
INSTALLATION AND MAINTENANCE
INSTRUCTIONS FOR MODELS M & MO
GAS VENTS (B-VENT)
This symbol on the nameplate
means this product is listed by
Underwriters Laboratories, Inc.
Listing No. MH7860
Testing No. 441
GENERAL:
The Model M and MO Gas Vents (B-Vent) have been
designed for use with gas burning Category I appliances.
A Category I appliance operates with a non-positive vent
static pressure and with a vent temperature that avoids
excessive condensate production in the vent.
B-Vent is of double wall construction, with the inner ue of
aluminum alloy (allowing rapid warm-up and better draft)
and the outer casing of galvanized steel or galvalume
steel.
Model M B-Vent is compatible with listed masonry relining
systems, single wall connectors and other listed gas
vents. Model M B-Vent may be used to reline masonry
chimneys (Separate instructions are available from MetalFab).
Model MO, Oval Gas Vent is designed for installation
within 2” x 4” or 2” x 6” wall studs and for venting of wall
mounted furnaces. Transition from oval to round for
lowest cost installation is easily obtained.
SAFETY:
CAUTION: UL listing is based on using B-Vent
components supplied by Metal-Fab, Inc. Performance
may be affected and a safety hazard created if parts
shown in these instructions are not used.
1. Metal-Fab B-Vent pipe and ttings were designed
and are listed to form a continuous passageway
from the gas burning appliance to the vent
termination above the roof, including the vent cap.
2. These B-Vent components are to be installed
with minimum one inch clearance to combustible
material. Strap vent in place, especially on lateral
or horizontal runs, to maintain proper clearances
to combustibles. Do not pack insulation or other
materials around the B-Vent.
3. When installing B-Vent always align “Up” arrow
away from appliance.
4. Locate vent as close as possible to appliance to
obtain maximum draft and minimize connector pipe
length.
5. For horizontal runs, maintain a pitch or rise from the
appliance. Minimum rise is 1/4 inch (6.4mm) per
foot (305 mm).
6. A B-Vent Cap should be used on all installations
to prevent back drafts and to keep out rain and
debris. The vent must extend through a ashing,
and should terminate with the lowest discharge
opening no closer to the roof than the minimum
height shown in the table below. These minimum
heights may be used provided the vent is not less
than 8’ from any vertical wall. For installations not
covered in TABLE 1, including sizes larger than
12”, the lowest discharge opening of the vent cap
should be at least 2’ above the highest point where
it passes through the roof, and at least 2’ higher
than any portion of a building within 10’ horizontally.
All gas vents extending above the roof more than 5
feet must be securely guyed or braced.
TABLE 1
Roof Pitch Minimum Height
Flat to 7/12 (305 mm) 1.0 ft
Over 7/12 to 8/12 (451 mm) 1.5 ft
Over 8/12 to 9/12 (610 mm) 2.0 ft
Over 9/12 to 10/12 (762 mm) 2.5 ft
Over 10/12 to 11/12 (991 mm) 3.25 ft
Over 11/12 to 12/12 (1218 mm) 4.0 ft
Over 12/12 to 14/12 (1524 mm) 5.0 ft
Over 14/12 to 16/12 (1829 mm) 6.0 ft
Over 16/12 to 18/12 (2134 mm) 7.0 ft
Over 18/12 to 20/12 (2286 mm) 7.5 ft
Over 20/12 to 21/12 (2438 mm) 8.0 ft
7. Vent sizing is dened by tables in NFPA54 (ANSI
Z223-1, 2015), or contact your Metal-Fab supplier.
Install in accordance with these instructions and
local code requirements.
Round Sizes 3” (76mm) - 14” (355 mm)
Oval Sizes 4” (102 mm) - 6” (152mm)
8. B-Vent is to be used to vent listed gas appliances
intended to burn only gas. Type B-Vent is NOT to
be used with the following:
A. Unlisted Gas Appliances
B. Incinerators
C. Recessed Heaters
D. Conversion Burners
E. Gas/Oil Burners
F.
Any appliance which may be readily converted
to a solid or liquid fuel.
G.
Any other appliance NOT intended to burn only
gas.
In areas where solid or liquid fuels are common,
the vent location should be marked “For use with
vented appliances burning only gas”.
9. Venting into an unlined masonry chimney may
cause condensation. Install B-Vent or MetalFab metal liner inside the chimney to prevent
condensation.
10. When installing exterior vent, not enclosed by
the structure or a chase, consult local gas utility,
appliance manufacturer, and/or authority having
jurisdiction.
11. If a power vent fan is used, make sure it is located at
the terminus (exhaust end) of vent system, so as to
maintain negative pressure within the vent.
12. A B-Vent support plate (MSP) is required if vertical
height exceeds 30 feet. Maximum of 30 feet
between supports.
INSTALLATION:
Round B-Vent
The Type M B-Vent sections and components 3”diameter use the Metal-Fab positive twist lock for
interconnections. Align the ends of the vent, push together
then twist section to lock in place. Use SureLock™ tab on
3
”- 6”
sizes only. See DETAIL 1.
SURELOCK™
TAB
LINE UP PIPE ENDS
AND PUSH TOGETHER.
TO UNLOCK, SIMPLY BEND
OUT THE TAB AND UNTWIST
TWIST TO ENGAGE TWIST
LOCK AND DEPRESS
SURELOCK™ TAB TO
SECURE PIPE SECTIONS
PATENT NO. 6811190
PULL PIPE APART
DETAIL 1 - INSTALLATION INTERCONNECTIONS
No additional fasteners are required to assure a safe
installation. It is acceptable to apply screws at the joints if
local code requires, or at the installing contractor’s option,
provided that the screws do not penetrate the ue.
1. Starting at the appliance outlet, attach the rst
section. It is acceptable to use screws to attach
the B-Vent to the appliance outlet. If the appliance
has a draft hood, the MDC draft hood connector is
attached to the top of the draft hood and the rst
B-Vent section is twist-locked to the MDC.
14”
2. If this is a single, straight up installation, and the
B-Vent must penetrate the ceiling, cut a hole in the
ceiling 2 inches (51 mm) larger than the outside
diameter (OD) of the outer casing. The B-Vent is to
be centered in this opening. When installed, check
to make sure the one inch (25.4 mm) clearance to
combustible has been maintained. (See FIGURE 1).
MC CAP
MSC STORM COLLAR
2.
1.
MF FLASHING
MAINTAIN 1” (25.4 mm)
CLEARANCE TO
COMBUSTIBLE THRU
JOIST AREA
ARROWS ALWAYS
POINT AWAY FROM
APPLIANCE FOR
EACH SECTION
NOTES:
1.
APPLY CAULKING OR METAL-FAB MST TAPE WHERE
VENT PASSES THROUGH FLASHING
2.
APPLY THICK RING OF CAULKING OR METAL-FAB MST
TAPE AROUND VENT AS SHOWN
3.
SLIDE STORM COLLAR DOWN INTO CAULKING OR
TAPE RING
UP
MSP-REQUIRED
FOR EVERY 30 FT.
OF VENT HEIGHT
MFS FIRESTOP
FIGURE 1
3. When a combustible oor is penetrated by B-Vent, a
MFS restop or MSP support plate is used to close
the opening. If the area above the ceiling is an attic,
the restop or support plate is mounted above the
joist to assure that insulation does not drop into the
joist area.
4. Continue with B-Vent penetrating the roof.
NOTE: For Canadian installations, use labeled ULC
section, designated with Sufx G, on vent
sections exposed to atmosphere.
At the roof, the opening should be 2 inches (51
mm) greater than the B-Vent OD. Above the roof,
a ashing is required to maintain the one inch (25.4
mm) clearance to the combustibles of the roof.
Installation of a storm collar allows water to
the ashing. Caulk as shown in FIGURE 1.
5. Install the B-Vent cap (MC) onto the B-Vent.
NOTE: See height of vents under “SAFETY”.
6. If a UL Listed gas vent other than Metal-Fab is to be
connected to the inlet end of the Metal-Fab B-Vent,
use the M6A, M12A, or M18A gas vent adapter.
Insert the male end of the other gas vent into the gas
vent adapter and secure by tightening the clamp on
the adapter (See FIGURE 2A). If Metal-Fab B-Vent
is to be inserted directly into the inlet end of a UL
Listed gas vent other than Metal-Fab, secure by
using three (3) 1/4 inch (6.4 mm) long sheet metal
screws. Do not penetrate the ue (See FIGURE 2B).
METAL-FAB M6A,
M12A, M18A
TIGHTEN CLAMP
TO SECURE
FIGURE 2A
FEMALE END OF GAS VENT
OTHER THAN METAL-FAB
SECURE WITH (3)
1/4” LONG SHEET
METAL SCREWS
INSERT 3/4” TO 1 1/2”
MALE END OF GAS VENT
OTHER THAN METAL-FAB
STANDARD
METAL-FAB B-VENT
INSERT 3/4” TO 1 1/2”
FIGURE 2B
3.
ROOFING TO
OVERLAP
FLASHING
BASE ON
HIGH SIDE
drain over

7. Although it is not a preferred practice, there may be
installations where B-Vent must run vertically-exterior
to the building-and wall support is needed. A wall
band (MH) or (MWB) is used by placing around
the B-Vent, then fastening to the wall. Using a wall
band assures that the clearance to combustibles is
maintained (See FIGURE 3).
a. Cut a hole in the outside wall 1/4” larger than
the diameter of the sleeve on wall thimble
b. Install the wall thimble by inserting the larger
of the two parts on the appliance side and the
other half through the outside wall.
c. Install chimney sections vertically, starting at
the tee. Attach a wall bracket every six feet to
secure the vent to the wall.
NOTE:
A minimum clearance of 1” (25.4 mm)
to combustibles is required.
(MPT).
d. Make remainder of vent installation per B-Vent
installation instructions.
1” MINIMUM CLEARANCE
MPT WALL THIMBLE
FIGURE 3
WALL BAND
MT TEE
8. When the connector from the appliance is single wall,
it must terminate into B-Vent. At this termination, it is
acceptable to secure the joint with sheet metal screws.
NOTE: Single wall connector, either rigid or exible,
cannot be enclosed within combustible
materials.
9. If the installation requires two appliances to terminate
into a common B-Vent, a B-Vent wye or tee is used.
It is recommended that the higher output appliance,
normally the furnace, insert into the bottom of the wye
or tee and the other appliance attach to the tap. To
minimize the length of run and to provide maximum
exibility in these installations, a swivel tee (MST)
or swivel wye (MSY) is used. These components
provide 360 degrees of rotation to position the tap in
the proper orientation (See FIGURE 4).
NOTE: Consult the Metal-Fab catalog for the many
variations of wyes and tees available.
SEE FIGURE 1
FOR TERMINATION
M45
SUPPORTS ON LATERAL
RUN - MAX. 5.0 FT. (1524 mm)
BETWEEN SUPPORTS
M12A OR M18A (USED TO ADJUST
FOR VARYING LENGTHS)
MSP [REQUIRED ABOVE TEE AND
EVERY 30 FT. (9144 mm)
APPLIANCE
#1
M90
MDC
DRAFT
HOOD
MST OR
MSY 360º
ROTATION
UP
APPLIANCE
#2
KEEP HORIZONTAL
LENGTH SHORT
AS POSSIBLE FOR
GOOD DRAFT
FIGURE 4
10. It is a common practice to utilize the 90 degree
adjustable elbow (M90) in the appliance area to
minimize vent run. Use of the M90 or M45/60 elbow
is acceptable and not limited to the appliance area.
11. For horizontal and lateral runs, it is recommended
that support be used every 5 feet (1524 mm).
Plumber’s straps are commonly used. They should
be positioned to maintain 1 inch (25.4 mm) clearance
to combustibles.
12. If your installation requires a change in diameter due
to vent capacity, a B-Vent increaser (MI) is available.
Installation is the same as standard B-Vent Sections.
Oval Vents
The 4MO and 5MO oval vents are listed for use in
either 2” x 4” or 2” x 6” stud walls, with restop/spacer to
maintain proper clearance to combustibles. The 6MO is
listed for use in 2” x 6” stud wall. The restop/spacer is to
be located centrally between studs spaced not less than
16” on centers. The oval vent is interlocked by pushing
together. See DETAIL 2.
PART SNAPS
WHEN ENGAGED
ALIGN AND PUSH
TOGETHER
DETAIL 2 - STYLE M OVAL INTERCONNECTIONS
The 4MO has a dual listing as MO and BW oval vent. The
4BW is used with recessed heaters with maximum output
of 85000 BTU/HR (25 KW) for single story and 65000
BTU/HR (19 KW) for multistory installations.
1. Normally the appliance outlet is of a round shape,
therefore, a B-Vent Section or Draft hood connector
(MDC) will be attached to the appliance. To
transition to oval sections, a Round to Oval Adapter
(MRO) is required. The oor and ceiling plates
must be cut away to allow placement of the oval.
To position the oval, and maintain clearance to
combustibles, a restop (MOFS) is used at the oor
and the ceiling (See FIGURE 5).
2. If the appliance is in the same room as the entry to
oval vent, the oval tee (MOT) can be installed in the
wall studs. To close the bottom of the Tee, use the
Tee Cap (MOTC). To support the tee within the wall
studs, use the Tee Support (MOTS). As the oval
vent continues upward, use the MOFS at the ceiling
level (See FIGURE 5).
SAFETY CAUTION: 5MO oval vents should not be
used in 2” x 4” stud walls when used to vent a gas
replace. In this application, install 5MO in 2” x 6”
stud wall only.
CEILING PLATE CUT
AWAY FULL WIDTH
OF STUD SPACE
BLOCKING REMOVED
SUB-FLOOR
CUT AWAY PLATES AND FLOOR
OVAL FIRESTOP
SPACERS CLOSE
OPENING BETWEEN
THE VENT AND THE
STRUCTURE AT THE
CEILING AND FLOOR
COMPLETED INSTALLATION WITH FIRESTOP SPACER
FIRESTOP SPACER
WALL TEE
TEE BASE NAILED
TO HEADER
4MOT OR 5MOT WITH TEE BASE
CEILING PLATE
STUDS
14 1/2” (368 mm)
PLATE AND FLOORING
CUT AWAY FULL WIDTH
OF STUD SPACE
FIRESTOP SPACER
NAILED TO PLATE
AND STUDS AT
FLOOR AND CEILING
OVAL GAS VENT PIPE
INTEGRAL SPACER
BE SURE LOCK
IS ENGAGED
16” MIN. FROM CEILING TO
CENTER OF TEE OPENING
FIGURE 5
BLOCKING
3. Normally, in the attic area, the oval vent transitions
back to the round using the Oval to Round Adapter
(MOR). The installation is then terminated as a
round B-Vent, as previously explained.
4. If your installation terminates as oval, the Oval
Flashing (MOF) and Oval Storm Collar (MOSC)
are shown in FIGURE 6. An Oval Vent Cap (MOC)
completes the installation.
MOC
OVAL VENT CAP
CAULK (OR MST)
FLASHING OVER
ROOFING ON DOWN
SIDE, UNDER ON
UP SIDE
MO OVAL VENT
FIGURE 6
5. Because oval vent lengths may not meet your
specic run, the Oval Adjustable Length (MOA) is
used to adjust for length differences. The female
end of the MOA accepts the male end of the Oval
Section. When the correct length is achieved, the
clamp on the MOA is tightened. The male end of
the MOA snaps into the next oval section.
6. If, within the stud wall, a direction change is required,
the 45 degree at elbow (MO45F) is available. If the
directional change occurs as the vent is exiting the
stud wall, the 45 degree standard elbow (M045S)
is used. Increasers (MOI) are available to go from
4MO to 5MO or to 6MO.
7. If the installation is with a recessed heater, the
4MOK installation kit is required. At the top of the
recessed heater mounted in the stud wall, the gasket
is applied under the base plate from the 4MOK. The
base plate is screwed to the heater outlet. The
base plate has provisions to allow 4BW vent to
snap in place. At the ceiling level, the ceiling plate
spacers are mounted to maintain proper clearances
to combustibles. At this point the installation is the
same as explained earlier (See FIGURE 7).
OPEN ATTIC OF SINGLE STORY OR
UPPER FLOOR OF MULTI-STORY BLDG.
2 x 4 STUDS
AT 16” CTRS.
RECESSED HEATER
HEADER PLATE
AT SECOND AND
SUBSEQUENT
CEILING LEVELS,
USE 4MOFS
FIRESTOP SPACER
AT FIRST CEILING
LEVEL USE 4CPS
CEILING PLATE
SPACER
HEATER
HEADER
PLATE
SEAL
SCREW
MOSC
STORM COLLAR
MOF
FLASHING
SECURE
FLASHING
ROOF - CAULK
MAINTAIN 1” (25.4 mm)
CLEARANCE TO
COMBUSTIBLES
CEILING PLATE
SPACER 4CPS
MO OVAL PIPE
OPTIONAL OVAL TO
ROUND ADAPTER
4BP BASE PLATE
4BP
BASE
PLATE
TO
FIGURE 7
MAINTENANCE:
Gas vent systems normally operate trouble free. Conduct
a yearly inspection of the system, and replace any
damaged parts.
NOTE: If extreme weather conditions occur, inspection
of all exposed vent components is necessary.
Replace any damaged parts.
©2015 Metal-Fab, Inc. Form No L041-7/18
9817