Menvier Security DC58M+ Installation Manual

Page 1
DC58M+
8 Channel Digital Communicator &
Digi-Modem
Installation & Programming
Instructions
Page 2
CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Application. . . . . . . . . . . . . . . . . . . . . . . . . . 3
Approval. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Connections. . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting The DC58M+ . . . . . . . . . . . . . . . . 3
Compatibility with PABXs. . . . . . . . . . . . . . . . 3
Connection To Telephone Network . . . . . . . 4
Overview
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operating Modes. . . . . . . . . . . . . . . . . . . . . 4
NVM Programming . . . . . . . . . . . . . . . . . . . . 4
Technical Specifications. . . . . . . . . . . . . . . . 4
Operation
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Three-Way Calling . . . . . . . . . . . . . . . . . . . . 5
Line Fault Monitor . . . . . . . . . . . . . . . . . . . . . 5
Temporary Out of Service. . . . . . . . . . . . . . . 5
Point ID Extended Format . . . . . . . . . . . . . . . 6
Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation
Plug-on Installation . . . . . . . . . . . . . . . . . . . . 6
Telephone Line Connections . . . . . . . . . . . . 7
NETLCD/TS900 Keypad Connections . . . . . . 7
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Programming
Programming Menu . . . . . . . . . . . . . . . . . . . 9
Telephone Numbers. . . . . . . . . . . . . . . . . . . 10
Account Numbers . . . . . . . . . . . . . . . . . . . . 10
Reporting Channels . . . . . . . . . . . . . . . . . . . 10
Set/Day Channels. . . . . . . . . . . . . . . . . . . . . 10
Restore Channels . . . . . . . . . . . . . . . . . . . . . 10
Dialling Modes . . . . . . . . . . . . . . . . . . . . . . . 11
Test Call Period . . . . . . . . . . . . . . . . . . . . . . . 11
Point ID Extended Format . . . . . . . . . . . . . . . 11
Temporary Out of Service . . . . . . . . . . . . . . 11
Monitor Mode
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 12
Transmitted Data Specification . . . . . . . . . . 12
Typical Test Call . . . . . . . . . . . . . . . . . . . . . . 12
Other Monitor Messages. . . . . . . . . . . . . . . . 12
NVM Programming Form . . . . . . . . . . . . . . . 13
2
DC58M+ Installation Instructions
Page 3
Regulatory Requirements
General
The DC58M+ digital communicator/modem must be installed by an electrically competent person. Before attempting to install the DC58M+, the installer must be aware of the following:
Application
The DC58M+ digital communicator/modem is suitable for connection to the following types of telephone line:
l
Direct exchange lines (PSTN) supporting DTMF (Tone dialling).
l
PABX exchanges (with or without secondary proceed indication).
Approval
The DC58M+ digital communicator/modem is not suitable for connection as an extension to a pay phone or 1+1 carrier systems. The DC58M+ digital communicator/modem is approved for the following usage:
l
Automatic call initialisation
l
Operation in absence of proceed indication
l
Automatic dialling
l
Multiple repeat attempts
l
Serial connection
l
Three-way calling using BT Network Services
l
Modem
Usage other than the approved usage or failure to comply with the installation and programming instructions may invalidate any approval given to the apparatus. The approval Label for the DC58M:
This product is manufactured to meet all European Economic Area Telecommunication networks requirements.
Connections
Connection terminals on the DC58M+ are described as either "Safety Extra-Low Voltage" circuits (SELV) or "Telecommunications Network Voltage" circuits (TNV).
The PCB layouts on page 7 shows the two types of circuits.
+
It is important that the installer ensures that TNV connections are only connected to the PSTN and SELV circuits are only connected to other circuits designated as SELV circuits.
+
Interconnection circuits should be such that the equipment continues to comply with the requirements of 4.2 of EN 41003 for TNV circuits and 2.3 of EN 60950 for SELV circuits, after making connections between circuits.
Mounting The DC58M+
The DC58M+ is supplied inside a polycarbonate enclosure and is small enough to be mounted inside most control panels.
+
Once the unit is installed the cover must be secured using the screws supplied.
Compatibility with PABXs
The DC58M+ is only approved for use with compatible PABX systems. Correct operation in all circumstances is not guaranteed. If you experience any difficulties contact Menvier Technical Support.
3
DC58M+ Installation Instructions Regulatory Requirements
0186
Page 4
Connection To Telephone Network
The person responsible for connection of the DC58M+ to a PABX system is as follows:
l
If the wiring is owned by British Telecom PLC - British Telecom
l
If the wiring is not owned by British Telecom, either:
(a) British Telecom
(b) The authorised maintainer
(c) A professional installer after 14 days written
notice to the authorised maintainer.
Overview
General
The DC58M+ digital communicator consists of a single PCB fitted in a small polycarbonate case. It is used to transfer fast format status information from an alarm system to a dedicated Alarm Receiving Centre (ARC) via the Public Switched Telephone Network (PSTN). The DC58M+ also functions as a V21/V22bis modem. The DC58M+ is required when using the up/downloading feature on compatible Menvier control panels.
Operating Modes
The DC58M+ can be used as a plug-on communicator, in this mode the communicator is plugged in to the control panel using the appropriate connections cable.
NVM Programming
All programmed data is stored in a plug-in NVM (Non-Volatile Memory) which will be retained for up to five years with no power present. The NVM can be programmed by using a Menvier LCD Remote Keypad (P/No. NETLCD/TS900.REM) and an engineer's interface lead (P/No. NETEKI) which will plug directly on to the DC58M+. Alternatively the NVM can be programmed using the desktop programmer PP5.
Your ARC will normally provide a programming service and will supply a pre-programmed NVM on request or alternatively fill in the programming form at the back of this manual and return/fax it to Menvier Security (Repairs Dept.).
Technical Specifications
Supply: 11.5V - 14V; <35mA dc (Standby);
135mA dc (Active)
The installer must ensure that power drawn by the DC58M+ plus any other auxiliary apparatus is within the rating of the control panel (host) power supply.
Low Battery: Detection threshold is at 10.8V +/-
0.2V
Modem: 300/300 Baud (V21), 2400/2400
Baud (V22bis)
Programmer: NETLCD/TS900 remote keypad &
interface lead or PP5.
Case Size: 142(w) x 82(h) x 36(d) mm.
Weight 265g
REN value: 0.0
Series Voltage Drop
The voltage drop introduce by the series connection through the DC58M+ at a line current of 40mA is 0.1V. When used with other apparatus (telephone, fax etc.) the total voltage drop @40mA MUST NOT exceed 2.0V.
4
Overview DC58M+ Installation Instructions
Plug-on Mode
NETLCD/TS900
Remote Keypad
(Programmer)
Plug-on to Menvier control panels
Figure 2 Operating Modes
Page 5
Operation
General
When triggered, the DC58M+ seizes the PSTN line. When a dial tone is detected the DC58M+ lights the indicator (LED).
1. The appropriate telephone number is dialled, when answered, the alarm receiver will send a I.D tone. If no I.D tone is received, the DC58M+ will release the line, and repeat the process a maximum of three times to each selected telephone number.
2. When the DC58M+ receives the ID tone it transmits the appropriate data in the selected format. If the data is successfully received the alarm receiver responds with an acknowledgement tone. The DC58M+ releases the line and flashes the red LED 4 times.
3. If the acknowledgement tone is not received, the DC58M+ releases theline and tries again.
4. After the third dialling attempt has failed a line fault is signalled to the control panel to allow any programmed bell delayto be cancelled.
Three-Way Calling
This is one the new features that is available from BT Network Services, for this feature to work correctly the telephone line must have this service enabled (contact BT for further details). In non-UK countries you can enabled or disable this feature (as well as pulse dialling) in programming. See page 9, Porgramming.
When the DC58M+ is triggered the unit checks for incoming ringing or off hook (someone trying to block the call). The unit then sends a "Recall" signal, which is detected by the exchange as a request for a new line. With a new line available the DC58M+ then attempts toconnect with the ARC.
If the DC58M+ is connected to an older pulse dial only exchange, the numbers being dialled must be selected to "Pulse" dial, see "Telephone Numbers" on page 10. This will disable the three-way calling facility as it is not available on the older type exchanges.
Line Fault Monitor
The line fault monitor continuously monitors the PSTN line and will detect:
l
The loss of line voltage (cut line)
l
A line voltage less than 35V (parallel telephone off hook)
l
An incoming ringing signal that will try and prevent DC58M+ operation
If the DC58M+ is used on a shared line then the line fault monitor can be selected to only monitor a cut line by setting the "HI/LO SECURITY" option to "LO". It is also recommended that "Three-Way Calling" is used (see above) so that the security of the system is not compromised.
Temporary Out of Service
In addition to the line fault monitor, the DC58M+ can be programmed to perform a more detailed line test at pre-set intervals. The DC58M+ will seize the line and dial all digits but the last one of telephone number 1. If the unobtainable tone is NOT detected it is assumed that the line is healthy and the unit releases the line. If the unobtainable tone is detected, a line fault is signalled.
Note: This feature must be disabled if this product is used in Germany.
5
DC58M+ Installation Instructions Operation
Page 6
Point ID Extended Format
This is a new format which is used to send additional fast format data to the alarm receiver. The additional information can be used to indicate the circuit that caused the alarm, the user that set/unset the system etc. For the DC58M+ to send this additional data, the unit must be plugged on to a Menvier control panel that supports "Point ID Extended Format"' and report to a compatible alarm receiver.
Modem
When a call is made to the alarm site the DC58M+ will pick up the call and attempt to connect to the modem that is connected to the P.C. If successful the communication link is established and data can be transferred. When the Modem is on-line the red LED on the DC58M+ flashes continuously until the communication link is broken. If during the Modem operation the control panel generates an alarm which is required to be transmitted to the ARC, the DC58M+ will suspend the Modem operation and attempt to communicate with the alarm receiver.
Installation
A LED 1
Activity LED. On whilst communicator is active. Flashes on and off 4 times when successfully communicated with the ARC. Flashes continuously when modem is in operation.
B Test Call
Short these two pins to initiate a test call.
C NVM
Removable Non-Volatile Memory used to store all programmed data.
D JP2 (SELV)
Connector for Menvier control panels.
E JP1 (SELV)
Connector to NETLCD/TS900 remote keypad (Programmer).
F Telephone Connections (TNV)
Terminal connections to the telephone line.
G HI/LO SECURITY
Line fault monitoring level: Link fitted = High Security Link removed = Low Security
Plug-on Installation
1. Isolate ALL power from the control panel
(battery and mains).
2. Do not attempt to continue if the mains or battery supply is still present.
3. Remove the cover from the DC58M+ case and if appropriate fita pre-programmed NVM.
4. Connect the interface lead to the control panel connector (DIGI MODEM) via the cable entry hole in the base, then connect the lead onto JP2 on the DC58M+ (marked TO CONTROL PANEL).
6
Installation DC58M+ Installation Instructions
A
A1
B
B1
NVM
TEST CALL
TS900
REMOTE
A
E
B
C
D
F
G
HI/LO SECURITY
TO CONTROL PANEL
JP 2
JP 2
Figure 3 DC58M+ PCB Layout
Page 7
5. Set the "HI/LO SECURITY" link to the appropriate setting.
6. Secure the DC58M+ base to the control panel base using the self-adhesive pads.
7. Refer to "Telephone Line Connections".
Telephone Line Connections
1. Connection to the telephone network must be
made via an NTE5 master socket (Line Box).
2. Using the cable type 1/0.5mm CW1308, strip back 5mm of the required cores and feed through the DC58M+ cable entry, see
Figure 4.
+
Keep all telephone cables at least 5mm away from other alarm cables.
3. CW1308 cable is available from RS Components (Part No. 368-413). Alarm or any other type of cable must not be used.
4. Connect the three cores to the terminal blocks marked A and B.
5. Remove the two screws from the BT master jack socket and remove the bottom section from the master jack.
6. Connect the cable from A and B terminals on the DC58M+ to the BT master jack terminals,
see Figure 4.
7. A special insertion tool will be required to connect the cable to the master jack, this is available from RS Components (Part No. 470-487).
8. Replace the bottom section of the master jack socket and do up the two screws. Refer to "Testing" (see below).
NETLCD/TS900 Keypad Connections
To convert a standard NETLCD/TS900 remote keypad into a DC58M+ programmer the following is required:
NETLCD TS900REM
32 character LCD remote keypad.
NETEKI Networker Engineer's Keypad
Interface lead.
7
DC58M+ Installation Instructions Installation
To PSTN
A1 B1
B A
Phone
Red White Green Blue
5
RJ11 Connector Terminals at Jack
Adaptor Lead 485226
Direct Connection DC58M+
Using Adaptor Lead DC58M+
2 3 4
A1 B1
B A
Figure 4 Telephone Line Connections
Figure 5 Engineer's Keypad Connections
Page 8
Testing
Once all the installation steps have completed, proceed as follows:
1. Ensure that you have informed the ARC that you will be sending test calls.
2. Connect power to the control panel.
(a) If the NVM is un-programmed or fitted
incorrectly the red LED will flash rapidly.
(b) If the DC58M+ is to be programmed using
the NETLCD/TS900 remote keypad, plug it onto the connector labelled "TS900 REMOTE". Refer to "Programming" for further details.
3. Send a test call by momentarily shorting the "TEST CALL" pins together, see Figures & 3. This will initiate a test transmission to the ARC.
+
The DC58M+ will not send a test call if there is a parallel hand-set off hook.
4. Trigger all the relevant channels by:
(a) Setting and unsetting the control panel to
send open/close signals.
(b) Set the system and cause a full alarm to
send an intruder signal.
(c) Press any PA buttons to send a PA signal.
(d) Activate any other devices that require
testing.
5. Unplug the NETLCD/TS900 remote keypad and secure the cover of the DC58M+ using the two screws supplied.
6. Finally replace and secure the cover on the control panel.
8
Installation DC58M+ Installation Instructions
Page 9
Programming
Programming Menu
9
DC58M+ Installation Instructions Programming
TELEPHONE NO.1 018112345678
TELEPHONE NO.2 018112345687
REPORTS TO NO.1 **34***8
Enter Telephone No. 1
Press any key
= Clear number = Pulse Dial (P) or Pause (-) = Tone Dial (T)
DC58M+ Vers 1.0 Press Any Key
Enter Telephone No. 2
TELEPHONE NO.3 018112345679
ACCOUNT NO.1 0001
Enter Telephone No.3
Enter account No.1
ACCOUNT NO.2 0001
ACCOUNT NO.3 0001
Enter account No. 2
Enter account No. 3
Select channels that report
to tel No.1 by pressing [1] - [8]
REPORTS TO NO.2 *234***8
REPORTS TO NO.3 *234***8
Select channels that report
to tel No.2 by pressing [1] - [8]
Select channels that report
to tel No.3 by pressing [1] - [8]
SET/DAY CHANNELS ***4****
Select Set/Day (Open/Close) channels by pressing [1] - [8]
RESTORE CHANNELS **34****
Select Restore channels
by pressing [1] - [8]
= Consecutive = Alternative = All
Dialling Mode is Consecutive
Select dialling mode:
= Disabled = Daily = Weekly
TEST CALL PERIOD Disabled
Select test call period:
= Fortnightly
Digi Format Standard
Select output type:
= Standard = Extended Limited = Extended Full
= Disabled = Daily = Weekly
T.O.S Calls are Disabled
Select Temporary Out of
Service monitoring period:
= Fortnightly
3-WAY CALLING Enabled
Enable/Disable 3-way calling:
= Disable = Enabled
Finish
Page 10
Telephone Numbers
Up to three telephone numbers can be programmed, each number can be up to 16 digits long. As part of the number, special codes can be inserted to allow for pulse dialling (P), tone dialling (T) and a 4 second pause (-) for PABX systems.
When the DC58M+ dials a telephone number it will automatically select the correct dialling format. However, the format can be forced if required.
Selecting Tone Dialling
Tone dialling is the modern format and is sometimes referred to as Multiple Frequency (MF) or Dual Tone Multiple Frequency (DTMF). To force the number to be dialled in this format press [C] before entering the telephone number. The telephone number will be prefixed with a "T" to indicate tone dialling.
Inserting a Pause for PABX's
If the DC58M+ is connected to an internal PABX telephone exchange system, normally the exchange requires a pre-fixed digit to be dialled before obtaining an outside line (normally 9). Some exchanges also require a pause after the pre-fixed digit before dialling the telephone number. To insert a 4 second pause, enter the PABX digit (normally 9) then press the [B] key the display will show "9-". Now enter the telephone number.
+
When programming telephone numbers it is very important check that they have been entered correctly otherwise the DC58M+ could dial a private number inadvertently.
Account Numbers
This is a 4 digit number that the alarm receiving centre uses to identify the alarm site. Up to three account numbers can be programmed. Account numbers can only be programmed if the corresponding telephone number is programmed i.e., if "Telephone No.2" is blank then the option to program "Account No.2" is not available.
Reporting Channels
Each channel can be programmed to report to any combination of telephone numbers. For example channel 1 can be programmed to report to all telephone numbers, whereas channel 3 can be programmed toonly report to telephone number 1. Reporting channels can only be programmed if the corresponding telephone number is programmed i.e., if "Telephone No. 2" is blank then the option to program "REPORTS TO NO. 2" is not available.
Set/Day Channels
Any channel can be programmed as a '"Set/Day" channel, this type of channel will report a "Close" signal when the input channel is active and an "Open" signal when the input channel is restored. Normally channel 4 is used to report an "Open/Close" signal, but if required this can be changed.
Restore Channels
Any channel can be programmed as a "Restore" channel, this type of channel will report a "Alarm" signal when the input channel is active and a "Restore" signal when the input channel is restored. If a channel is programmed without "Restore", only the "Alarm" signal will be transmitted.
+
If any channel is programmed as "Set/Day", its channel will automatically be programmed as "Restore".
10
Programming DC58M+ Installation Instructions
Page 11
Dialling Modes
The DC58M+ can be programmed for the following Dialling Modes:
Consecutive
In this mode the DC58M+ will dial the first telephone number and attempt to report the alarm signal. If the attempt fails, it will shut down and re-dial the first telephone number. If the second attempt fails, it will shut down for 1 minute then re-dial the first telephone number again. If the third attempt fails the the unit shuts down and now attempts the second telephone number. This sequence continues until all three attempts to each telephone number have been used, after which the unit will shut down completely.
Alternative
In this mode the DC58M+ will dial the first telephone number and attempt to report the alarm signal. If the attempt fails, it will shut down and dial the second telephone number. If the second attempt fails, it will shut down and dial the third number. This sequence continues until all three attempts to each telephone number have been used, after which the unit will shut down completely.
All
In this mode the DC58M+ will dial consecutively, but also requires a successful communication from all alarm receivers.
Test Call Period
The DC58M+ can be programmed to periodically send a "Test" signal (Code 9) to the Alarm Receiving Centre.
Point ID Extended Format
It is possible to send additional alarm information to the ARC, this can include circuit and user ID. For full details on the extended information refer to the relevant control panel "Installation Manual".
+
This feature is only supported by relevant Menvier control panels, for details on which control panels support this feature contact Menvier Technical Support.
Point ID can be setto one of the following reporting options:
1 Will NOT Report
This disables "Point ID Extended Format" and the DC58M+ will only report "Fast Format" data to the alarm receiver.
2 Limited Report
When "Limited Report" is selected the DC58M+ will only report the extended format data relating to the channel that is triggered. For example, if the DC58M+ is programmed to report channels 2 and 3 (PA and Intruder) then the unit will only report events relating to PA and Intruder activations.
3 Full Report
When "Full Report" is selected the DC58M+ will report all extended format data to the alarm receiver irrespective of the channels that are programmed to report. That is, if all eight channels are programmed as non reporting, the unit will still report all events to the ARC.
Temporary Out of Service
This feature is used to test the integrity of the telephone line by dialling all but the last digit of the first telephone number. If the unobtainable tone is NOT detected it is assumed that the line is in good working order, however, if an unobtainable tone is detected the DC58M+ will signal a line fault condition.
+
This feature is only supported by relevant Menvier control panels, for details on which control panels support this feature contact Menvier Technical Support.
11
DC58M+ Installation Instructions Programming
Page 12
Monitor Mode
Introduction
When the NETLCD/TS900 remote keypad is left plugged on to the DC58M+ it will act as a monitor, so that during testing to the ARC the display will show the communicator's status.
Transmitted Data Specification
The data transmitted to the alarm receiver is industry standard fast format. The data contains the following information:
Account No This is a 4 digit number and is unique
to the installation site.
Channel 1-8 Each channel can report its own
status code:
Code 1 = New Alarm
Code 2 = System Opened
Code 3 = Channel Restored
Code 4 = System Closed
Code 5 = Healthy Channel
Code 6 = Previouslyreported event
Channel 9 This channel is normally referred to
as the status channel and is used to report the following:
Code 7 = Normal
Code 8 = Low Battery
Code 9 = Test
Typical Test Call
When the "TEST CALL" pins are momentarily shorted the DC58M+ will send a test call to all programmed telephone numbers. The display should show:
Other Monitor Messages
The following monitor messages may also be displayed:
12
Monitor Mode DC58M+ Installation Instructions
DC58M+ MONITOR Waiting for I.D
DC58M+ MONITOR Sending Data
Dialling the first telephone No.
Waiting for the alarm receiver to answer the call and send its identenifation tone (I.D).
The alarm reciever is on line and the DC58 is sending its data.
The data send is displayed.
This is repeated for all
programmed telephone
numbers
The data was accepted and the alarm reciever has sent its acknowledgemnt tone.
DC58M+ MONITOR Dialling Number 1
DC58M+ MONITOR 0001 5555 5555 9
DC58M+ MONITOR Call Successful
DC58M+ MONITOR Unobtainable
Dc58 MONITOR No Ack. Tone
M+
DC58M+ MONITOR Engaged
Dc58 MONITOR T.O.S Call Ok
M+
No dial tone detected when the DC58 went on line.
The number was dialled but an unobtainable tone was detected.
The alarm receiver is engaged.
No reply from the alarm receiver.
The "Temporary Out of Service" test call was successful.
The DC58 sent its data to the alarm receiver, but the receiver failed to give an acknowledgement tone (corrupted data).
DC58M+ MONITOR No Dial Tone
DC58M+ MONITOR No Answer
Page 13
NVM Programming Form
13
DC58/58M Installation Instructions Monitor Mode
Telephone No. 1
Telephone No. 2
Telephone No. 3
Account No. 1
Account No. 2
Account No. 3
Channel No. 12345678
Reports to No. 1
Reports to No. 2
Report to No. 3
Set/Day Channels
Restore Channels
Three-way Calling
Disabled:
o
Enabled:
o
Dialling Mode Consecutive:
o
Alternative:
o
All:
o
Test Call Period Disabled:
o
Daily:
o
Weekly:
o
Fortnightly:
o
Format
Standard:
o
Extended Format
Limited Report:
o
Extended Format Full
Report:
o
SIA I
o
SIA II
o
T.O.S Monitoring Disabled:
o
Daily:
o
Weekly:
o
Fortnightly:
o
Page 14
14
Monitor Mode DC58/58M Installation Instructions
This page is intentionally blank.
Page 15
15
DC58/58M Installation Instructions Monitor Mode
This page is intentionally blank.
Page 16
496465 Issue 1
16
Monitor Mode DC58M+ Installation Instructions
Cooper Security Ltd. Security House, Xerox Business Park, Mitcheldean, Gloucestershire, GL17 0SZ. England
Product Support Tel: (01594) 545556 Between 09:00 and 17:00, Monday to Friday. Product Support Fax: (01594) 545501.
Email: menvier.security@dial.pipex.com www.coopersecurity.co.uk
Loading...