolerance for AC-power source frequency
Mini Maxi
Page 23
"ECO mode" tab
ECO mode is not possible unless it has first been authorized using the "UPS Driver" software
3. Operation
Authorized voltage range for operation in ECO mode (see figure 3)
Range for minimum authorized voltage for operation in ECO mode
Minimum authorized voltage for transfer to the bypas
Fig. 3
3.6 Shutdown
Personalizable function
ECO mode authorization
Rated
voltage
Default setting
Disabled
(not authorized)
The upper threshold (max. voltage) is between the maximum authorized voltage for transfer to
200 V to 240 V
(for 230 V rated
voltage)
The lower threshold (min. voltage) is between
the minimum authorized voltage for transfer to
Range for maximum authorized voltage for operation in ECO mode
Maximum authorized voltage for transfer to the bypass
Options
Enabled (click to check)
the bypass and the rated voltage.
the bypass and the rated voltage.
Voltage in V
1. Press button (return to the OFF position).
24
The connected equipment is no longer supplied with power.
24
2. Set the battery circuit breaker(s) to OFF.
8
The battery is no longer recharged.
8
5103321100/AA - Page 23
Page 24
4. Maintenance
4.1 Troubleshooting
If any of LEDs , , or flash, there is a operating anomaly or an alarm.
If a LED flashes, the bargraph data is no longer displayed.
Troubleshooting not requiring MGE after-sales support
LED flashes and the buzzer
14
beeps.
17
LED flashes.
14 15
Indication
16 17
Signification
UPS overload. Overload is too long or too high. The UPS cuts the supply of power to the connected equipment and the buzzer sounds continuously.
The ambient temperature is higher than
40° C.
The UPS is not designed to operate more than eight hours under these conditions.
Check the power drawn by the equipment and disconnect any non-priority devices.
Install the UPS in a room where the ambient temperature is not
greater than 40° C.
Remède
Page 24 - 5103321100/AA
Page 25
Troubleshooting requiring MGE after-sales support
4. Maintenance
Indication
LED flashes and the buzzer
15
beeps.
16
LED flashes.
Signification
UPS electronics have detected a UPS fault. Depending on the UPS personalization parameters (see section 3.5), there are two possibilities:
the equipment connected to the UPS
continues to be supplied, but directly from the AC-power source (via the automatic bypass (LED ON);
the connected equipment is no longer
21
supplied.
The equipment connected to the UPS is no longer protected.
A battery fault was detected during the battery test.
Correction
For UPSs equipped with Hot swap or Install connection modules, follow the UPS replacement procedure (see section 4.2).
Call the after-sales support department.
Make sure that the battery circuit breaker(s) is closed.If that is the case, call the after-sales support department because the battery is not OK
5103321100/AA - Page 25
Page 26
4. Maintenance
4.2 UPS replacement
Fault-tolerant connection module
Before carrying out this operation, the supply of power to the connected equipment must be cut.
Disconnection:
1. Shut down the UPS by pressing button (return to the OFF
24
position).
2. Open the battery circuit breaker(s) .
24
3. Remove the two fixing screws and the connection module
8
31
from the UPS.
Reconnection:
1. Insert the connection module in the connector and secure
8
2. Close the battery circuit breaker(s) .
using the two screws .
31
8
10
Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).
Page 26 - 5103321100/AA
10
31
31
3. Start the UPS by pressing button .
The connected equipment is again protected by the UPS.
24
Page 27
Hot-swap and Install connection modules
4. Maintenance
Before turning the switch,
see the manual
NORMAL
Before turning the switch,
see the manual
NORMAL
BY-PASS
BY-PASS
Disconnection:
1. Turn the manual bypass switch from the NORMAL
3
to the intermediate position.
2. Check that LED is ON before continuing to the BYPASS
21
position.
If LED is not ON, do not switch to the BYPASS
21
position and call the after-sales support department.
21
3. Turn the manual bypass switch from the intermediate
3
position to the BYPASS position. The connected equipment is supplied by the AC-power source, via the manual bypass.
4. Shut down the UPS by pressing button (return to the OFF
24
position).
5. Open the battery circuit breaker(s) .
6. Remove the two fixing screws and the connection module
8
31
from the electronic module.
The UPS can be replaced. The connected equipment is supplied by the AC-power source.
Reconnection:
1. Insert the connection module in the connector and secure using the two screws .
3. Close the battery circuit breaker(s) .
24
Check that UPS personalization settings still
31
8
10
correspond to the equipment to be supplied (see section 3.5).
4. Start the UPS by pressing button .
8
5. Check that LED is ON before turning the manual bypass switch to the intermediate position.
3
If LED is not ON, do not switch to the
20
20
24
intermediate position and call the after-sales support department.
10
6. Turn the manual bypass switch from the BYPASS position
3
to the intermediate position.
31
7. Turn the manual bypass switch from the intermediate
3
position to the NORMAL position.
The connected equipment is again protected by the UPS.
31
5103321100/AA - Page 27
Page 28
5. Environment
This product has been designed to respect the environment:
It does not contain CFCs or HCFCs. It was manufactured in a factory certified ISO 14001.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
Warning:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not correctly recycled by specialized companies.
Page 28 - 5103321100/AA
Web site : www.mgeups.com
Page 29
6.1 Glossary
Authorized voltage The range of voltage supplied by the AC-power source within which the UPS range for operation in ECO can operate in ECO mode. In ECO mode, the equipment connected to the in ECO mode UPS is supplied directly by the AC-power source, via the automatic bypass.
Authorized voltage Upper and lower voltage thresholds within which the UPS can operate range for transfer to on theautomatic bypass in the event of a UPS fault or overload. bypass if fault or overload
Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment
Automatic start following When AC input power returns following shutdown at the end of the battery return of AC input power backup time, UPS automatic start can be enabled or disabled.
Backup time Time that the connected equipment can operate on battery power.
Bargraph Device on the front panel indicating the percent remaining backup time
Battery test Internal UPS test on battery status.
CLA (Long backup- Module incorporating a charger for long backup times. The charger is powerful time charger) enough to charge battery extension modules offering very long backup times.
Cold start See "Start on battery power".
Connection module Unit grouping the receptacles for connection to the AC-power source
Dialog box A window in a computer program displayed for selection by the user of various
Double conversion The power supplied to the connected equipment is completely regenerated
ECO mode Operating mode by which the equipment is supplied directly by the AC-power
Equipment Devices or systems connected to the UPS output.
Fault tolerant Connection module (without manual bypass) offering receptacles
Forced shutdown Ten-second interruption in the supply of power to the connected equipment
6. Appendices
directly to the AC-power source.
or the percent load.
and the equipment.
options and parameter settings.
by continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power.
source if it is within the tolerances defined by the user. This mode reduces the consumption of electrical power.
for connection to the AC-power source and the equipment.
following a system shutdown, even if AC input power returns during the interruption period.
5103321100/AA - Page 29
Page 30
6. Appendices
Frequency-regulation rate The rate at which the UPS frequency is synchronized with that
Hot swap Connection module (with manual bypass) offering a socket for connection
Install Connection module (with manual bypass) offering terminal blocks
Manual bypass Rotary switch controlled by the user, used to connect the equipment directly
ON-LINE mode The normal UPS operating mode, by which the AC-power source supplies
Percent load Ratio between the power drawn by the connected equipment and the total
Personalization A number of UPS functions can be modified using the "UPS Driver" software
Redundancy See "Frequency-regulation rate".
Sleep mode This function shuts down the UPS when it operates on battery power
Start on battery power This function makes it possible to energize the connected equipment even
Tolerance for AC-power The range of frequency supplied by the AC-power source within which source frequency the UPS can operate in ON-LINE mode (double conversion).
UPS Uninterruptible Power Supply.
UPS ON / OFF It is possible to enable or disable use of UPS ON / OFF controls via software by the computer-system protection software.
of the AC-power source. Two possible cases:
1. The installation comprises a single UPS. The frequency-regulation rate is set to "Standard".
2. The installation comprises two UPSs connected in series. The AC-power source supplies power to the first UPS which in turn supplies the second UPS. The connected equipment is supplied by the second UPS. The frequency regulation rate of the first UPS must be set to "Standard", the frequency regulation rate of the second UPS must be set to "Redundancy".
to the AC-power source and outlets or a terminal block for connection to the equipment.
for connection to the AC-power source and the equipment.
to the AC-power source. Transfer of the load to the manual bypass enables UPS maintenance or replacement, without interrupting the supply of power to the connected equipment.
the UPS, which in turn, following double conversion of the AC power, supplies the connected equipment.
power that the UPS can supply.
to better meet the user's needs.
and no load is detected on the UPS output.
when AC input power is not available (operation exclusively on battery power).
Page 30 - 5103321100/AA
Page 31
6.2 Index
6. Appendices
A
AC power
Failure ........................................................... 20
Frequency tolerance ..................................... 22
Rated frequency ............................................22
Rated voltage ................................................ 22
Return ............................................................ 20
B
Bargraph .............................................................. 19
Battery
Battery test .................................................... 22
End of backup time ....................................... 20
Fault ......................................................... 10-19
Low-battery shutdown warning ..................... 20
Recycling ....................................................... 28
Transfer to battery power .............................. 20
Buzzer ......................................................... 4-10-20
By-pass
Automatic bypass .....................................18-25
Manual bypass ......................................... 10-26
C
Communication .................................................... 14
Connection
Communications card ................................... 14
Connection modules ................................ 16-17
RS 232 communications port ........................ 14
E
ECO mode ................................................ 10-18-23
F
Fault (UPS)
Load .............................................................. 10
Transfer to automatic bypass ........................ 25
Fault tolerant ............................................... 8-15-26
L
LEDs
Lamp test....................................................... 10
M
Mode
ECO mode.......................................... 10-18-23
O
Overload .................................................... 10-22-24
P
Personalization ................................................... 21
Battery .......................................................... 22
ECO mode.................................................... 23
ON / OFF conditions..................................... 21
Output........................................................... 22
R
Rack ..................................................................7-13
S
Safety .................................................................... 3
Shutdown
Forced shutdown ........................................... 21
UPS ON / OFF via software .......................... 21
UPS shutdown ......................................... 10-23
Sleep mode ................................................... 20-21
Software
UPS Driver .......................................... 11-12-21
Start-up
Automatic start .............................................. 21
T
Temperature
Excessive ambient temp .................... 10-19-24
H
Hot swap ..................................................... 8-16-27
I
Install ........................................................... 8-17-27
U
UPS Driver ................................................ 11-12-21
5103321100/AA - Page 31
Page 32
MGE UPS SYSTEMS
140, Avenue Jean Kuntzmann ZIRST - Montbonnot St Martin 38334 - ST ISMIER CEDEX - FRANCE www.mgeups.com
5103321100/AB
Page 32 - 5103321100/AA
Nothing will stop you now
Publication : MGE UPS SYSTEMS, 09/99.
Loading...