Menvier Security TS2500 Operator's Manual

TS2500
Intruder Alarm Control Panel
Operators Manual
CONTENTS
Glossary of Terms............................................................................................1
Introduction ....................................................................................................3
Circuits & Wards..............................................................................................4
Communication Devices ...............................................................................5
Remote Keypads............................................................................................6
Introduction ....................................................................................................8
Using the Set/Unset Menu ...............................................................................9
Setting Your Ward(s) ......................................................................................10
Setting with Circuits in Fault ...........................................................................12
Unsetting Your Ward(s)...................................................................................13
Part Setting the System .................................................................................15
Part Unsetting the System..............................................................................16
Setting with Circuits Omitted ..........................................................................17
Viewing Error Circuits .....................................................................................18
Unsetting after an Alarm.....................................................................................19
Resetting after an Alarm.....................................................................................20
Introduction ..................................................................................................22
Testing Bells & Sounders.....................................................................................23
Walk Testing Circuits......................................................................................24
Use Remote Reset ........................................................................................25
Changing Your Passcode .............................................................................26
Selecting Chime...........................................................................................27
Omitting a 24hr Group .................................................................................28
Omitting Circuits ...........................................................................................29
Silent Set Wards.............................................................................................30
Set/Unset Menu.............................................................................................31
Selecting User Menu 2 ..................................................................................32
Display Messages .........................................................................................33
System Details...............................................................................................37
User Details ...................................................................................................38
Circuit Details................................................................................................40
Service Record .............................................................................................44
Installer Information ......................................................................................45
1
Overview
Glossary of Terms
Alarm Receiving Centre
A permanently manned monitoring station used to receive alarm signals from an alarm system.
Chime
A facility which allows selected detection circuits to generate a two tone sound when triggered.
Detection Circuit
All detection devices, (e.g. magnetic contacts, movement sensors) are connected to detection circuits. Each circuit is allocated a number which identifies the detection device. For example, a room protected by a movement sensor may be "Circuit 1001", while a door protected by a magnetic Contact may be "Circuit 1002".
Digital Communicator
A signalling device fitted to the system which will transmit alarm information via the telephone line to the alarm receiving centre.
Downloading
A process which allows the alarm system to be remotely interrogated and programmed using a computer and modem.
Duress
A means of entering a passcode which generates a silent alarm via the signalling device (if fitted) to a the alarm receiving centre.
Entry Time
A pre-set time delay to allow the user to enter the protected area and access the remote keypad without causing an alarm.
Event Log
A record of system activity which is stored in memory (maximum of 4000 events).
Exit/Entry Route
The route which must be used when entering or leaving the protected area when the alarm system is being set.
Exit Terminator
An external push button switch used to complete the setting of the alarm system.
Exit Time
A pre-set time delay to allow the user to leave the protected area after initiating the setting procedure.
Final Exit
The door or detector used when leaving and entering the protected area.
Full Set
The state of the alarm system when it is protecting all areas of the premises.
2
Overview
Glossary of Terms
Master User
The user(s) who has the authority for assigning new users to the alarm system.
Modem
A device for transmitting and receiving data to and from a computer via the telephone line.
Omit
To intentionally exclude the monitoring of one or more detection circuits when setting the alarm system.
P.A(Panic Alarm)
An emergency push button switch used to activate an alarm. The alarm signal will also be transmitted to the alarm receiving centre if a signalling device is fitted to the alarm system.
Part Set
The state of the alarm system when it is protecting part of the premises.
Passcode
A unique number which must be entered before the alarm system can be operated.
Remote Keypad
A device located away from the main control panel that is used to operate the alarm system.
Reset
The action required to return the alarm system to its normal state after an alarm condition.
Set
To arm one or more wards.
System Open
The status of the system when all wards are unset.
Tamper Alarm
An alarm caused by the system being physically interfered with.
24hr Circuit
A circuit that is monitored at all times.
Unset
To disarm one or more wards.
Users
Persons allocated a passcode which allows them to operate the alarm system.
Wards
A group of detection circuits that can be set or unset independently of each other.
3
Overview
Introduction
The TS2500 is an advanced security alarm
control system using state of the art electronics to provide comprehensive but flexible protection for both large domestic and commercial premises. The system comprises of a number of components linked to a central control unit which is concealed from view but accessible for maintenance.
This manual describes the basic operating
procedures for your alarm system. For details of all operating procedures refer to the "Managers Operating Manual".
To avoid unnecessary operating errors
please discuss the details of your alarm system with your alarm company or master user before attempting to use it. Also ensure that alarm company completes the system record sheets at the back of this manual.
4
Overview
Circuits & Wards
Detection Circuits
A maximum of 1040 detection circuits can be monitored by the TS2500 alarm system. Each circuit is allocated a unique 4 digit circuit number and a 16 character text description which is used to identify the particular circuit. Your alarm company will have programmed each circuit to respond in a certain way when the circuit is activated during the set or unset state.
Wards allow the system to be broken down into specific areas so that parts of the system can be set and unset independently, Users can be given access to all wards or limited to specific wards. If a user does not have access to a particular ward they cannot set or unset that ward.
Wards
The TS2500 can be broken down into 16 wards, each ward is identified using the letters A - P. When the system is part set the display will show which wards are currently set.
5
Overview
Communication Devices
Your alarm system may be fitted with a digital communicator or RedCARE unit. The device is connected to your telephone line and in the event of an alarm activation, the device will signal the alarm condition to the alarm receiving centre. Where upon the necessary police action can be taken.
If your system has been fitted with such a device it is very important that you fully understand how to operate your alarm system. Operator misuse may result in
the police attending your premises under false conditions.
Remote Signalling
Downloading
A personal computer (PC) can be linked into your alarm system via the telephone line to allow remote programming and testing of the alarm system. This feature is known as "Downloading" and is normally performed by your alarm company or alarm receiving centre with your authorisation. An example of this feature would be for your alarm company to dial into your alarm system and adjust your entry time.
6
Overview
Remote Keypads
Your alarm system can be operated from
one or more remote keypads, which will have been strategically located within the protected premises.
Arming station
The remote arming station can only be used to set and unset the alarm system.
LED Keypad
The LED remote keypad can only be used to set and unset the alarm system.
Starburst Keypad
The Starburst remote keypad can only be used to set and unset the alarm system.
7
Overview
Remote Keypads
The LCD remote keypad is the only
keypad that will display full information. Any kind of programming or testing of the system, must be done using this type of keypad.
LCD Keypad
The LCD remote keypad is a full function keypad and can be used to program, test, set and unset the alarm system.
This is the remote keypad that is referred to throughout this manual.
1. Display - Used to show the system
time (LED & Starburst), along with other system messages (LCD only).
2. Green Power Indicator - Flashes if no
mains power is present. Steady when mains power is present.
3. Red Function Indicator - Can be
programmed by the alarm company, to indicate a fault, set or part-set etc.
4. Keyboard - Used for operating your
alarm system.
5. Cover - Fold-down cover with quick
guide operating instructions.
8
Operation
Introduction
Passcodes
Access to the system is gained by entering a 4 or 6 digit passcode. Every time you wish to use the system your passcode must be entered correctly.
User Types
The TS2500 can have up to 199 separate users each user is assigned a passcode, an access level and wards.
User Menus
The system has 4 users menus, with each menu having between 9 and 12 options.
User menu 1 is accessed by entering your
passcode followed by the [ key. Access
to user menus and options will depend on your user access level.
When a menu option is selected you may
abandon the option by pressing the ]
key. To leave the user menus and return the system to its original state simply keep
pressing the ] key.
Banner Message
The banner message is normally shown on the top line of display when the system is unset or full set. This message is configured by the installation engineer and is usually set to the alarm company's name.
Engineer on site
When your alarm company has an engineer on site and is logged into the system, the top line of keypads will show "ENGINEER ON SITE". You can continue to operate the system as normal, if required. The message is automatically cleared when the engineer logs off.
9
Operation
Using the Set/Unset Menu
The set/unset menu is displayed whenever
you enter your passcode. Pressing ]
whilst the menu is displayed will return the system to its original state.
The set/unset menu has several options, however, only options that are relevant will be displayed, e.g. if all wards are unset, the option to unset wards will not be displayed.
You can scroll forwards through the
options by pressing the A key and backwards by pressing the C key.
Set Wards
Pressing 0 will set your selected wards. Pressing 8 will set your selected wards
silently.
Pressing B will allow you to access the
part set groups.
Unset Wards
Pressing 0 will unset your selected wards.
Set With Omits
Pressing 0 will set your selected wards
with pre-defined circuits omitted.
View Error Circuits
Pressing 0 will display the circuits that
prevented your wards from setting.
User Menu 1
Pressing [ will select user menu 1.
10
Operation
Setting Your Ward(s)
Setting of wards can only be performed
at a valid remote keypad. If you attempt to set a ward from an invalid remote keypad the display will show: Cannot 'SET' from this keypad.
Before attempting to set your ward,
ensure all doors and windows are securely closed and the wards to be protected are vacated.
1. At the remote keypad enter your passcode.
2. Press 0 to set your ward(s) or 8 to set
your wards silently.
3. Leave the area to be protected by the designated exit route. The internal sounder will sound.
4. Close the final door and press the exit terminator button (if fitted).
5. When the internal sounder stops the ward(s) is set.
If the exit tone changes to an alarm tone, you must re-enter the protected area and enter your passcode. The display will show the ward(s) which failed to set.
11
Operation
Setting Your Ward(s)
If your user code is assigned to more than
one ward, you may be able to select the wards that you want to set after selecting the SET WARDS option.
1. At the remote keypad enter your passcode.
2. Press 0 to set your ward(s) or 8 to set
your wards silently.
3. Select wards by pressing 1 - 8, pressing A or C will toggle the display
between wards A - H & wards I - P.
4. When the required wards are displayed
press [ to set them.
5. Leave the area to be protected by the designated exit route. The internal sounder will sound.
6. Close the final door and press the exit terminator button (if fitted).
7. When the internal sounder stops the ward(s) is set.
If the exit tone changes to an alarm tone, you must re-enter the protected area and enter your passcode. The display will show the ward(s) which failed to set.
12
Operation
Setting with Circuits in Fault
When starting the exit procedure, any
active circuits, will cause the panel to enter into a fault mode. Whilst in this mode, the exit procedure is temporarily suspended.
1. At the remote keypad enter your passcode.
2. Press 0 to set your ward(s) or 8 to set
your wards silently.
3. The sounder will give a low fault tone and the exit procedure will be temporarily suspended, the display will also automatically show all circuits that
are in fault. Pressing A or C will scroll
through these circuits.
4. Check the circuits displayed, when all
circuits show healthy, press [ to restart
the exit procedure.
5. Leave the area to be protected by the designated exit route. The internal sounder will sound.
6. Close the final door and press the exit terminator button (if fitted).
7. When the internal sounder stops the ward(s) is set.
This procedure is a programmable option, and will only be displayed if enabled by your installation company.
13
Operation
Unsetting Your Ward(s)
Unsetting of wards can only be performed
at a valid remote keypad. If you attempt to unset a ward from an invalid remote keypad the display will show: Cannot 'UNSET' from this keypad.
1. Enter the protected area via the designated entry point, the internal sounder will sound.
2. Proceed directly to the remote keypad and enter your passcode. The internal sounder will stop.
If your passcode is not entered before the entry timer expires an alarm tone will be generated from the internal sounders.
A second entry timer is then started. If you
fail to enter your passcode before the second entry timer expires a full alarm condition will occur.
14
Operation
Unsetting Your Ward(s)
If your user code is assigned to more than
one ward you may be able to select the wards that you want to unset.
1. Enter the protected area via the designated entry point, the internal sounder will sound.
2. Proceed directly to the remote keypad and enter your passcode. The display will show that the ward in entry is going to be unset.
3. Select other wards by pressing 1 - 8, pressing A or C will toggle the display
between wards A - H & wards I - P.
4. When the required wards are displayed
press [ to unset them. The internal
sounder will stop.
If your passcode is not entered or
[
is not pressed before the entry timer expires an alarm tone will be generated from the internal sounders.
A second entry timer is then started. If you
fail to enter your passcode or press
[
before the second entry timer expires a full alarm condition will occur.
15
Operation
Part Setting the System
The TS2500 can store up to 10 pre-
defined part set groups, each group is allocated a combination of wards, e.g. "PART SET GROUP 1" could be allocated wards A and C, whereas "PART SET GROUP 2" could be allocated wards A and B etc.
1. At the designated remote keypad enter your passcode.
2. Press B to select the PART SET GROUPS.
3. Select the group by pressing 1 - 9 or
0. As you press the keys the top line of
the display will show the group description and the bottom line will show the wards that will be set.
4. When you have the required group
displayed press [ to set the selected
group.
5. Leave the area to be protected by the designated exit route. The internal sounder will sound.
6. Close the final door and press the exit terminator button (if fitted).
7. When the internal sounder stops the
ward(s) is set.
16
Operation
Part Unsetting the System
The TS2500 can store up to 10 pre-
defined part set groups, each group is allocated a combination of wards, e.g. "PART SET GROUP 1" could be allocated wards A and C, whereas "PART SET GROUP 2" could be allocated wards A and B etc.
1. At the designated remote keypad enter your passcode.
2. Press B to select the PART SET GROUPS.
3. Select the group by pressing 1 - 9 or
0. As you press the keys the top line of
the display will show the group description and the bottom line will show the wards that will be unset.
4. When you have the required group
displayed press [ to unset the
selected group.
17
Operation
Setting with Circuits Omitted
If you have configured the alarm system
to omit one or more circuits, you may set your wards with those circuits omitted. For details on selecting the circuits to be omitted, see "Omitting Circuit" on page
29. If no circuits are selected the option to "SET WITH OMITS" will not appear in the set/unset menu.
1. At the remote keypad enter your passcode.
2. Press 0 to set with circuits omitted. If
you want to set without circuits omitted,
press the A key until the display shows
"0 = SET WARDS".
3. Leave the area to be protected by the designated exit route. The internal sounder will sound.
4. Close the final door and press the exit terminator button (if fitted).
5. When the internal sounder stops the ward(s) is set and the selected circuits are omitted.
If the exit tone changes to an alarm tone, you must re-enter the protected area and enter your passcode. The display will show the wards which failed to set.
When you unset the ward(s) make sure all
previously omitted circuits are armed before setting the system again, see "Omitting Circuits" on page 29.
18
Operation
Viewing Error Circuits
If during the setting procedure one or more circuits remain active, the alarm system will fail to set. The internal sounder will sound and the external strobe will flash.
Before the alarm system can be successfully set you must ensure that the circuits that caused the "SET FAIL" condition are healthy.
The following procedure describes how to view the circuits that cause the "SET FAIL" condition, so that you can check and rectify the faults. Once rectified you should be able to successfully set your wards.
From a "SET FAIL" condition:
1. Re-enter the protected area and proceed directly to the remote keypad.
2. Enter your passcode, the display will show which ward failed to set.
3. Enter your passcode and press A until
the display shows "0=VIEW ERROR CCT".
4. Press 0 the display will prompt you to
select which wards you want to check.
5. To select or deselect wards A- H press 1
- 8. To select or deselect wards I - P press A then 1 - 8.
6. Check the displayed circuits, when all circuits show healthy you are ready to set.
7. Press ] and press 0 to set your wards.
19
Operation
Unsetting after an Alarm
If an alarm has occurred whilst the
system was set, the display will indicate the cause of the alarm when you unset the system. Once the cause of the alarm has been established the system must be reset, see "Resetting after an Alarm" on page 20.
1. Enter the protected area via the designated entry point. The internal sounder will sound.
2. Proceed directly to the remote keypad and enter your passcode. The internal sounder will stop.
3. The display will show the circuit that caused the alarm.
4. By pressing the B key the display will
alternate between the circuit text, e,g. Office window and the logged time/date of the alarm, e.g. 15:00.30 01/01.
5. The system now requires resetting.
If the alarm system is not reset after an alarm has occurred the internal sounder will generate a reset warning chime every minute as a reminder. To silence this tone simply re-enter your passcode.
20
Operation
Resetting after an Alarm
Each ward can be configured to be reset
by one of the following methods:
User Reset
Full alarms generated in a ward that is configured as user reset can be reset by any user that has access for that ward.
From step 5 of "Unsetting after an Alarm":
1. At the designated remote keypad enter your passcode.
2. Press ].
3. Your ward(s) is now reset.
Engineer Reset
Full alarms generated in a ward that is configured as engineer reset can only be reset by the engineer.
From step 5 of "Unsetting after an Alarm".
1. At the designated remote keypad enter your passcode. This will silence the reset warning chime.
2. Every minute the display will inform you of the action to take (normally "CALL ENGINEER TO RESET SYSTEM" although your alarm company can change this to more relevant information).
3. Contact your alarm company.
21
Operation
Resetting after an Alarm
Remote Reset
Full alarms generated in a ward that is configured as remote reset can be reset by the engineer or the user via the exchange of unique passcodes.
From step 5 of "Unsetting after an Alarm".
1. At the designated remote keypad enter your passcode.
2. Every minute the display will inform you of the action to take (normally "CALL A.R.C FOR REM. RESET CODE", although your alarm company can change this to more relevant information).
3. Enter your passcode followed by the [
key.
4. The display will advise you of the number to quote to your alarm receiving centre.
5. Contact your alarm receiving centre.
6. You will be asked to report the circumstances of the alarm. If the alarm receiving centre decides you do not require an engineer, a 4 digit remote reset code will be given to you.
7. Enter the 4 digit remote reset code
followed by the [ key and the system
will return to its normal condition.
22
User Menu 1
Introduction
User menu 1 is accessed by entering
your passcode followed by [ There are
9 menu options and access to these options will depend on your access level.
Each option has a "hotkey" and can be selected by pressing the relevant number, e.g. "Do Walk Test" is assigned to
key 2, so to select the weak test option press 2 followed by [.
Alternatively you can use the A & C
keys to scroll forwards and backwards through the available options. As you
press the A & C keys the bottom line of
the display will show the selected menu option. When you have found the
required option press the [ key to
perform the option.
To leave user menu 1 and return the system to its original state simply keep
pressing the ] key until the display shows
the time and date.
23
User Menu 1
Testing Bells & Sounders
This option allows you to periodically test
the external sounders (bell and strobe) and internal sounders.
1. At the remote keypad enter your
passcode followed by [.
2. Press 1 followed by [ to select the
bell test option.
3. The display will show which wards are selected for bell test.
4. To select or deselect wards A - H press
1 - 8. To select or deselect wards I - P press  then 1 - 8.
5. Once you have the required wards
selected press [ to start the test.
6. The external sounder is active. Press [ for next test or ] to end.
7. The external sounder & strobe is active.
Press [ for next test or ] to end.
8. The strobe is active. Press [ for next test or ] to end.
9. The internal alarm sounder is active.
Press [ to repeat all tests or ] to end.
10. Press ] twice to return the system to its
original state.
24
User Menu 1
Walk Testing Circuits
This option allows you to periodically test the operation of detection circuits. You can only select or deselect the wards that you have access to.
1. At the remote keypad enter your
passcode followed by [.
2. Press 2 followed by [ to select the walk
test option.
3. The display will show which wards are selected for walk test.
4. To select or deselect wards A - H press 1
- 8. To select or deselect wards I - P press A then 1 - 8.
5. Once you have the required wards
selected press [ to start the test.
6. Walk around the wards that are being tested and operate all detection devices. As each device is operated there will be a chime tone from the internal sounders and the display will show the triggered circuit.
7. When finished press ]. Pressing [ will
allow you to scroll through the tested circuits
in a chronological order. Press ] twice
times to return the system to its original state.
25
User Menu 1
Use Remote Reset
The remote reset option allows you to
reset your alarm via the exchange of unique passcodes.
The remote reset procedure is fully
covered on page 17.
If you select this option when the system
does not require resetting the display will show "Remote reset is not required".
26
User Menu 1
Changing Your Passcode
This option allows you to change your
own passcode.
1. At the remote keypad enter your
passcode followed by [.
2. Press 4 followed by [ to select the
change passcode option.
3. Enter your new passcode followed by
[.
4. If your new code is not accepted the display will show "NOT ACCEPTED try a different code".
5. Press ] to return the system to its
original state.
If your system has been configured to use 6 digit passcodes, the last two digits of the passcode will always be the last two digits of your user number, i.e. if you are user 001. Your passcode will be ????01. If you are user 002, your passcode will be ????02 etc.
27
User Menu 1
Selecting Chime
This option allows you to enable or
disable the chime feature for your wards. If a ward has the chime feature enabled, detection circuits that have been programmed as "Chime" will generate a chime tone when activated.
1. At the remote keypad enter your
passcode followed by [.
2. Press 5 followed by [ to select the
chime option.
3. The display will show which wards are currently selected for chime.
4. To select or deselect wards A - H press
1 - 8. To select or de-select wards I ­P press A then 1 - 8.
5. Once you have the required wards
selected press [ to accept.
6. Press ] twice to return the system to its
original state.
28
User Menu 1
Omitting a 24hr Group
This option allows you to omit a group of 24hr detection circuits. The group is pre­defined by the master user or alarm company.
1. At the remote keypad enter your
passcode followed by [.
2. Press 6 followed [ to select the 24hr
omit option.
3. Press 1 to select omit wards. To select or deselect wards A - H press 1 - 8.
To select or deselect wards I - P press
A then 1 - 8.
4. When the required wards are displayed
press [ to accept. The system will
automatically return to the unset condition and the display will show "WARDS ISOLATED! indicating that one or more 24hr circuits within the selected wards are isolated.
5. To reinstate the 24hr group repeat steps
1 to 4, except press 2 at step 3.
29
User Menu 1
Omitting Circuits
Occasionally it may be necessary to omit detection circuits when setting your ward, e.g. to leave door open that would normally be protected. This option allows you to select which circuits are to be omitted. Once selected you can then choose to set your ward(s) with or without the selected circuits omitted, see "Setting With Omits" on page 17.
1. At the remote keypad enter your
passcode followed by [.
2. Press 7 followed by [ to select the
omit circuits option.
3. The display will show circuit 0001 and its current omit status.
4. Select the circuit you require to omit by either entering its number or by pressing
the A & C keys to scroll up and down
through the circuits.
5. When the display shows the required
circuit, press B to alternate the circuit
between armed and omitted.
6. Repeat steps 4 and 5 for other circuits, if required.
7. When finished, press ] to return the
system to its original state.
30
User Menu 1
Silent Set Wards
This option allows you to configure which
wards will set silently, i.e. no exit tone when setting the selected ward. The wards that you select will remain configured as "silent set" until you deselect them using this menu option.
1. At the remote keypad enter your
passcode followed by [.
2. Press 8 followed by [ to select the
"Silent set wards option".
3. The display will show which wards are currently selected for silent set.
4. To select or deselect wards A - H press
1 - 8. To select or deselect wards I - P press A then 1 - 8.
5. Once you have the required wards
selected press [ to accept.
6. Press ] twice to return the system to its
original state.
Your selected wards will now set silently.
Pressing
8 when the display shows
"0 = SET WARDS" will also set all your wards silently.
31
User Menu 1
Set/Unset Menu
Normally the set/unset menu is displayed
whenever you enter your passcode. This option allows you to access the menu whilst user menu 1 is selected.
The set/unset menu has several options, however, only options that are relevant will be displayed, e.g. If all wards are unset, the option to unset wards will not be displayed.
Set Wards
Pressing 0 will set your selected wards. Pressing 8 will set your selected wards
silently.
Pressing B will allow you to access the
part set groups.
Unset Wards
Pressing 0 will unset your selected
wards.
Set With Omits
Pressing 0 will set your selected wards
with pre-defined circuits omitted.
View Error Circuits
Pressing 0 will display the circuits that
prevented your wards from setting.
User Menu 1
Pressing [ will select User menu 1.
32
User Menu 1
Selecting User Menu 2
User menu 2 is accessed by pressing [
whilst "User menu 1 Select option :-" is displayed. To leave user menu 2 and return to user
menu 1 simply press the ] key.
This manual does not cover the procedures available in user menu 2. For full details of user menus 2, 3 and 4 please refer to the "Managers Operating Manual".
33
Fault Finding
Display Messages
Unset alarms & Faults
These messages can occur when your ward is unset, if accompanied with an internal alarm they can be silenced by entering your passcode.
Your alarm system is fitted with a remote
signalling device which is reporting a telephone line fault. If the fault is not Cleared you may not be able to set your ward. If the fault persists. Contact your alarm company for further advice.
There is no mains power to the control panel
and the alarm system is now running on its standby battery. If the mains power is not restored you may not be able to set your ward, if the fault persists the standby battery will eventually run flat. Contact your alarm company for further advice.
The alarm system standby battery has
developed a fault. If the fault is not cleared you may not be able to set your ward. Contact your alarm company for further advice.
The lid of the control panel has been removed.
If the fault is not cleared you may not be able to set your ward. Contact your alarm company for further advice.
The control panel has two auxiliary tamper
circuits for monitoring auxiliary devices. The lid of the device has been removed. If the fault is not cleared you may not be able to set your ward. Contact your alarm company for further advice.
The lid of the external sounder has been
removed. If the fault is not cleared you may not be able to set your ward. Contact your alarm company for further advice.
The auxiliary supply used for powering
detection devices has blown its fuse. Contact your alarm company for further advice.
34
Fault Finding
Display Messages
One or more circuits have failed during a test routine initiated by your alarm company. You can still set and unset your wards but you should contact your alarm company for further advice.
One or more wards have been isolated so that 24hr protection with those wards can be accessed. Press [ to display which wards are currently isolated.
The TS2500 has an auto-set feature which will automatically set and unset specified wards at pre-programmed times, This message is displayed one minute before the wards are due to set and a chime tone is generated every ten seconds to warn you to leave the area. If you have the appropriate access code you can defer the automatic setting by entering your passcode and choosing the "DEFER SETTING" option.
The alarm system requires a routine maintenance visit from your alarm company. You can still set and unset your wards but you should contact your alarm company for further advice.
Your alarm company has enabled the payment timer and the timer has expired. You cannot set your wards and should contact your alarm company for further advice.
Your alarm company has had an engineer on site and is logged into the alarm system. You can continue to operate the system as normal, if required. The message is automatically cleared when the engineer logs off.
The hardware configuration of your alarm system has changed. You may not be able to set your wards and should contact your alarm company for further advice.
35
Fault Finding
Display Messages
Another user is accessing the alarm system.
You cannot use your keypad until this message has cleared.
The TS2500 has an high security feature which
can be applied to any ward. When the ward is unset the remote keypads display "HI SECURE UNSET" and the high security timer is started. Every time a detection device is triggered within the selected ward the timer is reset. However, if no detection devices within the selected ward are triggered, the timer will eventually expire. When the timer expires the ward is automatically set and the message on the keypads is cleared.
This message is displayed whenever a keypad
is locked out because there has been too many invalid code entries. This message will clear and the keypad will unlock itself after 5 minutes.
Cannot Set Messages
These messages occur when the system is unable to set your selected wards.
Cannot set due to a tamper fault on auxiliary
circuit 1 or 2. Clear the fault and if still displayed contact your alarm company for further advice.
Cannot set due to a tamper fault on the
external sounder. Clear the fault and if still displayed contact your alarm company for further advice.
Cannot set due to a fault from one or more
system components. The display will indicate the faulty device. Clear the fault and if still displayed contact your alarm company for further advice.
Cannot set due to a fault from one or more
circuits. The display will indicate the faulty circuits. Clear the fault and if still displayed contact your alarm company for further advice.
Cannot set due to a tamper fault on the
control panel. Clear the fault and if still displayed contact your alarm company for further advice.
36
Fault Finding
Display Messages
Cannot set due to no mains power at the
control panel. Clear the fault and if still displayed contact your alarm company for further advice.
Cannot set due to a phone line fault from your
remote signalling device. Clear the fault and if still displayed Contact your alarm company for further advice.
Cannot set due to the expiry of the payment
timer. Contact your alarm company for further advice.
The TS2500 has a code lock feature which can
be applied to selected users. When the code lock is in operation the selected users cannot use their passcode to set or unset their wards.
The remote keypad is locked out and cannot
be used by any users. The lock out is normally controlled by a key switch or similar.
The remote keypad that you are using to set
from is not assigned to your wards. Use a remote keypad that is assigned to your wards.
The remote keypad that you are using to unset
from is not assigned to your wards. Use a remote keypad that is assigned to your wards.
37
Records
System Details
Wards
Setting
A B C D E F G H
Entry Time
Exit Time
Setting Mode
Bell Delay
Bell Time
User Reset
Eng. Reset
Rem. Reset
Wards
Setting
I J K L M N O P
Entry Time
Exit Time
Setting Mode
Bell Delay
Bell Time
User Reset
Eng. Reset
Rem. Reset
Set with Line Fault Set with Mains Off
4 or 6 digit passcode Automatic Omitting
Remote Signalling Downloading
38
Records
User Details
No. Name Type Wards Auto-set Auto-Unset
000 Engineer A - P A A
001 Master
39
Records
User Details
No. Name Type Wards Auto-set Auto-Unset
40
Records
Circuit Details
No. Location Omit Chime Wards
41
Records
Circuit Details
No. Location Omit Chime Wards
42
Records
Circuit Details
No. Location Omit Chime Wards
43
Records
Circuit Details
No. Location Omit Chime Wards
44
Records
Service Record
Date Engineer Action
45
Records
Installer Information
Installation Engineer:
Installation Company:
Address:
Telephone No:
Reset Message:
Alarm Receiving Centre:
Telephone No:
Rem. Reset Message:
Part No. 496496 Issue 2
Loading...