Metal-Fab 5M-KIT Installation Manual

Page 1
INSTALLATION AND MAINTENANCE
INSTRUCTIONS FOR MODELS M & MO
GAS VENTS (B-VENT)
This symbol on the nameplate means this product is listed by Underwriters Laboratories, Inc. Listing No. MH7860 Testing No. 441
GENERAL:
The Model M and MO Gas Vents (B-Vent) have been designed for use with gas burning Category I appliances. A Category I appliance operates with a non-positive vent static pressure and with a vent temperature that avoids excessive condensate production in the vent.
B-Vent is of double wall construction, with the inner ue of
aluminum alloy (allowing rapid warm-up and better draft) and the outer casing of galvanized steel or galvalume steel.
Model M B-Vent is compatible with listed masonry relining systems, single wall connectors and other listed gas vents. Model M B-Vent may be used to reline masonry chimneys (Separate instructions are available from Metal­Fab).
Model MO, Oval Gas Vent is designed for installation within 2” x 4” or 2” x 6” wall studs and for venting of wall mounted furnaces. Transition from oval to round for lowest cost installation is easily obtained.
SAFETY:
CAUTION: UL listing is based on using B-Vent components supplied by Metal-Fab, Inc. Performance may be affected and a safety hazard created if parts shown in these instructions are not used.
1. Metal-Fab B-Vent pipe and ttings were designed and are listed to form a continuous passageway from the gas burning appliance to the vent termination above the roof, including the vent cap.
2. These B-Vent components are to be installed with minimum one inch clearance to combustible material. Strap vent in place, especially on lateral or horizontal runs, to maintain proper clearances to combustibles. Do not pack insulation or other materials around the B-Vent.
3. When installing B-Vent always align “Up” arrow away from appliance.
4. Locate vent as close as possible to appliance to obtain maximum draft and minimize connector pipe length.
5. For horizontal runs, maintain a pitch or rise from the appliance. Minimum rise is 1/4 inch (6.4mm) per foot (305 mm).
6. A B-Vent Cap should be used on all installations to prevent back drafts and to keep out rain and
debris. The vent must extend through a ashing,
and should terminate with the lowest discharge opening no closer to the roof than the minimum height shown in the table below. These minimum heights may be used provided the vent is not less than 8’ from any vertical wall. For installations not covered in TABLE 1, including sizes larger than 12”, the lowest discharge opening of the vent cap should be at least 2’ above the highest point where it passes through the roof, and at least 2’ higher than any portion of a building within 10’ horizontally. All gas vents extending above the roof more than 5 feet must be securely guyed or braced.
TABLE 1
Roof Pitch Minimum Height Flat to 7/12 (305 mm) 1.0 ft Over 7/12 to 8/12 (451 mm) 1.5 ft Over 8/12 to 9/12 (610 mm) 2.0 ft Over 9/12 to 10/12 (762 mm) 2.5 ft Over 10/12 to 11/12 (991 mm) 3.25 ft Over 11/12 to 12/12 (1218 mm) 4.0 ft Over 12/12 to 14/12 (1524 mm) 5.0 ft Over 14/12 to 16/12 (1829 mm) 6.0 ft Over 16/12 to 18/12 (2134 mm) 7.0 ft Over 18/12 to 20/12 (2286 mm) 7.5 ft Over 20/12 to 21/12 (2438 mm) 8.0 ft
7. Vent sizing is dened by tables in NFPA54 (ANSI
Z223-1, 2015), or contact your Metal-Fab supplier. Install in accordance with these instructions and local code requirements.
Round Sizes 3” (76mm) - 14” (355 mm)
Oval Sizes 4” (102 mm) - 6” (152mm)
8. B-Vent is to be used to vent listed gas appliances intended to burn only gas. Type B-Vent is NOT to be used with the following: A. Unlisted Gas Appliances B. Incinerators C. Recessed Heaters D. Conversion Burners E. Gas/Oil Burners F.
Any appliance which may be readily converted to a solid or liquid fuel. G.
Any other appliance NOT intended to burn only gas.
In areas where solid or liquid fuels are common, the vent location should be marked “For use with vented appliances burning only gas”.
9. Venting into an unlined masonry chimney may cause condensation. Install B-Vent or Metal­Fab metal liner inside the chimney to prevent condensation.
10. When installing exterior vent, not enclosed by the structure or a chase, consult local gas utility, appliance manufacturer, and/or authority having jurisdiction.
11. If a power vent fan is used, make sure it is located at the terminus (exhaust end) of vent system, so as to maintain negative pressure within the vent.
12. A B-Vent support plate (MSP) is required if vertical height exceeds 30 feet. Maximum of 30 feet between supports.
INSTALLATION:
Round B-Vent
The Type M B-Vent sections and components 3”­diameter use the Metal-Fab positive twist lock for interconnections. Align the ends of the vent, push together then twist section to lock in place. Use SureLock™ tab on 3
”- 6”
sizes only. See DETAIL 1.
SURELOCK™
TAB
LINE UP PIPE ENDS
AND PUSH TOGETHER.
TO UNLOCK, SIMPLY BEND
OUT THE TAB AND UNTWIST
TWIST TO ENGAGE TWIST
LOCK AND DEPRESS SURELOCK™ TAB TO
SECURE PIPE SECTIONS
PATENT NO. 6811190
PULL PIPE APART
DETAIL 1 - INSTALLATION INTERCONNECTIONS
No additional fasteners are required to assure a safe installation. It is acceptable to apply screws at the joints if local code requires, or at the installing contractor’s option,
provided that the screws do not penetrate the ue.
1. Starting at the appliance outlet, attach the rst section. It is acceptable to use screws to attach the B-Vent to the appliance outlet. If the appliance has a draft hood, the MDC draft hood connector is
attached to the top of the draft hood and the rst
B-Vent section is twist-locked to the MDC.
14”
2. If this is a single, straight up installation, and the B-Vent must penetrate the ceiling, cut a hole in the ceiling 2 inches (51 mm) larger than the outside diameter (OD) of the outer casing. The B-Vent is to be centered in this opening. When installed, check to make sure the one inch (25.4 mm) clearance to combustible has been maintained. (See FIGURE 1).
MC CAP
MSC STORM COLLAR
2.
1.
MF FLASHING
MAINTAIN 1” (25.4 mm)
CLEARANCE TO
COMBUSTIBLE THRU
JOIST AREA
ARROWS ALWAYS
POINT AWAY FROM
APPLIANCE FOR
EACH SECTION
NOTES:
1.
APPLY CAULKING OR METAL-FAB MST TAPE WHERE VENT PASSES THROUGH FLASHING
2.
APPLY THICK RING OF CAULKING OR METAL-FAB MST TAPE AROUND VENT AS SHOWN
3.
SLIDE STORM COLLAR DOWN INTO CAULKING OR TAPE RING
UP
MSP-REQUIRED FOR EVERY 30 FT. OF VENT HEIGHT
MFS FIRESTOP
FIGURE 1
3. When a combustible oor is penetrated by B-Vent, a MFS restop or MSP support plate is used to close
the opening. If the area above the ceiling is an attic,
the restop or support plate is mounted above the
joist to assure that insulation does not drop into the joist area.
4. Continue with B-Vent penetrating the roof. NOTE: For Canadian installations, use labeled ULC
section, designated with Sufx G, on vent
sections exposed to atmosphere. At the roof, the opening should be 2 inches (51 mm) greater than the B-Vent OD. Above the roof,
a ashing is required to maintain the one inch (25.4
mm) clearance to the combustibles of the roof. Installation of a storm collar allows water to the ashing. Caulk as shown in FIGURE 1.
5. Install the B-Vent cap (MC) onto the B-Vent. NOTE: See height of vents under “SAFETY”.
6. If a UL Listed gas vent other than Metal-Fab is to be connected to the inlet end of the Metal-Fab B-Vent, use the M6A, M12A, or M18A gas vent adapter. Insert the male end of the other gas vent into the gas vent adapter and secure by tightening the clamp on the adapter (See FIGURE 2A). If Metal-Fab B-Vent is to be inserted directly into the inlet end of a UL Listed gas vent other than Metal-Fab, secure by using three (3) 1/4 inch (6.4 mm) long sheet metal screws. Do not penetrate the ue (See FIGURE 2B).
METAL-FAB M6A, M12A, M18A
TIGHTEN CLAMP
TO SECURE
FIGURE 2A
FEMALE END OF GAS VENT
OTHER THAN METAL-FAB
SECURE WITH (3) 1/4” LONG SHEET
METAL SCREWS
INSERT 3/4” TO 1 1/2”
MALE END OF GAS VENT OTHER THAN METAL-FAB
STANDARD METAL-FAB B-VENT
INSERT 3/4” TO 1 1/2”
FIGURE 2B
3.
ROOFING TO OVERLAP FLASHING BASE ON HIGH SIDE
drain over
Page 2
7. Although it is not a preferred practice, there may be installations where B-Vent must run vertically-exterior to the building-and wall support is needed. A wall band (MH) or (MWB) is used by placing around the B-Vent, then fastening to the wall. Using a wall band assures that the clearance to combustibles is maintained (See FIGURE 3). a. Cut a hole in the outside wall 1/4” larger than
the diameter of the sleeve on wall thimble
b. Install the wall thimble by inserting the larger
of the two parts on the appliance side and the other half through the outside wall.
c. Install chimney sections vertically, starting at
the tee. Attach a wall bracket every six feet to secure the vent to the wall.
NOTE:
A minimum clearance of 1” (25.4 mm) to combustibles is required.
(MPT).
d. Make remainder of vent installation per B-Vent
installation instructions.
1” MINIMUM CLEARANCE
MPT WALL THIMBLE
FIGURE 3
WALL BAND
MT TEE
8. When the connector from the appliance is single wall, it must terminate into B-Vent. At this termination, it is acceptable to secure the joint with sheet metal screws.
NOTE: Single wall connector, either rigid or exible,
cannot be enclosed within combustible materials.
9. If the installation requires two appliances to terminate into a common B-Vent, a B-Vent wye or tee is used. It is recommended that the higher output appliance, normally the furnace, insert into the bottom of the wye or tee and the other appliance attach to the tap. To minimize the length of run and to provide maximum
exibility in these installations, a swivel tee (MST)
or swivel wye (MSY) is used. These components provide 360 degrees of rotation to position the tap in the proper orientation (See FIGURE 4).
NOTE: Consult the Metal-Fab catalog for the many
variations of wyes and tees available.
SEE FIGURE 1
FOR TERMINATION
M45
SUPPORTS ON LATERAL RUN - MAX. 5.0 FT. (1524 mm) BETWEEN SUPPORTS
M12A OR M18A (USED TO ADJUST FOR VARYING LENGTHS)
MSP [REQUIRED ABOVE TEE AND EVERY 30 FT. (9144 mm)
APPLIANCE
#1
M90
MDC
DRAFT
HOOD
MST OR
MSY 360º
ROTATION
UP
APPLIANCE
#2
KEEP HORIZONTAL
LENGTH SHORT
AS POSSIBLE FOR
GOOD DRAFT
FIGURE 4
10. It is a common practice to utilize the 90 degree adjustable elbow (M90) in the appliance area to minimize vent run. Use of the M90 or M45/60 elbow is acceptable and not limited to the appliance area.
11. For horizontal and lateral runs, it is recommended that support be used every 5 feet (1524 mm). Plumber’s straps are commonly used. They should be positioned to maintain 1 inch (25.4 mm) clearance to combustibles.
12. If your installation requires a change in diameter due to vent capacity, a B-Vent increaser (MI) is available. Installation is the same as standard B-Vent Sections.
Oval Vents
The 4MO and 5MO oval vents are listed for use in
either 2” x 4” or 2” x 6” stud walls, with restop/spacer to
maintain proper clearance to combustibles. The 6MO is
listed for use in 2” x 6” stud wall. The restop/spacer is to
be located centrally between studs spaced not less than 16” on centers. The oval vent is interlocked by pushing together. See DETAIL 2.
PART SNAPS WHEN ENGAGED
ALIGN AND PUSH
TOGETHER
DETAIL 2 - STYLE M OVAL INTERCONNECTIONS
The 4MO has a dual listing as MO and BW oval vent. The 4BW is used with recessed heaters with maximum output of 85000 BTU/HR (25 KW) for single story and 65000 BTU/HR (19 KW) for multistory installations.
1. Normally the appliance outlet is of a round shape, therefore, a B-Vent Section or Draft hood connector (MDC) will be attached to the appliance. To transition to oval sections, a Round to Oval Adapter
(MRO) is required. The oor and ceiling plates
must be cut away to allow placement of the oval. To position the oval, and maintain clearance to
combustibles, a restop (MOFS) is used at the oor
and the ceiling (See FIGURE 5).
2. If the appliance is in the same room as the entry to oval vent, the oval tee (MOT) can be installed in the wall studs. To close the bottom of the Tee, use the Tee Cap (MOTC). To support the tee within the wall studs, use the Tee Support (MOTS). As the oval vent continues upward, use the MOFS at the ceiling level (See FIGURE 5).
SAFETY CAUTION: 5MO oval vents should not be used in 2” x 4” stud walls when used to vent a gas
replace. In this application, install 5MO in 2” x 6”
stud wall only.
CEILING PLATE CUT
AWAY FULL WIDTH
OF STUD SPACE
BLOCKING REMOVED
SUB-FLOOR
CUT AWAY PLATES AND FLOOR
OVAL FIRESTOP
SPACERS CLOSE
OPENING BETWEEN
THE VENT AND THE
STRUCTURE AT THE
CEILING AND FLOOR
COMPLETED INSTALLATION WITH FIRESTOP SPACER
FIRESTOP SPACER
WALL TEE
TEE BASE NAILED
TO HEADER
4MOT OR 5MOT WITH TEE BASE
CEILING PLATE
STUDS
14 1/2” (368 mm)
PLATE AND FLOORING CUT AWAY FULL WIDTH OF STUD SPACE
FIRESTOP SPACER NAILED TO PLATE AND STUDS AT FLOOR AND CEILING
OVAL GAS VENT PIPE
INTEGRAL SPACER
BE SURE LOCK IS ENGAGED
16” MIN. FROM CEILING TO CENTER OF TEE OPENING
FIGURE 5
BLOCKING
3. Normally, in the attic area, the oval vent transitions back to the round using the Oval to Round Adapter (MOR). The installation is then terminated as a round B-Vent, as previously explained.
4. If your installation terminates as oval, the Oval Flashing (MOF) and Oval Storm Collar (MOSC) are shown in FIGURE 6. An Oval Vent Cap (MOC) completes the installation.
MOC
OVAL VENT CAP
CAULK (OR MST)
FLASHING OVER
ROOFING ON DOWN
SIDE, UNDER ON
UP SIDE
MO OVAL VENT
FIGURE 6
5. Because oval vent lengths may not meet your
specic run, the Oval Adjustable Length (MOA) is
used to adjust for length differences. The female end of the MOA accepts the male end of the Oval Section. When the correct length is achieved, the clamp on the MOA is tightened. The male end of the MOA snaps into the next oval section.
6. If, within the stud wall, a direction change is required,
the 45 degree at elbow (MO45F) is available. If the
directional change occurs as the vent is exiting the stud wall, the 45 degree standard elbow (M045S) is used. Increasers (MOI) are available to go from 4MO to 5MO or to 6MO.
7. If the installation is with a recessed heater, the 4MOK installation kit is required. At the top of the recessed heater mounted in the stud wall, the gasket is applied under the base plate from the 4MOK. The base plate is screwed to the heater outlet. The base plate has provisions to allow 4BW vent to snap in place. At the ceiling level, the ceiling plate spacers are mounted to maintain proper clearances to combustibles. At this point the installation is the same as explained earlier (See FIGURE 7).
OPEN ATTIC OF SINGLE STORY OR UPPER FLOOR OF MULTI-STORY BLDG.
2 x 4 STUDS
AT 16” CTRS.
RECESSED HEATER
HEADER PLATE
AT SECOND AND
SUBSEQUENT
CEILING LEVELS,
USE 4MOFS
FIRESTOP SPACER
AT FIRST CEILING
LEVEL USE 4CPS
CEILING PLATE
SPACER
HEATER
HEADER
PLATE
SEAL
SCREW
MOSC STORM COLLAR
MOF FLASHING
SECURE FLASHING ROOF - CAULK
MAINTAIN 1” (25.4 mm) CLEARANCE TO COMBUSTIBLES
CEILING PLATE SPACER 4CPS
MO OVAL PIPE
OPTIONAL OVAL TO ROUND ADAPTER
4BP BASE PLATE
4BP BASE PLATE
TO
FIGURE 7
MAINTENANCE:
Gas vent systems normally operate trouble free. Conduct a yearly inspection of the system, and replace any damaged parts.
NOTE: If extreme weather conditions occur, inspection
of all exposed vent components is necessary. Replace any damaged parts.
©2015 Metal-Fab, Inc. Form No L041-7/18
9817
Loading...