Mestek BMS, BTS Instruction Manual

Page 1
U.S.A.
62403262 - R1
INSTRUCTION MANUAL
For installation, use and maintenance for the
5-41-5
MODELS: BMS & BTS
Direct Vent
Combined Appliance
For Heating and Domestic Hot Water
These instructions MUST be read prior to installation and
left near the appliance when the installation is completed.
Text complies with minimum size requirements.
120601
Page 2
2
SAFETY INSTRUCTIONS
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
 Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
 WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.  Do not touch any electrical switch;
do not use any phone in your building.
Immediately call your gas supplier
from a neighbors phone. Follow the gas suppliers instructions.
If you cannot reach your gas
supplier, call the fire department.
 Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
Page 3
3
These instructions must be read prior to installation. If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
Hazards and Your Safety - Hot Water Can Scald!
Water temperature over 125°F can cause severe burns instantly, or death from scalds. Children, disabled, and elderly are at highest risk of being scalded; see instruction manual before setting temperature at water heater! Feel water before bathing or showering. Temperature limiting valves are available, see manual.
If there is a smell of gas:
-Turn the gas cock off - Air the room - Do not try to light any appliances - Do not use any phone in your building - Do not touch any electrical switch - Extinguish any flames - Call immediately a licensed authorized technician or your local gas company - Follow the gas suppliers instructions - If you cannot reach your gas supplier, call the fire department.
If there is a smell of combustion products:
-Turn the unit off - Air the room - Call a licensed authorized technician.
Installation, alterations
Licensed authorized personnel must carry out the installation, calibration or alteration of the gas apparatus. Flue gas ducts must not be modified in any way. Any replaced part or packaging parts should never be left within reach of children.
Explosive products or easily inflammable products
Do not keep, use or store explosive materials or easily inflammable materials such as Gasoline, Adhesives, Solvents, Paint Thinner, Butane, Liquefied Propane, paper, etc., near the heater.
Maintenance
The user, according to the heaters operating instructions, has to keep the installation in good condition and guarantee the reliable, safe operation of the heater. At least once a year the user must call in a licensed authorized technician for routine maintenance, before using it for central heating.
Servicing Manual
When the installation and commissioning of the system has been completed, the installer should instruct the homeowner to save the installation manual near the heater so that service technicians may refer to it in the future. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. V
ERIFY PROPER OPERATION AFTER SERVICING.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
SAFETY INSTRUCTIONS
Page 4
4
GENERAL INFORMATION .................................................................................................. 4
TABLE OF CONTENTS ....................................................................................................... 4
TABLE OF CONTENTS ....................................................................................................... 5
GENERAL LAYOUT of the main components of model BMS ........................................... 6
GENERAL LAYOUT of the main components of model BTS ............................................ 8
GENERAL LAYOUT of the main components of model BTS ............................................ 9
A INSTALLATION INSTRUCTIONS .................................................................................. 10
1 Operating and adjusting the output to the radiation system ........................................ 10
2 Location ..................................................................................................................... 10
3 Installation .................................................................................................................. 10
3.1 Installation Template ......................................................................................... 10
A INSTALLATION INSTRUCTIONS .................................................................................. 11
Clearances for installation ...................................................................................... 11
3.2 Safety Relief Valve ........................................................................................... 12
3.3.1 Installation of two heaters .............................................................................. 12
3.3.2 Installation of three or more heaters ............................................................. 12
GENERAL INFORMATION
This instruction manual refers to two types of heaters, the BMS and the BTS.
BMS - this appliance is a wall mounted, direct vent space/water heater BTS - this appliance is a self standing floor model, direct vent space/water heater
Each type of heater can be of two different input power rating; a 10/20 or 15/29;
10/20 has an input power rating of 87,000 (31.6) Btu/hr (kW) 15/29 has an input power rating of 107,000 (26) Btu/hr (kW)
BMS 10/20
or
BMS 15/29
or
BTS 10/20
or
BTS 15/29
When referring to this instruction manual, be sure of which type of heater you are working with. This can be verified by referring to the data plate marked Space water heater model . This data plate is located on the bottom side of the BMS, or on the inside of the front door (internal side) of the BTS. Also verify the type of gas for which the heater is set. A label in the front of your heater states NATURAL GAS, for heaters set to natural gas, or LP GAS for heaters set to LP gas.
TABLE OF CONTENTS
Page 5
5
TABLE OF CONTENTS
3.3.3 Radiant heating installation ........................................................................... 12
................................................................................................................................12
3.3.4 Used of glycol ................................................................................................ 12
................................................................................................................................13
3.4 Domestic Hot and Cold water ........................................................................... 13
3.5 Water Hardness ............................................................................................... 13
3.6 Gas Supply ....................................................................................................... 13
3.6 Gas Supply (cont.) ............................................................................................ 14
3.7 Electrical Supply Connection ............................................................................ 14
3.8 Room Thermostat Connection ......................................................................... 14
4 VENTING SYSTEMS ................................................................................................. 16
4.1 Concentric Flue (Coaxial) ................................................................................. 16
ATTENTION !!! .............................................................................................................. 17
4.2 Split Flue ........................................................................................................... 18
4.3 Chimney Venting .............................................................................................. 18
4.5 Venting Locations - Outside Walls (Direct Venting) ......................................... 18
4.6 Kit for air intake/flue discharge ......................................................................... 18
5 REGULATING THE DOMESTIC HOT WATER ........................................................... 31
6 BURNER.................................................................................................................... 31
6.1 Changing the Gas Type.................................................................................... 31
6.2 Adjusting Gas Flow and Pressure to the Burner .............................................. 31
7 WIRING DIAGRAMS ................................................................................................. 38
9.4 Summer-Winter Mode ...................................................................................... 42
9.5 Adjusting Central Heating ................................................................................. 42
9.6 Manual Reset High-Limit Thermostat ............................................................... 42
9.7 Resetting the Ignition Module ........................................................................... 42
9.8 Heating Circulator Pump .................................................................................. 42
9.9 Shut-Down Procedure ...................................................................................... 42
9.10 Maintenance ......................................................................................................... 42
9.11 Draining water from the heater .............................................................................. 42
10 - BTS model - INSTRUCTIONS FOR USE ............................................................... 43
10.1 Start-Up Instructions ....................................................................................... 43
10.2 Checks Prior to Ignition .................................................................................. 43
10.3 Ignition Procedure .......................................................................................... 43
10.4 Summer-Winter Mode .................................................................................... 44
10.5 Adjusting Central Heating ............................................................................... 44
10.6 Manual Reset High-Limit Thermostat ............................................................. 44
10.7 Resetting the Ignition Module ......................................................................... 44
10.8 Heating Circulator Pump ................................................................................ 44
10.9 Shut-Down Procedure .................................................................................... 44
10.10 Maintenance ....................................................................................................... 44
10.11 Draining water from the heater ............................................................................ 44
E IMPORTANT INFORMATION FOR THE CUSTOMER ................................................... 48
F SPARE PARTS............................................................................................................... 49
G TECHNICAL FEATURES .............................................................................................. 50
Page 6
6
GENERAL LAYOUT of the main components of model BMS
Figure 1 - BMS Front view
Coaxial discharge
Split discharge
A = Flue discharge B = Air intake
Page 7
7
GENERAL LAYOUT of the main components of model BMS
Figure 2 - BMS Side and top views
1 Central heating supply 2 Central heating return 3 Gas inlet 4 Domestic hot water outlet 5 Cold water inlet 6 Flue gas discharge fan 7 Automatic air vent 8 Thermostat bulb pocket
9 Gas valve service switch 10 Instrument panel 11 Temperature-pressure gauge 12 Failure lamp indicator 13 Ignition and detection electrodes 14 Burner 15 Gas manifold 16 Exchanger shell clamps 17 Gas valve 18 High limit thermostat 19 Power and circulator pump switches 20 Domestic hot water priority thermostat 21 Central heating regulation knob 22 Heater temperature control 23 Electrical control board 24 Ignition module 25 Electrical plastic cover 26 Electrical junction box 27 Expansion tank 28 Pressure switch 29 Domestic water heat exchanger 30 Heat exchanger 31 Turbulator 32 Support bracket 33 Central heating regulation valve 34 Circulator pump 35 Transformer
Page 8
8
GENERAL LAYOUT of the main components of model BTS
Figure 3 - BTS Front view
Page 9
9
GENERAL LAYOUT of the main components of model BTS
1 Central heating supply 2 Central heating return 3 Gas inlet 4 Domestic hot water outlet 5 Cold water inlet 6 Flue gas discharge fan 7 Automatic air vent 8 Thermostat bulb pocket
9- ­10 Instrument panel 11 Temperature-pressure gauge 12 Failure lamp indicator 13 Ignition and detection electrodes 14 Burner 15 Gas manifold 16 - ­17 Gas valve 18 High limit thermostat 19 Power and circulator pump switches
20 Domestic hot water priority thermostat 21 Central heating regulation knob 22 Heater temperature control 23 Electrical control board 24 Ignition module 25 - ­26 Electrical junction box 27 Expansion tank 28 Pressure switch 29 - ­30 - ­31 - ­32 - ­33 Central heating regulation valve 34 Circulator pump 35 Transformer 36 Low water cut-off
A Flue discharge B Air intake
Figure 4 - BTS side view
Page 10
10
A INSTALLATION INSTRUCTIONS
1 Operating and adjusting the output to the radiation system
The COSMOGAS heater can be installed in any domestic or light commercial building where the maximum BTU/H required is not greater than 84,000 BTU/H.
The unit has a internal mixing valve (heating side only) that can be adjusted to regulate the supply water temperature delivered to the heating system. The heating system will not receive any water unless the water temperature inside of the heater is at a minimum of 140°F. The heater built-in domestic hot water priority thermostat will cease the power to the circulator until the temperature is greater than 140°F.
2 Location
This space/water heater unit is not intended for outdoor installation. Choose a location centralized to the piping system along with consideration to the vent pipe length. Additionally, you will need to place the space/water heater so that the controls, drain, inlet/outlet, and gas valve are easily accessed. Also, care must be exercised when choosing the location of this appliance, where leakage from the safety relief valves, leakage from related piping, or connections, will not result in damage to the surrounding areas, or to the lower floor of the building. No valve is to be placed between the safety relief valves and the heater. The discharge from the temperature and pressure relief valve must be conducted to a suitable place for disposal. No reducing coupling or other restriction shall be installed in the discharge line. The discharge line should allow complete drainage of both valve and line.
3 Installation
The installation must conform to local codes and ordinances or, in the absence of local codes, the
National Fuel Gas Code ANSI Z 223.1/NFPA 54 -
1984. When installed the appliance must be
electrically grounded in accordance with the
National Electrical Code, ANSI/NFPA No.70 -
1987. For Canada, the installation should conform to CGA B149.1 INSTALLATION CODES and/or local
installation codes. The gas supply piping system should be tested before the heater is connected. The heater, (complete with all its parts: external jacket, intake and discharge flue pipes, etc.), must be installed leaving a distance of at least 10 cm, (4), from sidewalls and ceiling. Installation of the BTS combi directly on combustible flooring such as carpeting shall be
installed on a metal or wood panel extending behind the full width and depth of the appliance by at least 3, (76.2 mm), in any direction or, if the appliance is installed in an alcove or closet, the entire floor shall be covered by the panel.
3.1 Installation Template
ONLY model BMS is provided with an installation
Figure 5 - Installation template, Only for model BMS
Figure 5
Page 11
11
template to facilitate proper installation alignments (See figure 5 below).
Clearances for installation
The figures 5A and 5B show the proper distances to keep from any obstacle pertaining to the support bracket (2) or to the wall.
The procedure for installing the BMS is as follow:
1) - Take the support bracket (2) and choose a position with proper clearances, as per Figures 5A & 5B. A minimum clearance of 40 (100mm) is required from the front of the heater.
WARNING: Please take caution when choosing a mounting surface for the heater. The weight of the heater with water is approximately 165 lbs. Make certain that the wall can support such weight.
2) Screw the bracket to the wall. The screws MUST screwed in correspondence of the 16" vertical studs.
3) Place the template onto the support bracket and make all rough-in holes for the piping to the heater. The hole for the coaxial flue vent kit discharge may also be cut at this time.
4) Install the heater on the support bracket and secure all of the connections.
Figure 5A - Clearances for model BMS
Figure 5B - Clearances for model BTS
A INSTALLATION INSTRUCTIONS
Page 12
12
A INSTALLATION INSTRUCTIONS
3.2 Safety Relief Valve
An ASME approved safety relief valve, (set at 30 psi), must be installed in a vertical position on the outlet side of the central heating system, and as close as possible to the heater. There must be no valves between the safety relief valve and the heater. Manually operate the safety relief valve at least once a year to ensure proper operation. Precaution must be taken prior to operating the safety relief valve, to avoid contact with hot water coming out of the safety relief valve and to prevent water damege. If the safety relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the safety relief valve.
3.3 Heating Supply and Return
The central heating supply and return pipes are marked with different colored caps, (supply red and return blue). If there are any heating elements above heater level, it is advisable to install a check valve on the supply pipe to prevent natural circulation phenomena from occurring. If the heater is to be connected to an existing system it is advisable to wash out and remove any deposits from inside the existing pipes, and install a filter at the lowest point to trap any additional impurities when it is running. This equipment is designed for use in a closed loop system. Installation schematics are found in figures 23 to 28. WARNING !!! All the schematics in figures 23 to 28 are only samplesl. Safety apparatus, pipe diameters, and auxiliary accessories, must be verified by a qualified personnel only and in accordance with the national and/or local codes.
3.3.1 Installation of two heaters
Iinstalling two heaters in parallel. Follow the schema in the figure 23
3.3.2 Installation of three or more heaters
Installing three or more heaters in parallel. Follow the schema in the figure 24
3.3.3 Radiant heating installation
When the heater is used in conjuction with radiant heating, it is imperative that the tubing contains an oxygen diffusion barrier. If you are unsure whether or not the tubing has a barrier, a heat exchanger must be used to protect the heater from oxygen corrosion (See figure 25). This situation will also occur if the heater is used on an open-loop system where new, cold-fill water is introduced into the system. The oxygen will remove itself from solution and react chemically with the ferrous components (i.e. steel), causing them to rust and corrode. THIS TYPE OF FAILURE IS
NOT COVERED BY THE WARRANTY!
3.3.4 Used of glycol
If glycol is used with the heater, the glycol must be recognized as safe or approved by the United States Food and Drug Administration for food contact as listed in Code of Federal Regulations, title 21, part 182 of the Food Additive Regulations. Any additives introduced into the heating system must be recognized as safe by the United States Food and Drug Administration. If a
non-approved additive is used, it can cause serious health problems or possibly death.The pressure of the heating system
side of the heater must be fitted with devices (automatic water feed/pressure reducing valve not to exceed 30 psi) arranged to function automatically in order to maintain the pressure of the heating side at a level below that of the potable water leaving the heat exchanger.
3.4 Domestic Hot and Cold water
The domestic hot water flow restrictor must be installed on the cold water inlet, (Refer to figure 25, 26, 27 and 28). For servicing purposes, install a shut-off valve upstream from the cold water inlet.
Page 13
13
The heaters thermostat can be regulated to provide domestic hot water between 100°F and 180°F. Water temperature over 125°F can cause severe burns instantly. Since it is required that the heater water temperature reach above 140°F in order for the heating system side of the unit to operate, it is
imperative that a mixing valve be installed external of the heater to further regulate the temperature of the domestic hot water (See figures 23, 25, 26, 27 and 28). Failure to install a domestic side mixing valve will result in severe burns!
Piping and components connected to the water heater for space heating shall be suitable for use with potable water, and shall not be connected to any heating system or components previously used with a non­potable water heating appliance. The domestic hot water circuit needs an ASME approved temperature and pressure P-T relief valve, set at 150 psi and 210°F, installed as close as possible to the heater.
There must be no valves between the P-T relief valve and the heater. The P-T relief valve discharge pipe must not be restricted or plugged.
3.5 Water Hardness
In hard water areas (above 150 p.p.m), it is recommended that a suitable water treatment device (softener with filters) be installed. Excessive buildup of minerals in the heat exchanger can cause a non-warranty failure. Water hardness can be determined by using the standard test or by checking with your local water authority. Toxic chemicals, such as used for heater treatment, should not be introduced into the potable water used for space heating.
3.6 Gas Supply
Before making any gas connections, verify that the heater is being supplied with same gas type as indicated on the rating plate. The rating plate is located on the front of the BMS, and is located on the front door of the BTS.
This heater has orifices which will operate at an altitude of up to 2,000 feet. For installations in higher elevations, down-rate the heater by 10%. Install a manual gas cock outside of the heater. Refer to Figures 1 and 3, item 3, for the gas inlet location of the heater. Gas piping to the heater must be sufficient to guarantee a supply of gas to meet maximum requirements. See Table 1 for max. and min. values of gas pressure (Back of manual).
All piping must comply with local codes and ordinances or with the National Fuel Gas Code, (ANSI Z223.1 NFPA No. 54), whichever applies. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psig, (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig, (3.5 kPa).
Page 14
14
A INSTALLATION INSTRUCTIONS
Length of Gas Pipe Capacity of Gas Pipe Size in MBTUH
1/2" 3/4" 1" 1 1/4" 10' 132 278 520 1050 20' 92 190 350 730 30' 73 152 285 590 40' 63 130 245 500 50' 115 215 440 75' 93 175 360 100' 79 150 305 150' 64 120 250 Additional length to be added for 1.3' 1.7' 2.2' 2.7' each bend or tee
3.6 Gas Supply (cont.)
3.8 Electrical Supply Connection
The heater must be connected to a 115V 60Hz, single phase electrical supply fused to 15 amps, Grounding is required as well as the installation of a main emergency switch immediately upstream from the heater. An electrical junction box (see figures 1 and 3, item 26) is provided for connections for both the line voltage of 115V 60 Hz (See figure 6 item A) , and the room thermostat at low voltage of 24Vac (See figure 6 item B). The cable wire of the line voltage must be insered into the heater, through the pass­cable positioned in the side of the idraulic connections (see figure 7 and 8).
A Electrical supply
connection
B Room thermostat
connection
Figure 6 - Connecting the room thermostat and electrical supply
3.7 Room Thermostat Connection
This is installed by removing the electrical junction box cover indicated in fig.6, (see fig.1 and 3, item 26), and connecting the two wires of the room thermostat, or zone valve control thermostat, to the low voltage terminals, (figure 6, item B). NOTE: first remove factory installed jumper from terminals. The room thermostat must always be located in a point of the house where the temperature is not subject to sudden changes.
Page 15
15
A INSTALLATION INSTRUCTIONS
Figure 6A - Installation of the electrical supply cable on the model BMS
a) Remove or loosen screw (2) b) Pop- out the passage tunnel for the supply cable. Pass the supply cable through the passage (1) c) Connect the supply cable to the junction box d) Tighten screw (2); e) Re-insert the passage tunnel into its position (4). f) Feed wire to junction box and connect as shown in Figure 6.
Figure 6B - Installation of the electrical supply cable on the model BTS
a) Remove or loosen screw (2) b) Pop- out the passage tunnel for the supply cable. Pass the supply cable through the passage (1) c) Connect the supply cable to the junction box d) Tighten screw (2); e) Re-insert the passage tunnel into its position (4). f) Feed wire to junction box and connect as shown in Figure 6.
Page 16
16
A INSTALLATION INSTRUCTIONS
4 VENTING SYSTEMS
This heater can be fitted with either a concentric or split type venting system. Particular attention must be taken when installing the vent pipes that go through the wall to the outside. It must always be possible to carry out routine maintenance operations of the flue. The vent pipe must be installed in such a way that it can be removed, if needed, in the future. Hence, a suitable sheath should be prepared in which to insert the vent pipe. Both venting systems are suitable for venting through a wall 1 to 24 thick. The connection of the vent air intake system to the heater can turn 360°, which means in all directions, making installation extremely easy. To turn it just loosen the securing screws on the base of the vent elbow where it attaches to the heater, turn to desired position, then tighten the screws without forcing them. You must place the terminal in an open area, and follow the following guidelines:  Make certain that exhaust gas does not re-circulate back into the intake pipe.  Never vent into a walkway or patio area, or an alley, or otherwise public area less than 7ft from the ground level. This is to prevent anyone from walking into the vent;  Never vent over or under a window or over a doorway;  Never install a heat saver or similar product to capture waste heat from exhaust;  Always have vent 1ft above ground level, away from shrubs and bushes.  Follow local gas codes in your region or refer to National Fuel Gas Code, or Can
B149.1 INSTALLATION CODES.
Always have vent at least 3ft from an inside corner of outside walls.  Maintain at least 4ft clearance to electric, gas meters and exhaust fans.  Always place screens in all openings in intake and exhaust to prevent foreign matter from entering the heater.  The vent terminals, (concentric, split type exhaust), must be a minimum of 1ft above the ground level.  If split type vent will be venting into a chimney, make certain that no other appliances are vented into it. This power-
vented heater must not share a chimney. Vent exhaust terminal should be inserted into, but not beyond, inner wall of chimney. Do not vent into transient pipe. Warranty will be void.
CAUTION! - Take all precautionary measures to allow the angle of the flue to run down slightly to the outside, NEVER rising. Anticipate for all horizontal pipes, an inclination of 1/4 per foot toward the discharge. If a vertical pipe follows a horizontal one, place a condensation discharge fitting in the lowest part of the vertical pipe. A condensation discharge pipefitting must also be used for vertical discharge pipe installations directly from the heater with a pipe whose length is more than 10. During normal operating conditions, the heater will have exhaust gases exiting from the flue pipe. The smoke will be heavier on some days than on others. This is due to the outdoor weather conditions (the temperature, humidity, etc.), and is extremely common.
4.1 Concentric Flue (Coaxial)
The (Coaxial) concentric vent, (air inlet and flue outlet), system consists of 2 pipes: the outer one for fresh air intake, the inner pipe for flue exhaust discharge. With optional pipe, it is possible to increase the overall length up to 15ft (4.5 m). There are also 90° concentric elbows available, if they are installed, there will be a loss of draught equal to that caused by 3ft, (1 m), of straight pipe. Connections between the various parts must be secured by using self-tapping screws, (see fig.9). The vents stainless steel end terminal must always come completely out of the outer pipe. If for any reason the intake grid is
Page 17
17
blocked, the heater will not receive enough air for combustion and the burner would fail to ignite.
ATTENTION !!!
We want to remember that all accessories in the line of the air intake and in the line of flue discharge MUST be secured with screws beetween them, and MUST be sealed from flue or air leakage
PRECAUTION TO BE TAKEN
WHEN INSTALLING COAXIAL
VENTING
Proper assembly and installation of venting elbows and tubing must include the use of self-tapping screws to permanently secure in place the internal discharge tube. Self-tapping
screws are used to insure that the discharge vent tube remains in place and not allow discharge gases to re-enter the heater. Failure to secure the internal discharge tube may result in the heater backfiring and causing permanent damage to the heat exchanger. Heaters which have been damaged for this reason are not covered in our limited warranty. The stainless steel (End terminal) wind guard must fit properly and inter-lock into slip joint of intake pipe. It is imperative that the internal discharge pipe first be secured in place with self­tapping scews before attaching and securing the external vent pipe. Also, ensure that the two grids of the end terminal come completely out of the outer pipe. If the intake grid is hidden the heater will not receive enough air for combustion and would fail to ignite.
Picture # X: First, insert the vent inner pipe into the vent elbow and tighten using self­tapping screws
Picture # Y: Second, fit the outer pipe and secure it with proper screws See drawings below.
K = Screws provided L = Inner pipe M = Screws provided
A INSTALLATION INSTRUCTIONS
Page 18
18
A INSTALLATION INSTRUCTIONS
N = This position shall be respected O = Discharge grid P = Intake grid
4.2 Split Flue
The split flue vent system (two separate pipes) can be extended (on the discharge side only) up to a total length of 20 ft (6 m). Changes in direction can be obtained by using 90° and 45° elbows. If they are installed, there will be a loss of draught equal to 3ft (1 m) and 1 1/2ft (0.5 m) of straight pipe, respectively. This is valid only for pipes and elbows manufactured by Cosmogas s.r.l.. If the heater is installed in a large open area such as a full basement or alcove, the combustion air could also be supplied without the intake pipe, (For model BMS see figures 8, 11, 12, 13 and 14 or for model BTS see figures 16, 18, 19 and 20 for model BTS). NOTE: The heater will draw all air for combustion through the top of the unit from the space around the heater. Ventilation should be adequate to provide sufficient air to properly support combustion. Air for combustion and room ventilation must be obtained from spaces freely communicating with the outdoors. Air openings to the room should not be obstructed. For heaters in confined rooms, two permanent openings must be provided - one within 12 of the ceiling and one within 12 of the floor. Each opening must be at least one square inch per 1,000 BTU/H heater input, but not less than 100 square inches. These openings must freely connect with areas having adequate infiltration to the outside. When all air provided is supplied from the outdoors, the openings, as described above, shall be of the size listed below for each particular arrangement:
- All ducting shall be the same size as the opening which it is to be connected.
- One square inch of free area per 4,000 BTU/ H of heater input for direct outdoor air supply through an outside wall or vertical duct directly outside.
- One square inch of free area for every 2,000 BTU/H of heater input for direct outdoor air
through horizontal ducting.
Caution! The discharge pipe temperature is above 250°F while functioning, therefore it is essential that a thermal insulation protection sheath be used in the wall opening.
4.3 Chimney Venting
If split type vent will be venting into a chimney, make certain that no other appliances are vented into it. This power-vented heater must not share a chimney. Vent exhaust terminal should be inserted into, but not beyond, inner wall of chimney.
Do not vent into transient pipe. Warranty will be void.
4.5 Venting Locations - Outside Walls (Direct Venting)
The center line of the vent opening must be at least 16 1/2 above grade, outside, and at least 12 from any other building openings (doors, windows, etc.). Make sure that vent pipe is pitcheed down from the unit toward the outside wall 1/4 per foot. This will prevent any water from running back into the heater. Do not locate the vent terminal where flue products could strike against building materials and cause corrosion.
4.6 Kit for air intake/flue discharge
For comfort for the installer, COSMOGAS has created some flue kit, complete of all the necessary components for flue discharge and air intake. The four kits available are as follows:
Page 19
19
P/N 62617168. Split vent kit. This kit is for take the air from the room where the heater is installed, and discharge the flue outside from the building. The pipe of discharge is length 2.5ft.. If you need extensiones or elbows or other accessories, refer to figures R, S and T. This kit can be used for heaters model BMS and BTS.
P/N 62617174. Coaxial Vent & Elbow Kit. This kit is for taking and discharging air from/ to the outside of the building. The pipe of discharge length is 3ft. If you need extensions, elbows or other accessories, refer to figures O, P and Q. This kit can be used for heaters model BM and BTS. To discharge the flue in vertical position you must to use a roof vent terminal 62617070, (see figure P)
P/N 62617175. Coaxial Vent & Straight Adapter Kit. This kit is for taking and
discharging air from/to the outside of the building. The pipe of discharge length is 3ft. If you need extensions, elbows or other accessories, refer to figures O, P and Q. This kit can be used for heaters model BM and BTS. To discharge the flue in vertical position you must to use a roof vent terminal 62617070, (see figure P)
P/N 62630046. Vent Adaptor for 3" Discharge pipe. This kit is for to connect only
the flue discharge to a commercial 3 pipe. This kit must be used toghether with a heater mounted adapter P/N 62617124 or
62617060. With this configuration, the installer is responsible for the materials used and for the installation. In any case follow the national or local codes..
A INSTALLATION INSTRUCTIONS
Page 20
20
Besides the kits COSMOGAS has a series of accessories, that in conjonction with the kits, give the installer the possibility of many configuration of flue discharge and/or air intake. See exemples to the figures O, P, Q, R, S, T, U and V. Please remember that these configurations are only examples, and that many other possibilities exist.
Reference P/N Description 1 60702011 Washer for split 2 60702012 Washer for coaxial 3 61302011 Split system Roof terminal D. 80 4 62617010 Plug for flue test 5 62617049 3ft coaxial Extension 6 62617053 Split system Roof terminal D. 80 7 62617056 Split system In-Line Elbow FF 90° 8 62617058 Split system In-Line Elbow MF 90° 9 62617060 Coaxial elbow (Heater Mounted Only) 10 62617062 Split system Viking 11 62617063 Silicone Coupling + clamp 12 62617070 Coaxial Roof Terminal 13 62617077 In-Line Elbow 90° M/F (Coaxial) 14 62617086 3ft Extension for split system 15 62617087 Coaxial 3 ft vent, (End-Terminal only) 16 62617124 Straight coaxial Adapter (Heater mounted only) 17 62617159 In-Line Elbow 45° M/F (Coaxial) 18 62617168 Split vent kit 19 62617172 Coaxial 60/100 condensing trap 20 62617173 Split-vent D.80 condensing trap 21 62617174 Coaxial Vent & Elbow Kit 22 62617175 Coaxial Vent & Straight Adapter Kit 23 62630046 Vent Adaptor for 3" Discharge pipe 24 61302003 Intake grid D.80 25 61302004 Terminal vent D.80 26 62617059 In-Line elbow 45° M/F (for split) A not available Flat for roof B not available Condensate discharge C not available Terminal vent for roof (3 diameter) D not available Extension (3 diameter) E not available Tee raccord (3 diameter) F not available Condensate discharge with siphon (3 diameter) G not available In-Line Elbow 90° (3 diameter)
In the following pictures, the P/N 62617062 is repeated 4 times to show all of the possibilities that has this accessory has. It can be rotated 360° under the heater, and its elbows can also be rotated 360° to direct air intake and flue discharge in all orientations.
A INSTALLATION INSTRUCTIONS
Page 21
21
A INSTALLATION INSTRUCTIONS
Page 22
22
A INSTALLATION INSTRUCTIONS
Page 23
23
Some exemples of vent make with the kits predisposed by COSMOGAS P/N 62617168, P/N 62617174 e P/N
62617175.
Figure L
62617168
Figure M
Figure N
62617174 62617175
A INSTALLATION INSTRUCTIONS
Page 24
24
Some exemples of vent make with some accessories (Figure O and P) or with the combination of a kit P/N 62617174 and some accessories #13 and #5 (Figure Q).
Figure O
Figure P
Figure Q
A INSTALLATION INSTRUCTIONS
Page 25
25
Some exemples of vent make with some accessories for split and a kit for split. In all figures (R, S and T) we have used a kit 62617168 in combination with accessories for split system.
Figure R
Figure S
Figure T
A INSTALLATION INSTRUCTIONS
Page 26
26
Some exemples of vent make with a 3 commercial pipe. In the figure U we have a BMS heater, with elbow raccord #9, and with a kit #23 for to connect your 3 pipe. In the figure V, we have a BTS heater with with an straight raccord #16 and with a kit #23 for to connect your 3 pipe.
A INSTALLATION INSTRUCTIONS
Page 27
27
Wall
Figure 8 - Side view of BMS heater
39,8"
(1010)
> 4"
(100)
A - Securing screws B - Discharge pipe C - Intake pipe D - Discharge grid E - Intake grid
Figure 9 -Concentric flue (Coaxial) pipe position. For BMS model
Figure 7 - Top view of BMS heater
Figure 10- Example of air intake and flue gas discharge through the roof. For BMS model
A Condensate drainage pipe fitting B Condensate drainage tap
A INSTALLATION INSTRUCTIONS
Page 28
28
Figure 14 - Example of air intake through an outside wall, (without intake pipe), and discharge through the same wall. For BMS model
Figure 11 - Example of discharge to a chimney for a BMS model
Figure 12 - Example of air intake without intake pipe and discharge of flue gases through the roof. For BMS model
A Chimney B Washer C Discharge pipe D Split system elbow E Clamp with seal F Insulation G Condensing trap
A Condensate
drainage pipe fitting
B Condensate
drainage tap
A Chimney B Insulation C Condensing trap
Figure 13 - Example of air intake through an outside wall, (without intake pipe), and discharge to a chimney. For BMS model
A INSTALLATION INSTRUCTIONS
Page 29
29
Figure 15 - Discharge with coaxial flue for BTS model
1Wall 2 Sheat 3 Discharge pipe 4 Washer 5 Intake pipe
Figure 17 - Example of air intake and flue gas discharge through the roof. For BTS model
Figure 16 - Discharge with coaxial flue without intake pipe. For BTS model
1Wall 2 Sheat
3 Discharge pipe 4 Washer
A INSTALLATION INSTRUCTIONS
Page 30
30
Figure 18 - Example of air intake through an outside wall, (without intake pipe), and discharge to a chimney. For model BTS.
Figure 20 - Example of air intake through an outside wall, (without intake pipe), and discharge through the same wall. For model BTS.
Figure 19 - Example of air intake without intake pipe and discharge of flue gases through the roof. For model BTS.
A = Condensate discharge
A INSTALLATION INSTRUCTIONS
Page 31
31
A INSTALLATION INSTRUCTIONS
4.7 Water Connections for Model BMS
Each heater contains a kit of accessories to help the installer make the water connections. An example of these connections and all the accessories supplied with the heater is shown on the drawing below:
Pos. Description
1) 1/2" Gasket
2) 1/2" to 1" Connection
3) 1" Gasket
4) Domestic cold water connection
5) Domestic hot water connection
6) ASME T-P relief valve (not provided)
7) Heating return connection
8) Heating supply connection
9) ASME pressure relief valve
10) Connections (not provided)
11) Domestic drain cock (not provided)
12) Heating drain cock (not provided)
13) Mixing valve (not provided)
14) By-pass valve (not provided)
15) Flow selector
16) Ball valve (not provided)
17) Fitting 1/2" NPT/Copper (not provided)
18) Gas supply (3/4)
19) Cold water inlet
20) Hot water outlet
21) Central heating return
22) Central heating supply
Page 32
32
4.8 Water Connections for Model BTS
Each heater contains a kit of accessories to help the installer make the water connections. An example of these connections and all the accessories supplied with the heater is shown on the drawing below:
1) Ball valve (not provided)
2) Domestic hot water flow selector
3) Mixing valve (not provided)
4) ASME T-P relief valve (not
provided)
5) Connections (not provided)
6) By-pass valve (not provided)
7) Domestic drain cock (not
provided)
8) ASME pressure relief valve
9) Heating drain cock (not provided)
10) Domestic Hot water connections
11) Domestic Cold water
connections
12) Heating Supply connections
13) Heating Return connections
14) 1" Gasket
15) 1/2" to 1" Nipple
16) 1" Nipple
17) 1/2" Gasket
18) 1/2" Nipple (not provided)
19) Line voltage cable (not provided)
20) Fitting for block cable
21) Hot water outlet
22) Cold water inlet
23) Gas supply
24) Central heating supply
25) Central heating return
Page 33
33
A INSTALLATION INSTRUCTIONS
Figure 23 - Two (BMS or BTS model) heaters installation with domestic hot water recirculating system
1 Cosmogas combi
2 Heating drain cock
3 Sanitary drain cock
4 Gas cock
5 Safety relief valve
6 By-pass valve
7 Domestic relief valve
8 Radiator
9 Automatic feed
10 Back-flow preventer
11 Gas inlet
12 Mixing valve
13 Cold water inlet
14 Recirculating pump
15 Recirculating thermostat or timer
16 Recirculating return line
17 Hot water outlet
18 Cold water outlet
Page 34
34
A INSTALLATION INSTRUCTIONS
Figure 24 - Three or more (BMS or BTS models) heaters installation with connection for indirect water heater
1 Ambassador
2 Safety relief valves
3 Heating drain cocks
4 Ball valves
5 Gas cocks
6 Back-flow preventer
7 Supplementary expansione tank
8 Manometer
9 Gas supply
10 Cold water inlet
11 Supply and return for central
heating
12 Supply and return for eventual
indirect water heater
P1 Pump for central heating
P2 Pump for indirect water heater
VICGeneral automatic gas valve
Page 35
35
A INSTALLATION INSTRUCTIONS
Figure 25 - Example of (BMS or BTS model) heater installation for radiant heating
1 Ambassador 2 Safety relief valves 3 Heating Drain cock 4 Plate heat exchanger 5 Three ways valve 6 Floor protection thermostat set to
104°F (40°C)
7 Supplementary pump 8 Air vent
9 Radiant heating 10 Gas cock 11 Automatic feed 12 Back flow preventer
13 Pressure gauge 14 Additional expantion tank 15 Relief valve 16 Domestic relief valve 17 Sanitari drain cock 18 Mixing valve 19 Flow restrictor 20 Hot water outlet 21 Cold water inlet 22 Gas inlet
Page 36
36
Figure 26 - Example of (BMS or BTS model) heater installation for radiators
A INSTALLATION INSTRUCTIONS
1 Safety relief valve 2 By-pass valve 3 Heating drain cock 4 Radiators 5 Gas cock 6 Automatic feed 7 Domestic relief valve
8 Back-flow preventer
9 Sanitary drain cock 10 Mixing valve 11 Flow restrictor 12 Hot water outlet 13 Cold water inlet 14 Gas supply
Page 37
37
A INSTALLATION INSTRUCTIONS
Figure 27 - Zoning with pumps - Multizone hydronic piping. For BMS or BTS model
1 Ambassador 2 Safety relief valve 3 Heating drain cock 4 Pressure disconnector 5 Flow checks 6 Optional ball valve to isolate heater 7 Supply piping to zones 8 Gas cock
9 Automatic feed 10 Optional ball valve 11 Back-flow preventer
12 Added system pump 13 Optional ball valve 14 Tees with drains to bleed zones 15 Return piping from zones 16 Domestic relief valve 17 Sanitary drain cock 18 Mixing valve 19 Flow restrictor 20 Hot water outlet 21 Cold water inlet 22 Gas inlet
Page 38
38
A INSTALLATION INSTRUCTIONS
Figure 28 - Zoning with zone valves - Multizone hydronic piping. For BMS or BTS model.
11 Zone valves 12 Optional ball valve 13 Tees with drains to bleed zones 14 Return piping from zones 15 Domestic relief valve 16 Sanitary drain cock 17 Mixing valve 18 Flow restrictor 19 Hot water outlet 20 Cold water inlet 21 Gas inlet
1 Ambassador
2 Safety relief valve
3 Heating drain cock
4 By-pass valve
5 Optional ball valve to isolate heater
6 Supply piping to zones
7 Gas cock
8 Automatic feed
9 Ball valve 10 Back-flow preventer
Page 39
39
5 REGULATING THE DOMESTIC HOT WATER
The heater temperature control knob is adjusted to its lowest temperature position when shipped from the factory. Prior to starting heater, it should be adjusted to a starting point of 120°F as shown on the thermostat. After installing the space/water heater, it is necessary to regulate the flow rate of the domestic hot water so as to give a 75°F rise. For this function, you need to use a flow meter and a thermometer. Place the flow meter, under a hot water faucet, closest to the heater and open the faucet until water temperature is stabilized. The difference between cold and hot water should be approximately 75°F. Increase or decrease the water flow by regulating the incoming cold water to the heater with the DHW flow restrictor.
In any case, it is necessary to install a mixing valve external of the heater.
6 BURNER
The burner, depicted below, is made of stainless steel and can be used with both
Natural Gas (NAT) or Propane Gas (LP).
6.1 Changing the Gas Type
To convert the heater from one gas type to another (NAT to LP or LP to NAT). Conversion kits are available at an additional cost..
6.2 Adjusting Gas Flow and Pressure to the Burner
The gas pressure is calibrated in the factory. If any corrections are needed use a manometer and adjust the pressure according to Table 1 (back of manual). Please refer to Figure 22, below. Loosen the screw (B) on the bottom of the burner and place one of the manometer tubes on (B). Turn the burner on and compare the pressure found with the value given in Table
1. If any adjustments are needed remove the protection cap (A) and turn the burner pressure adjustment screw until the value given in Table 1 is reached. (Turn the screw clockwise to increase the flame and counter­clockwise to decrease it). Tighten the screw that closes the burner gas pressure (B).
Fig.21 - Exploded view of the burner
A Burner unit fixing pin B Manifold C O-ring D Nozzle E Spacer
F Tie rod
G Burner unit
Figure 22 - Gas valve
A Burner pressure adjustment screw
(under cap screw) B Burner gas pressure probe C Gas control knob D Inlet gas pressure probe
A INSTALLATION INSTRUCTIONS
Page 40
40
A INSTALLATION INSTRUCTIONS
Figure 29 - Wiring diagram. For BMS and BTS model
7 WIRING DIAGRAMS
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 18 AWG wire or its equivalent.
1 Domestic hot water priority thermostat
2 Power switch
3 Circulator pump switch
4 High limit thermostat
5 Transformer
6 Electrical junction box
7 Ground connections
8 Circulator pump
9 Flue gas discharge fan
10 Detection electrode
11 Ignition electrode
12 Ignition module
13 Failure lamp indicator
14 Gas valve service switch (Only for BMS)
15 Gas valve
16 Pressure switch
17 Heater temperature control
18 Low water cutoff
19 Electrical control board
Page 41
41
A INSTALLATION INSTRUCTIONS
Figure 30 - Functional wiring diagram. For BMS and BTS model
DL1 Heater temperature lamp control
DL2 Low water cutoff lamp control
DL3 NC (Normally Close) pressure switch lamp control
DL4 NO (Normally Open) pressure switch lamp control
DL5 Gas valve lamp control
DL6 Room thermostat lamp control
DL7 Ignition module lamp control
DL8 Transformer lamp control
r1 Resistor 780 Ohm
1 Fuse
2 Power switch
3 Pilot light of power switch
4 High limit thermostat
5 Circulator pump
6 Domestic hot water priority thermostat
7 Circulator pump switch
8 Circulator pump switch light
9 Flue gas discharge fan
10 Transformer
11 Heater temperature control
12 Low water cutoff
13 Pressure switch
14 Ignition and detection electrodes
15 Ignition module
16 Gas valve
17 Failure lamp indicator
18 Room thermostat connection
19 Gas valve service switch (only for BMS)
Page 42
42
A INSTALLATION INSTRUCTIONS
Figure 32a - Wiring diagram for taco
zone valvesFigure 31a - Taco zone valves
Figure 32b - Wiring diagram for zone
valves
Thermostat
zone 1
Thermostat
zone 2
115V 24V
External
transformer
1
2 3
1 2
3
Taco zone valves
COSMOGAS
Combi
Thermostat
N
L
115V 24V
External
transformer
Heating
thermostat
zone 1
Heating
thermostat
zone 2
N
L
COSMOGAS
Combi
Thermostat
1 2
3
1 2
3
Heating
zone
valve 1
Heating
zone
valve 2
End
switch
Motor
Zone valve 1
Room
thermostat
zone 1
End
switch
Motor
Zone valve 2
Room
thermostat
zone 2
End
switch
Motor
Zone valve 3
Room
thermostat
zone 3
Thermostat
24V 115V
115VAC
N
L
COSMOGAS
Combi
External
transformer
Figure 31b - Honeywell controls and
circulators
T87F
thermostat
T87F
thermostat
T87F
thermostat
115VAC
TT 12 TT 12
65 43 65 43 65 43
R-845 R-845 R-845
TT 12
External
pump
External
pump
External
Wiring schematic
useing circulators
and R-845 relays
for multi zone
system
115VAC
Thermostat
COSMOGAS
combi
L N
Page 43
43
B OPERATING AND MAINTENANCE INSTRUCTIONS for BMS
Qualified personnel must carry out installation, calibration or alterations to the gas apparatus, or to convert it from one gas type to another. Conversion kits are available, (optional).
9.1 Start-Up Instructions
Check that the system has been filled and purged. The indicator on the pressure gauge 8, (fig.33), should show 15-25 psi. To properly purge the heater and system of air it is imperative that these basic instructions be followed. The automatic feed should have a fast fill feature. There must be an isolation valve installed so that when it is closed it will direct the incoming water flow through the system and heater in the normal flow pattern and out a drain cock installed at the end of the loop. a) Attach a hose to the heating drain cock and run the hose to a suitable drain.
b) Open heating drain cock. c) Open the automatic feed using the fast fill feature
and allow the system to fill purge. On multi-zone systems, each zone must be purged separately with the other zones shut off.
9.2 Checks Prior to Ignition
Prior to ignition, it is necessary to carry out a few checks. a) Check that the appliance is electrically connected to a voltage of 115V 60Hz. Grounding is compulsory likewise the installation of a switch with fuse immediately upstream from
9 - BMS model - INSTRUCTIONS FOR USE
Figure 33 - Instrument panel for model BMS
1 Power switch 2 Central heating regulation knob 3 Circulator pump switch 4 High limit thermostat reset button
5 Heater temperature control knob 6 Gas valve service switch 7 Failure lamp indicator 8 Temperature-pressure gauge
the heater. b) Check that the heater is connected properly to the flue, it must not be clogged. The height and cross section must both be adequate.
9.3 Ignition Procedure
a) Open the gas cock. b) Turn the power switch on, (fig.33, item 1). c) Position the heater temperature control knob 5
(fig.33) on 120°F. The ignition module will provoke sparks for burner ignition for about 11 seconds. If, during this length of time it does not start up because there is still air in the gas line, the heater will shutdown and the indicator light of the failure lamp indicator 7 (fig.33) signaling the state, will come on. Turn the heater temperature control knob 5 (fig.33) to position 0 and repeat operation c). The ignition module will attempt a new ignition automatically. Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. It is important, especially in the heating season, to keep the heater temperature control knob 5 (fig.33) on 150°F seeing as the circulator pump starts working at 140°F. During the summer season, if the water is hot enough, this knob can be adjusted to a lower temperature.
Page 44
44
B OPERATING AND MAINTENANCE INSTRUCTIONS for BMS
9.4 Summer-Winter Mode
By means of the circulator pump switch, (fig.33, item 3), you can change over from the summer to the winter mode, as explained below. In the summer, the switch is turned off, allowing the production of domestic hot water only. In the winter or whenever central heating is required, the circulator pump switch must be turned
on.
9.5 Adjusting Central Heating
This is done by turning the central heating regulation knob 2 (fig.33) which optimizes the central heating system, controlling radiator temperature. It is advisable, during the in-between seasons, (spring and autumn), when you want only warm radiators, to turn the knob to minimum. In the winter you will have to turn it to maximum, leaving the heater temperature control knob 5 (fig.33) on 150°F. If you want hotter central heating, adjust the above knob by turning it to a higher temperature setting. It is however advisable to install a room thermostat well away from heating elements, doors and windows.
9.6 Manual Reset High-Limit Thermostat
This device acts on the heater, turning the burner off completely if heater temperature exceeds 210°F. The user can see this because the burner does not turn on any more even if heater temperature is low. To restore the heater to its normal functioning condition, unscrew and remove the protection cap of high limit thermostat reset button 4, (fig.33). Then press it. Use a pen or a skinny object to manually reset (the high limit thermostat will not reset unless the button is completely pressed). If the high limit thermostat continues to trigger, call a licensed authorized personnel.
9.7 Resetting the Ignition Module
The ignition module, (fig.1, item 24), carries out numerous checks on heater functioning: on the burner and on the flame detection system. When the ignition module detects that one of these components is malfunctioning, it stops the heater. To restart, Turn the heater temperature control knob
5 (fig.33) to position 0 and reposition it on 150°F.
Once this operation has been done and if the heater does not start up or if this situation repeats often, call a licensed authorized personnel.
9.8 Heating Circulator Pump
The circulator pump will only start working when heater the temperature reaches approximately
140°F and the circulator pump switch, (fig.33, item
3), is in the winter position (on position).
Initially, the circulator pump could make noises, which are due to pockets of air left inside the water circuit; they will disappear soon without having to do anything. In any case, check that the cap on the automatic air vent, (fig, 1, item 7) is open.
9.9 Shut-Down Procedure
To stop the supply of gas and consequently turn the system off, turn heater temperature control knob 5 (fig.33) to position 0. Turn power switch 1 (fig.33) off and close the gas cock.
9.10 Maintenance
The heater requires no specific maintenance; to keep it in good working order, however, it is advisable to have the flue pipe into the heat exchanger and burner cleaned at the beginning of each season. To clean proceed in this order: a) Remove the heater jacket, the burner, the flue gas discharge fan and the turbulators. b) With a plastic-bristled cylindrical brush, brush the insides of the flue gas pipes and the turbulators. c) Vacuum away the burnt deposits from the burner and from the ignition and detection electrodes. However, for this cleaning job it is necessary to call a licensed authorized technician.
9.11 Draining water from the heater
a) Turn off the main cold water supply valve. b) Open the heating drain cock. c) Open heating air vents. d) Open the sanitary drain cock. e) Open all hot water faucets to allow air to enter
into the pipes. The heater holds approximately 4 gallons of water, not including the water capacity of the other system components and piping.
Page 45
45
C OPERATING AND MAINTENANCE INSTRUCTIONS for BTS
Figure 34 - Instrument panel for model BTS
1 Power switch 3 Circulator pump switch 4 High limit thermostat reset button
5 Heater temperature control knob 7 Failure lamp indicator 8 Temperature-pressure gauge
Qualified personnel must carry out installation, calibration or alterations to the gas apparatus, or to convert it from one gas type to another. Conversion kits are available, (optional).
10.1 Start-Up Instructions
Check that the system has been filled and purged. The indicator on the pressure gauge 8, (fig.34), should show 15-25 psi. To properly purge the heater and system of air it is imperative that these basic instructions be followed. The automatic feed should have a fast fill feature. There must be an isolation valve installed so that when it is closed it will direct the incoming water flow through the system and heater in the normal flow pattern and out a drain cock installed at the end of the loop. a) Attach a hose to the heating drain cock and run the hose to a suitable drain.
b) Open heating drain cock. c) Open the automatic feed using the fast fill
feature and allow the system to fill purge. On multi-zone systems, each zone must be purged
separately with the other zones shut off.
10.2 Checks Prior to Ignition
Prior to ignition, it is necessary to carry out a few checks. a) Check that the appliance is electrically connected to a voltage of 115V 60Hz. Grounding is compulsory likewise the installation of a switch with fuse immediately upstream from
the heater. b) Check that the heater is connected properly to the flue, it must not be clogged. The height and cross section must both be adequate.
10.3 Ignition Procedure
a) Open the gas cock. b) Turn the power switch on, (fig.34, item 1). c) Position the heater temperature control knob 5
(fig.34) on 120°F. The ignition module will provoke sparks for burner ignition for about 11 seconds. If, during this length of time it does not start up because there is still air in the gas line, the heater will shutdown and the indicator light of the failure lamp indicator 7 (fig.34) signaling the state, will come on. Turn the heater temperature control knob 5 (fig.34) to position 0 and repeat operation c). The ignition module will attempt a new ignition automatically. Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. It is important, especially in the heating season, to keep the heater temperature control knob 5 (fig.34) on 150°F seeing as the circulator pump starts working at 140°F. During the summer season, if the water is hot enough, this knob can be adjusted to a lower temperature.
10 - BTS model - INSTRUCTIONS FOR USE
Page 46
46
10.4 Summer-Winter Mode
By means of the circulator pump switch, (fig.34, item 3), you can change over from the summer to the winter mode, as explained below. In the summer, the switch is turned off, allowing the production of domestic hot water only. In the winter or whenever central heating is required, the circulator pump switch must be turned
on.
10.5 Adjusting Central Heating
This is done by turning the central heating regulation knob 21 (fig.34) which optimizes the central heating system, controlling radiator temperature. It is advisable, during the in-between seasons, (spring and autumn), when you want only warm radiators, to turn the knob to minimum. In the winter you will have to turn it to maximum, leaving the heater temperature control knob 5 (fig.34) on 150°F. If you want hotter central heating, adjust the above knob by turning it to a higher temperature setting. It is however advisable to install a room thermostat well away from heating elements, doors and windows.
10.6 Manual Reset High-Limit Thermostat
This device acts on the heater, turning the burner off completely if heater temperature exceeds 210°F. The user can see this because the burner does not turn on any more even if heater temperature is low. To restore the heater to its normal functioning condition, unscrew and remove the protection cap of high limit thermostat reset button 4, (fig.34). Then press it. Use a pen or a skinny object to manually reset (the high limit thermostat will not reset unless the button is completely pressed). If the high limit thermostat continues to trigger, call a licensed authorized personnel.
10.7 Resetting the Ignition Module
The ignition module, (fig.3, item 24), carries out numerous checks on heater functioning: on the burner and on the flame detection system. When the ignition module detects that one of these components is malfunctioning, it stops the heater. To restart, Turn the heater temperature control knob
5 (fig.34) to position 0 and reposition it on 150°F.
Once this operation has been done and if the heater does not start up or if this situation repeats often, call a licensed authorized personnel.
10.8 Heating Circulator Pump
The circulator pump will only start working when heater the temperature reaches approximately
140°F and the circulator pump switch, (fig.34, item
3), is in the winter position (on position).
Initially, the circulator pump could make noises, which are due to pockets of air left inside the water circuit; they will disappear soon without having to do anything. In any case, check that the cap on the automatic air vent, (fig, 4, item 7) is open.
10.9 Shut-Down Procedure
To stop the supply of gas and consequently turn the system off, turn heater temperature control knob 5 (fig.34) to position 0. Turn power switch 1 (fig.34) off and close the gas cock.
10.10 Maintenance
The heater requires no specific maintenance; to keep it in good working order, however, it is advisable to have the flue pipe into the heat exchanger and burner cleaned at the beginning of each season. To clean proceed in this order: a) Remove the upper heater jacket, the burner, the flue gas discharge fan and the turbulators. b) With a plastic-bristled cylindrical brush, brush the insides of the flue gas pipes and the turbulators. c) Vacuum away the burnt deposits from the burner and from the ignition and detection electrodes. However, for this cleaning job it is necessary to call a licensed authorized technician.
10.11 Draining water from the heater
a) Turn off the main cold water supply valve. b) Open the heating drain cock. c) Open heating air vents. d) Open the sanitary drain cock. e) Open all hot water faucets to allow air to enter
into the pipes. The heater holds approximately 4 gallons of water, not including the water capacity of the other system components and piping.
C OPERATING AND MAINTENANCE INSTRUCTIONS fot BTS
Page 47
47
D TROUBLESHOOTING
Troubleshooting Sequence of Operation to Light the Burner
Turn power switch to the ON position Switch diode should be lit !
No
Yes
Verify the connections to the main electrical supply and check the fuse on the control board
Turn the heater temperature control clockwise (should hear a click)
Is the pressure switch at the NC position ?.
The fan will not start.
- Check if the DL8 diode is lit (transformer lamp control). If it is not lit, check the transformer.
Turn power on and carefully check the two terminals, 13 and 14 on the electrical control board (see fig. 29) for a minimum of 110VAC.
If there is no power, check
power to the heater at the on/off switch on the front panel. Place the leads of your meter on the outer two terminals of the power switch with the switch pushed to the ON position. If no power is present, check the fuse on the electrical control board for continuity. If there is power at the switch, verify that the high limit thermostat is working properly by turning the power OFF and remove one wire from terminal 6 or 7 (110 voltage side) and check for continuity. If continuity is present, reattach the wire.
- If DL8 is lit, check if DL1 is lit. If DL1 is not lit replace the heater temperature control. If DL1 is lit, check if DL3 is lit. If DL3 is not lit replace the pressure switch and/or check the connections between the pressure switch and the electrical control board.
No
DL1, DL2, DL3 and DL8 are lit
Yes
The fan will start
- Check for power between terminals 17 and 18 (see fig.
29) on the control board. If there is no power, replace electrical control board.
No
The pressure switch switches from NC to NO, only if there is a 0.3 inWC pressure change.
Yes
The lamp control DL4 diode is not lit.
- Check if the vent air-intake pipes are too long.
- Check if the vent air-intake pipe has an obstruction.
- Check if the two leads inside the fan are dirty or not attached.
- Check if flue condensation is inside the fan (in this case a condensing trap immediately up to the heater is necessary).
- Check if pressure switch has good connections.
No
DL4 is lit
Yes
Spark starts and gas valve opens
- Check if DL7 diode is lit. If not, replace the electrical control board.
- Check for power between 25V and 25V (gnd) on the ignition module. If voltage is OK, and the unit doesn't spark, replace ignition module. If there isn't any voltage, replace control board.
No
DL7 is lit
Yes
The burner lights
After 11 seconds (safety time), spark stops and gas valve closes. Failure lamp indicator becomes lit (see item 7 Fig. 33 or 34).
- Check if gas switch on front panel is at the ON position.
- Check if gas valve is at the open position. To check the gas valve for 24VAC, the power must be shut off to reset the cycle. Turn the power back on and 24VAC should be obtained during that 11 second period.
- Check if the inlet gas pressure is between the maximum and minimum operating ranges (see TABLE 1). Now check manifold pressure during the 11 second cycle (see TABLE 1 for correct manifold pressures).
- Check if the electrodes (flame sensor and ignition) are correctly positioning on the burner (3-4mm or an 1/8 from the top of the burner).
- Check if the electrodes are correctly connected to the ignition module.
No
All diodes are lit except for Dl6. Spark stops and burner is lit continuously
Yes
Unit is functioning properly
No
Yes
5J=HJ
The burner stops when heater reaches the set temperature
If the unit continuosly trips at the safety limit of 210°F (100°C), this would indicate an excessive amount of air in the heat exchanger or a faulty heater temperature control. Once the unit trips, the manual reset button must be pressed by unscrewing the black cap on the front panel. A sharp narrow object must be used to completely depress the button.
Page 48
48
D TROUBLESHOOTING
The pump switch is in winter mode
Is the heater temperature (shown on gauge) up to 140°F (60°C) ?.
Is the room thermostat calling for heat ?.
No
DL6 lamp diode is lit
Yes
The light of the pump-switch is not on.
- Check if the heater temperature control is set at a minimum of 140°F (60°C). If is already up to 140°F (60°C) replace the heater temperature control.
No
The DL6 lamp diode is not lit.
- Check if the room thermostat is wired properly.
- Check T-T inputs Thermostat 24Vac on the white junction box attached to the heater cavity. Jump across terminals to see if the pump starts. If it does, the problem is external of the boiler.
Yes
Turn the central heating regulation knob to the maximum setting.
Is the pump running ?.
The pump is not running. The radiators will be cold.
- Check if the pump is locked or jammed in its position. This may be due to the pump not running throughout the summer. In this case, turn the screw on top of the pump with flat head screwdriver to help loosen the pump impeller.
- Check for power to the pump by checking for 110VAC between terminals 15 and 16 on the main electrical control board. If pump is still not operational, remove cover on pump and check for power between N and L terminals. If 110VAC is obtained, replace pump cartridge by removing the four allen screws.
No
Yes
Are the radiators hot ?.
- Check if the zone valves are open.
- Check if you have air in the radiators (purge from the radiators)
- Check if you have air in the heater (loosen the cap of automatic air vent)
No
Pump runs until thermostat is satisfied or the temperature inside the heater is less than 140°F (60°C)
Yes
Troubleshooting Sequence of Operation for a Call for Heat
Troubleshooting Sequence of Operation for Domestic Hot Water
Start
The temperature inside the heater is set more than 122°F
(
50°C
)
Is the domestic hot water side hot?.
No
Yes
- Check if the external mixin
g
valve is installed correctly and
that it is set more than 104°F
(
40°C
)
- Check if the domestic hot water coil is dirty (domestic side
)
- Check if the domestic hot water exchanger is dirty
(
heating system side
)
- Check if the domestic hot water flow restrictor is correctly set
(
see TABLE 1 DHW output rise)
OK
Page 49
49
D TROUBLESHOOTING
PROBLEMS CAUSES CHECKS (IF NECESSARY) REMEDIES
(IF NECESSARY)
the pilot light of power switch is off there isnt electrical suppl
y
check the electrical supply level restore the electrical suppl
y
the fuse doesnt work check the fuse replace the fuse
the power switch is off check that the power switch is on turn the power switch on
the power switch doesnt work check the power switch operatin
g
replace the power switch
pilot light of power switch doesnt
work
check the pilot light of power switch
operatin
g
replace the power switch
the transformer lamp control,
(
DL8), is off
115V isnt reachin
g
the transformer
input
check the transformer has 115V
input
restore the electrical suppl
y
the transformer doesnt work
check the transformer has 24V
output
replace the transformer
the DL8 doesnt work check DL8 operatin
g
replace the electrical control board
the heater temperature lamp
control,
(
DL1) is off
the heater temperature control
contacts are open
check that the heater has the
required temperature
increase the heater temperature
set
24V isnt reaching C contact of
heater temperature control
check 24V presence on C heater
temperature control contact
restore the electrical connection
the heater temperature control
doesnt work
check heater temperature control
operatin
g
replace the heater temperature
control
the DL1 doesnt work check DL1 operatin
g
replace the electrical control board
the low water cutoff lamp control,
(
DL2), is off
there isnt enou
g
h water in the
heater
check theres enough water in the
heater
restore the water right level in the
heater
low water cutoff doesnt work check the low water cut-off
operatin
g
replace the low water cut-off
DL2 doesnt work check DL2 operatin
g
replace the electrical control board
the NC pressure switch lamp control, (DL3),
is off
24V isnt reaching the C contact
of pressure switch
check theres 24V on the C
contact of pressure switch
restore 24V on the C contact of
pressure switch
pressure switch contact is on NO check the flue gas discharge fan is
off
replace pressure switch
DL3 doesnt work check DL3 operatin
g
replace electrical control board
the NO pressure switch lamp
control,
(
DL4), is off
flue
g
as discharge fan is off
check the flue
g
as discharge fan is on
replace the flue
g
as discharge fan
115V isnt reaching the flue gas
dischar
g
e fan
check 115V is reachin
g
the flue
g
as discharge fan contacts
restore the electrical suppl
y
pressure switch contact is on NC check the pressure switch
operatin
g
replace the pressure switch
DL4 doesnt work check DL4 operatin
g
replace the electrical control board
the ignition module lamp control,
(
DL7), is off
24V isnt reachin
g ig
nition module check 24V is reaching ignition
module contacts
restore 24V
DL7 doesnt work check DL7 operatin
g
replace the electrical control board
the gas valve lamp control, (DL5),
is off
24V isnt reaching gas valve check 24V is reaching gas valve
contacts
replace ignition module
DL5 doesnt work check DL5 operatin
g
replace the electrical control board
the room thermostat lamp control,
(
DL6), is off
room thermostat contacts are
open, (if an
y)
check room thermostat operatin
g
replace the room thermostat
room thermostat doesnt work, (if
an
y)
check room thermostat operatin
g
replace the room thermostat
DL6 doesnt work check DL6 operatin
g
replace the electrical control board
the circulator pump switch light is
off
circulator pump switch is off check heater temperature is higher
than 140°F
check heater temperature is higher
than 140°F
dhw priority thermostat contacts
are open
check heater temperature is higher
than 140°F
increase the heater temperature, (if
necessar
y)
room thermostat contacts are open check room thermostat operatin
g
replace the room thermostat
circulator pump switch light doesnt
work
check circulator pump switch light
operatin
g
replace the circulator pump switch
6=> KI =
Page 50
50
E IMPORTANT INFORMATION FOR THE CUSTOMER
The technician will explain to the customer how the heater works and how
to operate it.
The customer must neither replace nor repair any parts.
The user must call in a licensed authorized technician to carry out necessary
routine maintenance on the heater at least once a year, before it is used for central heating.
A routine maintenance contract, with a licensed authorized technician, will
guarantee the heater works properly as well as ensuring a longer life.
Controlling Heater Operation
The customer must know how to fill and drain the circuit; he must also know how to control and correct if necessary the pressure in the central heating system.
What to do when:
the smell of gas is present-
Turn the gas cock off and ventilate the room. Call a licensed authorized technician and, if necessary your local gas company. Follow the gas suppliers instructions - If you cannot reach your gas supplier; call the fire department.
the heater is heating up but the system stays cold-
Open the radiator taps and make sure that the heater temperature control knob is on the 150°F position. If the system still does not warm up and the circulator pump is not working, turn the heater off and call a licensed authorized technician.
water is leaking from the domestic water side-
Turn off the main cold water supply valve. Call a licensed authorized technician.
Cleaning the heater jacket
Use a damp cloth. Do not use any abrasive detergents.
Page 51
51
F SPARE PARTS
Spare parts are available from your local authorized wholesale distributor. For a location of the one nearest you call Embassy Industries, Inc. at 631-694-1800.
Page 52
52
G TECHNICAL FEATURES
TABLE 1
Page 53
53
G TECHNICAL FEATURES
Curves of residual head for central heating system
Page 54
54
NOTES
Page 55
55
NOTES
Page 56
FOR TECHNICAL SUPPORT CALL:
Embassy Industries, Inc.
300 Smith Street
Farmingdale, NY 11735
PH - 631-694-1800
Fax - 631-694-1832
www.embassyind.com
sales@embassyind.com
MANUFACTURED BY:
COSMOGAS s.r.l.
Via L. da Vinci 16 - 47014
MELDOLA (FC) ITALY
info@cosmogas.com
www.cosmogas.com
(For emergencies after 5 pm please call 413-348-7822)
Loading...