Metal Fab PIC, IPIC Installation Manual

Page 1
INSTALLATION AND
MAINTENANCE
PIC
INSTRUCTIONS
IPIC
MODEL PIC/IPIC
CHIMNEY AND VENTS
A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (air spaces) TO COMBUSTIBLE MATERIALS. IT IS OF UTMOST IMPORTANCE THAT CHIMNEY BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS.
and by Underwriters
Laboratories of Canada
IMPORTANT: DO NOT INSTALL CHIMNEY WITHOUT FIRST READING THESE INSTRUCTIONS VERY CAREFULLY.
Metal-Fab’s Model PIC/IPIC Chimney has been fully tested and listed by Underwriters Laboratories, Inc. and Underwriters Laboratories of Canada.
Chimneys installed in accordance with these installation instructions will comply with national safety standards and building codes.
This booklet contains complete information on details concerning dimensions, installation, clearances to combustibles, and use of non-combustible enclosures. For any additional construction information, refer to Model PIC/IPIC Design Manual - L1690.
• BREECHING APPLICATIONS
• BOILER EXHAUST APPLICATIONS
• ENGINE/TURBINE EXHAUST APPLICATIONS
METAL-FAB, INC. • P.O. BOX 1138, WICHITA, KANSAS 67201 • (316)943-2351
Page 2
GENERAL INFORMATION
LISTINGS
Metal-Fab Model PIC/IPIC Chimney is “listed” by Underwriters Laboratories, Inc (UL File No. MH8251) as “Building Heating Appliance Chimney” for continuous operation at 1000ºF and intermittent operation (less than one hour) at 1400ºF. For higher temperature applications, it is also “listed” as “1400ºF Factory Built Chimney” for continuous operation at 1400ºF and intermittent operation at 1800ºF. PIC/IPIC Chimney is “listed” by Underwriters Laboratories of Canada (ULC File No. CMH1272) as a continuous operation “760ºC Factory-Built Chimney.” PIC/IPIC Chimney is “listed” for use at maximum 60-inch water column (2.19 psig) positive internal pressure when installed in accordance with the section “PIPE AND FITTING ASSEMBLY” for 60 in.wc. in these instructions. See TABLE 1 for clearances. For sizes 6” to 14” diameter: IPIC-2, IPIC-3 and IPIC-4 chimney is “Listed” to UL103-HT for use as a Residential Chimney and is permitted to be installed within fully enclosed combustible construction at 2” min. clearance.
APPLICATIONS
Model PIC/IPIC building heating appliance chimneys are suitable for use with building heating appliances and other low heat appliances as described in the Chimney Selection Chart of the National Fire Protection Association Standard No. 211, which produce
exhaust ue gas at a temperature not exceeding 1000ºF continuous. PIC/IPIC Chimneys are also suitable for use as complete
exhaust systems for diesel engines and gas turbines. The Model PIC/IPIC product line is listed for higher heat applications where continuous temperatures are not in excess of 1400ºF and where the intermittent maximum temperatures are less than 1800ºF.
These chimneys are to be installed as required by NFPA for Factory Built Chimneys and Chimney Units. They are not to be enclosed
within combustible construction. An interior exhaust system is to be enclosed in a re resistive shaft of appropriate size and rating
where the exhaust system extends through any story of a building above that in which the connected appliance is located. An
unenclosed chimney may be placed adjacent to walls of combustible construction at the clearances specied herein. Consult local
authorities having jurisdiction.
Model PIC/IPIC chimneys are intended for use as complete systems connecting the appliance, engine or duct to the outdoors, or
as appliance connector, ue gas collector and breeching conveying ue gas to a stack built in conformance with NFPA 211, while operating under positive forced draft, negative draft or neutral gravity ow internal pressure conditions.
The Model PIC/IPIC pipe is ideally suited to this application because it is a circular cross section (low friction loss), double-wall insulated, high-strength to weight ratio design using high quality stainless steels.
Complete system size and capacity information can be obtained from the ASHRAE Handbook, Equipment Volume or by contacting
Metal-Fab, Inc., PO Box 1138, Wichita, KS 67201.
Refer to Metal-Fab Model PIC/IPIC Design Maual - L1690 for description of all necessary components.
MULTI-ENGINE EXHAUSTS NOT RECOMMENDED
Where multiple engines are being considered, it is recommended that they not be connected into one common exhaust system.
Exhaust gases tend to ow to cooler, non-operating engines, thereby causing formation of condensation. Consult with your engine
manufacturer before the installation of multiple engines vented into a common exhaust.
When designing engine exhaust systems:
• Provide correct pipe diameter and keep runs short with the minimum number of turns possible.
• Ensure that exhaust system is properly supported and is isolated from vibration.
• Pay particular attention to thermal expansion and placement of bellows joints.
• Provide proper condensation traps and drains.
EXPLOSION PROTECTION
The use of PIC/IPIC ttings such as lateral tees, wyes and elbows should be kept to a minimum to reduce back pressure and accumulation of unburned fuels. When a change of direction is required in and engine exhaust system, ttings used for direction
change must be reinforced by means of plate support or wall support assemblies to prevent damage if an explosion caused by ignition of unburned fuel should occur. Additionally, the exhaust system should be equipped with a relief valve if possible. For methods of reinforcement and placement of relief valve, see section titled “ENGINE EXHAUST SYSTEM PRECAUTIONS.”
GREASE DUCT APPLICATIONS
Metal-Fab Model PIC/IPIC chimney is listed as grease duct for continuous temperature of 500ºF and intermittent temperatures of
2000ºF. Refer to the “Grease Duct Installation Manual L2502” for specic application information.
OPERATING PRECAUTIONS
CREOSOTE AND SOOT – Formation and Need for Removal
When wood is burned slowly, it produces tar and organic vapors which combines with expelled moisture to form creosote. The
creosote vapors condense in the relatively cool chimney ue of a slow burning re. As a result, creosote residue accumulates on the ue lining. If ignited, this creosote makes an extremely hot re. For this reason, the chimney should be inspected at least once every
two months during the heating season to determine if a creosote or soot buildup has occurred. If creosote or soot has accumulated,
it should be removed to reduce risk of chimney re.
A licensed or qualied chimney sweep should be contacted to clean the chimney. Contact local building or re ofcials about
restrictions and installation inspection in your area. Adequate clearance is required around cleanouts to assure accessibility for removal of caps and products accumulated within the chimney.
NOTE: Dimensions in these instructions are in American standard (feet and inches), with Metric (mm) in parenthesis except stated otherwise.
2
Page 3
CHIMNEY ENVIRONMENT
It is suggested that a chimney being installed in a corrosive atmosphere be constructed of Type 316 stainless steel. Type 316 stainless is resistant to corrosion and will add to the life expectancy of the installation. Chemicals containing halogen compounds should not be allowed to contaminate the combustion air supplied to the heating equipment. Storage or use of chemicals containing chlorine or chlorides in the vicinity of equipment, or the presence of these compounds in the fuel, or combustion air supply may lead to early deterioration of the chimney.
Chemicals which may cause attack on chimney materials include
(but are not limited to):
• chlorinated or halogenated dry cleaning solutions,
• uorocarbon refrigerants,
• hydrochloric (muriatic), sulfuric or other acids,
• uorocarbon aerosol propellants,
• vinyl plastics (when burned),
• chlorine bleach and cleaning solutions,
• titanium tetrachloride, or
• plating or etching baths or solutions.
Any of these chemicals passing through the combustion process produce acids which can corrode the heating equipment and the chimney.
If corrosion is found, an immediate investigation should be
undertaken of the entire area. Any corrosive materials should
be removed to avoid future contamination. A contaminate-free atmosphere for combustion and ventilation air must be obtained. It may be necessary to pressurize the equipment room with its own air supply. Any surface discoloration should be carefully studied as it may be caused by contaminates in the fuel, or corrosion of mild steel components of the chimney system, the breeching system, or the equipment being vented and may be indicative of deterioration of other components of the heating system.
Whenever the local atmosphere is high in pollutants, constantly or intermittently, it is recommended that the chimney components be of all stainless steel construction. When chimney is exposed to the elements, it is recommended that the outer wall be
either painted with one base coat and one nish coat of a heat
resistant primer and paint, or that the outer wall be constructed of stainless steel.
TERMINATION HEIGHT REQUIREMENTS
Model PIC/IPIC chimney is to terminate a minimum of 3’ (914) above the highest point where it passes thru a roof of a building and a minimum of 2’ (610) higher than any portion of a building within a horizontal distance of 10’ (3.05m) (See FIG. 1).
FIG. 1 - TERMINATION HEIGHT REQUIREMENTS
MORE THAN 10’ (3048)
LESS THAN
10’ (3048)
2’ (610)
3’ MIN. (914)
STRUCTURE
CHIMNEY OR VENT
CLEARANCES – BOILERS AND ENGINES
CAUTION– DO NOT ENCLOSE IN A CHASE OR PASSAGEWAY OF COMBUSTIBLE MATERIAL
For appliances operating with continuous exhaust temperatures up to 1400º F, where the chimney is installed in an open room or fully ventilated area on the same story as the appliance to which it is connected, Model PIC/IPIC Chimney shall be installed at a minimum of the clearance to combustibles as indicated in TABLE 1.
Except for installation in one or two family dwellings, a factory­built chimney that extends through any zone above that on which the connected appliance is located is to be provided with an
enclosure having a re resistance rating equal to or greater than that of the oor or roof assemblies through which it passes.
Metal-Fab Model PIC/IPIC Chimney can penetrate a combustible
roof by utilizing the Roof Support Assembly (RSA) or Ventilated Thimble Assembly (VTA). All other parts are for attachment to non-combustible construction (i.e., oor guides, wall guides,
plate or wall support assemblies).
TABLE 1 - PIC/IPIC INSTALLATION CLEARANCES
Operating Temperature
1000°F Continuous
(538°C)
1400°F Intermittent
(760°C)
Insulation Thickness
Exterior Wood Frame or Combustible Wall
Diameter: 6”
8 - 16”
24 - 26” 28 - 32”
36 - 40” 42 - 48”
Exterior Non-Combustible
Diameter: 6”
8 - 18” 20 - 42” 44 - 48”
Interior Wood or Other Combustibles
Diameter: 6”
8 - 16”
28 - 32”
36 - 40” 42 - 48”
Fully Enclosed Combustibles (UL103-HT)
Diameter: 6”-14” N/A N/A 2” (51) N/A N/A N/A
Fire Rated or Non-Combustible Chase
PIC IPIC-1
4” (102) 4” (102)
18”
5” (127)
20”
6” (152)
22”
6” (152) 6” (152) 6” (152)
34”
6” (152) 6” (152) 6” (152)
2” (51)
2” (51) 4” (102) 4” (102)
4” (102) 4” (102)
18”
5” (127)
20”
6” (152)
22”
7” (178)
24”
8” (204)
26”
9” (229)
10” (254)
34”
10” (254) 10” (254) 10” (254)
As necessary for installation and access, refer to NFPA 211.
4” (102) 5” (127) 5” (127) 6” (152)
4” (102)
4” (102) 5” (127) 5” (127) 6” (152)
1” (25) 2” (51) 3” (76) 3” (76) 3” (76) 3” (76)
1” (25) 2” (51) 3” (76)
1” (25) 2” (51) 3” (76) 3” (76) 3” (76) 3” (76) 3” (76)
IPIC-2 IPIC-4
1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25)
1” (25) 1” (25) 1” (25) 1” (25)
1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 3” (76) 3” (76)
Note: The above gures represent air space, in inches, from
outer surface to surroundings.
NOTES:
1. False ceilings are a potential hazard and require
restopping.Chimneyspassingthroughareasbetween  ceiling and roof must be installed in re-rated
enclosures in accordance with local building codes.
2. Decorative shrouds at the termination of a factory built chimney shall not be permitted per NFPA 211.
3
1400°F Continuous
(760°C)
1800°F Intermittent
(982°C)
PIC IPIC-1
4” (102) 4” (102) 6” (152) 8” (204)
9” (229) 10” (254) 10” (254) 10” (254) 10” (254) 10” (254)
2” (51)
2” (51) 4” (102) 4” (102)
4” (102) 4” (102) 6” (152) 8” (204) 9” (229)
10” (254) 10” (254) 10” (254) 10” (254) 10” (254) 10” (254)
1” (25) 2” (51) 3” (76) 3” (76) 3” (76)
3” (76) 4” (102) 5” (127) 5” (127) 6” (152)
1” (25)
2” (51)
3” (76) 4” (102)
1” (25)
2” (51)
3” (76)
3” (76)
3” (76)
3” (76)
3” (76) 4” (102) 5” (127) 5” (127) 6” (152)
IPIC-2 IPIC-4
1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25)
1” (25) 1” (25) 1” (25) 1” (25)
1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 1” (25) 3” (76) 3” (76)
Page 4
USE AND INSTALLATION OF INDIVIDUAL PARTS:
These instructions comprise both general and specic
requirements for all parts in the product line. Before specifying a design or beginning an installation, these instructions should be carefully reviewed.
PIPE WEIGHT
The average weight of the chimney, per foot of length, can be calculated using the following formula:
PIC: 0.80 x diameter = lbs per foot IPIC-1: 0.95 x diameter = lbs per foot IPIC-2: 1.05 x diameter = lbs per foot IPIC-4: 1.45 x diameter = lbs per foot
Example: 8IPIC-2: 1.05 x 8 = 8.4 lbs per foot
Chimney design should make provisions for support adequate to
ensure that chimney parts are not overloaded.
PART NUMBERS
These instructions identify Model PIC/IPIC parts by name of part
number in the text and illustrations. Actual parts also carry a ue diameter prex and a three digit “CTO” sufx which denes the
materials of construction, such as 24IPIC30-461 for a 24-inch diameter double wall pipe section 30 inches long with Type 304 stainless steel inner wall, Type 316 stainless steel outerwall and a 1” insulation. (See Table 2 for further explanations of CTO codes).
TABLE 2
1st DIGIT
(INNER WALL)
4 = 304 S/S 6 = 316 S/S
A = ALUMINIZED STEEL 4 = 304 S/S 6 = 316 S/S
2nd DIGIT
(OUTER WALL)
3rd DIGIT
(INSULATION)
0 = 1” AIR SPACE 1 = 1” INSULATION 2 = 2” INSULATION 4 = 4” INSULATION
JOINT ASSEMBLY
The Model PIC/IPIC joint sealing system is designed for quick and
easy installation. For most applications follow Steps 1 through 6. (For High Pressure applications, see additional steps.)
STEP 1
Fill the channel of the ange band with the proper sealant and install below ange of rst pipe section.
NOTE: Sealant is to be supplied by Metal-Fab. See TABLE 3 on Page 23 for number of tubes per joint.
CAUTION: THE USE OF ANY OTHER SEALANT ON THE FLANGE SURFACE WILL NEGATE ALL LISTINGS OF THE PRODUCT AND IMPAIR THE SEALING EFFECTIVENESS.
STEP 2
Apply a continuous bead of proper sealant
to one of the anges to be joined.
NOTE: For gas temperatures up to 600ºF, use P077 sealant.
For gas temperatures over 600ºF, use P071 sealant.
For high pressure applications, including ALL engine or turbine exhaust applications, use P071 sealant.
STEP 3
Join the two anged ends of
the pipe sections.
STEP 4
Install the ange band around the anges.
NOTE: Do not locate V-Clamp
hardware at the bottom side of horizontal duct joints.
When installing ange band, tap lightly with
hammer around periphery of band while tightening draw screws. This helps to align
anges for the best seal. Do not overtighten
draw screws.
NOTE: Allow sealant to cure 24 hours before operating appliances.
STEP 5 (IPIC Installations Only)
Pack the void between inner and outer
walls with insulation strips.
INSULATION STRIPS (PROVIDED)
STEP 6
Secure the outer casing with the closure band.
When system is installed outdoors, the upper side (upper half in the horizontal position) of the closure band bead
should be sealed with P077 sealant to make
the casing watertight.
For all ENGINE EXHAUST and other HIGH PRESSURE applications, perform Steps 1 through 3 above, then:
4. Install the seal clip(s) on the anges 6”, 8” and 10” only.
(See TABLE 4). Note: 6” & 8” require two seal clips located as shown.
SEAL CLIPS
SEAL CLIP BETWEEN
FLANGE AND FLANGE
BAND NOTCH
SEAL CLIP BETWEEN FLANGE AND FLANGE BAND BOLT CONNECTION
5. Install the ange band around the anges making sure the joint is located so the seal clip overlaps both edges of the joint.
6. Fill the space behind the ange band on both sides of the ange with P071 pressure sealant (See FIG. 3).
7. Pack void between inner and outer walls with insulation
strips for IPIC installations.
8. Secure the outer casing with the closure band. Apply sealant to closure band for exterior applications only.
See JOINT ASSEMBLY and FIG. 3 for llustrations of the
joining process and nished joint.
4
Page 5
TABLE 4 - SEAL CLIPS REQUIRED PER JOINT
FOR PRESSURE SEALS
Pipe Diameter No. of Clips Part No.
6”-8” 2 SCK6-8*
10” 1 SCK10
*SCK6-8 contians 2 seal clips
Properly sealed joints are gas tight and resistant to water, oil
solvents and acids (except hydrouoric).
IMPORTANT: P071 Sealant must cure at operating temperatures above 500°F at a minimum 3-hr curing time.
FIG. 3 – ASSEMBLED MODEL PIC JOINT
APPLY SEALANT BETWEEN
FLUE AND FLANGE BAND (SEE
STEP 6 ENGINE EXHAUST)
OUTER PIPE
INNER PIPE
SPACER CLIP
OUTER CLOSURE BAND
FLANGE BAND
APPLY SEALANT TO FLANGE BAND (SEE STEP 1 JOINT ASSY.)
APPLY SEALANT TO INNER PIPE FLANGES (SEE STEP 2 JOINT ASSY.)
INSULATION (IPIC ONLY)
SUPPORT LIMITS - SUPPORT SPACING
TABLE 5 provides the maximum vertical distances between
supports for various support types. Using these supports, the maximum installed chimney height is 200 feet (60.96m).
TABLE 5
Support Method Maximum Supported Height (meter)
Wall Support Pier or Appliance Outlet Plate Support Assembly Roof Support Assembly
Stack Support Assembly
Fan Adapter Plate 6”-36” dia.
PIC IPIC-1 IPIC-2 IPIC-4
40’ (12.19m) 100’ (30.48m) 100’ (30.48m)
30’ (9.1m)
100’ (30.48m)
20’ (6m)
34’ (10.4m) 85’ (25.9m) 85’ (25.9m)
25’ (7.6m)
100’ (30.48m)
6”-28” dia.
20’ (6m)
30”-36” dia.
15’ (4.6m)
30’ (9.1m) 75’ (22.9m) 75’ (22.9m)
22’ (6.7m)
100’ (30.48m)
6”-26” dia.
20’ (6m)
28”-36” dia.
15’ (4.6m)
29’ (8.8m) 73’(22.3m) 73’(22.3m)
22’ (6.7m)
100’ (30.48m)
6”-18” dia.
20’ (6m)
20”-26” dia.
15’ (4.6m)
28”-36” dia.
10’ (3m)
GUIDE SPACING
TABLE 6 provides maximum distance between guides for
chimney installed inside building. (For exterior installations, See TABLE 7 and FIG. 37.) These numbers represent ALL diameters and vary depending on the amount of insulation.
TABLE 6
Maximum Unsupported Horizontal Spacing:
PIC IPIC-1 IPIC-2 IPIC-4
Maximum Unsupported Vertical Spacing Below Roof Line:
PIC IPIC-1 IPIC-2 IPIC-4
12’-6” (3.8m) 10’ (3.1m) 9’ (2.7m) 9’ (2.7m)
25’ (7.6m) 21’ (6.4m) 19’ (5.8m) 18’ (5.5m)
TABLE 7 - PIC & IPIC-1 GUYING REQUIREMENTS
Pipe Diameter “A” “B”
6”
8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36” 38” 40” 42” 44” 46” 48”
17’ 0” (5.18m) 17’ 6” (5.33m) 18’ 6” (5.64m) 20’ 0” (6.10m) 21’ 0” (6.40m) 22’ 0” (6.71m) 23’ 0” (7.01m) 24’ 0” (7.32m) 24’ 6” (7.47m) 25’ 0” (7.62m) 26’ 0” (7.92m) 27’ 0” (8.23m) 27’ 0” (8.23m) 28’ 6” (8.69m) 29’ 0” (8.84m) 30’ 0” (9.14m) 30’ 6” (9.30m) 31’ 0” (9.45m) 32’ 0” (9.75m)
32’ 6” (9.91m) 33’ 6” (10.21m) 34’ 6” (10.52m)
8’ 6” (2.59m) 8’ 9” (2.67m)
9’ 3” (2.82m) 10’ 0” (3.05m) 10’ 6” (3.20m) 11’ 0” (3.35m) 11’ 6” (3.51m) 12’ 0” (3.66m) 12’ 3” (3.73m) 12’ 6” (3.81m) 13’ 0” (3.96m) 13’ 6” (4.11m) 13’ 6” (4.11m) 14’ 3” (4.34m) 13’ 6” (4.11m) 15’ 0” (4.57m) 15’ 3” (4.64m) 15’ 6” (4.72m) 16’ 0” (4.88m) 16’ 3” (4.95m) 16’ 9” (5.10m) 17’ 3” (5.26m)
TABLE 7 - IPIC-2 GUYING REQUIREMENTS
Pipe Diameter “A” “B”
10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36” 38” 40” 42” 44” 46” 48”
6” 8”
10’ 6” (3.20m) 12’ 0” (3.66m) 13’ 3” (4.04m) 14’ 6” (4.42m)
15’ 11” (4.85m)
17’ 0” (5.18m) 18’ 3” (5.56m) 19’ 6” (5.94m) 20’ 2” (6.15m) 20’ 9” (6.32m) 21’ 5” (6.53m) 22’ 1” (6.73m) 22’ 8” (6.91m)
23’ 4” (7.11m) 24’ 0” (7.32m) 24’ 7” (7.49m) 24’ 7” (7.49m) 24’ 7” (7.49m) 24’ 7” (7.49m) 24’ 7” (7.49m) 24’ 7” (7.49m) 24’ 7” (7.49m)
7’ 11” (2.41m)
8’ 5” (2.57m)
8’ 11” (2.72m)
9’ 5” (2.87m) 9’ 11” (3.02m) 10’ 6” (3.20m) 11’ 0” (3.35m) 11’ 6” (3.51m)
11’ 10” (3.61m)
12’ 3” (3.73m) 12’ 6” (3.81m) 13’ 1” (3.99m) 13’ 5” (4.09m)
13’ 10” (4.22m)
14’ 3” (4.34m) 14’ 7” (4.45m)
14’ 11” (4.55m)
15’ 3” (4.64m) 15’ 9” (4.80m) 16’ 3” (4.95m) 16’ 6” (5.03m) 17’ 0” (5.18m)
TABLE 7 - IPIC-4 GUYING REQUIREMENTS
Pipe Diameter “A” “B”
6”
8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36” 38” 40” 42” 44” 46” 48”
8’ 3” (2.51m) 9’ 7” (2.92m)
10’ 9” (3.28m)
11’ 11” (3.63m)
13’ 2” (4.01m) 14’ 2” (4.32m) 15’ 4” (4.67m) 16’ 4” (4.98m) 17’ 0” (5.18m) 17’ 7” (5.36m) 18’ 2” (5.54m) 18’ 9” (5.72m) 19’ 4” (5.89m)
19’ 11” (6.07m)
20’ 6” (6.25m) 21’ 0” (6.40m) 21’ 0” (6.40m) 21’ 0” (6.40m) 21’ 0” (6.40m) 21’ 0” (6.40m) 21’ 0” (6.40m) 21’ 0” (6.40m)
6’ 8” (2.03m) 7’ 3” (2.21m) 7’ 9” (2.36m) 8’ 4” (2.54m)
8’ 11” (2.71m)
9’ 6” (2.90m) 10’ 1” (3.07m) 10’ 8” (3.25m) 11’ 0” (3.35m) 11’ 6” (3.51m)
11’ 10” (3.61m)
12’ 4” (3.76m) 12’ 8” (3.86m) 13’ 2” (4.01m) 13’ 6” (4.11m)
13’ 11” (4.24m)
14’ 3” (4.34m) 14’ 8” (4.47m) 15’ 2” (4.62m) 15’ 8” (4.78m) 16’ 0” (4.88m) 16’ 5” (5.00m)
5
Page 6
CHIMNEY ABOVE ROOF
When chimney is extended above rooine, special consideration
should be given to support and guying requirements. Use of a
standard or variable pitch ashing requires that the chimney be
stabilized to resist side loading. FIG. 4 and 8 depict methods
of protecting a ashing from side loads using a full angle ring or plate support. Ventilated thimble and roof support assemblies
include lateral support rings, and additional guidance at the
rooine is not required.
FIG. 4 – FULL ANGLE RING FOR LATERAL SUPPORT
The guy ring consists of four (4) identical half rings with hardware to secure them together, two (2) half closure bands and a storm collar (FIG. 5). Select the joint where the guy ring is to be located and assemble the inner wall joint (Steps 1 to 6 under JOINT
ASSEMBLY on Page 4). Sandwich the ange band between the
guy rings with the joints of the top and bottom rings 90º apart and the cutouts aligned. Clamp the guy ring with the nuts and bolts provided. Install the half closure bands above and below the guy ring, then attach the cables or braces (See FIG. 6). Install the storm collar above the upper half closure. The collar should be
caulked with sealant to prevent water entry.
FIG. 6 – GUY RING CABLE ATTACHMENT
CLOSURE RING
STORM COLLAR
FLASHING
ROOF
ANGLE RING MUST BE USED WITH FLASHING
PIPE DIAMETER
GUY RING (GR)
Chimneys that extend above the roof, or are installed in severe weather regions, may require a guy ring (GR) to enable the chimney to resist wind loads. The guy ring is connected to the building or other structure by means of cables or braces TABLE 6 provides the spacing between guy rings and freestand height for Model PIC/IPIC Chimney.
FIG. 5 - PIC/IPIC GUY RING, EXPLODED VIEW
CASING
APPLY SEALANT BETWEEN
COLLAR & CASING
STORM COLLAR
CABLE THIMBLE
CABLE CLAMPS
NOTE: Align large holes on Guy Ring Halves during assembly.
GUY RINGS DRILLED FOR
3 OR MORE CABLES
NOTE: Cable, cable clamps and cable thimble supplied by
others.
Cable or braces (supplied by the installer) should be slightly loose to allow for thermal expansion for single guy ring installations (FIG. 8) or be equipped with tensioning springs on multiple guy ring installations (FIG. 9). To reduce the effect of thermal
expansion on the guy cables or braces, a xed-point support
(plate or wall support assembly) may be installed immediately
below the rooine as shown in FIG. 8.
NOTE: When chimney is installed outside building, adjacent to wall, spacing between guides is equal to dimension “A” in TABLE 6 (Refer to FIG. 34 on Page 15).
STORM COLLAR
GUY RING HALF RINGS (4 PCS.)
HALF CLOSURE BANDS (2 PCS.)
FIG. 7 – MAXIMUM FREE-STANDING HEIGHT ABOVE ROOF
“B”
NOTE: See TABLE 7 for “B” dimensions.
6
Page 7
FIG. 8 – GUYING FOR SINGLE SECTION
STORM COLLAR
GUY RING
FIG. 10 – HEIGHT LIMITS FOR RIGID GUYING
“B”
“B”
(ON INSIDE OF COLLAR)
USE RIGID GUYS IF
CHIMNEY IS CLOSE TO
GUY RING
OUTSIDE WALL
MAXIMUM
SPACING
5 FT.
STORM COLLAR
FLASHING
ROOF
PLATE SUPPORT
SUPPORT STEEL
(BY INSTALLER)
“A”
NOTE: See TABLE 7 for “A” and “B” dimensions.
FIG. 9 – CHIMNEY GUYING REQUIREMENTS
A PLATE SUPPORT OR WALL
SUPPORT ASSEMBLY MUST BE
USED AT ROOF LEVEL WHEN
RIGID GUYING IS USED
EXPANSION JOINT OR BELLOWS JOINT
NOTE: See TABLE 7 for “B” dimensions.
PIPE LENGTHS (9, 18, 30, 42)
Model PIC/IPIC pipe is available in 4 standard lengths: 9” (229),
“B”
18” (457), 30” (762) and 42” (1067). Pipe sections are joined,
using appropriate sealant, to make up desired length of run. These sections may be modied by use of nipples or couplings
to accept auxiliary equipment such as temperature probes or
smoke monitors. Consult factory or your local representative to obtain information regarding such modications.
“A”
DRAIN SECTION (DS)
A drain section is a special variation of an 18” (457) pipe length with provision to drain rain or condensate from the chimney. The
pipe ue is equipped with an annular catch ring and a 1” (25)
NPT nipple extending through the casing for attachment of drain piping. The drain piping should include a water leg of a height at least equal to the maximum expected operating pressure at
“A”
the appliance outlet to avoid allowing ue gases to vent through
the drain. Drain section should be installed indoors to prevent freezing (See FIG. 11).
NOTE: See TABLE 7 for “A” and “B” dimensions.
Cables should be spaced at or near 120º intervals (3 cables) or 90º (4 cables). Rigid bracing requires two (2) braces spaced between 60º and 150º apart. Maximum spacing between the
xed support and the guy ring is 5 feet when rigid bracing is used
(See FIG. 10).
FIG. 11 – DRAIN SECTION INSTALLATION
6 PIPE
DIAMETERS
OR MORE
TRAP HEIGHT EQUAL TO
MAX. APPLIANCE OUTLET
PRESSURE
1” PIPING
7
CLOSURE RING
FLASHING AND STORM COLLAR
FULL RING GUIDE
DRAIN SECTION
Page 8
STANDARD 90º TEE (90MT)
The 90º Manifold Tee (90MT) may be used to connect horizontal to vertical when a cleanout access or drain is desired. If more than 1/4” (6) of thermal expansion is expected between the
tee and the next xed support point (the appliance outlet, for
example), the tee should be protected from bending moments by use of an expansion joint or bellows joint. See the sections on
those ttings for additional information about compensation for
thermal expansion.
FIG. 12 – SUSPENDED TEE
PIPE RISER
HALF CLOSURE BAND
WALL SUPPORT ASSEMBLY
HALF CLOSURE BAND
TEE AT BASE OF RISER
DRAIN TEE CAP (TC), CLEANOUT CAP
The unused port of a tee must be closed to prevent leakage of ue gases. A drain tee cap is used to close the tee and drain
condensation or rainwater when the tee is installed at the base of a rise. When the tee is to be used for cleanout or access purpose only, a cleanout cap (TCN) is recommended. Both the drain tee cap and the cleanout cap are equipped with closures, which serve the dual purpose of maintaining the double wall clearance
to combustible and giving the cap a nished appearance.
The drain tee cap’s drain nipple must be connected to a suitable disposal point. Any rain entering the chimney will wash down
and remove any combustion residue from the chimney ue. The resulting efuent may be corrosive. The tee cap must be sealed
at the connection to the tee using the appropriate sealant for the application. This will assure that moisture will drain through the drain nipple, as intended.
45º MANIFOLD TEE (45MT), DOUBLE LATERAL (DL)
For systems where minimizing ow resistance is desirable or critical, a manifold tee having a 45º entrance to the trunk is available. When used to make 90º turns, an additional 45º
elbow is required. It is particularly important to isolate the 45º manifold tee from the effects of thermal expansion. This isolation is typically accomplished by the use of a 2-axis support (See FIG. 14). Otherwise, the installation details and precautions are similar to those for the 90º manifold tee.
PIPE SECTION
DRAIN TEE CAP
When a tee is used at the base of a riser, the preferred location for support is above the tee, thus suspending the tee (FIG. 12). If it is not possible to suspend the tee, it may be supported from the base of the tee (FIG. 13). When this type of support is necessary,
access to the drain cap may be hindered. A drain bucket should
be used under the tee to allow access to the tee cap.
FIG. 13 – BASE SUPPORTED TEE
PIPE RISER
TEE
HALF CLOSURE BAND
CLAMP RING
(SEE NOTE BELOW)
PIPE SECTION
FIG. 14 - TWO-AXIS SUPPORT METHOD
PLATE SUPPORT ATTACHED TO BUILDING STRUCTURE
WALL SUPPORT
ASSEMBLY
DRAIN BUCKET
MORE THAN 1/4” THERMAL
EXPANSION EXPECTED
BELLOWS JOINT OR EXPANSION JOINT
MULTIPLE APPLIANCE BREECHINGS (HEADERS)
When 90º or 45º manifold tees are used to manifold multiple
appliances together, it is important to make provisions for
expansion of the manifold. An expansion joint should be installed between tees (See FIG. 15). The manifold must be supported properly by means of plate supports or wall support assemblies arranged to protect the tees from bending forces.
FIG. 15 – LATERAL TEE MANIFOLD
PLATE SUPPORT
ADJUSTABLE LENGTHS OR BELLOWS JOINT
PLATE SUPPORT
90° ELBOW
HALF CLOSURE BAND
DRAIN BUCKET
STRUCTURAL STEEL STAND (BY OTHERS)
45° MANIFOLD
TEE
45° FIXED
ELBOW
OUTLET
30º, 45º OR 90º FIXED ELBOWS (30L) - (45L) - (90L)
Elbows are not designed to resist bending loads and must be protected by structural reinforcement. FIG. 16 depicts some alternative methods for protection of elbows. Elbows may be
8
Page 9
used singly or in combination to provide turns of 30, 45, 60, 75, or 90 degrees. For engine or turbine exhaust systems, it is recommended that 90º turns be accomplished by using two (2) 45º elbows or a combination of one 45º elbow and one 45º
manifold tee to minimize ow resistance.
FIG. 16 – METHODS OF STRUCTURAL REINFORCEMENT FOR ELBOWS
TABLE 8 - MINIMUM OFFSETS
MINIMUM ELBOW OFFSETS PIC & IPIC-1
PIPE DIA. “A” - 30° ELBOW “A” - 45° ELBOW
6” thru 12”
14” 16” thru 24” 26” thru 36” 38” thru 48”
6” (152) 7 3/4” (197) 7 3/4” (197) 8 1/2” (216)
11” (279)
9 7/8” (251) 14 1/8” (359) 14 1/2” (368) 16 5/8” (422) 19 3/4” (503)
PLATE SUPPORT
PLATE SUPPORT
ANGLE
45° FIXED ELBOW
ANGLE BRACING
2-45° ELBOWS REINFORCED WITH PLATE SUPPORTS
WALL SUPPORT
PLATE SUPPORT
ANGLE
45° FIXED ELBOW
ANGLE BRACING
2-45° ELBOWS REINFORCED WITH WALL SUPPORTS
CHIMNEY OFFSETS
Offsets should be avoided except when there is no other way to route the chimney. When an offset must be used, good design indicates that the angle used should be the minimum possible (See FIG. 18). If the appliance currently burns solid fuel or is capable of being converted to burn solid fuel, the offset cannot exceed 30 degrees. No more than 2 offsets (4 elbows) may be used.
FIG. 17 — MINIMUM ELBOW OFFSETS (REFER TO TABLE 8)
“A”
MINIMUM ELBOW OFFSETS IPIC-2
PIPE SIZE “A” - 30° ELBOW “A” - 45° ELBOW
6” thru 10”
12” 14” thru 22” 24” thru 34” 36” thru 46”
48”
6” (152) 7 3/4” (197) 7 3/4” (197) 8 1/2” (216)
11” (279)
12 3/4” (324)
9 7/8” (251) 14 1/8” (359) 14 1/2” (368) 16 5/8” (422) 19 3/4” (503) 23 3/4” (602)
MINIMUM ELBOW OFFSETS IPIC-4
PIPE SIZE “A” - 30° ELBOW “A” - 45° ELBOW
6”
8” 10” thru 18” 20” thru 30” 32” thru 42” 44” thru 48”
6” (152) 7 3/4” (197) 7 3/4” (197) 8 1/2” (216)
11” (279)
12 3/4” (324)
9 7/8” (251) 14 1/8” (359) 14 1/2” (368) 16 5/8” (422) 19 3/4” (503) 23 3/4” (602)
FIG. 18 – SUPPORT FOR CHIMNEY OFFSETS
VENTILATED THIMBLE ASSEMBLY
OR ROOF SUPPORT ASSEMBLY
EXPANSION JOINT
WALL SUPPORT ASSY.
30° FIXED ELBOW OR 45° FIXED ELBOW
MAX. 25 FT. (7620)
(OIL OR SOLID FUEL)
OR PLATE SUPPORT
EXPANSION JOINT
30° MAX. FOR OIL OR SOLID FUEL
30° FIXED ELBOW OR 45° FIXED ELBOW
WALL SUPPORT ASSY. OR PLATE SUPPORT
TABLE 8 indicates minimum center to center offset for two elbows connected directly to each other.
PLATE SUPPORT
45° FIXED ELBOW
EXPANSION JOINT
HALF ANGLE RING
Bracing, above and below the elbows, is needed to avoid subjecting them to bending moments. In order for bracing to be effective, it must be rigidly attached to building members or foundation. The design of the structure used to attach supports must include the weight of the sloped section and whatever additional pipe is carried by the support. Additionally, an expansion joint or bellows joint is needed between the elbows to relieve thermal expansion stresses.
9
Page 10
90º WYE (90Y)
The 90º wye is very useful when the vertical chimney is located between two appliances and a low-loss junction is desired. It is
ideal for engine with dual-exhaust connections. The wye tting
may be suspended by a plate support or roof support assembly. Expansion joints or bellows joints should be used to protect the wye from thermal expansion stresses (See FIG. 19).
FIG. 19 – 90º WYE APPLICATION, DUAL EXHAUST
90° WYE
TAPERED INCREASER
45° FIXED ELBOW
FLANGE ADAPTER
ENGINE WITH
DUAL EXHAUSTS
Installation procedure is as follows:
1. Loosen draw screw at gasket band and slide collar toward anged end of tube. Do not remove collar from tube.
2. Slide unanged end of tube into the upstream piece of pipe and make up joint between pipe and collar following the
procedures outlined under heading JOINT ASSEMBLY on Page 4.
3. Pull anged end of tube to the downstream piece of pipe and make up joint as above (See FIG. 20).
4. For IPIC, cut insulation to desired length and wrap inner pipe ensuring that it is covered completely before attaching half
jackets.
5. Wrap two half jackets around joint with bead at the
downstream end and punched edge overlapping plain edge by approximate 3/4” (19). NOTE: For horizontal installations the seams must be located at the top and bottom of the pipe, coat unpunched edge of casing with P077 sealant to waterproof the casing.
6. Install self-drilling screws (supplied with jacket) at punched
holed through both layers at overlap. Exercise care that half
jacket edges do not align with draw screws on ange bands and that no screws are installed in portion of jacket which is
over casing of adjacent pieces of pipe (See FIG. 21). The screws shipped with the expansion joint are of the correct
length to avoid penetrating the inner wall (ue) of the pipe.
Do not use any other screws to attach the casing.
EXPANSION JOINT (AL)
The expansion joint may be used to compensate for thermal
expansion and to make up odd lengths. It is essential that sufcient installed length be allowed to compensate for abnormal,
as well as normal, operating conditions. The expansion joint cannot be used to correct misalignment or to compensate for lateral movement or vibration. The use of the expansion joint in engine exhaust applications is not recommended.
An expansion joint is comprised of: (1) a collar that is 5¼” (133)
long with a ange and vee band at one end and a graphite impregnated ring gasket at the other; (2) a 30” (762) long tube, anged at one end, which ts into the 5¼” (133) collar; (3) an outer jacket consisting of two half jacket assemblies; and (4) loose insulation blanket to ll space between the tube and
casing.
FIG. 20 – EXPANSION JOINT FLUE ASSEMBLY
30” MAX. (762) OR TRIMMED AS REQ’D
8” MIN.
(203)
UNFLANGED END
INSTALLED LENGTH
3-3/4”
(95)
COLLAR
RETAINING SCREWS
FIG. 21 - EXPANSION JOINT CASING ASSEMBLY
Note: Do not screw through casing of adjacent pipe.
ADJOINING PIPE (DOWN SLOPE)
APPLY SEALANT UNDER SEAM (REF. JOINT ASSY. FOR PROPER SEALANT)
PIPE
ADJOINING PIPE (UP SLOPE)
10
Page 11
NOTES:
1. It is recommended that the pipe on both sides of the expansion joint is supported or guided to assure that the expansion joint will not bind during operation.
2. Installation of an expansion joint adjacent to ttings,
such as elbows, tees or wyes, is not recommended. However, it is not always possible to avoid these
ttings. Ifanexpansionjointmustbejoinedtooneof thesettings, theunanged endofthetubeshouldbe awayfromthettingandttedintoapipelengthinthe
manner described in the installation procedure above.
3. Expansionjointmustbeinstalledwithaangetoange
length of not more than 22”. The minimum length for installation must take into account the amount of expansion that may occur during operation. Minimum length is calculated as follows:
Expansion = Length (feet)/100 x Temperature Rise (ºF)/100
Minimum Length = Expansion + 6” (152mm)
It is recommended that the temperature used in the above formula be at least 300ºF higher than the expected normal operating temperature.
4. If inner tube is too long, it may be cut to length. Tube
must be a minimum of 8” (203) longer than ange-to­angelength.Priortoinstallationofcutpipe,removeall
burrs to ensure that interference does not occur.
5. Check gasket to ensure that it ts snugly without
binding on inner pipe.
6. Outer jacket must move during expansion or contraction. Ensure that no screws are located where the jacket overlaps the casing of the adjacent pipe and that it is loose enough to move as needed. Alignment of the bead on the jacket with the bead on the adjacent pipe will ensure that the jacket stays in the proper location.
7. Note that the expansion joint will not support any weight in the vertical position. It should not be used unless both ends of run, where an expansion joint is
installed,areanchoredasxedpoints.
FIG. 22 indicates appropriate locations for expansion joints in various orientations.
FIG. 22 – EXPANSION JOINT LOCATIONS
FLASHING
WALL GUIDE
WALL OR PLATE
SUPPORT
WALL GUIDE
FIXED POINT
PLATE SUPPORT
90° TEE
DRAIN TEE CAP
HALF OR FULL
ANGLE RING
CHIMNEY EXPANSION UP THROUGH ROOF. GUIDANCE IS REQUIRED THROUGH FLASHING OR THIMBLE
SEE TABLE 4 FOR
MAXIMUM DISTANCE
EXPANSION JOINT
ABSORBS UPWARD MOVEMENT
SEE TABLE 4 FOR
MAXIMUM DISTANCE
EXPANSION JOINT CAREFULLY ALIGNED
VARIABLE LENGTH (VL)
The function of the variable length is to make up odd lengths of
pipe, which are not to be used for expansion compensation. The use of the variable length in engine exhaust applications is not recommended. The variable length is comprised of the following
components: (1) a 3¼” (83) collar with a ange at one end used to clamp the ange at the desired length; (2) a 30” (762) long tube anged at one end, which ts into the 3¼” (83) collar; (3) an outer jacket consisting of two half jacket assemblies; and (4) loose insulation blanket to ll space between the tube and casing.
A variable length can be installed at any ange to ange length from 4”-26” (102-660). If the ue is too long to t into the adjacent section of pipe without interfering with the ow path, it should be trimmed to the desired ange to ange length plus 4” (102).
FIG. 23 VARIABLE LENGTH FLUE ASSEMBLY
30” (762) OR TRIM TO FIT
4” MIN.
(102)
UNFLANGED END
ADJOINING PIPE (UP STREAM)
Installation procedure is as follows:
1. Loosen draw screw at collar and slide collar toward anged
end of tube. Do not remove collar from tube.
2. Slide unanged end of tube into the upstream piece of pipe. Pull anged end of tube to the downstream piece of pipe and make up joint as outlined under JOINT ASSEMBLY on
Page 4.
3. Apply a thin coat of sealant, about 1” (25) wide at the plain end of the pipe where tube slides into mating pipe section. Press sealant into any gap between the tube and the mating pipe section. Apply sealant to ange of mating pipe (See FIG. 23).
4. Slide collar into position against ange of mating pipe. Fill ange band with sealant and install ange band.
5. Tighten bolts on clamp collar to complete installation. (For more positive seal, apply sealant to clamp collar slot and
ared end of collar prior to tightening bolts).
6. For IPIC, cut insulation to desired length and wrap inner pipe ensuring that it is covered completely before attaching half
jackets.
7. Wrap two half jackets around joint with bead at the
downstream end and punched edge that overlapping the plain edge by approximately 3/4”. Note: For horizontal installations, the seams must be located at the top and bottom of the pipe. Coat unpunched edge of casing with P077 sealant to waterproof the casing. Install self-drilling
screws (supplied with jacket) at punched holed through both layers at overlap. Exercise care that half jacket edges do not align with draw screws on ange bands, and that no screws are installed in portion of jacket which is over casing of
adjacent pieces of pipe (See FIG. 24). The screws shipped with the expansion joint are of the correct length to avoid
penetrating the inner wall (ue) of the pipe.
Do not use any other screws to attach the casing.
TUBE
COLLAR
ADJOINING PIPE (DOWN STREAM)
11
Page 12
FIG. 24 – VARIABLE LENGTH CASING ASSEMBLY
HALF JACKET
SCREWS
(INCLUDED)
NOTES:
1. It is recommended that the pipe adjacent to the variable length is supported or guided to prevent sagging.
2. If a variable length must be installed adjacent to a tee,
elbow,wyeorotherttingwheretubecaninterferewith ow,theunangedendofthetubeshouldbeawayfrom the tting and tted into a pipe length in the manner
described in the installation procedure under FIG. 23.
3. Avariablelengthmaybeinstalledwithaangetoange
length between 4” and 26” (102 and 660) inclusive.
4. If inner tube is too long, it may be cut to length. Tube
must beaminimumof4”(102)longerthanange to angelength.Priortoinstallationofcutpipe,removeall
burrs to ensure that interference does not occur.
5. Note that the variable length will not support any weight in the vertical position.
STEP INCREASER (SI) AND TAPERED INCREASER (TI)
Frequently, a diameter change is required in a chimney installation. To accomplish such a size change, a step increaser or tapered increaser may be used. These parts are usually used to provide an increase of size, as the name implies. However, they may be used to reduce the size of a run. Extreme caution should be exercised when reducing the size of a chimney. The resultant pressure drop may cause the chimney to mis-function and cause spillage of ue gases into the mechanical room. The step increaser should be used when the length of run available for the size change is restricted. The installed length of a step increaser is 2” (51) (See FIG. 25). The step increaser is a non-structural part and must not be subjected to loading in either the axial or lateral directions.
FIG. 25 - STEP INCREASER (SI)
INSTALLS AT 2” (51)
When sufcient length is available, use of a tapered increaser
is recommended, since it causes a considerably less pressure drop than an equivalent step increaser. The tapered increaser uses 5 inches of length per incremental diameter change. The maximum length for a tapered increaser is 30” (762) or 6 pipe sizes. A tapered increaser is considered to have the same load strength as straight pipe (See FIG. 26).
FIG. 26 - TAPERED INCREASER (TI)
“A”
STEPS
“C” =
“C”
1 2 3 4 5 6
5”
(127)
10”
(254)
15”
(381)
20”
(508)
25”
(635)
“B”
30”
(762)
TRANSITION BAND (TB)
The transition band provides the necessary increase or decrease
in casing diameter when change in insulation thickness occurs
(FIG. 27).
FIG. 27 - TRANSITION BAND (TB)
AIR FLOW
Note: Wrap pipe joint with insulation before attaching outer
casing.Caremust be takentocompletely llallgapswith
insulation.
Note: For IPIC, wrap increaser with insulation before
attachingoutercasing.Caremustbetakentocompletelyll
all gaps with insulation.
12
Page 13
PLATE SUPPORT (PS)
NOTE: See TABLE 5 for maximum supported height.
The plate support assembly is designed to provide maximal
support to vertical sections and to provide xed-point support for
horizontal sections. The plate support must be attached to the building structure or support with rigid structural members.
FIG. 29 – RESUPPORT REQUIREMENTS
FIG. 28 – PLATE SUPPORT BRACING REQUIREMENTS
“X”
BRACING
(BY OTHERS)
EXHAUST FLOW
PIPE SECTION
PLATE SUPPORT
PIPE SECTION
CLAMP RING
“X” is a minimum of 30° when bracing is used. A welded frame
must be adequately attached to structural member for framework
rigidity if bracing isn’t used.
Pipe
Diameter
PS Plate
Thickness
Bracing for (PS) Plate Support
Height of Stack
50’ (15.24m) 100’ (30.48m)
6” - 20” 3/16” (5) 1 1/4”x1 1/4”x1/8”
(32x32x3)
22” - 36” 1/4” (6) 2”x2”x1/8”
(51x51x3)
2”x2”x1/4” (51x51x6)
3”x3”x1/4” (76x76x6)
38” - 48” 1/4” (6) 3” (76) channel: 3”x1 1/2”x1/4”
(76x38x6)
Pipe
Diameter
PS Plate
Thickness
Framework for (PS) Plate Support
Height of Stack
50’ (15.24m) 100’ (30.48m)
6” - 20” 3/16” (5) 1 3/4”x1 3/4”x1/8”
(44x44x3)
22” - 36” 1/4” (6) 2”x2”x1/4”
(51x51x6)
3”x2”x3/16”
(76x51x5)
4”x3”x1/4”
(102x76x6)
38” - 48” 1/4” (6) 3” channel: 3”x1 1/2”x1/4”
(76x38x6)
When the supported section is subject to thermal expansion or is in a vertical position, so that the plate support is weight bearing, the support structure must be braced with diagonal members or gussets to prevent deection of the supported joint (See FIG. 28). Plate supports are usually located adjacent
to ttings, such as tees or elbows, to protect the tting from
expansion stresses. Chimneys heights in excess of a single plate support capability can be resupported with additional plate support(s). An expansion joint must be used between support points (See FIG. 29).
PLATE SUPPORT
EXPANSION JOINT
FULL ANGLE RINGS
200 FT. (60.96M)
MAXIMUM
PLATE SUPPORT
100 FT. (30.5M)
90° TEE
DRAIN TEE CAP
EXPANSION JOINT
FULL ANGLE RINGS
PLATE SUPPORT
TO APPLIANCE
A plate support assembly is to be attached only to
non-combustible construction such as block, concrete or steel
with clearance that is adequate for installation and access.
DO NOT ATTACH THE PLATE SUPPORT TO COMBUSTIBLE CONSTRUCTION.
For maximum support, the entire perimeter of the plate support assembly must be attached to structural framing (See FIG. 30). Structural members are supplied by the installer.
FIG. 30 – SECTIONAL DETAIL FOR PLATE SUPPORT
FLUE
CASING
CLAMP
FLANGE
BAND
STRUCTURAL BRACING
(BY OTHERS)
RING
PLATE
NOTE: Clamp ring sections and plate sections install at 90° angles.
13
Page 14
FULL ANGLE RING (FAR) AND HALF ANGLE RING (HAR)
The full angle ring is used as a guide to prevent the chimney from
exing due to lateral loading. The angle ring is split for ease of
installation. It is 1/8” larger in inside diameter than the outside diameter of the pipe to allow movement of the pipe inside the ring (See FIG. 31).
The clamp rings are installed with the splits 90º apart so that they support each other. The notches in the clamp rings are aligned
with the draw screws of the ange band. The clamp rings and full
angle ring are then bolted together with the hardware provided to form a rigid assembly (See FIG. 33).
FIG. 33 WALL SUPPORT ASSEMBLY EXPLODED VIEW
FIG. 31 – FULL ANGLE RING & HALF ANGLE RING
HALF ANGLE RING
FULL ANGLE RING
The half angle ring is used as a saddle in horizontal or sloped
runs. It may be suspended either on rigid framework or soft
frames, such as threaded rod. The half angle ring will not replace
a plate support or other xed support in horizontal runs. It should
not be used as the sole support for the chimney.
WALL SUPPORT ASSEMBLY (WSA)
A wall support assembly consists of a full angle ring, two clamp
rings, wall brackets and struts. The clamp rings sandwich a ange band at a pipe joint and are supported by the full angle
ring (See FIG. 32).
FIG. 32 – WALL SUPPORT ASSEMBLY ASSEMBLED VIEW
CLAMP RING
BRACE BRACKET
WALL BRACKET
FULL ANGLE
RING
STRUT
STRUT WALL BRACKET
When attached to a non-combustible wall, with the brackets and struts, the wall support makes up a xed-point in the chimney. An
expansion joint is required between the wall support assembly
and any adjacent xed point.
Multiple wall support assemblies may be used, in conjunction with expansion joints or bellows joints, to support chimney heights in excess of the allowable height for a single wall support assembly.
DO NOT ATTACH THE WALL SUPPORT ASSEMBLY TO COMBUSTIBLE CONSTRUCTION.
WALL GUIDE (WG)
The wall guide is designed to compliment the wall support assembly. It is used as a lateral guide to prevent the chimney
from exing due to lateral loading.
The wall guide consists of a full angle ring with wall brackets and
struts (See FIG. 34 & 35).
FIG. 34 – WALL GUIDE ASSEMBLY EXPLODED VIEW
BRACKETS
STRUT
Note: For IPIC, wrap pipe joint with insulation before attaching half closure bands.
HALF CLOSURE BAND
CLAMP FLANGE
SUPPORT RING
14
HORIZONTAL
STRUT
WALL BRACKET
FULL ANGLE
VERTICAL
STRUT
RING
Page 15
FIG. 35 – WALL GUIDE ASSEMBLED VIEW
The proper location for a wall guide is immediately below the outer closure band near a pipe joint. The outer band must be able to move away from the wall guide when thermal expansion occurs (See FIG. 36).
FIG. 36 – WALL GUIDE LOCATIONS
FIG. 37 – SPECIAL CONSIDERATIONS FOR CHIMNEY ON OUTSIDE WALL
FREE STANDING
38” THRU 48” PIC ONLY
WALL SUPPORT
6 TO 10 FEET
(1829 -3048)
WALL GUIDE
DO NOT INSTALL AN EXPANSION JOINT IN THIS AREA DUE TO BENDING FORCES
LOCATE EXPANSION JOINT OR BELLOWS JOINT BELOW WALL GUIDE
PIPE FLANGES
6”-12” (152-305)
WALL GUIDE OR FULL ANGLE RING (STRUCTURE BY OTHERS)
PIPE
DO NOT ATTACH THE WALL GUIDE TO
COMBUSTIBLE CONSTRUCTION.
SPECIAL CONSIDERATIONS
When a wall support assembly is used to support a chimney on an exterior wall, wind loading must also be considered. Below the highest wall support assembly, the chimney must be resupported at intervals not greater than 40’ (12.19m) (See TABLE 5). The chimney must be equipped with wall guides between each wall support assembly. Guide spacing is in accordance with maximum vertical spacing in TABLE 6 on Page 5. Additionally, a wall guide must be located between 6’ and 10’ (1.83m and 3.05m) below the highest wall support to stabilize the freestanding portion of the chimney above the wall support assembly (See FIG. 37).
FLOOR GUIDE (FG)
The oor guide is similar in function to a wall guide or full angle ring, but is modied specially for use at oor penetrations. The angle brackets and straps hold the guide centered in the oor
penetration (See FIG. 38). Maximum oor opening “X” is Duct I.D. + 10” (254).
FIG. 38 – FLOOR GUIDE
ANGLE BRACKET
STRAPS
ANGLE
RING
“X”
DO NOT ATTACH THE FLOOR GUIDE TO
COMBUSTIBLE CONSTRUCTION.
FLOOR
“X”
15
Page 16
STACK SUPPORT ASSEMBLY (SSA)
The stack support assembly is intended for use as a base mount for mounting the stack on a concrete oor or a structural steel
stand. It is equipped with a predrilled steel baseplate for the insertion of anchor bolts or studs. A 9-inch section of pipe is attached to the baseplate and contains a false bottom 4½” (114)
above the oor. A 1” (25) NPT nipple extends through the side of
the pipe section just above the false bottom to allow drainage of rain or condensate (See FIG. 39). It is recommended that a 90º
manifold tee with a cleanout cap be installed above the stack support to provide access to the stack.
FIG. 39 – STACK SUPPORT ASSEMBLY
1” N.P.T. NIPPLE
FIG. 41 – ROOF FRAMING FOR VENTILATED THIMBLE ASSEMBLY OR ROOF SUPPORT ASSEMBLY
“X”
“X”
Model PIC & IPIC-1 IPIC-2 IPIC-4
“X” I.D. + 8” (203) I.D. + 10” (254) I.D. + 14” (356)
The roof support assembly is a special variation of the ventilated thimble which also provides vertical support to the chimney. It is especially useful when the chimney rise below the roof is long enough to cause movement from thermal expansion to exceed approximately 2” (51).
The ventilated thimble consists of the thimble with 4 support
brackets; 2 lateral support rings, split for ease of installation; a ashing; a storm collar.
When using a stack support assembly as the stack base, it is important to use exact pipe lengths to raise the stack height to
the breeching connection point (See FIG. 40). Use of variable
lengths or expansion joints in the stack under the breeching connection defeats the purpose of the stack support assembly.
These components will not support weight.
FIG. 40 – STACK SUPPORT ASSEMBLY INSTALLATION
EXIT CONE
FULL ANGLE RING
BRACING (BY OTHERS)
90° TEE
NOTE: DO NOT USE VARIABLE LENGTH OR
BREECHING
EXPANSION JOINT BETWEEN BREECHING & STACK SUPPORT ASSY.
STACK SUPPORT ASSEMBLY
CONCRETE PAD OR STRUCTURAL BASE
VENTILATED THIMBLE ASSEMBLY (VTA) AND ROOF SUPPORT ASSEMBLY (RSA)
The ventilated thimble assembly is designed to allow Model PIC/IPIC chimney to penetrate a combustible roof at a nominal 3” clearance to combustibles. FIG. 41 illustrates the required minimum framing dimensions. The ventilated thimble is intended
for installation on a at roof. It may be used on a pitched roof if a
curb is installed at the penetration to provide a level surface for mounting the thimble.
FIG. 42 - VENTILATED THIMBLE ASSY. INSTALLATION
STORM COLLAR
FLASHING
LATERAL SUPPORT RING
SUPPORT BRACKET
THIMBLE
LATERAL SUPPORT RING
Installation of the ventilated thimble is as follows (See FIG. 42):
1. Cut the roof opening and reinforce the edges of the hole as appropriate for the expected load bearing requirements.
Attach the thimble brackets to the thimble using the
hardware provided.
2. Set the thimble through the roof, making sure it is centered in the roof penetration hole, and secure it to the roof deck with bolts or lag screws supplied. The brackets may be
welded to a metal roof, if desired.
3. Install the chimney passing through the thimble and extending above the roof.
4. Install the 2 split lateral support rings on the chimney casing, one above the thimble and one below the thimble. Leave the bolts loose enough to allow the ring to slide along the casing. The spacer tabs are to be toward the thimble.
5. Push the lateral rings along the chimney casing until they are completely enclosed in the thimble.
6. Install the ashing centered on the thimble. Secure it to the
roof and seal it to the roof membrane as appropriate.
16
Page 17
7. Install the storm collar around the chimney casing allowing the ventilation spacers on the underside of the collar to rest
on the upper edge of the ashing. Tighten the draw screw
and seal between the collar and the chimney casing with chimney sealant.
The roof support assembly consists of the same parts as the ventilated thimble except that one of the lateral rings is replaced with a vertical support ring. Installation is identical to the ventilated thimble except step 4 (See FIG. 43).
FIG. 43 - ROOF SUPPORT ASSY. INSTALLATION
PIPE O.D.
STORM COLLAR
FLASHING
1. The roof opening is sized as a at projection (See FIG. 44) to provide the correct clearance.
2. The thimble is centered in the roof hole with the two pivoting
brackets oriented parallel to the roof ridge and the hinged brackets running up and down the roof. The brackets are
secured to the roof with bolts, lag screws or welding as appropriate. Leave the bolts of the sliding mount loose until
the brackets are attached to the roof. Then tighten all bolts
and nuts.
3. Install the ashing centered on the thimble. Secure it to the
roof and seal it to the roof membrane as appropriate.
Note: The ashing pitch is xed, specify required pitch rate
with order.
FIG. 45 illustrates details of the pitched roof penetration component installation.
VERTICAL SUPPORT RING
BRACKET
LAG SCREW OR BOLT
THIMBLE
LATERAL SUPPORT RING
Install lateral support ring below thimble as per step 4 above.
Then install the vertical support ring. Vertical ring consists of 2 half-clamp rings designed to lock together when assembled.
The pipe section joint will rest on top of the assembled vertical support ring. The vertical support ring will rest on top of Thimble Flange and carries the weight of the chimney. Because it is not fastened to the thimble, the chimney can expand upward in the thimble if needed.
FIXED PITCH VENTILATED THIMBLE ASSEMBLY (FPVTA) AND FIXED PITCH ROOF SUPPORT ASSEMBLY (FPRSA)
These components are special variations of the ventilated thimble assembly. They provide the same clearance to combustibles and types of support, but are designed to be installed in pitched
roofs. Installation is similar to the at roof versions except for
the following.
FIG. 44 – ROOF FRAMING FOR VENTILATED THIMBLE ASSEMBLY OR ROOF SUPPORT ASSEMBLY
“X”
FIG. 45 – FIXED PITCH ROOF PENETRATION INSTALLATION
STORM COLLAR
PITCHED FLASHING
VERTICAL OR LATERAL
SUPPORT RING
HINGED BRACKET
PIVOTING BRACKET
THIMBLE
LATERAL SUPPORT RING
FLASHING (F) FIXED PITCH FLASHING (FPF) AND STORM COLLAR (SC)
Flashings, both standard (Tall Cone) and pitched, are intended
for installation on non-combustible roofs only. The ashing is
non-ventilated and does not provide for any reduced clearance to combustibles.
FIXED PITCH
TALL CONE
FLASHING (F)
FLASHING (FPF)
Model PIC & IPIC-1 IPIC-2 IPIC-4
“X” I.D. + 8” (203) I.D. + 10” (254) I.D. + 14” (356)
STORM COLLAR (SC)
To install the ashing, place it around the chimney. Secure and
seal it to the roof (FIG. 46).
17
Page 18
FIG. 46 – INSTALLATION OF FLASHING AND STORM COLLAR
SEALANT
DO NOT RESTRICT
VERTICAL MOVEMENT
OF FLANGE BAND
CURB
FLANGE BAND
STORM COLLAR
TALL CONE FLASHING
16 GA. PAN
FIG. 48 - STACK CAP
OPTIONAL BIRD SCREEN
CAP
CLOSURE RING (INCLUDED)
PLATE
MAINTAIN ADEQUATE EXPANSION
STRUCTURAL FRAME
With the ashing in place, the storm collar is placed around the
chimney and sealed to the casing with silicone sealer. The storm
collar should not quite rest on the ashing when the chimney is cold (1/4” gap between the collar and the top of the ashing).
When a chimney is installed with a ashing and collar rather than
a ventilated thimble, the chimney must be stabilized by installing either a full angle ring or a plate support just below the roof. If the chimney height above the plate support or full angle ring exceeds the “B” dimension in TABLE 7 on PAGE 5, it must be guyed to avoid wind damage.
CHIMNEY TERMINATIONS
STACK CLOSURE RING (CR)
The stack closure ring (FIG. 47) is the simplest method of terminating a chimney. It provides protection of the annular space between the inner and outer walls and leaves the top of the chimney open to the elements. A drain section (or tee with drain tee cap) should always be installed when a closure ring is used as a termination. The closure ring is installed on the inner wall and overlaps the outer wall. The joint at the inner wall should be sealed with chimney sealant. A closure ring may be used for either vertical or horizontal discharge.
FLANGE BAND
CLOSURE BAND
A cap is attached to the top section of pipe with a ange band
and sealant. The annular opening between the inner and outer walls of the pipe is protected with a closure ring provided with
the cap. When the chimney is terminated with a stack cap, it is
recommended that provisions be made for drainage of rain from
the base of the stack.
EXIT CONE (EC)
The exit cone (FIG. 49) is designed to produce additional gas
velocity at the chimney exit to help disperse the efuent. The
opening of the cone is based on a ratio of 0.8 times the nominal pipe diameter. Since the exit cone is an open top termination, provision for drainage is recommended. An exit cone may be used for either vertical or horizontal discharge.
FIG. 49 – EXIT CONE
APPLY SEALANT
0.8 D
FIG. 47 – STACK CLOSURE RING
STACK CAP (C)
The stack cap (FIG. 48) is designed to offer partial protection from rain entering the chimney. It is equipped with an inverted
cone to divert ue gases upward to avoid contamination of the
surrounding roof area. The cap may be equipped with a birdscreen
if desired. The stack cap is intended for use as a termination only
for a vertical discharge.
APPLY SEALANT
PIPE I.D.
STACK HEAD ASSEMBLY (SHA)
The stack head assembly is designed for free, unobstructed
venting of the chimney while providing maximal protection
from rain entering the chimney. The stack head is a “low loss” termination and is recommended by the Industrial Ventilation
Manual, 20th Edition, American Conference of Industrial Hygienists, FIG. 8-6.
For diameters 6” – 24”, the stack head adapter section is an integral component that attaches to the chimney ue using a ange band
and sealant. PSW sections are added to the desired height. A
closure ring is attached to the ue to protect the annular space
between the inner and outer walls from rain (See FIG. 50A). The
maximum free standing height of the stack head assembly is 60”
(1524). Heights above 60” (1524) will require guying.
18
Page 19
For diameters 26” thru 48” the chimney ue is terminated 9” (229)
below the required height for the installation (consult local codes).
A stack head adapter section is attached to the top section of the chimney using a ange band and sealant. A closure ring is attached to the ue to protect the annular space between the
inner and outer walls from rain. A plate support is located 6” (152)
below the top of the stack head adapter and PSW (Single Wall)
pipe, one size larger then the nominal chimney size, is attached to it. The PSW pipe is equal in height to 4 times the chimney diameter (See FIG. 50B). For guying requirements see TABLE
7 on Page 5.
Note: The structural steel supports for the stackhead are provided by the installer. The stackhead assembly is intended for use as a termination only for vertical discharge.
FIG. 50A – STACK HEAD ASSEMBLY
I.D. + 2” (51)
PSW PIPE
I.D. X 4
60” (1524) MAX FREE
STANDING HEIGHT
INTEGRAL STACK HEAD ADAPTER
FIG. 51 - MITER CUT (MC)
CLOSURE BAND
BIRD SCREEN
APPLIANCE CONNECTORS
SINGLE WALL BOILER ADAPTER (SBA)
The single wall boiler adapter is the most commonly used
appliance connector. It is designed to clamp over a shank type ue gas outlet. A thin layer of sealant, about 1” (25) wide is spread on the end of the appliance outlet shank. Then the single wall boiler adapter is placed around the shank covering the sealant.
The draw screw on the split tube is tightened to hold the single wall boiler adapter in place (See FIG. 52).
FIG. 52 – SINGLE WALL BOILER ADAPTER
CLOSURE RING
FIG. 50B – STACK HEAD ASSEMBLY
I.D. + 2” (51)
I.D. X 4
9” (229)
SUPPORT STRUCTURE TO ROOF- SUPPLIED BY INSTALLER
6” (152)
I.D.
PSW PIPE
PLATE SUPPORT
STACK HEAD ADAPTER
CLOSURE RING
ROOF
MITER CUT (MC)
The miter cut is intended for use as a termination for a horizontal discharge. It is designed to minimize the entry of rainwater when installed in the proper orientation. Note that the miter cut is a single wall part and requires a clearance of 18” (457) to combustibles.
The miter cut is equiped with a birdscreen at the short side of the miter (See FIG. 51). The miter must be installed so that the long side of miter is on the top of the pipe to afford protection from rain.
BOILER OUTLET SHANK
CLAMPING SCREW
The single wall boiler adapter is 6” (152) long. A 4” (102) long variation is available on request.
FLANGE ADAPTER (FA)
The ange adapter is intended for use as a connection to a Class 125 or 150 ANSI pipe ange. This type of connection requires a ange gasket and bolt set supplied by the installer. The gasket and bolts are typically sold by pipe, valve and ttings houses as
an “NBG” set. FIG. 53 illustrates a typical installation.
FIG. 53 – FLANGE ADAPTER
CASING CLOSURE INCLUDED
FLANGE ADAPTER
FLANGE GASKET (BY OTHERS)
BOLT AND NUT (BY OTHERS)
APPLIANCE OUTLET
19
Page 20
BOILER FLANGE ADAPTER (BFA)
The boiler ange adapter is used to connect PIC/IPIC pipe to anged appliance outlets other than those with ANSI pipe anges.
Typical use includes boilers, water heaters and connection to existing fabricated pipe. The adapter is designed to sandwich
the 1/2” inner pipe ange between the appliance outlet and the boiler ange adapter (See FIG. 54). The boiler ange adapter is
shipped with beam clips used to clamp the BFA to the appliance
ange. The connection may also be drilled and bolted or welded
if desired.
FIG. 54 - BOILER FLANGE ADAPTER INSTALLATION
CLAMP
HALF RING
BOILER OUTLET FLANGE
WALL PENETRATOR (WP)
This part is used to allow PIC/IPIC pipe to pass through non-re
rated walls at reduced clearance. It consists of a 30” (762) long
thimble with mounting brackets. The wall penetrator is mounted
as follows:
1. Cut the opening in the wall. See chart below for opening size.
2. Position the wall penetrator tube in the opening so it is centered. Secure it to the wall with bolts or lag screws (supplied.)
3. Install pipe so that it passes through the center of the wall penetrator. Install lateral braces around the pipe casing. Leave rings loose enough to slide along pipe.
4. Push the lateral rings into the wall penetrator centering the tabs within the ends of the tube.
ENGINE EXHAUST SYSTEM PRECAUTIONS
Engine exhaust systems require extra attention to support and protection detail due to the possibility of delayed fuel ignition in the exhaust system. It is important that all turns are protected as illustrated in FIG. 14, 16 & 18 or rigidly attached to structural framing or walls. FIG. 56 illustrates some of the special considerations that must be considered when designing an engine exhaust system.
FIG. 56 – ENGINE EXHAUST CONSIDERATIONS
PLATE
SUPPORT
BELLOWS
JOINT
WALL
GUIDE
PLATE
SUPPORT
BELLOWS
JOINT
WALL
GUIDE
PLATE
SUPPORT
FIXED
TEE
IMPORTANT: When installed vertically, bellows joint must not support weight of stack. Locate bellows joint near the
lowersideofxedsupportasshowninFIG.55.
The following components are primarily for use on engine or turbine exhaust systems.
3” (76) MAX. EXPANSION
3” (76) MAX. EXPANSION
PLATE SUPPORT
RELIEF
VALV E
BELLOWS JOINT
PLATE SUPPORT
HALF ANGLE
BELLOWS JOINT
MUFFLER
ENGINE
Model PIC & IPIC-1 IPIC-2 IPIC-4
“X” I.D. + 8” (203) I.D. + 10” (254) I.D. + 14” (356)
FIG. 55 - WALL PENETRATOR (WP)
COMBUSTIBLE WALLS
ATTACHED WITH 8D NAILS
4” MIN. (102)
OR #10 - 2” WOOD SCREWS (4 PLACES)
WALL PENETRATOR
BELLOWS JOINT (BJ)
Note: Standard bellows joints require greater clearance to combustibles that double wall components. See Table 9 for standard single wall and optional double wall bellows joints for clearances.
Bellows joints are recommended for vibration and expansion movement. This type of movement is typically encountered in diesel engine or turbine exhaust applications. FIG. 56 illustrates typical bellows joint locations in a diesel engine exhaust system.
NOTE: Bellows Joints are required for expansion joints in high pressure applications including engine or turbine exhaust. Systems that use Bellows Joints are to use seal clips (See TABLE 4 on Page 5) and additional joint sealant per Page 23.
20
Page 21
TABLE 9 - BELLOWS JOINT CLEARANCE
Location Size Single Wall Double Wall
Exterior
Combustible Non-combustible
6” - 48” 6” - 18”
20” - 48”
18”
2” 4”
SEE
TABLE
1
Interior
Combustible Non-combustible
6” - 48” 6” - 18”
20” - 48”
18”
2” 4”
SEE
TABLE
1
NOTE: P071 Sealant must be used for all joint connections when Bellows Joints are required. For exterior installations, sealant must be cured before exposure to moisture.
RELIEF VALVE (RV)
The relief valve is intended for use with diesel engines to provide extra protection to the pipe in case of a delayed ignition of unburned fuel in the exhaust system. It consists of a spring
loaded disk valve mounted on a ange adapter. The valve is
factory calibrated to open at 27 in. wc. The calibration nuts must not be changed or the valve may not function correctly.
The relief valve must be supported independently of the rest of the exhaust system. The best method to accomplish this is to locate a plate support at the joint between the relief valve and
the adjacent tting. It is crucial that the plate support be properly
secured to building structure so that it can withstand the forces generated in case of delayed fuel ignition (See FIG. 58).
FIG. 58 – RELIEF VALVE SUPPORT (RV)
FIG. 57 – BELLOWS JOINT LOCATION IN DIESEL ENGINE EXHAUST SYSTEM
PLATE SUPPORT PLATE SUPPORT
BELLOWS
JOINT
HALF ANGLE
BELLOWS
JOINT
LINER
TOWARD VENT
3” (76) EXPANSION
MAXIMUM
APPLIANCE OUTLET
Bellows joints may be used in either horizontal or vertical positions. It is imperative that the bellows joint be properly supported and guided in either orientation. A bellows joint is typically supported by a plate or wall support assembly on the appliance end of the bellows and guided by a full angle ring or wall guide on the exhaust end. The exhaust side guide should be located approximately 6”-12” (152-305) from the downstream end of the bellows joint.
IMPORTANT: When supporting high rise exhaust systems,
bellows joints must be located just below every xed
support to prevent compression at ambient temperatures (See FIG. 57).
Good design indicates that any section of exhaust piping over
4’ (1.2m) between xed points be equipped with a bellows joint.
A bellows joint can compensate for up to 3” (76) of expansion. The entire exhaust system should be examined to assure that bellows joints are installed in pipe runs in which 3” (76) or less of expansion is expected. For a method of calculating expansion (See NOTE 3 on PAGE 11 under expansion joints).
For example, a 60-foot run (18.3m) of exhaust pipe handling
1000º F ue gas would produce 60ft/100 X 1000ºF/100 = 6” (152)
of expansion. This run would require 2 bellows joints.
The bellows joint is lined to minimize contact between the bellows and exhaust gases. Thus, it cannot be used to correct mis-alignment. The liner extends approximately 2” (51) past one
end of the bellows joint ange. This extension should always be
toward the downstream (exhaust) side of the system to avoid
becoming an obstruction for the shockwave in the event of a
delayed ignition incident in the exhaust system.
TO VENT
TO MUFFLER
RELIEF
VALV E
PLATE SUPPORT (SECURE TO BUIDING)
METAL-FAB RECOMMENDS THAT ALL DIESEL ENGINE
EXHAUST SYSTEMS BE EQUIPPED WITH A RELIEF VALVE.
FLIP TOP (FT)
The ip top (FIG. 59) is designed to be installed either on a vertical or horizontal exhaust. If installed on a horizontal termination, the hinged side of the top must be oriented at the top of the pipe
keeping the counterweight up.
FIG. 59 – FLIP TOP (FT)
FLIP TOP
CLOSURE RING
USE OF VARIABLE LENGTH
Metal-Fab generally recommends the use of xed custom lengths where standard lengths do not work for engine exhaust
systems (See Pages 10 and 11). If a variable length must be
used, the inner tube must be installed with the anged end toward the engine. This allows an unobstructed ow path in
case of a delayed ignition occurrence.
21
Page 22
WEIGHT CALCULATIONS BY INSULATION THICKNESS FOR TABLE 4
PIC WEIGHT CALCULATIONS
Pipe IDI.D. x 0.8 =
lbs/ft 6 4.8 20 96 4 384 506.3 8 6.4 20 128 4 512 675.1
10 8 20 160 4 640 843.9 12 9.6 20 192 4 768 1012.7 14 11.2 20 224 4 896 1181.4 16 12.8 20 256 4 1024 1350.2 18 14.4 20 288 4 1152 1519.0 20 16 20 320 4 1280 1687.8 22 17.6 20 352 4 1408 1856.5 24 19.2 20 384 4 1536 2025.3 26 20.8 20 416 4 1664 2194.1 28 22.4 20 448 4 1792 2362.9 30 24 20 480 4 1920 2531.6 32 25.6 20 512 4 2048 2700.4 34 27.2 20 544 4 2176 2869.2 36 28.8 15 432 4 1728 2278.5
PipeIDI.D. x 0.95 =
lbs/ft 6 5.7 20 11 4 4 456 601.3 8 7.6 20 152 4 608 801.7
10 9.5 20 190 4 760 1002.1 12 11.4 20 228 4 912 1202.5 14 13.3 20 266 4 1064 1403.0 16 15.2 20 304 4 1216 1603.4 18 17.1 20 342 4 1368 1803.8 20 19 20 380 4 1520 2004.2 22 20.9 20 418 4 1672 2204.6 24 22.8 20 456 4 1824 2405.1 26 24.7 20 494 4 1976 2605.5 28 26.6 20 532 4 2128 2805.9 30 28.5 15 427.5 4 1710 2254.7 32 30.4 15 456 4 1824 2405.1 34 32.3 15 484.5 4 1938 2555.4 36 34.2 15 513 4 2052 2705.7
No. of ft
supported
ft. x lbs/ft =
lbs.
Safety Factor
IPIC-1 WEIGHT CALCULATIONS
No. of ft
supported
ft. x lbs/ft =
lbs.
Safety Factor
Test
lbs. x 1/.7584 =
lbs.
Test
lbs. x 1/.7584 =
lbs.
psi
psi
PipeIDI.D. x 1.05 =
lbs/ft
6 6.3 20 126 4 504 664.6
8 8.4 20 168 4 672 886.1
10 10.5 20 210 4 840 1107.6
12 12.6 20 252 4 1008 1329.1
14 14.7 20 294 4 1176 1550.6
16 16.8 20 336 4 1344 1772.2
18 18.9 20 378 4 1512 1993.7
20 21 20 420 4 1680 2215.2
22 23.1 20 462 4 1848 2436.7
24 25.2 20 504 4 2016 2658.2
26 27.3 20 546 4 2184 2879.7
28 29.4 15 441 4 1764 2325.9
30 31.5 15 472.5 4 1890 2492.1
32 33.6 15 504 4 2016 2658.2
34 35.7 15 535.5 4 2142 2824.4
36 37.8 15 567 4 2268 2990.5
IPIC-2 WEIGHT CALCULATIONS
No. of ft supported
ft. x lbs/ft =
lbs.
Safety Factor
22
Test
lbs. x 1/.7584 =
lbs.
psi
Page 23
IPIC-4 WEIGHT CALCULATIONS
PipeIDI.D. x 1.45 =
lbs/ft 6 8.7 20 174 4 696 917.7
8 11.6 20 232 4 928 1223.6
10 14.5 20 290 4 1160 1529.5
12 17.4 20 348 4 1392 1835.4
14 20.3 20 406 4 1624 2141.4
16 23.2 20 464 4 1856 2447.3
18 26.1 20 522 4 2088 2753.2
20 29 15 435 4 1740 2294.3
22 31.9 15 478.5 4 1914 2523.7
24 34.8 15 522 4 2088 2753.2
26 37.7 15 565.5 4 2262 2982.6
28 40.6 10 406 4 1624 2141.4
30 43.5 10 435 4 1740 2294.3
32 46.4 10 464 4 1856 2447.3
34 49.3 10 493 4 1972 2600.2
36 52.2 10 522 4 2088 2753.2
No. of ft
supported
ft. x lbs/ft =
lbs.
Safety Factor
Test
lbs. x 1/.7584 =
lbs.
psi
THE INFORMATION ON THIS PAGE PERTAINS TO ALL APPLICATIONS
TABLE 3 - EXPECTED NUMBER OF TUBES PER JOINT
(P071 OR P077 SEALANT)
Pipe Diameter No. of Tubes Pipe Diameter No. of Tubes Pipe Diameter No. of Tubes
6” 0.20 22” 0.33 38” 1.00
8” 0.20 24” 0.50 40” 1.00 10” 0.20 26” 0.50 42” 1.00 12” 0.25 28” 0.50 44” 1.00 14” 0.25 30” 0.67 46” 1.20 16” 0.25 32” 0.67 48” 1.20 18” 0.33 34” 0.67 20” 0.33 36” 0.67
EXPECTED NUMBER OF TUBES PER JOINT FOR PRESSURE SEALS, IN ADDITION TO THE ABOVE
Pipe Diameter No. of Tubes Pipe Diameter No. of Tubes Pipe Diameter No. of Tubes
6” 0.60 22” 1.80 38” 3.60
8” 0.70 24” 2.10 40” 3.70 10” 0.90 26” 2.20 42” 3.80 12” 1.00 28” 2.40 44” 4.10 14” 1.10 30” 2.67 46” 4.30 16” 1.33 32” 2.90 48” 4.50 18” 1.55 34” 3.00 20” 1.67 36” 3.20
(P071 SEALANT)
23
Page 24
NOTES
P.O. Box 1138 • WICHITA, KANSAS 67201
[email protected] • www.metal-fabinc.com
(316) 943-2351 • FAX (316) 943-2717
24
©2016 Metal-Fab, Inc. Form No. L2592 11/16 9602