metran MK3075, MK3076, MK3071 Installation Manual

METRAN
MULTI-FUNCTION
AIR TO WATER HEAT PUMP
MULTI-FUNCTION
AIR TO
WATER HEAT PUMP
Installation & instruction manual
CODE:MK3075/MK3076/MK3071
Multi-Function Heat Pump
Contents
I. Introduction
II. Specification
III. Installation
IV. Function diagram of the remote controller
V. Maintenance and repair
VI. Wiring diagram
VII. Engineering installation diagram
-------------------------------------------------------------------------------------
1.User Guide------------------------------------------------------------------------------------
2.Special warning------------------------------------------------------------------------------
3.Note---------------------------------------------------------------------------------------------
4.Work principle and function introduction-----------------------------------------------
----------------------------------------------------------------------------------
---------------------------------------------------------------------------
--------------------------------------------------------------
3.Product appearance and installation dimension--------------------------------------
------------------------------------------------------------------------------------
1.Outdoor unit installation position---------------------------------------------------------
2.Outdoor unit installation ----------------------------------------------------------
3.Installation options--------------------------------------------------------------------------
4.Install location select------------------------------------------------------------------------
5.The unit and water tank installation-----------------------------------------------------­6 -----------------------------------------------------------
.Terminal equipments pipe connection--------------------------------------------------
8.Installation of the temp detector----------------------------------------------------------
9.Electrical wiring------------------------------------------------------------------------------
10. Electrical Wire selection------------------------------------------------------------------
11.Trial run----------------------------------------------------------------------------------------
------------------------------------------
1.Remote controller interface displays ---------------------------------------------------
----------------------------------------------------------------------
-------------------------------------------------------
-----------------------------------------------------------------
-----------------------------------------------------------
---------------------------------------------------
---------------------------------------------------------------------------
------------------------------
9.Parameter Table-----------------------------------------------------------------------------
-------------------------------------------------------------------
1.Care and maintenance---------------------------------------------------------------------
2.Malfunction Indicating Table.-------------------------------------------------------------
3.Determine and solve malfunction--------------------------------------------------------
-----------------------------------------------------------------------------
1.Double system type electrical box of internal structure----------------------------
2.MK3071 PCB Power sequence, current protection board-------------------------
3. MK3075 PCB input and output port definition----------------------------------------
4. Wiring diagram------------------------------------------------------------------------------
----------------------------------------------------
1.System application connection diagram-----------------------------------------------
2.System application connection diagram-----------------------------------------------
3. Auxiliary heat source connection--------------------------------------------------------
-------------------------------------------------------------
1.Type naming rules
2. onolithic
Notice
.Terminal equipment installation
7
2.Operation and display
3.System State parameter checking
4.System parameter setting
5.The maintenance time inquires
6.Date/ time/ timing on and off settings
7.Fault code display
8.Lock button/ Fahrenheit and Celsius change
4.Remote controller connection
M type performance
1 1 1 1 2 3 3 3 6 8 8 8 9 9 9 10 10 11 11 12 14 15 15 15 17 18 20 20 20 21 21 22 22 23 24 25 25 25 26 27 28 28 29 30 31
1
Multi-Function Heat Pump
I. Introduction
1.1.This manual contains the necessary information of correct installation, commissioning, use and maintenance of machinery.
1.2.In order to use this product better and more safety, please read this instruction carefully before install and use, and focus on the installation, use and maintenance of all considerations, taking into safekeeping for when required.
1.3.Heat pump is a highly specialized appliances, improper installation may cause damage or danger, so the corresponding installation and maintenance need professionals, users please contact our company special, commissioned local installation repair services department, carefully read the installation section, and follow the prompts to install.
1. User Guide
2. Special warning
2.1.Please ask a qualified professional installation company responsible for installing heat
pumps. Installation people should have relevant professional knowledge, when self­installation, the wrong action will result in fire, electric shock, injury, leakage, and so on.
2.2.When installation, please check the distribution power capacity, switches, sockets whether
according to our heat pump power supply requirements, details please refer to unit nameplate or technical data sheet on the installation instructions.
2.3.When power connect, the unit must be a reliable ground connection, confirm that the ground
wire is effective. If the ground is imperfect, may result in personal injury.
2.4.Heat pump before testing, hot water side and air-conditioning side of the water system must
be full of water, drain pipes before switch on, test the hot water side and air-conditoning side water system water pump independently, when normal, turn off the water pump exit test status, allowed to select the operating mode into the normal state of the unit test run.
2.5.The water above 52 may cause skin burns, tank hot water need mixed with cold water
before use.
2.6.Insert any tool within the heat pump is strictly prohibited, in order not to hit the fan result in unit
damaged or an accident.
2.7.When installation, be sure to install filter in the heat pump inlet, make sure unit inlet water was
clean enough.
2.8.The units have been set parameters well in the factory, non-professionals against
arbitrary adjustments.
2.9.When the unit needs to be moved or re-installation, Please ask a qualified professional
installation company for help.
2.10.Any self-modification or repair is forbidden, if repair not properly, may result in fire, electric
shock, injury and leakage incidents, you should ask agent or professional to repair.
3.Note
3.1.Please confirm that the drainage pipe is smooth outlet, improper piping installation will result in water leakage, or wet the furniture.
3.2.Confirm whether already install the leakage protection switch, or else may result in electric
shock.
3.3.Prohibiting installed in the position of combustible gas leaks.
3.4.Ensure the installation base, lifting is solid and reliable enough.
Multi-Function Heat Pump
3.5.Please correct connect the cable, if the cable connection error, it may damage the electrical components.
3.6.Before installation, you should not expose the unit in water or other moisture, it may cause short-circuit the electrical components.
3.7 If unit in the room leaks refrigerant in the installation process, then please immediately open the
room ventilation.
3.8.The unit heat exchanger air inlet and outlet position can not be any things obstruction in and out of wind.
3.9.The unit wire controller must be fixed at a convenient operation, dry environment, not to rain water and the out of children , do not install in the bathroom, so as not to affect the unit work by wet.
3.10.When the installation is completed, confirm that there is no leakage of refrigerant.
reach
4. Work principle and function introduction
Units under the reverse Carnot cycle principle, take a small amount of electricity as driving force and refrigerant as carrier, an endless absorption the air and water low-grade thermal energy which is difficult to use(-15-43 ), change into available high-grade heat, achieve low temperature heat transfer to high temperature heat; then high-grade heat energy released into the water system to supply domestic hot water (up to 60 ), through the hot water supply pipeline transport to users to meet the demand for domestic hot water and heating.At the same time, It also can produce more than 7 water through the pipes transport to user terminal equipment to meet the cooling needs.Users can choose the heat pump operating mode and temperature settings, select: cooling, heating, hot water, cooling + hot water supply, heating + hot water supply. Mode selection and temperature set finish, start the unit, enter into automatic operation. The highest COP up to 7.5 or more when heat pump running.
2
Compressor
Appliance side
Appliance side
Cold/hot water tank
heat exchange
heat exchange
Air
heat exchange
hot water tank
expansion valve
Multi-Function Air To Water Heat Pump
2. M type performanceonolithic
2.1.Horizontal fan direction type
Note:(1)Cooling:Outdoor air trmp:35 /24 ,Outlet water temp:7 ,Inlet water temp:12 ,Heating:Outdoor air temp:7 /6 ,Outlet water temp:45 ,
Input water temp:40 .
(2)Using in ambient temperature: -15 ~45 .
Model
Rated Output Water
Rated Input Power
Rated Input Current
M
Power Supply
Compressor
Compressor Qty
Fan Qty
Noise
Water Connection
Water Flow Volume
Water Connection
Water Flow Volume
Refrigerant Gas Type
Main Unit Net Dimensions(L/M/H
Main Unit Shipping Dimensions L/M/H
Net Weight
Shipping Weight
inmum circuit ampacity
Max.fuse
MACHRW
L/h
kW
BTU/h
kW
BTU/h
kW
A
A
A
V/PH/Hz
dB(A)
inch
m/h
inch
m/h
mm
mm
kg
kg
3
3
Rated Heating Capacity
Rated Cooling Capacity
The figure represents the horse power of unit eg:010 means 1 horse power
A: Horizontal fan direction B: Upward fan direction
Design alternative serial number
MA FP -***- A (**)
Energy exchange medium
A: Air
MW: Water
M
FP: Fan coil
1.2.Split outdoor unit type naming rules
II. Specification
1. Type naming rules
MA CHR W - *** - Z A / P S (**)
Source medium MA: Air source MW: Ground source
Function of the unit C: Cooling R: Heating CH: Cooling and hot water CR: cooling and heating CHR: C heating and hot waterooling
Energy exchange medium A: Air W: Water
Z: Integrated type W: Split type(indoor unit )
P: With built in pump, (without built in pump )omitted
S: 3phase(single phase )omitted
A: Horizontal fan direction B: Upward fan direction
Design alternative serial number
The figure represents the horse power of unit eg:010 means 1 horse power
1.1.All in one unit type naming rules, Split indoor unit type naming rules
Hot water side
Air condition side
R410A
030ZA/(P)
205
7.5
25600
9.0
30800
2.70
12.3
20
30
220/1/50
Rotary
1
1
55
1
2-3
1
3-4
1115/470/945
1205/525/975
112
132
035ZA/(P)
230
9.0
30800
10.5
35900
3.10
14.1
20
35
220/1/50
Rotary
1
1
55
1
2-3
1
3-4
1115/470/945
1205/525/975
115
135
040ZA/(P)
270
10.0
34200
12.0
41000
3.60
16.4
25
40
220/1/50
Scroll
1
1
55
1
4-5
1
3-4
1115/470/945
1205/525/975
125
145
050ZA/(P)S
380
12.5
42700
15.0
51200
4.50
7.9
15
20
380/3/50
Scroll
1
2
57
1
4-5
1
3-4
1115/470/1250
1205/525/1280
150
170
040ZA/(P)S
270
10.0
34200
12.0
41000
3.60
6.3
10
15
380/3/50
Scroll
1
1
55
1
4-5
1
3-4
1115/470/945
1205/525/975
125
145
045ZA/(P)S
355
11. 5
39300
13.5
46100
4.00
7.0
10
20
380/3/50
Scroll
1
1
55
1
4-5
1
3-4
1115/470/945
1205/525/975
135
155
060ZA/(P)S
445
15.0
51200
18.0
61500
5.30
9.3
15
25
380/3/50
Scroll
1
2
57
1
5-6
1
4-5
1115/470/1250
1205/525/1280
155
175
3
Multi-Function Air To Water Heat Pump
2.2.Upward fan direction type
Rated Heating Capacity
Rated Cooling Capacity
Hot water side
Air condition side
Model
Rated Output Water
Rated Input Power
Rated Input Current
Minmum circuit ampacity
Max.fuse
Power Supply
Compressor
Compressor Qty
Fan Qty
Noise
Water Connection
Water Flow Volume
Water Connection
Water Flow Volume
Refrigerant Gas Type
Main Unit Net Dimensions(L/M/H
Main Unit Shipping Dimensions L/M/H
Net Weight
Shipping Weight
MACHRW
L/h
kW
BTU/h
kW
BTU/h
kW
A
A
A
V/PH/Hz
dB(A)
inch
m/h
inch
m/h
mm
mm
kg
kg
3
3
R410A
300ZB/(P)S
2030
75.0
255900
90.0
307100
26.50
46.5
65
110
380/3/50
Scroll
4
3
62
2
20-25
3
15-20
2180/1070/2000
2500/1270/2200
1100
1160
250ZB/(P)S
1760
62.5
213300
75.0
255900
22.10
38.8
55
90
380/3/50
Scroll
4
3
62
2
13-15
3
15-20
2180/1070/2000
2500/1270/2200
950
1010
200ZB/(P)S
1320
50.0
170600
60.0
204800
17.70
31.1
45
75
380/3/50
Scroll
3
3
62
2
13-15
2
10-12
2180/1070/2000
2500/1270/2200
850
910
120ZB/(P)S
885
30.0
102400
36.0
122900
10.60
18.6
25
45
380/3/50
Scroll
2
2
58
1-1/4
7-8
1-1/4
6-7
1450/730/1260
1545/780/1310
300
325
100ZB/(P)S
755
25.0
85300
30.0
102400
8.90
15.6
25
40
380/3/50
Scroll
2
2
58
1-1/4
7-8
1-1/4
6-7
1450/730/1260
1545/780/1310
265
290
Rated Heating Capacity
Rated Cooling Capacity
Hot water side
Air condition side
Model
Rated Output Water
Rated Input Power
Rated Input Current
Minmum circuit ampacity
Max.fuse
Power Supply
Compressor
Compressor Qty
Fan Qty
Noise
Water Connection
Water Flow Volume
Water Connection
Water Flow Volume
Refrigerant Gas Type
Main Unit Net Dimensions(L/M/H
Main Unit Shipping Dimensions L/M/H
Net Weight
Shipping Weight
MACHRW
L/h
kW
BTU/h
kW
BTU/h
kW
A
A
A
V/PH/Hz
dB(A)
inch
m/h
inch
m/h
mm
mm
kg
kg
3
3
R410A
030ZB/(P)
205
7.5
25600
9.0
30800
2.70
12.3
20
30
220/1/50
Rotary
1
1
55
1
2-3
1
2-3
760/704/770
785/770/870
93
108
040ZB/(P)S
270
10.0
34200
12.0
41000
3.60
6.3
10
15
380/3/50
Scroll
1
1
55
1
4-5
1
3-4
860/806/970
890/870/1070
108
123
050ZB/(P)S
380
12.5
42700
15.0
51200
4.50
7.9
15
20
380/3/50
Scroll
1
1
55
1
4-5
1
3-4
860/806/970
890/870/1070
135
150
080ZB/(P)S
540
20.0
68300
24.0
81900
7.10
12.5
20
30
380/3/50
Scroll
2
2
58
1-1/4
7-8
1-1/4
6-7
1450/730/1060
1545/780/1110
250
275
060ZB/(P)S
445
15.0
51200
18.0
61500
5.30
9.3
15
25
380/3/50
Scroll
1
1
55
1
5-6
1
4-5
860/806/970
890/870/1070
150
165
Note:(1)Cooling:Outdoor air trmp:35 /24 ,Outlet water temp:7 ,Inlet water temp:12 ,Heating:Outdoor air temp:7 /6 ,Outlet water temp:45 ,
Input water temp:40 .
(2)Using in ambient temperature: -15 ~45 .
4
Multi-Function Air To Water Heat Pump
2.3.Split type performance
Note:(1)Cooling:Outdoor air trmp:35 /24 ,Outlet water temp:7 ,Inlet water temp:12 ,Heating:Outdoor air temp:7 /6 ,Outlet water temp:45 ,
Input water temp:40 .
(2)Using in ambient temperature: -15 ~45 .
2.4.Pressure-bearing tank performance parameters
100
100
G1
0.7
470 1060
550/550/1150
25/30
MX
L
inch
Mpa
mm
mm
kg
150
150
G1
0.7
470 1500
550/550/1600
30/35
200
200
G1
0.7
520 1500
590/590/1600
35/40
250
250
G1
0.7
600 1320
635/635/1420
45/50
300
300
G1-1/4
0.7
600 1540
53/60
635/635/1660
400
400
0.7
700 1500
775/775/1620
65/75
G1-1/4
500
500
0.7
700 1800
775/775/1920
73/83
G1-1/4
R410A
Rated Heating Capacity
Rated Heating Capacity
MACHRW(S)
MAFP
MAFP
Indoor Unit Model
Outdoor Unit (Side Fan)Model
Outdoor Unit (Top Fan)Model
Rated Output Water
Rated Input Power
Rated Input Current
Minmum circuit ampacity
Max.fuse
Power Supply
Compressor
Compressor Qty
Fan Qty horizontal / vertical
Noise
Refrigerant Liquid Pipe
Refrigerant Gas Pipe
Water Connection
Water Flow Volume
Refrigerant Gas Type
Indoor Unit Net Dimensions(L/M/H
Indoor Unit Shipping Dimensions L/M/H
Out door (Side Fan)Unit Net Dimensions(L/M/H
Out door (Side Fan)Shipping Dimensions L/M/H
Out door (top Fan)Net Dimensions(L/M/H
Out door (top Fan) Shipping Dimensions L/M/H
Indoor Unit Net/Shipping Weight
Out door (Side Fan)Unit Net/Shipping Weight
Out door (Top Fan)Net/Shipping Weight
L/h
kW
BTU/h
kW
BTU/h
kW
A
A
A
V/PH/Hz
dB(A)
inch
inch
inch
m/h
mm
mm
mm
mm
mm
mm
kg
kg
kg
3
Hot water side / Air condition side
030W/(P)
030A
030B
205
7.5
25600
9.0
30800
2.70
12.3
20
30
220/1/50
Rotary
1
1/1
50
3/8
1/2
1
2-3
600/630/785
710/750/915
885/470/700
980/525/725
660/660/860
750/700/960
55/70
40/45
45/57
035W/(P)
035A
035B
230
9.0
30800
10.5
35900
3.10
14.1
20
35
220/1/50
Rotary
1
1/1
50
3/8
1/2
1
2-3
600/630/785
710/750/915
885/470/700
980/525/725
660/660/860
750/700/960
58/73
40/45
45/57
040W/(P)
040A
040B
270
10.0
34200
12.0
41000
3.60
16.4
25
40
220/1/50
Scroll
1
1/1
54
1/2
5/8
1
3-4
600/630/785
710/750/915
885/470/945
980/525/975
660/660/860
750/700/960
100/115
60/65
50/65
040W/(P)S
040A
040B
270
10.0
34200
12.0
41000
3.60
6.3
10
15
380/3/50
Scroll
1
1/1
54
1/2
5/8
1
3-4
600/630/785
710/750/915
885/470/945
980/525/975
660/660/860
750/700/960
100/115
60/65
50/65
045W/(P)S
045A
045B
355
11. 5
39300
13.5
46100
4.00
7.0
10
20
380/3/50
Scroll
1
1/1
54
1/2
5/8
1
3-4
600/630/785
710/750/915
885/470/945
980/525/975
660/660/860
750/700/960
105/120
60/65
50/65
050W/(P)S
050A
050B
380
12.5
42700
15.0
51200
4.50
7.9
15
20
380/3/50
Scroll
1
2/1
54
1/2
3/4
1
3-4
600/630/785
710/750/915
885/470/1250
980/525/1280
660/660/960
750/700/1060
110/125
70/75
60/75
060W/(P)S
060A
060B
445
15.0
51200
18.0
61500
5.30
9.3
15
25
380/3/50
Scroll
1
2/1
54
1/2
3/4
1
4-5
600/630/785
710/750/915
885/470/1250
980/525/1280
660/660/960
750/700/1060
115/130
70/75
60/75
20
20
G1
0.7
470 250
550/550/350
10/15
MH
L
inch
Mpa
mm
mm
kg
30
30
G1
0.7
470 380
550/550/480
12/17
50
50
G1
0.7
470 510
/22
550/550/610
15
80
80
0.7
G1-1/4
470 850
550/550/950
20/27
100
100
0.7
25/30
G1-1/4
470 1060
550/550/1150
120
120
0.7
28/33
G1-1/2
470 1300
550/550/1450
150
150
0.7
30/35
G1-1/2
470 1500
550/550/1600
Model
Water volume
WaterOutlet/Water Inlet
Max.Working Pressure Tank
Net Dimensions( xH
Shipping Dimensions L/M/H
Net/Shipping Weight
2.5.Buffer tank performance parameters
Model
Water volume
WaterOutlet/Water Inlet
Max.Working Pressure Tank
Net Dimensions( xH
Shipping Dimensions L/M/H
Net/Shipping Weight
5
Multi-Function Air To Water Heat Pump
2.6 Hot water tank and buffer tank options
1.1.If the unit without a tank when leave factory, please select tanks as follow requirements
(heater in the tank, if need the tank water temperature over 60 degrees, heaters required to be installed, need not to install if not required).
1.2.This heat pump water heater can be equipped with tank-type water heater (Figure 1) and
closed-type water heater (Figure 2).
A. Select the tank-type water heaters:
1) The tank-type water heater should be able to withstand the rated pressure of 0.03MPa.
2) If the devices capacity more than 15L, and can not be empty by a outlet which install in the pipe, it should be equipped with a kind of emission devices, which with tools to make it work. (Emission devices can be combined with pressure relief devices)
3) The unit without water level control output, need external water tank level control equipment.
B. Select the closed water heaters:
1) If not installed pressure relief device inside the water tank, so must be fitted with pressure relief devices (when installed refer to the "Third, installation, 3, pipe connection"), the parameter value is 0.7MPa.
2) The water can drain from the pressure relief device in the outlet pipe which should keep connected with the atmosphere.
3) The pressure relief device to periodically work to remove the
calcium carbonate deposition, and sure that device is not plugged.
4) Heat pump water heater installation is complete, the water tank empty refer to the "three, installation, 5, trial run."
5) Design an enclosed heater which directly connect to water, the rated pressure should be at least 0.6MPa.
6) If the devices capacity more than 15L, and can not be empty by a outlet which install in the pipe, it should be equipped with a kind of emission devices, which with tools to make it work. (Emission devices can be combined with pressure relief devices)
Outlet
3. Product appearance and installation dimension
3.1.Installation dimensions of integrated type unit
450 820 806 970
A
B C D
Size
Units: mm
MACHRW
030ZB/(P)~035ZB/(P)
040ZB/(P)(S)~060ZB/(P)S
450 720 704 770
B
A
C
D
440
755 1115 1250
A
B C D
Size
Units: mm
MACHRW
440 755
1115
945
030ZA/(P) ~045ZA/(P)(S)
050ZA/(P)S~060ZA/(P)S
A
B
C
D
D
6
Inlet
Outlet
Inlet
Figure 2
Figure 1
Outlet
Inlet
Tank
Ball valve
Vent
Overflow
Water level
Heaters
Size
Units: mm
MODEL
AB
MH20 MH30 MH50 MH80 MH100 MH120 MH150
470 470 470 470 470 470 470
250 380 510
850 1060 1300 1500
Size
Units: mm
MODEL
AB
MX100 MX150 MX200 MX250 MX300 MX400 MX500
470 470 520 600 600 700 700
1060 1500 1500 1320 1540 1500 1800
708
750 1450 1060
A
B C D
Size
080ZB/(P)S
Units: mm
MACHRW
100ZB/(P)S~120ZB/(P)S
708
750 1450 1260
D
B C
A
A
C
B
2000 1070 2180
A
B C
Size
Units: mm
MACHRW
200ZB/(P)S~300ZB/(P)S
Multi-Function Air To Water Heat Pump
4.2 Installation dimensions of split type unit
665 390 600 785
A B C D
Size
030W/(P)(S)~060W/(P)S
Units: mm
MACHRW
D
C
A
B
440 525 885 945
A
B C D
Size
030A~035A
Units: mm
MAFP
440 525 885
1250
040A~045A 050A~060A
440 525 885 700
D
A
B
C
D
300 685 660 860
A
B C D
Size
Units: mm
300 685 660 960
A
B
C
D
MAFP
030B~045B
050B~060B
2.4. ressure-bearing tankInstallation dimensions of p
L
R
L
R
A
B
Temperature­detection
Heating cycle inlet 1
2.5. uffer tankInstallation dimensions of b
L
R
L
R
A
B
7
Heating cycle outlet 1
Drain
Hot wate cycle inlet
Hot wate cycle outlet
Heating cycle inlet 2
Heating cycle outlet 2
Cold inlet
Cycle outlet 1
Temperature­detection
Cycle inlet 1
Drain
Cycle outlet 2
Cycle inlet 2
Cold inlet
1. Outdoor unit installation position
2. Outdoor unit installation
Notice
To avoid ventilation short, the outdoor unit discharged air should not return when installation.
Please keep enough space around the outdoor unit for repair. Right and wrong means as below:
2.1.To get enough air for ventilation of the unit, the installation position should be with good ventilation.
2.2.The installation position can hold the outdoor unit without noise and shake.
2.3.No sunlight to the unit. Set an awning if necessary.
2.4.The water from rain and defrosting can be discharged in the installation position.
2.5.The unit will not be covered by snow in the installation position.
2.6.The discharged air will not face strong air in the installation position.
2.7.Be sure the noise caused by the unit ventilation and operation will not affect the neighbor.
2.8.The installation position will not be affected by garbage, oil and mist.
2.9.The outdoor unit will be damaged under the condition with oil, salt and sulfide air.
Wrong Right
MACON
III. Installation Notice
Multi-Function Air To Water Heat Pump
8
300mm
200mm
1500mm
600mm
Air outlet
500mm
200mm
600mm
Bolt fix
500mm
200mm
600mm
700mm
400mm
600mm
1000mm
700mm
400mm
400mm
1000mm
2000mm
Multi-Function Air To Water Heat Pump
3. Installation options
3
A Side fan type installation space requirements:
.1. The unit can be installed in the balcony, roof, floor or any other convenient place and reliable
load-bearing.
3.2.Airiness place.
3.3.No heat radiation or other heat source place
3.4.Should be set up shed against the snow in winter.
3.5.Barrier-free at the air inlet or outlet place.
3.6.Outlet against strong winds blowing place.
3.7.There should be drainage channels around the machine in order to rule out the condensate.
3.8.Control Panel, do not install in the bathroom, so as not to affect the unit work by wet.
3.9. Should leave enough space around the machine. As shown below.
B Top fan type installation space requirements:
4.hot water tank(water tank)and buffer tank(water tank) install location select
4.1.The water tank can be installed in the outdoor with heat pump outdoor unit, such as balconies,
roofs, floors, also can be installed in the room.
4.2.Water tank must be standing install, the installation place is a solid foundation, must be bear the weight of the tank when full of water.
4.3.Around the water tank , as well as water pipes and hot water pipes should install a valve.
4.4.Do not install the water tank, where exist pollute and corrosive gases.
5.The unit and water tank installation
5.1.Unit install base is concrete structures, also can be made of steel angle brackets, plus vibration
rubber pad placed on the ground or roof, to ensure the unit horizontally.
5.2.Installed base design should in accordance with units and water tanks installed size And operational quality.
5.3.Directly use expansion bolts to fix unit and water tank to the concrete base.
5.4.Around the unit and tank should be drain or outlet.
9
Air intlet
Bolt fix
Unit
Unit
Unit
Bolt fix
Multi-Function Air To Water Heat Pump
6.Installation of terminal equipment
6.1.Indoor terminal equipment installation (such as: fan coil, radiator heater or floor heating), the
equipment should be installed in accordance with relevant regulatory requirements.
6.2.In accordance with the requirements of engineering design drawings, installation and construction.
6.3.Use a soft connector to connect the unit and fan coil inlet and outlet pipes; install fan coil condensate drain pipe, connect the condensate drain interface, and to ensure smooth drainage of condensate water.
7. The unit and hot water tank, buffer tank and terminal equipments pipe connection (Refer to installation diagram)
7.1.Pipe material selection, can be stainless steel pipe, copper pipe, aluminum water pipe, hot
water PPR pipes and so on, according with national health and safety standards, heat­resistant, rust-proof, no scaling pipe.
7.2.The choice of pipe sizes can be used the one which is matches the heat pump inlet and outlet
main pipe, and, respectively connect to heat pump inlet and outlet, and follow the proper construction of plumbing standards.
7.3.Water tank outlet pipe and overflow pipe installed in the gutter or outlet position as far as
possible, where convenient to drainage.
7.4.The unit and the junction to the tank must be installed valve or demolition loose joint, for
maintenance use.
7.5.Water pipes are arranged reasonably to minimize bending and reduce the pressure loss of
water system
7.6.The unit air-conditioning side and the hot water side circle inlet must be installed a above 50
mesh water filter to reduce the water system resistance loss.
7.7.The unit air-conditioning side and the hot water side which connect to running water must be
installed a one-way valve, filter and pressure relief devices (pressure relief devices used on the closed water tank, water tank accessories in general, the parameter value 0.7MPa), in accordance with the flow and valve arrow direction, to avoid flow be obstructed.
7.8.The unit hot water side circle outlet connect to tank circle inlet, and the host hot water side
circle inlet connect to tank circle outlet,tank hot water supply connect to hot water pipe.
7.9.Air-conditioning side buffer tank in series installed on the outlet of the main pipe.
7.10. After hot water side and air-conditioning side water system pipes, circulated pipes, hot water
supply pipes connected, it must be pipe connection rigorous testing , plus 0.7Mpa pressure testing 24 hours, system pipes connector no leakage and clean and sewage pipes, to ensure that the system clean, no debris. No leakage after the test, then pack the pipe and valve with insulation (including the replenishment pipes and valves).
7.11.In order to discharge the water system air clean, avoid air trapping in the pipeline, the water
supply return pipe highest point should be set up a automatically exhaust valve.
7.12.The water system expansion tank, automatic water valve and stop valve should be installed
indoors, to prevent water pipes and valves crack when not use in the winter.
7.13.The metal pipe must be used above 50mm thickness of glass fiber or high-density fire
retardant PE for thermal insulation and moisture, PPR water pipe can be used 30mm thickness of glass fiber or high-density fire retardant PE for thermal insulation and moisture to prevent cold, heat loss and condensation.
10
Multi-Function Air To Water Heat Pump
7.14.The unit water inlet and outlet must install a thermometer, water pressure gage, to facilitate
inspection when operate.
1) Tubing pipeline should be separate test pressure, must not test with hot water unit or tanks.
2) The water system working pressure: 0.2-0 .7 Mpa.
3) The water system operating temperature: 5-75 .
4) Water can drain from the pressure relief device drainage pipe, and the piope keep open to atmosphere.
5) The pressure relief device regularly move to remove the calcium carbonate, and prove that the device is not plugged.
6) Installation of one-way valves, filters and pressure relief device, valve body arrow as same as flow direction .
7) The pressure relief device discharge pipe should be installed in the frost-free environment in
A continuous down way.
Note:
9.Electrical wiring
9.1. should use dedicated power supply, power supply voltage line corresponding
with rated voltage.
9.2.The unit power cable must use copper cable, the cable diameter must ensure that the unit's maximum starting current requirements.
9.3. power supply circuit must have a grounding wire, which should connect with a reliable external ground wire, and the external ground wire is effective.
The unit
The unit
8. Installation of the temp detector
The head of sensor
The heat conduction silica gel
Detector
Tank
The first step
The second step The third step
The fourth step
Tank Tank Tank
The heat conduction silica gel
Detector
The head of sensor
< 5 pin
< 5 pin
The head of sensor
Detector
Detector
The head of sensor
The heat conduction silica gel
< 5 pin
8.1.The first step Daub the heat conduction silica gel spreads in the front of sensor, and insert into the detector.
8.2.The second step use < 5 pin to push the detector into the end of the detector against the end of the sensor, and marks on level of the pin and the detector.
8.3.The third step putout the pin the position of mark to be at the same level with the inlet of detector check whether the sensor is inserted to the pipe terminal.
8.4.The fourth step the inlet of the detector is sealed with the glass silica gel, and keep the inlet of the detector upwards and uprightness about an hour
11
Multi-Function Air To Water Heat Pump
9.4.Wiring construction must be installed by professional technicians refer to circuit diagram.
9.5.Power lines and signal line layout should be neat, rational, strong and weak lines separate and can not interfere with each other, while not contacted with the connecting pipe and the valve body.
9.6.When power lines and control lines parallel, the wires were placed in each tube, also leave appropriate distance between the lines.
9.7.Unit electric wire connection: take the unit power line, remote control three core lines, electric heater power line, solar circulated water pump control power line, water tank temperature sensing line, solar collector temperature sensor line, terminal equipments connect to unit lines, through the unit wiring hole set into the electrical box, connect to the appropriate terminals according to wiring diagram, and fix it by the pressure line of board in the electrical box.
9.8.Unit control panel Code MK3075, Fuse specifications: 10A/250V
10. Electrical Wire Selection
10.1.Voltage drop occur may due to the large current draw during compressor starting, and may
be result in the compressor is difficult to stat. So we recommend selecting the wire specification from the table below.
10.2.Size Table of Electrical Wire
within 5m
2.0
3.5
5.5
8.0
Within 10m
2.0
3.5
5.5
8.0
14.0
Within 15m
2.0
3.5
5.5
8.0
14.0
22.0
Within 20m
3.5
5.5
8.0
14.0
22.0
30.0
Within 30m
5.5
8.0
14.0
22.0
30.0
38.0
50.0
Within 50m
8.0
14.0
22.0
30.0
38.0
50.0
60.0
80.0
Within 1m
2.0
3.5
5.5
8.0
14.0
Starting current
(A)
Below 20
30 40 50 60 70 80
90 100 110 120 140 160 180 200 220 240
Below Below Below Below Below Below
Below Below Below Below Below Below Below Below Below Below
Markor Mark (Heat resistance temperature above 60 )
The wiring specifications (mm2)
Mark (Heat resistance temperature above 120 )
Power supply
PCB
Unit
1
2
Compressor
COM
Power supply installation condition: The touching space of breaker should be more than 3mm,
use copper wire only.
12
Multi-Function Air To Water Heat Pump
10.3 Caution of Ground The internal motor protector does not protect the compressor against all possible
conditions.Please be sure that the system utilizes the ground connection when installed in the field.
10.4 Warning: To avoid fire, electric shock and other accidents, keep in mind about these tips:
10.4.1.Only use power supply voltage indicated on the label, if you do not know the family of
voltage, contact the dealer or local power company.
10.4.2.When you use the unit by the maximum current please view the specifications, so make sure
your home's power supply (current, voltage and cable) to meet the machine's normal load Requirements.
10.4.3.To protect the power lines. Power lines should be fixed, so that people will not be trip over or
the lines damaged by other things. Paying particular attention to plugs, which should be easily plug into the socket, careful the plug position.
10.4.4.Do not overload wall plugs or extension the cable. Line overload can cause fire or electric
shock.
10.4.5.To ensure your safety, you must plug the power lines into the socket with a grounded
three-phase, and check to ensure your socket is accurate and reliable grounding.
030Z(W)A(B)
035Z(W)A(B)
040Z(W)A(B)
040Z(W)A(B)/S
045Z(W)A(B)/S
050Z(W)A(B)/S
060Z(W)A(B)/S
080ZB/S
100ZB/S
120ZB/S
200ZB/S
300ZB/S
220V/1PH/50Hz
2.5mm
2mm2
380V/3PH/50Hz
2.5
mm2mm
2
4.0mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
4.0mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
2.5mm
2mm2
4.0mm
2mm2
4.0mm
2mm2
6.0mm
2mm2
4.0mm
2mm2
4.0mm
2mm2
6.0mm
2mm2
4.0mm
2mm2
4.0mm
2mm2
4.0mm
2mm2
4.0mm
2mm2
10.0mm
2mm2
4.0mm
2mm2
4.0mm
2mm2
16.0mm
2mm2
4.0mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
0.5mm
2mm2
15
15
15
15
15
15
15
15
15
15
15
15
50
50
50
50
50
50
50
50
50
50
50
50
RSTNLN
13
Host PowerMode Phase line Zero line
Ground line
Max.line length (m)
Signal line
Tem. sensor assistance line
Max.line length (m)
Phase line
Zero line
Ground line
Phase line 1
Phase line 2
Phase line 3
Zero line
Ground line
Note:
1. used PVC insulated copper wire for above wiring
2. for installation requires, the line is longer than the maximum line length, please contact the company
10.5.Power wiring as follows (single unit):
MACON
11.Trial run 11
Note:
.1.Check the hot water side, air-conditioning side and solar side of the water system piping and
all accessories are installed correctly, heat pumps, water tanks, terminal equipment piping connections are correct. The fill water supply of hot water side, air-conditioning side and solar side are normal, the replenishment port whether installed pressure relief valve, ony-way valve, filter and other accessories.
11.2.Open the unit hot water side, air-conditioning and solar side hydrating valve, circular inlet and outlet water valve, main pipe backwater valve, floor branch pipe valve, terminal equipment inlet and outlet valve, fill the hot water side water tank, air-conditioning side water tank and solar collector system with water. Check the valves should be open if all open, the valves should be closed if all closed, pipe insulation if complete.
11.3.Open the exhaust valve, hot water valve, drain the pipe air, confirm pipe clean, close the exhaust valve, hot water valve.
11.4.Check the power supply if required with the unit power supply on the nameplate, power supply voltage if normal.
11.5.Check all power supply and control wires are all connected in place, whether connect correctly according to the cable wiring diagram, all the terminals are tightened and check the reliability of ground connection.
11.6.Test Hot water side, air-conditioning side, solar side water to test, first of all, heat pump units connected to power supply, operating the remote controller (refer to the remote controller operation), start the hot water side, air-conditioning side, solar side circulating pump, opened the exhaust valve again to drain the pipe air, observe and listen water pump operation, the circulating water flow whether normal. Until the hot water side, air­conditioning side, and solar side circulating water system work completely normal, close the hot water side, air conditioning and solar side circulating pump.
11.7.When a full inspection of the entire system to install correctly and meet the requirements, may carry out the whole test run.
11.8.Operate the unit controller, select the heat pump working mode and setting temperature, back to controller main interface, press to start the heat pump.
11.9.First water pump operate 30s, the compressor starts. To determine unit operation if have different sound through hearing, if is, shunt down power immediately and check, only continue running if there is no different sound, at the same time pay attention to system high and low pressure if normal.
11.10.Check again whether the unit input power and current normal, if not, then shut down to check.
11.11.View the unit control operation status display, check and record the unit's output and input status, the value of each point temperature indicated if normal.
11.12.Operate the unit controller, change the heat pump working mode, check and record the unit's output and input status, the value of each point temperature indicated if normal. Unit put into normal run only after checking all the working modes are normal.
1 unit the first time power on without three minutes delay protection, other times there is three
minutes delay protection.
2 must clean the pipe air when first the unit boot.
system
Multi-Function Air To Water Heat Pump
14
1. Remote controller interface displays as below
IV. Function diagram of the unit controller
Prg
Ese
UNIT ON/OFF
SET
BACK
UP
DOWN
ENTER
Press this button to control the unit's ON or OFF
Press this button to enter the main menu interface Press this button to return to the previous screen
Press this button and enter the next parameters interface or enter parameters modification state, and confirm the modification
Modification parameter values or turn to next page
Modify theparameter values or turn to next page
Power off (Standby display status)
2.1 . Power on(off)/mode display status Power on: Under the standby status,press for 3 second,after hear beep means
power on,operation pannel display the corresponding mode.
Power off: Under the standby status,press for 3 second,after hear beep means
power off,operation pannel display the corresponding off status.
Multi-Function Air To Water Heat Pump
Prg
Ese
MODE
A.C. water Inlet Hot water tank Solar Collector Ambient temp. 2011-04-08 11:25
Off
12 25 25 30
Prg
Ese
Welcometouse
Prg
Ese
MODE
A.C. water Inlet Hot water tank Solar Collector Ambient temp.
2011-04-08 11:25
Off
12 25 25 30
Under the main interface,press: enter into parameter setting interface,choose "main menu ",press button,choose "Mode select",press into the mode setting, press to view and choose,press again to go into the modify parameter interface, the corresponding parameter value is flashing,press to modify the value,press
eturn to the previous menu.
(E.g)
Prg
Ese
Prg
Ese
MODE
A.C. water Inlet Hot water tank Solar Collector Ambient temp. 2011-04-08 11:25
Cooling
Hot water
12 25 25 30
Power on(Corresponding mode)
2.2 Mode of operation
2. Operation and display
Press button
Prg
Prg
Ese
Main menu Maintenance Clock
Prg
Ese
Mode select Unit status
Press button
Prg
Ese
Mode Heating
Hot water A.C.heat temp. 38 Hot water temp. 55 A.C.aux.heat on H.W.aux.heat on
Press button again
Prg
Ese
Mode Heating
Hot water A.C.heat temp. 38 Hot water temp. 55 A.C.aux.heat on H.W.aux.heat on
Press button you can change the running mode
Press button you can change the set heating temp.
Press button you can
change the set hot water temp. Press button you can turn on/off air condition auxiliary electric heater
Press button you can turn on/off hot water auxiliary electric heater
15
Prg
Ese
Mode
A.C.heat temp. A.C.aux. heat
Heating
35
On
Prg
Ese
Mode
Hot water temp. H.W. aux. Heat
Hot water
55
on
Multi-Function Air To Water Heat Pump
2.3 Mode introduction
Prg
Ese
Mode Heating
Hot water A.C.heat temp. 38 Hot water temp. 55 A.C.aux.heat on H.W.aux.heat on
There are eight selection modes, the following is the mode of display and introduction
Prg
Ese
3.1 Aux.start delay
3.2 Ambient temp.set
30M
15
Prg
Ese
4.1 Ambient low
4.2 Power remember
4.3 System number
4.4 Priority
4.5 A.C. pump
4.6H.W.pump
4.7 E.H.A.C. Pump
4.8 E.H.H.W. Pump
-15 On
2
H.W.
Special
Normal Special Special
Heating+Hot water mode
1.This mode is running according to 4.4 parameters setting, giving priority to meet the demand for hot water, or air-conditioning heating needs.
2.When open the air condition or hot water auxiliary electric heater, the auxiliary electric heater control by parameter 3.1 and 3.2.
he auxiliary electric heater start ambient temperature(When the ambient temperature is below the set temperature, the electric heating allows the output . When the unit while meeting the parameters of 3.1and3.2 .The auxiliary heating output.
Parameter 3.1:Auxiliary electric heater start delay time (the time to delay after unit power on, the electric heater allows to output). Parameter 3.2:T
Prg
Ese
4.1 Ambient low
4.2 Power remember
4.3 System number
4.4 Priority
4.5 A.C. pump
4.6H.W.pump
4.7 E.H.A.C. Pump
4.8 E.H.H.W. Pump
-15 On
2
H.W.
Special
Normal Special Special
Prg
Ese
1.1 A.C.C & H.W.water
1.2 A.C. T
1.3 H.W T
48
2 5
Prg
Ese
Mode
A.C. cool temp.
Cooling
12
1.Parameter 1.2 under air condition side cooling and heating mode,the compressor restart difference temperature.
2.Parameter1.3 under hot water heating mode,the compressor restart difference temperature.
3.Parameter4.5 air condition water cycle pump working way. Special:Air condition reaches the set temperature, the air condition pump long-term work. Normal:Air condition reaches the set temperature, the air condition pump stop work.
4.Parameter4.6 hot water cycle pump working way. Special:hot water tank temp. reaches the set temperature, the hot water cycle pump long-term work. Normal:hot water tank temp. reaches the set temperature, the hot water cycle pump stop work.
Cooling mode /Heating mode/ Hot water mode
12
16
Prg
Ese
A.C. water Inlet A.C. water outlet Hot water tank H.W. Water outlet Sys. 1 coil temp. Sys. 2 coil temp. Ambient temp. Solar temp.
8
25 25 25 25 30 25
-1
Multi-Function Air To Water Heat Pump
Prg
Ese
Mode
A.C.heat temp. Hot water temp.
Elec. heating
Elec. hotwater
35 55
Prg
Ese
4.1 Ambient low
4.2 Power remember
4.3 System number
4.4 Priority
4.5 A.C. pump
4.6H.W.pump
4.7 E.H.A.C. Pump
4.8 E.H.H.W. Pump
-15 On
2
H.W. Special Normal Special Special
Air condition electric heating + Hot water e modelectric heating
1.Parameter4.7 when the unit running air condition electric heating mode the air condition water cycle pump working way. Special:the air condition water pump required output. Normal: .
2
the air condition water pump not required output
.Parameter4.8 when the unit running hot water electric heating mode the hot water cycle
pump working way. Special:the hot water cycle pump required output. Normal:the hot water cycle pump not required output.
Prg
Ese
Mode
A.C.cool temp. Hot water temp. H.W. aux. heat
Cooling
Hot water
12 55
on
Cooling+Hot water mode
Prg
Ese
Mode
Hot water temp.
Elec. hotwater
55
Prg
Ese
Mode
A.C. Heat temp.
Elec.heating
35
Air condition electric heating mode
Hot water electric heating mode
3.System parameter checking:State
On the main interface,press enter into parameter setting interface,choose
"Main menu " press button,choose "Unit status",press into the mode setting,press
to view the paramter, press return to the previous menu.
Prg
Ese
Prg
Ese
Main menu Maintenance Clock
Mode select Unit status
Prg
Ese
Press button Press button
Unit State parameters
Display
A.C. water Inlet A.C. water outlet Hot water tank H.W. Water outlet Sys. 1 coil temp. Sys. 2 coil temp. Ambient temp. Solar temp. Discharge temp.1
Status
12
8 25 28 25 25 30 25 87
Means
Air condition water inlet temp. Air condition water outlet temp. Hot water tank temp. Hot water outlet temp. System 1 coil temp. System 2 coil temp. Ambient temp. Solar collector temp. System 1 discharge temp.
17
Multi-Function Air To Water Heat PumpMulti-Function Air To Water Heat Pump
Display
Discharge temp.2 Compressor 1 Compressor 2 Fan motor 4way-valve1 4way-valve 2 2way-valve 1 2way-valve2 A.C. pump H.W. pump Solar pump A.C.aux. Heater H.W.aux. heater A.C. flow sw H.W. flow sw Sys1 HP SW Sys1 LP SW Sys2 HP SW Sys2 LP SW Heat pump WK SW Mode select SW Aux. heat SW Phase PT SW A.C. aux. TH SW H.W aux. TH SW
87
On/Off On/Off On/Off On/Off On/Off On/Off
Close/Open Close/Open Close/Open Close/Open Close/Open Close/Open Close/Open Close/Open Close/Open Close/Open
Status
On/Off On/Off On/Off On/Off On/Off
On/Off Close/Open Close/Open
System 2 discharge temp. On/Off On/Off On/Off On/Off On/Off On/Off On/Off Air condition water cycle pump Hot water cycle pump Solar water cycle pump Air condition auxiliary electric heater Hot water auxiliary electric heater Air condition side water flow switch Hot water flow switch System 1 high pressure switch System 1 low pressure switch System 2 high pressure switch System 2 low pressure switch Air condition side net switch Mode switch( ) Forced electric heating switch Power phase sequence protection switch Overheating protection switch Overheating protection switch
Means
effective for disconnect wire controller
4. :System parameter setting
Prg
Prg
Ese
On the main interface,press the button enter into page2(picture1),press for 5 second until hear the beep ,one more parameter parameter)appear, press
to view the parameter, choose Parameter and press to enter the
paremters setting interface,press to view the parameter,press to
enter the paremters setting interface press to view the parameter, press
to enter the system paremters setting interface,corresponding parameter flashing,
press to modify,press to return previous menu.
Prg
Ese
Main menu Parameter Maintenance Clock
Picture1
Prg
Ese
Main menu Maintenance Clock
Press button for 5 second until hear the beep
Prg
18
Multi-Function Air To Water Heat Pump
4.1 Detailed description of the function parameters
Prg
Ese
1.1 A.C.C & H.W.water
1.2 A.C. T
1.3 H.W T
48
2 5
Parameters 1.0 select Heat pump
Prg
Ese
2.1 Def. cycle
2.2 Def. inlet temp.
2.3 Def. outlet temp.
2.4 Def. max. time
3M
-3
13
8M
Parameters 2.0 select Defrost
Prg
Ese
3.1 Aux.start delay
3.2 Ambient temp.set
30M
15
Parameters 3.0 select Aux-heating
Prg
Ese
4.1 Ambient low
4.2 Power remember
4.3 System number
4.4 Priority
4.5 A.C. pump
4.6H.W.pump
4.7 E.H.A.C. Pump
4.8 E.H.H.W. Pump
-15 On
2
H.W.
Special
Normal Special Special
Parameters 4.0 select Systems
Prg
Ese
4.9 Comp.PT temp. 115
Prg
Ese
5.1 Solar start T
5.2 Solar stop T
10
1
Parameters 5.0 select Solar setting
Prg
Ese
A.C. pump H.W. pump Solar pump
on/off on/off on/off
Parameters 6.0 select Water pump testing
Parameters 1.1:When operation cooling + hot water mode, is conducive to cooling efficiency. When the temperature is set too high, it will reduce the cooling energy efficiency.
Parameter 1.2 under air condition side cooling and heating mode. The compressor restart difference temperature. Parameter1.3 under hot water heating mode,the compressor restart difference temperature.
Parameter 2.1: Parameter 2.2:
parameter 2.3:
parameter 2.4:
Cycle defrost cycle time setting. Into the defrost state conditions. When the coil temperature is
below this parameter setting, the conditions are met.
Exit defrost state condition 1, when the coil temperature is higher
than the set value of this parameter, the condition is met.
out defrost state condition 2, when the defrost time is running
larger than this parameter setting the time, conditions are met.
Parameter 4.1:
arameter 4.2: arameter 4.3: T
arameter 4.4: Parameter 4.5: Air condition water cycle pump working way. Parameter 4.6: Hot water cycle pump working way. Parameter 4.7: When the unit running air condition electric heating mode the air condition water cycle pump working way. Parameter 4.8: When the unit running hot water electric heating mode the hot
water cycle pump working way.
arameter 4.9:
Unit work environment set the minimum ambient temperature. P Power-down memory options parameters. P he system number parameters. P Heating + hot water mode preference parameters.
P Compressor discharge temperature too high protection exhaust temperature setting.
Parameter 5.1:
arameter 5.2:
Solar pump starts difference temperature set. The difference temperature of solar collectors measured values and hot water tank measured temperature. P The difference temperature of solar water pump set off.
Parameter 6.0:
parameter.
This parameter is used by engineers debugging parameters, you can manually open the air-conditioning pumps, water pumps, and solar water pump
Parameter 3.1:Auxiliary electric heater start delay time (the time to delay after unit power on, the electric heater allows to output). Parameter 3.2:The auxiliary electric heater start ambient temperature(When
the ambient temperature is below the set temperature, the electric heating allows the output .
19
Prg
Ese
Main menu Parameter Maintenance Clock
Prg
Ese
1: E01 2010-01-14 09:00 2: P01 2010-01-14 09:10 3: E08 2010-01-14 09:30 4: E05 2010-01-14 09:40 5: P06 2010-01-14 09:50 6: P08 2010-01-14 10:00 7: P12 2010-01-14 10:10 8: E07 2010-01-14 10:20
Prg
Ese
Date Clock
2010-04-15
18:30
5. The maintenance time inquires
In the interface ,press to enter parameter setting interface,choose "Maintenance'' and press to enter Maintenance time inquires, press to turn a choice, and press key returns the last menu.
Prg
Ese
6. Date/ time/ timing on and off settings
7. Fault code display
When a fault, unit controller display automatically corresponding fault code and the fault
reasons.When fault resolution, fault display automatically eliminate or after re-power to
eliminate.
Multi-Function Air To Water Heat Pump
Prg
Ese
Date Clock Timer on Timer off
2010-04-15
18:30 X X
Press button for 5 second until hear the beep
Prg
In the main interface, press key to enter the parameter setting interface, select Clock, press key to enter the time setting / timing on or off interface, press the
key to turn options: Note: Press button for 5 seconds, when you hear the beep sound, you can see the page to add Timer on and Timer off select column.
Prg
Prg
6.1 . When you select "Date", press key, the date of the year setting flash, press the key to modify Year, then press key again, the month setting flash, press the key to modify the month, click the key again, Day flash, press the key to modify the day, then press key to confirm and exit, press the
button to return the layer menu.
Ese
6.2. When you select "Clock", press the key, the time hourly position flash, press the key to modify hour value, then press key, minutes flash, press the
key to modify the minute value, press the key again confirm and exit,
press the to return the layer menu.
Ese
6.3. When you select "Timer on", press the key, regular on or off setting flash, press key to modify the boot time whether on / off, appear " " symbol when choose
on, and show regular boot time settings, click the key, regular on or off hour value setting flash, press the key to modify the value, then press key, regular on or off minute value setting flash, press key to modify the value, press key to confirm and exit, press the "Ese" to return the layer menu.
Ese
20
Multi-Function Air To Water Heat Pump
8. Lock button/ Fahrenheit and Celsius change:
8.1 Display Lock Under the power on or standby status:Press for 10s, all buttons on the display are locked, but it can be unlocked after pressing for 10s again. Shows
8.2 Fahrenheit and Celsius change Under the Celsius status, press for 10 s can changed Fahrenheit ,it will change to Celsius again when press for 10s.
Ese
Ese
9. Parameter Table
Display code1 Display code2
Setting data explanation or working state
Parameter setting range
Default
Remarks
1.0 Heat pump
2.0 Defrost
Parameter
30 60
115
115
2.1 Def. Cycle 30M
2.2 Def. inlet temp. -3
2.3 Def. outlet temp.13
2.4 Def. Max. Time 3M
defrosting cycle setting
Start defrosting coil temperature setting
Exit defrost temperature setting
Defrost time setting
30min 90min
-30 -0
130
1min 12min
45min
-3
13
8min
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
48
2
5
30min
15
-20 45
3min 90min
Adjustable
Adjustable
3.0 Aux-heating
4.0 Systems
-25 - 5
On/OFF
1or2
A.C./H.W
Special/Normal
Special/Normal
Special/Normal
Special/Normal
30 ~ 125
1.1 A.C.C & H.W.water
1.2 A.C. T
1.3 H.W T
3.1 Aux.start delay
4.1 Ambient low
4.2 Power remember
4.3 System number
4.4 Priority
4.5 A.C. pump
4.6H.W.pump
4.7 E.H.A.C. Pump
4.8 E.H.H.W. Pump
4.9 Comp.PT temp.
-15
On
2
H.W.
Special
Normal
Special
Special
115
5.1 Solar start T
5.2 Solar stop T
10
1
1~20
1~20
A.C. Pump
H.W. pump
Solar pump
On/Off
On/Off
On/Off
Off
Off
Off
Air conditioner start temperature difference setting Hot water heating start temperature difference setting
5.0 Solar setting
6.0 Water pump testing
Solar start temperature difference setting Solar stop temperature difference setting
Air conditioner pump
Hot water pump
Solar pump
System number
Priority
Unit stop when the ambient temperature lower than the setting value Whether recover to the previous status after power is reset
Auxiliary electric heater start to work when ambient temperature lower than the setting value
3.2 Ambient temp.set
Auxiliary electric heater start delay
21
Air condition side water pump working way
Hot water pump working way
Electric heating mode, air condition side water pump working way
Electric heating mode, hot water pump working way.
Compressor discharge temp.too high protection setting.
Special: turn on Normal: turn off
Special: turn on Normal: turn off
Special: turn on Normal: turn off
Special: turn on Normal: turn off
V .Maintenance and repair
Multi-Function Air To Water Heat Pump
22
1. Care and maintenance
Heat pump water heater is high automation equipment, regular checks unit when use, if the unit are kept effective and long-term maintenance, the unit's operating life and reliability are significantly increased.
1.1.The water filter installed outside the machine should be cleaned regularly to ensure the system is clean and in order to avoid dirty or jam cause damage.
1.2.Users in the use and maintenance of the unit should pay attention to: all the security devices setting are finished in factory, do not adjust.
1.3.Regular check the power unit and electrical wiring system if strong enough, electrical components if disorders, if is, maintenance and replace it timely.
1.4.Always check the water system replenishment water tank safety valves, liquid level controller and exhaust device if working properly, so as not to cause air entering the system reduced the water cycle, thus affecting the unit's heating capacity and unit reliability.
1.5.Check the water pump, water valve is working properly, water pipeline and pipe fittings if leak.
1.6.The unit surrounding should be clean and dry, well-ventilated. A regular time (1-2 months) to clean air side heat exchanger to maintain good heat transfer.
1.7.Always check the unit's parts work, check units inside pipe joints and pneumatic valve whether there is any oil, to ensure the unit no leakage of refrigerant.
1.8.Dont pile up debris around the unit so as not to plug air inlet and outlet, unit around should be kept clean and dry, well-ventilated.
1.9.If the unit downtime is too long, first should empty the pipeline water, and cut off power, dress a good shield. When run again, boot the system after full examination.
1.10.Main unit condenser cleaning, our company recommends 50 degrees to 60 degrees, the concentration of 15% thermal phosphoric acid to clean the condenser, turn on the circulation pump comes with system to clean 3 hours, and finally washed three times with tap water. (Pipe installation, we recommend to set aside three links interface, with a seal to plug an
interface), for fear to connect pipe when cleaning. Prohibit use corrosive cleaning fluid to clean the condenser. 1.11, tanks need to use a period of time (usually two months, the concrete may be based on local water quality) to remove fouling. 1.12, if unit fails, the user can not resolve, please call our local special maintenance department, we will promptly send People to maintenance it.
Multi-Function Air To Water Heat Pump
2.Malfunction Indicating Table. Determine and solve the malfunction by malfunction code as below:
Malfunction and Protection Name
Reason
Solution
Display Mode
Cooling/heating inlet water temp. Sensor failure
Cooling/heating outlet water temp. Sensor failure
System1coil temp. Sensor failure
System 2 coil temp. Sensor failure
Ambient temp. sensor failure
Solar collector sensor failure
1.Check whether the connection of sensor is poor.
2.Check or change the solar collector sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the ambient sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the system 2 coil sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the sensor.system 1 discharge
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
The sensor is open or short circuit
1.Check whether the connection of sensor is poor.
2.Check or change the system 1 coil sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the hot water outlet sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the hot water tank sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the air condition outlet sensor.
1.Check whether the connection of sensor is poor.
2.Check or change the air condition inlet sensor.
Hot water tank temp. Sensor failure
Hot water outlet temp. Sensor failure
System 1 discharge temp. Sensor failure
E00
E01
E02
E03
E05
E06
E07
E08
E09
E10
System 2 discharge temp. Sensor failure
The sensor is open or short circuit
1.Check whether the connection of sensor is poor.
2.Check or change the system 2 discharge sensor.
System 2 high pressure protection
Hot water side water flow switch failure protection
Air condition side antifreezing protection in winter
Air condition side frost protection
System 1 discharge temp too high protection
Hot water side antifreezing protection in winter
Auxiliary electric overheating protection(hot water side)
No water/little water in water system.
System 1 low pressure protection.
The unit is not
running well.
System 1 high pressure protection.
1.Check whether the hor water side flow switch is normal.
2.Check whether the hot water side water system is normal.
System 2 low pressure protection.
Air condition side water flow switch failure protection
System 2 discharge temp too high protection
Auxiliary electric overheating protection(air condition side)
Phase sequence protection
P00
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P15
Ambient temperature too low protection
System 1 highpressure switch is opened
System 1 lowpressure switch is opened
System 2 highpressure switch is opened
System 2 lowpressure switch is opened
No water/little water in water system.
Air condition side water outlet temp. too low
System 1 is not
running well.
System 2 is not
running well.
Ambient temp. too low.
Overheating protection switch is open.
Overheating protection switch is open.
Power supply phase failure /lacking
Ambient temp.is too low
1.Check whether the high pressure switch is normal.
2.Check whether the water tank temperature setting is too high.
3.Check whether the refrigerant is over capacity.
1.Check whether the low pressure switch is normal.
2.Check whether refrigerant leak.
1.Check whether the high pressure switch is normal.
2.Check whether the water tank temperature setting is too high.
3.Check whether the refrigerant is over capacity.
1.Check whether the low pressure switch is normal.
2.Check whether refrigerant leak.
1.Check whether the air condition side flow switch is normal.
2.Check whether the air condition side water system is normal.
Check the whether it 's power supply phase failure /lacking or not, if phase failure ,please exchange the position of phase ,and power up again.
1.Check whether the hor water side flow switch is normal.
2.Check whether the hot water side water system is normal.
1.Check whether the water tank temperature setting is too high.
2.Check whether the system 1 refrigerant is over capacity.
1.Check whether the water tank temperature setting is too high.
2.Check whether the system 2 refrigerant is over capacity.
1.Check whether the air condition side flow switch is normal.
2.Check whether the air condition side water system is normal.
Defrost
With automatic antifreezing funtion to avoid the unit freezing off.
With automatic antifreezing funtion to avoid the unit freezing off.
With automatic antifreezing funtion to avoid the unit freezing off.
23
3. Determine and solve malfunction by below table:
Malfunction
Reason Solution
1. Shut down and check the power
2.Check the reason and repair
3.Check and change the power fuse
1.check the water supplement equipment and supply water into the system.
2.Exhaust the air from the water system
3.Clean the water filter or exhaust the air from system
4.Clean the water filter
1.Check the leakage and add refrigerant
2.Enhance the thermal insulation of the pipe route
3.Clean the exchanger and improve the condensation condition
4. Clean the water filter
1. Discharge surplus refrigerant
2. Clean the exchanger and improve the condensation condition
1.Check the leakage and add refrigerant
2.Change the capillary tube or filter
3.Clean the exchanger and improve the condensation
condition
4.Change the expansion valve
1.Check the power and solve the malfunction
2.Change the contacter
3.Check loose reason and repair
4. Compressor overload protection
5. Reset the return water temperature
6. Clean the water filer and exhaust the air from the system
1.Check the reason and solve the malfunction
2.Change the compressor
1. Change the fan relay
2. Change the fan motor
1.Check the leakage and add refrigerant
2.Check the reason and change the plate exchanger
3.Change the compressor
1.Clean the water filter and exhaust the air from the system
2.Re-set
1.Clean the water filter and exhaust the air from the system
2.Change the flow switch
1. Power failures
2. The unit wire loses
3. The unit power fuse burns out.
1. The water system is lack of water
2. There's air in the system.
3. The water system valve doesn't open entirely
4. The water filter is dirty and jam
1. Refrigerant is insufficient
2. Thermal insulation of the water system is poor
3. Thermal discharge of the exchange is poor
4. Water flow volume is insufficient
1.Too much refrigerant
2.Thermal discharge of the exchange is poor
1. Refrigerant is insufficient
2. The filter and or capillary tube jam
3. Water flow volume is insufficient
4. Capillary tube of expansion valve sensor bulb breakdown
1. Power failure
2. Compressor contacter damaged
3. Wire loses
4. Compressor overload protection
5. Return water temperature setting incorrect
6. Water flow volume is insufficient
1.Refrigerant enter into the compressor
2.Compressor damaged
1. Fan relay damaged
2. Motor is burnt out
1. The refrigerant leak out
2. Plate exchanger freezes
3. Compressor failure
1.Water flow volume is insufficient
2.Temperature control setting is too low
1.Water flow volume is insufficient
2.Flow switch
The unit can't run
The water pump can run but can't circulate and is noisy
The cooling capacity is too low and the compressor works continuously without pause.
The compressor exhausted pressure is too high
The compressor suction pressure is too low
Compressor can't work
Compressor noisy
Fan can't work
The compressor run but no refrigeration
Low water temperature protection to the unit
Few water flow volume protection to the unit
Multi-Function Air To Water Heat Pump
24
VI.Wiring diagram
1. Double system type electrical box of internal structure
Multi-Function Air To Water Heat Pump
2. MK3071 PCB Power sequence, current protection board
Power input Power input Power input
Power input Signal output Signal output
Connect transformer output (12VAC)
Connect PCB(MK3075) transformer output
Meaning
Symbol
NO .NO
T S R
N P3 P4
TRAN-OUT1 TRAN-OUT2
1 2 3 4 5 6 7 8
Note: The power input requirements for 380V/3PH/50Hz.
NO .
NO .
Meaning Meaning
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28
29
System 1 Ac contactor System 2 Ac contactor
Transformer Controller Fan motor relay Air conditioner pump relay Hot water pump relay Solar water pump relay Air conditioner electricity heating Hot water electricity heating NO.1 fan motor capacitor NO.2 fan motor capacitor Public terminals(AC-N) Fan motor power supply
Phase sequence current protection board
number 1 4-way valve power supply No. 2 4-way valve power supply No. 1 solenoid valve power supply No. 2 solenoid valve power supply Crankcase heater power supply Power input (380V/3PH/50Hz) Connection air conditioner cycle pump Connection hot water cycle pump Connection solar cycle pump
Connection air conditioner aux. electric Connection hot water aux. Electric Air condition side net switch. Mode switch(effective for disconnect the wire controller)
Aux. Electric power input (220V/1PH/50Hz)
MK3071
FUSE
1234
ON
DIP
R
S
T
N
P3
P4
0057W
0057W
0057W
0057W
JK1
IC6
CON1
TRAN-OUT1
TRAN-OUT2
L1
L1
L2
L3
L4
2.1.The setting of current protection value
1234
ON
DIP
Symbol :0000
1234
ON
DIP
Symbol:1111
MK3075
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
FUSE
1234
ON
DIP
CN1
CN2
CN3
CN9
CN10
IC6
IC12
IC7
N3
N2
AC-N
AC-L
RY1
OUT1
RY2
RY3
RY4
RY5
RY6
RY7
RY8
OUT2
OUT3
OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10
OUT11
OUT12
RY9 RY10
RY11 RY12
RY13
OUT13
RP1
RP4
CC394B-V1.1
W101122
E-VALVE1
E-VALVE2
01
02
03
04
05
06
07
08
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
TRAN-IN
MK3071
FUSE
1234
ON
DIP
CC196-V5.0
Y81128
R
S
T
N
P3
P4
0057W
0057W
0057W
0057W
JK1
IC6
CON1
TRAN-OUT1
TRAN-OUT2
L1 L2 L1 L2L1 L2 L1 L2L1 L2 L1 L2
RSTN
10
1
5
2
4
3
6
8
9
7
13
12
11
14
15 161718 19 20
21 22
23
24
25 26
27 28
Power Run
Symbol
Current value 0011 1101 0101 1001 0001 1110
Symbol
Current value
8A
9A 10A 11A 12A 18A
1010 0010 1100 0100 1000 0000
20A 21A 28A 29A 30A 31A
Attention: Unit demand to set it as "1110" forcibly
For example:
25
29
Multi-Function Air To Water Heat Pump
Symbol
Meaning
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
Compressor of system 1 Compressor of system 2 Fan motor 4 way valve 1 4 way valve 2 Electromagnetic valve1 Electromagnetic valve2 Air condition water pump Hot water pump Solar water pump
Air condition electricity heating Hot water electricity heating Crankcase heater Power Input Power Input Power Input(AC-N) Power Input(AC-N) Transformer input Wire controller Transformer output
Meaning
Symbol
NO .NONO .NO
3. MK3075 PCB input and output port definition
35 36 37 38 39 40 41 42 43 44 45 46 47
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 AC-L AC-N N2 N3 TRAN-IN CN9 CN10
MK3075
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
FUSE
1234
ON
DIP
CN1
CN2
CN3
CN9
CN10
IC6
IC12
IC7
N3
N2
AC-N
AC-L
RY1
OUT1
RY2
RY3
RY4
RY5
RY6
RY7
RY8
OUT2
OUT3
OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10
OUT11
OUT12
RY9 RY10
RY11 RY12
RY13
OUT13
RP1
RP4
CC394B-V1.1
W101122
E-VALVE1
E-VALVE2
01
02
03
04
05
06
07
08
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
TRAN-IN
CN1
CN2
CN3
CN2
GND Hot water tank temp. GND Ambient temp. GND
System1 discharge temp. GND System 2 discharge temp. GND System 1 pipe temp. GND System 2 pipe temp. GND
Air-conditioning outlet water temp. GND Air-conditioning inlet water temp. GND Hot water outlet temp. GND Solar water collector temp. GND
Air condition side net switch GND
Mode switch GND Forced electric heater model switch GND System 1 high-pressure switch GND System 1 low-pressure switch GND Hot water flow switch
GND Air conditioning water flow switch GND
GND
GND
GND
GND Phase sequence protection GND
System 2 high-pressure switch
System 2 low-pressure switch
Hot water electricity heating protection switch
Air conditioner electrical heating protection switch
Run led display
Failure indication
1flash 1 off
L1 side overcurrent protection
Run led display
Failure indication
2flash 1 off
3flash 1 off
4flash 1 off
5flash 1 off
L2 side overcurrent protection
L3 side overcurrent protection
L4 side overcurrent protection
Power phase sequence protection
2.2 .MK3071 PCB Power sequence, current protection board failure indication
26
Multi-Function Air To Water Heat Pump
4 Wiring diagram (MK3075-0101).
27
0102 030405 0607 08
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
A:
B:
C:
D:
E:
F:
G:
H:
L:
M:
System 1 No.1-4-way valve
System 2 No.1-4-way valve
System 1 No.2-4-way valve
System 2 No.2-4-way valve
System 1 No.1 Solenoid valve
System 2 No.1 Solenoid valve
System 1 No.2 Solenoid valve
System 2 No.2 Solenoid valve
System 1 crankshaft heating
System 2 crankshaft heating
Note1
Note2:
:( Face the unit)the left side is system 1,the right side is system 2.
Air conditioning and hot water electric heating power should be lower than 3KW.
3 phase Power input
(380VAC/3PH/ 50HZ)
R
S
N
T
Transformer
R
S
TN
P3 P4
L1 L2
L
1L2
Air condition
side water
cycle pump
(220VAC)
Hot water
cycle pump
(220VAC)
Protection board
R
S
C
Compressor
System 2
System 1
R
S
C
Compressor
COMNOCOMNOCOMNOCOM
NO
COMNOCOM
NO
T1
T2
T3
L1
L2
L3
T1
T2
T3
L1
L2
L3
Compressor 1
Compressor 2
Outdoor fan
NO.1 4-wayvalve
Air conditionwater cycle pump
Hot watercycle pump
Solar watercycle pump
Air conditionelectric heating
Hot waterelectric heating
Crankshaft heating
NO.2 4-wayvalve
NO.1 Solenoidvalve
NO.2 Solenoidvalve
FUSE
1
2
3
4
5
7
8
9
10
11
6
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
12
13
14
15
16
17
18
19
20
21
22
Power
AC-N
AC-L
L1 L2
L
1L2
L1 L2
L
1L2
Fan
Red
Orange
Capacitance
Fan
Red
Orange
Capacitance
Black
White
Black
White
A
B
C
D
E
F
G
H
10A/250V
23
Red
Blue
White
Red
Blue
Red
Blue
White
Blue
Red
Red
Blue
White
Red
Red
Red
Black
White
Blue
Red
Red
Red
Red
Red
Solar water
cycle pump
(220VAC)
Aux. electric
heating
power input
(220VAC)
Air conditionside
aux.electric
heating output
(220VAC <3KW)
Hot waterside
aux.electric
heating output
(220VAC <3KW)
White
Blue
Y/G
Y/G
Y/G
Y/G
Y/G
Y/G
Relay
Relay
Relay
Relay
Relay
Relay
Contactor 1
Contactor 2
L
M
Red
1234
on dip
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Air condition outlet temp.
Air condition inlet temp.
Hot water outlet temp.
Solar collector temp.
Hot water tank temp.
Ambient temp.
System 1 discharge temp.
System 2 discharge temp.
System 1 coil pipe temp.
System 2 coil pipe temp.
Reservation
Air condition side net switch
(close :turn on open :turn off)
Mode switch
(effective for disconnect the wire controller)
(close: heating +hot water mode)
(open: cooling + hot water mode)
Forced electric heating switch
(close : forced hot water electric heating)
(open: normal)
Air conditionside water flow switch
Hot waterside aux.electric overload protection
(close: normal,open: protection)
Air conditionside aux.electric overload protection
(close: normal,open: protection)
phase sequenceerror and current overload protection
(close: normalopen: protection)
System 1 high pressure switch
System 1 low pressure switch
System 2 high pressure switch
System 2 low pressure switch
pressure switch
(close :normal open: protection)
Hot water flow switch
water flow switch
(close :normal open:protection )
1
2
3
4
5
6
Air condition
side netswitch
Mode switch
Red
Multi-Function Air To Water Heat Pump
1.System application connection diagram
19
18
17
16
15
14
1
2
3
4
5
6
7
8
9
10
11
12
13
Pressure gauge
Flexible connectors
Globe valves
Electric driven three-way valve
Electric driven two-way valve
Glass thermometer
Y-graph filter
1
Hot water tank
2
Controller
3
Unit
Expansion Tank
4
5
Buffer tank
6
Water distribution device
7
Water collection device
Fan coil
14
Water to waterexchanger
15
Swimming pool
16
Swimming pool cycle pump
17
Sand cylinder filter
18
8
Solar
9
Solar cycle pump
13
Radiators
Supply hot water pump
10
Bath room
11
Floor heating coil
12
19
Replenishment water tank
28
VII. Engineering installation diagram:
Multi-Function Air To Water Heat Pump
2. System application connection diagram
18
17
15
16
14
8
10
11
6
7
12
13
19
2
3
4
5
1
4
Fan coil
14
Water to waterexchanger
15
Swimming pool
16
Swimming pool cycle pump
17
Sand cylinder filter
18
Replenishment water inlet
19
8
Solar
9
Solar cycle pump
13
Radiators
Supply hot water pump
10
Bath room
11
Floor heating coil
12
Pressure gauge
Flexible connectors
Globe valves
Electric driven three-way valve
Electric driven two-way valve
Glass thermometer
Y-graph filter
1
Hot water tank
2
Controller
3
Unit
5
Buffer tank
6
Water distribution device
7
Water collection device
4
Expansion Tank
9