Meriam 70H, 72H User Manual

ACCUTUBE
File No. 957:440-11
INSTALLATION
INSTRUCTIONS
10920 Madison Avenue · Cleveland, Ohio 44102 · (216) 281-1100 · FAX (216) 281-0228
e-mail: meriam@meriam.com web site: www.meriam.com
ACCUTUBE INSTALLATION INSTRUCTIONS
ACCUTUBE MODEL NO. CONFIGURATOR................................................................3
ACCUTUBE MODELS .....................................................................................................4
1 SYSTEM CONSIDERATIONS.........................................................................................5
2 OPERATIONAL CONSIDERATIONS............................................................................. 9
3 READOUT INSTRUMENTATION .................................................................................. 9
4 INSTALLATION PROCEDURE ......................................................................................9
4.1 GENERAL REQUIREMENTS.................................................................................9
4.2 SERIES 10A, 11A, & 12A ......................................................................................10
4.3 SERIES 20T, 21T, 22L, 23L, 40H, 41H, 42H & 43H.............................................11
4.4 SERIES 24D & 25D ................................................................................................ 12
4.5 SERIES 33T INSTALLATION ..............................................................................13
4.6 PROBE REMOVAL................................................................................................15
4.7 SERIES 37L, 70H & 72H INSTALLATION..........................................................15
4.7.1 EQUIPMENT REQUIRED ..........................................................................15
4.7.2 INSTALLATION – ½” AND 1” DIA. PROBES W / SOCKET DRIVE.....15
4.7.3 INSTALLATION – ½” AND 1” DIA. PROBES W / GEAR DRIVE .........17
4.7.4 INSTALLATION – 2 3/8” DIA. PROBES W / SOCKET DRIVE.............. 18
4.7.5 INSTALLATION – 2 3/8” DIA. PROBES W / GEAR DRIVE...................20
4.7.6 SPECIAL DOUBLE-SUPPORT INSTRUCTIONS.....................................21
4.7.7 RECTRACTION PROCEDURE FOR SOCKET DRIVE UNITS...............22
4.7.8 RECTRACTION PROCEDURE FOR GEAR DRIVE UNITS ...................23
4.8 DIRECT TRANSMITTER MOUNT HEADS WITH EQUALIZING VALVES...24 AND INTEGRAL RTD OPTION, SERIES 40H – 43H, 70H & 72H
4.9 SPECIAL APPLICATIONS (DUCTS/SADDLE CLAMPS/ROTATED HEAD)..25
5 OPERATIONS .................................................................................................................26
6 INTERCHANGEABILITY..............................................................................................27
7 MAINTENANCE & REPLACEMENT PARTS .............................................................28
8 TROUBLESHOOTING ...................................................................................................28
9 CALCULATIONS & FLOW COEFFICIENTS......................................................... 29-31
ACCUTUBE MODEL NUMBER CONFIGURATOR
2
SERIES LINE SIZE PROBE PROBE INSTRU. INSERT. MOUNTING WET TAP DIA. MATL. VALVES VALVE DRIVE (1) THE FIRST THREE DIGITS
IDENTIFY THE STYLE OF PROBE
10A = SCH 40 INLINE 11A = SCH 80 INLINE 20T = LOW PRESSURE INSERTION, SINGLE MOUNT 21T = LOW PRESSURE INSERTION, DOUBLE MOUNT 22L = HIGH PRESSURE INSERTION, SINGLE MOUNT 23L = HIGH PRESSURE INSERTION, DOUBLE MOUNT 24D = HIGH PRESSURE FLANGE, SINGLE MOUNT 25D = HIGH PRESSURE FLANGE, DOUBLE MOUNT 33T = LOW PRESSURE WET TAP 37L = HIGH PRESSURE WET TAP 40H = DIRECT XMITER MOUNT W / 3-VALVE, SINGLE MT 41H = DIRECT XMITER MOUNT W / 3-VALVE, DOUBLE MT 42H = DIRECT XMITER MT W / 3-VALVE & RTD, SINGLE 43H = DIRECT XMITER MT W / 3-VALVE & RTD, DOUBLE 70H = DIRECT XMITER MT W / 3-VALVE, WET TAP 72H = DIRECT XMITER MT W / 3-VALVE & RTD, WET TAP
(2) NOMINAL LINE SIZE
0005 = 1/2” LINE 0100 = 10” LINE 0007 = 3/4” LINE 0300 = 30” LINE 0060 = 6” LINE 1020 = 102” LINE 0080 = 8” LINE 1440 = 144” LINE
(2A) PROBE DIAMETER
A = 1/2” D = 3/8” B = 1” E = 3/4” C = 2-3/8” F = ALL INLINE SERIES 10A & 11A
(3) SENSOR MATERIAL
00 = 316SS PROBE WITH BRASS CONNECTION HEAD (SERIES 20T, 21T & 33T ONLY) 02 = CARBON STEEL (SERIES 10A & 11A ONLY) 03 = ALL 316SS PROBE (AVAILABLE IN ALL SERIES) 10 = BRASS BODY AND PROBE (SERIES 10A & 11A ONLY) 30 = PVC WITH THREADED PROCESS CONNECTIONS (SERIES 11A ONLY) 31 = PVC WITH PLAIN END PROCESS CONNECTIONS (SERIES 11A ONLY) SP = SPECIAL - CONSULT FACTORY
(4) INSTRUMENT SHUTOFF VALVES, TYPE & MATERIAL
XX = NONE 00 = BRASS (SERIES 10A, 20T, 21T & 33T); = BRONZE (SERIES 22L, 23L, 24D & 37L) 02 = CARBON STEEL 03 = 316 SS (ALL SERIES EXCEPT 40H-43H, 70H & 72H. CALLS OUT HEAD MAT’L FOR THESE) 04 = C.S. OS&Y TYPE (SERIES 22L, 23L, 24D, 25D & 37L ONLY) 05 = 316 SS OS&Y TYPE (SERIES 22L, 23L, 24D, 25D & 37L ONLY) 14 = PVC BALL VALVE (PVC 11A ONLY) SP = SPECIAL - CONSULT FACTORY
(5) INSERTION VALVE, TYPE & MATERIAL
XX = NONE REQUIRED 00= BRONZE BALL VALVE (33T ONLY) 02 = CARBON STEEL BALL VALVE (37L, 70H & 72H ONLY) 03 = 316 SS BALL VALVE (33T, 37L, 70H & 72H ONLY) 04 = C.S. OS&Y VALVE (37L ONLY) 05 = 316 SS OS&Y VALVE (37L ONLY) SP = SPECIAL - CONSULT FACTORY
(6) MOUNTING, TYPE & MATERIAL
XX = NONE REQUIRED 01 = STEEL SADDLE CLAMP (20T, 22L & 33T ONLY) 02 = 3000# C.S. THRED-O-LET WITH BRASS PACKING (20T, 21T & 33T ONLY) 03 = 3000# C.S. THRED-O-LET WITH 316 SS PACKING (20T, 21T, 22L, 23L, 33T, 37L, 40H, 41H, 42H, 43H, 70H & 72H) 04 = 316 SS THRED-O-LET WITH 316 SS PACKING (20T, 21T, 22L, 23L) NYLON PKG (33T) GRAFOIL PKG (37L, 70H & 72H) 06 = ROUND DUCT MOUNT HARDWARE, C.S. (20T, 21T, 22L, 23L ONLY) 07 = RECTANGULAR DUCT MOUNT HARDWARE, C.S. (20T, 21T, 22L, 23L ONLY) 08 = PVC THRED-O-LET (20T, 21T, 22L, 23L, 33T ONLY) 1C = 150# C.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 3C = 300# C.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 6C = 600# C.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 9C = 900# C.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 1S = 150# S.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 3S = 300# S.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 6S = 600# S.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) 9S = 900# S.S. FLANGE (24D & 25D, SPECIAL 37L, 70H & 72H) SP = SPECIAL - CONSULT FACTORY
(7) DRIVE MECHANISM FOR WET TAPS
SC = SOCKET DRIVE GD = GEAR DRIVE
ACCUTUBE MODELS
3
10A and 11A 20T and 21T
22L and 23L
40H thru 43H
24D and 25D 33T 37L Socket Drive
5
1 SYSTEM CONSIDERATIONS
1.1 Selection of the proper location and position of the Accutube flow sensor within the piping system is important. The first consideration is to locate the Accutube with proper upstream and downstream straight pipe runs. This is required to assure a fully developed symmetrical flow profile at the Accutube. Accuracy can be affected if sufficient piping is not provided. Table 1 shows recommended straight run requirements with various types of upstream flow disturbances. For inline series sensors the straight pipe run must be of the same schedule/I.D. as the Accutube.
RECOMMENDED STRAIGHT RUNS OF PIPE
(Upstream Length in Terms of Internal Diameter of Pipe - See Notes)
UPSTREAM FLOW DISTURBANCE ONE ELBOW
WITH
STRAIGHTENING
VANES
6 - 8 8 - 10
OR TEE TWO 90° BENDS IN
8 - 10 12 - 15 SAME PLANE TWO 90° BENDS
10 - 12 24 - 28 DIFF. PLANE REDUCERS OR
8 - 10 8 - 10 8 - 10 EXPANDERS ALL VALVES
10 - 12 24 - 28 24 - 28
(SEE NOTE 3)
TABLE 1
WITHOUT
STRAIGHTENING
VANES-IN-PLANE
WITHOUT
STRAIGHTENING
VANES-OUT-PLANE
Note 1: Downstream straight run of pipe should be a minimum of 4 to 5 internal diameters.
Note 2: The values listed in Table 1 are acceptable for most applications. Additional lengths are
recommended where precise measurements are desired.
Note 3: Recommendations for valve disturbances are for non-throttling (fully open) position
only. The Accutube should not be located downstream of a throttling valve.
Note 4: Straightening vanes (where used) shall be installed 2 diameters downstream of the
upstream flow disturbance.
Note 5: Deviations from the above recommendations will normally not affect repeatability of the
flow signal.
Note 6: Combination of various types of fittings can cause severe flow distortion, the results of
which are unpredictable. Installations with fitting combinations other than those listed above should be approached with caution. Flow straightening vanes are strongly recommended to insure accurate flow measurement.
6
1.2 Determine the position of the Accutube and indicating instrument with respect to the pipe. Selection of the entry location (i.e. in from top or bottom, etc.) is determined by considering the fluid in the pipe. Sections 1.2.1 through 1.2.4 give general requirements for Accutube position and installation, and specific recommendations for each general category of fluid (1.2.1-Liquid; 1.2.2-Gas; 1.2.3-Steam; 1.2.4-General Requirement).
1.2.1 LIQUID FLOW METERING
1.2.1.1 With liquid flow the readout instrument is normally located below the Accutube. This prevents air entrapment in the instrument lines. Figures 1.1 through 1.4 show recommended orientation for liquid flow.
1.2.1.2 See Section 1.2.4 General Interconnection Requirements.
1.2.1.3 Instrument lines should be properly sloped (1/2” per foot) without high points that may cause air entrapment. If this is not possible, air vent valves must be placed at any high points in piping. Trapped air is a frequent cause for measurement error with liquids. Refer to Figs. 1.1 thru 1.4.
1.2.1.4 The air vent valves should be bled on a regular basis during normal operation and upon restart after a system shutdown.
1.2.2 GAS FLOW METERING
1.2.2.1 Few restrictions apply to system arrangement in dry gas flow. Figures
1.1, 1.2 and 1.5 are recommended for simplicity in installation.
1.2.2.2 For installations where condensation or entrained liquids accumulate in the instrument piping, it is recommended that the instrument be mounted above the Accutube or install the Accutube in the top portion of the line. If mounting the instrument below the Accutube is necessary, then sediment traps and/or drain valves should be used as in Figure 1.6.
1.2.2.3 See Section 1.2.4 for General Interconnection Requirements.
1.2.3 STEAM FLOW APPLICATIONS
1.2.3.1 As in liquid flow, the indicator should be located below the Accutube. Figure 1.1 shows the recommended configuration. This configuration allows condensate to collect in instrument lines and finds its natural level within the Accutube. See Figure 1.4 for top entry (probe) in horizontal lines.
1.2.3.2 An installation in a vertical pipe should only be performed when a horizontal line location is not available. This installation should be as in Figure 1.2. A special “rotated head” Accutube is normally used. This permits side port connection, allowing installation similar to Figure 1.2.
1.2.3.3 See Section 1.2.4 for General Interconnection Requirements.
7
7
The indicator must be placed far enough away from the Accutube to prevent thermal damage from line heat. Allow 1 ft. of uninsulated instrument piping for every 100° F of process temperature.
1.2.3.4 Slope the instrument lines to probe at an incline of approximately 1/2” per foot to prevent air entrapment.
WARNING: DO NOT ATTEMPT TO FILL INSTRUMENT LINES IF SYSTEM CONNECTING LINES ARE UNDER PRESSURE.
1.2.3.5 Fill the instrument lines with water before connecting the Accutube or opening block valves.
1.2.3.6 Allow approximately 1/2 hour after system startup for condensate level to stabilize. Stabilization time may be reduced by section 1.2.3.5 above.
1.2.3.7 Accutubes should not be used for steam applications when the differential pressure is less than 10” water column.
1.2.4 GENERAL INTERCONNECTION REQUIREMENTS
1.2.4.1 Instrument lines to the Accutube shall be as large as possible in liquid and steam applications. For Accutube with 1/2” NPT connections, 1/2” pipe or tubing is recommended. Accutubes with 1/8” NPT connections should use 1/4” pipe or tubing.
1.2.4.2 Use of the optional instrument shutoff valves at the Accutube head are recommended.
1.2.4.3 Use of a 3-valve manifold is recommended at the indicator to aid system startup and to ease indicator maintenance and calibration.
1.2.4.4 Where instrument-piping slopes are required, use 1/2” per foot minimum.
1.2.4.5 The length of the instrument lines does not affect accuracy. Long lines can, however, dampen the indicator response time.
1.2.4.6 Test the system for leaks after connecting instrumentation to assure that no leaks exist.
1.2.4.7 In situations where accumulation of sediment or condensation within the piping is possible, a system drain or pressure blow down should be performed on a regular basis. Valves are recommended for indicators/transmitters without drain valves/plug.
8
2 OPERATIONAL CONSIDERATIONS
2.1 The Accutube flow sensor is a bi-directional flow meter. It can measure flow in either direction. The Accutube head is labeled High and Low pressure as observed for normal flow directions. With reverse flow, the High-pressure signal will occur at the Low­pressure port and vice versa. Reverse flow measurement is as precise as forward flow. This unique feature allows measurement of flow that changes direction. Special consideration should be given to the indicating instrument. Instruments which allow positive and negative (zero center) differential pressure readings are best applied here.
2.2 Accutube probes have limits as to the maximum flow rate that can be tolerated without risking damage to the sensor. The limits are defined as the maximum allowable differential pressure. See the Accutube general catalog which lists the maximum allowable differential pressures for your Accutube model.
2.3 Installation of the Accutube in locations where significant pipe vibrations exist should be avoided. Double mount style Accutubes are recommended where vibration is a concern.
3 READOUT INSTRUMENTATION
3.1 Many types of readout instrumentation can be used to measure the Accutube differential pressure. The most common types are manometers, dial gauge indicators, electronic transmitters/transducers or electronic gauges. Each type has its own installation and operational characteristics. Refer to manufacturer’s manuals for installation instructions.
3.2 Mounting position can affect zero indication on certain types of instruments. In such cases, the zero setting should be adjusted after installation of the instrument.
3.3 When a mercury manometer is used with a steam or liquid flow a correction factor must be applied to the flow calculations. Refer to Handbook, File No. 957:081, for determining the correction factor.
4 INSTALLATION PROCEDURE
4.1 GENERAL REQUIREMENTS
4.1.1 Prepare the surface of the pipe or duct where the Accutube is to be mounted.
Proper preparation involves removal of scale, rust, paint and grease for proper welding of the threaded coupling.
4.1.2 Drill or burn a hole through the pipe at the mounting location. The hole should
be 1/16" to 1/8" larger than the probe diameter as identified in Table 4.
TABLE 4
PROBE
DIAMETER
RECOMMENDED
DRILL SIZE 3/8 7/16 1/2 9/16 3/4 13/16
11-1/16
2-3/8 2-1/2
9
4.1.3 Double support type sensors require a second hole on the opposite side of the pipe. Location of this hole is important as it establishes proper alignment of the probe with respect to the flow. A common method of locating the opposite support hole is by wrapping a piece of string totally around the pipe, with the string crossing square to the pipe. The position can be marked at 1/2 the total length of the string.
4.1.4 Center the threaded weld coupling over the hole and tack weld in place.
4.1.5 Thread the packing gland fitting in place (compression type), and insert the probe into the pipe. Observe the position of the probe assuring that it is perpendicular within the tolerance shown in Figure 4.1. If adjustments are required, remove the probe and packing, and thread a pipe into the threaded fitting a few feet long. With the leverage of the pipe force the threaded fitting into the proper position.
DO NOT TRY TO USE THE ACCUTUBE AS A LEVER. DAMAGE TO THE PROBE AND/OR PACKING CAN RESULT!
4.1.6 Once alignment is verified, perform a final weld of the threaded fitting.
4.1.7 Re-assemble the packing and insert the Accutube as described in Section 4.3.
FIGURE 4.1 ACCUTUBE PROBE POSITIONING
(Maximum Allowable Misalignment)
4.2 INLINE FLOW SENSORS: SERIES 10A, 11A & 12A
4.2.1 The inline series flow sensors are flow-through devices in which the line must be interrupted for the device to be installed.
4.2.2 Positioning of the sensor is the same as recommended for the other types of sensors as listed in Section 1.0.
4.2.3 Connections to the main line are made through either threaded pipe fittings, solvent cement for PVC plain end type, hose connections for plain end types, or soldered joint for copper tube units.
10
Loading...
+ 21 hidden pages