Mettler Toledo GPro 500 Quick Setup Manual

GPro™ 500 Quick Setup Guide

English 3 German 29 French 55 Portuguese 81 中国的 107 한국의 133
Quick Setup Guide TDL GPro™ 500
GPro™ 500 Quick Setup Guide

Content

Packing content 5 Site Requirements 5 Ambient operating conditions 5 What you also need 5 Optional accesssories 6
Flange placement 7 Flange requirements 7 Flow conditions at measuring point 8 Purging 9
Purging with thermalbarrier 10 Grounding and wiring (ATEX) 11 Active analog inputs (ATEX Version) 12 Loop powered analog inputs (ATEX) 13 Grounding and wiring (FM) 14 Active analog inputs (FM Version) 15 Loop powered analog inputs (FM Version) 16 GPro™ 500 cables 17 Cable connections in M400 19

English

General Setup (applies for all parameters) 20 Channel Selection 20 Calibration 20 TDL Installation 20 Setting the correct process side purging 23
One-point calibration for TDL gas sensors 24 Process calibration for TDL gas sensors 24 Calibration using a calibration cell 25
3
Quick Setup Guide TDL GPro™ 500
4
Quick Setup Guide TDL GPro™ 500
1 Preparation
– GPro™ 500 Tunable Diode Laser Analyzer
Packing content
– 1 Safety Instruction – 1 Documentation CD with Instruction manual and MT-TDL Software Suite.
Site Requirements
– 24 VDC, 5 W for power supply of the GPro™ 500
– 110 / 220 VAC for the power supply of M400 – Purge gas, > 99.7% purity (minimum recommended), 0.5…5 L /min.
The purity requirements are:
conform to standard set by ISO 8573.1, class 2–3, analog to instrument air. For oxygen TDL, nitrogen or any other ”O used.
Ambient operating
– 20…+ 55 °C (– 4…+ 131 °F) during operation
conditions
What you also need
• 1 M400 T3 Transmitter (p / n 52121350)
• 1 Ethernet cable CAT5
• RS 485 cable (< 250 m)
• 1 Laptop (WinXP / 7 / 8) with MT-TDL software installed
• Flat gasket 82.14 3 3.53 mm
• Check valve
• 2 pcs open-end wrenches (spanners) for M16 bolts
• 1 pcs Allen key 5 mm for the locking screws on anges and Tx lid screws
• 1 pcs Allen key 3 mm for the RS 232 cover screws
• 2 Flat keys for Swagelok
• 1 pcs at screwdriver 2.5 mm for electrical connections
• 1 pcs at (6 mm) or cross head (No 2) screwdriver for Rx lid screws
• Adjustable wrench (spanner) for purge connections
• Torque wrench for FM version
free” clean and dry gas can be
2
5
Quick Setup Guide TDL GPro™ 500
Optional accesssories
Accessory Order number
Thermal barrier 30 034 138 Junction box 30 034 149
Purging box for M400 Ex d 30 034 148
Calibration kit 30 034 139
O
2
Kit Flat gasket ST 30 080 914 Kit Flat gasket HT (Graphite) 30 080 915 Cable GPro 500 ATEX, FM 5 m 30 077 735 Cable GPro 500 ATEX, FM 15 m 30 077 736 Cable GPro 500 ATEX, FM 25 m 30 077 737
6
Quick Setup Guide TDL GPro™ 500
2 Before the installation
Flange placement
)
"
60 cm (23.6
The TDL head should be easily accessible. A person should be able to stand in front of it and adjust the M16 xing bolts using two standard spanners. There should be at least 60 cm free space measured from the ange xed to the stack and outwards as shown below.
60 cm (23.6")
Flange requirements
min. clearance: 61,5 mm
(schedule 40)
DIN 50 or ANSI 2"
min. clearance: 77,5 mm
(schedule 80)
100 mm
(4")
DIN 65 or ANSI 2½"
7
Quick Setup Guide TDL GPro™ 500
DIN
DN50/PN25 DN65/PN25
DN 50
100 mm 100 mm
DN100
min. Ø 54 mm
min. Ø 67 mm
DN65
ANSI
4"
min. 2.12"
2"
min. 2.64"
ANSI 2.5"/300 lbsANSI 2"/300 lbs
2.5"
4" 4"
When deciding the placement of the GPro™ 500 TDL in the process, we recom-
Flow conditions at measuring point
8
Quick Setup Guide TDL GPro™ 500
Purging
1 Purge gas inlet for instrument side (6 mm or ¼" tube tting). 2 Purge gas inlet for process side (must have a check valve). 3 Purge gas outlet for instrument side (6 mm or ¼" tube tting). 4 Process gas ow. 5 Region that denes the boundaries of the effective path length.
0…1 L /min
0…10 L /min
RotameterPressure regulator
WARNING
Always start purging at maximum flow before starting the process.
WARNING
Purging must always be switched on in order
to avoid dust deposition onto the optical surfaces.
WARNING
Do not remove and / or disassemble the purge gas inlet for processes (2).
If disassembled, the PED pressure certificate is void.
WARNING
Do not connect instrument and process side purging in series, otherwise
when disassembling the sensor heat the probe purging will stop.
9
Quick Setup Guide TDL GPro™ 500
Purging
with
thermalbarrier
Purging configuration
1 Purge gas inlet for thermal barrier (6 mm or ¼" tube tting) 2 Purge gas outlet for thermal barrier (6 mm or ¼" tube tting) 3 Purge gas inlet for process side (Must have a check valve) 4 Mandatory check valve (to be supplied by the user)
21 4
3
WARNING
The purge gas for the thermal barrier must always be turned on
when the process is running in order to protect the sensor head
from permanent damage.
10
WARNING
The failure of the instrument side and thermal barrier purging
system must trigger an alarm. This alarm has to be implemented
in th DCS ny the user.
Quick Setup Guide TDL GPro™ 500
Grounding
andwiring(ATEX)
External earth point for > 4 mm (M6 × 12)
2
cables
Exernal earth point.
11
Quick Setup Guide TDL GPro™ 500
RS-485 A
Activeanaloginputs(ATEXVersion)
ACTIVE ANALOG INPUTS
24 VDC
User-provided
GND
Red
Blue
Junction Box
GND
24 VDC
Green
Yellow
Brown
+
Purple
+
xT
100 mm
+
xT
Power L N
M400
24 VDC
Analog
Outputs
GND
Ethernet
1
24 VDC GND
2 3
RS-485 A RS-485 B
4 5
RS-485 GND
6
+Ain 1 4…20 mA
7
–Ain 1 4…20 mA
8
+Ain 2 4…20 mA
9
–Ain 2 4…20 mA
10
24 VDC
11
Aout 1 Aout 2
12 13
TX+
14
TX–
15
RX+
16
RX–
Black
Pink
Grey
Red/Blue
Grey/Pink
White
White/Yellow
Yellow/Brown
White/Green
Brown/Green
987654321
+
16151413121110
TB4
987654321
Pressure
(4")
Temperature
24 VDC Power 0.2 A (5W)
M400 TB4
Temperature sensor
Pressure sensor
2x 4…20 mA passive analog outputs
Ethernet
6 7 8
RS-485 GND RS-485 B RS-485 A
12
RS-485
GND
20 – 30 VDC or 100 – 230 VAC +/– 10%
Quick Setup Guide TDL GPro™ 500
Looppoweredanaloginputs(ATEX)
User-provided
Red
Blue
Junction Box
GND
24 VDC
Green
Yellow
Brown
Purple
Black
SENSOR IN
xT
GND
24 VDC
100 mm
(4")
Pressure
Temperature
SENSOR IN
xT
Pink
Grey
Red/Blue
Grey/Pink
White
White/Yellow
Yellow/Brown
White/Green
Brown/Green
GND
987654321
TB4
16151413121110
M400
Power L N
987654321
24 VDC
Analog
Outputs
Ethernet
1 2 3 4 5 6 7
8
9 10 11 12 13 14 15 16
24 VDC GND RS-485 A RS-485 B RS-485 GND Sensor In GND Sensor In GND 24 VDC Aout 1 Aout 2 TX+ TX– RX+ RX–
24 VDC Power 0.2 A (5W)
M400 TB4
Temperature sensor
Pressure sensor
2x 4…20 mA passive analog outputs
Ethernet
6 7 8
RS-485 GND RS-485 B RS-485 A
RS-485
GND
20 – 30 VDC or 100 – 230 VAC +/– 10%
WARNING
All openings have to be closed with certified cable glands
or blocking plugs of the same degree of certification as the GPro™ 500.
WARNING
It is essential that you observe all provided information
and warnings. The system must be closed and grounded
before switching on the system.
13
Quick Setup Guide TDL GPro™ 500
Groundingandwiring(FM)
External earth point for > 4 mm (M6 ×12)
2
cables
Exernal earth point.
Protective grounding Material: chromated AISi7Mg0.3 Size: M6 × 12 mm
Protective grounding.
14
2 options for inner protective grounding Material: 1.4404 (AISI 316L) Size: M4 × 6 mm Hex cap screw Connect with 4 mm2 cable
Quick Setup Guide TDL GPro™ 500
RS-485 A
Activeanaloginputs(FMVersion)
ACTIVE ANALOG INPUTS
24 VDC
User-provided
GND
Red
Blue
Junction Box
GND
24 VDC
Green
Yellow
Brown
+
Purple
+
xT
100 mm
+
xT
Power L N
M400
24 VDC
Analog
Outputs
GND
Ethernet
1
24 VDC GND
2 3
RS-485 A RS-485 B
4 5
RS-485 GND
6
+Ain 1 4…20 mA
7
–Ain 1 4…20 mA
8
+Ain 2 4…20 mA
9
–Ain 2 4…20 mA
10
24 VDC
11
Aout 1 Aout 2
12 13
TX+
14
TX–
15
RX+
16
RX–
Black
Pink
Grey
Red/Blue
Grey/Pink
White
White/Yellow
Yellow/Brown
White/Green
Brown/Green
987654321
+
16151413121110
TB4
987654321
Pressure
(4")
Temperature
24 VDC Power 0.2 A (5W)
M400 TB4
Temperature sensor
Pressure sensor
2x 4…20 mA passive analog outputs
Ethernet
6 7 8
RS-485 GND RS-485 B RS-485 A
RS-485
GND
20 – 30 VDC or 100 – 230 VAC +/– 10%
15
Quick Setup Guide TDL GPro™ 500
Looppoweredanaloginputs(FMVersion)
User-provided
Red
Blue
Junction Box
GND
24 VDC
Green
Yellow
Brown
Purple
Black
SENSOR IN
xT
GND
24 VDC
100 mm
(4")
Pressure
Temperature
SENSOR IN
xT
Pink
Grey
Red/Blue
Grey/Pink
White
White/Yellow
Yellow/Brown
White/Green
Brown/Green
GND
987654321
TB4
16151413121110
M400
Power L N
987654321
24 VDC
Analog
Outputs
Ethernet
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16
24 VDC GND RS-485 A RS-485 B RS-485 GND Sensor In GND Sensor In GND 24 VDC Aout 1 Aout 2 TX+ TX– RX+ RX–
24 VDC Power 0.2 A (5W)
M400 TB4
Temperature sensor
Pressure sensor
2x 4…20 mA passive analog outputs
Ethernet
6 7 8
RS-485 GND RS-485 B RS-485 A
16
RS-485
GND
20 – 30 VDC or 100 – 230 VAC +/– 10%
Quick Setup Guide TDL GPro™ 500
GPro™ 500 cables
Signal Description Cable no. Color TB1 TB2
Junction Box Pin no Pin no
Power + 24 V GND (Power) 2 Blue 2
Power 24 V, 5 W
RS 485 A RS 485 B 4 Yellow 4
Interface M400 (RS 485)
1 Red 1
3 Green 3
RS 485 GND 5 Brown 5
4...20 mA pos
4...20 mA neg 7 Black 7
4...20 mA pos
4...20 mA neg 9 Grey 9 + 24 V Out 1 11 Out 2 12 White 12
Current input temperature
Current input pressure
Direct anolog output
(2 3 4 … 20 mA) (optional)
TX+ TX– 14 RX+ 15
Ethernet interface for communication
with PC
RX– 16
6 Purple 6
8 Pink 8
10
Red / Blue 10 Grey / Pink 11
13
White / Yellow 1 Yellow / Brown 2 White / Green 3 Brown / Green 4
17
Quick Setup Guide TDL GPro™ 500
TB1
Pin 1
Pin 4
Connections on motherboard in the sensor head.
Note:ThesensorheadcoverofATEXversionshouldneverbeen
opened,asthiswillinvalidatetheATEXcertification.
TB2
Pin 1
Pin 12
Connections on IO board in the sensor head.
WARNING
All openings have to be closed with certified cable glands
or blocking plugs of the same degree of certification as the GPro™ 500.
WARNING
It is essential that you observe all provided information
and warnings. The system must be closed and grounded
before switching on the system.
18
Quick Setup Guide TDL GPro™ 500
Cable connections
inM400
USB
3
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
TB1
141 2 3 4 5 6 7 8 9 10111213
TB2 TB3 TB4
1 Connection terminal for the power cable 2 TB4 – connection terminal for the GPro™ 500 3 TB1 – connection terminal for the relays.
These can be congured with the M400.
- + N L
POWER
1
2
19
Quick Setup Guide TDL GPro™ 500
3 Installation
GeneralSetup(appliesforallparameters)
(PATH: Menu / Quick Setup)
While in Measurement mode press the [MENU] key to bring up the Menu selec-
20.9 %V O
25.0 °C
MENU Quick Setup
Please select the type of Sensor:
A
A
Channel Select=ISM Parameter=Auto
6.0 pH
25.0 °C
2
tion. Select QUICK SETUP and press the [ENTER] key.
Display Convention:
u
1st line on display → a 3rd line on display 2nd line on display → b 4th line on display
c d
Channel Selection
Analog: For conventional analog sensors (will be displayed on channel A”). ISM: For ISM sensors (will be displayed on channel ”B”).
u
Please select the parameter requirement:
The choice of parameter depends on the level of transmitter. If an ISM sensor is selected, the setting Auto” means, all possible ISM sensors will be recognized and accepted. If a special parameter is chosen, only this parameter will be recognized and accepted on the transmitter.
Calibration
The GPro 500 is calibrated at the factory and does not require calibration at installation & Startup.
TDLInstallation
(path: Quick Setup / TDL / Installation)
While in measurement mode press the key [MENU] . Press the m or . key to
B
20.9 %V O
B
20.9 %Trm
MENU Quick Setup
In this mode, the current live value of the % transmission is displayed during
B
20.9 %V O
B
20.9 %Trm
Transmission Signal 021 %
2
select the TDL and then the Installation menu item.
u
2
5 minutes until it automatically returns to the Measurement mode. Use this
value to rotate the blue sensor head attached with a loose clamp connection on
u
to the probe until the maximum transmission is found. In this position, and secure the blue sensor head into position and tighten the clamp.
20
Quick Setup Guide TDL GPro™ 500
TDLCommissioning(path: Quick Setup / TDL / Commissioning)
B
20.9 %V O
B
20.9 %Trm
–TDL
O
2
Commissioning
2
While in measurement mode press the key [MENU] . Press the m or . key to select the TDL and then the Commissioning menu item.
u
First, select the type of pressure compensation selected: – External: current external pressure value coming from a pressure transducer
of 4.. 20 mA analog output
– Fixed: pressure compensation uses a xed value to be set manually.
Note: if this pressure compensation mode is selected, a consider­able gas concentration measurement error resulting from a non­realistic pressure value can take place.
If External compensation is selected, then the minimum (4 mA) and maximum
B
20.9 %V O
B
20.9 %Trm
Pressure=External
2
(20 mA) analog output signals from the pressure transducer must be mapped to the corresponding Analog input of the TDL. Key in the minimum and maxi-
u
mum values of the pressure in the following units:
– hPa – mmHg – mbar – psi – kPa
In general, METTLER TOLEDO recommends the use of absolute pressure trans-
B
20.9 %V O
B
20.9 %Trm
Ain 4 mA = 940.0 mbar Ain 20 mA = 2000. mbar
2
ducers for more accurate signal compensation over a broad pressure range. If, however, small pressure variations around atmospheric pressure are to be
u
expected, relative pressure sensors will produce better results; but the variations of the underlying barometric pressure will be ignored.
For relative pressure sensors, the minimum and maximum values must be mapped so that the TDL can interpret the analog pressure signal as “absolute”, i.e. a xed barometric pressure of 1013 mbar (for example) has to be added to the mapped values.
If Fixed compensation is selected, the xed pressure value with which the mea-
B
20.9 %V O
B
20.9 %Trm
Pressure=fixed
B
20.9 %V O
B
20.9 %Trm
Pressure=1013. mbar
If External compensation is selected, then the minimum (4 mA) and maximum
B
20.9 %V O
B
20.9 %Trm
Temperature=External
2
surement signal will be calculated has to be keyed in manually. For the xed pressure, the following units can be used:
u
– hPa – mmHg – mbar – psi – kPa
2
u
2
(20 mA) analog output signals from the temperature transducer must be mapped to the corresponding Analog input of the TDL. Key in the minimum and
u
maximum values of the temperature in °C.
21
Quick Setup Guide TDL GPro™ 500
B
20.9 %V O
B
20.9 %Trm
Ain 4 mA = 0.000 °C Ain 20 mA = 250_0 °C
If Fixed compensation is selected, the xed temperature value with which the
B
20.9 %V O
B
20.9 %Trm
Temperature=Fixed
B
20.9 %V O
B
20.9 %Trm
Temperature=320.0 °C
Last, select the initial optical path length corresponding to the probe length in-
B
20.9 %V O
B
20.9 %Trm
Pathlength=00200 mm
2
u
2
measurement signal will be calculated has to be keyed in manually. For the xed temperature, only °C can be used.
u
2
u
2
stalled:
– 290 mm probe: 200 mm
u
– 390 mm probe: 400 mm
– 590 mm probe: 800 mm
This initial value is valid when instrument purging on the instrument and on the
process side is running. Depending on the process conditions and after the optimum of the process purging ow has been found (see next chapter), this value may have to be slightly adapted.
22
Quick Setup Guide TDL GPro™ 500
Setting the correct
The ow rate of the purging will affect the effective path length and conse-
process side purging
quently the measurement value.
Therefore the following procedure should be used. Start with a very high ow rate and gradually decrease it. The measurement value will then start at a low value and increase with decreasing purge ow. At some point it will level out and stay constant for a while and then again start increasing. Choose a purge ow in the middle of the constant region.
2
1
Inecreased reading
Decreasing purge flow
Optimizing the purge ow
1 Concentration reading with high purge ow. The path length is now shorter
than the effective path length since the purge tubes is completely lled with purging gas and some of the purging gas is owing into the measurement path.
2 Concentration reading with optimized purge ow. The path length is now
equal to the effective path length since the purge tubes are completely lled with purge gas. See the illustration below.
3 Concentration reading with no purge ow. The path length is now equal to
the nominal path length since the probe is completely lled with process gas.
4 The optimized purge ow.
3
4
WARNING
Always start purging at maximum flow before starting the process.
WARNING
Purging must always be switched on in order
to avoid dust deposition onto the optical surfaces.
23
Quick Setup Guide TDL GPro™ 500
4 VericationandMaintenance
One-pointcalibrationforTDLgassensors
Enter calibration mode as described in section 7.1 “Enter Calibration Mode”.
B
20.9 %V O
B
25.0 °C
Calibrate Sensor Channel B TDL
Select 1 point as calibration type.
B
20.9 %V O
H
25.0 °C
TDL Calibration Type = 1 Point
Enter values for the effective temperature and pressure values of the gas used
B
20.9 %V O
25.0 °C
Pressure = 1013 hPa Temperature = 23.00 °C
Place the sensor in the calibration gas (e.g. air). Press [ENTER].
B
20.9 %V O
25.0 °C
Press ENTER when Sensor is in Gas
2
u
dened gas concentration.
2
Press [ENTER].
u
2
u
Adjust the optical path length for your individual system.
2
u
ProcesscalibrationforTDLgassensors
Enter calibration mode as described in section 7.1 “Enter Calibration Mode”.
B
12.1 %V O
B
25.0 °C
Calibrate Sensor Channel B Oxygen
Select Process as the calibration type.
B
12.1 %V O
25.0 °C
TDL Calibration Type = Process
Take a sample and press the [ENTER] key again to store the current measuring
B
12.1 %V O
B
25.0 °C
Press ENTER to Capture
=0.0000 V% O2 u
B O
2
2
A process calibration of gas sensors is always a slope calibration.
u
2
Press [ENTER]
u
2
value. To show the ongoing calibration process, A or B (depending on the chan­nel) is blinking in the display.
After determining the concentration value of the sample press the
c
key again
to proceed with the calibration.
24
Quick Setup Guide TDL GPro™ 500
150 mm (5.91")
Enter the concentration value of the sample then press the [ENTER] key to start
B
12.1 %V O
B
25.0 °C
B Point1 = 56.90 %sat
= 57.1 %air u
B O
2
After the calibration the slope ”S” is displayed.
B
12.1 %V O
B
25.0 °C
S=– 0.070 nA Z=0.0000 nA
O
2
Save Adjust
2
the calculation of the calibration results.
2
In case of a successful calibration, the calibration values are stored in the cal history and taken over (Adjust), stored in the cal history and not taken over
u
(Calibrate) or discarded (Abort).
If ”Adjust” or ”Calibrate” are chosen, the message ”Calibration successful” is displayed. The M400 returns to the measuring mode.
Calibration using a calibration cell
For a more accurate calibration the calibration cell can be used. Doing this the TDL (the units head) needs to be removed from the probe. Then it has to be mounted on the calibration cell according to the illustration below. Before cali­bration is started new values for path length, temperature and pressure have to be entered on M400. Then the calibration gas is owed through the calibration cell and the calibration is done in the calibration menu of M400.
During calibration with the calibration cell the process is still sealed and no
extra precautions need to be taken.
Calibration cell.
EPL
2 × 100 mm (3.94")
104,6 mm (4.12")
25
Quick Setup Guide TDL GPro™ 500
5 Error messages
Message Comment Action Source Relay State Mapping
No sensor on channel 3 The M400 is unable to detect any of the ISM sensor(s) it can identify.
If no sensor is found it will disply the message NO SENSOR DETECTED
Signal Processing Failed Fitting of the line proles failed. Send unit back to METTLER TOLEDO TDL Fault Software error Laser Source Error The laser wavelength has shifted. Readjustment of the laser tempera-
ture necessary
Bad Signal Quality Transmission lower than 5% threshold Clean corner cube and process window.
Flashcard Error Missing or bad calibration and / or database data Perform a calibration with the calibration
Pressure Input Error Pressure reading out of extended range: 0.6 bara < P < 8 bara
4 – 20 mA input error: 4 mA > P > 20 mA
Temperature Input Error Pressure reading out of extended range: –20°C<T<1000°C
4 – 20 mA input error: 4 mA > P > 20 mA
Conguration Mode Ethernet port in use: diagnostic or conguration in progress Disconnect Ethernet cable TDL Maintenance
The GPro™ 500 error messages can be found in the M400 under the following path: Menu Service Diagnostics TDL Messages
26
Quick Setup Guide TDL GPro™ 500
– This is the initial message after Power on.
M400 Fault B disconnected – Wait for the GPro™ 500 to fully boot. – Check if the GPro™ 500 is powered and
wait until the system is fully started.
– Check the RS485 wiring of the
GPro™ 500 to the M400
– Check with the MT-TDL software and the
Ethernet port if the system is running correctly.
– If timeout still occurs after 60 s, send unit
back to METTLER TOLEDO.
Send unit back to METTLER TOLEDO TDL Fault System error
TDL Fault System error
Check the gasket between TDL and probe.
Rotate TDL on the probe to maximize Trans-
mission. Reduce the dustload in the process.
TDL Fault Software error tube. If still not successful, send unit back to METTLER TOLEDO for Flashcard exchange.
Check external pressure sensor and mapping TDL Maintenance
System error
request
Check external temperature sensor and mapping
TDL Maintenance
request
System error
Software error
request
27
Quick Setup Guide TDL GPro™ 500
GPro™ 500 Quick Setup-Leitfaden

Inhaltsverzeichnis

Lieferumfang 31 Anforderungen vor Ort 31 Umgebungs-bedingungen 31 Außerdem erforderlich 31 Optionales Zubehör 32
Montageort für Flansch 33 Anforderungen an den Flansch 33 Strömungs-verhältnisse anderMessstelle 34 Spülen 35 Spülen mit Wärmeschutz 36 Erdung und Verdrahtung (ATEX) 37 Aktive Analogeingänge (ATEX-Ausführung) 38 Schleifengespeiste Analogeingänge (ATEX-Ausführung) 39 Erdung und Verdrahtung (FM) 40 Aktive Analogeingänge (FM-Ausführung) 41 Schleifengespeiste Analogeingänge (FM-Ausführung) 42 GPro™ 500 Kabel 43 Kabelanschlüsse im M400 45

German

Allgemeines Setup (gilt für alle Parameter) 46 Kanalwahl 46 Kalibrierung 46 TDL Installation 46 Einstellung der korrekten Spülung der Prozessseite 49
Einpunktkalibrierung von TDL-Gassensoren 50 Prozesskalibrierung für TDL-Gassensoren 50 Kalibrierung mit einer Kalibrierzelle 51
29
Quick Setup Guide TDL GPro™ 500
30
Loading...
+ 128 hidden pages