Metermann EPM3 User Manual [en, de, fr, it]

EPM3
Phase Sequence and Motor Rotation Tester
Users Manual
Mode d’emploi
Bedienungshandbuch
Manual de uso
PN 2099589 September 2004 2004 Meterman Test Tools. All rights reserved. Printed in Taiwan
English
M1
M2
BATT
TEST
M3
L1
ABC
L2 L3
MOTOR ROTATION DETERMINED WHILE FACING MOTOR SHAFT
CAT
600
V
MOTOR
ROTATION
TESTER
3
-PHASE TESTER
EPM
3
EPM
3
DO NOT CONNECT TO LIVE VOLTAGE!
1
4
6
7
3
5
2
A
Phase rotation input terminals
B
Open phase indicators
C
Phase rotation indicators
D
Motor tester power switch
E
Motor tester power indicator
F
Motor rotation indicators
G
Motor rotation input terminals
1
EPM3 Phase Sequence and Motor
Rotation Tester
Contents
Safety Information ..............................................................................................2
Symbols Used in this Manual ..........................................................................2
Introduction ........................................................................................................3
Making Measurements........................................................................................3
3-Phase Rotation Test......................................................................................3
Open Phase Test ..............................................................................................4
Motor Rotation Test.........................................................................................4
Maintenance .......................................................................................................5
Battery and Fuse Replacement.........................................................................5
Cleaning and Storage.......................................................................................5
Limited Warranty and Limitation of Liability .......................................................5
Repair .................................................................................................................6
Specifications .....................................................................................................7
General Specifications .....................................................................................7
Electrical Specifications ...................................................................................7
2
Safety Information
The EPM3 Phase Sequence and Motor Rotation Tester conforms to CSA 22.2 -1010-1 and EN61010-1, CAT III 600 V.
To ensure safe operation and usage of this instrument, follow instructions in this manual. Failure to observe Warnings may result in SEVERE injury or death.
It is recommended for use in distribution level and fixed installations, as well as lesser installations, and not for primary supply lines, overhead lines and cable systems.
Do not exceed the maximum overload limits per function (see specifications) nor the limits marked on the instrument itself. Never apply more than 600 V ac rms between the test lead and earth ground.
Inspect the tester, test leads and accessories before each use. Do not use any damaged part.
Never ground yourself when taking measurements. Do not touch exposed circuit elements or test probe tips.
Do not operate the tester in an explosive atmosphere.
Exercise extreme caution when: measuring voltage >20 V // current >10 mA //
AC power line with inductive loads // AC power line during electrical storms // current, when the fuse blows in a circuit with open circuit voltage >600 V.
Never replace a fuse with one of a different rating.
Remove test leads before opening the case.
Do not use in a manner not specified or the protection afforded by the
instrument may be impaired.
Symbols Used in this Manual
X Dangerous Voltage W Refer to the manual
T Double insulated B Alternating Current F Direct Current J Earth Ground
P
Complies with EU directives
)
Canadian Standards Association
s
Complies with TÜV
3
Introduction
The tester provides three functions in one unit, including open phase, phase sequence and motor rotation indication. This tester is ideal for installing conveyor lines, pump systems and interconnected drivers.
The EPM3 is two measurement devices. One half measures the phase sequence of a 3-wire system using the power of the system under test. Using lamp indicators, it will indicate the 3-phase sequence or it will indicate an open phase situation. The other half of the EPM3 measures 3-phase motor rotation on an unpowered motor using the EPM3's internal 9 volt battery. The unit will indicate whether the motor shaft has clockwise or counter-clockwise rotation.
Features:
Identifies 3-phase sequence and open phase check
Motor shaft rotation
Battery operated
Meets EN61010 safety requirements
Supplied with three CAT III rated large alligator clips and color coded test leads
XWCaution
Read all Safety Information before using this tester.
Making Measurements
3-Phase Rotation Test
XWCaution
This instrument only indicates that voltage is present, not the voltage level. Verify the actual voltage with a multimeter. Using the wrong voltage can damage a motor.
1. Connect the three color coded test leads to the 3-phase input terminals, L1
(Red) - L2 (Green) - L3 (Blue) also know as A-B-C or R-S-T. See Figure 1.
2. Connect the three color coded alligator clips to the terminals of a 3-phase
power source. The connection order is optional. Use extreme caution in this high voltage situation.
3. Confirm that all three lights below the test lead inputs on the EPM3 are ON. If
one or more of the three lights is OFF, there is an open phase condition. Correct the power source problems before proceeding (See Open Phase Test later in this manual). If the Open Phase tests are good, the EPM3 is defective. Repair or replace the EPM3 before proceeding.
4. If all three lamps are ON, check the phase rotation indication for the rotation
direction, clockwise (w) or counter-clockwise (x) indicator.
5. If the counter clockwise lamp is ON, reverse the connections of any two of the
three alligator clips for clockwise rotation. Use extreme caution in this high voltage situation.
6 The phase sequence is correct for clockwise (w) rotation when the
clockwise lamp is ON and the power source terminals are connected by the RED, GREEN, and BLUE alligator clips to L1, L2, and L3. Remove power and label the power source wires.
4
Open Phase Test
XWCaution
The multimeter used for this test should be properly rated for the circuit under test.
1. Connect a multimeter (set to VAC and the voltage range expected) V input to the phase wire in question and the COM input to neutral or ground to check the phase voltage. Use extreme caution in this high voltage situation.
2. Verify that the two other phases are working properly and that the 3-phase to phase voltages are correct. If a problem is found, correct the problem before returning to the 3-phase rotation test.
Motor Rotation Test
This test can be used to verify the shaft rotation and the M1-M2-M3 connections or to determine the M1-M2-M3 connections on a motor that is not marked.
XWWarning
Make all connections with circuits unpowered. If the clockwise or counterclockwise RED indicator is ON before rotating the motor shaft, voltage is present. Stop measuring. Remove the test leads and turn off the external power.
1. Use a multimeter to verify that no voltage is present on the motor windings.
2. Connect the color coded test leads to the three motor input terminals M1- M2­M3. Press the power button (See Figure 2). The green indicator light will be ON.
3. Facing the motor shaft, hand rotate the motor shaft clockwise.
4. If the clockwise indicator (w) is ON, the M1-M2-M3 connections are correct for clockwise rotation.
5. If the counterclockwise (x) indicator is ON, the M1-M2-M3 connections are correct for counterclockwise rotation.
6. If the motor rotation direction is wrong, reverse any two of the M1-M2-M3 connections and repeat the test.
After 3-phase rotation and motor phasing are verified:
1. Turn off power at the source.
2. Connect the previously identified power wire L1 to motor wire M1. Repeat the connections for L2 to M2 and L3 to M3. See Figure 3.
3. Inspect the connections for electrical safety.
The motor will rotate in the desired direction when power is applied.
5
Maintenance
If the EPM3 appears to operate incorrectly, check the following items:
1. Review the operating instructions to ensure the meter is being used correctly.
2. Inspect and test the continuity of the test leads.
3. Make sure the battery is in good condition. Replace a low battery immediately.
4. Check the condition of the fuses.
XWWARNING
To avoid electrical shock, remove the test leads from the EPM3 and the test circuit before accessing the battery or the fuse.
Battery and Fuse Replacement
To access these parts, you must first remove the rear cover of the EPM3. The rear cover is held in place with two screws. After removing the screws, you can easily remove and replace the battery or a fuse. To replace a fuse, pry it from the retaining clips using a small screwdriver. See Figure 4.
Use the following replacement parts: Battery: 9 V NEDA 1604, IEC 6F22 Phase Sequence Fuse: Fast Blow 200 mA/600 V (Meterman FP900) Motor Rotation Fuse: Fast Blow 100 mA/250 V (Littel Fuse 216.100)
Cleaning and Storage
Periodically wipe the case with a damp cloth and detergent. Do not use abrasives or solvents. Remove the battery if the tester is not in use for periods longer than 60 days.
Limited Warranty and Limitation of Liability
Your Meterman product will be free from defects in material and workmanship for 1 year from the date of purchase. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling. Resellers are not authorized to extend any other warranty on Meterman’s behalf. To obtain service during the warranty period, return the product with proof of purchase to an authorized Meterman Test Tools Service Center or to a Meterman dealer or distributor. See Repair Section for details. THIS WARRANTY IS YOUR ONLY REMEDY. ALL OTHER WARRANTIES - WHETHER EXPRESS, IMPLIED OR STAUTORY - INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, ARE HEREBY DISCLAIMED. MANUFACTURER SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM ANY CAUSE OR THEORY. Since some states or countries do not allow the exclusion or limitation of an implied warranty or of incidental or consequential damages, this limitation of liability may not apply to you.
6
Repair
All test tools returned for warranty or non-warranty repair or for calibration should be accompanied by the following: your name, company’s name, address, telephone number, and proof of purchase. Additionally, please include a brief description of the problem or the service requested and include the test leads with the tester. Non-warranty repair or replacement charges should be remitted in the form of a check, a money order, credit card with expiration date, or a purchase order made payable to Meterman Test Tools.
In-Warranty Repairs and Replacement – All Countries
Please read the warranty statement, and check your batteries and fuses before requesting repair. During the warranty period any defective test tool can be returned to your Meterman Test Tools distributor for an exchange for the same or like product. Please check the “Where to Buy” section on www.metermantesttools.com for a list of distributors near you. Additionally, in the United States and Canada In-Warranty repair and replacement units can also be sent to a Meterman Test Tools Service Center (see below for address).
Non-Warranty Repairs and Replacement – US and Canada
Non-warranty repairs in the United States and Canada should be sent to a Meterman Test Tools Service Center. Call Meterman Test Tools or inquire at your point of purchase for current repair and replacement rates.
In USA In Canada
Meterman Test Tools Meterman Test Tools 1420 75th Street SW 400 Britannia Rd. E. Unit #1 Everett, WA 98203 Mississauga, ON L4Z 1X9 Tel: 888-993-5853 Tel: 905-890-7600 Fax: 425-446-6390 Fax: 905-890-6866
Non-Warranty Repairs and Replacement – Europe
European non-warranty units can be replaced by your Meterman Test Tools distributor for a nominal charge. Please check the “Where to Buy” section on www.metermantesttools.com for a list of distributors near you.
European Correspondence Address* Meterman Test Tools Europe P.O. Box 1186 5602 BD Eindhoven The Netherlands *(Correspondence only – no repair or replacement available from this address. European customers please contact your distributor.)
7
Specifications
General Specifications
Operating Environment: 0 °C to 40 °C at <80 % R.H. Power: Single standard 9 V battery, NEDA 1604, JIS 006P, IEC 6F22 Battery life: Approximately 200 hours typical with carbon-zinc battery Low battery indication: The BATT LED does not come ON when TEST button is
pressed
Dimensions: 153(L) x 72(W) x 35(D) mm. (6.02 x 2.83 x 1.37 in) Weight: Approximately 218 g (7 oz) including battery Enviroment: Indoor use Altitude: 2000 m (6561 ft.) Overload protection: 600 V ac Accessories: Test Leads (red, green, and blue) with alligator clips (TL-EPM3), Soft
Vinyl Case, Users Manual, Battery
Agency Approvals
P )s
Safety: Conforms to EN61010-1:2001; CAT III 600V, Pollution degree 2, Class 2; CSA 22.2 -1010-1, and EN61557-7
EMC: Conforms to EN61326-1. This product complies with requirements of the following European Community Directives: 89/ 336/ EEC (Electromagnetic Compatibility) and 73/ 23/ EEC (Low Voltage) as amended by 93/ 68/ EEC (CE Marking). However, electrical noise or intense electromagnetic fields in the vicinity of the equipment may disturb the measurement circuit. Measuring instruments will also respond to unwanted signals that may be present within the measurement circuit. Users should exercise care and take appropriate precautions to avoid misleading results when making measurements in the presence of electronic interference.
Electrical Specifications
Phase Sequence
Input Voltage: 3 phase to phase inputs - 100 V ac to 600 V ac max. Frequency: 45 to 70 Hz Operating time: 10 minutes ON maximum at 600 V ac. 10 minutes OFF minimum
at 600 V ac. 3-Phase load: Approx. 7 mA per phase of ac power source
Motor Rotation
Operating time: 10 minutes ON maximum. 10 minutes OFF minimum. Motor Rotation tester field: 14 mA of 9 V battery
8
L1
3Ø 115 VAC to 600VAC
L2
L3
M1
M2
BATT
TEST
M3
L
1
ABC
L2L
3
MOTOR ROTATION DETERMINED WHILE FACING MOTOR SHAFT
CAT
600
V
MOTOR
ROTATION
TESTER
3
-PHASE
TESTER
EPM
3
EPM
3
DO NOT CONNECT TO LIVE VOLTAGE!
Red
Green
Blue
Figure 1
9
M1
M2
BATT
TEST
M3
L
1
ABC
L2L
3
MOTOR ROTATION DETERMINED WHILE FACING MOTOR SHAFT
CAT
600
V
MOTOR
ROTATION
TESTER
3
-PHASE
TESTER
EPM
3
EPM
3
DO NOT CONNECT TO LIVE VOLTAGE!
M1
M2
M3
Red
Green
Blue
Figure 2
10
M1
M2
M3
L1
L2
L3
3Ø 115 VAC to 600VAC
Blue
Green
Red
Figure 3
Fuse
9 V Battery
Figure 4
EPM3
Contrôleur de rotation de moteur et d’ordre de phases
Mode d’emploi
(French)
Français
M1
M2
BATT
TEST
M3
L1
ABC
L2 L3
MOTOR ROTATION DETERMINED WHILE FACING MOTOR SHAFT
CAT
600
V
MOTOR
ROTATION
TESTER
3
-PHASE TESTER
EPM
3
EPM
3
DO NOT CONNECT TO LIVE VOLTAGE!
1
4
6
7
3
5
2
A
Bornes d’entrée de rotation de phase
B
Indicateurs de rupture de phase
C
Indicateurs de rotation de phase
D
Interrupteur marche/arrêt du vérificateur de moteur
E
Témoin d’alimentation du vérificateur de moteur
F
Indicateurs de rotation de moteur
G
Bornes d’entrée de rotation de moteur
1
Contrôleur de rotation du moteur et d’ordre de
phases EPM3
Sommaire
Consignes de sécurité.........................................................................................2
Symboles utilisés dans ce mode d’emploi .......................................................2
Introduction ........................................................................................................3
Mesures..............................................................................................................3
Test de rotation triphasé ..................................................................................3
Test de rupture de phase .................................................................................4
Test de rotation du moteur ..............................................................................4
Entretien .............................................................................................................5
Remplacement des fusibles et des piles ..........................................................5
Nettoyage et stockage......................................................................................5
Limites de garantie et de responsabilité..............................................................5
Réparation ..........................................................................................................6
Caractéristiques ..................................................................................................7
Caractéristiques générales ...............................................................................7
Caractéristiques électriques .............................................................................7
2
Consignes de sécurité
Le contrôleur de rotation de moteur et de séquence de phase EPM3 est conforme aux normes CSA 22.2 -1010-1 et EN61010-1, CAT III 600 V.
Pour un fonctionnement et une utilisation sans danger de cet appareil, suivez les instructions de ce mode d’emploi. Le non-respect des mises en garde peut entraîner des blessures GRAVES, voire la mort.
Il est recommandé pour les installations fixes et au niveau distribution, ainsi que pour les installations secondaires, mais non pour les lignes d’alimentation primaires, les lignes aériennes et les systèmes câblés.
Ne pas dépasser les limites de surcharge maximum par fonction (voir les caractéristiques techniques) ou les limites indiquées sur l’appareil lui-même. Ne jamais appliquer plus de 600 V c.a. eff. entre le cordon de mesure et la prise de terre.
Inspecter le contrôleur, les cordons de mesure et les accessoires avant chaque utilisation. Ne pas utiliser de pièce endommagée.
Ne jamais se relier à la terre en prenant des mesures. Ne toucher ni aux éléments de circuit exposés ni aux pointes des sondes de test.
Ne pas utiliser l’appareil dans une atmosphère explosive.
Faire preuve d’extrême prudence en : mesurant une tension >20 V // un courant
>10 mA // les lignes d’alimentation secteur avec charges inductives // les lignes d’alimentation secteur pendant les orages électriques // un courant alors que le fusible a sauté dans un circuit avec une tension en circuit ouvert > 600 V.
Ne jamais installer un fusible de calibre différent.
Retirer les cordons de mesure avant d’ouvrir le boîtier.
Cet appareil doit être utilisé selon les conditions spécifiées afin de ne pas
entraver sa protection intrinsèque.
Symboles utilisés dans ce mode d’emploi
X Tension dangereuse W Se reporter au mode d’emploi
T Double isolation B Courant alternatif F Courant continu J Prise de terre
P
Conforme aux directives de l’UE
)
Association canadienne de normalisation (CSA)
s
Conforme à la norme TÜV
3
Introduction
Le contrôleur propose trois fonctions dans un appareil compact, notamment l’indication de rupture de phase, de succession des phases et de rotation de moteur. Ce contrôleur est idéal pour l’installation des tapis transporteurs, des systèmes de pompage et des commandes interconnectées.
L’EPM3 se compose de deux modules de mesure. L’un mesure l’ordre des phases d’un système trifilaire en utilisant l’alimentation du système testé. Il indique grâce à des témoins lumineux la séquence triphasée ou une situation de rupture de phase. L’autre module de l’EPM3 mesure la rotation du moteur triphasé sur un moteur au repos en utilisant la pile interne de 9 volts de l’EPM3. L’appareil indique alors si l’arbre moteur tourne dans le sens de rotation horaire ou anti-horaire.
Fonctions :
Identifie la séquence triphasée et le contrôle de rupture de phase
Rotation de l’arbre moteur
Alimenté sur pile
Conforme aux exigences EN61010 sur la sécurité
Fourni avec trois grandes pinces crocodiles homologuées CAT III et des
cordons de mesure repérés par couleur
XWAttention
Lire toutes les consignes de sécurité avant d’utiliser ce contrôleur.
Mesures
Test de rotation triphasé
XWAttention
Cet instrument indique uni quement la présence d’une tension, et non pas son niveau. Vérifier la tension réelle à l’aide d’un multimètre. L’utilisation d’une tension erronée peut endommager le moteur.
1. Branchez les trois cordons de mesure repérés par couleur aux bornes d’entrées
triphasées, L1 (rouge) - L2 (vert) - L3 (bleu) aussi appelées A-B-C ou R-S-T. Voir Figure 1.
2. Branchez les trois pinces crocodiles repérées par couleur aux bornes d’une
source d’alimentation triphasée. L’ordre de branchement est facultatif. Faire preuve d’extrême prudence dans cette situation de tension élevée.
3. Confirmez que les trois témoins en dessous des entrées des cordons de
mesure sur l’EPM3 sont allumés. L’extinction d’un ou de plusieurs témoins signale une condition de rupture de phase. Corrigez les problèmes de la source d’alimentation avant de poursuivre (voir Test de rupture de phase dans la suite de ce manuel). Si les tests de rupture de phase sont corrects, l’EPM3 est défectueux. Réparez ou remplacez l’EPM3 avant de poursuivre.
4. Si les trois témoins sont allumés, vérifiez le sens de rotation en consultant
l’indicateur de rotation de phase : sens horaire (w) ou anti-horaire (x).
5. Si le témoin de directio n anti-horaire est allumé, inversez les branchements de
deux des trois pinces crocodiles pour obtenir une rotation en sens horaire. Faire preuve d’extrême prudence dans cette situation de tension élevée.
6. L’ordre des phases est correct en rotation horaire (w) lorsque le témoin de
rotation horaire est allumé et que les bornes de la source d’alimentation sont connectées par les pinces crocodiles ROUGE, VERT et BLEU en L1, L2 et L3. Coupez l’alimentation et identifiez les fils de la source d’alimentation.
4
Test de rupture de phase
XWAttention
Le multimètre utilisé pour ce test doit être correctement homologué pour le circuit testé.
1. Branchez l’entrée V d’un multimètre (réglé sur VAC et la gamme de tension attendue) au fil de phase voulu, et l’entrée COM à neutre ou à la terre pour vérifier la tension de phase. Faire preuve d’extrême prudence dans cette situation de tension élevée.
2. Vérifiez si les deux autres phases fonctionnent correctement et si les tensions triphasées à phase sont correctes. Si un problème est détecté, corrigez-le avant de revenir au test de rotation triphasé.
Test de rotation du moteur
Ce test permet notamment de vérifier les branchements M1-M2-M3 et la rotation de l’arbre, ou de vérifier les branchements M1-M2-M3 sur un moteur qui n’est pas marqué.
XWAvertissement
Établir tous les branchements avec les circuits non alimentés. Si l’indicateur ROUGE de rotation horaire ou anti-horaire est allumé avant la rotation de l’arbre moteur, une tension est présente. Arrêter la mesure. Retirer les cordons de mesure et mettre l’alimentation externe hors tension.
1. Utilisez un multimètre pour vérifier si aucune tension n’est présente sur les enroulements du moteur.
2. Branchez les cordons de mesure repérés par couleur aux trois bornes d’entrée M1-M2-M3 du moteur. Appuyez sur le bouton marche/arrêt (voir Figure 2). Le témoin vert s’allume.
3. En étant face à l’arbre, faites tourner à la main l’arbre moteur dans le sens horaire.
4. Si l’indicateur de rotation horaire (w) est allumé, les branchements M1-M2­M3 sont corrects pour une rotation en sens horaire.
5. Si l’indicateur de rotation anti-horaire (w) est allumé, les branchements M1-M2-M3 sont corrects pour une rotation en sens anti-horaire.
6. Si le sens de rotation du moteur est incorrect, inversez deux des branchements M1-M2-M3 et recommencez le test.
Après avoir vérifié la rotation triphasée et les phases du moteur :
1. Mettez le circuit hors tension à la source.
2. Reliez le fil d’alimentation L1 identifié plus haut au fil du moteur M1. Répétez les branchements pour L2 à M2 et L3 à M3. Voir la figure 3.
3. Inspectez les branchements pour la sécurité en électricité. Le moteur tourne dans le sens souhaité lorsque l’alimentation est appliquée.