METREL DELTAPAT 3309 Quick Reference Manual

METREL DELTAPAT 3309
QUICK REFERENCE GUIDE
0800 111 780 www.portableappliancetesters.co.nz
Class I
1. Connect the BLACK return lead (using clip or probe) to an exposed metal part on the appliance, then the other end into the socked laballed ‘S/EB’ on top right of the DeltaPAT.
2. Connect the power supply lead from the appliance into the front of the DeltaPAT tester and turn the appliance on.
3. On the DeltaPAT Main Menu, select SIMPLE TEST and press TEST.
4. Using the arrow keys scroll to Class I.
5. Press the TEST button to start the test.
6. The DeltaPAT will cycle through the ‘Earth Bond’ and ‘Insulation Resistance Test’.
7. A PASS or FAIL will be indicated on the screen once the test has been completed.
8. Press the ESC to start a new test.
Class II
1. Ensure the appliance is turned ON.
2. If you’re using an Earth Cloak shroud the device. Connect the BLACK return lead (using clip or probe) to a metal part or cloak if used. The other end will be placed into the socket labelled ‘S/EB’ on the top right of the DeltaPAT.
3. Connect the power supply lead from the appliance into the front of the DeltaPAT tester and turn the appliance on.
4. On the DeltaPAT Main Menu select SIMPLE TEST and press TEST.
5. Using the arrow keys scroll to Class II test.
6. Press the TEST button to start the test.
7. The DeltaPAT will cycle through the ‘Insulation Resistance Test’.
8. A PASS or FAIL will be indicated on the screen once the test has been completed.
9. Press the ESC to start a new test.
0800 111 780 www.portableappliancetesters.co.nz
Extension Leads
1. Connect the IEC LEAD (supplied with the DeltaPAT) into the socket labelled ‘IEC’ on the top left of the DeltaPAT.
2. Plug the Extension Lead into the front of the DeltaPAT and the other in the IEC LEAD (above) to create a circuit.
3. On the DeltaPAT Main Menu, select SIMPLE TEST and press TEST.
4. Using the arrow keys scroll to IEC.
5. Press the TEST button to start the test.
6. The DeltaPAT will cycle through the ‘Earth Bond’, ‘Insulation Resistance Test’ and ‘Polarity Test’.
7. A PASS or FAIL will be indicated on the screen once the tester has been completed.
8. Press the ESC to start a new test.
Leakage Current
1. Testing Leakge Current on Class I, Class II and RCD’s - refer to the above procedures. However, ensure that the ‘MAINS’ supply is connected and the correct test is selected on SIMPLE TEST mode and LKG is selected.
RCD Testing
1. Ensure that the MAINS supply is connected to 230V using an IEC cable supplied.
2. Plug the RCD to the front of the DeltaPAT.
3. Connect the other IEC Lead (supplied with the DeltaPAT) into the socket labelled ‘IEC’ on the top left of the DeltaPAT and the other end into a socket of the RCD under test.
4. On the DeltaPAT Main Menu, select SINGLE TEST and press TEST.
5. Using the arrow keys scroll to RCD and press TEST.
6. Using the arrow keys select Out: PRCD (portable RCD).
7. Press the ‘TAB’ button and select 1Δ: 30mA
or 10mA.
8. Press the ‘TAB’ button and select Mod: AUT).
9. Press the TEST button to start the test.