Metal-Fach ecoMAX860P2-T Installation Manual

Page 1
APPLIES TO SOFTWARE:
MODULE
A/B
PANEL
v06.XX.XX
v06.XX.XX
11-2015
functions available in the additional module B
ecoSTER TOUCH
ecoNET
Boiler controller
ecoMAX860P2-T
FOR AUTOMATIC SOLID FUEL FIRED BOILERS WITH INGITION
(GUTTER AND RETORT FEEDERS)
INSTALLATION AND OPERATING MANUAL
ISSUE: 1.0
Page 2
2
Page 3
CONTENTS
11 TECHNICAL DATA ............................................... 23
1 RECOMMENDATIONS REGARDING SAFETY ........ 4
2 GENERAL ............................................................. 5
3 INFORMATION ABOUT DOCUMENTATION ......... 5
4 STORAGE OF DOCUMENTATION ......................... 5
5 APPLIED SYMBOLS .............................................. 5
6 DIRECTIVE WEEE 2002/96/EG ACT ON
ELECTRICAL AND ELECTRONIC EQUIPMENT ................... 5
REGULATOR INSTRUCTION MANUAL ............ 7
7 STRUCTURE – MAIN MENU ................................. 8
8 OPERATING THE REGULATOR ............................. 9
8.1 DESCRIPTION OF DISPLAY MAIN WINDOW ................. 9
8.2 SWITCHING ON AND OFF THE BOILER ........................ 9
8.3 SETTING PRESET BOILER TEMPERATURE ................... 10
8.4 FIRING-UP ..................................................... 10
8.5 OPERATION ................................................... 10
8.6 REGULATION MODE ............................................ 10
8.7 SUPERVISION ................................................ 11
8.8 BURNING OFF ................................................ 11
8.9 STANDSTILL ................................................... 11
8.10 DOMESTIC HOT WATER SETTINGS HUW ................. 11
8.11 SETTING HUW PRESET TEMPERATURE................... 12
8.12 HUW CIRCULATION ........................................... 12
8.13 ENABLING THE SUMMER FUNCTION ....................... 12
8.14 MIXER CIRCUITS SETTINGS ................................... 12
8.15 WEATHER CONTROLLED OPERATION ...................... 13
8.16 DESCRIPTION OF NIGHT TIME DECREASE SETTINGS .... 14
8.17 FUEL LEVEL SETUP .............................................. 15
8.18 INFORMATION ................................................... 16
8.19 MANUAL CONTROL ............................................ 16
8.20 GRATE ............................................................. 16
8.21 FAVOURITE MENU .............................................. 16
8.22 ECOSTER TOUCH ............................................. 16
8.23 ECONET .......................................................... 16
9 DESCRIPTION OF ALARMS ................................. 16
9.1 BOILER MAX. TEMP. EXCEEDED ............................. 16
9.2 FEEDER MAX. TEMP. EXCEEDED ............................. 16
9.3 FEEDER CONTROL SYSTEM FAILURE ........................ 17
9.4 BOILER TEMP. SENSOR FAILURE ............................. 17
9.5 FEEDER TEMP. SENSOR FAILURE ............................ 17
9.6 EXHAUST TEMPERATURE SENSOR FAILURE ............... 17
9.7 BOILER IGNITION FAILED ...................................... 17
9.8 EXHAUST TEMPERATURE NOT MET. CHECK FUEL QUALITY
...................................................................... 17
9.9 BOILER OVERHEATING, STB LIMITER OPEN .............. 18
9.10 MAX EXHAUST TEMPERATURE EXCEEDED. SENSOR
DAMAGE DANGER! ............................................. 18
9.11 LACK OF COMMUNICATION .................................. 18
9.12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING ......... 18
9.13 FAN OR FAN SPEED SENSOR FAILURE ...................... 18
12 CONDITIONS OF STORAGE AND TRANSPORT .... 23
13 REGULATOR INSTALLATION ............................... 23
13.1 ENVIRONMENTAL CONDITIONS .............................. 23
13.2 INSTALLATION REQUIREMENTS .............................. 23
13.3 ASSEMBLY OF TOUCH CONTROL PANEL.................. 23
13.4 MOUNTING OF WORKING MODULE ........................ 24
13.5 IP PROTECTION RATE ........................................... 25
13.6 CONNECTING ELECTRICAL SYSTEM .......................... 26
13.7 WIRING DIAGRAM .............................................. 27
13.8 CONNECTION OF TEMPERATURE SENSORS ................ 29
13.9 CONNECTING WEATHER SENSOR ............................ 29
13.10 CHECKING TEMPERATURE SENSORS ........................ 29
13.11 CONNECTION OF MIXERS ROOM THERMOSTAT .......... 30
13.12 CONNECTION OF BOILER'S ROOM THERMOSTAT ........ 30
13.13 CONNECTION OF RESERVE BOILER .......................... 30
13.14 CONNECTION OF ALARM SIGNALLING ...................... 31
13.15 CONNECTION OF MIXER ....................................... 31
13.16 CONNECTING TEMPERATURE LIMITER STB ............... 32
13.17 CONNECTING ROOM PANEL .................................. 32
14 SERVICE MENU STRUCTURE .............................. 33
15 SERVICE SETTINGS ............................................. 35
15.1 BURNER ......................................................... 35
15.2 BOILER ........................................................... 36
15.3 CH AND HUW .................................................. 37
15.4 BUFFER .......................................................... 38
15.5 MIXER ............................................................ 39
15.6 H OUTPUT ...................................................... 40
15.7 ADVANCED SETUP ......................................... 40
15.8 RESTORE DEFAULT SETTINGS......................... 40
16 SOFTWARE UPGRADE ........................................ 41
17 OTHERS .............................................................. 42
17.1 POWER SUPPLY DECAY ......................................... 42
17.2 ANTI-FREEZING PROTECTION ................................. 42
17.3 FUNCTION OF PROTECTING PUMPS AGAINST
STAGNATION ..................................................... 42
17.4 BUNKER FEEDER ................................................. 42
17.5 REPLACEMENT OF MAINS FUSE .............................. 42
17.6 REPLACEMENT OF CONTROL PANEL ........................ 42
18 REVISION HISTORY ............................................ 42
CONTROLLER INSTALLATION AND SERVICE
SETTINGS MANUAL .................................... 19
10 HYDRAULIC DIAGRAMS ..................................... 20
3
Page 4
1 RECOMMENDATIONS REGARDING
SAFETY
Requirements concerning safety are described in detail in individual chapters of this manual. Apart from them, the following requirements should in particular be observed.
means that in the case of malfunction it can be the source of a spark or high temperature, which in the presence of flammable dusts or liquids can cause fire or explosion. Thus, the regulator should be separated from flammable dusts and gases, e.g. by means of an appropriate body.
Before starting assembly,
repairs or maintenance, as well as during any connection works, please make sure that the mains power supply is disconnected and that terminals and electric wires are devoid of voltage.
After the regulator is turned off
using the keyboard, dangerous voltage still can occur on its terminals.
The regulator cannot be used at
variance with its purpose.
Additional automatics which
protect the boiler, central heating (CH) system, and domestic hot water system against results of malfunction of the regulator, or of errors in its software, should be applied.
Choose the value of the
programmed parameters accordingly to the given type of boiler and fuel, taking into consideration all the operational conditions of the system. Incorrect selection of the parameters can cause malfunction of the boiler (e.g. overheating of the boiler, the flame going back to the fuel feeder, etc.),
The regulator must be installed
by a boiler manufacturer in accordance with the applicable safety standards.
The programmed parameters
should only be altered by a person familiarized with this manual.
The device should only be used
in heating systems in accordance with the applicable regulations.
The electric system in which the
regulator operates must be protected by means of a fuse, selected appropriately to the applied loads.
The regulator cannot be used if
its casing is damaged.
In no circumstances can the
design of the regulator be modified.
Electronic isolation of the
connected devices is applied in this regulator.
Keep the regulator out of reach
of children.
The regulator is intended for
boiler manufacturers. Before applying the regulator, a boiler manufacturer should check if
the regulator’s mating with the
given boiler type is proper, and whether it can cause danger.
The regulator is not an
intrinsically safe device, which
4
Page 5

2 General

The regulator is an advanced electronic device intended for controlling boilers with automated solid fuel feeders and ignitors. Flame is detected via the exhaust temperature sensor. It can be used to control the operation of an unregulated central heating circuit, HUW circuit and three regulated heating circuits. Preset temperature of heating circuits may be set on the basis of weather sensor read­out. A possibility to work together with room thermostats helps to maintain comfortable temperature in heated rooms. Moreover, if needed, the equipment switches on gas -or oil fired reserve boiler. The regulator may operate in connection with additional control panel installed in rooms. Regulator is easy to operate in an intuitive manner. It may be used in households and other similar premises and in light industry facilities.

4 Storage of documentation

This assembly and operation manual, as well as any other applicable documentation, should be stored diligently, so that it was available at any time. In the case of removal or sale of the device, the attached documentation should be handed over to the new user / owner.

5 Applied symbols

In this manual the following graphic symbols are used:
- useful information and tips,
- important information, failure to observe these can cause damage of property, threat for human and household animal health and life.
Caution: the symbols indicate important information, in order to make the manual more lucid. Yet, this does not exempt the user from the obligation to comply with requirements which are not marked with a graphic symbol.

3 Information about documentation

The regulator manual is a supplement for the boiler manual. In particular, except for this manual, the boiler manual should also be observed. The regulator manual is divided into two parts: for user and fitter. Yet, both parts contain important information, significant for safety issues, hence the user should read both parts of the manual. We are not responsible for any damages caused by failure to observe these instructions.
6 Directive WEEE 2002/96/EG Act on
electrical and electronic equipment
Recycle the product and the packaging at
the end of the operational use period in an appropriate manner.
Do not dispose of the product together
with normal waste.
Do not burn the product.
5
Page 6
Page 7
REGULATOR INSTRUCTION MANUAL
ecoMAX860P2-T
Page 8

7 STRUCTURE MAIN MENU

Boiler settings
Preset boiler temperature
Weather control the boiler*
Boiler heating curve*
Curve shift*
Room temperature factor*
Output modulation
Max. boiler output 100% fan speed 100% Oxygen* 50% fan speed 50% H2 hysteresis Medium boiler output 50% fan speed 30% H1 hysteresis Min. boiler output 30% fan speed 30% Oxygen* Boiler hysteresis Feeder correction FL min. boiler output FL max. boiler output Ignition fan speed – grate*
Heat source
Burner Grate Auxiliary boiler*
Regulation mode:
Standard FuzzyLogic Max kW Avg kW Min kW
Fuel Selection
Fuel level
Alarm level Fuel level calibration
Lambda calibration*
Scheduled operation
On [No/Yes] Schedule
Night time decrease boiler
On [No/Yes] Reduction value Schedule
HUW settings
HUW preset temperature
HUW pump mode
Off Priority No priority
HUW container hysteresis
HUW disinfection
Night time decrease HUW
On [No/Yes] Reduction value Schedule
Night time decrease circulation pump*
On [No/Yes] Schedule
Mixer 1-4 settings*
Preset mixer temperature
Mixer room thermostat
Mixer weather control*
Heating curve mixer*
Curve translation*
Room temperature *
Mixer night time decrease
On [No/Yes] Reduction value Schedule
General settings
Clock
Date
Screen brightness
Sound
Language
Software update*
WiFi settings*
Main menu
Information
Boiler settings
HUW settings*
Summer mode [Winter/Summer]
Mixer 1-4 settings*
General setting
Manual control
Alarms
Regulator On/Off
Service settings
* unavailable if no adequate sensor or
additional module is connected or the parameter is hidden.
8
Page 9

8 Operating the regulator

Both, left and right windows may display different information. By touching the screen, you may navigate between displayed information: mixer circuits information window, HUW window, fuel level window.
OPERATION
THU

8.1 Description of display main window

1. Mode of regulator operation: FIRING-UP,
OPERATION, SUPERVISION, EXTINGUISHING, STAND-BY.
2. preset boiler temperature – press and
hold the button to edit value,
3. measured boiler temperature,
4. key to enter ’’Menu” list
5. Information fields:
fan,
feeder ,
- increase of preset boiler temperature
for the time of HUW container filling;
- increase of preset boiler temperature
by mixer circuit;
- increase of preset temperature for
buffer loading.
- grate operation,
pump,
lighter,
6. measured temperature of HUW container,
7. preset temperature of HUW container –
press and hold the button to edit value,
8. clock time and weekday
9. outside temperature (weather),
10. symbols:
- opening of room thermostat contacts
– preset room temperature has been reached;
- of preset boiler temperature for
active time intervals;

8.2 Switching on and off the boiler

- auxiliary boiler operation (gas or oil).
To have the fuel level displayed, first enter the settings acc. sec.8.17. Note: fuel level may be displayed on ecoSTER TOUCH room control panel.
Make sure fuel is present in the tank and tank hatch is closed. Now boiler may be
9
Page 10
switched on. To start the boiler - press BURNER OFF? at any place on the screen. The message: ACTIVE REGULATOR? appears.
Confirm the message. Boiler enters firing-up stage. There is also another method of boiler start-up. Press MENU button and find and
press button in pie menu.
To stop the boiler - press MENU button, and
find and press button in pie menu. Note: regulator enters burning off phase. Upon completion of burning off stage, the message BURNER OFF appears.
After three unsuccessful attempts, an alarm Failed firing-up attempt is reported. In such case, the boiler operation is halted. Boiler operation cannot be continued automatically
- service crew must intervene. After removing causes of impossibility to fire-up, the boiler must be restarted.

8.5 OPERATION

The fan operates continuously. Fuel feeder is activated cyclically. A cycle consists of feeder operation time and duration of feeding interval Parameters related with the Operation mode are: Feeder operation time and Fan output in:
Boiler settings Output modulation

8.6 Regulation mode

There are two regulation modes for stabilizing the set temperature of the boiler: Standard and FuzzyLogic
Boiler settings Regulation mode
Operating in Standard Mode

8.3 Setting preset boiler temperature

Preset boiler temperature, just like the preset mixer circuit temperature, can be set in the menu:
Boiler settings Preset boiler temp.
Mixer 1,2,3,4 settings Preset mixer temp.
Regardless of that, the preset boiler temperature is automatically increased in order to fill the hot utility water tank and feed heating mixer cycles.

8.4 FIRING-UP

The FIRING-UP mode is used for automatic firing-up of furnace in the boiler. All parameters which influence the firing-up process can be found in menu:
Service settings Burner settings Firing-up
If the firing-up failed, additional attepnts will be made. Consecutive attempts are visualised by numbers next to the lighter
When the boiler temperature reaches its set value, the regulator switches to SUPERVISION mode.
The regulator has a boiler output modulation mechanism allowing it to gradually reduce the output as the boiler temperature nears its set value Three boiler output levels can be set: maximum, medium, and minimum. Each level can be additionally adjusted with individual fuel feeding times and fan speeds, affecting the actual output of the boiler. The output level parameters are accessible through the menu Boiler Settings Output modulation. The regulator sets the current output of the burner depending on the set temperature of the boiler and H1 and H2 hysteresis settings
It is possible to set the H1 and H2 values to modulate the output withouth the medium power stage, ie. reducing output from 100% to 30%, skipping the 50% output (right side of the figure below)
symbol .
10
Page 11
Note: If only the HUW is heated (summer mode), it is recommended to set the regulator to Standard mode.
Parameters should be so selected that the boiler temperature in this mode gradually drops. Incorrect settings may lead to boiler overheating.
For the setting Supervision time = 0, the regulator skips the SUPERVISION mode and enters the BURNING-OFF mode.
When the Supervision time = 255, the regulator will work continuously in SUPERVISION mode, until the boiler temperature decreases and it automatically switches to OPERATION mode.
Power levels
Power levels
Set
temperature T=85°C
Set
temperature T=85°C
Operating in FuzzyLogic mode
In FuzzyLogic mode, the regulator automatically sets the output of the burner in order to maintain the set boiler temperature. The regulator uses the output settings predefined in Standard mode. This mode does not require setting the H1 and H2 hysteresis.
After the set temperature is exceeded by 5 degrees, the boiler switches to SUPERVISION mode.

8.7 SUPERVISION

In SUPERVISION mode, the fan and the feeder are switched on cyclicall at larger intervals than in OPERATION mode. This is to prevent the fire from being extinguished.
Supervision parameters can be found in menu:
Service Settings Burner Settings Supervision
SUPERVISION parameters should be set in accordance with the recommendations of the boiler or burner manufacturer. The parameters should be adjusted to prevent
the furnace from extinguishing during intervals.
When the supervision time expires, the regulator switches to EXTINGUISHING mode, unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode.

8.8 BURNING OFF

The extinguishing process does not occur when coal is the fuel of choice. When pellets are the fuel, they are burned off for several minutes (depending on the set time). After BURNING OFF, the regulator switches to STANDSTILL.

8.9 STANDSTILL

In the STANDSTILL mode, the boiler is put out and awaits signal to resume heating. A signal to start heating can be:
decrease in preset boiler temperature
below the preset temperature minus the value of boiler hysteresis Boiler hysteresis,
if the boiler is set to work with a buffer -
decrease in upper buffer temperature below the preset value Loading start temperature.

8.10 Domestic hot water settings HUW

The device controls temperature of the domestic how water - HUW – tank, provided that a HUW temperature sensor is connected. If the sensor is disconnected, an
11
Page 12
information about lack thereof is displayed in
Keep the tenants informed of activating the disinfection function as there is risk of being burnt with hot usable water.
In low hysteresis values, the HUW pump will start faster when the HUW temperature drops.
In Summer mode, all heat receivers may be shut off, so before enabling it please make sure that the boler does not overheat.
the main window. The parameter:
Menu HUW settings HUW pump mode allows the user to:
disable filling of the tank, parameter off, set HUW priority, using the priority
parameter - in this case, the CH pump is deactivated to speed up filling of the HUW tank.
set simultaneous operation of the CH and
HUW pump, using parameter no priority,
The regulator has a function of automatic, periodic heating of HUW container to 70 °C to eliminate bacterial flora from the HUW container.
The time settings of the circulation pump are analogous to the settings of night time decrease. The pump will be off in the defined time periods. At other times, the pump will be on at Circulation pump working time between every Circulation pump stand-by time.

8.13 Enabling the Summer function

To enable the SUMMER function, heating the WUH tank without the need of supplying the CH installation, set the Summer mode parameter to on.
Menu Summer mode
The regulator increases the HUW container temperature once a week, at 2:00 a.m. Monday. After 10 minutes of maintaining the
temperature at 70 °C, the HUW pump is
switched off and the boiler returns to normal operation. Do not activate the disinfection function when the HUW support is off.

8.11 Setting HUW preset temperature

Preset HUW temperature is defined by parameter:
HUW settings HUW preset temp.
HUW tank hysteresis When the temperature drops below the HUW set temperature – HUW tank hysteresis, the HUW pump will start in order to supply the HUW tank.

8.12 HUW Circulation

The settings are located in:
HUW SettingsCirculation pump night time decrease
and
Service SettingsCH and HUW settings
If the weather sensor is connected, switching between SUMMER and WINTER mode may occur automatically.

8.14 Mixer circuits settings

Settings for the first mixer circuit can be found in the menu:
Menu Mixer 1 settings
Settings for other mixers can be accessed in next menu items and they are identical for each circuit.
Settings for mixer (without weather sensor) It is necessary to manually set the required water temperature in the heating mixer circuit using parameter Preset mixer temp.,
e.g. at a value of 50°C. The value should
allow to obtain the required room temperature.
After connecting room thermostat, it is necessary to set a value of decrease in preset mixer temperature by thermostat (parameters Mixer room therm.) e.g. at 5°C. This value should be selected by trial and error. The room thermostat can be a traditional thermostat (no/nc), or room panel ecoSTER TOUCH. Upon activation of the thermostat, the preset mixer circuit
12
Page 13
temperature will be decreased, which, if proper decrease value is selected, will stop growth of temperature in the heated room.
Settings for mixer with weather sensor (without room thermostat ecoSTER TOUCH)
Set parameter Weather contr.mixer to on. Select weather curve as per point 8.15
Using parameter Curve translation, set preset room temperature following the formula: Preset room temperature = 20°C + heating curve translation. Example. In this setup, it is possible to connect a room thermostat which will equalize the inaccuracy of selecting heating curve, if the selected heating curve value is too high. In such case, it is necessary to set the value of preset mixer temperature decrease by thermostat, e.g. at 2°C. After opening of the thermostat contacts, the preset mixer circuit temperature will be decreased, which, if proper decrease value is selected, will stop growth of temperature in the heated room.
Settings for mixer with weather sensor and with room thermostat ecoSTER TOUCH
Set parameter Weather contr.mixer to on. Select weather curve as per point. 8.15
The ecoSTER TOUCH regulator automatically translates the heating curve, depending on the preset room temperature. The regulator relates the setting to 20 °C, e.g. for preset room temperature = 22 °C, the regulator will
translate the heating curve by 2°C, for
preset room temperature = 18 °C, the regulator will translate the heating curve by
-2 °C. In some cases described in point. 8.15 it may be necessary to fine-tune the heating curve translation.
In this setup, the ecoSTER TOUCH room thermostat can:
- decrease the heating cycle temperature by a constant value when the preset room
temperature is reached. Analogously, as specified in the previous point (not recommended), or
- automatically, continuously correct the heating cycle temperature.
It is not recommended to use both options at the same time.
Automatic correction of room temperature is carried out in accordance with the following formula:
Correction = (Preset room temperature ­measured room temperature) x room temperature coefficient /10
Example. Preset temperature in the heated room (set at ecoSTER200) = 22 °C. Temperature measured in the room (by ecoSTER200) = 20 °C. Room temp. coeff. = 15. Preset mixer temperature will be increased by (22 °C - 20 °C) x 15/10 = 3 °C. It is necessary to find appropriate value of the Room temp. coeff. Range: 0…50. The higher the coefficient, the greater the correction of preset boiler temperature. If
the setting is “0”, the preset mixer
temperature is not corrected. Note: setting a value of the room temperature coefficient too high may cause cyclical fluctuations of the room temperature!

8.15 Weather controlled operation

Depending on the temperature measured outside the building, both preset boiler temperature and temperatures of mixer circuits can be controlled automatically. If proper heating curve is selected, the temperature of the circuits is calculated automatically, depending on the outdoor temperature. Thus, if the selected heating curve is appropriate for the given building, the room temperature stays more or less the same, regardless of the temperature outside.
Note: during trial and error selection of appropriate heating curve, it is necessary to exclude influence of the room thermostat on regulator operation (regardless of whether the room thermostat is connected or not), by setting the parameter:
13
Page 14
Mixer 1 settings Mixer room therm.=
Note! Setting of time intervals for 24 hours (one day) should start from 00:00!
0. If an ecoSTER TOUCH room panel is connected, also temporarily set the Room temperaturę factor = 0.
Guidelines for proper setting of the heating curve:
- floor heating 0,2 -0,6
- radiator heating 1,0 - 1,6
- boiler 1,8 - 4
8.16 Description of night time decrease
settings
Boiler night time decreases
The boiler operates in selected time intervals. Outside of the selected intervals, the boiler is burned off.
Night time decreases for heating circuits, HUW container and circulation pump operation.
Guidelines for selection of appropriate heating curve:
- if the outdoor temperature drops, and the room temperature increases, the selected heating curve value is too high,
- if the outdoor temperature drops, and the room temperature drops as well, the selected heating curve value is too low,
- if during frosty weather the room temperature is proper, but when it gets warmer - it is too low, it is recommended to increase the Curve translation and to select a lower heating curve,
- if during frosty weather the room temperature is too low, and when it gets warmer - it is too high, it is recommended to decrease the Curve translation and to select a higher heating curve. Buildings with poor thermal insulation require higher heating curves, whereas for buildings which have good thermal insulation, the heating curve can have lower value. The regulator can increase or decrease the preset temperature, calculated in accordance with the heating curve, if it exceeds the temperature range for the given circuit.
The intervals can be used to define time periods at which lower preset temperature may be set e.g. for a night time or when the user is not at home (e.g. he/she left for a work/school). This feature enables automatic reduction of preset temperature without compromising the heat comfort and reduces fuel consumption.
To activate time intervals, set the parameter: Night time decrease for the given heating circuit to ON. Night time decrease may be set for working days, Saturdays and Sundays.
The example of night time decrease of preset temperature from 22:00 to 06:00 next day and from 09:00 to 15:00 is given below.
14
Page 15
Time interval is disregarded when its decrease is set to "0" even though "from... to ..." values have been entered.
Decrease of preset boiler temperature in selected time intervals is indicated by the symbol:
on the main screen
In the given example, the regulator will set
the decrease of preset temperature by 3 °C
from 00:00 to 06:00, and will keep the preset value (without the decrease) from 06:00 to 09:00. Then, it will set the decrease by 5 °C from 09:00 to 15:00, and will keep the preset value (without the decrease) again from 15:00 to 22:00; and again will
set the decrease by 3 °C from 22:00 to
23:59.

8.17 Fuel level setup

Activating the fuel level gauge
In order to enable display of the fuel level, set value of parameter
Boiler settings Fuel level Alarm level
to a value greater than zero, e.g. 10%. By pressing the right or left box in the main window you can select the fuel level indicator. Fuel level can also be displayed on the ecoSTER TOUCH room panel.
Operation of fuel level indicator Any time upon filling fuel tank, press and hold pressed current fuel level value. Following prompt appears:
"Set fuel level at 100% Once selected and confirmed YES, fuel level is set at 100%. Once selected and confirmed YES, fuel level is set to 100%. Note: Fuel may be replenished at any time without a need to wait for complete empty fuel tank. Replenish fuel always to the level corresponding to 100% level of the fuel tank and set 100% level as described above.
Description of operation The regulator calculates the fuel level basing on the current fuel consumption. Default settings do not always correspond to the actual consumption of fuel by the given boiler, therefore, for proper operation this method requires the regulator user to perform level calibration. No additional fuel level sensors are required.
Calibration To perform calibration - fill the fuel tank to the level corresponding to its full load and set the parameter:
Boiler settings Fuel Level Fuel level calibration Fuel Level 100%
The indicator in the main window will be set to 100%. On-going calibration process is signalled by flashing fuel level gauge. The gauge will flash until the time of marking the point corresponding to minimal fuel level. One must systematically control the decreasing level of fuel in the bin. When the level reaches the requested minimum, set the value of the parameter:
Boiler settings Fuel Level Fuel level calibration Fuel Level 0%
Calibration can be skipped if the Feeder Efficiency and Tank capacity, parameters are
set correctly in: Menu → Service settings Burner settings Operation.
15
Page 16

8.18 Information

Upon connection of mixers' extension module, information windows of additional mixers are displayed.
Note: Access to manual control menu is possible only in the STAND­BY mode, i.e. when the boiler is OFF.
Note: Long-term operation of the fan, the feeder or other working equipment may lead to occurrence of hazardous conditions.
Changing modes between grate and burner can be done via the ecoNET internet module, but only after all the manually loaded fuel is burned off. In order to change modes, turn the regulator off and on by clicking
“Work mode” in the “Current information” tab.
Note: placing the temperature sensor outside the water coating of the boiler, for example on the outlet pipe, is unfavourable because it can delay the detection of overheating.
Information" menu allows to preview temperatures being measured and to recognize which equipment is currently ON.
. Upon activation of this key, a quick selection menu appears. To add new item to this menu - hold respective icon pressed in pie menu for a while. To remove selected item from favourite menu - hold corresponding icon pressed and confirm REMOVE.

8.19 Manual control

Regulator offers possibility to manual start of working equipment such as pump, feeder motor or fan. This feature enables checking whether the given equipment is fault-free and properly connected

8.20 Grate

The regulator is able to work with a Grate, where the fuel is loaded manually. The feeder is switched off, but the fan is operational. You can switch between Burner and Grate modes in:
Boiler settings Heat source
Fan speeds are regulated in:
Boiler settings Output modulation
Fan speed settings are different for the grate than for the burner. Other parameters are set in the service settings.

8.22 ecoSTER TOUCH

The controller can work together with ecoSTER TOUCH remote control device, which have a built-in room thermostat. This room panel shows useful information such as: fuel level, alarm indication etc.

8.23 ecoNET

The controller can work together with ecoNET 300 internet module. It enables online control and supervision over the controller.

9 Description of alarms

9.1 Boiler max. temp. exceeded

Overheating protection occurs in two stages. First, after the boiler cooling temperature is exceeded, the regulator tries to decrease the temperature by transferring the heat excess to the HUW tank and by opening the mixer actuators (only when mixer use = CH enabled). If the temperature measured by the WUH senor exceeds the Max. WUH temp., the WUH pump will be switched off in order to prevent burns. When the temperature on the boiler drops, the regulator returns to normal operation. If the temperature continues to rise (reaching 95C), a constant boiler heating alarm will start, paired with a sound signal. The alarm can be cleared by pressing the Touch and Play button or turning the power supply off and on.

8.21 Favourite menu

In Touch version in the menu bar at the bottom of the screen there is a button:

9.2 Feeder max. temp. exceeded

16
Page 17
This alarm will occur after the feeder
The flame return protection function will not work if there is no power supply to the regulator.
The regulator cannot be used as the only flame return protection. Use additional automatic protection.
Note: operating in emergency mode is allowed only under user supervision and until the arrival of the service team to remove the
failure. If user supervision is not possible, extinguish the boiler. When operating in emergency mode, prevent the consequences of improper feeder work (feeder working constantly or not at all).
See temperature senor check in pt.
13.10.
See temperature senor check in pt.
13.10.
See temperature senor check in pt.
13.10.
Note: Before continuing operation, make sure that the combustion chamber does not contain excessive unburnt fuel. If so, remove the excess fuel. Ignition with excessive fuel may lead to explosion of combustion gasses!
temperature exceeds the service parameter:
Service setting sBurner settings Max. feeder temp.
In such cases, the regulator will attempt to push out the burning fuel from the feeder by switching it on for a short time. If three consecutive attempts to switch the feeder on do not reduce the temperature, the feeder will be switched on for a a longer time and report a constant alarm. Before returning to regular operation, remove the excess fuel from the combustion chamber. For additional information, see pt. 15.

9.4 Boiler temp. sensor failure

This alarm occurs when the boiler temperature sensor is damaged or when its measurement range is exceeded. Check the sensor and replace it if necessary.

9.5 Feeder temp. sensor failure

This alarm occurs when the sensor is damaged or when its measurement range is exceeded.

9.3 Feeder control system failure

The regulator has an additional protection preventing it from feeding fuel constantly. This informs the user about failures in the electrical system controlling the fuel feeder. In case of alarm, stop the boiler and repair the regulator as soon as possible.
It is also possible to continue operation in emergency mode. Before continuing operation, mane sure that the combustion chamber does not contain excessive unburnt fuel. If so, remove the excess fuel. Ignition with excessive fuel may lead to explosion of combustion gasses! Emergency mode is activated after entering the special password: 4445. Before activating emergency mode, familiarize yourself with the user manual. After accepting the password, the feeder control is taken over by the emergency system and the boiler continues to operate.

9.6 Exhaust temperature sensor failure

This alarm occurs when the sensor is damaged or when its measurement range is exceeded.

9.7 Boiler ignition failed

This alarm occurs after the third failed attempt to automatically ignite the furnace The causes of this alarm include: faulty igniter or fan, damaged fuel feeding system, improper parameter settings, low fuel quality, lack of fuel in the container.
9.8 Exhaust temperature not met.
Check fuel quality
This alarm is sounded when the exhaust gases are not heated above the lack of fuel detection threshold in the exhaust temperature increase time. The alarm prevents filling the combustion chamber with
17
Page 18
unburnt fuel. Check the quality and moisture of the fuel.
9.9 Boiler overheating, STB limiter
open
This alarm occurs when the independent safety thermostat protecting the boiler from being overheated is activated. The burner is
switched off. After the boiler’s temperature
drops, unscrew the round cover of the temperature limiter and press the reset button.
9.10 Max exhaust temperature
exceeded. Sensor damage danger!
This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature. The fan is turned off. Its aim is to protect the exhaust temperature sensor from being damaged by temperatures exceeding its resistance level. When the temperature on the boiler drops, the regulator returns to normal operation.

9.11 Lack of communication

The control panel is being linked with the rest of the electronics with RS485 digital communication link. In case a cable of this link will be damaged, an alarm will occur on
the screen with the information “Attention!
No communication”.
The controller doesn’t stop to operate and
works normally with before preset parameters. It is required to check the connection cable between control panel and the module and replaced it with a new one or repair it.
9.12 Unsuccessful attempt of buffer
loading
This feature has an application only after module B connection. It is a silent alarm, which informs about unsuccessful attempt of adding fuel from additional fuel container (bunker) to boiler container. In case, when during preset time of container loading, a sensor in this container will not detect the increase of fuel level, this alarm will occur. This signalisation does not shut down boiler automatic operation.

9.13 Fan or fan speed sensor failure

This alarm occurs then the fan’s speed
sensor or the fan itself is damaged, based on the voltage capacity on the terminal controlling the sensor. The regulator switches off the fan.
18
Page 19
CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL
ecoMAX860P2-T
19
Page 20

10 Hydraulic diagrams

The presented hydraulic diagram does not replace central heating engineering design and may be used for information purposes only.
In order for the valve (6) to be able to effectively increase the return water temperature, set a high set temperature of the boiler. In order to improve the water circulation in natural systems (highlighted circuit in the figure): use large nominal diameter pipes and four-way valve, avoid unnecessary angles and reductions, maintain a min. 2° horizontal pipe slope, etc. If the sensor (3) is attached to the pipe, isolate it with foam surrounding the pipe and sensor.
Parameter
Setting
MENU
Preset boiler temperature
75-80C
menu BOILER SETTINGS
Min. preset boiler temperature
65C
menuService Settings Boiler Settings
Increasing of preset boiler temp.
5-20C
menuService Settings CH and HUW Settings
Mix1 support
CH ON
menuService SettingsMixer 1 settings
Max. preset temperature of mixer 1
70
menuService SettingsMixer 1 settings
Heating curve, mixer 1
0.8 – 1.4
menuMixer 1 settings
Mixer 1 weather control
ON
menuMixer 1 settings
Mixer 1 thermostat selection
ecoSTER T1
menuService SettingsMixer 1 settings
Diagram A with 4-way control valve for central heating circuit, where: 1 – boiler, 2 controller, 3 - water temperature sensor returning to the boiler CT4, 4 – boiler temperature sensor CT4, 5 – exhaust temperature sensor CT2S (temperature monitoring only), 6 – 4-way valve servo, 7 – mixer circuit pump, 8 – mixer circuit temperature sensor, 9 – HUW container, 10 – hot utility water pump, 11 – HUW sensor, 12 – out-door temperature (weather) sensor CT4-P, 13 –ecoSTER TOUCH room control panel or standard room thermostat, 14 – thermal isolation.
RECOMMENDED SETTINGS:
20
Page 21
Parameter
Setting
MENU
CH pump activation temperature
55C
Menuservice settingsCH and HUW settings
CH pump = boiler pump
YES
Menuservice settingsCH and HUW settings
Mixer 1 control
CH activated
Menuservice settingsMixer 1 control
Max. set temp. of mixer 1
70
Menuservice settingsMixer 1 settings
Mixer 1 heating curve
0.8 – 1.4
MenuMixer 1 settings
Mixer 1 weather control
activated
MenuMixer 1 settings
Mixer 1 thermostat selection*
ecoSTER T1
Menuservice settingsMixer 1 settings
Mixer 2 control
Activate floor
Menuservice settingsMixer 2 settings
Max. set temp. of mixer 2
45
Menuservice settingsMixer 2 settings
Mixer 2 heating curve
0.3 – 0.8
MenuMixer 2 settings
Mixer 2 weather control
activated
MenuMixer 2 settings
Mixer 2 thermostat selection*
ecoSTER T1
Menuservice settingsMixer 2 settings
Diagram B with two adjustable heating circuits and the HUW container, where:1 – boiler, 2 heat exchanger, 3 – controller, 4 – boiler temperature sensor, 5 – exhaust temperature sensor (temperature monitoring only), 6 – boiler pump, 8 – HUW pump, 9 – HUW container, 10 – HUW temperature sensor, 11 – mixer pump, 12 –ecoSTER TOUCH room control panel with room thermostat feature , 13 – HUW container temperature sensor CT4, 14 - out-door temperature (weather) sensor CT6-P, 15 - safety thermostat off the underfloor heating pump, 16 - expansion tank, 17 – panel controller.
RECOMMENDED SETTINGS:
21
Page 22
Diagram C with heat buffer, where:1 – boiler/burner, 2 – panel controller, 3 – controller, 4 – boiler
Parameter
Setting
MENU
Boiler set temperature
80C
MenuBoiler settings
Min. boiler set temperature
75C
Menuservice settingsboiler settings
CH pump activation temperature
55C
Menuservice settingsCH and HUW settings
Operation ON (Buffer use)
activated
Menuservice settingsbuffer settings
Buffer load activation temperature
50
Menuservice settingsbuffer settings
Buffer load deactivation temperature
75
Menuservice settingsbuffer settings
Mixer 1 control
CH activated
Menuservice settingsMixer 1 settings
Max. set temp. of mixer 1
70
Menuservice settingsMixer 1 settings
Mixer 1 heating curve
0.8 – 1.4
MenuMixer 1 settings
Mixer 1 weather control
activated
MenuMixer 1 settings
Mixer 1 thermostat selection*
ecoSTER T1
Menuservice settingsMixer 1 settings
Mixer 2 control
Activate floor
Menuservice settingsMixer 2 settings
Max. set temp. of mixer 2
45
Menuservice settingsMixer 2 settings
Mixer 2 heating curve
0.3 – 0.8
MenuMixer 2 settings
Mixer 2 weather control
activated
MenuMixer 2 settings
Mixer 2 thermostat selection*
ecoSTER T1
Menuservice settingsMixer 2 settings
temperature sensor CT4, 5 – exhaust temperature sensor CT2S, 6 – boiler pump, 7 – heat buffer, 8 – HUW pump , 9 - mixing valve actuator, 10 - mixer temperature sensor CT4, 11 - mixer pump, 12 - upper sensor of buffer temperature CT4, 13 - lower sensor of buffer temperature CT4, 14 - ecoSTER TOUCH room control panel, 15 - thermostatic three-way valve to the return protection, 16 - out-door temperature (weather) sensor CT4-P, 17 - thermostat to turn off the pump.
RECOMMENDED SETTINGS:
* When using a standard room thermostate with ON/OFF terminals instead of the ecoSTER TOUCH (14), select the “Universal” option, or when the setting is hidden, do not choose anything.
22
Page 23

11 Technical data

Voltage
230V~; 50Hz;
Current consumed by regulator
I = 0,04 A
Maximum rated current
6 (6) A
Regulator protection rating
IP20
Ambient temperature
0...50 C
Storage temperature
0...65 C
Relative humidity
5 - 85% without steam condensation
Measuring range of temperature sensors CT4
0...100 C
Measuring range of temperature sensors CT6-P
-35...40 C
Accuracy of temperature measurements with sensors CT4 and CT6-P
2 C
Terminals
network
screw terminals, wire cross-section area
0.75 mm2 through
1.5mm2, screwing torque 0.4Nm, insulation removed:
communication
screw terminals, wire cross-section area up to 0.75mm2 , screwing torque 0.3 Nm, insulation removed: 6 mm
Display (TOUCH)
Color display 480x272 with touch panel
External dimensions
210x115x60 mm
Total weight
2 kg
Standards
PN-EN 60730-2-9 PN-EN 60730-1
Software class
A
Protection class
Suitable to build into Class I devices
Pollution degree
2nd degree according to PN-EN 60730-1

13 REGULATOR INSTALLATION

13.1 Environmental conditions

Due to the risk of fire is prohibited to use the controller in explosive gas and dust enviroment (eg coal). Regulator should be separated using appropriate enclosure. In addition, controller cannot be used in the presence of water vapor condensation and be exposed to water.

13.2 Installation requirements

The regulator should be installed by a qualified and authorised fitter, in accordance with the applicable norms and regulations. The manufacturer bears no responsibility for damages caused by failure to observe this manual. The regulator is to be built-in. The regulator cannot be used as a stand-alone device. The temperature of the ambient and the fitting surface cannot exceed the range of 0 - 50˚C. The device consists of two modules: control panel and working module. Both elements are connected with electric wire.
12 Conditions of storage and
transport
The regulator cannot be exposed to direct effects of weather, i.e. rain and sunlight. Storage and transport temperature cannot exceed the range of -15…65 °C. During transport, the device cannot be exposed to vibrations greater than those typical of normal road transport.

13.3 Assembly of TOUCH control panel

The Control Panel is intended to be installed in a mounting plate. Make sure there is sufficient thermal insulation between the hot walls of the boiler and the control panel and wiring. The amount of space needed to properly install the control panel is illustrated below. Follow the guidelines below when installing the Panel.
Make an opening in the mounting plate
according to the following illustration.
23
Page 24
Control panel mounting requirements. 1 – control panel, 2 – vent holes to provide air circulation (note: the holes may not cause downgrading of required IP rating. They are not required if permitted ambient temperature around the control panel is not exceeded.)
Disassembly of control panel: To remove the control panel (1) from the housing - insert flat elements (2) into indicated slots to release housing catches and remove the panel (1).

13.4 Mounting of working module

The executive module must be covered. The cover must ensure a level of protection relevant to the environment in which the regulator will be used. Moreover, it must prevent access to parts which are carrying dangerous voltage, such as terminals. A standard installation cabinet may be used as the cover. In such case, the user has access to the face plate of the executive module. The cover may be composed from boiler elements surrounding the whole module. The module cover does not provide resistance to dust and water. To protect it from these factors, provide a suitable additional cover. The executive module is intended for mounting on a standard DIN TS35 rail. The rail must be installed tightly on a secure surface. Before placing the module on the rail (2), lift the pin (3) up. After placing the module, press the pin (3) to its original position. Make sure that the device is installed securely and cannot be removed from the rail without the use of tools. For safety reasons, maintain a safe distance between the active elements of the terminal of the executive module and the conductive (metal) elements of the cover (at least 10 mm). The connection wires must be protected from plucking it out and loosening, or covered in a way that prevents the wires from tightening.
24
Page 25
b – in the cover without access to front surface, 1- working module, 2 – DIN TS35 rail, 3 – catch.

13.5 IP protection rate

Enclosure of the regulator’s executive module provides various IP protection rates, depending on the method of installation. After enclosing in accordance with this drawing, the device has protection rate IP 20 from the front side of the executive module enclosure (specified on the rating plate). From the side of the terminals, the casing has protection rate IP00, thus the terminals of the executive module must unconditionally be enclosed, in order to prevent access to this part of the casing. If it is necessary to access the part with the terminals, disconnect the mains supply, make sure that there is no voltage on terminals and leads, and remove the executive module enclosure.
Methods of module installation: a – in modular housing with access to front surface,
25
Page 26

13.6 Connecting electrical system

Caution: After the regulator is turned off using the keyboard, dangerous voltage can occur on the terminals. Before starting any assembly works, you must disconnect the mains supply and make sure that there is no dangerous voltage on the terminals and the leads.
Connecting mains supply 230V~ to terminals 22-49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock!.
All peripherals (such like: pumps, RE-marked relays and connected recipients) may be connected only by qualified persons in accordance with applicable regulations. Safety precautions to prevent electrocution should be observed. Regulator should be equipped with a set of pins connected to the 230V AC mains
Regulator is designed to be fed with 230V~, 50Hz voltage. The electrical system should be:
three core (with protective wire), in accordance with applicable
regulations.
The connection wires should not have contact with surfaces of temperature exceeding the nominal temperature of their operation. Terminals number 1-21 are intended only for connecting devices with mains supply 230V~. Terminals 22-49 are intended for cooperation with low voltage devices (below 12 V).
Tips of the connected wires, especially power leads, must be secured against splitting by means of insulated clamp sleeves.
Connect power supply wires to terminals indicated with an arrow.
Connect protective wire of power supply cable to ground strip linked with metal boiler housing. Connect coupling to the terminal of
the regulator indicated with a sign and to earthing terminals of devices connected to the regulator.
26
Page 27

13.7 Wiring diagram

Controller wiring diagram: BT - CT4 boiler temperature sensor, RS - CT4 boiler return water temperature
sensor, CWU - CT4 hot usable water temperature sensor, FS - feeder temperature sensor, BH - top buffer
temperature sensor, BL - bottom buffer temperature sensor, H - voltage output for controlling the auxiliary
boiler, or alarm signalling, or hot usable water circulation pump, RELAY - relay, M1 - CT4 regulated circuit
(mixer 1) temperature sensor, M2 - CT4 regulated circuit (mixer 2) temperature sensor, WS - CT6-P
weather sensor, FT - CT2S exhaust temperature sensor, BP - control panel, B - additional heating circuits control module, λ - lambda probe module, RP - ecoSTER TOUCH room panel with a room thermostat
function, RT - no/nc room thermostat, RPM - circulation pump control output, DS - fuel container cover or
door opening sensor input.
L N PE - 230V~ power supply, STB - temperature limit switch input, FH - fan, FA - main feeder, FL - hot
usable water circulation pump, BP - boiler or buffer loading pump, DH - hot usable water pump, PM - mixer
pump, SM - mixer actuator, IG - igniter, CPU - controller.
27
Page 28
Wiring diagram - additional B module, where: M3 - CT4 regulated circuit (mixer 3) temperature sensor, M4 - CT4 regulated circuit (mixer 4) temperature sensor, RM3 - mixer 3 room thermostat, RM4 - mixer 4 room thermostat, FS - fuel level sensor used with the BU feeder, H2 - voltage output for controlling the auxiliary boiler, or alarm signalling, or hot usable water circulation pump, RELAY - relay, L N PE - 230V~ power supply, PM3/4 - mixer 3/4 pump, SM3/4 - mixer 3/4 actuator, BU - fuel feeder from bunker to the container by the boiler, CPU - controller, A - ecoMAX860P2-T Module A regulator.
28
Page 29

13.8 Connection of temperature sensors

Sensors shall be protected against loosening from surfaces they are mounted to.
CT4
Ambient temp.
°C
Min. Ω Rated
Max.
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
exhaust CT2S-2, CT6-P
Temp.
°C
Min. Ω Rated
Max.
0
999.7
1000.0
1000.3
25
1096.9
1097.3
1097.7
50
1193.4
1194.0
1194.6
100
1384.2
1385.0
1385.8
125
1478.5
1479.4
1480.3
150
1572.0
1573.1
1574.2
Sensor wires may be extended using wires of cross-section area not less than 0.5 mm2. Total length of wires of each sensor should not exceed 15 m. Insert boiler temperature sensor into thermometer well fastened to boiler shell. Fasten feeder temperature sensor to the surface of feeder screw tube. Insert temperature sensor of HUW container into thermometer well welded to the container. The best way to mount mixer temperature sensor is to insert it into a sleeve located in the stream of flowing water, however, it is also allowed to fasten the sensor in a contact manner provided that the sensor and the pipe are properly heat-insulated.
Make sure thermal contact between the sensors and the surface which temperature is measured is good. Apply thermal paste to improve the contact. Pouring sensors with oil or water is not allowed. Sensor wires should be separated from power supply wires. Otherwise, temperature indications may be erroneous. Min. distance between these wires should be 10 cm. Do not allow sensor wires to contact hot parts of the boiler and heating system. Wires of temperature sensors are heat resistant to the temperature not exceeding 100°C.
Attach the sensor to the wall using tackbolts. To access the tackbolts holes, unscrew the sensor lid.

13.10 Checking temperature sensors

The temperature sensor can be checked by measuring its resistance in a given temperature. Replace the sensor if there are significant differences between the measured resistance and the values provided in the table below.

13.9 Connecting weather sensor

The regulator cooperates only with a weather sensor of the CT6-P type. The sensor should be installed on the coldest wall of the building, usually this is the northern wall, under a roof. The sensor should not be exposed to direct sunlight and rain. The sensor should be fitted at least 2 m above the ground, far from windows, chimneys and other heat sources which could disturb the temperature measurement (at least 1,5 m). Connect the sensor using cable of 0,5 mm2 cross-section, up to 25 m long. Polarity of the leads is insignificant. Connect the other end of the cable to the regulator.
29
Page 30
13.11 Connection of mixers room
thermostat
Room thermostat with open contacts reduces preset temperature of mixer circuit by the decrement set in:
Mixer 1,2,3,4,5 settings, Mixer room thermostat
Select the value of this parameter so that once the room thermostat has responded (its contacts have opened), the temperature in the room drops. When connecting the ecoSTER room control panel, make sure the Thermostat select parameter is set to a correct value.
Service Settings Mixer 1-4 settings Thermostat select.
Details on how to connect room control panel are given in sect. 0.
13.12 Connection of boiler's room
thermostat
Boiler circuit room thermostat may activate the burner or deactivate CH boiler pump. In order for the room thermostat to control boiler operation, set the Thermostat select. value to standard or ecoSTER T1 (if the ecoSTER TOUCH room control panel is connected)
Service Settings Boiler Settings Thermostat select.
In order for the room thermostat to control CH pump operation (without deactivating the boiler), set the Pump off by therm. value to YES.
Service Settings Boiler Settings Pump off by therm.
fitter, in accordance with the technical documentation of this boiler. The reserve boiler should be connected via relay to terminals 46-47
Model diagram of layout for connecting a reserve boiler to the ecoMAX regulator, where: 1­regulator ecoMAX, 2 – reserve boiler (gas- or oil­fired), 3 – Module U3, consisting of relay RM 84­2012-35-1012 and base GZT80 RELPOL.
Standard version of the regulator is not equipped with a relay. Reserve boiler control is switched off upon setting the H-output function to the reserve boiler.
Menu Service Settings H-output H-output function
The reserve boiler is switched on when there is no voltage on terminals 46-47. The reserve boiler is switched off when there is voltage on terminals 46-47.

13.13 Connection of reserve boiler

The regulator can control a reserve boiler (gas- or oil-fired), eliminating the necessity of enabling or disabling this boiler manually. The reserve boiler will be enabled if the temperature of the boiler drops below parameter:
Service Settings H-output Reserve boiler activation temperature
Connection to a reserve boiler, e.g. oil-fired one, should only be made by a qualified
Hydraulic diagram with reserve boiler, where: 1 – regulator, 2 – reserve boiler, 3 – relay, 4 –
switching valve (with limit switches).
30
Page 31
When connecting mixer servo, take due care to prevent boiler overheating, which may occur when the flow of boiler water is limited. You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from the boiler at any time it is required by opening it completely.
Wiring diagram of control of the switching valve in the reserve boiler, where: 1 – ecoMAX regulator, 2 – reserve boiler, 3 – relay, 5 – switching valve servo (with limit switches). Note: terminals 22,21,24 have to be galvanically insulated from terminals 12,11,14.

13.14 Connection of alarm signalling

Regulator may announce alarm conditions by activating an external device (e.g. a bell or GSM device to send a text message). Alarm signalling may be deactivated by setting the H-output function to alarms.
Service Settings H-output H-output function
Connection of an external alarm annunciator. 1­regulator , 2 – external alarm annunciator, 3 –
relay.

13.15 Connection of mixer

The regulator works only with mixing valve servos equipped with limit switches. Use of other servos is not allowed. The servos of full turn time from 30 to 255 s may be used. Description of mixer connection: Description of mixer connection:
- connect mixer temperature sensor, ­connect mixer pump wiring,
- switch on the regulator and select proper mixer support in the service menu
Service settings Mixer 1 Settings
- enter the proper Valve Opening Time in Service Settings (this time should be indicated on servo rating plate e.g. 120 s).
- connect power supply to the regulator and switch on the regulator to start the mixer pump,
- determine direction of servo closing/ opening. For this purpose, set the selector
31
Page 32
located on the housing of the servo to
The STB must have nominal operating voltage of at least ~230V, and have the applicable certifications.
Note: 12V and GND wires connecting the room panel should be at least 0.5mm2.
manual control and find the positions in which the temperature in mixer circuit is maximum and minimum (it corresponds to the setting of the regulator of "100% ON" and "0% OFF, respectively). Note the position to verify the connections later,
- disconnect power supply to the regulator,
- connect mixer servo and regulator wiring according to valve servo manufacturer's technical documentation. Do not mistake direction of valve opening with its closing,
- connect regulator power supply and put it in the STAND-BY mode,
- check whether wires to mixer closing and opening are not interchanged. To do this, enter Menu Manual control and open the mixer by selecting Mix1 Open = ON. When opening the servo, the temperature on mixer sensor should increase. If not, disconnect regulator power supply and switch the wires. (Note: other reason may be incorrect mechanical connection of the valve! – refer to the documentation of valve manufacturer and check whether the valve is properly connected).
The maximum length of the wires should not exceed 30 m. The length can be extended when using wires with bigger cross sections.
Four-wire connection: Connect in accordance to the wiring diagram.
Two-wire connection: Two-wire diagram requires a 12V DC power adapter with a nominal current of at least 400 mA. Power supply points: Connect GND and 12 V to the external power adapter. Connect D+ and D- in accordance to the wiring diagram.
13.16 Connecting temperature limiter
STB
In order to prevent the boiler from overheating due to the regulator malfunction, an STB safety temperature limiter, or any other appropriate for the given boiler and heating system, should be fitted. When the STB is activated, the fan and fuel feeder motors are disabled.

13.17 Connecting room panel

It is possible to connect an additional ecoSTER TOUCH room panel to the regulator, which may serve as:
- room thermostat,
- boiler control panel,
- alarm signaller,
- fuel level indicator.
32
Page 33

14 Service menu structure

Service settings
Burner settings
Boiler settings
CH and HUW settings
Buffer settings*
Mixer 1-4 settings*
H-output
Show advanced setup
Restore default settings
Touch screen calibration
Burner settings
Firing-up
Ignition test time  Feed time  Ignition end exhaust temperature  Exhaust delta  Ignition fan  Ignition time  Fan time extension  Heating-up time
Operation
OPERATION mode cycle time  Feeder efficiency  Fuel caloric value  Container capacity  Feeder:
- Efficiency test time
- Feeder efficiency test
- Fuel weight
Burning off
Purge speed  Burning off time
Supervision
Supervision time  Fan speed  Feed time  Interval time  Fan time extension
Min. Fan speed
Lack of fuel detection time
Exhaust temperature when no fuel
Exhaust temperature increase time
Max. feeder temperature
Boiler settings
Grate
Max. ignition time Purge operation - supervision Purge interval - supervision Lack of fuel detection time Lack of fuel detection method [exhaust
only/water and exhaust]
Exhaust temperature - fan reduction
Return protection
4-way return protection  Return hysteresis  Min. return temperature  Valve closing
Min. boiler temperature
Max. boiler temperature
Boiler cooling temperature
Parameter A,B,C FL
Thermostat select
Off  Universal
Pump shut-off from thermostat
CH and HUW Settings*
CH Pump activation temperature
CH Pump Standstill when Loading HUW*
CH pump standstill time from thermostate
CH activation time from thermostate
Minimum HUW Temperature*
Maximum HUW Temperature*
Increasing boiler temperaturę from HUW
and mixer
Prolonging HUW operation*
Circulating pump standstill time*
Circulating pump operation time*
Circulation pump starting temperature*
Exchanger [No/Yes]
Buffer Settings*
Buffer activation
Loading start temperature
Loading stop temperature
Heating installation start
Mixer 1-4 settings*
Mixer support
Off CH on Floor ON Pump only
Thermostat select *
Off  Universal  ecoSTER
Minimum mixer temperature
Maximum mixer temperature
Proportional range*
Integration time constant*
Valve full opening time
Off by thermostat
Mixer input dead zone*
H-output*
H1/H2 output*
33
Page 34
Off Reserve boiler Alarms
Auxilliary boiler activation temperaturę*
Alarms*
Manufacturer menu**
Reset counters
Reset alarms
Exhaust alarm temperature
Flame return - feed time
Flame return - detection delay
Flame return alarm - feed time
Hall sensor control
Min RPM
Max RPM
* unavailable if no adequate sensor or additional module is connected or the parameter is hidden.
** the manufacturer menu is accessed after entering a special password
34
Page 35

15 SERVICE SETTINGS

Burner settings
Firing-up
Ignition test time
Time of checking whether the burner is ignited. The regulator checks if there was a proper rise (increase) of exhaust temperature. After successfully completing the check, the regulator switches to OPERATION mode.
Feed time
Fuel dosage feed time at ignition.
End-ignition exhaust temp.
Exhaust temperature above which the burner is considered to be ignited. Ignition test is ignored. Note: setting a low temperature may result in switching to OPERATION mode without a sufficient flame in the furnace. Recommended value: 130-150 °C.
Exhaust delta
Rise (increase) of exhaust temperature necessary to switch to OPERATION mode.
Ignition fan
Fan % at ignition. Note: setting a high value will prolong the ignition process and result in failed ignition attempt.
Ignition time
Time of consecutive ignition attempts. After this time, the regulator will make another ignition attempt (max. 3 attempts).
Fan time extension
Between each ignition attempt, the fan works without the heater. Thanks to this, before making another ignition attempt, the possible flame in the burner has a chance to increase the exhaust temperature and cause the switch from IGNITION to OPERATION mode without the need for additional ignition attempts.
Heating-up time
Igniter heating-up time before switching on the fan. This should not be set too high to prevent damage to the heater. After such time, the heater continues to work until an increase in the exhaust temperature is detected.
Operation
OPERATION mode cycle time
Complete cycle time of fuel feeding in OPERATION mode. OPERATION cycle time = OPERATION feed time + feeder standstill time
Feeder efficiency
Efficiency of the fuel feeder in kg/h. Entered a measured amount of fuel in constant feed (feeder working constantly). The parameter does not affect the work of the burner and is used for calculating the fuel level and current boiler output.
Fuel caloric value
Fuel caloric value in Kwh/kg. This parameter is only used for information. The parameter does not affect the work of the burner and is used for calculating the fuel level and current boiler output.
Container capacity
Fuel container capacity used for calculating the fuel level. Entering the correct value relieves the user from the need to calibrate the fuel level. The regulator uses this data if the fuel level has not been calibrated. After calibrating the fuel level successfully, the regulator does not use this parameter.
Feeder
It is possible to conduct a feeder efficiency test and to set the duration of this test. Additionally, fuel weight can be entered here. This data facilitates the adjustment of fuel oriented parameters.
Burning off
BURNING OFF mode is not used when coal is the fuel of choice.
Burning off time
Fan time in order to burn off remaining fuel.
Purge speed
Fan speed during burning off in %.
Supervision
Supervision time
BURNING OFF mode and then into PAUSE mode. When the parameter Supervision time = 0, then the controller skip the SUPERVISION mode and goes directly to BURNING OFF mode. When the parameter Supervision time = 255, then the controller stays in SUPERVISION mode until the boiler temperature drops down up to the level, by which the controller returns to OPARATION mode.

15.1 BURNER

35
Page 36
Fan speed
Fan speed in SUPERVISION mode; too high value may cause the boiler to overheat or the flame to return to the feeder; too low value results in fuel over-filling.
Feed time
Feed time in SUPERVISION mode; too high value may cause the boiler to overheat or fuel over-filling; too low value results in fuel returning to the container.
Interval time
Feeder work cycle time in Supervision mode. SUPERVISION cycle time = feed time + interval time
Fan time extension
In SUPERVISION mode, after a fuel dose is supplied and the feeder is off, the continues to work for the extension period in order to ignite the fuel dose. This parameter should not be set too high as it may over heat the boiler.
Min. Fan speed
Minimal fan speed in % that can be selected by the user of the regulator. This parameter is used to limit the access to the complete fan speed range in the user menu. It is not used in the fan control algorithm. The parameter should be set relatively low, allowing the fan to spin slowly and freely.
Lack of fuel detection time
Lack of fuel detection time is deduced after the exhaust temperature drops below the Lack of fuel detection threshold. After this time is deduced, the regulator makes 3 attempts to ignite the burner, and when this fails, it displays the “ignition failed” alarm.
Lack of fuel detection threshold
Exhaust temperature increase time
This time is used as function preventing the extinguishing of flame in OPERATION mode. If the exhaust temperature does not exceed the Lack of Fuel Detection threshold after such time, an ignition test will be made.
Max. feeder temp.
This parameter determines the maximum temperature at which the alarm for exceeding the maximum feeder temperature is displayed. When this temperature is exceeded, the feeder is engaged for a predefined time, with a several-minute pause. If the temperature drops, the regulator resumes normal operation; if not, the feeder will be engaged for a longer period in order to remove embers from the feeding pipe. These times may be edited in a special menu accessible only to the manufacturer of the boiler.

15.2 BOILER

Boiler settings
Grate
Max. ignition time
When this time is exceeded ant the exhaust temperature does not rise above the Lack of Fuel detection threshold +15°C, a failed ignition alarm will be displayed. Note: during ignition in RUST mode, the fan works at the Ignition fan - grate speed. This parameter is adjusted via the user menu.
Purge operation - supervision
Fan purge time when the boiler temperature exceeds the boiler’s set temperature
Purge interval - supervision
Fan purge interval time when the boiler temperature exceeds the boiler’s
set temperature
Lack of fuel detection time
When the exhaust temperature in OPERATION mode drops below the Lack of fuel detection threshold, lack of fuel is detected and the fan is stopped.
Lack of fuel detection method
Only exhaust - lack of fuel detection occurs via the indications of the exhaust temperature sensor. This method allows to detect the lack of fuel quickly. It can only be used when there is an exhaust sensor in the flue of the boiler. Water and exhaust - lack of fuel detection occurs both via the indications of the exhaust temperature sensor and the water temperature sensor in the boiler. To detect the lack of fuel, both temperatures need to drop, and the water temperature in the boiler must drop below the CH pump activation temperature.
Exhaust temperature - fan
reduction
In order to limit the chimney loss, the fan speed is reduced to the value of Fan speed 30% This happens when the exhaust temperature
36
Page 37
exceeds the Fan speed reduction temperature.
Return protection
Return protection 4D
This parameter turns on/off the boiler return protection function, which is being done by mixing valve together with electric actuator. Attention: do not activate this function when there is no actuator installed on the valve!
Return histeresis
The electric actuator will return to its normal operation with return temperature ≥ min. return temperature + return hysteresis.
Min. set return temperature
The boiler return temperature below which the electric actuator will close the mixing valve.
Valve closing percentage
It is a value for opening the mixing valve during active return protection function. This value is given in percentage. This value should be set in such way, that the return temperature can raise. Attention: the return protection function will work only in case when the set boiler temperature will be set on sufficiently high value, otherwise there will be too many lock ups of the actuator. Attention: The valve is locking up with the +-1% of precision.
Min. boiler temperature
Minimal set temperature for the boiler, that can be edited by the user in user menu and also a minimal temperature, that can be automatically set by a controller e.g. from night decrease, weather control etc.
Max. boiler temperature
Maximal set temperature for the boiler, that can be edited by the user in user menu and also a maximal temperature, that can be automatically set by a controller e.g. from night decrease, weather control etc.
Boiler cooldown temp.
Preventive boiler cooldown temperature. When this temperature is exceeded, the regulator switches on the hot usable water pump and opens the mixer circuits in order to cool the boiler down. The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum value. The regulator will not open the mixer circuit when mixer control = floor activated.
Thermostat select
The following options are available: deactivated (deactivates the effect of the room thermostat on the boiler’s operation) universal (enables a no/nc room thermostat on terminals 42-43, recommended for thermostats with hysteresis below 1K) ecoSTER (this option is available when the ecoSTER TOUCH room panel is connected, the signals on the status of the thermostat are sent from the room panel)
Pump shut-off from thermostat
Available options: No (the CH boiler pump is not switched off when the room thermostat is activated) YES (the CH boiler pump is switched off when the room thermostat is activated)
CH and HUW settings
CH Pump activation temperature
This parameter decides on the temperature of boiler pump activation. It secures the boiler against retting, that can occur when the boiler is being cooled down with cold water from the installation. Attention: deactivation
of boiler pump doesn’t guaranteed, that the boiler is secure against
retting and therefore corrosion. It is recommended to apply additional automatics e.g. 4-way valve or 3-way thermostatic valve.
CH pump standstill when loading HUW
It requires a HUW sensor to be plugged in. A prolonged HUW tank loading can, with HUW priority activated, lead to excessive cooling down of CH installation, because with these kind of settings the CH pump is switched off. The parameter of pause time of CH pump preventing this by periodic operation of CH pump while HUW tank loading. The CH pump will after this time activate for fixed set time of 30s.

15.3 CH and HUW

37
Page 38
CH pump standstill time from the thermostat
When the temperature of the heated rooms is reached (the contact of the room thermostat is open), the CH pump is stopped for the CH pump standstill time from the thermostat, after which the CH pump operation time from the thermostat is activated. Note: The following conditions must be met in order to stop the pump via the room thermostat:
Boiler room thermostat selection ≠ deactivated Pump shut-off from thermostat = YES
CH pump standstill time from the thermostat Min. HUW temperature
It requires a HUW sensor to be plugged in. This parameter can be used for limitation of possibility to choose too low value of HUW set temperature.
Max. HUW temperature
It requires a HUW sensor to be plugged in. This parameter decides on which maximum temperature will the HUW tank be heated during dropping down excessive heat in alarm states. It is a crucial parameter because setting this for too high value can lead to the risk of users scalding with utility water. On the other hand, too low value of this parameter can lead to a situation, when during boiler overheating there will be no possibility to drop down excessive heat into the HUW tank. When projecting the HUW installation, there should be an assumption of controller malfunction. This situation can lead to dangerous level of HUW temperature, leading to user scalding. It is advised to use additional security precautions in form of thermostatic values.
Boiler temperature increase from HUW and Mixer
This parameter determines the increase of the set boiler temperature in order to load the HUW tank, buffer, and the mixer circuit. The temperature is only increased when there is a need to do so. When the set temperature of the boiler is on a satisfactory level, the regulator will not change it in order to load the HUW tank, buffer, or mixer circuit. The increase of the set boiler temperature for the period of loading the HUW tank is signalled with the letter “C” in the main window of the display.
HUW operation extension
Available after connecting a HUW sensor. When the HUW tank is fully loaded and the HUW pump is switched off, the boiler may be in danger of overheating. This occurs when the set HUW temperature is higher than the set boiler temperature. The problem is particularly prominent
when the HUW pump works in “SUMMER” mode and the CH pump is
deactivated. In order to cool the boiler down, the HUW pump operation can be extended by the HUW operation time time value.
Circulation pump standstill time
It is the time between periods of circulation pump operation and it is defined by the parameter circulation standstill time (recommended setting is between 15-40 min.) The circulation pump is operating in cycles for the time of circulation operation time (recommended setting is between 60 and 120s.)
Circulation pump pperation time
Exchanger
It comes only for hydraulic installations with heat exchanger between open and closed circuit. Available options are: YES (the boiler pump is operating constantly in short circuit boiler – heat
exchanger, it is not excluded e.g. from “SUMMER” function or HUW
priority) NO (standard operation of boiler pump)
Buffer settings
Activation
This parameter is used to turn on operation with the buffer. It is available after connecting an additional B module and buffer temperature sensors.
Loading start temperature
The parameter Loading Start temperature defines the upper buffer temperature below which the process of buffer loading is being started. This process will then be finish when the bottom buffer temperature will reach defined temperature in the parameter Loading
Loading stop temperature

15.4 BUFFER

38
Page 39
Stop temperature.
Central heating installation activation
If the top buffer temperature drops below this value, in order to save electrical power, the mixer pumps and HUW pumps will be deactivated. This function is particularly useful when working in GRATE mode.

15.5 MIXER

Mixer 1-4 settings
Mixer suport
Off
The mixer actuator and pump are not in operation.
CH On
It is being used when a mixing circuit is loading a heat installation of CH. The maximum mixing circuit temperature is not being limited, the mixer is fully opened during alarms e.g. with boiler overheating. Attention: do not use this option when the heat installation is made with pipes not resistant for high temperatures. In such cases it is recommended to set the mixer operation for FLOOR switched on.
Floor On
It is being used when the mixer circuit is loading floor heating installation. The maximum mixer circuit temperature is limited to the value of max. mixer set temperature. Attention: after choosing the option – FLOOR switched on the parameter of max. mixer set temperature should be so edited, that the floor heating will be not damaged and there would be no danger of scalding.
Pump Only
By the moment when the mixer circuit temperature exceeds the set temperature in the parameter mixer set temperature, the mixer pump supply will be shut down. When the circuit temperature will drop by
2˚C then the pump will again be switched on. This option is usually be
used for control of floor heating pump in situation, when this pump is operating together with thermostatic valve without actuator.
Thermostat select*
Options to choose from: Shut down: (it cuts the influence of room thermostat upon the boiler operation.) Universal: (it turns on the no/nc room thermostat coupled to 42-43 contacts, it is required to use thermostats with 1K hysteresis.) ecoSTER: (this option is available after remote control device ecoSTER TOUCH is being connected, thermostat signal is being send from room panel.)
Minimum mixer temperature
It is the parameter used for limitation of choosing too low value of set mixer circuit temperature by the user. Automatic regulation (e.g. periodic temperature reduction) also does not cause the reduction of set temperature value below the value given in this parameter.
Maximum mixer temperature
This parameter has two functions: _ it enables the limitation of choosing too high value of set mixer temperature by the user. Automatic regulation (correction upon heating curve, that comes from outside temperature) also does not cause crossing the set temperature above the value given for this parameter. _ when the Mixer Support = On, then the mixer pump will shut down
by max. mixer temperature +5˚C, which protects the floor against
destruction. For the floor heating it should be set for the value below 45+/-50 ˚C or even lower, when the thermal resistance of this floor is lower. Attention: setting too lower value of this parameter can lead to unnecessary shut down of the pump.
Valve opening time
The time of valve full opening should be entered – this time can be read from the nameplate of valve actuator, e.g. 140s.
Proportionality range
This parameter affects the movement of the mixer actuator. Increasing this value results in the mixer reaching the set temperature faster. Setting this parameter to excessive values causes deregulation of the
39
Page 40
temperature and unnecessary actuator movement. The proper values is set experimentally. It is recommended to set this parameter in the range of 2-6 [3].
Constant for integration time
The greater the value of this parameter, the slower is the actuator reaction for temperature deviation. Setting too lower values can lead to unnecessary actuator movements, too high value extending the time needed to find set value of the temperature. The right value is being edited according to research results. It is recommended to set this parameter value between 100 and 180 [160].
Pump shut-off from thermostat
Setting this parameter to “YES” results in closing the mixer and
deactivating the mixer pump after opening the room thermostat contact (the room is warm). This setting is not recommended because the heated room may cool down too much.
Mixer insensitivity*
This parameter determines the value of temperature insensitivity (dead zone) of the mixer control system. The regulator controls the mixer so that the measured temperature in the mixer circuit sensor is equal to the set temperature. In order to avoid frequent actuator movements which can wear it down unnecessarily, the parameter should only be regulated when the measured temperature of the mixer circuit is lower or higher than the set temperature by a value exceeding the mixer insensitivity.

15.6 H OUTPUT

H output
H1 output
There are option to choose from: Reserve boiler – 46-47 output controls the reserve boiler, Alarms – when an alarm occurs, output 46-47 is being activated,
H2 output*
Functions analogous to terminal H1 executed in terminal 30-31 of the B module
Reserve boiler**
This option appears, when an H1 output = reserve boiler, defines the temperature of solid fuel boilers above which the reserve boiler will be turn on or off. During buffer operation it also defines the buffer temperature above which the reserve boiler will be turn on or off.
Show advanced setup
Available options:
YES (shows hidden parameters, which edition is not
recommended)
NO (hides hidden parameters)
Restore default settings
Restoring the service settings will automatically lead to restoring the settings from main menu (user settings)

15.7 ADVANCED SETUP

15.8 RESTORE DEFAULT SETTINGS

40
Page 41

16 Software UPGRADE

Note: software may be upgraded by authorised personnel only. All electric shock preventive measures must be applied!
Inserting a microSDHC card
To upgrade the TOUCH version software, use only microSDHC memory card. In this section, software upgrade in the TOUCH version using memory card is described.
To upgrade the software, disconnect power supply of the regulator and remove ecoTOUCH control panel from the regulator housing. Insert memory card into indicated slot. Memory card should contain new software stored in the *.pfc format (two files: one with software for control panel, and the other one with software for module "A" of the regulator). Upload new software directly to the memory card. Do not nest data in sub-directory. Re­install the control panel in regulator housing
and connect power supply. Enter:
General Settings Software Upgrade and upgrade the software: first in the A module, then in regulator's control panel.
41
Page 42

17 Others

Note: This function must not be the only anti-freezing protective measure! Apply other methods too. Regulator manufacturer is not liable for anti-freezing related damages.
the regulator is turned off, via keyboard (regulator in STAND-BY).

17.1 Power supply decay

In the cases of power supply failure, the regulator will resume the operation mode in which it was before the failure.

17.2 Anti-freezing protection

In case the boiler temperature has fallen below 5 C, CH pump is activated to force boiler water circulation. It delays water freezing process, but in case of very low temperature or lack of power it may not be sufficient to protect the equipment from freezing.
17.3 Function of protecting pumps
against stagnation
The regulator protects the CH, HUW and mixer circuit pumps against stagnation. It does so by activating them periodically (every 167 h for several seconds). This protects the pumps against immobilization due to sedimentation of boiler scale. For this reason, the regulator power supply should be connected also when in the boiler is not in use. This function can be enabled also when

17.4 Bunker feeder

After connecting an additional B module, the regulator can cooperate with the low fuel level sensor in the container (fuel supply from the bunker). After the senor activates (the contact opens), the regulator will activate the additional feeder for an additional feeder operation time, in order to refill the fuel container. This parameter is found in:
Service settingsBurner settings
If the Additional feeder operation time is set to zero, the additional feeder is deactivated.

17.5 Replacement of mains fuse

Mains fuses are located in each working module. They protect the regulator and other connected equipment. In case of replacement, use 6.3 A, 5x20mm ceramic time fuse. To remove the fuse, press down fuse holder using flat screwdriver and turn it in CCW direction.

17.6 Replacement of control panel

It is not recommended to replace only the control panel as the software in the panel must be compatible with the software in the rest of the regulator.

18 Revision history

Page 43
Page 44
Page 45
Page 46
Page 47
Page 48
Jacek Kucharewicz
ul. Sikorskiego 66
16-100 Sokółka
Poland
tel. +48 85 711 94 54
www.metalfachtg.com.pl
Loading...