Mercoid 3200G Operating Manual

Bulletin P-3200
Series 3200 Explosion-Proof Smart Pressure Transmitter
Specifications - Installation and Operating Instructions
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com
Phone: 219/879-8000 www.dwyer-inst.com
Table of Contents
Chapter 1. Introduction
1.2 Overview of Transmitter
1.3 Software Compatibility
1.4 Transmitter Components
Chapter 2. Handling Cautions
2.1 Unpacking Transmitters and Specifications Check
2.2 Models and Specifications Check .3 Storage
2
2.4 Selecting the Installation Locations
2.5 Calibration after Installation
2.6 Pressure Connections
2.7 Waterproofing Cable Conduit Connections
2.8 Restrictions on Use of Radio Transceiver
2.9 Installation Resistance Test and Dielectric Strength Test
2.10 EMC Conformity Standards
Chapter 3. Transmitter Functions
3.1 Overview
3.2 Safety Messages
3.3 Warning
3.4 Fail Mode Alarm
3.5 EEProm-Write Enable and Disable Mode Jumper
3.6 Configuration of Alarm and Security Jumper Procedures
3.7 Configuration of Zero and Span Procedure
3.8 Commissioning on the Bench with HHT
Chapter 5. On-line Operation
5.1 Overview
5.2 Safety Messages
5.3 Configuration Data Review
5.4 Check Output
5.5 Basic Setup
5.6 Detail Setup
5.7 Information Variables Setup
5.8 Diagnostics and Services .9 Calibration
5
Chapter 6. Maintenance
6.1 Overview
6.2 Safety Messages
6.3 Hardware Diagnosis
6.4 Hardware Maintenance
Appendix I
3200 Smart Pressure Transmitter LCD Display Code
HART®is a registered Trademark of Hart Communication Foundation
Chapter 4. Installation
4.1 Overview
4.2 Safety Messages
4.3 Warning
4.4 Commissioning on the Bench with Hand-Held Terminal
4.5 General Considerations
4.6 Electrical Considerations
4.7 Wiring
4.8 Mechanical Considerations
4.9 Environmental Considerations
Page 1
Chapter 1 Introduction
The 3200 Smart Pressure Transmitter is calibrated at the factory before shipping. To ensure correct and efficient use of the instrument, please read the manual thoroughly and fully understand how to operate the instrument before operation.
1. The contents of this manual are subject to change without prior notice.
2. All rights reserved. No part of this manual may be reproduced in any form without Dwyer Instruments, Inc. written permission.
3. If any question arises, errors are found or if any information is
issing from this manual, please inform Dwyer Instruments, Inc.
m
4. The specifications covered by this manual are limited to standard transmitters and do not cover custom-made instrument.
5. Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
1.1 Using This Manual
The operating manual provides information on installing, operating, and maintaining the Mercoid
®
Model 3200 Smart Pressure
Transmitter. The Chapters are organized as follows.
Chapter 2 Handling Cautions
Chapter 2 provides instructions on commissioning and operating Model 3200 Smart Pressure Transmitters. Informations on software functions, configuration parameters, and on-line variables are also included.
Chapter 3 Transmitter Functions
Chapter 3 contains suggestions on handling the Model 3200 Smart Pressure Transmitters.
1.2 Overview of Transmitter
The Mercoid
®
Smart Pressure Transmitter is a microprocessor based pressure transmitter with a capacitance sensor optimized for draft measurement. The Model 3200 has a true draft analog range from 0 to 20 mA. This transmitter is explosion-proof, high precision accuracy, reliability and has digital communication for remote communication system. The Model 3200 is enabled with HART HHT (HART various variables in host are able to be changed, configured and calibrated by users. The HART
upply and transmitter requires a 250~ 550 Ohm resistance.
s
1.3 Software Compatibility
The Mercoid at the factory. The following functions can be configured using a HHT (HART
®
Communicator) or PC Configurator. The transmitter’s
®
®
Smart Pressure Transmitter's software is implemented
®
Communicator).
®
communication with Host,
Communication between DC power
Function Supports
Function
ZERO/SPAN Button
PC/PDA
HART HHT
Rev. 58
ZERO/SPAN ZERO TRIM ZERO Adj Units set Range set Dampening set LCD Decimal set
● ∆
● : Supported. ∆ : Supported but update required
Chapter 4 Installation
Chapter 4 contains mechanical, environment consideration and electrical installation instructions for the Model 3200 Smart Pressure Transmitters.
Chapter 5 On-line Operation
Chapter 5 describes how to configure the parameters of the Model 3200 Smart Pressure Transmitter. See the following list for the details.
1. Regulations of circuit's Input/Output characteristics; Sensor or Output Trim
2. Changing the output characteristic; Range Configuration, Output Type, Dampening, Unit
3. Changing the general data; Tag No., Date, Message, etc.
Chapter 6 Maintenance
Chapter 6 contains hardware diagnostics, troubleshooting and maintenance task.
Page 2
Chapter 2 Handling Cautions
This chapter consists of cautions for transmitter handling, storage, installation, insulation and explosion structure, etc.
Step
Job
1
Unpacking
2
Model and S
3
Storage
4
Calibration
5
Installation Locations
6
Mechanical Considerations
7
Electrical Considerations
8
Mounting and Installation
9
Calibration on Spot
11
Operation
pecifications
Job Details
- Unpack transmitter packing
- Make sure the transmitter nameplate matches the model number on the PO
- In a dry, non-vibration and non-impact area
- Ambient temperature around 77°F (25°C) and 65% relative humidity
- Configuration of the Range, Zero/Span, Unit, Tag, Dampening Time, Transfer Function, DA Trim and other parameters
- Where ambient temperature are consistant
- Exposure to chemical corrosion, etc.
- Where shock and vibration are minimal
- Where the area classification does not exceed the exposion-proof rating
- Where maintenance is easy Where transmitter can be handled easily
-
- Be cautious of process connections leaking
- 24 VDC (Power Supply is 11.9 Vdc – 45 Vdc)
- For HART
®
communication, total resistance on transmitter terminal loop
should between 250 – 550 Ohm
- When mounting the transmitter, an appropriate bracket should be used
- The transmitter should be mounted securely to prevent swing
- Sensor Zero Trim should be done after ten seconds after the differential pressure stabilizes
- Make sure that PV value is zero and current is 4 mA
- Make sure the transmitter operates properly
Instrument
- HHT
-Pressure Source
- Galvanometer (Engineering)
(Engineering)
(Engineering)
(Mounting and Installation)
HHT or Zero/Span button
Eye or HHT
Page 3
2.1 Unpacking
When moving the transmitter to the installation site, keep it in the original packaging. Unpack the transmitter at the installation site to avoid damage on the way.
2.2 Models and Specifications Check
The model number and specifications are indicated on the nameplate. Please check the specification and model number.
2.3 Storage
The following precautions must be observed when storing the
nstrument, especially for a long period.
i
1. Select a storage area that meets the following conditions:
- is not exposed to rain or water.
- minimal vibration and shock.
- stored at normal temperature and humidity (approx. 77°F (25°C), 65% RH).
The ambient temperature and relative humidity ratings are:
Ambient Temperature: -40 to 185°F (-40 to 85°C)
(without LCD module)
-22 to 176°F (-30 to 80°C)
(with LCD module) General Use: -4 to 140°F (-20 to 60°C) Relative Humidity: 5% ~ 98% RH at 104°F (40°C)
2. When storing the transmitter, repack it the way it was delivered from the factory.
2.5 Calibration on Spot after Installation
1. Sensor Zero Trim should be done after transmitter is installed, because the zero point is not configured for mounting status.
2. When calibrating the Sensor Zero Trim apply a pressure of zero in advance, Sensor Zero Trim the sensor when the pressure is sufficiently stabilized (after approximately 10 seconds).
3. Sensor Zero Trimming can also be done with the Zero/Span button or a HHT (HART
®
Communicator), PC or PDA configurator.
4. Refer to On-line Operation for configuring other parameters.
2.6 Pressure Connections
WARNING
• Never loosen or tighten as it may cause dangerous spouting of process fluid. If the
process fluid is toxic or otherwise harmful, take appropriate care to avoid contact or inhalation of vapors even after disconnecting the instrument from process line for
aintenance.
m
nstrument installed in the process under pressure.
I
The following precautions must be observed in order to safely operate the transmitter under pressure.
1. Never apply a pressure higher than the specified maximum working pressure.
2. Confirm the option pressure of transmitter. It is necessary to use standardized and quality-approved parts.
3. There should be isolation valves in case of leakage.
2.7 Waterproofing Cable Conduit Connections
Apply a non-hardening sealant (silicone or tape, etc.) to the threads to waterproof the transmitter cable conduit connections.
3. If storing a used transmitter, thoroughly clean the diaphragm surfaces, so that no media remains. Make sure the transmitter assemblies are securely mounted before storing.
2.4 Selecting Installation Locations
The transmitter is designed to withstand severe environmental conditions. However, to ensure stable and accurate operation, the following precautions must be observed when selecting an installation location.
1. Ambient Temperature Avoid locations subject to wide temperature variations or a significant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate insulation or ventilation.
2. Ambient Atmosphere Avoid installing the transmitter in a corrosive atmosphere. If the transmitter must be installed in a corrosive atmosphere, there must be adequate ventilation. Precautions must be put into place to prevent intrusion or stagnation of rainwater in conduits.
3. Shock and Vibration Select an installation site with minimal shock and vibration (although the transmitter is designed to be relatively resistant to shock and vibration).
4. Installation of Explosion-Proof Transmitters Explosion-Proof transmitters can be installed in hazardous areas according to the gas types for which they are certified.
2.8 Restrictions on Use of Radio Transceivers
WARNING
transmitter’s external wiring, the transmitter may be affected by high frequency noise pickup. To test for such effects, bring the transceiver in slowly from a distance of several feet from the transmitter, and observe the measurement loop for noise affects. Always use the transceiver outside the area affected by noise.
Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the
5. Select a place where transmitter can be maintenanced easily.
Page 4
2.9 Insulation Resistance Test and Dielectric Strength Test
Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory, normally these tests are not required. However, if required, observe the following precautions in the test procedures.
1. Do not perform such tests more frequently than necessary. Even test voltages, that do not cause visible damage to the insulation, may degrade the insulation and reduce safety margins.
2. Never apply a voltage exceeding 500VDC for the insulation resistance test, or a voltage exceeding 500VAC for the dielectric
trength test.
s
3. Before conducting these tests, disconnect all signal lines from the transmitter terminals. Perform the tests using the following procedure.
2. Operating Temperature : -20°C ≤ T
3. T6 for process ≤ 85°C;
4. T5 for process ≤ 100°C;
5. T4 for process ≤ 130°C;
NOTICE
Electrical Data
1. Supply Voltage : 42 Vdc Max
2. Output Signal : 4 to 20 mA + HART
NOTICE
NOTICE
Electrical Connection : 1/2˝-14 NPT Female
200 ATEX Certification is according to the
3 below standards
EN 60079-0 : 2006 EN 60079-1 : 2007
amb
≤ +60°C
Insulation Resistance test
1. Short-circuit the + and - SUPPLY terminals in the terminal
box.
2. Turn OFF the insulation tester. Then connect the insulation
tester plus (+) lead wire to the shorted SUPPLY terminals and the minus (-) lead wire to the grounding terminal.
3. Turn ON the insulation tester power and measure the insulation
resistance. The voltage should be applied briefly to verify that insulation resistance is at least 20MΩ.
4. After completing the test and being very careful not to touch
exposed conductors. Disconnect the insulation tester and connect a 100kW resistor between the grounding terminal and the short-circuiting SUPPLY terminals. Leave this resistor connected at least three seconds to discharge any static potential. Do not touch the terminal while it is discharging.
Dielectric Strength Test
1. Short-circuit the + and - SUPPLY terminals in the terminal
box.
2. Turn off the dielectric strength tester. Then connect the tester
between the shorted SUPPLY terminal and the grounding
terminal. Be sure to connect the grounding lead of the dielectric
strength tester to the ground terminal.
3. Set the current limit on the dielectric strength tester to 10mA,
then turn on the power and gradually increase the tester voltage from '0' to the specified voltage.
4. When the specified voltage is reached, hold it for one minute.
5. After completing this test, slowly decrease the voltage to avoid
any voltage surges.
2.10 Explosion-Proof Rating
NOTICE
Installation
1. All wiring shall comply with local installation requirement.
2. The cable glands and blanking elements shall be of a certified flameproof type, suitable for the condition of use and correctly installed. Also those devices should be endured at the 130°C.
3. Housing Ground must be followed to “local electrical codes”. The most efficient ground procedure is to connect directly to the earth as least impedance.
1. How to Housing Ground: A. Internal Ground Connection:
Internal ground connection screw is located in terminal in housing; the screw can be identified as ground sign.
B. External Ground Assembly:
This is located in the right side of housing and identified as ground sign. (Grounding with a cable lug)
2. When use tubing, stopping boxes must be connected with the wall of housing directly.
3. Tubing is installed a minimum of 5 threads.
4. Sensor is to be threaded a minimum of 7 threads and prevented from turing by tightening the housing rotation set screw.
5. Do not disassemble flameproof Joints but in an unavoidable case to disassemble it or need the specification of flameproof Joints, contact the manufacturer before doing.
NOTICE
WARNING
Operation
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT.
1. Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous location.
2-10-1. FM Certification
HAZARDOUS LOCATION ELECTRICAL EQUIPMENT
Equipment Rating : Explosion-Proof for use in Class I, Division 1, Groups A, B, C and D; Dust-Ignition-Proof for Class II/III, Division 1, Groups E, F and G; Nonincensive for use in Class I, Division 2, Groups A, B, C and D; Suitable for use in Class II, Division 2, Groups E, F and G; and Suitable for Class III, Division 1; Hazardous(classified) location, indoor and outdoor (NEMA Type 4X/IP67).
2.10.2 DEKRA/ATEX Certification
ATEX Certification number : DEKRA 11ATEX0192X CE 0344 II 2 G
NOTICE
Model 3200 for potentially explosive atmosphere
1. Ex d IIC T6...T4
NOTICE
authorized representative of Dwyer/Mercoid is prohobited and will void KEMA/ATEX explosion-proof/flame-proof.
Maintenance and Repair
The instrument modification or parts replacement by other than
2.11 EMC Conformity Standards
EMI (Emission): EN55011
EMS (Immunity): EN50082-2
Dwyer Instruments, Inc. recommends customer use metal conduit wiring or twisted pair shield cable for signal wiring to conform with EMC regulation, when installing the Mercoid
®
3200 transmitters.
Chapter 3 Transmitter Functions
3.1 Overview
This chapter contains information on operating the Model 3200. Tasks that should be performed on the bench prior to installation are explained in this chapter.
Page 5