Metal-Fach ecoMAX860P TOUCH Operating Manual

Page 1
APPLIES TO SOFTWARE:
MODULE A
PANEL
v01.XX.XX
v.01.XX.XX
ecoSTER TOUCH**
ecoNET300**
functions available in the additional module B
** room panel ecoSTER TOUCH and internet module ecoNET300 - not the standard equipment of the controller.
02-2017
ecoNET.apk
www.econet24.com
Boiler controller
ecoMAX860P TOUCH
FOR AUTOMATIC SOLID FUEL FIRED BOILERS WITH INGITION (GUTTER AND RETORT FEEDERS), execution: ecoMAX920P1-T
ISSUE: 1.0
Page 2
Page 3
TABLE OF CONTENTS
1 SAFETY REQUIREMENTS ..................................... 4
2 GENERAL INFORMATION .................................... 5
3 INFORMATION ABOUT DOCUMENTATION ......... 5
4 STORAGE OF DOCUMENTATION ......................... 5
5 APPLIED SYMBOLS .............................................. 5
6 DIRECTIVE WEEE 2012/19/UE ............................. 5
INSTRUCTION MANUAL ............................................... 7
7 STRUCTURE – MAIN MENU ................................. 8
8 OPERATING THE REGULATOR ............................. 9
8.1 DESCRIPTION OF DISPLAY MAIN WINDOW ................. 9
8.2 SWITCHING ON/OFF THE BOILER............................ 10
8.3 SETTINGS PRESET TEMPERATURE ..................... 10
8.4 FIRING UP ...................................................... 10
8.5 OPERATION ....................................................... 10
8.6 REGULATION MODE .......................................... 10
8.7 SUPERVISION ................................................ 11
8.8 BURNING OFF ................................................ 11
8.9 STANDSTILL ................................................... 11
8.10 DOMESTIC HOT WATER SETTINGS HUW ................. 11
8.11 SETTING HUW PRESET TEMPERATURE................... 12
8.12 HUW CONTAINER HYSTERESIS .............................. 12
8.13 HUW CIRCULATION ........................................... 12
8.14 ENABLING THE SUMMER FUNCTION .................... 12
8.15 DISINFECTION HUW CONTAINER .......................... 12
8.16 MIXER CIRCUITS SETTINGS ................................... 12
8.17 WEATHER CONTROLLED ...................................... 13
8.18 DESCRIPTION OF NIGHT TIME DECREASE SETTINGS .... 14
8.19 FUEL LEVEL SETUP .............................................. 15
8.20 INFORMATION ................................................... 15
8.21 MANUAL CONTROL ............................................ 15
8.22 GRATE ............................................................. 15
8.23 FAVOURITE MENU .............................................. 16
8.24 ROOM PANEL ECOSTER TOUCH .......................... 16
8.25 INTERNET MODULE ............................................. 16
INSTALLATION AND SERVICE SETTINGS ..................... 17
9 HYDRAULIC DIAGRAMS ..................................... 18
10 TECHNICAL DATA .............................................. 21
11 STORAGE AND TRANSPORT CONDITIONS ......... 21
12 REGULATOR INSTALLATION .............................. 21
12.1 ENVIRONMENTAL CONDITIONS ............................. 21
12.2 MOUNTING REQUIREMENTS ................................. 21
12.3 MODULE INSTALLATION ...................................... 21
12.4 IP PROTECTION RATE .......................................... 22
12.5 ELECTRIC CONNECTION ........................................ 22
12.6 CONNECTION OF TEMPERATURE SENSORS ............... 26
12.7 CONNECTING WEATHER SENSOR ........................... 26
12.8 CONNECTING EXHAUST SENSOR ............................ 26
12.9 CHECKING TEMPERATURE SENSORS ........................ 27
12.10 CONNECTION OF MIXERS ROOM THERMOSTAT ......... 27
12.11 CONNECTION OF BOILER'S ROOM THERMOSTAT ....... 28
12.12 CONNECTION OF RESERVE BOILER .......................... 28
12.13 CONNECTION OF ALARM SIGNALING ....................... 29
12.14 CONNECTION OF MIXER ....................................... 30
12.15 CONNECTING TEMPERATURE LIMITER STB .............. 30
12.16 DS INPUT ......................................................... 30
12.17 CONNECTING ROOM PANEL .................................. 30
12.18 SOFTWARE UPDATE ............................................ 31
13 SERVICE MENU .................................................. 32
14 SERVICE SETTINGS............................................. 34
14.1 BURNER ......................................................... 34
14.2 BOILER ........................................................... 35
14.3 CH AND HUW .................................................. 36
14.4 BUFFER .......................................................... 37
14.5 MIXER ............................................................ 37
14.6 OTHER PARAMETRES ..................................... 38
15 ALARM DESCRIPTION ........................................ 40
15.1 MAX. BOILER TEMP. EXCESS .................................. 40
15.2 EXCEEDING MAX. FEEDER TEMPERATURE ................. 40
15.3 FAULTY FUEL FEEDING SYSTEM .............................. 40
15.4 BOILER TEMP. SENSOR DAMAGED .......................... 40
15.5 FEEDER TEMP. SENSOR DAMAGED .......................... 40
15.6 EXHAUST SENSOR TEMP. DAMAGED ....................... 40
15.7 UNSUCCESSFUL FIRING UP ATTEMPT ....................... 41
15.8 EXHAUST TEMPERATURE NOT MET. CHECK FUEL QUALITY
....................................................................... 41
15.9 BOILER OVERHEATING STB, OPEN CONTACT............. 41
15.10 MAX EXHAUST TEMPERATURE EXCEEDED. SENSOR
DAMAGE DANGER! .............................................. 41
15.11 NO COMMUNICATION ......................................... 41
15.12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING ......... 41
15.13 NO POWER SUPPLY ............................................. 41
15.14 FAN OR FAN SPEED SENSOR DAMAGED .................... 41
16 ADDITIONAL FUNCTIONS................................... 42
16.1 POWER SUPPLY DECAY ......................................... 42
16.2 ANTI-FREEZING PROTECTION ................................. 42
16.3 FUNCTION OF PROTECTING PUMPS AGAINST
STAGNATION ..................................................... 42
16.4 FEEDER BUNKER ................................................. 42
17 REPLACEMENT OF PARTS AND COMPONENTS . 42
17.1 REPLACEMENT OF MAINS FUSE .............................. 42
17.2 REPLACEMENT OF CONTROL PANEL ........................ 42
17.3 LAMBDA SENSOR ................................................ 42
Page 4
1 Safety requirements
Requirements concerning safety are described in detail in individual chapters of this manual. Apart from them, the following requirements should in particular be observed.
flammable dusts or liquids can cause fire or explosion. Thus, the regulator should be separated from flammable dusts and gases, e.g. by means of an appropriate body.
The regulator must be installed by a
boiler manufacturer in accordance with the applicable safety standards.
Before starting assembly, repairs or
maintenance, as well as during any connection works, please make sure that the mains power supply is disconnected and that terminals and electric wires are devoid of voltage.
After the regulator is turned off using
the keyboard, dangerous voltage still can occur on its terminals. The regulator cannot be misused.
The regulator is designed to be
enclosed.
Additional automatics which protect
the boiler, central heating (CH) system, and domestic hot water system against results of malfunction of the regulator, or of errors in its software, should be applied.
Choose the value of the programmed
parameters accordingly to the given type of boiler and fuel, taking into consideration all the operational conditions of the system. Incorrect selection of the parameters can cause malfunction of the boiler (e.g. overheating of the boiler, the flame going back to the fuel feeder, etc.),
The programmed parameters should
only be altered by a person familiarized with this manual.
The device should only be used in
heating systems in accordance with the applicable regulations.
The electric system in which the
regulator operates must be protected by means of a fuse, selected appropriately to the applied loads.
The regulator cannot be used if its
casing is damaged.
In no circumstances can the design of
the regulator be modified.
In the regulator there is applied
electronic disconnection of connected devices (2Y type of operation according to PN-EN 60730-1) as well as micro-disconnection (2B type of operation according to PN-EN 60730-
1).
Keep the regulator out of reach of
children.
The regulator is intended for boiler
manufacturers. Before applying the regulator, a boiler manufacturer should check if the regulator’s mating with the given boiler type is proper, and whether it can cause danger.
The regulator is not an intrinsically
safe device, which means that in the case of malfunction it can be the source of a spark or high temperature, which in the presence of
4
Page 5
2 General information
Boiler regulator ecoMAX860P TOUCH is a modern electronic device intended to control boiler operation with automatic feeding of solid fuel and with the ignitors. Flame is detected via the exhaust temperature sensor. The regulator is a multipurpose device:
it automatically maintains a preset boiler
temperature by controlling the fuel combustion process,
it controls timing fuel feeder and fan
(modulating its power),
it automatically stabilizes a preset
temperature of the domestic hot water container,
it automatically maintains preset
temperature of several independent
mixer heating cycles. The preset temperature of heating cycles and the boiler can be set on the basis of a weather sensor readouts. The device includes the control panel with horizontal regulation of its position, the main operating unit and optional modules to control additional heating circuits. The regulator can cooperate with an additional room panel ecoSTER TOUCH situated in living quarters and module for the web WiFi ecoNET300. It can be used in a household and similar facilities, as well as in lightly industrialized facilities.
3 Information about documentation
The regulator manual is a supplement for the boiler manual. In particular, except for this manual, the boiler manual should also be observed. The regulator manual is divided into two parts: for user and fitter. Yet, both parts contain important information, significant for safety issues, hence the user should read both parts of the manual. We are not responsible for any damages caused by failure to observe these instructions.
4 Storage of documentation
This assembly and operation manual, as well as any other applicable documentation, should be stored diligently, so that it was
available at any time. In the case of removal or sale of the device, the attached documentation should be handed over to the new user / owner.
5 Applied symbols
In this manual the following graphic symbols are used:
- useful information and tips,
- important information, failure to observe these can cause damage of property, threat for human and household animal health and life.
Caution: the symbols indicate important information, in order to make the manual more lucid. Yet, this does not exempt the user from the obligation to comply with requirements which are not marked with a graphic symbol.
6 Directive WEEE 2012/19/UE
Act on electrical and electronic equipment.
Recycle the product and the packaging at
the end of the operational use period in an appropriate manner.
Do not dispose of the product together
with normal waste.
Do not burn the product.
5
Page 6
6
Page 7
INSTRUCTION MANUAL
ecoMAX 860P TOUCH
Page 8
7 STRUCTURE – MAIN MENU
Boiler settings
Preset boiler temperature
Weather control the boiler*
Boiler heating curve*
Curve shift*
Room temperature factor*
Output modulation
 Max. boiler output  100%% Blowing power  100%% Blow-in  100% Oxygen*  50% Hysteresis H2  Boiler medium power  50% Blowing power  50% Blow-in  50% Oxygene*  30% Hysteresis H1  Minimum boiler output  30% Blowing power  30% Blow-in  30% Oxygene*  Blow firing grate*  Boiler hysteresis  Feeding correction  Minimum boiler output FL  Maximum boiler output FL
Heat source
Burner
Grate
Reserve boiler*
Regulation mode:
Standard
FuzzyLogic
Max kW
Avg kW
Min kW
Fuel selection
Fuel level
Alarm level  Calibration of fuel level
Lambda sonde calibration*
Scheduled
On
Reduction value
Schedule
HUW settings
HUW preset temperature
HUW pump mode
Off Priority No priority
HUW container hysteresis
HUW disinfection
Schedule - HUW
On [No/Yes]
Reduction value
Schedule
Schedule - circulation pump*
Mixer 1-4 settings*
Preset mixer temperature
Mixer room thermostat
Mixer weather control*
Heating curve mixer*
Curve translation*
Room temperature factor*
Schedule
On [No/Yes]
Reduction value
Schedule
Summer/Winter
SUMMER mode
Winter
Summer
Auto*
SUMMER mode act. temperature
SUMMER mode deact. temperature
General settings
Clock
Date
Screen brightness
Sound
Language
Software update*
WiFi settings*
Main menu
Information
Boiler settings
HUW settings*
Summer/Winter
Mixer 1-4 settings*
General settings
Manual control
Alarms
Services settings
* unavailable if no adequate sensor or additional module is connected or the parameter is hidden.
8
Page 9
8 Operating the regulator
Both, left and right window may display different information. By touching the screen, user may navigate between displayed information: mixer circuits information window, HUW window, fuel level window.
OPERATION
THU
8.1 Description of display main window
1. mode of regulator operation: FIRING UP,
OPERATION, SUPERVISION BURNING OFF, STANDSTILL
2. preset boiler temperature
3. measured boiler temperature
4. key to enter ’’Menu” list
5. Information field:
- increase of preset boiler temperature
for the time of HUW container filling,
- increase of preset boiler temperature
by mixer circuit,
fan
feeder
pumps
igniter
6. measured temperature of HUW container
7. preset temperature of HUW container
8. clock time and weekday
9. outside temperature (weather)
10. field of functions, which modify preset temperature -meaning of the symbols:
- opening of room thermostat contacts – preset room temperature has been reached,
- of preset boiler temperature for
active time intervals,
- increase of preset temperature for
buffer loading,
- operation mode – grate,
- work on the reserve boiler (gas- or oil­).
Fuel level may be displayed on ecoSTER TOUCH room control panel.
9
Page 10
8.2 Switching on/off the boiler
Make sure fuel is present in the tank and tank hatch is closed. Now boiler may be switched on. To start the boiler - press BURNER OFF? at any place on the screen. The message: Active regulator? appears.
Confirm the message. Boiler enters firing-up stage. There is also another method of boiler start­up. Press MENU button and find and press
If firing up the furnace fails, further attempts are carried. Consecutive attempts are visualised by numbers next to the lighter
symbol . After three unsuccessful attempts, an alarm Failed firing up attempt is reported. In such case, the boiler operation is halted. Boiler operation cannot be continued automatically
- service crew must intervene. After removing causes of impossibility to fire up, the boiler must be restarted.
8.5 OPERATION
The fan operates continuously. Fuel feeder is activated cyclically. A cycle consists of feeder operation time and duration of feeding interval Parameters related with the Operation mode are: Feeder operation time and Fan output in:
Boiler settings Output modulation
button in pie menu.
To stop the boiler - press MENU button, and
find and press button in pie menu.
8.3 Settings preset temperature
Preset boiler temperature or preset HUW temperature, just like the preset mixer circuit temperature, can be set in the menu:
Boiler settings Preset boiler temp. HUW settings HUW preset temp. Mixer 1-4 settings Preset mixer temp.
The value set as Preset boiler temp. is ignored by the regulator if the preset boiler temperature is controlled by weather sensor. Regardless of that, the preset boiler temperature is automatically increased in order to fill the hot utility water tank and feed heating mixer cycles.
8.4 FIRING UP
The FIRING UP mode is used for automatic firing up of furnace in the boiler. All parameters which influence the firing-up process can be found in menu:
Service settings Burner settings Firing up
8.6 Regulation mode
There are two regulation modes for stabilizing the set temperature of the boiler: Standard and FuzzyLogic
Boiler settings Regulation mode
Operating in Standard Mode
When the boiler temperature reaches its set value, the regulator switches to SUPERVISION mode. The regulator has a boiler output modulation mechanism allowing it to gradually reduce the output as the boiler temperature nears its set value Three boiler output levels can be set: maximum, medium, and minimum. Each level can be additionally adjusted with individual fuel feeding times and fan speeds, affecting the actual output of the boiler. The output level parameters are accessible through the menu Boiler Settings Output modulation. The regulator sets the current output of the burner depending on the set temperature of the boiler and H1 and H2 hysteresis settings It is possible to set the H1 and H2 values to modulate the output withouth the medium power stage, ie. reducing output from 100%
10
Page 11
to 30%, skipping the 50% output (right side
Note: If only the HUW is heated (summer mode), it is recommended to set the regulator to Standard mode.
Parameters should be so selected that the boiler temperature in this mode gradually drops. Incorrect settings may lead to boiler overheating.
For the setting Supervision time = 0, the regulator skips the SUPERVISION mode and enters the BURNING-OFF mode.
When the Supervision time = 255, the regulator will work continuously in SUPERVISION mode, until the boiler temperature decreases and it automatically switches to OPERATION mode.
Power levels
Power levels
Preset
temperature T=85°C
Preset
temperature T=85°C
of the figure below).
Operating in FuzzyLogic mode
In FuzzyLogic mode, the regulator automatically sets the output of the burner in order to maintain the set boiler temperature. The regulator uses the output settings predefined in Standard mode. This mode does not require setting the H1 and H2 hysteresis.
When the supervision time expires, the regulator switches to BURNING OFF mode, unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode.
8.8 BURNING OFF
The extinguishing process does not occur when coal is the fuel of choice. When pellets are the fuel, they are burned off for several minutes (depending on the set time). After BURNING OFF, the regulator switches to STANDSTILL.
After the set temperature is exceeded by 5ºC, the boiler switches to SUPERVISION mode.
8.7 SUPERVISION
In SUPERVISION mode, the fan and the feeder are switched on cyclicall at larger intervals than in OPERATION mode. This is to prevent the fire from being extinguished. Supervision parameters can be found in menu:
Service Settings Burner Settings Supervision
SUPERVISION parameters should be set in accordance with the recommendations of the boiler or burner manufacturer. The parameters should be adjusted to prevent the furnace from extinguishing during intervals.
8.9 STANDSTILL
In the STANDSTILL mode, the boiler is put out and awaits signal to resume heating. A signal to start heating can be: decrease in preset boiler temperature
below the preset temperature minus the value of boiler hysteresis Boiler hysteresis,
if the boiler is set to work with a buffer -
decrease in upper buffer temperature below the preset value Buffer loading start temperature.
8.10 Domestic hot water settings
HUW
The device controls temperature of the domestic how water - HUW – tank, provided that a HUW temperature sensor is connected. If the sensor is disconnected, an information about lack thereof is displayed in the main window. The parameter:
Menu HUW settings HUW pump mode allows the user to:
disable filling of the tank, parameter Off,
11
Page 12
set HUW priority, using the Priority
After setting a low hysteresis value, HUW pump will run faster when HUW temperature falls.
In Summer mode, all heat receivers may be shut off, so before enabling it please make sure that the boiler does not overheat.
Keep the tenants informed of activating the disinfection function as there is risk of being burnt with hot usable water.
parameter - in this case, the CH pump is deactivated to speed up filling of the HUW tank.
set simultaneous operation of the CH and
HUW pump, using parameter No priority.
8.11 Setting HUW preset
temperature
Preset HUW temperature is defined by parameter:
HUW settings HUW preset temp.
8.12 HUW container hysteresis
Below HUW preset temp. – HUW container hysteresis starts HUW pump to load the HUW
container.
8.13 HUW circulation
The settings can be found in:
HUW Settings Schedule - circulation pumps
and
Service settings CH and HUW settings
Setting of circulating pump control is analogical to night decrease setting. Circulating pump switches on in selected time intervals. In disregarded time intervals circulating pump will start and remain in operation for the period of time set in Circulating pump operation time , then will stop and remain out of operation for the period of time set in Circulating pump standstill time.
8.14 Enabling the SUMMER function
In order to activate the SUMMER function, which enables to load the HUW tank in the summer, without the need for activating the CH system and mixer cycles, set the parameter SUMMER mode to Summer.
Summer/Winter SUMMER mode
If the weather sensor is connected SUMMER function can be activated automatically with the Auto parameter including settings for
SUMMER mode act. temperature, SUMMER mode deact. temperature.
8.15 Disinfection HUW container
The regulator has a function of automatic, periodic heating of HUW container to 70°C to eliminate bacterial flora from the HUW container.
The regulator increases the HUW container temperature once a week, at 2:00 a.m. Monday. After 10 minutes of maintaining the
temperature at 70°C, the HUW pump is
switched off and the boiler returns to normal operation. Do not activate the disinfection function when the HUW support is off.
8.16 Mixer circuits settings
Settings for the first mixer circuit can be found in the menu: Mixer 1 settings Settings for other mixers can be accessed in next menu items and they are identical for each circuit.
Settings for mixer without weather sensor
It is necessary to manually set the required water temperature in the heating mixer circuit using parameter Preset mixer temp.,
e.g. at a value of 50°C. The value should
allow to obtain the required room temperature. After connecting room thermostat, it is necessary to set a value of decrease in preset mixer temperature by thermostat (parameters Mixer room therm.) e.g. at 5°C. This value should be selected by trial and error. The room thermostat can be a traditional thermostat (NO-NC), or room panel ecoSTER TOUCH. Upon activation of the thermostat, the preset mixer circuit temperature will be decreased, which, if proper decrease value is selected, will stop growth of temperature in the heated room.
12
Page 13
Settings for mixer with weather sensor without room thermostat ecoSTER TOUCH
Set parameter Mixer weather control to On. Select weather curve. Using parameter Curve translation, set preset room temperature following the formula:
Preset room temperature = 20°C + heating
curve translation. In this setup, it is possible to connect a room thermostat which will equalize the inaccuracy of selecting heating curve, if the selected heating curve value is too high. In such case, it is necessary to set the value of preset mixer temperature decrease by thermostat, e.g. at 2°C. After opening of the thermostat contacts, the preset mixer circuit temperature will be decreased, which, if proper decrease value is selected, will stop growth of temperature in the heated room.
Settings for mixer with weather sensor and with room thermostat
Set parameter Mixer weather control to On. Select weather curve. The room panel automatically translates the heating curve, depending on the preset room temperature. The regulator relates the setting to 20°C, e.g. for preset room temperature = 22°C, the regulator will translate the heating curve
by 2°C, for preset room temperature = 18°C,
the regulator will translate the heating curve by -2°C. In some cases it may be necessary to fine-tune the heating curve translation. In this setup, the ecoSTER TOUCH room thermostat can:
- decrease the heating cycle temperature by a constant value when the preset room temperature is reached. Analogously, as specified in the previous point (not recommended), or
- automatically, continuously correct the heating cycle temperature. It is not recommended to use both options at the same time. Automatic correction of room temperature is carried out in accordance with the following formula: Correction = (Preset room temperature ­measured room temperature) x room temperature coefficient /10
Example: Preset temperature in the heated room (set at ecoSTER TOUCH) = 22°C. Temperature measured in the room (by ecoSTER TOUCH) = 20°C. Room temp. factor. = 15. Preset mixer temperature will be increased by (22°C - 20°C) x 15/10 = 3°C. It is necessary to find appropriate value of the Room temp. factor. The higher the coefficient, the greater the correction of preset boiler temperature. If the setting is
“0”, the preset mixer temperature is not
corrected. Note: setting a value of the room temperature coefficient too high may cause cyclical fluctuations of the room temperature!
8.17 Weather controlled
Depending on the temperature measured outside the building, both preset boiler temperature and temperatures of mixer circuits can be controlled automatically. If proper heating curve is selected, the temperature of the circuits is calculated automatically, depending on the outdoor temperature. Thus, if the selected heating curve is appropriate for the given building, the room temperature stays more or less the same, regardless of the temperature outside. Note: during trial and error selection of appropriate heating curve, it is necessary to exclude influence of the room thermostat on regulator operation (regardless of whether the room thermostat is connected or not), by setting the parameter:
Mixer 1 settings Mixer room therm. =
0. If a room panel ecoSTER TOUCH is connected, it is also necessary to set the parameter Room temperature factor = 0.
Guidelines for proper setting of the heating curve:
floor heating 0,2 -0,6 radiator heating 1,0 - 1,6 boiler 1,8 - 4
13
Page 14
Guidelines for selection of appropriate
Note! Setting of time intervals for 24 hours (one day) should start from 00:00!
heating curve:
- if the outdoor temperature drops, and the room temperature increases, the selected heating curve value is too high,
- if the outdoor temperature drops, and the room temperature drops as well, the selected heating curve value is too low,
- if during frosty weather the room temperature is proper, but when it gets warmer - it is too low, it is recommended to increase the Curve translation and to select a lower heating curve,
- if during frosty weather the room temperature is too low, and when it gets warmer - it is too high, it is recommended to decrease the Curve translation and to select a higher heating curve. Buildings with poor thermal insulation require higher heating curves, whereas for buildings which have good thermal insulation, the heating curve can have lower value. The regulator can increase or decrease the preset temperature, calculated in accordance with the heating curve, if it exceeds the temperature range for the given circuit.
8.18 Description of night time decrease
settings
Night time decreases for boiler, heating circuits, HUW container and circulation pump operation.
The intervals can be used to define time periods at which lower preset temperature may be set e.g. for a night time or when the user is not at home. This feature enables automatic reduction of preset temperature without compromising the heat comfort and reduces fuel consumption. Decrease of preset temperature in selected time intervals is indicated by the symbol:
on the main screen. To activate time intervals, set the parameter Schedule for boiler or for the given heating circuit to ON. The parameter Reduction value set the temperature reduction, one for all time intervals. Night time decreases can be defined separately for every day of the week set Schedule. The example of night time decrease of preset temperature from 22:00 to 06:00 next day and from 09:00 to 15:00 is given below.
In the given example, the regulator will set
the decrease of preset temperature by 3°C
from 00:00 to 06:00, and will keep the preset value (without the decrease) from 06:00 to 09:00. Then, it will set the decrease by 5°C from 09:00 to 15:00, and will keep the preset value (without the decrease) again from 15:00 to 22:00; and again will
14
Page 15
set the decrease by 3°C from 22:00 to
Time interval is disregarded when its decrease is set to "0" even though "from... to ..." values have been entered.
Upon connection of mixers' extension module, information windows of additional mixers are displayed.
Note: Access to manual control menu is possible only in the STAND­BY mode, i.e. when the boiler is OFF.
Note: Long-term operation of the fan, the feeder or other working equipment may lead to occurrence of hazardous conditions.
23:59.
8.19 Fuel level setup
Activating the fuel level gauge
In order to enable display of the fuel level, set value of parameter
Boiler settings Fuel level Alarm level
to a value greater than zero, e.g. 10%. By pressing the right or left box in the main window you can select the fuel level indicator. Fuel level can also be displayed on the ecoSTER TOUCH room panel.
Operation of fuel level indicator Any time upon filling fuel tank, press and hold pressed current fuel level value. Following prompt appears:
perform level calibration. No additional fuel level sensors are required.
Calibration To perform calibration - fill the fuel tank to the level corresponding to its full load and set the parameter:
Boiler settings Fuel Level Fuel level calibration Fuel Level 100%
The indicator in the main window will be set to 100%. On-going calibration process is signalled by flashing fuel level gauge. The gauge will flash until the time of marking the point corresponding to minimal fuel level. One must systematically control the decreasing level of fuel in the bin. When the level reaches the requested minimum, set the value of the parameter:
Boiler settings Fuel Level Fuel level calibration Fuel Level 0%
Calibration can be skipped if the Feeder Efficiency and Tank capacity, parameters are
set correctly in: Menu → Service settings Burner settings Operation
"Set fuel level at 100% Once selected and confirmed YES, fuel level is set at 100%. Once selected and confirmed YES, fuel level is set to 100%. Note: Fuel may be replenished at any time without a need to wait for complete empty fuel tank. Replenish fuel always to the level corresponding to 100% level of the fuel tank and set 100% level as described above.
Description of operation The regulator calculates the fuel level basing on the current fuel consumption. Default settings do not always correspond to the actual consumption of fuel by the given boiler, therefore, for proper operation this method requires the regulator user to
8.20 Information
Information" menu allows to preview temperatures being measured and to recognize which equipment is currently ON.
8.21 Manual control
Regulator offers possibility to manual start of working equipment such as pump, feeder motor or fan. This feature enables checking whether the given equipment is fault-free and properly connected
8.22 Grate
15
Page 16
The regulator is able to work with a Grate,
Changing modes between grate and burner can be done via the ecoNET internet module, but only after all the manually loaded fuel is burned off. In order to change modes, turn the regulator off and on by clicking
“Work mode” in the “Current information” tab.
where the fuel is loaded manually. The feeder is switched off, but the fan is operational. You can switch between Burner and Grate modes in:
Boiler settings Heat source
Fan speeds are regulated in:
Boiler settings Output modulation
Fan speed settings are different for the grate than for the burner. Other parameters are set in the service settings.
8.23 Favourite menu
In Touch version in the menu bar at the bottom of the screen there is a button:
. Upon activation of this key, a quick selection menu appears. To add new item to this menu - hold respective icon pressed in pie menu for a while. To remove selected item from favourite menu - hold corresponding icon pressed and confirm REMOVE.
8.24 Room panel ecoSTER TOUCH
The controller can work together with ecoSTER TOUCH remote control device, which have a built-in room thermostat. This room panel shows useful information such as: fuel level, alarm indication etc.
8.25 Internet module
The controller can work together with ecoNET300 internet module. It enables online control and supervision over the
controller for the help of the website www.econet24.com. You can use the convenient mobile application ecoNET.apk. Mobile application can be downloaded free of charge from the website:
16
Page 17
INSTALLATION AND SERVICE SETTINGS
ecoMAX 860P TOUCH
Page 18
9 Hydraulic diagrams
The presented hydraulic diagram does not replace central heating engineering design and may be used for information purposes only.
In order for the valve (6) to be able to effectively increase the return water temperature, set a high set temperature of the boiler. In order to improve the water circulation in natural systems (highlighted circuit in the figure): use large nominal diameter pipes and four-way valve, avoid unnecessary angles and reductions, maintain a min. 2° horizontal pipe slope, etc. If the sensor (3) is attached to the pipe, isolate it with foam surrounding the pipe and sensor.
Parameter
Setting
MENU
Preset boiler temperature
75-80C
menuBoiler settings
Min. preset boiler temperature
65C
menuService settings Boiler settings
Increasing of preset boiler temp.
5-20C
menuService settings CH and HUW settings
Mixer 1 support
CH ON
menuService settingsMixer 1 settings
Maxer 1 preset temperature
70C
menuService settingsMixer 1 settings
Mixer 1 heating curve
0.8 – 1.4
menuMixer 1 settings
Mixer 1 weather control
ON
menuMixer 1 settings
Mixer 1 thermostat selection
ecoSTER T1
menuService settingsMixer 1 settings
Diagram with 4-way control valve for central heating circuit: 1 – boiler, 2 – controller, 3 - water temperature sensor returning to the boiler, 4 – boiler temperature sensor, 5 – exhaust temperature sensor (temperature monitoring only), 6 – 4-way valve servo, 7 – mixer circuit pump, 8 – mixer circuit temperature sensor, 9 – HUW container, 10 – HUW pump, 11 – HUW sensor, 12 – weather temp. sensor, 13 – ecoSTER TOUCH room control panel or standard room thermostat, 14 – thermal isolation.
RECOMMENDED SETTINGS:
18
Page 19
Parameter
Setting
MENU
CH pump activation temperature
55C
menuService settingsCH and HUW settings
CH pump = boiler pump
YES
menuService settingsCH and HUW settings
Mixer 1 support
CH activated
menuService settingsMixer 1 control
Max. preset temp. of mixer 1
70C
menuService settingsMixer 1 settings
Mixer 1 heating curve
0.8 – 1.4
menuMixer 1 settings
Mixer 1 weather control
activated
menuMixer 1 settings
Mixer 1 thermostat selection*
ecoSTER T1
menuService settingsMixer 1 settings
Mixer 2 support
Activate floor
menuService settingsMixer 2 settings
Max. preset temp. of mixer 2
45C
menuService settingsMixer 2 settings
Mixer 2 heating curve
0.3 – 0.8
menuMixer 2 settings
Mixer 2 weather control
activated
menuMixer 2 settings
Mixer 2 thermostat selection*
ecoSTER T1
menuService settingsMixer 2 settings
Diagram with two adjustable heating circuits and the HUW container:1 – boiler, 2 heat exchanger, 3 – controller, 4 – boiler temperature sensor, 5 – exhaust temperature sensor (temperature monitoring only), 6 – boiler pump, 8 – HUW pump, 9 – HUW container, 10 – HUW temperature sensor, 11 – mixer pump, 12 – ecoSTER TOUCH room control panel with room thermostat feature , 13 – HUW container temperature sensor CT4, 14 - weather temp. sensor, 15 - safety thermostat off the underfloor heating pump, 16 - expansion tank.
RECOMMENDED SETTINGS:
19
Page 20
Parameter
Setting
MENU
Boiler preset temperature
80C
menuBoiler settings
Min. boiler preset temperature
75C
menuService settingsBoiler settings
CH pump activation temperature
55C
menuService settingsCH and HUW settings
Buffer support
activated
menuService settingsBuffer settings
Loading start temperature
50C
menuService settingsBuffer settings
Loading stop temperature
75C
menuService settingsBuffer settings
Mixer 1 support
CH activated
menuService settingsMixer 1 settings
Max. preset temp. of mixer 1
70C
menuService settingsMixer 1 settings
Mixer 1 heating curve
0.8 – 1.4
menuMixer 1 settings
Mixer 1 weather control
activated
menuMixer 1 settings
Mixer 1 thermostat selection*
ecoSTER T1
menuService settingsMixer 1 settings
Mixer 2 support
Activate floor
menuService settingsMixer 2 settings
Max. preset temp. of mixer 2
45C
menuService settingsMixer 2 settings
Mixer 2 heating curve
0.3 – 0.8
menuMixer 2 settings
Mixer 2 weather control
activated
menuMixer 2 settings
Mixer 2 thermostat selection*
ecoSTER T1
menuService settingsMixer 2 settings
Diagram with heat buffer, where: 1 – boiler, 2 burner, 3 controller, 4 boiler temperature sensor, 5 exhaust temperature sensor, 6 boiler pump, 7 heat buffer, 8 HUW pump , 9 - mixing valve actuator,
10 - mixer temperature sensor, 11 - mixer pump, 12 - upper sensor of buffer temperature, 13 - lower sensor of buffer temperature, 14 - ecoSTER TOUCH room control panel, 15 - thermostatic three-way valve to the return protection, 16 – weather temp. sensor, 17 - thermostat to turn off the pump.
RECOMMENDED SETTINGS:
* When using a standard room thermostate with ON/OFF terminals instead of the ecoSTER TOUCH (14), select the Universal option, or when the setting is hidden, do not choose anything.
20
Page 21
10 Technical data
Power supply
230V~, 50Hz
Current consumption by the regulator
0,2 A
Max. rated current
6 (6) A
IP rating of the regulator
IP20
Ambient temperature
T50
Ambient temperature
0...50 C
Storage temperature
0...65C
Relative humidity
5 - 85% without steam condensation
Temperature measurement range of sensors CT4
0...100 C
Temperature measurement range of sensors CT6-P
-35...40 C
Accuracy of temperature measurement using sensors CT4 and CT6-P
2C
Connectors
Screw terminals at supply voltage side -
2.5mm
2
Screw terminals at control voltage side -
1.5mm2
Graphical display with touch panel
Display 480x272 pix. Overall dimensions
340x225x60mm
Total weight
1,6 kg
Standards
PN-EN 60730-2-9 PN-EN 60730-1
Software class
A
Pollution degree
2nd pollution degree
Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust. Moreover the controller cannot be used in conditions of water steam condensation or be exposed to effects of water.
12.2 Mounting requirements
Regulator should be installed by qualified and authorized technician with observance of applicable standards and regulations. The manufacturer disclaims any liability for damage caused by non-observance of instructions specified in this manual. The regulator is intended to build into other equipment, and may not be used as a stand-alone device. Ambient temperature and temperature of mounting base should be within the range of 0…+50˚C. The regulator is composed of two modules: a control panel and an operating unit, connected with electric wire.
11 Storage and transport conditions
The controller cannot be exposed to immediate effects of atmospheric conditions i.e. rain or sunrays. Temperature of storage and transport should be within scope
-15…+65°C. During transport the controller cannot be exposed to vibrations bigger than typical for transport of boilers as well as direct pressure upon the clamp cover in order to protect the STB capillary, which is situated inside the clamp box for the controller version equipped with STB device.
12 REGULATOR INSTALLATION
12.1 Environmental conditions
12.3 Module installation
The regulator casing does not provide dust and water immunity. In order to provide the protection from these factors the regulator should be enclosed with a proper casing. The regulator is to be enclosed – which means the regulator should be screwed on to the flat horizontal or vertical surface (e.g. boiler housing, room wall). To screw on the regulator use mounting holes and proper screws. Location and spacing of mounting holes are shown in the picture below. The regulator must not be used as a free­standing device.
After installation make sure that the device is properly mounted and it is impossible to detach it from the mounting surface.
21
Page 22
Opening of the boiler door or flue leakiness cannot expose the regulator directly to hot gases and fire from the fireplace.
In case of using the version with STB device before making the montage and wiring it is strongly recommended to take out the STB capillary from inside the clamp box using cable opening as described on the picture below.
Attention! This capillary cannot be smashed or bend with acute angle.
1- Cable opening 2 – The STB capillary cable,
Caution: After the regulator is turned off using the keyboard, dangerous voltage can occur on the terminals. Before starting any assembly works, you must disconnect the mains supply and make sure that there is no dangerous voltage on the terminals and the leads.
Connection of the 230V~ mains voltage to terminals 25-48 or to transmission terminals G2, G3, B and USB results in the regulator damage and poses a threat of electrocution.
Unconditionally check if any lead of the insulated cable, or the cable itself DO NOT have electrical connection with the metal grounding strip (which is placed near to high voltage terminals of the regulator).
Insulated clamp sleeve, 6mm lenght.
Insulated clamp sleeve, 6mm lenght.
which was being correctly taken out from the clamp box.
Connection cables should not have contact with surfaces which temperature exceeds cables nominal operating temperature. Terminals 1-22 are designed to connect devices supplied by the mains 230V~ voltage. Terminals 25–48 are designed to work with low-voltage devices (<12V).
Tips of connection cables, especially mains voltage cables should be secured from splitting by e. g. insulated clamp sleeves in accordance with the picture below: a – properly secured, b – improperly secured.
12.4 IP protection rate
The regulator casing provides the IP20 protection rating. The casing on the connectors cover side provides IP00 rating, and because of that connectors must be unconditionally covered with the cover. If there is a need to gain an access to the terminals side, it is a must to disconnect the mains voltage and make sure there is no dangerous voltage on regulator terminals.
12.5 Electric connection
The regulator is designed to be fed with 230V~, 50Hz voltage. The electrical system should be:
three core (with protective wire PE), in accordance with applicable regulations.
The feeder cable should be connected to the terminals marked with an arrow.
22
Page 23
All peripherals (such like: pumps, RE-marked relays and connected recipients) may be connected only by qualified person in accordance with applicable regulations. Safety precautions to prevent electrocution shall be observed. Regulator shall be equipped with a set of pins connected to 230V AC mains.
Protection lead of the power supply cable and
Electrical cables should be isolated from hot parts of the boiler, especially from flues.
The connectors cover should be always screwed on to the casing of the regulator. Apart from providing safety for the user, the connectors cover also protects the interior of the regulator from hazardous environmental conditions providing a proper level of the IP protection.
protection leads of connected devices should be connected to the grounding strip placed inside the casing of the regulator marked
it is not allowed to coil excess of the
cable and to leave not connected leads inside the casing of the regulator.
with . Before making any connections remove the cover from the casing of the regulator as shown below.
cables secured from splitting should be
connected to screw terminals of the (6) connector.
cables should be put through cable
outlets in the casing (1) and secured from ripping or loosening by a holdfast (5 – break it out from the casing).
cables insulation should be stripped by
the minimum possible, max. 60mm. If there is a necessity to strip cable insulation more than 60mm, cable leads should be fasten together or with other leads near the connector – in order to prevent contact with unsafe parts in the case of falling out the lead from the connector.
1 – cable outlets, 2 – holdfasts placing (should be broken out for the casing), 3 – improper cable connection (it is not allowed to coil excess of the cable inside the device and to leave cables with stripped insulation), 4 – proper cable connection, 5 – holdfast of the cable, 6 – connector.
When the cables connection is done the
cover of the connectors has to be put in place.
23
Page 24
: Panel
– control panel and additional room panel
ecoSTER200/ecoSTER TOUCH
, λ – Lambda
module
, B
to support additional heating
circuits,
BT – boiler temp. sensor type CT4,
FS
fuel feeder temperature sensor type CT4,
CWU
– HUW temp. sensor
RS
– boiler return water temperature sensor
type
CT4,
M1
/M2
– mixer temp. sensor type CT4,
BH
– upper buffer temp. sensor type CT4,
BL –
WS
– weather temp. sensor t
ype CT6
-P, FT – exhaust temp. sensor type CTS2
, TR – universal boiler thermostat (
NO
-
H – output to control the signaling alarms or reserve boiler,
RE – relay (
12V, max
. 80mA)
, DS
- input to the sensor opening of fuel tank flap or door
,
– input to the RPM
sensor
.
- power supply 230V~,
GR
– ground strip,
STB
– safety temperature limiter
, PO
– main fuel feeder
, W - fan
, PM
– circulation pump,
PCO
– boiler
r pump
, IG – ingition
, PCW
– HUW pump
, SM
1/SM2
– mixer servo
, PM
1/PM2
– mixer pump
, CPU
– controlling
24
Page 25
Electric scheme – additional module B: M3 - regulated circuit (mixer 3) temperature sensor type CT4, M4 - regulated circuit (mixer 4) temperature sensor type CT4, FS - fuel level sensor used with the BU
feeder, RM3 - mixer 3 room thermostat, RM4 - mixer 4 room thermostat, H2 - voltage output for controlling the reserve boiler, or alarm signalling, or HUW circulation pump, RELAY – relay. L N PE - power supply 230V~, PM3/PM4 - mixer 3/4 pump, SM3/SM4 - mixer 3/4 servo, BU - fuel feeder from bunker to the container in the boiler, CPU - controlling, A - module A regulator.
25
Page 26
12.6 Connection of temperature
Sensor must be protected from getting loose from the surfaces to which they are connected.
sensors
The regulator is compatible only with CT4 and CT2S sensors. The use of other sensors is prohibited!. Wires of sensors can be extended by wires with diameter no smaller than 0,5mm2. Total length of wires in each sensor should not exceed 15m. The boiler temperature sensor should be installed in a thermostatic pipe installed in the boiler. Temperature sensor of hot water silo should be installed in a thermostatic pipe welded into the silo. The mixer temperature sensor should be installed in a sleeve located in stream of running water in pipe, but also it can be installed on the pipe, on condition that it is thermally isolated from the pipe.
12.7 Connecting weather sensor
he regulator cooperates solely with the weather sensor type CT6-P. The sensor should be installed on the coolest wall of the building. Usually it is the northern wall, under the roof. The sensor should not be exposed to direct sunrays and rain. The sensor should be installed at least 2 m above the ground, far away from windows, chimneys and other sources of heat. To make the connection use wire with diameter at least 0,5mm2 up to 25m long. Polarization of wires is not essential. Second end should be connected to terminals of the regulator or properly to the used kind of regulator. The sensor should be screw to the wall. Access to assembly holes is possible after unscrewing the cover of the sensor.
Mounting temperature sensor: 1 - pipe, 2 – clamps, 3 - thermal insulation, 4 - temperature sensor.
Good thermal contact should be maintained between sensors and the measured surface. To this purpose thermal grease should be used. It is not acceptable to lubricate sensors with water or oil. Wires of sensors should be separated from network electrical wires. In such a case wrong readings of temperature may be shown. Minimum length between those wires should be 10 cm. It is not acceptable to allow for contact between wires of sensors and hot parts of the boiler and the heating installation. Wires of sensors are resistant to temperature not exceeding 100°C.
12.8 Connecting exhaust sensor
The exhaust sensor should be fitted in the boiler flue. The gap between the sensor and the flue should be sealed. The sensor should be installed by a qualified fitter, while observing regulations applicable for chimney systems. The emission sensor should be connected to the sensor terminals acc. to The emission sensor lead cannot touch hot elements of the boiler and the flue, the
temperature of which exceeds 350°C. The
emission sensor should be installed in such distance from the boiler at which it is not directly exposed to flames, and where the emission temperature does not exceed 450°C.
26
Page 27
Caution: Opening the boiler door can cause the emission temperature to exceed the
sensor‘s thermal resistance,
which can burn the sensor out.
CT4 (KTY81)
Temp.
°C
Min.
Nom.
Max.
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
CT6-P (PT1000) weather
Temp.
°C
Min.
Nom.
Max.
-25
901,6
901,9
1000,2
-20
921,3
921,6
921,9
-10
960,6
960,9
961,2
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2 CT2S (PT1000) - exhaust
Temp.
°C
Min.
Nom.
Max.
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2
Connecting emission sensor: 1 – exhaust temp. sensor type CT2S, 2 – sensor lead, 3 – flue.
12.9 Checking temperature sensors
Temperature sensors CT4/CT6-P/CT2S can be checked by measuring their resistance at the given temperature. In the case of finding significant differences between the value of measured resistance and the values presented in the table below, the sensor must be changed.
12.10 Connection of mixers room
thermostat
Room thermostat connected to the operational unit affects mixer 1 circuit and/or boiler circuit. If the whole heating circuit of the building is supplied by a mixer with electric servo, room thermostat for boiler should be turned off. Room thermostat, after disconnection of its connectors reduces preset temperature of the mixer circuit by a value set up in: Reduce preset mixer temp. to thermostat. This parameter is available in: Mixer 1-4 settings The mixer pump does not stop upon opening contacts of the room thermostat unless other settings have been made in the Service Menu. Select the value of this parameter so that once the room thermostat has responded (its contacts have opened), the temperature in the room drops.
27
Page 28
12.11 Connection of boiler's room
Note: the boiler room thermostat should be switched off if the whole central heating system of the building is supplied through a mixing valve equipped with electric servo.
Once the preset room temperature has been reached, thermostat opens its contacts and the display shows:
.
The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated.
It should to perform assembly and installation of the module by yourself, in conformity with the applicable standards.
thermostat
The regulator may work with mechanical or electronic room thermostat, which opens the contacts once the preset temperature has been achieved. Set-up the operation of room thermostat in:
Boiler settings Room thermostat
Thermostat selection Universal
Once the temperature in the room, in which the room thermostat is installed, has reached the preset value, regulator reduces the preset boiler temperature by the value set in Inc. p. b. temp. thermostat and the display
shows . This will cause longer breaks in boiler operation (the boiler will remain in SUPERVISION mode) and the same, temperature in heated rooms will drop. Moreover, the boiler pump (CH pump) may be interlocked for a certain time by opening the contacts of the room thermostat in heated rooms. To activate this function ­enter:
Boiler settings Room thermostat CH pump standstill
and set the value of this parameter >0.
Setting the value of e.g. ,,5” causes the
pump will be stopped by the room
thermostat for 5 min. When ,,0” is set, the
CH pump will not be stopped by the room thermostat. Once this time has elapsed, the regulator switches on CH pump for a time set in CH pump op t. th. on e.g. 30s. This feature prevents from excessive cooling of the system caused by a pump stop.
12.12 Connection of reserve boiler
The regulator can control a reserve boiler (gas- or oil-), eliminating the necessity of enabling or disabling this boiler manually. The reserve boiler will be enabled if the temperature of the pellet boiler drops, and disabled when the pellet boiler reaches an appropriate temperature. Connection to a reserve boiler, e.g. oil-boiler one, should only be made by a qualified fitter, in accordance with the technical documentation of this boiler. The reserve boiler should be connected via relay to terminals 43-44 (Output H).
Model diagram of layout for connecting a reserve boiler to the regulator, where: 1- regulator, 2 – reserve boiler (gas- or oil-), 3 – module U3, consisting of relay RM 84-2012-35-1012 and base GZT80 RELPOL.
In a standard version, the regulator is not equipped with the U3 module.
Set the temperatures of reserve boiler switch on/off:
Service settings Boiler settings Reserve boiler Reserve boiler Reserve boiler activation temp.
Control of reserve boiler is off upon setting this parameter at ,,0”. Then should set the support for output H for reserve boiler:
Service settings Output H = Reserve boiler
Once the boiler has been fired up, and its temperature has exceeded the preset value (e.g. 25C), regulator switches off the reserve boiler and applies voltage 12V DC at output H, which causes release of coil of U3 module relay and opening its contacts. Once the boiler temperature has dropped below
28
Page 29
the value set in the parameter of Reserve
Entry of the regulator to Boiler switch off” conditions causes the reserve boiler switches on.
boiler activation temperature, the regulator stops to supply voltage to the output H, and the reserve boiler switches on.
Hydraulic diagram with the reserve boiler, connection of open and close circuits 1 – regulator, 2 – reserve boiler, 3 – U3 module (2 pcs), 4 – switching valve (with limit switches), 5 – heat exchanger (recommended settings: HUW mode = No priority, Heat exchanger = ON.
Electric diagram for switching valve of the reserve boiler, where: 1 – regulator, 2 – reserve boiler, 3,4 – relay RM 84-2012-35-1012 RELPOL and base GZT80 RELPOL, 5 – servo of switching valve.
Hydraulic diagram with the reserve boiler and the 4-way valve in close circuit 1 – regulator, 2 – reserve boiler, 3 – U3 module, 2 pcs., 4 – switching valve servo (with limit switches) - to ensure free gravitational flow of water in the boiler circuit, active cross-section of switching valve (4) has to be larger than or equal to cross­section of boiler circuit pipes. Use pipes of large cross section for gravitational boiler circuit.
12.13 Connection of alarm
signaling
The regulator may announce an alarm condition by activating external device (e.g. bell or GSM device to send SMS). Alarm signaling and reserve boiler control use the same terminals, therefore, setting of the H output for alarm signaling deactivates the function of reserve boiler control. Connect alarm annunciator through U3 module.
Connection of an external alarm annunciator 1 ­regulator - module A, 2 – external alarm
29
Page 30
annunciator, 3 – relay RM 84-2012-35-1012
When connecting mixer servo, take due care to prevent boiler overheating, which may occur when the flow of boiler water is limited. You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from the boiler at any time it is required by opening it completely.
Safety temperature limiter should have nominal operation voltage of ~230V and should follow current regulations.
Warning: 1-2 terminals are under dangerous voltage.
RELPOL and base GZT80 RELPOL.
12.14 Connection of mixer
The regulator works only with mixing valve servos equipped with limit switches. Use of other servos is not allowed. The servos of full turn time from 30 to 255 s may be used. Description of mixer connection:
- connect mixer temperature sensor, ­connect mixer pump wiring,
- switch on the regulator and select proper Mixer support in the service menu Service settings Mixer 1 Settings
- enter the proper Valve opening time in (this time should be indicated on servo rating plate e.g. 120 s).
- connect power supply to the regulator and switch on the regulator to start the mixer pump,
- determine direction of servo closing/ opening. For this purpose, set the selector located on the housing of the servo to manual control and find the positions in which the temperature in mixer circuit is maximum and minimum (it corresponds to the setting of the regulator of "100% ON" and "0% OFF, respectively). Note the position to verify the connections later,
- disconnect power supply to the regulator,
- connect mixer servo and regulator wiring according to valve servo manufacturer's technical documentation. Do not mistake direction of valve opening with its closing,
- connect regulator power supply,
- check whether wires to mixer closing and opening are not interchanged. To do this, enter MENU Manual control and open the mixer by selecting Mix1 Open = ON. When
opening the servo, the temperature on mixer sensor should increase. If not, disconnect regulator power supply and switch the wires. Note: Other reason may be incorrect mechanical connection of the valve! – refer to the documentation of valve manufacturer and check whether the valve is properly connected.
12.15 Connecting temperature
limiter STB
When temperature of water in the boiler
exceeds 95°C, power supply of the electric
feeder and the fan is cut off by the safety temperature limiter. To reset the limiter it is needed to press the button placed in the side of the casing, near the power switch. Pressing of that button is only possible when temperature of water in the boiler drops. If the regulator is not factory-equipped with the safety temperature limiter, the STB should be connected as an external device. The STB temperature limiter should be connected to the 1-2 terminals shown on the electric scheme. If the safety temperature of water in the boiler exceeds, the power supply of the fan and the engine of feeder will be cut off by the temperature limiter.
12.16 DS input
There is a possibility of connecting the sensor that detects a door or fuel tank flap opening. Opening of the DS contact results in disconnection of the fan and the feeder power supply. DS connector is under safe voltage.
12.17 Connecting room panel
The regulator can be equipped with room panel ecoSTER TOUCH, which can serve as:
- room thermostat,
- boiler control panel,
- alarm signalling device,
- fuel level indicator.
30
Page 31
Cross-section area of wires used to connect ecoSTER TOUCH control panel should be 0,5mm2.
Max. length of wires should not exceed 30 m.
Software update can be performed only by a qualified person. Precautions to prevent electrocution should be observed!.
ecoMAX860P
TOUCH
ecoSTER TOUCH
This length may be longer if the wires used have cross-section area larger than 0,5mm2.
Four-wire connection Connection – see Electric scheme.
Two-wire connection For two-wire connection, power supply of 12V DC and rated current of min. 200mA is required. Disconnect GND and +12V wires from the module (2) and re-connect them to external power supply unit arranged near ecoSTER200 or ecoSTER TOUCH. The power supply unit is not included in the regulator supply. The max. length of wires to the ecoSTER200 or ecoSTER TOUCH control panel depends on cross-section area of a wire, and e.g. for a wire of cross-section of
0.5 mm2 it should not exceed 30m. The cross-section area of the wire should not be less than 0.5 mm2.
To update the software:
disconnect power supply of the regulator. insert microSDHC memory card (other
types of memory cards are not supported) to a socket in the movable casing of the panel shown above. On the memory card there should be written new software in the *.pfc format as a 2 files: a file with the panel software and a file with the module A software.
Software files should be placed directly
on the memory card, do not place them in any subdirectory,
then connect power supply of the
regulator and go to: General settings Software update and perform the update firstly in the A module, then in the panel, and in the end in other devices.
12.18 Software update
Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC.
31
Page 32
13 Service menu
Service settings
Burner settings
Boiler settings
CH and HUW settings
Buffer settings*
Mixer 1-4 settings*
Output H
Show advanced setup
Restore default settings
Touch screen calibration
Burner settings
Firing up
Ignition test time  Feed time  Ignition end exhaust temperature  Exhaust delta  Ignition fan  Ignition time  Fan time extension  Heating-up time
Operation
OPERATION mode cycle time  Feeder efficiency  Fuel caloric value  Container capacity  Feeder:
- Efficiency test time
- Feeder efficiency test
- Fuel weight
Burning off
Purge speed  Burning off time
Supervision
Supervision time  Fan speed  Feed time  Interval time  Fan time extension
Min. fan speed
Lack of fuel detection time
Exhaust temperature when no fuel
Exhaust temperature increase time
Exhaust temperature - blow reduction
Max. feeder temperature
Feeder 2 operation time*
Boiler settings
Grate
Max. ignition time Lack of fuel detection time Threshold of fuel detection Lack of fuel detection method [Exhaust
only/Water and exhaust]
Boiler hysteresis Purge operation - supervision Purge interval - supervision
Return protection
Return protection 4D  Return hysteresis  Min. return temperature  Valve closing  Temperature shunt pump activation*
Thermostat select
Off  Universal  ecoSTER T1-T3
Min. boiler temperature
Max. boiler temperature
Reserve boiler*
Temperature activation reserve boiler
Alarms*
Boiler cooling temperature
Parameter A,B,C FL
CH and HUW settings*
CH pump activation temperature
CH pump standstill when loading HUW*
Min. HUW temperature*
Max. HUW temperature*
Increasing boiler temp. from HUW and mixer
HUW operation extension*
Circulating pump standstill time*
Circulating pump operation time*
CH pump working mode
OFF/ON  Shut pump  Exchanger
CH pump standstill time by thermostat
CH activation time by thermostat
Circulation pump starting temperature*
Buffer settings*
Buffer support
Loading start temperature
Loading stop temperature
Heating start installation
Mixer 1-4 settings*
Mixer support
Off CH on Floor ON Pump only
Thermostat select *
Off  Universal  ecoSTER
Min. mixer temperature
Max. mixer temperature
32
Page 33
Proportional range*
Integration time constant*
Valve full opening time
Pump Off by thermostat
Mixer input dead zone*
Output H*
Output H1/H2*
Off Reserve boiler Alarms
Manufacturer menu**
Reset counters
Reset alarms
Exhaust alarm temperature
Flame return - feed time
Flame return - detection delay
Flame return alarm - feed time
Hall sensor control
Min RPM
Max RPM
Grate mode blockade
Automatic switching fuel
* unavailable if no adequate sensor or
additional module is connected or the parameter is hidden.
** the manufacturer menu is accessed after entering a special password.
33
Page 34
14 SERVICE SETTINGS
Firing up
Ignition test time
Time of checking whether the burner is ignited. The regulator checks if there was a proper rise (increase) of exhaust temperature. After successfully completing the check, the regulator switches to OPERATION mode.
Feed time
Fuel dosage feed time at ignition.
Ignition end exhaust temp.
Exhaust temperature above which the burner is considered to be ignited. Ignition test is ignored. Note: setting a low temperature may result in switching to OPERATION mode without a sufficient flame in the furnace. Recommended value: 130-150 °C.
Exhaust delta
Rise (increase) of exhaust temperature necessary to switch to OPERATION mode.
Ignition fan
Fan % at ignition. Note: setting a high value will prolong the ignition process and result in failed ignition attempt.
Ignition time
Time of consecutive ignition attempts. After this time, the regulator will make another ignition attempt (max. 3 attempts).
Fan time extension
Between each ignition attempt, the fan works without the heater. Thanks to this, before making another ignition attempt, the possible flame in the burner has a chance to increase the exhaust temperature and cause the switch from IGNITION to OPERATION mode without the need for additional ignition attempts.
Heating-up time
Igniter heating-up time before switching on the fan. This should not be set too high to prevent damage to the heater. After such time, the heater continues to work until an increase in the exhaust temperature is detected.
Operation
OPERATION mode cycle time
Complete cycle time of fuel feeding in OPERATION mode. OPERATION cycle time = OPERATION feed time + feeder standstill time
Feeder efficiency
Efficiency of the fuel feeder in kg/h. Entered a measured amount of fuel in constant feed (feeder working constantly). The parameter does not affect the work of the burner and is used for calculating the fuel level and current boiler output.
Fuel caloric value
Fuel caloric value in Kwh/kg. This parameter is only used for information. The parameter does not affect the work of the burner and is used for calculating the fuel level and current boiler output.
Container capacity
Fuel container capacity used for calculating the fuel level. Entering the correct value relieves the user from the need to calibrate the fuel level. The regulator uses this data if the fuel level has not been calibrated. After calibrating the fuel level successfully, the regulator does not use this parameter.
Feeder
It is possible to conduct a feeder efficiency test and to set the duration of this test. Additionally, fuel weight can be entered here. This data facilitates the adjustment of fuel oriented parameters.
Burning off
BURNING OFF mode is not used when coal is the fuel of choice.
Burning off time
Fan time in order to burn off remaining fuel.
Purge speed
Fan speed during burning off in %.
Supervision
Supervision time
BURNING OFF mode and then into PAUSE mode. When the parameter Supervision time = 0, then the controller skip the SUPERVISION mode and goes directly to BURNING OFF mode. When the parameter Supervision time = 255, then the controller stays in SUPERVISION mode until the boiler temperature drops down up to the level, by which the controller returns to OPARATION mode.
Fan speed
Fan speed in SUPERVISION mode; too high value may cause the boiler to overheat or the flame to return to the feeder; too low value results in fuel over-filling.
14.1 BURNER
34
Page 35
Feed time
Feed time in SUPERVISION mode; too high value may cause the boiler to overheat or fuel over-filling; too low value results in fuel returning to the container.
Interval time
Feeder work cycle time in Supervision mode. SUPERVISION cycle time = feed time + interval time
Fan time extension
In SUPERVISION mode, after a fuel dose is supplied and the feeder is off, the continues to work for the extension period in order to ignite the fuel dose. This parameter should not be set too high as it may over heat the boiler.
Min. fan speed
Minimal fan speed in % that can be selected by the user of the regulator. This parameter is used to limit the access to the complete fan speed range in the user menu. It is not used in the fan control algorithm. The parameter should be set relatively low, allowing the fan to spin slowly and freely.
Lack of fuel detection time
Lack of fuel detection time is deduced after the exhaust temperature drops below the Lack of fuel detection threshold. After this time is deduced, the regulator makes 3 attempts to ignite the burner, and when this fails, it displays the “ignition failed” alarm.
Exhaust temperature when no fuel
If exhaust temperature is lower than this value for a time longer than the time set in the Fuel lack detection time parameter, lack of fuel will be detected and next firing-up attempt will be made.
Exhaust temperature increase time
This time is used as function preventing the extinguishing of flame in OPERATION mode. If the exhaust temperature does not exceed the Lack of Fuel Detection threshold after such time, an ignition test will be made.
Exhaust temperature - blow reduction
Exhaust temperature over which revolutions of the fan are reduced (down to a minimum power).
Max. feeder temp.
This parameter determines the maximum temperature at which the alarm for exceeding the maximum feeder temperature is displayed. When this temperature is exceeded, the feeder is engaged for a predefined time, with a several-minute pause. If the temperature drops, the regulator resumes normal operation; if not, the feeder will be engaged for a longer period in order to remove embers from the feeding pipe. These times may be edited in a special menu accessible only to the manufacturer of the boiler.
Feeder 2 operation time
Additional (external) feeder operation time.
14.2 BOILER
Grate
Max. ignition time
When this time is exceeded ant the exhaust temperature does not rise
above the Lack of Fuel detection threshold +15°C, a failed ignition alarm
will be displayed. Note: during ignition in RUST mode, the fan works at the Ignition fan - grate speed. This parameter is adjusted via the user menu.
Lack of fuel detection time
Time is counted after fumes temperature drops below the Fuel detection threshold value. In the grate mode, blow operation is stopped. If the burner is active, flame test is started. Lack of fuel detection is off for "0" setting.
Lack of fuel detection method
Only exhaust - lack of fuel detection occurs via the indications of the exhaust temperature sensor. This method allows to detect the lack of fuel quickly. It can only be used when there is an exhaust sensor in the flue of the boiler. Water and exhaust - lack of fuel detection occurs both via the indications of the exhaust temperature sensor and the water temperature sensor in the boiler. To detect the lack of fuel, both temperatures need to drop, and the water temperature in the boiler must drop below the CH pump activation temperature.
Boiler hysteresis
If boiler temperature goes below preset temperature by value of boiler hysteresis, then automatic firing-up of burner takes place.
Purge operation - supervision
Fan purge time when the boiler temperature exceeds the boiler’s set
temperature
Purge interval - supervision
Fan purge interval time when the boiler temperature exceeds the boiler’s set temperature
35
Page 36
Return protection
Return protection 4D
This parameter turns on/off the boiler return protection function, which is being done by mixing valve together with electric actuator. Attention: do not activate this function when there is no actuator installed on the valve!
Return histeresis
The electric actuator will return to its normal operation with return temperature ≥ min. return temperature + return hysteresis.
Min. set return temperature
The boiler return temperature below which the electric actuator will close the mixing valve.
Valve closing percentage
It is a value for opening the mixing valve during active return protection function. This value is given in percentage. This value should be set in such way, that the return temperature can raise. Attention: the return protection function will work only in case when the set boiler temperature will be set on sufficiently high value, otherwise there will be too many lock ups of the actuator. Attention: The valve is locking up with the +-1% of precision.
Temperature shunt pump
activation
The temperature at which the shut pump is activated.
Thermostat select
The following options are available: Off (deactivates the effect of the room thermostat on the boiler’s operation) Universal (enables a NO-NC room thermostat on terminals 42-43, recommended for thermostats with hysteresis below 1K) ecoSTER (this option is available when the ecoSTER TOUCH room panel is connected, the signals on the status of the thermostat are sent from the room panel)
Min. boiler temp.
Minimal set temperature for the boiler, that can be edited by the user in user menu and also a minimal temperature, that can be automatically set by a controller e.g. from night decrease, weather control etc.
Max. boiler temp.
Maximal set temperature for the boiler, that can be edited by the user in user menu and also a maximal temperature, that can be automatically set by a controller e.g. from night decrease, weather control etc.
Reserve boiler
Determines pellet boiler temperature below which reserve boiler is
activated (i.e. gas boiler). Setting "0” value causes deactivation of
reserve boiler control and switching joint number 43-44 on alarms service.
Alarms
Allows for definition of alarm number or group of alarms after which exit number 46-47 is connected. In order for alarms to connect exit, parameter RESERVE BOILER must be set for value "0”.
Boiler cooling temp.
Preventive boiler cooling temperature. When this temperature is exceeded, the regulator switches on the hot usable water pump and opens the mixer circuits in order to cool the boiler down. The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum value. The regulator will not open the mixer circuit when mixer support = floor On.
Parameter A,B,C FL
Parameter is related with automatic power modulation of boiler by stabilizing the preset boiler temperature. The bigger the value the bigger increase in power of the boiler. Too big value can cause instability of sustaining the preset boiler temperature.
CH pump activation temperature
This parameter decides on the temperature of boiler pump activation. It secures the boiler against retting, that can occur when the boiler is being cooled down with cold water from the installation. Attention: deactivation
of boiler pump doesn’t guaranteed, that the boiler is secure against
retting and therefore corrosion. It is recommended to apply additional automatics e.g. 4-way valve or 3-way thermostatic valve.
CH pump standstill when loading HUW
It requires a HUW sensor to be plugged in. A prolonged HUW tank loading can, with HUW priority activated, lead to excessive cooling down of CH installation, because with these kind of settings the CH pump is switched off. The parameter of pause time of CH pump preventing this by periodic operation of CH pump while HUW tank loading. The CH pump will after this time activate for fixed set time of 30s.
Min. HUW temperature
It requires a HUW sensor to be plugged in. This parameter can be used for limitation of possibility to choose too low value of HUW set temperature.
14.3 CH and HUW
36
Page 37
Max. HUW temperature
It requires a HUW sensor to be plugged in. This parameter decides on which maximum temperature will the HUW container be heated during dropping down excessive heat in alarm states. It is a crucial parameter because setting this for too high value can lead to the risk of users scalding with utility water. On the other hand, too low value of this parameter can lead to a situation, when during boiler overheating there will be no possibility to drop down excessive heat into the HUW tank. When projecting the HUW installation, there should be an assumption of controller malfunction. This situation can lead to dangerous level of HUW temperature, leading to user scalding. It is advised to use additional security precautions in form of thermostatic values.
Increase boiler temp. from HUW and Mixer
This parameter determines the increase of the set boiler temperature in order to load the HUW tank, buffer, and the mixer circuit. The temperature is only increased when there is a need to do so. When the set temperature of the boiler is on a satisfactory level, the regulator will not change it in order to load the HUW tank, buffer, or mixer circuit. The increase of the set boiler temperature for the period of loading the HUW tank is signalled with the letter “C” in the main window of the display.
HUW operation extension
Available after connecting a HUW sensor. When the HUW tank is fully loaded and the HUW pump is switched off, the boiler may be in danger of overheating. This occurs when the set HUW temperature is higher than the set boiler temperature. The problem is particularly prominent
when the HUW pump works in “SUMMER” mode and the CH pump is
deactivated. In order to cool the boiler down, the HUW pump operation can be extended by the HUW operation extension time value.
Circulation pump standstill time
It is the time between periods of circulation pump operation and it is defined by the parameter circulation standstill time (recommended setting is between 15-40 min.) The circulation pump is operating in cycles for the time of circulation operation time (recommended setting is between 60 and 120s.)
Circulation pump operation time
CH pump working mode
Available options: OFF = no support boiler pump; ON = boiler pump works normally; shunt pump = boiler pump works as shunt pump; heat exchanger = boiler pump works continuously in a short circuit boiler ­exchanger.
CH pump standstill time by thermostat
When the temperature of the heated rooms is reached (the contact of the room thermostat is open), the CH pump is stopped for the CH pump
standstill time from the thermostat, after which the CH pump operation time from the thermostat is activated. Note: The following conditions
must be met in order to stop the pump via the room thermostat:
Boiler room thermostat selection ≠ deactivated Pump Off by thermostat = YES
CH pump activation time by thermostat
Circulation pump starting temperature
The temperature at which the circulation pump is activated.
14.4 BUFFER
Buffer support
This parameter is used to turn on operation with the buffer. It is available after connecting an additional B module and buffer temperature sensors.
Loading start temperature
The parameter Loading start temperature defines the upper buffer temperature below which the process of buffer loading is being started. This process will then be finish when the bottom buffer temperature will reach defined temperature in the parameter Loading stop temperature.
Loading stop temperature
Heat start installation
If the top buffer temperature drops below this value, in order to save electrical power, the mixer pumps and HUW pumps will be deactivated. This function is particularly useful when working in GRATE mode.
Mixer support
Off
The mixer actuator and pump are not in operation.
CH On
It is being used when a mixing circuit is loading a heat installation of CH. The maximum mixing circuit temperature is not being limited, the mixer is fully opened during alarms e.g. with boiler overheating. Attention: do not use this option when the heat installation is made with pipes not resistant for high temperatures. In such cases it is recommended to set the mixer operation for FLOOR switched on.
14.5 MIXER
37
Page 38
Floor On
It is being used when the mixer circuit is loading floor heating installation. The maximum mixer circuit temperature is limited to the value of max. mixer set temperature. Attention: after choosing the option – FLOOR switched on the parameter of max. mixer set temperature should be so edited, that the floor heating will be not damaged and there would be no danger of scalding.
Pump only
By the moment when the mixer circuit temperature exceeds the set temperature in the parameter mixer set temperature, the mixer pump supply will be shut down. When the circuit temperature will drop by 2˚C then the pump will again be switched on. This option is usually be used for control of floor heating pump in situation, when this pump is operating together with thermostatic valve without actuator.
Thermostat select
Options to choose from: Off: (it cuts the influence of room thermostat upon the boiler operation.) Universal: (it turns on the NO-NC room thermostat coupled to 42-43 contacts, it is required to use thermostats with 1K hysteresis.) ecoSTER: (this option is available after remote control device ecoSTER TOUCH is being connected, thermostat signal is being send from room panel.)
Min. mixer temperature
It is the parameter used for limitation of choosing too low value of set mixer circuit temperature by the user. Automatic regulation (e.g. periodic temperature reduction) also does not cause the reduction of set temperature value below the value given in this parameter.
Max. mixer temperature
This parameter has two functions: _ it enables the limitation of choosing too high value of set mixer temperature by the user. Automatic regulation (correction upon heating curve, that comes from outside temperature) also does not cause crossing the set temperature above the value given for this parameter. _ when the Mixer support = On, then the mixer pump will shut down by max. mixer temperature +5˚C, which protects the floor against destruction. For the floor heating it should be set for the value below 45+/-50 ˚C or even lower, when the thermal resistance of this floor is lower. Attention: setting too lower value of this parameter can lead to unnecessary shut down of the pump.
Proportionality range
This parameter affects the movement of the mixer actuator. Increasing this value results in the mixer reaching the set temperature faster. Setting this parameter to excessive values causes deregulation of the temperature and unnecessary actuator movement. The proper values is set experimentally. It is recommended to set this parameter in the range of 2-6 [3].
Integration time constant
The greater the value of this parameter, the slower is the actuator reaction for temperature deviation. Setting too lower values can lead to unnecessary actuator movements, too high value extending the time needed to find set value of the temperature. The right value is being edited according to research results. It is recommended to set this parameter value between 100 and 180 [160].
Valve opening time
The time of valve full opening should be entered – this time can be read from the nameplate of valve actuator, e.g. 140s.
Pump Off by thermostat
Setting this parameter to “YES” results in closing the mixer and deactivating the mixer pump after opening the room thermostat contact (the room is warm). This setting is not recommended because the heated room may cool down too much.
Mixer input dead zone
This parameter determines the value of temperature insensitivity (dead zone) of the mixer control system. The regulator controls the mixer so that the measured temperature in the mixer circuit sensor is equal to the set temperature. In order to avoid frequent actuator movements which can wear it down unnecessarily, the parameter should only be regulated when the measured temperature of the mixer circuit is lower or higher than the set temperature by a value exceeding the Mixer input dead zone.
14.6 OTHER PARAMETRES
Show advanced setup
Available options: YES (shows hidden parameters, which edition is not recommended) NO (hides hidden parameters).
Restore default settings
Restoring the service settings will automatically lead to restoring the
38
Page 39
settings from main menu (user settings).
Output H1 Output H2 (only when conneting additional module B)
Reserve boiler – output 43, 44 controls the reserve boiler.  Alarms – when an alarm occurs output 43,44 is activated.
Alarm exhaust temperature
Exhaust temperature above which the alarm will be activated. Available only in the GRATE mode..
Flame retract feeding time
Feeding time when appear flame retract.
Flame retract timer
Flame retract timer period.
Alarm flame retract
Feeder operation time at flame retraction alarm.
39
Page 40
15 ALARM DESCRIPTION
Note: arrangement of temperature sensor outside the boiler water jacket (e.g. at the outlet pipe) is not recommended because boiler overheating may be detected with delay.
The function of protection against flame recession is inoperative if the feeder sensor is disconnected or
damaged. The function of protection against flame recession is inoperative if the regulator is not powered.
Regulator cannot be used as the only protection against flame recession in a boiler. Use additional protective automatics.
Checking temperature sensors described in this manual, in point.12.8.
Checking temperature sensors described in this manual, in point.12.8.
15.1 Max. boiler temp. excess
Protection against boiler overheating comprises two stages. In first instance i.e. once the Boiler cooling temp. has been exceeded, the regulator attempts to reduce the boiler temperature by activation of the boiler pump, HUW pump and opening the mixer servo (only in case mixer circuit = CH ON). Has the temperature dropped - the regulator returns to normal operation. Is the temperature still increasing (and has reached 95C), power supply to the fuel feeder and the fan is off and permanent boiler overheating alarm with sound signal is produced. If, during boiler overheating time, temperature measured by HUW sensor is higher than Max. HUW temp., HUW pump goes off. In this manner, users of hot utility water are protected from burning. The alarm is reset by switching the regulator off and on. The alarm can be reset by restarting the power supply.
15.2 Exceeding max. feeder
temperature
This alarm will occur after the feeder temperature exceeds the parameter Max. feeder temp. If the feeder temperature exceeds this value, the regulator will enable the feeder for a constant, programmed time and will activate the poker. The airflow is disabled and the pumps are enabled. After
„pushing the fuel out”, the regulator disables
the feeder and does not activate it again, even if the feeder temperature is still high. This alarm can be cancelled only after the feeder temperature decreases, by restarting the regulator.
15.3 Faulty fuel feeding system
This alarm occurs when an electronic control circuit of the feeder is damaged. In that case the feeder become controlled by an electromechanical relay and because of that feature boiler operation will not stop – which is especially important during heating season. The regulator then works in the safe mode, which is indicated by a prompt
„Feeder control system failure” on the
screen. In the event of an alarm, stop the
operation of the boiler and repair immediately regulator.
15.4 Boiler temp. sensor damaged
This alarm occurs in case of boiler temperature sensor damage and excess of its measurement range. Upon occurrence of this alarm, boiler, HUW and mixer pumps start to possibly cool down the boiler. To reset the alarm - switch OFF and ON the regulator. Check the sensor and replace it, if necessary.
15.5 Feeder temp. sensor damaged
This alarm occurs in case of damage of fuel feeder temperature sensor and excess of its measurement range. To reset the alarm ­switch OFF and ON the regulator. Check the sensor and replace, if necessary.
15.6 Exhaust sensor temp. damaged
This alarm occurs in case of damage of exhaust temperature sensor and excess of its
40
Page 41
measurement range. To reset the alarm -
Checking temperature sensors described in this manual, in point.12.8.
Attention! Before work continuation it is required to check, if in the combustion chamber there was a large accumulation of unburned fuel. If it is the case, than it is required to remove this excessive fuel. Firing the boiler with an fuel overdose can lead to an explosion of combustible gases!.
switch OFF and ON the regulator. Check the sensor and replace, if necessary.
15.7 Unsuccessful firing up attempt
This alarm occurs after the third unsuccessful automatic furnace firing up attempt. The reason behind this alarm occurrence can be among other things: malfunctioning igniter or ventilator, malfunction of fuel feeder system, incorrect parameter setting, insufficient fuel quality or lack of fuel in the container. The alarm can be reset by restarting the power supply.
15.10 Max exhaust temperature
exceeded. Sensor damage danger!
This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature. The fan is turned off. Its aim is to protect the exhaust temperature sensor from being damaged by temperatures exceeding its resistance level. When the temperature on the boiler drops, the regulator returns to normal operation. The alarm can be reset by restarting the power supply.
15.11 No communication
The control panel is being linked with the rest of the electronics with RS485 digital communication link. In case a cable of this link will be damaged, an alarm will occur on the screen with the information CAUTION!!!
No communication”.
The controller doesn’t stop to operate and
works normally with before preset parameters. It is required to check the connection cable between control panel and the module and replaced it with a new one or repair it.
15.8 Exhaust temperature not met.
Check fuel quality
This alarm is sounded when the exhaust gases are not heated above the lack of fuel detection threshold in the exhaust temperature increase time. The alarm prevents filling the combustion chamber with unburnt fuel. Check the quality and moisture of the fuel. The alarm can be reset by restarting the power supply.
15.9 Boiler overheating STB, open
contact
This alarm occurs after activation of independent safety thermostat that secures the boiler against overheating. The burner will then be deactivated. After the boiler temperature will drop down it is required to unscrew an oval STB lid and then press the Reset button.
15.12 Unsuccessful attempt of
buffer loading
This feature has an application only after module B connection. It is a silent alarm, which informs about unsuccessful attempt of adding fuel from additional fuel container (bunker) to boiler container. In case, when during preset time of container loading, a sensor in this container will not detect the increase of fuel level, this alarm will occur. This signalisation does not shut down boiler automatic operation.
15.13 No power supply
This alarm occurs after power to the regulator, in the case of early no power supply. The regulator returns to the mode of operation where worked before the power failure.
15.14 Fan or fan speed sensor
damaged
This alarm occurs then the fan’s speed sensor or the fan itself is damaged, based on the voltage capacity on the terminal
41
Page 42
controlling the sensor. The regulator switches
Note: This function must not be the only anti-freezing protective measure! Apply other methods too. Regulator manufacturer is not liable for anti-freezing related damages.
off the fan.
17 REPLACEMENT OF PARTS AND
COMPONENTS
16 ADDITIONAL FUNCTIONS
16.1 Power supply decay
In the cases of power supply failure, the regulator will resume the operation mode in which it was before the failure.
16.2 Anti-freezing protection
If the boiler temperature drops below 5C, the CH pump will be enabled, thus forcing circulation of the boiler water. This will delay the process of water freezing, yet in the case of great frost or shortage of power, it will not protect the system against freezing.
16.3 Function of protecting pumps
against stagnation
The regulator performs the function of boiler, HUW and mixer pumps and servo protection from locking caused by scale deposit. To do this, these components are periodically (every 167h) switched on for few seconds. In this way the pumps are protected from immobilization caused by scale deposits. Therefore, during boiler shut-down, power supply to the regulator should be on, and the regulator should be in STANSTILL mode.
16.4 Feeder bunker
After connect an additional module B controller can be used with the sensor low fuel level in the tank (the fuel supply from the bunker). Upon activation of the sensor (opening) at the Additional feeder operation time controller activates additional feeder in order to supplement the base fuel tank. This parameter can be found in:
Service settings Burner settings
If the parameter Additional feeder operation time is set to “0” this work additional feeder
is turns off.
17.1 Replacement of mains fuse
Mains fuse is located in the Operating Unit. It protects the regulator and other equipment. In case of replacement, use 6.3A. In order to take out the fuse, raise the fuse holder using flat-blade screwdriver and take out the fuse.
17.2 Replacement of control panel
It is not recommended to replace only the control panel as the software in the panel must be compatible with the software in the rest of the regulator
17.3 Lambda sensor
Burner efficiency can be increased by connecting additional Lambda sensor module. Connect the module according to electric scheme. Lambda sensor is to be activated in:
Service settings Burner settings Lambda sensor
If parameter Operation with Lambda sensor is set on ON then the controller will operate using Lambda sensor readings. The amount of air provided to the furnace will be automatically set in such a way to obtain preset amount of air in fumes. If this parameter is set on OFF then Lambda sensor readings will not have influence on controller’s operation. Amounts of air for given burner power are set in:
Boiler settings Output modulation
Periodical calibration of Lambda sensor readings can be necessary. To conduct Lambda sensor calibration it is necessary to extinguish the boiler. To make a successful calibration the furnace in boiler must be completely extinguished. To start up the calibration use the parameter:
Boiler settings Lambda calibration
Calibration process lasts approximately 8 minutes.
42
Page 43
Page 44
ul. Wspólna 19, Ignatki
16-001 Kleosin, Poland
phone +48 85 749-70-00
fax +48 85 749-70-14
plum@plum.pl
www.plumelectronics.eu
Jacek Kucharewicz
ul. Sikorskiego 66
16-100 Sokółka
Poland
tel. +48 85 711 94 54
www.metalfachtg.com.pl
Loading...