Mercoid MPC Data sheet

Series
4-1/2
[114.3]
17/32 [13.5]
3-19/32
[91.3]
3-25/32
[95.9]
3-25/32
[95.9]
MAX. PANEL THICKNESS 0.25 [6.35]
PANEL CUT-OUT: 3.620 X 3.620 IN, +0.032/-0.000
(92 X 92 MM, +0.8/-0.0).
ALLOW FOR 0.5 IN (13 MM) CLEARANCE
AT THE REAR OF THE INSTRUMENT.
MEETS IP66 (UL TYPE 4X)
MPC Jr.
Pump Controller
One or Two Pump Control with Built-In Alternation
The Mercoid
®
MPC Junior Pump Controller provides versatile
level control in a standard 1/4 DIN package. Designed for use with almost any style level transmitter the unit displays the present level and main set point value. Incorporated in the MPC Jr. is programmable level differential for on/off control of one or two pumps, valves, or other devices through two SPDT relays. Also featured are two additional programmable alarm contacts with front alarm light indication. The MPC Jr. is flexible and incorporates a user-friendly programming menu. The front face meets NEMA 4X (IP66) for outdoor panel mounting.
FEATURES
• Selectable pump alternation when used with two pumps to minimize pump wear.
• Integral 24 VDC power supply for transmitter.
• User selectable security lock-out of programming and/or set points.
• Optional process input retransmission as a current (4 to 20 mA) or voltage (2 to 10 VDC) analog signal.
• Analog output of pump “on” condition for activation of separate pump run time meters.
Series MPCJR, Pump Controller
OPTIONS
Retransmisssion of input, 4 to 20 mA, Add suffix – RC Retransmission of input, 0 to 10 VDC, Add suffix – RV RS-232 Modbus
®
-RTU Serial Communications
Add suffix – 232 RS-485 Modbus Add suffix – 485
®
-RTU Serial Communications
SPECIFICATIONS Inputs: 4 (or 0) to 20 mA DC or 2 (or 0) to 10 VDC selectable. Input Impedance: Current = 10 Ω; Voltage = 5 K Ω. Output Ratings:
Control relays: SPDT, rated 10A @ 240 VAC res.,1/4 hp @ 120 VAC, 1/3 hp @ 240 VAC; Alarm relays: SPST, 3A @ 240 VAC res., 1/10 hp @ 120 VAC; Others: 15 VDC @ 20 mA for output one and output two.
Control Type: On/off, reverse (pump out) or direct (pump in) acting. Power Requirements: 100 to 240 VAC nominal, +10%-15%, 50 to 400 Hz, single phase; 132 to 240 VDC nominal, +10%­15%.
Power Consumption: 7.5 VA maximum. Accuracy: ±0.25% of span, ±1 least significant digit. Display: Two 4-digit, 7 segment 0.56˝ high LED’s. Display Resolution: 1 count. Memory Backup: Nonvolatile memory (no batteries required). Serial Communications: Optional RS-232 or RS-485 with
Modbus
®
protocol.
Ambient Operating Temperature/RH: 14 to 131°F (-10 to 55°C)/0 to 90% up to 104°F (40°C) non-condensing, 10 to 50% at 131°F (55°C) non-condensing.
Weight: 16 oz (454 g). Front Panel Rating: Meets UL Type 4X (IP66). Loop Power Supply (isolated): 24 VDC @ 50 mA, regulated. Agency Approvals: CE, cUL, UL.
ACCESSORY Weatherproof Enclosures, NEMA 4X (IP66).
See page 374 for details.
For compatible level transmitters see Mercoid
®
Series SBLT2 and PBLT2.
A-901
LEVEL
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Modbus®is a registered trademark of Schneider Automation.
355