Menvier Security MF9300 Installation Manual

Installation and User Instructions and Systems Log
Menvier Fire System
MF9300
Eight and sixteen zone control panels
IMPORTANT
THIS MENVIER FIRE PANEL IS DESIGNED TO BE USED WITH POLARISED AND SUPPRESSED BELLS. DO NOT USE WITH UNSUPPRESSED BELLS, UNSUPPRESSED RELAYS OR NON-POLARISED SOUNDERS OR STROBES ETC. DO NOT CONNECT 230V MAINS DIRECTLY TO THE PCB. ELECTRICAL INSULATION TESTS SHOULD NOT BE CARRIED OUT WITH THE CABLES CONNECTED TO THE PANEL OR DETECTORS OR SOUNDERS.
BEFORE MOUNTING THE PANEL PLEASE CARRY OUT THE FOLLOWING TEST:
CONNECT ALL END OF LINE RESISTORS TO ZONE AND ALARM LINE TERMINALS (SEE FIG. 3 PG. 27). CONNECT A MAINS SUPPLY,THAT IS NOT SWITCHED ON, TO THE PANEL. SCREW THE CENTRE SECTION INTO PLACE ON THE BACK BOX. CONNECT THE BATTERIES AND THEN SWITCH ON THE MAINS SUPPLY.
CHECK THAT ALL LIGHTS EXTINGUISH APART FROM THE POWER ON LIGHT. SELECT LAMP TEST AND CHECK THAT ALL LAMPS LIGHT AND THE INTERNAL BUZZER SOUNDS. IF ANY FAULT EXISTS THEN PLEASE CONTACT THE MENVIER SALES OFFICE.
ACCESSORIES
MBG913 Flush Mounting Call Point MBG914 Surface Mounting Call Point MBG917 Weatherproof Call Points MMT760 Medium Response Heat Detector MHT790 High Temp. Response Heat Detector MFR730 Fast Response Heat Detector MID710 Ionisation Smoke Detector MDP720 Photoelectric Smoke Detector MDB700 Common Detector Base MBB244 4ins (100mm) Bell MBM246 6ins (150mm) Bell MBM248 8ins (200mm) Bell MWB824 8ins (200mm) Weatherproof Bell MDS724 Ceiling Sounder MFS324 Flush Sounder MWS424/DB Weatherproof Sounder - Deep Base MWS424/SB Sounder - Shallow Base MCD524/DB Combined Sounder/Beacon - Deep Base MCD524/SD Combined Sounder/Beacon - Shallow Base MXB124/DB Xenon Beacon - Deep Base (1W) MXB124/SB Xenon Beacon - Shallow Base (1W) MXB224/DB Xenon Beacon - Deep Base (2W) MXB224/SB Xenon Beacon - Shallow Base (2W) MAS175 Discrete Sounder/Indicator MAR724 Heavy Duty Replay
IMPORTANT NOTICE RELATING TO INSTALLING AND
SER VICING THE P ANEL
WHENEVER POWERING UP THE PANEL FROM A COMPLETELY POWERED
DOWN STATE,
I.E. NO MAINS OR BATTERY SUPPLY CONNECTED, THE SYSTEM RESET
BUTTON MUST BE PRESSED - SEE FIG. 2 FOR THE LOCATION OF THIS
PUSH BUTTON.
PLEASE ALSO NOTE THAT ACCESS TO THE SERVICE AREA, BEHIND THE
UPPER DOOR, SHOULD BE GAINED BY USING THE SPECIAL FORKED KEY
PROVIDED. INSERT THE KEY AS SHOWN BELOW, PRESS DOWN AND THE
DOOR LATCH WILL CLEAR ALLOWING THE DOOR TO BE OPENED.
ATTEMPTING TO GAIN ENTRY TO THE SERVICE AREA WITH-
OUT USE OF THE KEY MAY DAMAGE THE PANEL.
TABLE OF CONTENTS
ACCESSORIES 1 OVERVIEW 4 SYSTEM OPERATION 4 OPERATING THE PANEL 5 SPECIALISED OPTIONS 8 APPENDIX A
Fire Alarm Log 9 Details Of Installation 18 Details Of Modifications 19
APPENDIX B
Faults - How To Recognise Them & What Action To Take 20 Fires - How To Recognise Them 20
APPENDIX C
Installation Of The MF9308 Control Panels 21 Using The Panel Interfaces 22 Setting System Parameters 24
APPENDIX D
Assembly Drawing 25 Positional Layout of Components 26 Wiring Diagram 27 Technical Specifications 28
PAGE 3
OVERVIEW
This document gives details of how to install, test, use and maintain operation of your MF9300 fire alarm panel.
SYSTEM OPERATION
What To Do At A Glance
The following information tells you what the various indicators, visible on the front panel, mean and how you should react to them.
INDICATOR STATUS ACTION
GENERAL FIRE ON Fire detected alarms not sounded.
FLASHING Fire detected alarms sounded.
ALARM LINE DELAY ON No action. Alarm line delays are set
up.
FLASHING Fire has been detected. Alarm delay
is in action, check for fire.
SYSTEM FAULT ON Refer to service provider (see front of
this manual for telephone number) DISABLEMENT FLASHING No action. Zone(s) disabled. TEST FLASHING Zone in test. If service provider is on
site take no action. Else refer to
service provider (see front of this
manual for telephone number). REMOTE SIGNAL ISOLATE ON No action. Remote signal output is
isolated. SUPERVISOR MODE ON No action - you are in Supervisor
mode - see section on `Operating
The Panel`.
FLASHING No action. System is self-checking.
Indicator should go out within 25
seconds. GENERAL FAULT FLASHING Refer to Appendix B
PAGE 4
OPERA TING THE P ANEL
General
The panel operates in 1 of 2 modes - Normal mode or Supervisor mode. In Normal mode the Supervisor mode LED is extinguished. In Supervisor mode the Supervisor LED is continuously ON.
Control of the facilities at the panel is available via the keyboard. Akey press is acknowledged by a blip of the internal panel buzzer. All keys that are active in the Normal mode have their legend actual­ly on the key itself, whereas all those facilities that are active once in the Supervisor mode have their legends above the corresponding key. For example, in Normal mode pressing the SILENCE BUZZER key will silence the internal panel buzzer. However, if in the Supervisor mode pressing the same key will perform a Lamp Test.
Normal Mode
This is the condition the panel is generally to be found in. From the Normal mode the user may: Silence Buzzer:
The user can silence the panel buzzer by pressing the SILENCE BUZZER button on the keyboard. The buzzer will then only sound approximately once every 10 seconds. NOTE that this does not silence any alarms, only the buzzer within the panel.
Entering the Supervisor mode:
By entering a 4 digit access code the user may get into the Supervisor mode. The access code for this panel is 2214. By pressing the numbered keys in the correct order, and then by hitting the ENTER key, the user will see the Supervisor mode indicator come on. Note that the buzzer will sound when it has recognised each key press. You are then in the Supervisor mode and may carry out additional facilities at the panel (see below).
Supervisor Mode
When in this mode a number of extra features are available to the user. Silence/Resound Alarms:
When in the Supervisor mode this key can be used to either turn the alarms on or to silence them. It is a toggle action. So, for example, to initiate an evacuation of a site you could press the Silence/resound alarm button to cause the alarms to sound. You could then silence the alarm at a later time by pressing the same button again. Note that if the alarms are silenced but there is still a Fire condition then the internal panel buzzer will buzz every 10 seconds. Also, if the alarms are silenced then this will not prevent subsequent new fire conditions from automatically resounding the alarms.
PAGE 5
PAGE 6
Reset:
This facility allows you to reset the panel. When hit, all panel indicators will light and the internal panel buzzer will sound. On the MF9304 the Fault relay output will also activate. On releasing the button the lights will extinguish, the buzzer will silence and the relay output will deactivate. For a period of approximately 25 seconds after pressing the Reset button the Supervisor mode indicator will flash. This is indicating that the panel is 'self testing'. Once the panel is ready the Supervisor mode indicator will extinguish and you can continue using the panel as you like.
Disable/Enable:
The panel allows a supervisor to disable individual zones and/or the alarm lines. A zone
which has been disabled will not be monitored for faults or for fires. Similarly, if the alarm lines are put into disablement then they will not be monitored for faults, nor would they be activated in a fire condition on a zone. (Note alarm lines are disabled in
pairs i.e. lines 1/2 and/or lines 3/4). To actually disable zone/alarm lines you have to be in the Supervisor mode. Once there,
press the Right Arrow key and a flashing 'cursor' will appear in the Alarm Line indicators. By repeatedly pressing the Right Arrow key you can step this 'cursor' through the Alarm Line indicators, onto the Zone Fault indicators. Keep pressing the same key and you will step through the zones, one at a time, until eventually it returns to the Alarm line indicators, and so on. When the indicator is at the zone or alarm lines that you wish to disable/re-enable then by simply pressing the Disable/Enable button in zone/alarm lines will be toggled accordingly. The Disablement indicator will flash, the internal buzzer will sound every 10 seconds and the corresponding Fault indicator(s) will light continuously for any zone or alarm line that is disabled. You may then use the Right Arrow key to move on and disable/re-enable further zones/alarm lines as required.
Note that a disablement is not cancelled by a reset or a removal of power to the panel.
Test:
The fire panel will allow the supervisor to put any zone into a test mode. To do this go into the Supervisor mode. Then press the Right Arrow key once and a flashing 'cursor' will appear in the Alarm indicators. Continue pressing the Right Arrow key until the 'cursor' reaches the zone that you want to put into test. Then press the Test button. The Test indicator will begin to flash, the internal panel buzzer will buzz at 10 second intervals and the Fault indicator of the zone concerned will light continuously. That particular zone is now in the Test mode.
When in test mode a detector/manual call point can be put into fire on that particular zone. The panel will recognise the fire condition and sound the alarms for 2 seconds. Then the panel will automatically reset the zone, in order to try and clear the fire condition. If the zone resets successfully then the alarms will sound again for 2 seconds. You can then go on and test the next detector/manual call point on the zone. If the zone fails to reset successfully, maybe due to a faulty detector or such like, then the panel will keep on trying to reset the zone for 2 minutes. If it has still failed at the end of this period then that zone immediately goes into fire.
Note that the alarm lines cannot be put into the test condition.
The fact that a zone is in test will not prevent the panel from recognising and acting upon fires or faults in other zones.
To take a zone out of the test mode you must go into the Supervisor mode and then press Reset.
Remote Signal Isolate:
To isolate the Remote Signal output press the Remote Signal Isolate button, whilst in Supervisor mode. The Remote Signal Isolate indicator will light, the Disablement indicator will flash and the internal panel buzzer will buzz every 10 seconds. To re-enable the Remote signal again at a later time simply press the Remote Signal Isolate button again. The corresponding indicators will extinguish and the panel buzzer will silence itself. Note that the remote signal isolate facility is not cancelled by a system reset.
Lamp Test Facility:
It is possible to test the indicators and the internal panel buzzer manually. To do this from within the Supervisor mode the Lamp Test button should be pressed. For the period that the button is kept depressed all panel indicators should light and the internal buzzer should sound. Once the button is released the panel will return to the condition it was in prior to the lamp test.
Exiting from the Supervisor Mode:
This mode will automatically exit if no key press is detected for a period of greater than 15 seconds. Alternatively, if you have finished in the Supervisor mode you may simply press ENTER. In either case the Supervisor mode indicator will extinguish and the panel will be back in the Normal mode.
PAGE 7
SPECIALISED OPTIONS
Certain additional features may be set up by the service provider at the commissioning stage. They are as follow:
Non-latching Zone
This feature is available on zone 1 and is selectable at commissioning by use of a switch in the panel (see Appendix C for selecting this feature). Note that this facility is additional to the requirements of EN54.
When activated any fire condition on zone 1 will not be latched i.e. once the condition has cleared, by whatever means, at the detecting device, the panel will automatically come out of the fire state for zone 1 - no user intervention would be required at the panel.
Further details of this interface are available on request.
Coincidence Detection
This feature is available on zone 2 and is selectable at commissioning by use of a switch in the panel (see Appendix C for selecting this feature).
On the first detector going into fire the panel indicates the event by sounding the buzzer and by hav­ing a double flash followed by a pause on the zonal fire indicator. Once the second detector goes into fire the full fire condition is initiated by the panel.
Using coincidence detection on zone 2 does not affect the way in which fires are recognised or acted upon from other zones in the system.
Note also that a manual call point pressed on any zone will put the panel into the fire condition immediately, irrespective of whether coincidence detection is active.
Alarm Line Delays
Delays can be introduced between the panel recognising a detector fire signal and the alarms being sounded. That delay is selectable at commissioning by use of switches in the panel (see Appendix C). The length of the delay can be set anywhere between 0 minutes i.e. no delay, and 7 minutes, in 1 minute intervals.
When the panel has alarm line delays set up the ALARM LINE DELAY indicator will be permanently ON. When a fire is detected on a zone the ALARM LINE DELAY indicator will flash, the buzzer will sound intermittently and the appropriate zonal fire indicator will flash. After the set delay period the panel will switch the alarms ON, unless the panel is reset.
Note that, delays do not affect fire signals from manual call points. These signals are acted upon immediately.
NOTE: AUX contacts are also delayed when this facility is active.
PAGE 8
Loading...
+ 20 hidden pages