is manual is intended only for use by a quali ed heating installer/technician. Read and follow this manual, all supplements and related
instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in these
instructions. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination of
the burner, resulting in possible severe personal injury, death or substantial property damage. e boiler can only be operated with a dustfree air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated by operation
with contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.
A x these instructions near to the boiler/water heater. Instruct the building owner to retain the instructions for future use by a quali ed
service technician, and to follow all guidelines in the User’s Information Manual.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 2
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
The Mestek 200i condensing cast iron boiler
Operation
Overview
e 200i is a cast iron boiler designed and constructed to allow full condensing operation. e illustra-
tion at le shows how the boiler is heated with a down- red premix gas burner mounted above the heat
exchanger. e 200i blower pulls gas and air through a venturi assembly and pushes the mixture into the
burner. e power of the blower forces the ue products through the heat exchanger and out the vent.
Boiler operation is controlled with the 200i electronic control. e control modulates boiler ring rate
based on system demand, allowing input as low as 20% of maximum (5:1 turndown). Combined with
the indoor or outdoor reset option of the 200i control, this allows maximum possible condensing mode
operation, with combustion e ciency up to 98%.
Cast iron heat exchanger
e 200i cast iron heat exchanger uses Mestek’s graphite port seals and ground joint t-up between sections
for maximum exibility and resistance to thermal expansion. e heat exchanger provides maximum
heat transfer with its counter ow design and ow-controlling ba e assembly.
Premix burner
Premix means the air and gas are mixed before they enter the burner. e mixing of gas and air in the
blower and piping ahead of the burner causes a uniform gas/air mix in the burner, providing reliable operation with low excess air. e result is exceptional combustion e ciency.
e burner consists of a high-temperature stainless mesh secured to a stainless steel distributor plate. e
design causes uniform ame across the entire surface of the burner and the ability to operate at very low
ring rates. e ame is ignited with direct-spark electrodes and an electronic ignition control. Flame is
proven using a ame rod ( ame recti cation sensing).
Because of its low excess air operation and controlled combustion, the burner also provides low NO
emissions and quiet operation.
X
Gas valve, blower and venturi
Most gas valves regulate at a positive pressure downstream of the valve (typically 3½ inches water column). But the 200i gas valve regulates to ZERO pressure downstream. is is called a “zero governor”
valve. e advantage is that gas will only ow if something lowers the pressure downstream of the valve
below zero. at is just what happens when the blower pulls air through the venturi. As the air speeds up
to pass through the narrow throat of the venturi, a vacuum forms in the throat. e more air that ows
through the throat, the greater the vacuum.
e gas valve raises the negative pressure in the venturi to zero by le ing gas ow. e lower the pressure in
the venturi throat, the more gas will that will ow. So gas ow automatically adapts to air ow, ensuring
consistent gas/air mix throughout the boiler’s modulating range. us, the 200i SmartCycleTM electronic
control regulates the blower speed to control boiler ring rate.
200i
schematic
ow diagram
2
200i SmartCycleTM control
e 200i SmartCycleTM electronic control consists of a microprocessor-based module and a keypad/
display unit for user interface. e control regulates boiler water temperature by adjusting boiler ring
rate (by varying the blower speed). e control considers how fast the temperature changes and how the
temperature varies over time to establish the best ring rate to meet demand. Options include an outdoor
sensor for outdoor reset operation and an indoor reset option. (Indoor reset monitors up to 8 zone thermostats and determines a maximum ring rate needed to meet the demand. is keeps the boiler at the
highest possible e ciency.) In addition, the control can be set for multiple boiler operation, either standalone or utilizing Mestek’s on-board SmartCycleTM technology. e control also automatically cycles the
factory-installed postpurge circulator to equalize residual heat in the boiler a er ring.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 3
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
The Mestek 200i condensing cast iron boiler
Components
1. Gas valve
2. Pressure/temperature gauge
3. Jacket
4. Cast iron section assembly
5. Inlet air lter access panel
6. Blower
7. 200i SmartCycleTM control
8. Venturi assembly
9. Pressure switches (blocked
10. Control connection board
11. Electrical box (power and
12. Water return connection
13. Air inlet sleeve
14. Relief valve
15. Relief valve piping
16. Water supply connection
17. Fenwal ignition module
18. Ignition electrodes/ ame
19. Control transformer
20. Postpurge circulator,
21. Vent connection sleeve
22. Condensate tubing connection
23. Upper section cover and
24. Gas connection, ½” NPT
with keypad and display
ue and blocked air inlet)
control entrances)
(by installer)
rod assembly
(120/24 VAC)
factory-installed and piped
(with ue gas sampling port)
premix burner
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
200i
components
3
Page 4
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
Contents
1 Read before beginning the installation . . . . 5
Please direct all questions to your Mestek distributor or contact
the Mestek Customer Service Department at:
260 North Elm Street West eld, MA 01085
Phone (413) 568-9571
Always include the model and serial numbers from the rating
plate of the boiler in question.
Claims for damage or missing components must be led immediately against the transportation company by the consignee.
Other manuals
You must read and follow this
manual, the 200iVent/Air manual, the 200iControl manual
and all additional materials
supplied with the boiler. Failure
to do so can result in severe
personal injury, death or substantial
property damage.
Start-up/service history
Before leaving the installation site
after start or service, ll out the
Start-up/service history information
on the back page.
4
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 5
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
1
Read before beginning the installation
Codes and standards
Boiler compliances
e 200i has been design certi ed by CSA for
use with natural and propane gas under the latest
revision of ANSI-Z21.13/CSA 4.9, Gas-Fired
Low Pressure Steam and Hot Water Boilers
and CAN1-3.1, Industrial and Commercial
Gas Fired Packaged Boilers. Each unit has been
constructed and hydrostatically tested for a
maximum working pressure of 100 psi (700
kPa), in accordance with Section IV of the
A.S.M.E. Boiler and Pressure Vessel Code.
Code compliances
All aspects of the boiler installation must
conform to the requirements of the authority
having jurisdiction, or, in the absence of such
requirements, to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54-latest revision. Where
required by the authority having jurisdiction, the
installation must conform to the Standard for
Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance
with the requirements of CSA B149.1 or .2,
Installation Code for Gas Burning Appliances
and Equipment.
Commonwealth
of Massachusetts
If installing a 200i boiler in the Commonwealth
of Massachuse s, you MUST FOLLOW the
additional instructions contained in Mestek’s
instruction sheet, MA CODE. If you don’t have
a copy, call your Mestek dealer or Mestek.
When installed in the Commonwealth of
Massachuse s, ensure the following:
• e boiler must be installed by a licensed
plumber or gas er.
• W hen antifreeze is used in the system, install
an approved pressure back- ow preventer.
• Per DOE mandate, the 200i operator
control incorporates an automatic means
(outdoor/indoor air reset) of adjusting the
boiler water temperature for hot water
heating. e boiler must not operate without
the automatic means enabled.
In accordance with Section 325 (f) (3) of the Energy Policy
and Conservation Act, this boiler is equipped with a feature
that saves energy by reducing the boiler water temperature as
the heating load decreases. is feature is equipped with an
override which is provided primarily to permit the use of an
external energy management system that serves the same
function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT
LEAST ONE OF THE FOLLOWING CONDITIONS
IS TRUE:
• An external energy management system is installed that
reduces the boiler water temperature as the heating load
decreases.
• is boiler is not used for any space heating .
• is boiler is part of a modular or multiple boiler system
having a total input of 300,000 BTU/hr or greater.
• is boiler is equipped with a tankless coil.
IMPORTANT
Before placing the boiler . . .
Verify boiler rating and gas supply
• Before installing the 200i boiler, check the rating plate to ensure that the unit has been sized
properly for the job.
• Ensure that the boiler is set up for the type of gas available at the installation site.
Verify location is suitable
• Ensure the availability of an adequate electrical supply, uncontaminated air for combustion, and
that vent (and air) piping can be correctly installed.
• Ensure the boiler can be connected to system water piping and gas supply.
• e boiler must not be exposed to dripping or spraying water or to rain.
• If replacing an existing boiler, nd out what caused the boiler to fail before installing a new boiler.
Correct the problems that led to failure, or the failure may happen to the new boiler.
Do not install or operate the boiler, or leave an installation, without complying with
all of the following, and with all information supplied in the boiler manuals.
Should overheating occur
• Do not shut o power to the circulators if the boiler should overheat or the gas supply fail
to shut o . Instead, shut o gas supply to the boiler with a manual valve in the gas supply
line.
When servicing or operating the boiler
• Disconnect electrical power when servicing the boiler to avoid potential for electrical
shock.
• Allow the boiler, components and water to cool before a empting to remove or handle
boiler parts.
• Do not add cold water to the boiler if it is hot. Allow the boiler to cool completely before
introducing cold water.
• Do not operate the boiler if any part has been under water.
• Follow the guidelines in the Maintenance section for dealing with berglass and ceramic
ber materials.
You must have the following equipment
• Electric multimeter • Ammeter
• Surface temperature gauge • Metric Allen wrenches
• Pressure di erential gauge or included DP manometer
• (3) Gas pressure meters: Two @ 0 – 14 inches WC; One @ 0 – 5 psi
• Combustion analyzer You must use a combustion analyzer and follow all instructions
in this manual to correctly start-up the boiler. As prescribed in this manual, the O2 levels
must be between 5% and 7%. roughout all ring rate conditions, the burner surface
must never show red areas. Follow manual procedures to correct this condition.
Boiler water
• You must thoroughly ush the system, with the boiler isolated from the system, to remove
sediment. Existing systems, in particular, o en contain large amounts of iron sediment.
Excess suspended solids in the water can lead to premature boiler failure.
• High e ciency equipment requires suitable water for reliable operation. Follow the ASME
recommendation for water treatment on hydronic applications that have dissolved solids
greater than 200 parts per million. Fill water must be so ened if the solids concentration
is higher than this. See additional guidelines in this manual.
• Do not allow the boiler to operate with frequent introduction of make-up water. Correct
all problems causing leaks, relief valve weeping, or other factors that could cause fresh
water to be added.
• Do not use automotive anti-freeze in the boiler waterways. If the use of antifreeze is
necessary, an anti-freeze speci cally formulated for hydronic heating systems must be
used or damage to the boiler may occur, voiding the warranty.
• On applications that use antifreeze or other low conductivity uid in the water, provide
for increased water ow or ensure proper temperature rise.
Train the user
• Before leaving, review the User’s Information Manual with the boiler user/homeowner,
including the required maintenance to be performed by the user, the need for annual startup/maintenance by a quali ed technician, the avoidance of combustion air blockage or
contamination, and never bringing or storing ammable products into the boiler area.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
5
Page 6
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
2
Boiler ratings and speci cations
Boiler modelUnits
AFUE (DOE seasonal e ciency)%92.71
CSA Input (Max)
CSA Input (Min)
Maximum allowable working pressure
Water supply and return connectionsInches, NPT1¼
Boiler water volume
Shipping weight
Operating weight
FuelsNatural gas or propane3
Gas connection sizeInches, NPT½
Gas supply pressure, minimum
Gas supply pressure, maximum
Vent connection size
Vent options
Combustion air options
Combustion air adapter size
Electrical requirements
Voltage120 vac/60 hz/1-phase
Current draw (120-volt power line)Amperes2.75
Thermostat anticipator settingAmperes05
Operating controlMestek SmartCycle
Control operation options
Control methods
Btuh
Kw
Btuh
Kw
PSIG
kPa
Gallons
Liters
Pounds
Kg
Pounds
Kg
Inches WC
mm WC
Inches WC
mm WC
Inches
mm
Direct Vent or Category IV only
(pressurized vent, condensing)
Heat demand (SmartCycle or stand-alone)
On/O
BMS (4-20 ma input)
Staging
RS485 digital communication
TM
200i
200,000
58.6
40,000
11.7
100
700
4.75
18.0
540
245
510
231
3
102
14
356
3
76.2
Air from boiler room or
3
76.2
TM
control4
Notes
2
2
4
4
1
2
3
4
5
6
Notes
DOE Heating capacity is based on standard tests speci ed by the United States Department of Energy.
All capacity ratings above are based on sea level. Input adjustments allow se ing the high re input and may compensate for moderate altitudes.
For higher altitudes the maximum boiler input will be derated slightly.
e gas valve is capable of operating with natural gas or LP. See instructions in this manual to adjust for the speci c fuel used.
For additional information, refer to the 200i Control manual.
ermostat anticipator se ing is for a single thermostat connected to a single 200i boiler. Also jumper from the Heat Demand terminals to the
IAR1 terminals on the connection board. See the 200i Control manual for details.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 7
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
3
Installation site preparation
Boiler location requirements
Do not install the boiler unless the location
meets all of the requirements in this box.
Failure to comply could result in severe personal
injury, death or substantial property damage.
Indoor installation only
• Do not install the boiler outside or in an area that would expose the boiler or its gas or electrical components to rain or
dripping or spraying water.
• Do not install the boiler in a location that would subject the
boiler to freezing. Where freeze protection is needed, follow
the guidelines in this manual.
Flooring
• e boiler can be installed on combustible ooring, but
must not be installed on carpeting.
• e oor must be structurally sound and capable of supporting the weight of the boiler.
• e boiler must be leveled front to back and side to side.
Use metal shims if necessary.
Accessibility
• Jacket parts will have to be removed for some service procedures. Ensure that the location provides a reasonable means
for service and operation of the boiler.
System piping, fuel and electrical supply
• e boiler must be located such that piping for water, gas,
vent and air can reasonable be connected.
• ere must be a reasonable means of providing electrical
supply to the boiler.
Adjacent construction
• Locate the boiler in an area that will prevent water damage
to adjacent construction should a leak occur or during routine maintenance.
Combustion air
• Do not place the boiler in a location that would restrict
the ow of combustion air into the air intake or subject the
boiler to a negative air pressure in the space when using air
from the boiler room.
• Provide required combustion air openings to the boiler
room and the building (when required) when using air
from the boiler room for combustion (see page 8). If air is
piped to the boiler air intake connection, combustion air
openings are not required unless other appliances share the
same room.
• Buildings will require the installation of a fresh air duct or
other means of providing make-up air if the intake air option isn’t used. Any building utilizing other gas burning appliances, a replace, wood stove or any type of exhaust fan
must be checked for adequate combustion air when all of
these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all
such devices.
• e boiler must be supplied with combustion air in accordance with Section 5.3, “Air for Combustion and Ventilation,” of the latest revision of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 and all applicable local
building codes. Canadian installations must comply with
CSA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local
building codes.
Negative room pressure
• Never operate the boiler in an environment subjected to a
negative pressure unless it is Direct Vented. Failure to comply with this warning can result in excessive levels of carbon
monoxide.
Combustion air contamination
• Combustion air contaminated with uorocarbons or other
halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. ese acids will cause premature failure
of the boiler.
• Construction dust: If the boiler is operated while the
building is under construction it must be protected from
wood, concrete, sheet rock and other types of dust. Failure
to properly protect the boiler from construction dust will
damage the boiler.
• If the boiler has been operated with contaminated air, it
must be thoroughly inspected. Where possible, boiler components must be cleaned, following instructions provided
in this manual and/or supplementary instructions from
Mestek. Where cleaning is not possible, the boiler may have
to be replaced.
• Never store combustible materials, gasoline or any product
containing ammable vapors or liquids in the vicinity of the
boiler.
Clearances
• All installation must provide the minimum clearances to
combustible materials given on page 8.
• e installation should provide the minimum service clearances given on page 8 when possible. If these clearances
cannot be met, then:
• Ensure that boiler components can be accessed for
operation/start-up/maintenance as required in the
200i manuals.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
7
Page 8
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
3
Installation site preparation (continued)
Clearance requirements
Clearances to combustible surfaces
All installations must provide the minimum clearances to combustible
materials and surfaces given in Table 1. Failure to comply could result
in a re hazard, causing severe personal injury, death or substantial
property damage.
Table 1 Minimum clearances to combustible materials/surfaces for ALL
From:InchesMillimeters
Top6153
Back6153
Left side6153
Right side6153
Front6153
Rear6153
Vent piping251
System water piping125.4
EXCEPTION: Ventilation openings are not required if the boiler room
installations (Figure 1)
If the boiler is located in a closed room, the room must be provided with
ventilation openings even if air is ducted to the boiler. See Figure 1. Size
the openings with a free area no less than 1 square inch per BTUH input
of all 200i boilers in the room.
provides at least the minimum SERVICE/OPE TION clearances
given in Table 2. Failure to provide adequate ventilation could result in
overheating of the boiler components or the room, potentially causing
severe personal injury, death or substantial property damage.
Figure 1 Clearance to combustibles references
Clearances for service and operation
e installation must provide reasonable access and clearance for service
and operation of the boiler. Table 2 gives recommended minimum
clearances for service and operation. e boiler may be installed in a
space that does not provide these recommended clearances provided
it is accessible for the service and operation procedures required in the
200i manuals.
Table 2 Recommended minimum clearances for service/operation
From:InchesMillimeters
Top24610
Back24610
Left side24610
Right side24610
Front36914
Rear18457
Flame observation port e ame observation port on the LEFT
side of the boiler must be accessible to view the combustion chamber
during boiler start-up. Make sure that the installation allows serviceman
access to the le side for this purpose.
(Figure 2)
8
Figure 2 Service/operation clearance references
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 9
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
3
Installation site preparation (continued)
Combustion air requirements
Air ducted to boiler air intake
If air is ducted from outside to the boiler air intake, follow instructions in the
200i Vent/Air manual to size and install the air piping.
If the boiler is located in a small room (clearances less than the recommended
SERVICE/OPE TION clearances given in Figure 2):
• No other appliances in the room Provide two ventilation openings
through one of the enclosure walls. Each opening must be sized for a free
area of at least 1 square inch per 1,000 BTUH input of the 200i boilers in
the room. One opening must be within 12 inches of the ceiling, the other
within 12 inches of the oor.
• Other appliances in the same room e room must have combustion
air openings sized for the other appliances. Increase the free area of the air
openings by one square inch per 1,000 BTUH of the 200i boilers located
in the room.
Air from boiler room
When the boiler draws combustion air from the boiler room:
• If the room volume is at least 50 cubic feet per BTUH of the combined
input of all appliances in the room, no special openings are needed
UNLESS the building is of tight construction (see de nition). If the building is
of tight construction, provide openings to the building in accordance
with all applicable codes.
• If the boiler is in a space smaller than 50 cubic feet volume per BTUH input,
provide air openings using one of the methods in Figure 3.
De nitions
Free area Louvers or grilles reduce the area of an opening. Free area is the
area remaining with the louver or grille in place. If the free area of a louver is
unknown, use the following:
• Metal louver Multiply required free area of the opening times 1.7 to
determine actual area of the required opening.
• Wood louver Multiply required free area of the opening times 5 to determine actual area of the required opening.
Tight construction When a building is extensively sealed to prevent air
in ltration, it cannot provide enough air for combustion unless openings are
provided to the outside. e National Fuel Gas Code de nes such buildings as
having all of the following:
• Walls and ceilings exposed to the outside atmosphere have a continuous
water vapor retarder with a rating of 1 perm or less with openings gasketed.
• Weather-stripping has been added on openable windows and doors.
• Caulking or sealants are applied to areas such as joints around windows
and door frames, between sole plates and oors, between wall-ceiling
joints, between wall panels, at penetrations for plumbing, electrical, and
gas lines, and in other openings.
Conversion factors
In2/1,000 BTUH to cm2/kw Multiply In2/1,000 BTUH times 22
2
/2,000 BTUH to cm2/kw Multiply In2/2,000 BTUH times 11
In
2
/3,000 BTUH to cm2/kw Multiply In2/3,000 BTUH times 7.4
In
2
/4,000 BTUH to cm2/kw Multiply In2/4,000 BTUH times 5.5
In
Figure 3 Air opening options for combustion air
Upper openings (U) must be within 12 inches of the ceiling. Lower
openings (
Option 1 —
When air is supplied to the boiler room through openings in an interior
wall (air supply from inside the building), size each opening to provide
minimum free area of:
1 in2 per 1,000 BTUH of all 200i boilers in the room.
Option 2 —
When air is supplied to the boiler room through openings in an outside
wall (air supply from outside the building), size each opening to provide
minimum free area of:
1 in2 per 4,000 BTUH of all 200i boilers in the room.
drawn from boiler room
If other appliances are located in the same room
as the boiler, increase the size of air openings
to provide the free area required for the other
appliances in addition to the air required for the
200i boiler(s).
L) must be within 12 inches of the oor.
air openings through interior wall
air openings through outside wall
Option 3 —horizontal ducts to outside wall
When air is supplied to the boiler room through horizontal ducts to an
outside wall (air supply from outside the building), size each opening
to provide minimum free area of:
1 in2 per 3,000 BTUH of all 200i boilers in the room.
Option 4 —
Air openings can be connected to a ventilated a ic or crawl space. e
upper opening must be to the a ic. e lower opening can be a vertical
duct from the a ic or an opening in the oor from the craw l space. Size
each opening to provide minimum free area of:
1 in2 per 3,000 BTUH of all 200i boilers in the room.
Option 5 —
A single opening directly connected to the outdoors through a wall or
a vertical or horizontal duct can be used if the installation provides the
clearances of Figure 2, and the top of the opening is within 12 inches of
the ceiling. Size the opening to provide minimum free area of:
1 in2 per 3,000 BTUH of all 200i boilers in the room.
openings to attic/crawl space
single opening (not shown)
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
9
Page 10
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
4
Prepare the boiler
Remove the boiler from the crate
Cold weather handling e boiler jacket
includes plastic parts. If the boiler has been in a cold
environment (below 0 °F), allow the boiler to warm
to room temperature before handling.
Do not drop the boiler or allow the jacket to bump
against the oor or wall when handling.
1. Remove the crate from the skid. But leave the boiler on the
skid to move the boiler near its location.
2. Inspect the boiler thoroughly for any possible damage that
may have occurred in shipping or handling.
3. Slide the boiler o of the skid into position.
4. Use a spirit level to check whether the boiler sides and front
are vertically plumb. If not, slide metal shims under the base
until the boiler is level.
Install the relief valve
Check relief valve pressure setting
Inspect the boiler relief valve before installing to ensure it is set
at the pressure required for the system. You should also verify
that all water system components are rated for at least the pressure se ing of the relief valve to avoid component damage due
to excess pressure.
Piping guidelines:
• All installations must be installed by a quali ed technician
in accordance with the latest revision of the ANSI/ASME
Boiler and Pressure Vessel Code, Section IV.
• Where required, the installation must comply with ANSI/
ASME CSD-1, Standard for Controls and Safety Devices
for Automatically Fired Boilers.
• All applicable local codes and ordinances must also be followed.
• A minimum clearance of 1 inch (25 mm) must be maintained between heating system pipes and all combustible
construction.
• All heating system piping must be supported by suitable
hangers not by the boiler.
• e thermal expansion of the system must be considered
when supporting the system.
• A minimum system pressure of 12 psig (84 kPa) must be
maintained.
Figure 4 Relief valve piping
e boiler maximum allowable working pressure
is 100 psig (700 kPa). e relief valve must never
have a se ing greater than 100 psig. Using a higher
pressure relief valve could result in an explosion,
causing possible severe personal injury, death or
substantial property damage.
Connecting the relief valve
Connect ¾-inch NPT black iron pipe and ing so the relief
valve as shown in Figure 4. Follow all instructions provided in
the relief valve manufacturer’s instructions and labeling.
Never install any type of valve between the boiler
and the relief valve, or in the relief discharge
piping. An explosion could occur, causing severe
personal injury, death or substantial property
damage. General piping requirements.
Boiler piping — general
Improper piping of the boiler will void the
manufacturer’s warranty, and can cause boiler
failure, resulting in possible severe personal
injury, death or substantial property damage.
Install a shut-o valve in the boiler supply and
return connections to allow isolation of the
boiler for servicing when necessary.
10
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 11
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Water piping
Boiler piping connections
e boiler supply and return connections are shown in Figure 4.
Both connections are 1¼-inch NPT.
Size piping for the ow required. Piping connections to the
200i boiler should generally be 1¼-inch NPT.
System design
Design options
e 200i boiler works well in a single or multiple-boiler application
for any type of system. e following pages include suggested
piping diagrams for the following system options:
• Single boiler, zoning with zone valves (page 13).
• Single boiler, zoning with circulators (page 14).
• Guidelines for chilled water systems (page 17).
All of the piping diagrams show the suggested piping for optional
indirect- red DHW tanks. Follow the DHW tank manufacturer’s
instructions for installation and piping. Make sure to size the
DHW circulator and piping to provide the ow needed for the
required recovery capacity.
Pipe sizing
Generally install 1¼-inch piping in the boiler circuit. Size system
and other circuit piping based on a 20 °F temperature drop
through the zones. For water-source heat pump systems, the
primary circuit ow rate will usually be based on a 5°F temperature
drop. Such high ow systems must be piped with the boiler on
a separate loop.
e 200i boiler requires a continuous minimum water ow for proper
operation. e circulator for the boiler must be sized to overcome the
head loss of the boiler and the heating system in order to achieve the
required temperature rise. If the system contains hydronic antifreeze
this must be considered when sizing the pump. e temperature rise
across the boiler must never exceed 100°F (55.6°C).
Boiler pressure drop
Assume a pressure drop of:
• 1.9 feet WC (0.7 meter) for a ow rate of up to 18 GPM (68 LPM).
• 7.5 feet WC (2.3 meters) for a ow rate of up to 36 GPM (136 LPM).
Maintain boiler ow rate between 2 GPM and 36 GPM (7.6 to 136 LPM).
Boiler and system circulators
See the following pages for suggested piping for 200i boilers. All circulators are supplied by the installer, except the factory-installed postpurge circulator.
Boiler circulator the circulator that ows water through the boiler.
System circulator the circulator that ows water through the system, but not
through the boiler.
Boiler/system circulator a circulator that ows water through the boiler and
the system.
Circulator activation
See section 7 of this manual and the 200i Control manual for instructions on wiring
boiler and system circulators.
e 200i SmartCycle Control provides an isolated contact to operate the boiler circulator
(or boiler/system circulator).
e system circulator must be activated by a relay supplied by the installer. is relay
is usually activated by the system control or thermostat.
Piping guidelines
Support the piping All piping and
components must be supported such that no loads
or stresses are applied to the boiler. Al low for thermal
expansion in the piping design and passageways.
e piping diagrams in this manual omit piping
components such as unions. Always install unions
where needed to simplify piping and improve
serviceability.
Circulator requirements
Boiler postpurge circulator
e postpurge circulator supplied with the
200i (Figure 4), factory piped between the boiler
supply and return connections, is
for use in the system. It must remain connected as
supplied. e postpurge circulator is only used by
the 200i for postpurge ow to remove residual heat
in the combustion zone. e postpurge circulator
includes an integral check valve to prevent by-pass
ow during operation.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Additional controls
Local codes or job speci cations may require the use of additional controls, such as low
water cut-o s, ow switches, and high limit controls. Refer to the 200i Control manual
for electrical connections for auxiliary controls.
Follow the guidelines below to install typical controls in the piping.
Low water cut-o
When the boiler is installed above terminal units, or when required by applicable
codes, install a low water cut-o in the piping above the boiler. See suggested piping in
the diagrams in this section.
Use a probe-type control when possible.
Flow switch
When a ow switch is required, install the switch in a section of the piping that will
ensure enough ow to operate the switch.
NOT intended
Additional high limit controls
For ASME CSD-1 or Canadian applications, or when required by applicable codes,
install an additional high limit control in the supply piping above the boiler.
Make sure the limit control is set at least 20 °F above the highest operating temperature
of the 200i boiler.
11
Page 12
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Water piping (continued)
Expansion tank and air separation
e system must include an expansion tank to control thermal expansion. Install the
tank as close as possible to the boiler, and locate on the suction side of the system circulator. Make sure the tank is sized large enough to handle the system volume.
Figure 5 Expansion tank comparison
Figure 6 Diaphragm or bladder-type expansion tank
suggested piping
Diaphragm/bladder type expansion tank
Diaphragm or bladder-type expansion tanks have a membrane that separates the water
from the air in the tank. See Figure 5, le side. See Figure 6 for suggested piping.
Guidelines for diaphragm/bladder-type expansion tanks
• Always remove the tank from the system before charging. is ensures the air pressure
will be accurate. Make sure the charge pressure equals the required system cold- ll
pressure (usually 12 psig ).
• Install an automatic air vent on top of the air separator to remove air from the system.
Closed-type expansion tank
Closed-type tanks are those that have air above the water, in direct contact with the
water. See Figure 5, right side. See Figure 7 for suggested piping.
Guidelines for closed-type expansion tanks
• NEVER use automatic air vents in systems with closed-type tanks. e air must be
kept in the system, and returned to the tank, in order to keep the tank operating
correctly. Automatic air vents will bleed air out of the system, resulting in waterlogging of the tank, causing the boiler relief valve to weep.
• Air separation is done by connecting from an in-line air separator to the bo om of
the expansion tank (Figure 7). e tank must be mounted above the air separator.
• Install a tank ing in the bo om of the tank. It allows captured air to ow into
the upper portion of the tank, facilitates lling, and reduces recirculation in the
expansion tank piping.
Cold water ll
Follow all applicable codes when connecting the cold water ll to the piping. Use a
back ow preventer where required. See suggested piping on this and the following
pages. Also consider installing a water meter on the cold water make-up line. e water
meter will show if excessive make-up water is entering the system.
Figure 7 Closed-type expansion tank suggested piping
Undersized or waterlogged expansion tanks will
cause excessive make-up water to enter the system.
is will lead to section failure due to oxygen
corrosion and lime deposits.
12
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 13
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Zoning with zone valves
Flow balancing and control
On large systems, or when using a high-head circulator, install a di erential
pressure by-pass valve to limit the head applied to the zone valves.
Some systems may require balancing valves to control ow in the loops.
Figure 8 Suggested piping — single boiler — zone valve zoning — two-pipe or series loop (left), or primary/secondary piping (right)
Water piping (continued)
DHW operation, when required
e piping shown throughout this manual allows for domestic water heating
without ow through the heating loop(s). is is important for summertime operation of DHW tanks.
Make sure to incorporate ow/check valves as shown. ese prevent forced
ow in idle zones.
LEGEND • • • • • • •
1 200i boiler
2 Boiler circulator
3 System circulator
4 Boiler/system circulator
5 Indirect- red DHW tank
(when used)
6 DHW circulator
7 Flow/check valve
8 Cold water ll line
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
9 Expansion tank (shown with diaphragm-type —
see page 12 for piping a closed-type tank)
Expansion tank (shown with diaphragm-type —
see page 12 for piping a closed-type tank)
10 Air separator with automatic air vent (Replace air
vent with piping to the tank ing on closed-type
expansion systems.)
11 Low water cut-o (when required)
12 Extra high limit (when required)
13 Zone valve
14 Zone circulator
15 Di erential pressure by-pass valve — Use when high-
head circulator may cause noise, erosion or valve li ing
problems when only a few zone valves are open.
16 Boiler postpurge circulator (see page 11)
17 Header sensor, required where shown
Isolation valve
Purge valve — Suggested locations allow for improved
system lling and draining and initial air elimination.
Temperature gauge
13
Page 14
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Zoning with circulators
Sizing and ow control
Size circulators to provide the ow needed for the individual zones.
Provide ow/check valves where shown to prevent gravity circulation or
forced ow in idle zones.
Figure 9 Suggested piping — single boiler — circulator zoning — two-pipe or series loop (left), or primary/secondary piping (right)
Water piping (continued)
DHW operation, when required
e piping shown throughout this manual allows for domestic water heating
without ow through the heating loop(s). is is important for summertime operation of DHW tanks.
Make sure to incorporate ow/check valves as shown. ese prevent forced
ow in idle zones.
LEGEND • • • • • • •
1 200i boiler
2 Boiler circulator
4 Boiler/system circulator
5 Indirect- red DHW tank
(when used)
6 DHW circulator
7 Flow/check valve
8 Cold water ll line
9 Expansion tank (shown with diaphragm-type — see
page 12 for piping a closed-type tank) Expansion tank
(shown with diaphragm-type — see page 12 for piping
a closed-type tank)
10 Air separator with automatic air vent (Replace air vent
with piping to the tank ing on closed-type expansion
systems.)
11 Low water cut-o (when required)
12 Extra high limit (when required)
14 Zone circulator
14
16 Boiler postpurge circulator (see page 11)
17 Header sensor, required where shown
Isolation valve
Purge valve — Suggested locations allow for improved
system lling and draining and initial air elimination.
Temperature gauge
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 15
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Multiple boilers, primary/secondary
Sizing and ow control
Size circulators to provide the ow needed for the individual zones.
Provide ow/check valves where shown to prevent gravity circulation or
forced ow in idle zones.
e piping shown throughout this manual allows for domestic water heating
without ow through the heating loop(s). is is important for summertime operation of DHW tanks.
Make sure to incorporate ow/check valves as shown. ese prevent forced
ow in idle zones.
12" max
(305 mm)
8
9
7
12
11
Return
from system
7777
2
222
1111
16161616
LEGEND • • • • • • •
1 200i boiler
2 Boiler circulator
3 System circulator
5 Indirect- red DHW tank
(when used)
6 DHW circulator
7 Flow/check valve
8 Cold water ll line
9 Expansion tank (shown with diaphragm-type — see
page 12 for piping a closed-type tank) Expansion tank
(shown with diaphragm-type — see page 12 for piping
a closed-type tank)
10 Air separator with automatic air vent (Replace air vent
with piping to the tank ing on closed-type expansion
systems.)
11 Low water cut-o (when required)
12 Extra high limit (when required)
16 Boiler postpurge circulator (see page 11)
17 Header sensor, required
Isolation valve
Temperature gauge
DHW tappings
4
5
20010
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
15
Page 16
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Multiple boilers, parallel ow
Sizing and ow control
Size the boiler/system circulator to handle the ow needs of all zones. If
using variable speed control of the boiler/system circulator, ensure that the
ow never drops below the total minimum for all boilers connected. Do
not exceed the maximum ow of 50 GPM through any boiler.
When heating system boilers are piped in parallel as in Figure 12, connect
the DHW tank as a zone o of the main header or install boilers dedicated
to the DHW application.
LEGEND • • • • • • •
1 200i boiler
4 Boiler/system circulator
5 Indirect- red DHW tank
(when used)
6 DHW circulator
16
8 Cold water ll line
9 Expansion tank (shown with diaphragm-type — see
page 12 for piping a closed-type tank) Expansion tank
(shown with diaphragm-type — see page 12 for piping
a closed-type tank)
10 Air separator with automatic air vent (Replace air vent
with piping to the tank ing on closed-type expansion
systems.)
11 Low water cut-o (when required)
12 Extra high limit (when required)
16 Boiler postpurge circulator (see page 11)
17 Header sensor, required
Isolation valve
Temperature gauge
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 17
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
5
Chilled water systems
General
Provide the piping components shown in Figure 13 when
connecting a boiler to a chilled water system. e check valve
(item 4) prevents chilled water from entering the boiler loop.
Sizing and ow control
Size the system circulator to handle the ow needs of all zones.
If using variable speed control of the system circulator, ensure
that the ow never drops below the total minimum for all boilers connected.
Figure 13 Suggested piping — boilers connected to chilled water systems
Water piping (continued)
e boiler loop can be any of the designs in this manual, or per
standard engineering practices.
Use the balancing valve to adjust the boiler loop ow.
Expansion tank/air control
Chilled water systems generally use closed-type expansion
tanks. DO NOT use automatic air vents in these systems. All air
must be return to the expansion tank for the system to operate
reliably.
If the boiler loop is connected to air handling units
that use chilled water, install ow control devices to
prevent gravity circulation in the boiler loop during
the cooling cycle in the air handling units.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
17
Page 18
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
6
Gas piping
Check the gas type
e 200i comes from the factory ready to be piped to the gas
supply. If for any reason the boiler is not for the type of gas available at the installation site, call your Mestek representative to
resolve the problem. (See WARNING below.)
Gas supply components
Figure 14 depicts the proper way to connect the boiler to the gas
supply piping. e gas connection at the boiler is ½” NPT.
Item 1 Install the gas line piping from the gas meter or branch
in accordance with all applicable codes. See the next page for
suggested sizing, or refer to the National Fuel Gas Code or Canadian Gas Code for recommendations.
Item 2 e manual shut-o valve must be installed in the
supply piping. Install 5 feet above the oor where required by
applicable codes.
Failure to adhere to the following
could result in severe personal injury, death or substantial property
damage.
Item 3 For all gas supply piping, use only clean, burr-free black iron pipe, supported
independently from the boiler gas connection.
Item 4 Install a ground-joint union in the gas line for ease of installation and servicing.
Item 5 Provide a sediment trap at the bo om of the vertical section of the gas supply
pipe upstream of the gas controls.
Item 6 e gas cock must be equipped with a pressure test port. is test port is
used to measure the gas supply pressure at the boiler.
e gas line components in Figure 14 are not supplied with the boiler. ey must be
supplied by the boiler installer.
Always use a wrench on the gas grain components when making gas
connections. Never over-tighten the piping components or a failure
could result, causing possible severe personal injury, death or substantial
property damage.
Figure 14 Connecting gas supply line
Verify the gas type
Check the boiler rating plate to make sure that the boiler
is for the type of gas that will be used. If it is not, do not
connect the boiler to the gas supply.
Support the gas line
Support the gas line with hangers. DO NOT allow gas
train weight to rest on or cause bending of the boiler gas
connection ing.
Protect the gas connection tting
Use a – inch open-end wrench to hold the boiler
gas connection ing when tightening gas connection
piping to the boiler.
Never leak test with ame
Never use an open ame to test for gas leaks. Always use
an approved leak detection method.
Protect the boiler gas valve from
excessive pressure
When pressure testing system gas piping, disconnect
the gas piping from the boiler or isolate the boiler with
the manual shut-o valve if test pressure will be higher
than ½ psig (3.5 kPa).
1 Piping from gas supply
2 Manual gas valve with test port
(use tee-handle valve for
Massachuse s installations)
3 Piping must be clean and burr-free
black iron pipe
4 Ground-joint union
5 Drip leg with cap
6 Gas cock pressure test port
18
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 19
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
6
Gas piping (continued)
Gas piping joints
Always use a pipe sealant that is suitable for use
with LP gas. Failure to comply could result in
an explosion, causing possible severe personal
injury, death or substantial property damage.
Only use pipe dope listed for use with propane gas. Even natural
gas may contain some amount of propane.
Use pipe dope sparingly. Excessive pipe dope can block pipe
ow or foul gas train components.
Gas pipe sizing
Required supply pressure at boiler
Minimum gas supply pressure (natural gas or propane), both for
owing and static conditions:
4 inches (102 mm) water column.
Maximum gas supply pressure (natural gas or propane), both
for owing and static conditions:
Table 3 Gas ow capacity for black iron pipe
Iron
pipe
size
¾”278190152130115105907964
1 ”520350285245215195170150120
1 ¼”1050730590500440400350305250
1 ½”16001100890760670610530460380
¾”17211894817165564940
1”3202201751501351201059575
1 ¼”650455365310275250220190155
1
2
3
Pipe length, equivalent feet (length plus allowance for ttings)
10203040506080100150
Natural gas pipe ow capacity
Propane gas pipe ow capacity (cubic feet per hour) (notes 2, 3)
Notes, Table 3
Natural gas ow capacity is based on 0.60 speci c gravity. Refer to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, for other pressure drops and other speci c gravity gases.
e ow rates above allow for a pressure drop of:
Natural gas — 0.30 inches water column, with gas pressure 14 inches water column or less.
Propane — 0.30 inches water column, with gas pressure 14 inches water column or less.
To determine required ow rate in cubic feet per hour for all appliances connected to the gas line:
Natural gas — Divide total Btuh by the gas Btu per cubic foot rating (typically 1,000 Btu/
Propane — Divide total Btuh by 2,500.
(cubic feet per hour) (notes 1, 2, 3)
3
nominal).
14 inches (356 mm) water column.
Sizing guidelines
e sizing recommendations of Table 3 are taken from the National
Fuel Gas Code, ANSI Z223.1/NFPA 54. Propane values are based
on adjustment from propane speci c gravity and pressure.
Table 3 allows for a pressure drop from the main supply regulator
to the boiler of 0.3 inches (7.6 mm) water column for natural
gas or propane.
For conditions not shown in Table 3, other pressure drops, or
natural gas with other than 0.6 speci c gravity, refer to the appropriate code guidelines for sizing.
Equivalent length
Do not neglect the pressure drop due to pipe ings.
Equivalent length is the sum of the actual length of piping plus
the total equivalent lengths of all ings in the line from the
main regulator to the boiler connection. See Table 4 for equivalent lengths of common ings and components.
Multiple appliances
If more than one appliance is supplied by the same supply pipe, the
piping must be sized based on the maximum possible demand.
Undersized gas supply piping can cause the
gas line pressure to become negative during
operation of the 200i boiler. is can cause pilot
outages and operation failures of other appliances
connected to the line, including gas ranges, water
heaters, etc. Failure to properly size the gas lines
can result in potential for severe personal injury,
death or substantial property damage.
Table 4 Equivalent feet of pipe for common gas line components
Iron
pipe
size
1”2.65.20.61.5
1 1/4”3.56.90.81.9
1 1/2”4.08.00.92.3
2”5.210.31.23.0
12Allows for ow through the branch of the tee.
90° ElbowTee
Assumes valve is full open.
Equivalent feet of pipe for each tting
(note 1)
Notes, Table 4
Gate valve
(note 2)
Gas cock
Test all gas piping for leaks
All gas piping, components and connections must be leak tested
before pu ing the boiler in operation. Isolate the boiler from the gas
supply piping if testing with pressure greater than 14 inches (12.7 mm)
pressure. Failure to do so could result in severe personal injury, death or
substantial property damage.
Check all gas piping components and joints for
leaks. Use either a soap suds mixture, a gas leak
detector or other suitable means.
A er testing the system gas piping, remove the
gas valve cover plate on the le side of the boiler
(see illustration at right). Inspect and leak test
around the interior gas line and gas valve. Replace
the cover a er completing the gas connection
inspection and testing.
(note 2)
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
19
Page 20
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
7
Wiring a single boiler
Electrical shock hazard — Disconnect
all electrical power sources to the
boiler before making any electrical
connections.
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation! Verify proper operation a er
servicing.
Au moment de l’entretien des com-
mandes, étiquetez tous les ls avant de
les débrancher. Des erreurs de câblage
peuvent entraîner un fonctionnement
inadéquat et dangereux. S’assurer que
l’appareil fonctionne adéquatement une
fois l’entretirn terminé.
Failure to comply with the above could
result in severe personal injury, death or
substantial property damage.
e electrical connections to this boiler
must be made in accordance with all
applicable local codes and the latest
revision of the National Electrical Code,
ANSI /NFPA-70. Installation should
also conform to CSA C22.1 Canadian
Electrical Code Part I if installed in
Canada. Install a separate 120 volt 15
amp circuit for the boiler. A properly
rated shut-o sw itch should be located at
the boiler. e boiler must be grounded
in accordance with the authority having
jurisdiction, or if none, the latest revision
of the National Electrical Code, ANSI/
NFPA-70.
Figure 15 Electrical connection board (see item 10,
page 3 for location — Also see the wiring
summary illustrations on the next pages)
Figure 16 120VAC power service terminals on electri-
cal connection board — See Figure 15 for
location of the power terminal strip
Line voltage eld wiring of any controls
or other devices must use copper
conductors with a minimum size of #14
awg. Use appropriate wiring materials
for units installed outdoors.
General
• e wiring and control information in the Boiler manual is
targeted at single-boiler, stand-alone installations. For multiple
boilers and advanced options, see the 200i Control manual.
• See Figures 20 and 21 for a wiring summary. See the Control
manual for content not covered in this manual.
Power supply (120 VAC)
• See Figures 15 and 16.
• Connect minimum 14 awg copper wire to the power
connection as shown in Fig ure 16.
• Install a fused service switch, mounted and installed in
accordance with all applicable codes.
20
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 21
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
7
Wiring single boiler (continued)
Circulator wiring
Postpurge circulator
• The circulator shipped installed with the boiler
cannot be used for system circulation.
as supplied from the factory. It circulates water a er the boiler
stops ring to prevent potential damage from heat pocketing
in the top of the heat exchanger.
• e postpurge circulator is factory-piped and pre-wired. Do
not change the usage, the wiring, the location or the piping.
Boiler circulator
• See section 5 of this manual for circulator piping.
• Figure 19 shows wiring of the Boiler circulator (or boiler/
system circulator) to the terminal strip of the 200i electrical
connection board.
• DO NOT directly connect a circulator with a motor larger
than 1/4 hp. For larger motors, install a circulator relay or
motor contactor . Figures 17 and 18 show the correct ways
to install the boiler circulator using a relay or motor starter.
It mu st be used
Figure 19 Circulator wiring terminal strip (see Figure 15
for location) — Also see the wiring summary
illustrations on the next pages)
Figure 17 Wiring the boiler circulator using a circulator
Figure 18 Wiring the boiler circulator using a relay or
relay (required for motors over 1/4 hp)
starter (required for motors over 1/4 hp)
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
21
Page 22
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
7
Wiring single boiler (continued)
Sensor wiring
No sensor wiring is necessary unless:
• Outdoor reset application To operate with outdoor reset, purchase and install
an outdoor sensor. Mount the sensor such that it is shielded from direct sunlight if
possible and not likely to be covered by snow dri s or debris. Connect the outdoor
sensor leads to the electrical connection board as shown in Figure 21b, page 24.
• Header sensor application As show n in the piping diagrams in this manual,
a header sensor is needed if the boiler supply temperature may be di erent from
the header temperature. If required, purchase and install a header sensor in an immersion well. Locate the sensor where it will accurately sense the system water
supply temperature. Connect the sensor leads to the electrical connection board
as shown in Figure 21b, page 24.
• Return water temperature sensor e return water temperature sensor
is optional, only needed if you want to automatically control the boiler postpurge
pump cycle time. To use the return water temperature sensor, purchase and install
the sensor in a well in the boiler return piping. Connect the sensor leads to the
electrical connection board as shown in Figure 21b, page 24.
IAR (Indoor Air Reset) wiring, when used
• Heat Demand terminal connections e end switch leads from the zone valves
must connect to the Heat Demand terminals on the electrical connection board as
shown in Figure 20 and Figure 21a.
• See Figure 20 for typical wiring to the IAR inputs when using 4-wire zone valves
without a zone controller. For other applications, such as circulator relays or zone
controllers, see Appendix A in this manual. Also see the Control manual.
Polarity e connections to the IAR positive terminals (IAR +)
must be to the same location on the zone valve as the thermostat wire,
as shown in Figure A1. e connections to the IAR negative terminals
(IAR –) must be from the zone valve terminal connected to the 24VAC
common line, as shown. Connecting the wires incorrectly can cause the
transformer to be shorted out and damaged. Verify the wiring with a
voltmeter.
Figure 20 Indoor Air Reset wiring to IAR terminals with
4-wire zone valves and no zone controller
(see Figure 21a for terminal block 6 location).
Always use a voltmeter to check the leads coming from the end switches
of the zone valves. With the thermostat calling for heat, connect the
voltmeter leads across the wires coming from the end switches. If
the meter shows a voltage reading, the zone valve wires are incorrect.
Change the wiring and retest. DO NOT connect the wires to the boiler
until you have tested as described. Incorrect wiring can damage the
boiler control or other system components.
• If there is only one transformer feeding all of the zone valves in the system, you can
omit the wires to the IAR negative terminals (IAR –) on all but one of the zone
valves. is is because these terminals are jumpered internally on the electrical
connection board. If there is more than one transformer, provide one wire from
each transformer common side to one of the IAR negative terminals (IAR –).
DHW wiring
• To operate the boiler for domestic water heating with a storage tank, install and
pipe the tank according to the tank manufacturer’s instructions and the recommended piping diagrams in this manual. Consult the factory for applications not
covered.
• e circulator used for DHW must be operated by a circulator relay or zone controller that is activated when the tank aquastat calls for heat.
• Connect the tank aquastat terminals across the DHW DEMAND terminals on
the electrical connection board as shown in Figure 21.
22
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 23
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
7
Figure 21a 200i wiring summary (see Boiler manual and Control manual text for additional information)
Wiring and control setup (continued)
Also see page 20
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
23
Page 24
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
7
Figure 21b 200i wiring summary (see Figure 21 for locations) (see Boiler manual and Control manual text for additional information)
Wiring and control setup (continued)
Also see page 21
24
Also see page 22
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 25
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
8
Control setup
Before control setup
Before beginning the HeatNet control setup, remove the wires
connected to the HEAT DEMAND and DHW DEMAND
terminals
must be removed to prevent a call for heat during the setup process.
Close the manual gas valve before proceeding to prevent any possibility
of the boiler ring during setup.
on the electrical connection board (see Figure 21). ese
The HeatNet control display
Starting the display
1. Check all wiring to make sure it is complete and all wires are securely connected.
2. Verify that the HEAT DEMAND and DHW DEMAND wires are removed.
3. Turn on power to the boiler and then turn the boiler on/o switch ON.
4. e control will beep at least twice and the display will show the rst STANDBY
display in Figure 22. Note that pushing the DOWN bu on on the keypad will
change the right side of the display as shown, providing information on various
setpoints and parameters.
5. e display, LOC SET, means the setpoint temperature. Figure 22 shows the factory default values.
Figure 22 HeatNet display during Standby (no call
for heat) — pressing the DOWN key on the
keypad changes the display as shown
Accessing setup menus
1. With the display in STANDBY, press and hold the BACK key for 5 seconds.
2. e display will change to:
3. Press the SELECT key to select setup. (Note that pressing the DOWN key would
change the selection to VIEW LOG.)
4. e display will now show the rst options in the setup menus:
5. Press the DOWN key to access additional menu options. Pressing the DOWN
bu on once will change the display to:
6. e cursor moves to the second line, indicating this option could now be selected
with the SELECT key.
7. Continuing to press the DOWN key will access these menu options:
• BOILERS
• SETPOINTS
• INDOOR AIR
• PUMP OPTIONS
• NIGHT SETBACK
• OPTIONS
• LOG/RUNTIME
• AUX FUNCTIONS
• SYSTEM CLOCK
• ADVANCED SETUP
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
25
Page 26
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
8
Control setup (continued)
Recommended settings
1. e following recommendations should cover most single-boiler applications.
2. e se ings covered in this manual are SETPOINTS, INDOOR AIR, OUTDO OR
AIR and SYSTEM CLOCK.
3. For other se ings and a complete menu tree, consult the 200i Control manual for
information.
Adjust SETPOINTS
Setpoint menus
1. Use the arrow keys until the cursor points at SETPOINTS.
2. Press the SELECT bu on to enter the SETPOINTS menus. e menu selections
available as you use the arrow keys will be:
• LOC SETPOINT (means the local setpoint, or the target temperature of the
boiler supply water; this is sensed by the SUPPLY sensor).
• SOURCE (means whether the setpoint temperature is to be controlled at the
boiler or by a remote device leave the default se ing of AUTO unless you
plan to use a remote controller with a 4-20ma output).
• DHW SETPOINT (means the supply temperature the boiler will target when
operating on a call for DHW heating; this uses the same sensor as the local
setpoint).
• OP LIMIT (means the operating limit temperature of the boiler).
• LIMIT BAND (this is the di erential for the limit function).
Set the local setpoint (LOC SETPT)
1. Use the arrow keys until the cursor points at LOC SETPT. e display will show:
3. With the cursor on DHW SETPT, press the SELECT key
to change the value, using the same procedure as with the
LOC SETPT adjustment.
4. e DHW setpoint should usually be 190°F. To obtain this
setpoint, you will also have to increase the OP LIMIT setting to 225 or 230°F so the boiler won’t prematurely cycle
on the limit function.
5. When the DHW se ing is complete, press SELECT and
BACK to return to the setpoint menus.
Set OP LIMIT (operating limit)
1. Use the same procedure as on the previous se ings to
change the operating limit temperature.
2. Use the arrow keys to select OP LIMIT, then press SELECT.
3. If the boiler setpoint is to be higher than 180°F, you will
need to increase OP LIMIT. e maximum se ing for OP
LIMIT is 230°F. So the maximum allowable boiler setpoint
is generally 190°F.
4. Once the se ing is correct, press SELECT, then BACK to
return to the setpoint menus.
The LIMIT BAND
1. Do not change the LIMIT BAND se ing unless speci c
application demands require a change or when directed by
the factory.
2. e cursor must be pointing at LOC SETPT. e value shown may vary if the control has been adjusted before.
3. Press the SELECT bu on to change the local setpoint value.
4. e cursor will move to the temperature number.
5. Use the arrow keys to increase or decrease the temperature to the desired se ing.
If you hold down the arrow key the numbers will change faster a er a
brief waiting period.
6. W hen the se ing is correct, press the SELECT key to accept. en press the BACK
key to leave the local setpoint adjustment.
7. e local setpoint should be set at the design water temperature for the heating
units (typically 180°F for nned-tube baseboard, for example).
e setpoint must never be higher than the OP LIMIT se ing minus
the LIMIT BAND minus half of the HEAT BAND se ing. is would
cause the boiler to hit limit while trying to modulate.
Example: If LIMIT BAND is 20°F, OP LIMIT is 215°F, and HEAT
BAND is 30°F, the local setpoint must never be higher than 215 - 20
- 30/2 = 180°F.
Set the DHW setpoint (DHW SETPT)
1. Skip this procedure if the boiler is not used for DHW heating.
2. Use the arrow keys until the cursor is at DHW SETPT. e display will be:
Return to main menus
When the setpoints have all been adjusted as
desired, press the BACK key until you return to
SETPOINTS.
INDOOR AIR
General
• Use the indoor air reset option whenever possible. e
indoor air technology monitors space heating demand to
help the boiler operate at the highest possible e ciency
throughout the season.
• To apply indoor reset you must wire the IAR inputs and the
HEAT DEMAND terminals as described in Section 7.
Enable or disable IAR
1. e only se ing for indoor air reset that you will need to
make is to enable the function.
2. Use the arrow keys until the cursor points to INDOOR AIR.
3. Press SELECT to enter the indoor air menus.
4. e display will show:
26
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 27
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
8
5. e factory default se ing is ON, or IAR enabled. If the boiler is wired for IAR,
then leave the se ing at ON.
6. To change the se ing to o , press SELECT with the cursor pointing at IA RESET.
7. Press either arrow key and the value will change to OFF.
8. Press SELECT to save and BACK to return to the main menus (INDOOR RESET again).
Control setup (continued)
Return to main menus
When you have nished with IAR, return to the main menus by using
the BACK key.
OUTDOOR AIR, when used
General
Skip this procedure if there is no outdoor sensor present.
• W hen possible, use Indoor Air Reset instead of outdoor reset. IAR provides much
be er feedback on system needs.
OUTDOOR AIR menu
1. Use the arrow keys until the cursor points at OUTDOOR AIR . en press SELECT.
2. e display will show the beginning of the OUTDOOR AIR menus:
7. Press SELECT and the display will show:
8. Don’t use the arrow keys yet, but if you use the DOWN
arrow twice, the display will show:
9. With the cursor on the se ing you want to change, press
the SELECT key, then use the arrow keys to change the
temperature as you did for SETPOINTS.
10. LOW WATER (@ HI OA) Set for the supply water temperature desired when the outside air is at the temperature
when no heat is needed (HI OA). is should generally be
set equal to room temperature, or 70°F unless the application calls for another se ing.
11. HI OA Set this to the outside temperature at which no
heat is needed, usually 68°F or lower.
3. OUTDOOR AIR menus are:
• OA SHUTDOWN (shuts the boiler down when outside temperature is above
OA SETPT).
• OA SETPOINT (outside temperature at which no heat is needed used to
shut down boiler above this temperature).
• OA RESET (enables or disables outdoor reset function).
• SET OA SETPTS (when outdoor reset is enabled, this leads to setpoint selections).
Outdoor shutdown
1. Enable or disable outdoor shutdown by pressing the SELECT bu on with the
cursor on OA SHUTDOWN.
2. Use the arrow keys to change from ON to OFF.
3. Press SELECT to save, then BACK to return.
4. en arrow key to OA SETPT to set the desired outdoor air shutdown temperature.
5. Press SELECT and the cursor will move to the temperature.
6. Use the arrow keys to change the se ing.
7. Press SELECT, then BACK to accept and return.
Outdoor reset, when desired
1. To set outdoor reset operation, use the arrow keys until the cursor points at OA
RESET.
2. e default se ing is ON.
3. To change the se ing, press SELECT and use the arrow keys to change from ON
to OFF.
4. Press SELECT, then BACK.
5. If outdoor reset is enabled, set the reset temperatures as follows:
6. Use the arrow keys until the cursor points at SET OA SETPTS.
12. HI WATER (@LO OA) is is the required supply water
temperature at design heating conditions; i.e. when outside
air temperature is at ODT, the outdoor design temperature,
or maximum heating conditions. is temperature would
typically be 180° for nned-tube baseboard systems.
13. LO OA is is the ODT, or design outdoor temperature
for maximum heating requirements from the system.
14. Use the arrow keys to navigate to each of the above. en
adjust as required.
Return to main menus
When you have nished with outdoor reset,
return to the main menus by using the BACK key.
Set the system clock
• Use the arrow keys in the main menus to navigate to SYSTEM
CLOCK. Use the procedures used for SETPOINTS and
other adjustments to select and modify TIME, DAY OF WEEK,
MONTH, DAY and YEAR.
• Because the events log gives time of occurrence, it is best for
the system clock to be correct.
After completing setup, press the BACK
key until the display returns to STANDBY.
Then turn o power and the boiler on/o
switch. Reconnect HEAT DEMAND and
DHW DEMAND wires.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
27
Page 28
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
9
Vent piping (and air piping when used)
All 200i boilers must be vented using only the materials listed in the 200i Vent/Air manual. e vent installation must meet
requirements for direct vent (when air is ducted to the boiler air intake) or ANSI Category IV venting (when air is taken from
the boiler room).
DO NOT install a 200i boiler on a common vent system. All 200i boilers must be individually vented. Failure to
comply could result in improper operation of any of the appliances on the vent system, resulting in possible severe
personal injury, death or substantial property damage.
When a 200i boiler replaces a boiler that shared a common vent system, follow the guidelines below to check operation of the remaining
appliance(s).
BEFORE PROCEEDING FURTHER Install the vent (and air) piping according to the 200i Vent/Air manual.
Common vent systems
If an existing boiler is removed from a common venting system,
the common venting system may then be too large for the proper
venting of the remaining appliances connected to it. At the time of
removal of an existing boiler, the following steps shall be followed
with each appliance remaining connected to the common venting
system placed in operation, while the other appliances remaining
connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction,
leakage, corrosion and other de ciencies which could cause
an unsafe condition.
3. Insofar as is practical, close all building doors and w indows and
all doors between the space in which the appliances remaining connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers
and any appliance not connected to the common venting
system. Turn on any exhaust fans, such as range hoods and
bathroom exhaust, so they will operate at maximum speed.
Do not operate a summer exhaust fan for a boiler installation.
Close replace dampers.
4. Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5. Test for spillage at the dra hood relief opening a er 5 minutes of main burner operation. Use the ame of a match or
candle, or smoke from a cigare e, cigar or pipe.
6. A er it has been determined that each appliance remaining
connected to the common venting system properly vents when
tested as outlined above, return doors, windows, exhaust
fans, replace dampers and any other gas-burning appliance
to their previous condition of use.
7. Any improper operation of the common venting system
should be corrected so the installation conforms with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54. When
resizing any portion of the common venting system, the
common venting system should be resized to approach the
minimum size as determined using the appropriate tables in
Appendix F in the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 and or CSA B149 Installation Codes.
Systèmes d’évacuation d’communs
Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé
au système d’évacuation commun et qui fonctionne alors que
d’autres appareils toujours raccordés au système d’évacuation ne
fonction-nent pas: système d’évacuation
1. Sceller toutes les ouvertures non utilisées du sys-tème
d’évacuation.
2. Inspecter de façon visuelle le système d’évacu-ation pour
déterminer la grosser et l’inclinaison horizontale qui conviennent et s’assurer que le système est exempt d’obstr uction,
d’étranglement de fruite, de corrosion et autres défaillances
qui pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les portes et les
fenêtres du bâtiment et toutes les portes entre l’espace où les
appareils toujours raccordés du système d’évacuation sont
installés et les autres espaces du bâtiment. Me re en marche
les sécheuses, tous les appareils non raccordés au système
d’évacuation commun et tous les ventilateurs d’extraction
comme les ho es de cuisinère et les ventilateurs des salles
de bain. S’assurer que ces ventilateurs fonctionnent à la
vitesse maximale. Ne pas faire fonctionner les ventilateurs
d’été. Fermer les registres des cheminées.
4. Me re l’appareil inspecté en marche. Suivre les instructions
d’allumage. Régler le thermostat de façon que l’appareil
fonctionne de façon continue.
5. Faire fonctionner le brûleur principal pendant 5 min ensuite,
déterminer si le coupe-tirage déborde à l’ouverture de
décharge. Utiliser la amme d’une allune e ou d’une chandelle ou la fumée d’une cigare e, d’un cigare ou d’une pipe.
6. Une fois qu’il a été d éterminé, selon la métode indiquée ci-dessus,
que chaque appareil raccordé au système d’évacuation est
mis à l’air libre de façor adéquate. Reme re les portes et les
fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
7. Tout mauvais fonctionnement du systéme d’évacu-tion
commun devrait étré corrigé de façor que l’instal-lation soit
conforme au National Fuel Gas Code, ANSI Z223.1/NFPA
54 et (ou) au x codes d’installation CSA-B149. Si la grosseur
d’une section du système d’ évacuation doit étré modi ée,
le système devrait étré modi é pour respecter les valeurs
minimales des tableaux pertinents de l’appendice F du National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) des
codes d’installation CSA-B149.
28
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 29
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
10
Condensate drain line
Fill the condensate trap
Before installing the condensate line, you must ll the condensate
trap with water. is will prevent ue products from escaping
into the room. To ll the trap:
• Temporarily a ach a –inch clear plastic hose to the condensate hose barb (see Figure 23).
• A ach a funnel to the othe end of the hose and hold the funnel
so it is higher than the hose barb.
• Pour water into the funnel until water backs up into the tube.
• Remove the temporary plastic hose.
e condensate trap must be lled when ring the
boiler to prevent ue gases from escaping into the
room.
Condensate line installation
Condensate tubing material
e condensate tubing must be silicone rubber, –inch
(9.5 mm) diameter.
Condensate line requirements
Failure to adhere to the following could result in
condensate line leakage, resulting in potential for
severe personal injury, death or substantial property
damage.
❑ Use only silicone rubber tubing, -inch (9.5 mm)
diameter.
❑ Protect the condensate line from damage and
secure it in position.
❑ Terminate the condensate line at an appropriate
drain.
❑ Do not install the condensate drain line such that it
could be exposed to freezing temperatures.
❑ Install a condensate pump if no appropriate drain is
available.
Attachment
Feed the silicone rubber tubing through the condensate line exit
opening and slide the tubing end onto the condensate line hose
barb as shown in Figure 23.
Securing/protecting the condensate line
Secure the tubing Secure the condensate line to the oor
with clips or other means to prevent movement.
Protect tubing from damage If foot tra c poses a risk to
the tubing, install a cover over the tubing, or some other means
to protect it from damage or movement.
Prevent freezing Do not route the line through, or termi-
nate the line in, any area that could expose the condensate to
freezing temperatures.
Floor drain termination
If the condensate line can be routed to a oor drain, and applicable codes do not prohibit draining untreated condensate,
terminate the condensate line so condensate can reliably ow to
the drain.
Condensate pump termination
If no gravity drain is available, install a condensate pump. Use
only a pump designed for use with condensing furnaces and
boilers. e pump must have an over ow switch to prevent
damage from over owing condensate. Wire the switch into the
boiler limit circuit. See the 200i Control manual for details.
❑ Install a condensate neutralizing system when
required.
Figure 23 Connecting a condensate drain line
Neutralization
When required by codes or preference, install an appropriate
condensate neutralization system.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
29
Page 30
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
11
Fill and test the system
Failure to adhere to the following could result in
boiler section failure, resulting in potential for
severe personal injury, death or substantial property
damage.
❑ Flush and clean the system before lling.
❑ Provide clean water to ll the system
❑ Water quality must be as prescribed in this manual.
Follow the system water checklist
Follow the guidelines in this section to ll and test the system. e system water quality must meet the conditions given, and you and the owner must make
sure the conditions will be maintained throughout the life of the boiler.
❑ Closed systems only
• A er ushing the system thoroughly, use trisodium phosphate or other chemical sold for cleaning hydronic systems
to remove sediment and sludge.
Use caution when working with chemicals,
following all guidelines speci ed by the chemical
supplier and the applicable codes.
❑ Purge air from the system
• e system should be installed with purge valves such as
those shown in the suggested piping in this manual. Purging
is the most e cient way to ll the system and remove most
of the air.
• Connect a hose to a purge valve and run the hose to an appropriate draining area. (When lling with antifreeze solution,
run the hose back to the solution tank.)
• Close all isolation valves in the system.
• Do not apply the 200i boiler on open systems, such as direct heating of domestic
water, swimming pool heating or process applications that use system water. For
these applications, you must install a heat exchanger.
❑ Hard water conditions
• If water hardness exceeds 7 grains, use a water so ener in the ll line to so en the
water before it enters the system.
• On multiple boiler commercial installations, the large volume of water in the system can contain substantial mineral salts, even if the ll water hardness is less than
7 grains. ese salts can deposit in the boiler heat exchanger as limestone, causing
possible section damage. Commercial installations should usually be lled with
so water to avoid this problem.
❑ Prevent oxygen corrosion
• Make sure the system is provided with adequate automatic air elimination, including
an in-line air separator and automatic air vents (diaphragm or bladder tank systems)
or piping to the expansion tank (closed-type expansion tank systems).
• Do not connect the 200i boiler to a system that contains non-barrier radiant tubing.
Non-barrier tubing can allow oxygen to enter the system, causing oxygen corrosion
of the boiler heat exchanger.
❑ Flush and clean the system
• Open the manual valve (or quick- ll valve) on the make-up
water line. (When lling the system with glycol, connect
from the glycol pump to one of the purge valves with a hose.)
• Purge each zone separately by opening the isolation valves
for that zone, allowing water to push the air through and ll
the zone. A er lling the zone, close the isolation valves and
move to the next zone.
• Fill and purge the boiler loop in the same manner.
• A er the boiler is operated for a while, air entrained in the
ll water will bubble out of the water as it heats, and will
have to be removed by using air vents in the system.
❑ Add a chemical inhibitor
• A er purging and lling the system, add a chemical inhibitor sold for use in hydronic systems to prevent limestone
and magnetite deposits from forming, and to protect the
boiler from galvanic corrosion.
❑ Water pH
• Flush the system to remove sediment, ux, lings and other foreign ma er. Use
cleaning chemicals sold for use in hydronic systems.
• Replacement boiler installations o en have large amounts of accumulated sediment
and corrosion that must be removed to ensure boiler life and reliable operation.
• Flush each zone of multi-zone systems individually using the purge valves and isolation valves in the system.
• Flush until the water runs clean.
30
• e boiler water must be slightly basic, never acidic. Use litmus paper to check pH, which should range from 7.0 minimum to 8.5 maximum.
• If pH does not comply, provide water chemistry correction
from a quali ed water treatment specialist. If required, make
sure that the owner is aware and that the regimen will be
continued.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 31
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
11
Fill and test the system (continued)
❑ Antifreeze
• Antifreeze for hydronic systems contains propylene glycol and an inhibitor. Without the inhibitor the glycol is actually corrosive. So the system water must be
checked at least annually to ensure that the inhibitor is at the correct level .
• Never use galvanized piping in a system that contains antifreeze. Never use chromate
water treatment. Either of these will react with the inhibitor in the antifreeze mix .
• Antifreeze concentration If not using a pre-mixed antifreeze solution, determine the amount of antifreeze to add based on the total volume of the system
piping, the boiler and the expansion tank. Follow the antifreeze manufacturer’s
instructions for the ratio of glycol required for the lowest expected exposure temperature. NEVER use a glycol mix greater than 50%.
• Prevent leaks Glycol will escape more easily than water through any leak in
the system. So the glycol concentration will reduce if a leak is allowed to continue.
Eliminate all leaks in the system and have the owner frequently inspect the visible
portions of the system for leaks periodically. Do not use circulators or valves with
packing glands, the packing glands can weep.
• Install a water meter Because the system must be installed with automatic
water make-up to ensure pressure will always be at least 12 psig, you should install
a water meter with one half-gallon resolution on the make-up water line. is will
allow monitoring to see if excessive make-up water is entering the system.
• Circulator sizing Glycol/water mixtures do not move heat as well as water
only. e circulator size must be increased to account for this. As a rule of thumb,
increase the ow rate by 15%. Assume a 10% reduction in pressure drop compared
to water only at a give ow rate.
• Constant circulation For areas of the system that will be exposed to low temperatures, use continuous circulation to keep the water moving in the pipes.
• Expansion tank sizing Increase the expansion tank size about 20% to account
for the e ects of the antifreeze.
❑ System pressure
• Once the system is cleaned, lled, purged and treated as
required, set the make-up water pressure reducing valve
to the correct cold- ll pressure. is is usually 12 psig for
systems using 30 psig relief valves. For higher pressure systems, set the cold- ll pressure such that the system pressure
will never exceed about 80% of the boiler relief valve se ing
when system water temperature reaches the maximum operating temperature that the system and boiler temperature
controls will allow.
e pressure in the boiler must never be below
12 psig. Lower pressure could allow localized
boiling in the boiler heat exchanger, causing
possible damage and section failure.
• At cold ll, the water level in closed-type expansion tanks
should not be above center. Use the tank ing to verify
tank water level is correct.
• As the system heats up, the water will expand, causing the
system pressure to increase. If the expansion tank is properly
sized and installed, the system pressure will never exceed
about 80% of the relief valve set pressure (24 psig for typical
residential systems).
• If the system operating pressure becomes too high, check the
expansion tank to ensure it is large enough. For closed-type
expansion tanks, make sure there are no leaks in the piping
or the tank and the tank ing is correctly installed. For diaphragm or bladder-type tanks, you may have to remove the
tank from the system and verify that it can hold pressure. If it
cannot hold pressure, the membrane may be damaged.
If the system pressure is allowed to rise too high,
the boiler relief valve will open, allowing water to
escape from the system. e resultant addition of
make-up water will cause mineral deposits and
oxygen corrosion in the boiler.
• Indirect heat exchangers Output from indirect heat exchangers (including
indirect water heaters) can drop substantially when using antifreeze/water. Make
sure the exchanger is sized correctly for the application.
Use only antifreeze sold for use in hydronic systems
Never use automotive antifreeze. Automotive antifreeze
and ethylene glycol are toxic to humans and animals and will
damage rubber components in the system.
Make sure the owner is aware that the antifreeze must be
checked periodically by a quali ed technician to ensure
the concentration is correct and that the inhibitor level is
adequate.
Obtain the MSDS for the antifreeze and leave a copy with
the owner. Follow antifreeze manufacturer’s guidelines for
application and maintenance.
Failure to follow these guidelines could result in system or
boiler failure, causing possible severe personal injury, death or
substantial property damage.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
❑ Final checks
• A er the system is cleaned, lled and purged, and the system
pressure is correctly set, make sure the water chemistry is
correct. e pH and chemistry must be as required (and
speci ed by the chemical treatment specialist when required).
• Make sure all valves are correctly set. Isolation and ll valves
should be open before start-up. Purge valves must be closed.
• Open the valve on each automatic vent in the system about
one quarter turn to allow venting.
• oroughly inspect the system for leaks or weeping valves.
Eliminate all system leaks to prevent excessive
make-up water, which introduces oxygen as well
as lime-forming minerals. is can lead to heat
exchanger damage, resulting in possible severe
personal injury, death or substantial property
damage.
• Watch the boiler pressure/temperature gauge throughout
the start-up process. Make sure the pressure never drops
below 12 psig and never goes higher than 80% of the boiler
relief valve se ing pressure.
31
Page 32
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Starting the boiler
Failure to adhere to the following could result in severe personal
injury, death or substantial property damage.
Accessibility
e boiler must be accessible from both the right and le sides in order to do a
correct start-up/adjustment. Make sure the ame window on the le side and
the gas valve thro le adjustment opening in the jacket top are accessible. See
Figure 29, page 38.
Follow the start-up checklist
Perform the start-up check list procedures before starting the boiler.
Turn o power and fuel supply
Turn o electrical power to boiler if not already o . Close the main manual gas
valve at the boiler.
Verify the gas type
Check the boiler rating plate to make sure that the boiler is for the type of gas
that will be used. If it is not, do not the boiler will have to be adjusted for the
correct gas, for both high re and low re.
Install boiler per manuals
Read and follow all boiler instructions, including this Boiler manual, the 200i
Vent/air manual and the 200i Control manual.
All water piping, gas piping, vent piping and air piping must be complete before
starting the boiler.
Should overheating occur or
gas supply fail to shut o :
Do not interrupt water ow to the boiler.
Instead, shut o gas supply to the boiler
with the manual valve in the gas supply
line.
En cas de surchau e ou si
soupape en gaz ne s’arrête
pas :
N’interrompez pas l’écoulement d’eau
par la chaudière. Fermez manuellement
le robinet d’arrêt de l’admission de gaz.
Start-up checklist
❑ Read all boiler manuals
• e 200i is supplied with three manuals:
• Boiler manual
• Vent/air manual
• Control manual.
• Read and familiarize yourself with all three manuals before
proceeding with start-up.
❑ Check the boiler area
• Make sure there are no combustible materials or chemicals
that could cause air contamination in the boiler room.
Check gas piping for leaks
Check all gas piping for leaks, including the boiler interior gas piping and
connections, per page 19 of this manual.
Never leak test with ame
Never use an open ame to test for gas leaks. Always use an approved leak
detection method.
Propane gas applications
e odorant in propane gas can fade over time, reducing or eliminating the gas
odor. is makes the gas undetectable by smell. Before start-up, and periodically a erwards, have the propane supplier check/verify the odorant level.
Never attempt to measure gas valve outlet pressure
Do not a empt to measure the boiler gas valve outlet pressure. e high negative
pressure in the venturi can suck uid out of a manometer, pulling it into the gas
valve. is would destroy the gas valve, rendering it unusable.
32
❑ Verify vent piping
• Inspect vent piping to be sure all joints are secure and properly sealed.
• Verify vent piping supports are correctly placed and secure.
• Check vent termination to be sure it is correct and not obstructed.
• Measure total vent pipe length and note the number of
ings. Make sure the vent complies with the 200i Ve nt /
air manual.
❑ Verify combustion air and ventilation
• If combustion air is supplied from the boiler room, make
sure air openings agree with the requirements given in this
manual.
• If combustion air is piped to the boiler:
• Inspect air piping to be sure all joints are secure and
properly sealed.
• Verify air piping supports are correctly placed and se-
cure.
• Check air inlet termination to be sure it is correct and
not obstructed.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 33
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
• Measure the air piping length and note the number
of ings. Make sure the air piping complies with the
200i Vent/air manual.
• Verify ventilation openings to the boiler room. Even if air is
piped to the boiler, the boiler room must have ventilation
openings as speci ed in this manual.
Starting the boiler (continued)
❑ Verify electrical connections
Before turning power on to the boiler:
• Remove the electrical box covers on the right side of the
boiler.
• Inspect all wiring and connections. Make sure there are no
loose connections or wires.
❑ Controls
• Follow the instructions in the 200i Control manual to set
the operating temperatures and parameters required for the
installation (if not already done).
• Set limit controls to their lowest se ings.
• Verify thermostat circuits following the procedure given in
the 200i Control manual (if not already done).
❑ Prepare the condensate system
• Verify the condensate line is connected to the boiler, correctly installed and terminated.
• Turn on power to the condensate pump (if used).
• Make sure the condensate neutralization system (if used) is
functional.
• Slide the condensate hose o of the boiler condensate hose
barb. Connect a clear plastic tube (3/16 inch diameter) to
the hose barb. Pour water into the tube until water backs
into the tube at the hose barb, indicating the trap is full.
• A er lling the condensate trap, remove the ll hose.
• Rea ach the condensate line to the boiler condensate hose
barb.
❑ Verify boiler/system water piping
• Inspect all water piping. Make sure it complies with this
manual.
• Check the boiler relief valve. Verify the relief valve se ing is
correct for the application.
• Make sure the boiler and system are full of water and that
the system has been purged and is ready for operation.
• System pump Activate the system pump if it is not controlled by the 200i SmartCycle Control.
❑ Verify gas piping and connections
• Before starting the boiler, smell around the area for presence
of gas odorant. Immediately locate and correct any leak.
• Connect a manometer to the manual gas valve outlet test
port. Open the valve and measure the gas pressure. It must
not be above ½ psig (3.5 kPa).
Manual gas valve
• Open the main manual gas valve and check the gas piping
and joints in the boiler. Check for leaks, if not already done,
following the instructions on page 19.
❑ Turn on power and gas
• Turn on power to the boiler.
• Open the manual gas valve.
❑ Operating instructions
• Adjust system controls or thermostats to call for heat.
• Read about the SmartCycle control display on page 34.
en start the boiler following the Operating instructions
on page 35 (page 36 for French version).
• e boiler must be checked and adjusted, if necessary, a er
starting. Once the boiler has started, follow the instructions
beginning on page 37 to check boiler operation and adjust
as needed, using instruments.
❑ If the boiler doesn’t start:
• Check external limit controls, low water cut-o s, etc. to be
sure they are closed.
• Check the 200i SmartCycle control display for indications
of faults.
• Are SmartCycle control se ings correct for the application?
• Is the gas supply on, and is gas pressure within acceptable
range?
• Are room thermostats or building controls calling for heat?
• Are all electrical connections intact?
• If none of the above resolve the problem, follow the troubleshooting guide in the 200i Control manual.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
33
Page 34
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Starting the boiler (continued)
To reset the SmartCycle control from lockout: Turn the boiler on/o switch OFF, then back ON.
Figure 24a SmartCycle control display during operation
Figure 24b Boiler sequence of operation, fault states and SmartCycle control display information
Normal conditionBlower statusTimeIgnition
Standby (not heat call)OFF
Start (call for heat)OFF (Flow switch and other interlocks in
the ow switch circuit must prove)
OFF
if supply temperature is above the
bottom of the heat band; circulator runs,
but boiler does not re yet
ON at purge RPM (55% of maximum)
when supply temperature drops below
the bottom of the heat band
Ignition trialON at ignition RPM (30% of maximum)
Flame is sensed
(Stabilization period)
Operate on demandON at RPM based on demand (control
End call for heatON at purge RPM (55% of maximum)
Ignition failureON at purge RPM
Flame failureON at purge RPM for postpurge
ON at ignition RPM (30% of maximum)
determines ring rate % based on
demand and rate of change, etc.)
Boiler restarts a normal sequence
Control will try 3 times, then lockout
Boiler restarts a normal sequence
10 secondsOFFOFF
DemandOFFOFF
10 seconds
4 secondsONON
6 secondsOFFON
DemandOFFON
Normal display unless three attempts fail, then shows:
Normal display unless ignition is unsuccessful three times after
restart
status
OFFOFF
OFFOFF
Gas valve
status
IGN LOCKOUT
Date & Time of lockout
Display
(upper left)
STANDBY
FLOW WAIT
HEATING
PRE PURGE
IGN 30%
IGN 30%
RUN %XXX
POST PRGE
(alternating to:)
For more information: See the 200i Control manual for additional information and troubleshooting.
34
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 35
Cast iron condensing boiler — Installation and operation manual
WARNIN G
WARNIN G
Cast iron condensing boiler
12
Figure 25 Operating instructions (for starting boiler only — follow manual instructions to check boiler operation and adjust as needed)
Starting the boiler (continued)
FOR Y OUR SAFETY READ BEFORE OPERA TING
WARNIN G
A. This boiler does not hav e a p ilot. It is equipped
with an ignition device which automatically
light s t he burner .
BURNER BY HAND
B. BEFORE OPER AT ING, smel l a ll around the boile r
area fo r gas . B e sur e t o smel l n ex t t ot he oor
because some gas is heavier than air and will
settle on the oor .S ee below .
•D o not tr y t o light an y applianc e.
•D o not touch an y e le c t ric switch; do not use an y
phone in your buildin g.
If yo u d o not f ollow these instruc tions e xac tly ,a r eo re xplosion ma y r esult, causing
proper ty damage , personal injur y o r loss of lif e.
C. Use onl y y our hand to turn the gas valve handl e. Never us e t ool s. If
DO NOT TR Y T OL IGHT THE
.
the handl e w ill not turn by hand, don 't tr y t or epai r i t. Call a
qualied ser vice technician. Fo rc e o ra ttempted repai r m ay resul t
in a r e o re xplosion.
D. Do not use this boile r i fa ny par t has been under water .
Immediately cal l a qualied ser vice technician to inspec t t he
boiler and to replac e a ny par t o ft he contro l s ystem and an y gas
contro l t hat has been under water .
WH AT TO DO IF YO U SMELL GAS
•I mmediately cal l y our gas supplie r f ro m a phone outside of
the building.
•I fy ou cannot reach your gas supplie r, cal l t he re depar tment.
Followthe gassupplier's instructions.
WARNIN G
STOP!
1.
2. Set the thermostat to lowest setting.
Pr ess the boiler ON/OFF switch to .
DO NO T T RY TO LIGHT THE BURNER BY HAND
3.
Tu rn manual gas valv e handle clock wise to the gas valv e. (G as
4.
valve may have lever handle. Va lve location will va ry by installations .)
5. Wa it ve ( ) minutes to clear out an y gas . T hen smell fo r gas , including near
the oor . If you smell gas ,F ollo w “ B” in the saf ety in fo rmation abo ve. If
you don 't smell gas , go to the ne xt step .
6. Tu rn manual gas valv e handle counterclock wise to the gas valv e.
7. Tu rn ON all electrical po wer to the boile r.
8. Set the thermostat to its highest setting. Press the ON/OFF switch to
9. The DISPLA Y will cy cle through the ignition sequenc e, and show "RUN" when
the boiler is operatin g.
10. If the boiler does not oper ate, follow the instruc tions below to " TURN OFF
GAS TO BOILER. " Call your ser vice technician or gas supplie r.
OPERA TING INSTR UCTIONS
Do not attempt to operate this boiler unless it has been star ted, adjusted and maintained at least annually b y a qualied heating ser vic e t echnician.
Read the saf ety in fo rmation abo ve on this label .
Tu rn o all electrical po wer to the boile r.
OFF
.
CL OSE
5
ST OP!
OPEN
ON.
CL OSE
DISPL AY
ON/OFF
SWIT CH
OPEN
M ANU AL
GA S VA LV E
TO TURN OFF GAS TO BOILER
1. Set the thermostat to its lowest setting.
2. Tu rn o all electric po wer to the boiler if ser vice is to be
per fo rmed .
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
3. Tu rn manual gas valv e handle clock wise to .
DO NO T FORCE THE HANDLE .
CL OSE
42-5230
35
Page 36
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Illustration 26 En francaise . . .
Starting the boiler (continued)
36
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 37
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Starting the boiler (continued)
Turn the boiler OFF
1. Turn OFF the boiler on/o switch and allow the boiler to cycle o .
2. CLOSE the manual gas valve.
3. Multiple boiler SmartCycle applications Disconnect the communications
cable or 3-wire connection to the boiler connection board. (Replace when done.)
Check ignition
1. With the manual gas valve CLOSED, start the boiler with the on/o switch.
2. Look into the ame window, le side of the boiler (Figure 29, page 38).
3. When ignition starts, the spark should jump between the electrodes, not to other
surfaces.
4. e spark should be strong and steady. If the spark is acceptable, turn the boiler
on/o switch
5. If the spark jumps to ground or is unsteady, turn the boiler OFF. See the Maintenance
section of this manual for the procedure to remove and inspect the electrode assembly. Replace the electrode assembly if it is damaged or not within speci cations.
OFF. en proceed with the start-up adjustment procedure.
Insert combustion analyzer probe
e boiler must be checked and adjusted using combustion test
instruments. Failure to accurately measure ue gas analysis and adjust
the boiler as needed could result in severe personal injury, death or
substantial property damage.
1. A er the boiler has cycled o , loosen the hose clamp covering the ue gas sampling hole (Figure 27).
e ue gas vent pipe may be hot. Touching the pipe with unprotected
skin could result in a severe burns.
2. Slide the hose clamp o of the sample opening.
3. Insert the combustion analyzer probe into the sample opening.
4. If using an electronic analyzer, zero and calibrate it before proceeding.
5. If using a chemical analyzer, make sure that the uid is fresh and is at room temperature. Have a monoxer and test tubes available to test carbon monoxide levels.
Figure 27 Flue gas sampling hole
Seal test hole with high temperature silicone a er
each combustion test and annual inspection to
prevent gases and condensation from leaking
during appliance operation.
Figure 28 Electrical panel
Check high re operation
1. Remove the electrical panel cover on the right side of the boiler (see item 11,
page 3) as in Figure 28.
Electrical shock hazard e electrical box contains line-voltage
wiring and contacts. Use caution when working in the electrical box to
avoid contact with line-voltage elements. Turn o power to the boiler
panel if necessary.
2. Connect a jumper wire across the high- re terminals of the connector board
(Figure 28). ese terminals are located on the lower row as shown.
3. Turn the boiler on/o switch ON.
4. e boiler will start at about 30% of maximum input and immediately go to high re.
5. Obser ve the ame through the ame window (le side of boiler; see Figure 29).
• e ame should be blue and well-de ned, with white traces.
• If the ame is too lean (too much air), it will be light blue and unsteady.
• If the ame appears reddish, or there are red areas on the burner surface, turn
the boiler
6. Check the analyzer. A rapid increase in CO is an indicator of bad combustion.
Turn the boiler OFF and reduce fuel input as explained on page 38.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
OFF and reduce fuel with the gas valve thro le (see page 38).
37
Page 38
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Starting the boiler (continued)
Adjust gas valve throttle setting
Allow combustion to stabilize
• Allow the boiler to operate 15 minutes, or as needed to obtain a steady reading on
the analyzer.
If the ame or burner surface appear red, NO NOT allow the boiler
to run without adjusting the gas valve thro le to reduce fuel input as
described below. Proceed with nal thro le se ing only if the ame is
visually acceptable (blue and steady).
Acceptable CO2/O2 values
• e CO2/O2 values must be within the limits given in Table 5. e ame must be blue
and steady as discussed on page 37. CO must be no higher than 100 ppm.
Adjusting gas input with throttle screw - max input
1. Adjust gas input with the thro le screw adjustment using a long-shank common
bit screwdriver inserted through the hole in the jacket top. (Figure 29)
2. When adjusting the thro le se ing, make changes in half-turn increments. Allow
the ame to stabilize before adjusting each time. (Reduce gas input if the ame or
burner appears red.)
3. If CO2 is too HIGH (O2 too low):
• REDUCE gas by turning the adjustment CLOCKWISE (one half turn at a
time). Recheck the analyzer and ame a er each half turn.
4. If CO2 is too LOW (O2 too high):
• INCREASE gas by turning the adjustment COUNTERCLOCKWISE (one
half turn at a time). Recheck the analyzer and ame a er each half turn.
Verify gas inlet pressure
1. With the boiler operating at high re, check the gas pressure at the manual gas
valve. Gas pressure should never fall o by more than 2 inches WC (50 mm).
To meter gas input (natural gas only):
1. Meter gas input with the high- re jumper in place.
2. Turn o all other gas appliances that use the same gas meter as the boiler.
3. Call your gas supplier and ask for the heating value of the gas (Btu per cubic foot).
4. Start the boiler and let it run for 15 minutes (high- re jumper in place).
5. With the boiler operating, clock the time in
10 cubic feet of gas at high re.
6. Insert the heating value and the time, in seconds, into the formula below.
Input = [
7. If the computed rate exceeds the desired input rate or 200,000 Btuh, reduce the gas
input with the gas thro le adjustment.
Gas Btu per cubic foot] x [3600] x [10] ÷ [seconds]
SECONDS that it takes to burn
Never operate the boiler at an input higher than
its rating. Excess input can result in overheating
and damage to the heat exchanger and boiler
components.
Check low re operation.
1. Turn the boiler on/o switch OFF.
2. Remove the high- re contact jumper. Connect the jumper
wire across the low- re terminals of the connector board
(Figure 28, page 37). ese terminals are located on the
lower row as shown.
3. Turn the boiler on/o switch ON.
4. e boiler will start at about 30% of input and then move to
the low re condition.
5. Make sure the ame is blue and steady, NOT red or light
blue and unsteady.
6. If the ame or burner appears red, or if the CO2 or O2 are
outside the ranges of Table 5, turn the boiler on/o switch
OFF.
7. See the next page for instructions to adjust the gas valve
low- re se ing.
8. If ame and CO2/O2/CO are acceptable, proceed with setup (page 40) No further gas valve adjustments
are needed
low- re jumper and replace the electrical panel cover.
. Replace the gas valve cover plate. Remove the
Changing from propane to natural gas or
natural gas to propane
the boiler for a di erent gas, the low- re gas
adjustment must be changed using the procedure
on page 39.
When adjusting
38
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 39
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Starting the boiler (continued)
When is low re adjustment required?
Adjust the gas valve low- re se ing ONLY if the ame is unacceptable,
the CO2, O2 or CO are out of acceptable range or you are changing
fuels. You will need to remove the boiler jacket top and adjust the gas
valve low- re se ing as described below.
The boiler jacket top must be removed when it is necessary to access the gas
valve low- re adjustment screw or other interior components, such as the blower motor. Use the procedure below.
Removing the boiler jacket top
1. See Figure 30.
2. Remove the three thumb screws securing the lter access plate.
3. Remove and set aside the lter access cover and gasket.
4. Pull back on the lter clamp and remove the lter.
5. Hold the lter clamp back as in Figure 30.
6. Squeeze the conical grommet sides and maneuver the grommet out of the opening
in the jacket top.
7. If there is no air pipe a ached to the air inlet, leave the air inlet plate in place.
8. If air is piped to the air inlet plate, remove the air inlet plate and gasket by removing the
four screws that secure it to the jacket top. Make sure the air piping is properly supported.
9. Remove the seven Phillips-head screws securing the jacket top to the jacket sides.
10. Li o the jacket top. (Leave the wire harnesses connected.)
11. Move the insulation aside if necessary.
Figure 30 Removing boiler jacket top
Adjusting the low- re setting
DO NOT adjust the low- re se ing unless low- re ame or combustion
are unacceptable.
1. See Figure 31 for the location of the gas valve low- re adjustment. Use a 2-mm
hex wrench.
2. When adjusting the low- re se ing, make changes in half-turn increments. Allow
the ame to stabilize before adjusting each time. (Reduce gas input if the ame or
burner appears red.)
3. If CO
4. If CO
is too HIGH (O2 too low):
2
• REDUCE gas by turning the adjustment COUNTERCLOCKWISE (one
half turn at a time). Recheck the analyzer and ame a er each half turn.
is too LOW (O2 too high):
2
• INCREASE gas by turning the adjustment CLOCKWISE (one half turn at a
time). Recheck the analyzer and ame a er each half turn.
Replace the boiler jacket top
1. To replace the jacket top, reverse this order above. Make sure insulation is in place.
2. Slide the conical grommet over the blower inlet en seat the grommet ring into
the hole in the jacket top.
3. Rea ach the air inlet plate if it was removed. Inspect the air piping to make sure it
was not displaced.
4. Pull the air lter clamp back. Replace the lter, gasket and access cover. Secure with
the three thumbscrews. Replace the gas valve cover plate if removed.
5. Remove the low- re jumper from the connection board. Replace the electrical
panel cover.
Figure 31 Gas valve adjustments
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
39
Page 40
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
12
Starting the boiler (continued)
Measure ame current
Electrical shock hazard e electrical box contains line-voltage
wiring and contacts. Use caution when working in the electrical box to
avoid contact with line-voltage elements. Power must be on to measure
ame current.
1. With the boiler operating at low re (low- re jumper in place), measure the ame
current.
2. Remove the upper electrical panel cover (upper right side of boiler).
3. A ach microammeter leads to the ame current test pins of the Fenwal ignition
module as in Figure 32.
4. e ame current should be approximately 6 microamps, and never less than 1 microamp. Record the ame current value on the back page of this manual.
5. If ame current is acceptable, continue with setup. If ame current is too low, check
the ignition electrode/ ame rod assembly following the instructions in the Maintenance section of this manual.
Check boiler modulation
1. Remove the low- re jumper from the electrical connection panel (see Figure 28).
2. e boiler ring rate should change to meet demand. e SmartCycle control display will show the percentage of maximum ring rate (between 20% and 100%).
Figure 32 Throttle adjustment and ame window
Test ame failure modes
Flame loss
1. With the boiler running in normal operation, close the manual gas valve on the
incoming gas line.
2. Within 0.8 second a er the ame goes out, the boiler gas valve should shut o .
3. e SmartCycle control will restart operation with prepurge, then continue
through a normal start cycle.
4. With the manual gas valve closed, the boiler should a empt ignition three times,
then lockout, as described below.
Ignition failure
1. Make sure there is a call for heat.
2. Turn the boiler on/o switch OFF.
3. Close the manual gas valve on the gas supply line.
4. Turn the boiler on/o switch ON.
5. e boiler should start a regular cycle.
6. When the boiler a empts ignition, no ame will occur. Within 4 seconds of ignition start, the control will close the boiler gas valve and a empt another start.
7. A er three failed ignition a empts, the Fenwal control will lockout.
8. e boiler will shut o and the SmartCycle control display will show “LOCKOUT.”
9. Open the manual gas valve.
10. Reset the controls by turning the boiler on/o switch o , then on again.
11. e boiler should restart and operate normally.
2. e boiler should gradually cycle to minimum input ( ring
rate = 20%), then turn o .
Test external controls
1. Lower the se ing of external limit controls below the supply water temperature. Verify that the controls shut down
as required.
2. Test operation of low water cut-o s, ow switches and other
external devices.
3. Test external gas pressure interlocks, if used.
4. Test/verify operation of combustion air dampers and end
switches, if used.
DHW applications
1. For DHW applications, verify that the boiler operates on demand
from the indirect water heater and shuts o as required.
Test control & interlock operation
Test SmartCycle operating limit function
1. Allow the boiler to re until the supply temperature reaches the upper end of the
control band.
40
Fill out the installation certi cate
1. Complete the checklist and installation certi cate on the
back page of this manual.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 41
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
13
Annual start-up
e boiler and system must be inspected, started
and serviced at least annually by a quali ed
service technician. Follow all procedures
speci ed in the 200i manuals. Failure to
inspect, test and maintain the boiler and system
could result in severe personal injury, death or
substantial property damage.
Electrical shock hazard Use caution
when working on the boiler where electrical
components are exposed. Turn o power to the
boiler if necessary to avoid potential for electrical
shock.
Annual start-up overview
Perform start-up, pages 32 – 40
Perform the complete start-up, testing and inspection procedures given on pages 32 through 40 to ensure the boiler and
system comply with the requirements in this manual.
In addition, perform the additional follow-up procedures given
below.
Perform follow-up procedures
Operating conditions or abuse can damage the boiler or system components. e start-up checklist that follows includes
inspections and testing intended to verify that the boiler and
system are still fully functional.
Annual start-up checklist
obstructed heat exchanger could result in severe
personal injury, death or substantial property
damage.
❑ Verify boiler water treatment
• If the system requires water treatment, make sure the treatment is being performed as required. Ensure that the water
so ener, if used, is operational and is being maintained.
• If the system uses antifreeze, check the antifreeze concentration and inhibitor level. If the levels are low, check for
leaks or other causes. Adjust the antifreeze level or re ll the
system as indicated.
❑ Check expansion tank & air vents
• Inspect the relief valve and piping to be sure there are no
signs of relief valve leakage.
• If the relief valve has been weeping, make sure the expansion tank is not waterlogged or undersized.
• When performing the boiler start-up, watch the pressure
gauge as the boiler and system heat up. If the pressure rises
too fast or too high, the relief valve is not working properly.
Correct the problem as required.
• Make sure all air vents are operating correctly.
❑ Inspect and test the relief valve
• Follow the instructions on the relief valve label to inspect
and test the boiler relief valve.
When discharging the relief valve, make sure there
is not risk of spraying water to you or others.
❑ Discuss system performance with the
homeowner or boiler operator
• Ask the homeowner or boiler operator to rate the performance of the heating system over the last season.
• If the homeowner or boiler operator identi es boiler or
system problems,, identify the cause and adjust or repair as
necessary.
❑ Inspect the air lter
• Remove, inspect (and clean if needed) the air lter. (See
instructions in the Maintenance section.)
If the lter enclosure and blower inlet show signs
of drywall dust, construction debris or other
deposits, you may need to inspect the burner.
Follow the procedure in the Maintenance
section. Accumulation of debris in the burner can
result in burner damage and potential for severe
personal injury, death or substantial property
damage.
If the burner is removed for inspection, also
inspect the boiler heat exchanger. If the heat
exchanger is damaged or blocked with debris,
consult the factory for corrective action.
Operating the boiler with a damaged or
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
❑ Condensate line maintenance
• Make sure the condensate line, condensate pump and neutralization system, if used, are operational.
• Remove the condensate line at the boiler hose barb connection.
• Pour water into the line and make sure the water drains
freely. Flush or replace the line if necessary.
• Fill the condensate trap by a aching a -inch clear plastic
tube to the hose barb. Pour water into the tubing until the
trap is full.
• Remove the clear tubing and rea ach the condensate line to
the boiler hose barb.
❑ Perform a complete start-up
• Inspect, adjust and start-up the boiler and system components as instructed on pages 32 through 40. Perform all
procedures to ensure the boiler and system are operating
properly.
❑ Review with homeowner/operator
• Review the User’s information manual with the homeowner or operator.
• Make sure that all maintenance procedures are being followed and that all instructions are clear and understood.
41
Page 42
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
13
Maintenance
Read before proceeding
Failure to adhere to the following
could result in severe personal
injury, death or substantial property
damage.
Licensed technician only
e procedures in this manual must only be done by
a quali ed service technician. Some details of service
procedures are le to the expected good practices of a
quali ed technician.
Electrical shock hazard
Except when the boiler must be tested or adjusted with
the power on, always turn power OFF before sevicing
the boiler.
Burn or scald risk
Always allow the boiler and parts to cool before
a empting to service or remove. Some parts may be
very hot.
Do not open water piping components unless the water has been allowed to cool to avoid scald hazard from
spraying hot water.
Test/verify the boiler after servicing
Following service of any kind, verify that the boiler,
controls and system devices are fully functional by
performing the appropriate start-up testing procedures
given in this manual.
Seals
If any pressure-tight seal is broken for servicing (such
as combustion chamber/burner seals, air or vent piping
joints or seals, or gas piping joints or seals, make sure
the seal is restored when servicing is complete. Gaskets must be in good position and placed as originally
installed.
Handling ceramic ber
and berglass materials
The 200i boiler contains some ceramic
fi ber and fi berglass materials. Ceramic
fi ber materials, such as the burner gasket, may contain carcinogenic particles
(chrystobalites) after exposure to heat.
Airborne particles from fi berglass or
ceramic fi ber components have been
listed as potentially carcinogenic by the
State of California. Take the following
precautions when removing, replacing
and handling these items.
Protective measures
• Avoid breathing dust and avoid contact with skin
or eyes. Wear long-sleeved, loose- ing clothing, gloves and eye protection. Use a NIOSH
N95 certi ed respirator. is respirator meets
requirements for protection from chrystobalites.
e actual job requirements or NIOSH regulations may require other or additional protection.
For information, refer to the NIOSH website,
h p://www.cdc.gov/niosh/homepage.html.
Ceramic ber removal
• Ceramic ber removal: To prevent airborne dust,
thoroughly wet ceramic ber with water before
handling. Place ceramic ber materials in a plastic
bag and seal to dispose.
• Avoid blowing, tearing, sawing or spraying berglass or ceramic ber materials. If such operations
are necessary, wear extra protection to prevent
breathing dust.
Read the instructions
Do not a empt the procedures in this manual without
thoroughly reading the instructions given. Follow all
instructions.
If problems can’t be resolved
If following the procedures in the 200i manuals do not
resolve problems, contact Mestek for technical support
to resolve the issues.
42
• Wash work clothes separately from other laundry.
Rinse clothes washer thoroughly a erwards to prevent contamination of other clothing.
NIOSH First aid procedures:
• Eye exposure irrigate immediately
• Breathing fresh air.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 43
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
13
Maintenance (continued)
Cleaning the air lter
1. Turn the boiler on/o switch OFF.
2. Remove the three thumb screws that secure the lter access
plate (see Figure 33).
3. Remove the lter access plate and gasket.
4. Pull the lter clamp back and remove the air lter.
5. Inspect the lter and the lter enclosure area for dust or debris.
6. Clean the lter, if necessary, by washing under running water.
Shake o excess water and towel dry.
If the lter enclosure and blower inlet show
signs of drywall dust, construction debris or
other deposits, you may need to inspect the
burner. Follow the procedure in this section.
Accumulation of debris in the burner can result in
burner damage and potential for severe personal
injury, death or substantial property damage.
7. If the lter is damaged or cannot be cleaned e ectively, obtain a replacement lter from your boiler distributor.
8. To replace the air lter, pull the lter clamp back, insert the
lter, and allow the clamp to secure the lter in place.
9. Replace the lter access cover gasket and access cover.
10. Replace the three thumbscrews and nger tighten securely.
11. Turn the boiler on/o switch
ON.
Figure 33 Accessing the air lter
Figure 34 Electrode/ ame rod assembly inspection
Accessing the electrode assembly
1. Turn the boiler on/o switch OFF.
2. If the boiler ignition electrodes or ame rod appear to be
operating incorrectly, remove and inspect the assembly as
follows.
Do not remove the electrode assembly while the
boiler is operating. Allow the boiler and electrode
assembly to cool before a empting removal to
avoid possible burns. Failure to comply could
result in severe personal injury.
3. With the boiler and manual gas valve closed, remove the
upper electrical box cover (right side of boiler).
• Remove the two ¼ inch bolts that secure the electrode/
ame rode assembly to the boiler (Figure 34).
• e electrode spacing must be 1/8 inch (3.2 mm) as shown
in Figure 26.
4. If the electrodes or ame rod are damaged or the tip spacing
is incorrect, replace the assembly. e electrodes are NOT
adjustable.
5. Re-install the assembly in the boiler.
Make sure the electrode plate gasket is in good
condition and that the assembly is securely
bolted to the boiler. e combustion chamber
operates with a positive pressure. Failure to
comply could result in severe personal injury,
death or substantial property damage.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
43
Page 44
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
14
Maintenance (continued)
Accessing the burner
If the lter enclosure and blower inlet show signs of drywall dust,
construction debris or other deposits, you may need to inspect the
burner. Follow the procedure below. Accumulation of debris in the
burner can result in burner damage and potential for severe personal
injury, death or substantial property damage.
Perform this procedure only if evidence indicates the burner may be
fouled or damaged.
1. Turn the boiler on/o switch OFF.
2. Close the manual gas valve.
3. Remove the boiler jacket top following the procedure given on page 39.
4. Disconnect the gas supply piping at the ground joint union installed adjacent to
the boiler.
5. Carefully remove the upper insulation (item 4, Figure 35)that covers the upper
section cover. See Figure 35. Set the insulation aside for reuse.
e upper insulation must be replace a er completing this work to
prevent overheating of the gas valve, blower and jacket top.
6. To access the bolts and nuts that secure the upper section cover:
• Remove the sheet metal cover plate at the ame observation window (item 1,
Figure 35).
• Remove the plastic plug from the jacket rear (item 2, Figure 35).
• Removing these items provides open-end wrench access to the ¼ inch bolts
and nuts.
7. Remove the seven ¼ inch bolts, nuts and washers that secure the upper section
cover (item 2, Figure 36). Note for reinstallation that there is a at washer on both
sides of the assembly and a lock washer on top.
8. Disconnect the three wire harnesses at the gas valve and blower (items 2 and 3,
Figure 36). In this illustration, the wires are not shown.
9. Li the upper cover plate/blower/gas valve assembly o of the section assembly. ( e
upper section cover gasket is adhered to the bo om the cover with silicone RTV.)
10. e burner is now exposed.
11. Li the burner up as in Figure 37 and inspect both sides. ( e burner gasket is
adhered to the bo om the cover with silicone RT V .)
12. Look down into the section assembly to verify it is clean. If the heat exchanger is
blocked with sediment or shows damage, contact Mestek immediately for corrective action.
13. If the burner is damaged, obtain a replacement burner from your distributor. Install the new burner.
14. If the burner is fouled with debris, a empt to clean by using a shop vacuum. Be
careful not to damage the burner surface. If the burner cannot be cleaned, obtain a
replacement from your distributor.
15. Inspect the ceramic ber chamber (item 3, Figure 37) and ber gasket (item 2,
Figure 37). Make sure they are in good condition, or replace.
16. Replace the burner or install a new one.
17. Replace all components in the reverse order from above.
Use extreme care when replacing the upper section cover. e seal must
be secure to avoid potential of carbon monoxide leakage or heat damage
caused by ue gas spillage. Inspect all components to ensure they are in
good condition and correctly installed. Soap suds leak test the gas line,
particularly the ground joint union, to ensure the gas line is intact a er
servicing. Follow servicing by a complete start-up/test procedure of the
boiler.
Figure 35 Preparing to remove upper section cover
Figure 36 Upper cover bolt locations
Figure 37 Burner and chamber
44
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 45
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
14
Notes
Maintenance (continued)
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
45
Page 46
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
15
Replacement parts
ITEM PART No.DESCRIPTIONQTY
120-1022
270-1655
558-1555
770-1223
1170-1421
1760-4280
1957-3657
2259-1089
2459-1091
2902-1580
3170-1657
T&P Gauge
Jacket Panel Assembly
Illuminated Rocker Switch
Base Assembly
Blank Box Assembly
Sight Glass
Filter Box Thumb Screw
Combustion Air Filter
Filter Box Adapter Gasket
Gas Valve
Burner
1
1
1
1
1
1
3
1
1
1
1
ITEM PART No.DESCRIPTIONQTY
4109-1520
4256-3346
4526-3211
4602-4288
NS02-4290
NS58-1831
NS70-2074
NS70-2075
NS70-2076
NS70-2077
4702-5210
TACO 005 W/Internal Flow Check
3" Flue Adpater
50V Transformer
Breakout Board w/Wire Connectors
Display Board
5K Resistor
Harness (J2) Ctrl
Harness (J3) Ctrl
Harness (J4) Ignition/Flue Switch
Harness (J5) Blower/Gas Valve
Blocked Flue Switch
1
1
1
1
1
1
1
1
1
1
2
NS59-1086
3322-1203
22-1200
22-1803
22-1201
3570-6700
04-1344
04-1345
04-1346
3602-4296
NS59-1112
3703-1756
3802-3928
Lower Chamber Gasket
30 psi Relief Valve
50 psi Relief Valve
75 psi Relief Valve
100 psi Relief Valve
Ignitor Assembly
Spark Rod
Ground Rod
Flame Sensor
Ignition Control
Ignition Block Gasket
Ignition Cover
High Limit Switch
2
1
1
1
1
1
1
1
1
1
1
1
1
4845-1274
5001-1640
5158-1837
NS70-1651
NS02-1584
NS02-1585
5257-3413
5402-4287
NS60-5616
NS60-5628
NS70-1244
NS70-1232
NS70-1660
Ceramic Fiber Chamber
Upper Casting Cover
Blower
Blower Assembly
Intake Adapter Flat
Intake Adapter Hose
#6 X 1/2" Blk Screw
Control Board w/Display
Control Overlay
Display Label
Drain Assembly
Condensate Drain Extension
Drain Pan Assembly
1
1
1
1
1
1
2
1
1
1
1
1
1
3902-3927
4003-1776
Operator - Supply Sensor
Ignition Box Cover
46
1
1
NS42-2999
NS60-4257
Rating Label
Air Vent
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
1
1
Page 47
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
15
Replacement parts (continued)
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
47
Page 48
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
16
Appendix A — suggested wiring
IAR (Indoor Air Reset) wiring, when used
Wiring for 3-wire zone valves without a zone
controller
• Heat Demand terminal connections using 3-wire zone valves e end switch
leads from the zone valves must connect to the Heat Demand LEFT SIDE (+)
terminal on the electrical connection board as shown in Figure A1.
• I AR connections See Figure A1 for typical wir ing to the IAR inputs when using
3-wire zone valves without a zone controller. For other applications, see the Control manual and Section 7 of this manual.
Polarity e connections to the IAR positive terminals (IAR +)
must be to the same location on the zone valve as the thermostat wire,
as shown in Figure A1. e connections to the IAR negative terminals
(IAR –) must be from the zone valve terminal connected to the 24VAC
common line, as shown. Connecting the wires incorrectly can cause the
transformer to be shorted out and damaged.
3-wire zone valves: You will have to rewire existing 3-wire zone valves
to meet the requirements shown in Figure A1. Move the thermostat lead
and the 24VAC hot lead to the CENTER terminal of the valve. Move
the 24VAC common lead to the outer terminal of the valve. Discard
existing wires connected to the end switch terminals. Install a new wire
single wire from each end switch to the Heat Demand LEFT SIDE (+)
terminal as shown in Figure A1.
Figure A1 Indoor Air Reset wiring to IAR terminals with
3-wire zone valves and no zone controller
(see Figure 21a for terminal block 6 location)
3-wire zone valves: Always use a voltmeter to verify the wiring is
correct. e center terminal of the valve must be 24VAC to ground
when the thermostat is calling for heat. e motor common terminal
(outer post) must not have voltage. Change the wiring and retest. DO
NOT connect the wires to the boiler until you have tested as described.
Incorrect wiring can damage the boiler control or other system
components.
• If there is only one transformer feeding all of the zone valves in the system, you can
omit the wires to the IAR negative terminals (IAR –) on all but one of the zone
valves. is is because these terminals are jumpered internally on the electrical
connection board. If there is more than one transformer, provide one wire from
each transformer common side to one of the IAR negative terminals (IAR –).
48
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 49
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
16
Appendix A — suggested wiring (continued)
IAR (Indoor Air Reset) wiring, when used
Wiring for circulator relays (relays must have
24VAC common terminals)
Relays must have a 24VAC common terminal: e IAR inputs
require a connection to the 24VAC common of the circulator relay to
operate. If the circulator relays do not have a 24VAC common terminal,
you cannot connect to the IAR inputs. To operate with indoor reset,
you will have to remove the existing relays and replace with a circulator
zoning controller or install relays that provide a 24VAC common
terminal.
• Heat Demand terminal connections using circulator relays e end switch
leads from the relays must connect to the Heat Demand terminals on the electrical
connection board as shown in Figure A2.
• I AR connections See Figure A1 for typical wir ing to the IAR inputs when using
circulator relays. For other applications, see the Control manual and Section 7 of
this manual.
Polarity e connections to the IAR positive terminals (IAR +)
must be as shown in Figure A2. e connections to the IAR negative
terminals (IAR –) must be from the 24VAC common terminals of the
circulator relays, as shown. Connecting the wires incorrectly can cause
the transformer to be shorted out and damaged.
Figure A2 Indoor Air Reset wiring to IAR terminals with
3-wire zone valves and no zone controller
(see Figure 21a for terminal block 6 location)
Verify 24VAC switched lead from thermostat: Before connecting
the wires to the IAR terminals, use a voltmeter to verify the 24VAC hot
lead is NOT powered when the thermostat is not calling for heat.
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
49
Page 50
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
16
Appendix A — suggested wiring (continued)
IAR (Indoor Air Reset) wiring, when used
Wiring for typical zone controller
• Heat Demand terminal connections e end switch leads from the controller
must connect to the Heat Demand terminals on the electrical connection board as
shown in Figure A3.
• I AR connections See Figure A3 for typical wir ing to the IAR inputs when using
a zone controller. For other applications, see the Control manual and Section 7 of
this manual.
Polarity e connections to the IAR positive terminals (IAR +)
must be to the same location on the zone valve as the thermostat wire,
as shown in Figure A3. e connections to the IAR negative terminals
(IAR –) must be from the zone controller’s 24VAC common terminal
as shown. Connecting the wires incorrectly can cause the transformer
to be shorted out and damaged.
Thermostat terminal connections: Use a voltmeter to verify the
wiring is correct. Measure the voltage on the thermostat terminals
with the zone controller powered, BEFORE connecting any wires. e
IAR positive terminal connections (IAR +) must be to the side of the
thermostat connections that have zero voltage.
DHW priority zone: Most zone controllers will provide a priority
zone for connection to a DHW tank aquastat and circulator. e priority
switch will turn o space heating when there is a DHW call. Read the
controller manufacturer’s instructions to determine which zone is set
up for priority operation.
50
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
Page 51
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
16
Figure A3 Indoor Air Reset wiring to IAR terminals, Heat Demand and DHW Demand using typical zone controller for
Appendix A — suggested wiring (continued)
either circulators or zone valves
(see Figure 21a for terminal block 2 and 6 locations)
P/N 42-9470 1/12 Copyright 2012 Mestek, Inc.
51
Page 52
Cast iron condensing boiler — Installation and operation manual
Cast iron condensing boiler
Start-up & service history
Installation and start-up (complete before leaving installation site)
Start-up dateBoiler modelSerial numberInstaller/start-up company name and address: