Menvier Security DC58 Installation Manual

Page 1
DC58 & DC58M
8 Channel Digital Communicator &
Digi-Modem
Installation & Programming
Instructions
Page 2
CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Application. . . . . . . . . . . . . . . . . . . . . . . . . . 3
Approval. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Connections. . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting The DC58/58M . . . . . . . . . . . . . . . 3
Compatibility with PABXs. . . . . . . . . . . . . . . . 3
Connection To Telephone Network . . . . . . . 4
Overview
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operating Modes. . . . . . . . . . . . . . . . . . . . . 4
NVM Programming. . . . . . . . . . . . . . . . . . . . 5
Technical Specifications. . . . . . . . . . . . . . . . 5
Operation
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Special Information Tones (SIT) . . . . . . . . . . . 5
Three-Way Calling . . . . . . . . . . . . . . . . . . . . 6
Line Fault Monitor . . . . . . . . . . . . . . . . . . . . . 6
Temporary Out of Service. . . . . . . . . . . . . . . 6
Point ID Extended Format. . . . . . . . . . . . . . . 6
Modem (DC58M Only). . . . . . . . . . . . . . . . . 6
Installation
Plug-on Installation . . . . . . . . . . . . . . . . . . . . 8
Stand-alone Installation (DC58 Only) . . . . . . 8
Telephone Line Connections . . . . . . . . . . . . 8
TS900 Remote Keypad Connections . . . . . . 9
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Programming
Programming Menu. . . . . . . . . . . . . . . . . . . 10
Telephone Numbers. . . . . . . . . . . . . . . . . . . 11
Account Numbers . . . . . . . . . . . . . . . . . . . . 11
Reporting Channels . . . . . . . . . . . . . . . . . . . 11
Set/Day Channels. . . . . . . . . . . . . . . . . . . . . 11
Restore Channels. . . . . . . . . . . . . . . . . . . . . 11
Invert Channels . . . . . . . . . . . . . . . . . . . . . . 12
Dialling Modes . . . . . . . . . . . . . . . . . . . . . . . 12
Test Call Period. . . . . . . . . . . . . . . . . . . . . . . 12
Digicom Outputs . . . . . . . . . . . . . . . . . . . . . 12
Point ID Extended Format. . . . . . . . . . . . . . . 13
Temporary Out of Service . . . . . . . . . . . . . . 13
Ring Count (DC58M Only) . . . . . . . . . . . . . . 13
Monitor Mode
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 14
Transmitted Data Specification . . . . . . . . . . 14
Typical Test Call . . . . . . . . . . . . . . . . . . . . . . 14
Other Monitor Messages. . . . . . . . . . . . . . . . 14
NVM Programming Form . . . . . . . . . . . . . . . 15
2
DC58/58M Installation Instructions
Page 3
Regulatory Requirements
General
The DC58/58M digital communicator/modem must be installed by an electrically competent person. Before attempting to install the DC58/58M, the installer must be aware of the following:
Application
The DC58/58M digital communicator/modem is suitable for connection to the following types of telephone line:
l
Direct exchange lines (PSTN) supporting DTMF (Tone dialling) or Loop Disconnect (Pulse Dialling).
l
PABX exchanges (with or without secondary proceed indication).
Approval
The DC58/58M digital communicator/modem is not suitable for connection as an extension to a pay phone or 1+1 carrier systems. TheDC58/58M digitalcommunicator/modemisapprovedforthe following usage:
l
Automatic call initialisation
l
Operation in absence of proceed indication
l
Automatic dialling
l
Multiple repeat attempts
l
Serial connection
l
Three-way calling using BT Network Services
l
Modem
Usageother than theapprovedusage or failure to comply with the installation and programming instructions may invalidate any approval given to the apparatus. The approval Label for the DC58:
The approval Label for the DC58M:
Connections
Connection terminals on the DC58/58M are described as either "Safety Extra-Low Voltage" circuits (SELV) or "Telecommunications Network Voltage" circuits (TNV).
The PCB layouts on page 7shows the two types of circuits.
+
Itisimportantthattheinstallerensures that TNV connections are only connected to the PSTN and SELV circuits are only connected to othercircuits designated as SELV circuits.
+
Interconnection circuits should be such that the equipment continues to comply with the requirements of 4.2 of EN 41003 for TNV circuits and 2.3 of EN 60950 for SELV circuits, after making connections between circuits.
Mounting The DC58/58M
The DC58/58M issupplied inside a polycarbonate enclosure and is small enough to be mounted inside most control panels.
+
Oncetheunitisinstalledthe cover must be secured using the screws supplied.
Compatibility with PABXs
The DC58/58M is only approved for use with compatible PABX systems. Correctoperation in all circumstances is not guaranteed. If you experience any difficulties contact Menvier Technical Support.
3
DC58/58M Installation Instructions Regulatory Requirements
MENVIER SECURITY
DC58
POWER REQUIREMENTS 12v DC @100mA MAX
REN=0.0
S/1100/3/R/503310
MENVIER SECURITY
DC58M
POWER REQUIREMENTS 12v DC @100mA MAX
REN=0.0
S/1100/3/R/503311
Page 4
Connection To Telephone Network
The person responsible for connection of the DC58/58M to a PABX system is as follows:
l
If the wiring is owned by British Telecom PLC -
British Telecom
l
If the wiring is not owned by British Telecom, either:
(a) British Telecom (b) The authorised maintainer (c) A professional installer after 14 days written
notice to the authorised maintainer.
Overview
General
TheDC58/58M digital communicator consistsofa single PCB fitted in a small polycarbonate case. It is used to transfer fast format status information from an alarm system to a dedicated Alarm Receiving Centre (ARC) via the Public Switched Telephone Network (PSTN). The DC58M offers the same features asthe DC58 butit also functions as aV21 modem. TheDC58Mis required when using the up/downloading feature on compatible Menvier control panels.
Operating Modes
The DC58 can be used as a stand-alone communicator,in this mode the communicatoris hard-wired to the control panel using the appropriate terminal block connections. Alternatively the unit can be plugged on to a suitable Menvier controlpanel, suchas the TS510, TS700,TS790, TS900, TS2500 orTS2200.Whenused in this mode the communicator plugs on to the controlpanel using the lead supplied.TheDC58M can only be used in the plug-on mode.
4
Overview DC58/58M Installation Instructions
Plug-on Mode
Stand-alone Mode
(DC58 Only)
Terminal connections for other control panels
TS900 Remote Keypad
(Programmer)
TS900 Remote Keypad
(Programmer)
Plug-on to Menvier control panels
Figure 1 Operating Modes
Page 5
NVM Programming
All programmed data is stored in a plug-in NVM (Non-VolatileMemory)whichwill be retainedforup to five years with no power present. The NVM can be programmed by using a Menvier LCD Remote Keypad (P/No. TS900.REM) and an engineer's interfacelead(P/No.NETEKI) which willplugdirectly ontothe DC58/58M. Alternatively the NVMcanbe programmedusingthedesktop programmerPP5.
Your ARC will normally provide a programming service and will supply a pre-programmed NVM on request or alternatively fill in the programming form at theback of thismanual and return/fax it to Menvier Security (Repairs Dept.).
Technical Specifications
Supply: 11.5V - 14V; 35mA dc (Standby);
100mA dc (Active)
Theinstallermustensurethatpower drawn by the DC58/58M plus any other auxiliary apparatus is within theratingofthecontrolpanel(host) power supply.
Low Battery: Detection threshold is at 10.8V +/-
0.2V
Outputs: [1+]: Switched +ve @100mA
[2-]: Switched -ve @100mA
Ch 1 - 8: Maximum input voltage 28V.
Channel input trigger either +ve or
-ve applied (JP3)
Modem: 300/300 Baud (V21) Programmer: TS900 remote keypad & interface
lead or PP5.
Case Size: 142(w) x 82(h) x 36(d) mm. Weight 265g REN value: 0.0 BT Approval: DC58 - S/1100/3/R/503310
DC58M - S/1100/3/R/503311
Series Voltage Drop
The voltage drop introduce by the series connection through the DC58/58M at a line current of 40mA is 0.1V. When used with other apparatus (telephone, fax etc.) the total voltage drop @40mA MUST NOT exceed 2.0V.
Operation
General
When triggered, the DC58/58M seizes the PSTN line.Whenadialtone is detected,itteststhelineto determine if Loop Disconnect(Pulse) or Dual Tone Multiple Frequency (Tone) dialling is required. (If the dial tone is not detected within six seconds then Pulse dialling is automatically selected). The indicator (LED) is then illuminated. If the unit Pulse dialstheLEDwill flashasthenumbersare dialled.
1. The appropriate telephone number is dialled, when answered, thealarm receiver will send a I.D tone. If no I.D tone is received, the DC58/58M will releasethe line, andrepeat the process a maximum of three times to each selected telephone number.
2. If a Special Information Tone (SIT) is detected, the DC58/58M immediately aborts the call and tries again.
3. When the DC58/58M receives the ID tone it transmits the appropriate datain fast format.If the data is successfully received the alarm receiver responds with an acknowledgement tone. The DC58/58M releases the line and flashes the red LED 4 times.
4. If the acknowledgement tone is not received, the DC58/58M releases the line and tries again.
5. After the third dialling attempt has failed a line fault is signalled to the control panel to allow anyprogrammedbelldelay tobecancelled.
Special Information Tones (SIT)
These tones are sometimes encountered when the number dialled is not available or thenumber is incorrect. If the DC58/58M detects a SIT it will immediately abandon the call and try again.
5
DC58/58M Installation Instructions Operation
Page 6
Three-Way Calling
Thisisonethenewfeaturesthat is available from BT Network Services, for this feature to work correctly the telephone linemust have thisservice enabled (contact BT for further details).
When the DC58/58M is triggered the unit checks forincomingringing or off hook (someone tryingto block the call). The unit then sends a "Recall" signal, which is detected by the exchange as a requestforanewline. With anewlineavailablethe DC58/58M then attempts to connect with the ARC.
If the DC58/58M is connected to an older pulse dial only exchange, the numbers being dialled must be selected to "Pulse" dial, see "Telephone Numbers" on page 11. This will disable the three-waycallingfacilityas itisnotavailableonthe older type exchanges.
Line Fault Monitor
The line fault monitor continuously monitors the PSTN line and will detect:
l
The loss of line voltage (cut line)
l
Alinevoltageless than 35V(paralleltelephone off hook)
l
An incoming ringing signal that will try and prevent DC58/58M operation
If the DC58/58M is used on a shared line then the line fault monitor can be selected to only monitor a cut line by setting the "HI/LO SECURITY" option to "LO". It is also recommended that "Three-Way Calling" is used (see above) so that the security of the system is not compromised.
Temporary Out of Service
In addition tothe line fault monitor, theDC58/58M can be programmed to perform a moredetailed line test at pre-set intervals. The DC58/58M will seize the line and dial all digits but the last one of telephone number 1. If the unobtainable tone is NOT detected it is assumed that the line is healthy and the unit releases the line. If the unobtainable tone is detected, a line fault is signalled.
Point ID Extended Format
This is a new format which is used to send additional fast format data to the alarm receiver. The additional information can be used to indicatethecircuitthat caused thealarm,theuser thatset/unsetthesystemetc.FortheDC58/58Mto send this additional data, the unit must be plugged on to a Menvier control panel that supports "Point ID Extended Format"' and report to a compatible alarm receiver.
Modem (DC58M Only)
When a call is made to the alarm site the DC58M will pick up thecall and attemptto connect to the modemthat is connected totheP.C. If successful the communication link is established and data can be transferred. When the Modem is on-line the red LED on the DC58M flashes continuously untilthecommunicationlinkisbroken.Ifduringthe Modemoperationthecontrolpanelgenerates an alarm which is required to be transmitted to the ARC, the DC58M will suspend the Modem operation and attempt to communicate with the alarm receiver.
6
Operation DC58/58M Installation Instructions
Page 7
Installation
1 Output 2- (SELV)
Programmable switched -ve output rated @100mA.
2 Output 1+ (SELV)
Programmable switched +ve output rated @100mA.
3 Power Input (SELV)
12V power input, only use in stand-alone mode.
4 CH1 - CH8 (SELV)
Input channels 1 - 8, only use in stand-alone mode.
5 JP5
Input channel trigger polarity, stand-alone mode only. [+] = +ve applied (0v going to 12v) [-] = -ve applied (12v going to 0v)
6 LED 1
Activity LED. On whilst communicator is active. Flashes on and off 4 times when successfully communicated with the ARC. Flashes continuously when modem is in operation.
7 Test Call
Short these two pins to initiate a test call.
8 NVM
RemovableNon-VolatileMemoryused tostore all programmed data.
7
DC58/58M Installation Instructions Installation
CH1CH2CH3CH4CH5CH6CH7CH8
12V 0V
1+ O/P 2-
A
A1
B
B1
BC
NVM
TEST
JP5
Trig
Polarity
TS900
REMOTE
TO CONTROL
PANEL
JP2
JP1
HI/LO
SECURITY
12
1
2
3
4 5
6
10
7
8
9
11
Figure 2 DC58 PCB Layout
+
2-
1+
-
A
A1
B
B1
BC
NVM
TEST
TS900
REMOTE
TO CONTROL
PANEL
JP2
JP1
HI/LO
SECURITY
12
1
2
6
10
7
8
9
11
Figure 3 DC58M PCB Layout
Page 8
9 JP2 (SELV)
Connector for Menvier control panels.
10 JP1 (SELV)
Connector to TS900 remote keypad (Programmer).
11 Telephone Connections (TNV)
Terminal connections to the telephone line.
12 HI/LO SECURITY
Line fault monitoring level: Link fitted = High Security Link removed = Low Security
Plug-on Installation
1. Isolate ALL power from the control panel
(battery and mains).
2. Do not attempt to continue if the mains or battery supply is still present.
3. Remove the cover from the DC58/58M case andifappropriatefit apre-programmedNVM.
4. Connect the interface lead to the control panel connector (DIGI MODEM) via the cable entry hole in the base, then connect the lead onto JP2 on the DC58/58M (marked TO CONTROL PANEL).
5. Set the "HI/LO SECURITY" link to the appropriate setting.
6. Secure the DC58/58M base to the control panel base using the self-adhesive pads.
7. Refer to "Telephone Line Connections".
Stand-alone Installation (DC58 Only)
1. Isolate ALL power from the control panel
(battery and mains).
2. Do not attempt to continue if the mains or battery supply is still present.
3. Remove the cover from the DC58 case and if appropriate fit a pre-programmed NVM.
4. Connect theinputchannelstotheappropriate outputsonthecontrolpanelfeeding all cables through the cable entry hole in the base.
5. Ensure that "JP5" is set for the appropriate polarity.
6. Connect 12V and 0V to the control panel digicom supply, if aline fault outputis required use output 1 or 2 and program the output as line fault.
7. Set the "HI/LO SECURITY" link to the appropriate setting.
8. Secure the DC58 base to the control panel base using the self-adhesive pads.
9. Refer to "Telephone Line Connections".
Telephone Line Connections
1. Connection tothe telephone network mustbe
made via an NTE5 master socket (Line Box).
2. Using the cable type 1/0.5mm CW1308, strip back 5mm of the required cores and feed through the DC58/58M cable entry, see
Figure 4.
+
Keep all telephone cables at least 5mm away from other alarm cables.
8
Installation DC58/58M Installation Instructions
A
A1B1
B
BC
Cable Entry
Telephone cable Type 1/0.5mm CW1308
Telephone line to "series connected" telephone, Fax etc.
A = 5 - White/Blue ring B = 2 - Blue/White ring BC= 3 - Orange/White ring
3 2 1
6 5 4
Figure 4 Telephone Line Connections
Page 9
3. CW1308 cable is available from RS Components (Part No. 368-413). Alarm or any other type of cable must not be used.
4. Connect thethreecores to the terminalblocks marked A, B and BC.
5. Remove the two screws from the BT master jack socket and remove the bottom section from the master jack.
6. Connect thecable from A,B and BC terminals on the DC58/58M to the BT master jack terminals, see Figure 4.
7. A special insertion tool will be required to connect the cable to the master jack, this is available from RS Components (Part No. 470-487).
8. Replace the bottom section of the master jack socket and do up the two screws. Refer to "Testing" (see below).
TS900 Remote Keypad Connections
ToconvertastandardTS900remote keypad into a DC58/58M programmer the following is required:
TS900REM 32 character LCD remote keypad. NETEKI Networker Engineer's Keypad
Interface lead.
Testing
Once all the installation steps have completed, proceed as follows:
1. Ensure that you have informed the ARC that you will be sending test calls.
2. When used in the stand-alone mode, ensure that any unused reporting channels are linked to their healthy condition or re-programmed notto report, e.g., ifchannel4 is programmed to report but is not connected to the control panel, then link it to +12V if the trigger is set to
-ve or to 0V if the trigger is set to +ve.
3. Connect power to the control panel. If the DC58 is being used as a stand-alone, wait for approximately 10 seconds for the unit to automatically configure itself.
(a) If the NVM is un-programmed or fitted
incorrectly the red LED will flash rapidly.
(b) If the DC58/58M is to be programmed
using the TS900 remote keypad, plug it onto the connector labelled "TS900 REMOTE". Refer to "Programming" for further details.
(c) If at the end of the 10 seconds any input
channel is active the red LED will illuminated and the dialling sequence will commence.
4. Send a test call by momentarily shorting the "TESTCALL"pinstogether,see Figures 2 & 3. This will initiate a test transmission to the ARC.
+
The DC58/58M will not send a test call if there is a parallel hand-set off hook.
5. Trigger all the relevant channels by: (a) Setting and unsetting the control panel to
send open/close signals.
(b) Set the system and cause a full alarm to
send an intruder signal.
(c) Press any PA buttons to send a PA signal. (d) Activate any other devices that require
testing.
6. Unplug the TS900 remote keypad and secure the cover of the DC58/58M using the two screws supplied.
7. Finally replace and secure the cover on the control panel.
9
DC58/58M Installation Instructions Installation
Set I/D to "ENG"
NETEKI Lead
Pol.
TS900 Remote Keypad
Blue
White
Yellow
Black
Red
A B
C D E
O/P-
Figure 5 Engineer's Keypad Connections
Page 10
Programming
Programming Menu
10
Programming DC58/58M Installation Instructions
ENT
ENT
Enter Telephone No. 1
Press any key
= Clear number
A
ENT
= Pulse Dial (P) or Pause (-)
B
= Tone Dial (T)
C
Enter Telephone No. 2
ENT
ENT
Enter Telephone No.3
Enter account No.1
ENT
ENT
Enter account No. 2
Enter account No. 3
Select channels that report
to tel No.1 by pressing [1] - [8]
ENT
Select channels that report
to tel No.2 by pressing [1] - [8]
Select channels that report
to tel No.3 by pressing [1] - [8]
ENT
Select Set/Day (Open/Close) channels by pressing [1] - [8]
ENT ENT
Select Restore channels
by pressing [1] - [8]
ENT
= Consecutive = Alternative = All
1 2 3
= Will NOT Report = Limited Report = Full Report
1 2 3
Select dialling mode:
Select point ID reporting mode:
ENT
= Disabled = Daily = Weekly
1 2 3
= Disabled = Daily = Weekly
1 2 3
Select test call period:
Select Temporary Out of
Service monitoring period:
= Fortnightly
4
= Fortnightly
4
ENT
Select Invert channels
by pressing [1] - [8]
ENT
ENT
Select output type:
= Line Fault = Digi Successful = Digi Failed
1 2 3
= Digi Active
4
= Serial Coms Fault
5
ENT
Select output type:
= Line Fault = Digi Successful = Digi Failed
1 2 3
= Digi Active
4
= Serial Coms Fault
5
ENT
= Instant = Delayed
1 2
Select Ring Count
(DC58M Only):
Page 11
Telephone Numbers
Up to three telephone numbers can be programmed, each number can be up to 16 digits long. As part of the number, special codes can be inserted to allow for pulse dialling (P), tone dialling (T) and a 4 second pause (-) for PABX systems.
When the DC58/58M dials a telephone number it will automatically select the correct dialling format. However, the format can be forced if required.
Selecting Pulse Dialling
Pulse dialling is the older (slower) format and is sometimesreferred to asLoopDisconnect (LD). To force the number to be dialled in this formatpress [B] before entering the telephone number. The telephone number will be prefixed with a "P" to indicate pulse dialling.
Selecting Tone Dialling
Tone dialling is the modern format and is sometimes referred to as Multiple Frequency (MF) or Dual Tone Multiple Frequency (DTMF). To force the number to be dialled in this format press [C] before entering the telephone number. The telephone number will be prefixed with a "T" to indicate tone dialling.
Inserting a Pause for PABX's
If the DC58/58M is connected to an internal PABX telephone exchange system, normally the exchange requires a pre-fixed digit to be dialled before obtaining an outside line (normally 9). Some exchanges also require a pause after the pre-fixed digit before dialling the telephone number. To insert a 4 second pause, enter the PABX digit (normally 9) then press the [B] key the display will show "9-". Now enter the telephone number.
+
Whenprogramming telephone numbers it is very important check that they have been entered correctly otherwise the DC58/58M could dial a private number inadvertently.
Account Numbers
This is a 4 digit number that the alarm receiving centre uses to identify the alarm site. Up to three accountnumberscanbeprogrammed.Account numbers can only be programmed if the corresponding telephone number is programmedi.e.,if"TelephoneNo.2"isblankthen the option to program "Account No.2" is not available.
Reporting Channels
Each channel can be programmed to report to any combination of telephone numbers. For example channel 1 can be programmed to reporttoalltelephonenumbers,whereaschannel 3canbeprogrammed to onlyreporttotelephone number 1. Reporting channels can only be programmed if the corresponding telephone numberis programmed i.e., if"TelephoneNo. 2" is blankthentheoptiontoprogram"REPORTSTONO. 2" is not available.
Set/Day Channels
Any channel can be programmed as a '"Set/Day" channel, this type of channel will report a "Close" signal when the input channel is active and an "Open" signal when the input channel is restored. Normally channel 4 is used to report an "Open/Close" signal, but if required this can be changed.
Restore Channels
Any channel can be programmed as a "Restore" channel, this type of channel will report a "Alarm" signal when the input channel is active and a "Restore"signalwhentheinputchannel is restored. Ifachannelisprogrammedwithout"Restore",only the "Alarm" signal will be transmitted.
+
If any channel is programmed as "Set/Day", its channel willautomatically be programmed as "Restore".
11
DC58/58M Installation Instructions Programming
Page 12
Invert Channels
When the DC58/58M is used in the stand-alone modeitis possible to invert thesignalforanyof the input channels. An inverted channel will report a "Restore"signal when the inputchannel is inalarm and an "Alarm" signal when the input channel is restored.
Dialling Modes
The DC58/58M can be programmed for the following Dialling Modes:
Consecutive
In this mode the DC58/58M will dial the first telephone number and attempt to report the alarm signal. If the attempt fails, it will shut down and re-dial the first telephone number. If the second attempt fails, it will shut down for 1 minute then re-dial the first telephone number again. If the third attempt fails the the unit shuts down and now attempts the secondtelephone number. This sequence continues until all three attempts to each telephone number have been used, after which the unit will shut down completely.
Alternative
In this mode the DC58/58M will dial the first telephone number and attempt to report the alarm signal. If the attempt fails, it will shut down and dial the second telephone number. If the second attempt fails, it will shutdown anddial the third number. This sequence continues until all three attempts to each telephone number have been used, after which the unit will shut down completely.
All
In this mode theDC58/58M will dialconsecutively, but also requires a successful communication from all alarm receivers.
Test Call Period
The DC58/58M can be programmed to periodically send a "Test" signal (Code 9) to the Alarm Receiving Centre.
Digicom Outputs
The DC58/58M has two programmable outputs, [1+] is a switched +ve output and [2-] is a switched -ve output. Both outputs are rated at 100mA and can be programmed to one of the following types:
1 Line Fault
Activates the output when the unit detects a telephoneLinefaultwhichincludescutline,off hook and incoming ringing.These types ofline fault condition will clear when the telephone line is restored to its normal condition (after 30 seconds).
The output also activates after the third failed attempt to the ARC and will clear when the next attempt to the ARC is successful. The Temporary Out of Service test will also cause the output to activate if the test fails after the thirdattemptandwillclear when thetestorany other communication is successful.
+
If the "HI/LO SECURITY'"link is set to "LO", the monitoring of the telephone line is reduced to line cut only.
2 Digi Successful
Activates for 1 minute when the communication to the ARC is successful.
3 Digi Failed
Activates after the third failed attempt to the ARC station and will clear when the next attempt to a central station is successful.
4 Digi Active
Activates when the digicom is active.
5 Serial Coms Fault
Activates when the serial communication between the DC58/58M and control panel fails (plug-on mode). The output clears when the communication link is re-established.
12
Programming DC58/58M Installation Instructions
Page 13
Point ID Extended Format
WhentheDC58/58Misused in the "plug-onmode" (i.e., connected to a Menvier control panel) it is possible to send additional alarm information to theARC,thiscanincludecircuitand user ID. For full details on the extended information refer to the relevant control panel "Installation Manual".
+
This feature is only supported by relevant Menvier control panels, for details on which control panels support this feature contact Menvier Technical Support.
PointIDcanbeset to one ofthefollowingreporting options:
1 Will NOT Report
This disables "Point ID Extended Format" and the DC58/58M will only report "Fast Format" data to the alarm receiver.
2 Limited Report
When "Limited Report" is selected the DC58/58Mwillonlyreport the extended format data relating to the channel that is triggered. For example, if the DC58/58M is programmed to report channels 2 and 3 (PA and Intruder) then the unit will only report events relating to PA and Intruder activations.
3 Full Report
When "Full Report" is selected the DC58/58M will report all extended format data to the alarm receiver irrespective of the channels that are programmed to report. That is, if all eight channels are programmed as non reporting,the unit will still reportalleventsto the ARC.
Temporary Out of Service
This feature is used to test the integrity of the telephonelinebydialling all but the last digit ofthe first telephone number.If the unobtainabletone is NOT detected itis assumed that the lineis in good working order, however,if anunobtainable tone is detected the DC58/58M will signal a line fault condition.
Ring Count (DC58M Only)
The DC58M Ring Count can be programmed for one of the following options:
1 Instant
The DC58M will answer any incoming calls immediately.
2 Delayed
The DC58M will answer any incoming calls after approximately 30 seconds.
+
Some Menvier control panels allow the ring count to be performed by the control panel. If the control panel has a ring count option then set the DC58M to "Instant" and program the panel ring count to the required amount.
Page 14
Monitor Mode
Introduction
When the TS900 remote keypad is left plugged on to the DC58/58M it will act as a monitor, so that during testing to the ARC the display will show the communicator's status.
Transmitted Data Specification
The data transmitted to the alarm receiver is industry standard fast format. The data contains the following information:
Account No This isa4digitnumberandisunique
to the installation site.
Channel 1-8 Each channel can report its own
status code: Code 1 = New Alarm Code 2 = System Opened Code 3 = Channel Restored Code 4 = System Closed Code 5 = Healthy Channel Code6=Previously reportedevent
Channel 9 This channel is normally referred to
as the statuschannel and isused to report the following:
Code 7 = Normal Code 8 = Low Battery Code 9 = Test
Typical Test Call
Whenthe"TESTCALL"pinsaremomentarily shorted the DC58/58M will send a test call to all programmed telephone numbers. The display should show:
Other Monitor Messages
The following monitor messages may also be displayed:
14
Monitor Mode DC58/58M Installation Instructions
No dial tone detected when the DC58 went on line.
The number was dialled but an unobtainable tone was detected.
The alarm receiver is engaged.
The number was dialled but a "Special Information Tone" was detected.
No reply from the alarm receiver.
The "Temporary Out of Service" test call was successful.
The DC58 sent its data to the alarm receiver, but the receiver failed to give an acknowledgement tone (corrupted data).
Dialling the first telephone No.
Waiting for the alarm receiver to answer the call and send its identenifation tone (I.D).
The alarm reciever is on line and the DC58 is sending its data.
The data send is displayed.
This is repeated for all
programmed telephone
numbers
The data was accepted and the alarm reciever has sent its acknowledgemnt tone.
Page 15
NVM Programming Form
15
DC58/58M Installation Instructions Monitor Mode
Telephone No. 1 Telephone No. 2 Telephone No. 3
Account No. 1 Account No. 2 Account No. 3
Channel No. 1 2 3 4 5 6 7 8 Reports to No. 1 Reports to No. 2
Report to No. 3
Set/Day Channels
Restore Channels
Invert Channels
Dialling Mode Consecutive: o Alternative: o All: o
Test Call Period Disabled: o Daily: o Weekly: o Fortnightly: o
Output 1 (+ve)
Line Fault: o Digi Success: o Digi Failed: o Digi Active: o
Serial Coms Fault: o
Output 2 (-ve)
Line Fault: o Digi Success: o Digi Failed: o Digi Active: o
Serial Coms Fault: o
Extended Format Will NOT Report: o Limited Report: o Full Report: o
T.O.S Monitoring Disabled: o Daily: o Weekly: o Fortnightly: o
Ring Count Instant: o Delayed: o
Page 16
18307 Drg No. 33:1639:00 Issue 05 Doc 01. March 1997
MENVIER
SECURITY
Menvier Security Ltd. Kenn Road, Clevedon, Bristol BS21 6LH Tel: 01275 870078; Fax: 01275 343453
Loading...