Mendota DT3-PF2-LX, DXV-45 DT4 - LX Instructions Manual

Page 1
GAS DIRECT VENT FIREPLACE
with Premium Fiber Log Set Combustion System
Model DXV-45 DT3-PF2- LX
INSTALLATION & OPERATING INSTRUCTIONS
NO. DXV45-DT3-LX-PF2-0113
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
mable vapors away.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
Do NOT use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
les instructions dans la présente notice risque de dé­clencher un incendie ou une explosion entraînant des dommages, des blessures ou la mort.
ATTENTION. Garder l’essence ou autres liquides produi­sant des vapeurs inflammables loin del’appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
Ne pas tenter d’allumer d’appareil.
Ne touchez à aucun interrupteur; ne pas vous servir
des téléphones se trouvant dans le bâtiment.
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur, appelez
le service des incendies.
même partiellement. Faites inspecter l’appareil par un technicien qualifiéet remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation consult a qualified installer, service agency or the gas supplier.
cation, une réparation ou un entretien mal effectué peut cau­ser des dommages matériels ou des blessures. Voir la notice de l'utilisateur quiaccompgne l’appareil. Pour de l’aide oueds renseignements supplémentaires, consultez un installateur, un technicien agréé ou le fournisseur de gaz.
Page 2
Installer l'appareil selon les codes ou règlements
Fuel Gas Code ou CAN/CGA-B149 en vigueur.
Cet appareil doit être utilisé uniquement avec le
This appliance must be installed in accordance
Propane Installation Code, CSA B149.1
This appliance is only for use with the type(s) of
CAUTION
improper and dangerous operation.
Attention. Au moment de l’entretiennes com-
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING Do not operate this appliance with the glass re­moved, cracked or broken. A licensed or quali­fied person should do replacement of glass.
with local codes, if any; if none, follow the Nation­al Fuel Gas Code, ANSI Z223.1, or Canadian Installation Codes, CAN/CGA-B149. Gas and
gas indicated on the rating plate and may be in­stalled in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. See owner's manual for details. This appliance is supplied with a conversion kit.
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
Attention. Ne pas utiliser l’appareil si le panneau frontal en verre n’est pas enplace, est craqué ou brisé. Confiez leremplacement du panneau à untechnicien agréé.
locaux, ou, en l'absence dételés règlements, se­lon les codes d'installation ANSI Z223.1, National
type de gaz indiqué sur la plaque signalétique. Cet appareil peut être installé dans une maison préfabriquée ou mobile (É.-U. seulement) instal­lée à demeure si les règlements locaux le per­mettent. Voir la notice de l'utilisateur pour plus de renseignements. Cet appareil ne peut pas être utilisé avecd'autres gaz sauf si une trousse de­conversion certifiée est fournie.
In the Commonwealth of Massachusetts:
Installation must be performed by a licensed plumber or gas fitter;
A CO detector shall be installed in the room where the appliance is installed.
THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER.
mandes, étiquetez tous les fil savant de les dé­brancher. Des erreurs decâblage peuvent entraîner unfonctionnement inadéquat etdangereux.
1
Page 3
DXV45 DT3 FEATURES - QUICK REFERENCE INFORMATI ON
EXTERNAL DIMENSIONS: 40-3/8” Wide X 39” High X 19-1/8” Deep MINIMUM FRAMING DIMENSIONS: 41” WIDE x 38-1/8” HIGH X 20” DEEP GLASS SIZE: NeoCeram Glass with non-reflective coating. Visible Glass measures 707.5 in
2
.
in
MANTEL ALLOWANCE: 8” Deep Mantel at 14” Above Top Convection Opening VENT SYSTEM ALLOWANCE: Top Vent Only. 0” Vertical 24” max horizontal. 55 feet Vertical Maximum. 5” exhaust and
8” combustion air intake coaxial vent pipe required. 12’ maximum horizontal run allowed with 4’ minimum vertical starter section.
VENT DAMPER ADJUSTMENT AVAILABLE: There is one exhaust vent damper included in this unit and located in the top convection chamber at the center.
CONTROLS: IPI Electronic Ignition System with AC Primary Power and DC Backup Power. Accent light and Blowers op­erate on AC Power only. Thermostatic Remote Control Transmitter with Smart Thermostat Mode.
BLOWER SYSTEM: 210 CFM Dual Blower System. 120VAC, 2Amps. Dedicated Hot Power only. No switches, Fan Speed Controls or Light Dimmers are allowed in same circuit. Blower speeds can be varied from Remote Control. Fan cannot be turned completely off.
Accent Light System: Accent Light System Included. Light can be turned on or off or dimmed using dimmer mounted behind lower grill. Accent Light can also be turned on or off and dimmed using Remote Control Transmitter.
2
. Actual Glass size is 840
BURNER SYSTEM: Dual 304 Stainless Steel Tubular burners. BURNER AIR SHUTTER SYSTEMS: Externally controllable Rear Burner air shutter and Internal rotary Front Burner air
shutter.
LOG SET: 10-piece, Premium Fiber Log Set with Real- Glow effects and Real ember bed. REFRACTORY PANELS: High Detail Red Clinker Soldier Course Fiber Brick Panels included. Brick Panels required for
operation. NATURAL GAS INFORMATION: Factory equipped for Natural Gas. 4.5”WC Minimum inlet pressure required. For NG
applications, Front Burner Orifice Size is #44 and the Rear Burner Orifice Size is #38. LPG INFORMATION: An LP conversion kit is required to burn LPG in this appliance. Use kit #HA-42-00302 to convert
this appliance to burn LPG. 12”WC Minimum inlet pressure required. For the DXV45 DT3 LPG application, Front and
Rear orifices are to be #53 (Rear) and 3/64” (Front). For higher altitude, adjustment to orifice size may be necessary.
INITIAL STARTUP ADVICE
PAINT CURING CYCLE RECOMMENDATION: It is recommended that you run this Fireplace on maximum flame height,
for 3 cycles of 2 hours ON and 2 hours OFF, initially, to cure the paint. Some non-toxic smoking will be visible during the cure cycles. It is recommended that all windows be opened during the first 2-hour burn cycle to expel the visible smoke.
BLOWER BREAK-IN PERIOD: The integrated blowers in this Insert may exhibit some bearing noise and electrical static noise during the first few days of operation. This is normal during the break-in period. It is recommended that following the Paint Curing Cycle, the blowers be run at their maximum speed for two 3-hour periods. The burner flames must be on dur­ing these cycles. The blowers in a few fireplaces may take longer to break-in and may require additional operation time before all extraneous noise is eliminated. Please allow adequate operational time for the blowers to break-in before you contact your dealer for service.
2
Page 4
Contents
FOR YOUR SAFETY READ BEFORE LIGHTING 1 DXV45 DT3 FEATURES - QUICK REFERENCE INFORMATION 2 INITIAL STARTUP ADVICE 2 CONTENTS 3 SPECIFICATIONS 4 BUILDING PERMIT AND INSTALLATION INSPECTION APPROVAL REQUIREMENTS 4 LOCATING THE FIREPLACE AND GENERAL INFORMATION 6 HEATING PERFORMANCE 7 ELECTRICAL REQUIREMENTS: 7 DXV-45 GAS DIRECT VENT FIREPLACE 8 INSTALLATION INSTRUCTIONS 9 GAS SUPPLY REQUIREMENTS 11 GAS PRESSURE REQUIREMENTS 12 EXTERIOR VENT LOCATIONS AND RESTRICTIONS 13 FLUE VENTING INSTRUCTIONS 14 FLUE VENTING REQUIREMENTS FOR NG AND LPG 15 MENDOTA DESIGNER FRONTS INSTALLATION INFORMATION 22 DOOR REMOVAL AND REPLACEMENT 24 GLASS FRAME ASSEMBLY REPAIR AND REPLACEMENT 25 TO REPLACE DAMAGED GLASS 25 DXV45 COAL BED AND LOGS INSTALLATION 26 COMPLETED LOGS AND COAL BED ASSEMBLY EVALUATION 32 INSTALLATION CHECK OFF LIST 33 LIGHTING CHECK OFF LIST 33 BEFORE YOU BEGIN 34 REMOTE TRANSMITTER OPERATING INSTRUCTIONS 35 INITIALIZING THE REMOTE CONTROL SYSTEM 37 IPI/STANDING PILOT SYSTEM INFORMATION 38 BACKUP BATTERIES 39 OPERATING DURING POWER OUTAGES 39 BLOWER OPERATION AND WIRING 40 TROUBLESHOOTING MENDOTA GAS DXV FIREPLACE 41 CUSTOMER INFORMATION AND TROUBLE-SHOOTING 42 MAINTENANCE 43 WIRING SCHEMATICS 44 NATURAL TO LP GAS CONVERSION INSTRUCTIONS 45 INSTALLING THE LP PRESSURE REGULATOR 48 LP GAS PRESSURE REQUIREMENTS 49 CHECKING FOR NORMAL BURNER(S) IGNITION CHARACTERISTICS 49 REPLACEMENT PARTS 50 LISTING LABEL, RATING PLATE REPSENTATION 51 MENDOTA WARRANTY QUALIFICATION & SERVICE REFERENCE FORM 53 MENDOTA EXTENDED PROTECTION AND LIMITED WARRANTY 55
3
Page 5
HIGH ALTITUDE INSTALLATION INFORMATION
SPECIFICATIONS
MENDOTA, MODEL DXV-45
High Fire - Adjustable to - Low Fire
BTUH. (MODEL DXV-45) NAT. GAS 45,000 7,500 BTUH. (MODEL DXV-45) L.P. GAS 40,000 5,000
NOTE: LP CONVERSION KIT #HA-42-00225 OR AA-11-01257 MUST BE PURCHASED SEPARATELY FOR THE DXV­45 FIREPLACE TO BURN LPG.
MAIN ORIFICE: REAR BURNER #38 NAT. GAS-#53 L.P. GAS – FRONT BURNER #44 NAT. - #3/64 LP OVERALL EFFICIENCY EXCEEDS D.O.E. EFFICIENCY REQUIREMENTS (A.F.U.E.) FOR DIRECT VENT
WALL HEATERS
CO-AXIAL DIRECT VENT FLUE 5" INNER, 8" OUTER TOTAL WEIGHT 205 POUNDS SAFETY AGA CERTIFIED IPI PILOT SAFETY SYSTEM, ACTIVATED WITH SWITCH, THERMOSTAT
OR REMOTE CONTROL.
GAS REQUIREMENTS SUPPLY PRESSURE: GAS INLET: 3/8" N.P.T.
NAT. GAS: 7" W.C. (5" W.C. MIN., 11" W.C. MAX.) L.P. GAS: 12.0" W.C. (12" W.C. MIN., 14" W.C. MAX.) ELECTRICAL REQUIREMENTS 120 VOLT ON LEFT OR RIGHT SIDE OF APPLIANCE. CONNECT TO ONLY
ONE OF THE TWO SERVICE OUTLET BOXES INSTALLED IN THIS APPLIANCE. USE EITHER RIGHT SIDE OR LEFT SIDE SERVICE OUTLET BOX CONNECTION.
APPROVED VENT SYSTEMS: AMERIVENT, DURAVENT, SELKIRK METALBESTOS, SECURITY CHIMNEY Certified under ANSI Z21.88-2005•CSA 2-33-2005 and CAN/CGA 2.17 M91. DXV-45 is also deemed in compliance with
ANSI Z21.50•CSA 2.22 2000“Vented Gas Fireplace Heaters" not for use with solid fuel. Approved for bedroom installa­tions and mobile homes. UL307B approved for "mobile homes, after first sale of home, not for recreational vehicles." “Gas-fired appliances for use at high altitudes.”
: Prior to installing at altitudes higher than 7500, please con-
tact the Mendota technical service department for specific venting requirements and venting restrictions.
Building Permit and Installation Inspection Approval Requirements
All installations of Mendota Fireplaces and Inserts must comply with all
the requirements stated in this Installation and Operating Instructions Manual. The Dealer and/or installer must also obtain all required Building Permits and Inspection Approval from the local building inspection de­partment or the local body having jurisdiction. In or der t o validate warran­ty coverage, Mendota may require facsimile copies of the Building Permit and Inspection Approval forms. Failure to provide adequate proof that
the installation conforms to all local requirements and the requirements stated in the Installation and Operating Instructions Manual will void all applicable warranty.
INSTALLER: THESE INSTRUCTIONS ARE TO REMAIN WITH HOMEOWNER
4
Page 6
CONGRATULATIONS!
You are the owner of a world class, heat producing, gas, direct vent, sealed combustion fireplace. This elegant, highly efficient Fireplace will be a constant source of comfort and fascination. It will be the focal point of
beauty and interest in your home. The Mendota Gas Fireplace is a true heating appliance incorporating the traditional aesthetics of fireplace fire viewing with
the controllability and fuel efficiency of a home gas furnace. Of particular interest is the low fuel consumption and brilliant fire viewing afforded by the realistic, Deep Timber, wood fire-like combustion system.
Carefully read the following instructions prior to actual installation. Proper Mendota Gas Fireplace installation and opera­tion will give you years of safe trouble free comfort and enjoyment.
If you have any questions regarding installation or operation of your Mendota Fireplace please contact your local dealer.
......CAUTION.....
FOR YOUR SAFETY do not install or operate your Mendota Gas Fireplace without first reading and understanding this manual. Any installation or operational deviation from this manual voids the Mendota Gas Fireplace Warranty and may prove hazardous!
Due to high temperatures, the Fireplace should be located out of traffic and away from furniture and draperies. Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition. Young children should be carefully supervised when they are in the same room as the Mendota Gas Fireplace.
Clothing or other flammable material should not be placed on or near the Fireplace. The Mendota Gas Fireplace is a powerful, efficient heating unit. It has been designed as a major source of supplemental
heat. As with any mechanical appliance there can be component shut downs. It is advisable to have an alternate heat supply.
Installation, repair and any adjustments to logs or burner must be done by a qualified service person. The Fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, carbon build-up, etc. It is imperative that control compart­ments, burners and circulating air passageways of the appliance be kept clean. The burner and pilot flames and logs should be visually checked periodically.
DO NOT use this Fireplace if any part has been under water or exposed to moisture corrosion. Immediately call a quali­fied service technician to inspect the Fireplace and replace any part of the control system and any gas control, which has been under water. DO NOT use this fireplace if the burner does not light immediately. Turn unit off and call Mendota ap­proved service person if there is any delay in burner light off.
It is Johnson Gas Appliance Company's policy that no responsibility is assumed by the Company or by any of its employ­ees or representatives for any damages caused by an inoperable, inadequate, or unsafe condition which is the result, ei­ther directly or indirectly, of any improper operation, installation or servicing procedures.
Building Permit and Installation Inspection Approval Requirements
All installations of Mendota Fireplaces and Inserts must comply with all the requirements stated in this Installation and Op­erating Instructions Manual. The Dealer and/or installer must also obtain all required Building Permits and Inspection Ap­proval from the local building inspection department or the local body having jurisdiction. In order to validate warranty coverage, Mendota may require facsimile copies of the Building Permit and Inspection Approval forms. Failure to provide adequate proof that the installation conforms to all local requirements and the requirements stated in the Installation and Operating Instructions Manual will void all applicable warranty.
5
Page 7
LOCATING THE FIREPLACE AND GENERAL INFORMATION
Your Mendota Gas Fireplace has a state-of-the-art co-axial direct vent, sealed combustion system. This advanced, highly efficient system brings in outside air for combustion, has a separate exhaust vent and efficiently heats and re-circulates room air. The Mendota system maintains high air quality, maximizes efficiency and assures proper operation.
SAFETY AND STRUCTURAL CONCERNS:
The DXV Fireplace must be installed and serviced by a Mendota approved service person. Any adjustments to burner, pilot, logs or coal bed must be made by a Mendota approved service person. Pilot flame must be checked with voltmeter. Pilot flame must register a minimum of 250 on mill volt meter. If pilot goes out always wait five (5) minutes before relight­ing pilot. Always remove the glass door when lighting the pilot. The burner must light immediately & the flame must travel promptly and smoothly around "curve" and light entire burner. The flame must not "lift off" burner. All vent pipe sections must be "twist locked" and leak proof.
The Mendota Direct Vent Fireplace may be placed within inches of adjacent sidewalls. (See FIGURE 1 on pg. 8). The fireplace may be placed directly on concrete or wood flooring. If the appliance is to be installed on carpeting, vinyl or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance. Combustible mantels must be installed as per FIGURE 1 on pg. 4. Non-combustible (marble, brick, stone, etc.) mantels or mantels with steel protector plate on underside maybe installed at any desired height above upper grill.
NEVER BLOCK OFF UPPER OR LOWER GRILLS. ALWAYS USE MENDOTA GRILLS, MENDOTA APPROVED VENT SYSTEMS AND MENDOTA APPROVED VENT CAPS. SEE PAGEA 8-15 FOR SPECIFIC VENTING INFORMATION.
KEEP ELECTRONIC APPLIANCES AWAY: DUE TO THE HIGH TEMPERATURES IN THE VICINITY OF THIS FIREPLACE, MENDOTA RECOMMENDS THAT ALL ELECTRONIC APPLIANCES INCLUDING AUDI O/VIDEO APPLIANCES AND THEIR RECORDING MEDIA (ie. TV, VCR, DVD PLAYER, CD PLAYER, TUNERS, TELEPHONES, CASSETTE TAPES, VIDEO TAPES, CDs, DVD CDs) BE KEPT WELL AWAY FROM THIS FIREPLACE.
VENTING REQUIREMENTS: Use only Mendota specified vents and vent caps when installing your fireplace. Closely follow venting locations, directions
and requirements (see pages 10-17). Observe the restrictions relating to vent position on exterior of home (see pg. 10).
6
Page 8
HEATING PERFORMANCE
Mendota Gas Built-in Fireplaces are true, high efficiency gas heaters. With its high heat output the Mendota Fireplace will heat a large area of your home if situated to maximize heat circulation. Air movement options for maximizing heat circula­tion which can be considered are through-the-wall grills or floor grills, the continuous operation of central heating furnace blowers, or ceiling fan. The most efficient method for overall heat distribution is a ceiling fan. The heat output of the Fireplace can be reduced down to 22,500 BTUH by slowly turning the Hi/Lo temperature knob on the gas valve counter clockwise from "Hi" to "Lo". Further reduction of heat output, down to 7,500 BTUH, can be achieved by turning off the rear burner using the switch provided behind the lower grill. The blower can also be turned down to reduce heat output.
AESTHETIC CONSIDERATIONS: Burning or static fireplaces are a major aesthetic focus in any room. Locate your gas fireplace as you would a television
set. The Mendota Hearth Gas Fireplace will be a continuing source of comfort and fascination. Corner installations will afford you the greatest potential for viewing in many rooms.
HEARTH PROTECTION REQUIREMENTS: A non-combustible hearth protector is required and must extend a minimum of 14" in front of the fireplace (see Figure 1 on pg. 4 for raised hearths). We suggest installing the Mendota Fireplace 6 to 12 inches above the floor by utilizing an elevated hearth.
CAUTION: If you intend to install either the Andover Door Front or the Prairie Door Front on this fireplace, make certain that the top surface of the hearth protector is flush with the bottom surface of the fireplace, no higher. Failure to follow this guideline will prevent proper mounting and function of these two Fronts. See Page 16 for specific details.
ELECTRICAL REQUIREMENTS:
A blower kit is supplied as standard equipment on your Mendota Direct Vent Fireplace; A 120 volt electrical service must be supplied at the fireplace location at the time of installation. It must be electrically grounded in accordance with local codes or in their absence with current edition of the National Electric Code ANSI/NFPA 70. Power supply to blower must be continuous. DO NOT use a switch or variable control in power supplied to fireplace. Connect this 120 VAC supply line to e left side. CONNECT 120 VAC TO ONLY THE JUNCTION BOX INSTALLED ON THE LEFT SIDE OF THIS APPLIANCE.
The blower kit in this appliance is equipped with a three-prong plug for protection against shock hazard and should be plugged directly into the grounded three-prong receptacle provided with the fireplace. Do not cut or remove the ground-
ing prong from the plug. NOTE: The blower output can be adjusted with the remote control transmitter. There will be delays in blower operation
during "heat-up" (approx. ½ hr.) and extended blower operation during "cool-down" (approx. ½ hr.) of unit . Wall Thermostats are NOT recommended for this appliance. A Thermostatic Remote Transmitter is supplied with this
appliance. Consult your dealer or the Mendota Service Department if you wish otherwise.
7
Page 9
HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-
51 7/16
51 7/16
DXV-45 GAS DIRECT VENT FIREPLACE
SPECIFICATIONS & CLEARANCES
DIRECT VENT COAXIAL PIPE SIZE: 5" I.D. X 8" O.D.
FIGURE 1: Specifications & Clearances
tact the Mendota technical service department for specific venting requirements and venting restrictions.
8
Page 10
INSTALLATION INSTRUCTIONS
CAUTION: Each installation must conform to all local, state and national codes. Refer to the national fuel gas code and
local zoning and code authorities for details on installation requirements. The Mendota Fireplace must be vented to the outside in accordance with the latest edition of the National Fuel Gas Code. In the absence of local codes, the installation must conform to the most current edition of the National Fuel Gas Code ANSI Z223.1, also known as NFPA 54. NOTE: The Mendota DXV Fireplace is approved for mobile home and bedroom installations.
CAUTION: The Mendota DXV Fireplace may be installed in a manufactured (mobile) homes after the first sale of the home. Manufactured home (mobile home) installation must conform with the Manufactured Home Construction and Safe­ty Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI A225.1/NFPA 501A, or CSA Z240.4-Gas Equipped Mobile Housing. Consult your local building official. Note: For mobile home installations unit must be bolted to the floor and properly grounded.
1. After selection of the desired fireplace location, prepare the rough opening using framing dimensions on page 4. Prepare opening to allow for co-axial vent (see "Flue Venting Instructions" on pgs. 13-21).
2. Check to make certain all venting requirements and locations are being followed. (See pg 13 -21).
3. The Fireplace is designed to be installed into rough framing. The drywall will cover the adjustable nailing flanges on the Fireplace sides. Before sliding the Fireplace into the framed opening, adjust the nailing flanges to accom­modate the thickness of the wall material. NOTE: FRAMING MATERIAL ABOVE FIREPLACE MUST MAINTAIN CORRECT CLEARANCES TO VENT PIPE.
4. Slide Fireplace into the rough fram ed opening. When finishing the unit, combustible materials may overlay nailing flanges and com e in contact with the side edges of the black front surface, but may not overlay the 2" black surface. A 40-1/8” x 4” T op Screw Strip (par t #HA-41-00015) is supplied with the fireplace and must be installed on the top of this fireplace. The Top Screw Strip provides a 4” clearance to combustible materials at the t op of the fireplace. See Pag e 8 for specific details.
5. Combustible wall covering materials may only be installed down to the top flat edge of the Top Screw Strip. Noncombustible boards such as “Dura-Rock” or “ wonder board” can be installed on top of t he face of the Top Screw Str ip and on top of the r est of the black face of the fireplace. Noncombustible material, such as m arble or br ick , can be installed over the 2" black surf ace up t o the inside edges of black frame only if some Designer Fr onts are to be installed. See Page 23 for spec ific details and exceptions. Rough framing can com e no closer t o unit than the stand-offs.
6. Level the Fireplace and secure into opening by nailing throug h the nailing flanges on cabinet side panels. Holes are provided in fireplace floor behind grill to lag screw fireplace to floor, if required. NOTE: A removable panel in the enclosure for f uture visual inspection of the flue connection is recommended
7. Have an electrician install a 120 Volt supply to the junction box on lower left side of the fireplace cabinet. Connect wires to the duplex outlet. This duplex outlet is removable from outside of cabinet for easy wiring. Make sure the outlet is properly grounded and that the installation conforms to all local and national wiring codes. See "Blower Operation" below, Blower Wiring Diagram and "Electrical Requirements".
8. Have gas supplier or qualified plumber install gas supply line to fir eplace and connect to gas nipple. Be sure gas and plumbing instructions and all local and national codes are c arefully followed. Care­fully check for gas leak s and for proper gas pressure.
IMPORTANT: Any safety screen, guard, glass, grill, pressure relief cap, etc. removed for servicing a fireplace/room heater must be replaced prior to operating the fireplace/room heater.
BLOWER OPERATION
The Mendota DXV Fireplace is designed so the blower operates continually when main burner is on. The blower output can be regulated with the Remote Control Transmitter but the blowers cannot be turned off when this fireplace is hot. NOTE: There will be a time delay in blower operation during "heat-up" (approx. 10 min.) and extended blower operation during "cool-down" of unit. (Approx. 1/2 hour).
OPERATION DURING POWER OUTAGES: This fireplace is designed to operate for a maximum 1-1/2 continuous hours during power outages on HIGH FIRE. The blower will not operate, but natural convection can be improved by re­moving the upper Millennia grills, opening the Andover and Prairie Doors and opening the Wellington Screens. If burned on LOW FIRE (front burner only), this appliance may be run continuously indefinitely during power outages.
9
Page 11
10
Page 12
GAS SUPPLY REQUIREMENTS
Correct gas pressure and proper gas supply line sizing is imperative to the successful performance of your Mendota gas fireplace. Be sure the gas supplier or plumber carefully checks for correct gas pressure and gas line sizing when installing the fireplace.
It is critical to carefully check for gas leaks when hooking up the fireplace -- check with soap & water solution. Be sure to install "approved" flex gas line with brass-to-brass fittings to prevent gas leaks at connections. Gas supply piping must include a drip leg to eliminate the possibility of contaminants entering the gas train.
Adhere strictly to local and national codes for entire installation.
GAS SUPPLY LINE SIZING
The Mendota Gas Fireplace comes equipped with a 12” flexible connector kit including a manual shutoff ball valve. Gas supply piping must enter the Fireplace cabinet from the right side.
The included manual shut-off valve meets Federal Codes. I required by local codes, install an additional manual shutoff valve upstream of the fireplace’s manual shutoff valve. The appliance and its individual shut-off valve must be discon­nected from the gas supply piping system during any pressure testing of that system at test pressures in excess (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
1/2 PSIG (3.5 kPa).
A proper gas line diameter must be selected to run from the supply regulator to the Fireplace. Refer to the following table for proper gas pipe diameters. Strictly adhere to the correct pipe sizes. If in doubt, use the next larger size.
PIPE LENGTH
(FEET)
NAT. L.P. NAT. L.P.
0-10 1/2" (1.3 cm) 3/8" (1.0 cm) 1/2" (1.3 cm) 3/8" (1.0 cm)
10-40 1/2" (1.3 cm) 1/2" (1.3 cm) 5/8" (1.6 cm) 1/2" (1.3 cm)
40-100 1/2" (1.3 cm) 1/2" (1.3 cm) 3/4" (2.0 cm) 1/2" (1.3 cm) 100-150 3/4" (2.0 cm) 1/2" (1.3 cm) 7/8" (2.3 cm) 5/8" (1.6 cm) 150-200 3/4" (2.0 cm) 1/2" (1.3 cm) 7/8" (2.3 cm) 3/4" (2.0 cm)
SCHEDULE 40 PIPE
INSIDE DIA.
TUBING, TYPE L
OUTSIDE DIA.
of ½ PSIG
NOTE: Some areas all ow copper tubing or galvanized pipe - check wi t h l ocal approval agencies and codes. NEVER use plastic
GAS PRESSURE CHECKING REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve (see Figure 2 on Page 10). A qualified installer should use these fittings for setting the correct gas pressure during initial installation.
NOTE: DO NOT DAMAGE OR KINK THE FLEX CONNECTOR. CHECK FOR GAS LEAKS WITH SOAP AND WATER
SOLUTION.
NOTE: 3/8" FLEX OR RIGID PIPING MAY BE USED TO CONNECT GAS SUPPLY TO UNIT DEPENDING ON STATE
AND LOCAL CODES.
NOTE: BE SURE TO INSTALL FLEX GAS HOSE WITH BRASS-TO-BRASS FITTINGS TO PREVENT LEAKS AT
CONNECTION.
NOTE: THE HARD PLUMBING FITTING PROVIDED IS TO BE USED WITH INSTALLATIONS REQUIRING HARD
PLUMBING. IT MAY BE REMOVED IF THE FIREPLACE IS BEING INSTALLED WITH A FLEXIBLE CONNECTOR.
11
pipe.
Page 13
GAS PRESSURE REQUIREMENTS
A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLIANCES CAN BE IMPROPER GAS PRESSURE!
Problems such as changes in flame color or flame height, pilot or burner out ages, intermittent operation, changes in heat output, excessive burner noise, etc. are nearly always the result of changes in gas pressure or improper gas pressure at t he time of the installation. The m ost important item to check dur ing the installa­tion and the first thing t o chec k when problems occur is gas pressure!
Gas supplies normally enter a residence at 1/2 PSI (13" - 15" W. C. ) ( 3. KPA). A regulator is then placed in­side the residence, which drops this pressure to 7" W.C. (1.8 KPA) ( Nat . Gas). This "inches to inches" regula­tor is of adequate capacity to ser vice the g as appliances (s uch as dr yer, furnace, etc.). I f this regulator's capacity is not sufficient to add the G as Fireplace, an additional "inches to inches" regulator must be installed for the Fireplace. EXCEPTIO N: Som e c odes allow 2-PSI (1. 4KPA) supplies t o ent er the residence, in which case "pounds to inches" regulators ar e used.
The following table provides information on correc t gas pressure requirements . Be sur e your gas supplier or plumber carefully follows this table.
GAS PRESSURE REQUIREMENTS
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION*
NATURAL GAS 7.0" W.C.
(1.75 kPa)
L.P. GAS 12.0" W.C.
(3.00 kPa)
TURN GAS VALVE KNOB TO "HIGH" POSITION. GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
NOTE: For High Altitude (Above 5.000 Feet) Some Variations In Air Shutter Settings May Be Required. Manifold pressure must be tak en at the Output Pressure tap and inlet pressure at the I nlet Pressure tap with the burner
operating by a qualified installer (see
Figure 2: Gas Pressure Test Port).
5.0" W.C.
(1.12 kPa)
11" W.C.
(2.75 kPa)
Figure 2: Gas Pressure Test Ports
11" W.C.
(2.61 kPa)
13.0" W.C. (3.24 kPa)
3.5" W.C.
(0.87 kPa)
10.0" W.C. (2.5 kPa)
1/16 - 3/16 "
OPEN
1/4" OPEN-MIN.
12
Page 14
-
-
-
A =
Clearance above grade, veranda, porch, mum). Vinyl surfaces require 24” min.
H =
*Not to be installed above a meter/regulator as­the center-line of the regulator
B =
Clearance to window or door that may be (*12 inches (30 cm) minimum.
I =
Clearance to service regulator vent outlet (*6 *12 inches (30 cm) minimum.
D =
Vertical clearance to ventilated soffit located
surfaces require 24” min.
K =
Clearance to a mechanical air supply inlet (*6 E =
Clearance to unventilated soffit (18 inches (46
L =
Clearance above paved side-walk or a paved F =
Clearance to outside corner - 6 inches (15 cm).
M =
Clearance under veranda, porch, deck, or bal­cony (*18 inches (30 cm) minimum ‡)
G =
Clearance to inside corner - 12 inches (30
N=
Minimum 24” horizontal clearance to any sur­terminations.
EXTERIOR VENT LOCATIONS AND RESTRICTIONS
Figure 3: Exterior Vent Locations
NOTE: ALL MEASUREMENTS TO BE TAKEN FROM CENTER LINE OF VENT CAP
Vent Terminal
deck, or balcony (*12 inches (30 cm) mini-
opened
C = Clearance to permanently closed window
(minimum 12 inches (30 cm) recommended to prevent condensation on window)
above the terminal from the center-line of the terminal (12 inches (30 cm) minimum) Vinyl
cm) minimum) Vinyl surfaces require 24” min.
Air Supply Inlet
sembly within 3 feet (90 cm) horizontally from
feet (1.8m) minimum) Clearance to non-mechanical air supply inlet to
J =
building or the combustion air inlet to any other appliance.
feet (1.8 m) minimum)
driveway located on public property (*7 feet (2.1 m) minimum)
Area where terminal is not permitted
cm). Vinyl surfaces require 24” min.
A vent shall not terminate directly above a sidewalk or paved driveway, which is located between two single-family dwellings and serves both dwellings. Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. * As specified in CGA B1:19 Installation Codes (1991). Note: Local codes or regulations may require different
clearances.
13
face, such as an exterior surface, for vertical
Page 15
HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-
FLUE VENTING INSTRUCTIONS
The Mendota Fireplace must be vented using DuraVent or Amerivent or Security venting system. All warranties will be voided and serious fire, health or other safety hazards may result from any of the following actions: Installation by unau­thorized personnel; Installation of any damaged component; unauthorized modification of vent system; installation of any components not manufactured or approved by security chimney Simpson DuraVent, Amerivent and Mendota; failure to meet all clearance requirements; failure to properly twist-lock all components.
Consult local building codes before beginning the installation.
tact the Mendota technical service department for specific venting requirements and venting restrictions.
WARNING
Always maintain required clearances (air spaces) to combustibles to prevent a fire hazard. Do not fill air spaces with insu­lation. Check installation instructions for minimum clearance requirements between the outer walls of the vent pipe and nearby combustible surfaces. Be sure to check the vent termination clearance requirements from decks, windows, soffits, gas regulators, air supply inlets, and public walkways, as specified in these installation instructions and local building codes. SAFETY PRECAUTIONS FOR THE INSTALLER: 1) Wear gloves and safety glasses for protection; 2) Exercise extreme caution when using ladders or on roof tops; and 3) Be aware of electrical wiring locations in walls and ceilings.
The gas appliance and vent system must be vented directly to the outside of the building, and never attached to a chimney serving separate solid fuel or gas burner appliance. Each direct vent gas appliance must have its own separate vent sys­tem. Common vent systems are prohibited.
To assure proper venting performance of the high-performance Mendota Direct Vent Fireplaces and Stoves, it is critical that the DuraVent GS vent pipe sections are sealed tightly and leak-proof. This means that all pipe sections must be care­fully rotated into the fully "twist-locked" position (Dura Vent only).
WE STRONGLY RECOMMEND THAT FIXED LENGTH PIPE SECTIONS BE USED IN PLACE OF TELESCOPING SECTIONS WHENEVER POSSIBLE
Note: When using Dura-vent DV pipe you must use a silicate stove masonry sealant [Millpak Sealant #65-06-00909] on all inner pipe joints. On the exterior (air intake) pipe joints, high temperature foil tape may be used instead of the masonry sealant. Contact your dealer to obtain this sealant material.
DO NOT SEPARATE TELESCOPING SECTIONS. THEY MUST BE USED AS COMPLETE ASSEMBLIES.
COMPONENT "TWIST-LOCK" CONNECTION PROCEDURE
DuraVent, Amerivent and Security brand pipe and fittings are designed with special twist-lock connections. Twist-lock procedure is as follows: four (4) indentations, lo­cated on the female ends of pipes and fittings are designed to slide straight in to the male ends of the adjacent pipes and fittings, by orienting the four pipe identifications so that they match and slide into the four entry slots on the male ends (FIGURE 4). FIGURE 4: Twist-Lock Piping Push the pipe sections completely together then twist-lock one section clockwise, approximately 1/4 turn until the two sections are fully locked. The female locking lugs will not be visible from the outside on the black pipe or fittings.
14
Page 16
HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-
FLUE VENTING REQUIREMENTS FOR NG AND LPG
NOTE: IF A 90º ELBOW IS CONNECTED DIRECTLY TO THE FLUE OULET, THE MAXIMUM HORIZONTAL DISTANCE FROM THE FLUE OUTLET CENTERLINE TO THE OUTSIDE WALL IS 24".
A maximum of three (3) 90ºelbows are allowed per installation. Each 90º elbow USED, after the first 90
USED, after the first 90
o
elbow, reduces the maximum horizontal distance by 1-1/2’.
o
elbow, reduces the maximum horizontal distance by 3'. Each 45o elbow
tact the Mendota technical service department for specific venting requirements and venting restrictions.
15
Page 17
ITEM #
PART #
DESCRIPTION 1
45-01-00222
12" VENT STACK 5" / 8"
1
45-01-00223
24" VENT STACK 5" / 8"
1
45-01-00224
36" VENT STACK 5" / 8"
1
45-01-00225
48" VENT STACK 5" / 8"
2
45-01-00228
90ºGALVANIZED ELBOW 5" / 8"
3
45-01-00227
45º GALVANIZED ELBOW 5" / 8"
4
45-01-00229
ADJUST. WALL THIMBLE 5" / 8"
5
45-01-00226
11 - 14" ADJUSTABLE PIPE 5" / 8"
9
45-01-00239
ATTIC INSULATION SHIELD 12" 5"/8"
10
45-01-00236
ROOF FLASHING (0/12 TO 6/12) 5"/ 8"
10
45-01-00237
ROOF FLASHING (7/12 TO 12/12)5"/8"
11
45-01-00238
STORM COLLAR 5" / 8"
12
45-01-00230
VERTICAL VENT CAP 5" / 8"
13
45-01-00234
SUPPORT BAND 5" / 8"
14
45-01-00231
HORIZONTAL VENT CAP 5" / 8"
15
45-01-00235
FIRESTOP SPACER 5" / 8"
16
45-01-00221
6" VENT STACK GALV. 5" / 8"
17
AA-11-00458
HEAT SHIELD (FOR VINYL, WOOD & COMBUSTIBLE SIDING)
5"/ 8"FLUE VENTING COMPONENT S FOR NG AND LPG
16
Page 18
HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-
Adjustable– telescoping – pipe sections must be sealed using 1000° MILLPAK SILICATE STOVE MASONRY SEALANT (part #65-06-00909).
tact the Mendota technical service department for specific venting requirements and venting restrictions.
17
Page 19
HEAT SHIELD #AA-11-00458
Y
HEAT SHIELD
AA-11-00458
A-1 MINIMUM RISE THROUGH-THE-WALL VENTING FOR NG AND LPG
WARNING: ALWAYS USE HEAT SHIELD (#AA-11-00458) WHEN EXTERIOR WALL COVERING IS MADE OF VINYL,
WOOD OR OTHER COMBUSTIBLE MATERIALS. HEAT SHIELD (#AA-11-00458) IS INCLUDED WITH THE DXV45 FIREPLACE.
IMPORTANT: REFER TO DRAWINGS ON PAGE 12-14 WHILE FOLLOWING THESE INSTRUCTIONS.
o
The horizontal distance from flue outlet center to outside wall must not exceed 24" if a 90 flue outlet. ALWAYS MAINTAIN 1" CLEARANCES FROM VENT PIPE TO COMBUSTIBLES, 2" ABOVE PIPE ON HORIZONTAL RUNS. Use "fixed" pipe sections in place of adjustable pipe sections wherever possible. If adjustable pipe sections must be used, 1000
º Millpak sealant (#65-06-00909) must be used on the inner pipe joints (DuraVent Only). Do
not fill air spaces within the required clearance distances (1” around vertical pipe sections and 2” above horizontal pipes and fittings) with insulation or other material.
elbow is connected directly to
Position fireplace in desired location. See pg.12 for guidelines on proper vent cap placement on the exterior of home. Check to determine if wall studs are in the way when venting system is attached. If this is the case, you may want to ad­just the fireplace location.
Measure from the top of the fireplace up minimum 7 1/2" to centerline of 90
º elbow. (pg. 8) and mark wall directly at the
center of where the vent pipe will penetrate the wall. Cut and frame a 10-3/4" x 10-3/4" opening in the outside wall. The hole must be positioned so the vent system will run
level or have a ¼ " rise AND be perpendicular to the wall. The height of the opening must be located to meet all local and national building codes and not allow the termination to be easily blocked or obstructed. If wall being penetrated is non­combustible material, i.e. masonry block, brick, etc., an 8 ½" diameter hole is acceptable. A Wall Thimble (#45-01-00229) must be used when penetrating a combustible wall.
Make sure that all component connections are in their fully twist-locked position and are leak-proof. Make sure that 1000
Millpak
sealant (#65-06-00909) is used on the inner pipe joints of all pipe sections (Dura Vent only).
*NOTE: DO NOT SEPARATE TELESCOPING SECTIONS. USE AS COMPLETE ASSEMBLIES.
The length of the horizontal piece that fits through the wall will be determined by the thickness of the wall. When installed, the end of the horizontal piece must be flush with the exterior wall of the home. There MUST be a minimum of 1" air space clearance to combustibles from all vent pieces (2" above horizontal runs).
From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly secure the cap to the wall with screws. Seal with a high quality caulking.
NOTE: The Horizontal Vent Cap should not be recessed into the wall or siding.
º
18
Page 20
A-2 ELEVATED RISE THROUGH-THE-WALL VENTING FOR NG AND LPG
The minimum vertical rise from top of fireplace is 48 in. when used with the maximum horizontal run of 16 ft. For other venting configurations within these maximum limits see pg. 15.
NOTE: All horizontal runs of vent pipes must have a ¼" rise for every 1' of run toward the termination. Never allow the vent to run downward. This will cause high temperatures and the possibility of a fire.
USING OFFSETS AND RETURNS: A single 90º vertical-to-horizontal elbow is already calculated into the allowable maximum 16' horizontal run. Each additional 90º elbow reduces the maximum horizontal distance by 3'. A max-
imum of two 90° or four 45° elbows, in addition to the first 90 in entire vent system. 45º elbows reduce the maximum horizontal distance by 1½ '.
SUPPORT: Horizontal runs of pipe will require one vent support for every 3 ft. of pipe. CAUTION: Be sure to maintain 1" air space clearances to any combustibles around all pipe sections that are vertical. Be sure to maintain 1” air space clearances to any combustibles on the sides and below all horizontal pipe sections and el­bows and 2" from the top of all horizontal pipes and fittings.
IMPORTANT: REFER TO DRAWINGS ON PAGE 15 & 16 WHILE FOLLOWING THESE INSTRUCTIONS.
o
elbow, can be used (total equivalent of three (3) 90o elbows
Position fireplace in desired location. See pg. Error! Bookmark not defined. For guidelines on proper vent cap place- ment on exterior of home. Check to determine if wall studs are in the way when vent system is attached. If this is the case you may need to adjust the fireplace location.
Locate position where vent pipe will pass through any ceilings and will penetrate the outside wall. Since vent pipe sections "overlap" we suggest pre-assembling and measuring the total vent pipe run so you can more accurately locate the point where the vent pipe will penetrate the outside wall. Be sure all vent components are properly twist locked and leak-proof. Be sure 1000
*NOTE: DO NOT SEPARATE TELESCOPING SECTIONS USE AS COMPLETE ASSEMBLIES.
Cut and frame a 10-3/4" x 10-3/4" opening in the outside wall and in any ceiling openings. The outside wall hole must be positioned so the vent system will have a ¼ " rise per foot of run AND be perpendicular to the wall. The height of the open­ing must be located to meet all local and national building codes and not allow the termination to be easily blocked or ob­structed. A ceiling fire stop spacer is required at any floor (ceiling) opening.
Connect a 90° elbow to the fireplace adapter on top of fireplace vent outlet. Always use a Wall Thimble (#45-01-00229) when penetrating a combustible wall. The horizontal pipe must end flush with the exterior wall of the home. Horizontal pipe will require a proper support (part
#45-01-00234) every 3 ft. of vent pipe. THERE MUST BE A MINIMUM OF 1" CLEARANCE TO COMBUSTIBLES FROM ALL VENT PIECES (2" above horizontal runs). From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly secure the vent cap to the wall with screws. Seal with high quality caulking.
NOTE: Venting terminal should not be recessed into the w all or siding.
º silicate sealant (Millpak #65-06-00909) is used in the inner joints of all pipe sections (Dura Vent only).
19
Page 21
B - 1 VERTICAL THROUGH-THE-ROOF VENTING FOR NG AND LPG
The maximum vertical run of vent pipe is 36 ft. from the top of the fireplace. The fireplace will support a run of a maximum of 36 ft. Maintain 1" air space clearances on all sides of vents (2" above horizontal vents).
IMPORTANT: REFER TO DRAWING ON PAGE 10 & 11 WHILE FOLLOWING THESE INSTRUCTIONS. Place the fireplace in its desired location. Drop a plumb bob from the ceiling to the center position of the fireplace flue exit.
Mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling. Mark and drill the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the venting system. You may need to relocate the fireplace or need to offset, to avoid cutting load bearing members.
Cut and frame a 10-3/4" x 10-3/4" opening in the ceiling centered on the hole drilled in No. 1. To determine the length of the vent pipe required, measure the distance from the fireplace flue outlet to the ceiling, the
ceiling thickness, and the vertical rise in the attic or second story and allow sufficient vent height above roofline. For two story installations, fire stops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required.
Assemble the desired lengths of vent pipe and elbows to reach from the fireplace flue outlet. Ensure that all pipe and el­bow connections are in there fully twist-lock position and are leak-proof. Maintain 1" airspace clearances to combustibles (2" above horizontal runs). Be sure 1000º silicate sealant (Millpak #65-06-00909) is used on the inner pipe joints of all pipe sections (DuraVent Only).
If an offset is necessary, it is important to support the vent pipe every 3 ft. to avoid excessive stress on the elbows and possible separation. Wall straps (#45-01-00231) are available for this purpose.
Whenever possible, use 45º elbows instead of 90º elbows. The 45º elbow offers less restriction to the flow of flue gases and intake air. If a 90º elbow is necessary there must be a minimum of a one-foot pipe section rise after the 90º elbow to the vent cap or to the next offset. A maximum of three (3) 90ºelbows are allowed per installation.
o
Each 90º elbow, after the first 90 equivalent 90
o
elbow, reduces the maximum horizontal distance by 1-1/2’.
elbow, reduces the maximum horizontal distance by 3'. Each 45o elbow, after the first
Cut a 12" x 12" opening in the roof, center ed in t he small drilled hole placed in the roof in No. 1. The opening should be a sufficient size to meet all clearance requirements. Continue to assemble leng ths of pipe and el­bows necessary to reach up through the roofline. G alvanized pipe and elbows may be utilized in the attic, as well as above the roofline. The galvanized finish is desirable above the roofline due to its higher cor r osive re­sistance.
Slip the flashing over the pipe sections protruding t hr ough the roof. Secure the base of the flashing to t he r oof with roofing nails and seal flashing to roof. Ensure the roofing material overlaps the top edge of the flashing. Verify you have at least the minimum clearance to combustibles at t he r oofline.
Continue to add pipe sections until the pipe and the vent cap meet the minimum building code requirements, as outlined in No. 8 on the following page.
For multi-story vertical installation, a ceiling fire stop is required at the second floor and any subsequent floors. The open­ing should be framed to 12" x 12" inside dimensions as described in step No. 5.
Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passes through, must be enclosed. The enclosure may be framed and sheet rocked with standard construction materials, however, be sure to maintain minimum allowable clearances between the outside of the vent pipe and the combustible surfaces of the enclosure.
20
Page 22
HIGH ALTITUDE INSTALLATION INFORMATION: Prior to installing at altitudes higher than 7500, please con-
"H" DIMENSION
ROOF PITCH
FEET
METERS
FLAT to 6/12
2
.6
7/12 to 9/12
2
.6
10/12 to 12/12
4
1.2
13/12 to 16/12
6
1.8
17/12 to 21/12
8
2.4
Height "*H" of top of vent cap can be determined as follows:
Complete installation with storm collar and vent cap.
tact the Mendota technical service department for specific venting requirements and venting restrictions.
1"
21
Page 23
MENDOTA DESIGNER FRONTS INSTALLATION INFORMATION
The following Designer Fronts are available for the DXV-45 Fireplace:
1. Andover Arched Door Kit with Firescreen with optional Overlays as listed below:
2. Black Andover Overlay
3. Pewter Andover Overlay
4. Antique Copper Andover Overlay
5. Gold Andover Overlay
6. Prairie Rectangular Door Kit with Firescreen with optional Overlays as listed below:
7. Black Prairie Overlay
8. Pewter Prairie Overlay
9. Antique Copper Prairie Overlay
10. Gold Prairie Overlay
11. Black or Gold Victoria Filigree
12. Black or Gold Tuscany Filigree
13. Millennia Flat Grills in four optional color schemes as listed below:
14. Black Millennia Flat Grills
15. Full Brass Millennia Flat Grills
16. Classic Black and Brass Millennia Flat Grills
17. Classic Black and Bright Silver Millennia Flat Grills
Information specific to the installation of the Andover and Prairie Fronts
The Andover Door and Prairie Door Fronts are designed to be “Full-Face” trim kits. These two Fronts cover an area equivalent to that shown in the diagram below. Any material that protrudes into this area on the sides, top or bottom edges can only be flush with the front surface of the fireplace faceplate.
If planning to install either the Andover Door or the Prairie Door Front, DO NOT
COVER THE FACEPLATE OF THE FIREPLACE WITH ANY MATERIALS.
Furthermore, any drywall or wall cover­ing material that is adjacent to the sides, top or bottom of the Fireplace’s faceplate may not protrude out past the front sur­face of the Fireplace Faceplate’s front surface.
The Andover and Prairie Doors Mounting Faceplate (required for installation of the Andover and prairie Doors) may be cov­ered over with noncombustible facing materials.
To install Tile, Marble, Slate, Stone, Rocks or other noncombustible to en­hance the arch shape of the Andover Doors or the Rectangular shape of the Prairie Doors, do so only after the Ando­ver or Prairie Door Kits have been in­stalled on the DXV-45 Fireplace.
22
Page 24
HEARTH PAD SURFACE MUST BE FLUSH WITH FIREPLACE BOTTOM
HEARTH PAD
SURFACE
Hearth Protection Pad Installation Information when planning to Install the Andover or Prairie Fronts
Any hearth protection pad installed in front of the DXV-45 Fireplace must be designed, built and installed so that the hearth protection pad’s top surface is flush with the bottom-most surface of the DXV45 Fireplace. See the diagram to the right.
Information specific to the installation of Millennia Flat Grills, Victoria Filigrees and Tuscany Filigrees
The Millennia Flat Grills, Victoria Filigree and Tuscany Filigree are designed to be “inside-fit” trim kits. All of these trim kits fit within the inner perimeter of the Fireplace’s Faceplate and remain flush within the Faceplate’s front surface, see Figure below. This fitting method allows flexibility in covering the black visible surface of the Faceplate with non-combustible materials such as Tile, Mar­ble, Slate, Stone and Brick; as long as enough room is al­lowed for the removal of these Mendota Designer Fronts and the glass door for servicing,
WARNING: COMBUSTIBLE MATERIALS MUST NOT COVER THE FRONT SURFACE OF THE FIREPLACE’S FACEPLATE.
23
Page 25
GLASS FRAME ASSY.
SPRING LATCH
INSERT
TAB
IN SLOT
DETAIL A
DOOR REMOVAL AND REPLACEMENT
CAUTION: Do not operate the appliance with glass removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person. Glass latch tool #HA-57-00743 is supplied with the unit.:
To Unlatch Glass Frame Latches:
1. Insert Glass Latch Tool into hole in latch (two latches exist at top of glass frame).
2. Pull Glass Latch Tool outward about 3/8”.
3. Rotate Glass Latch Tool 90 degrees.
4. Slowly Release Glass Latch Tool.
5. Remove Glass Latch Tool.
To Latch Glass Frame Latches, reverse steps 5 to 1,
above.
To Remove Glass Frame:
1. Rotate top edge of freed glass frame outward about 15 degrees.
2. Lift Glass Frame Up and Out.
To Install Glass Frame:
1. Align and insert tabs in side flanges of Glass Frame into Slots into the slot in the side bracket.
2. Rotate Glass Frame upward until vertical.
3. Latch Glass in place per instructions above.
1.) INSERT
2.) PULL
3.) ROTATE
4.) RELEASE
24
Page 26
GLASS FRAME ASSEMBLY REPLACEMENT PARTS LIST
GASKET, TADPOLE, 3/8”BULB, 3/4” TAIL
GLASS
TRACER LINES IN GASKET
GLASS SHALL SIT BETWEEN
TRACER LINES IN GASKET
ROTATE GASKET UP SO ADHESIVE MAKES CONTACT WITH GLASS SURFACE
ADHESIVE
GASKET
GASKET IN
FLAT FORM
GLASS FRAME ASSEMBLY REPAIR AND REPLACEMENT
DO NOT substitute other manufac-
turer's materials or components. DO NOT operate unit with cracked, broken or missing glass. DO NOT abuse the glass door by striking the glass, slamming the door shut, etc
WARNING Use only authorized parts and materials obtained from Johnson Gas Appliance Company when replacing defective or damaged glass.
WARNING
Do not operate this appliance with the glass removed, cracked or broken. G lass should be replaced by a li­censed or qualified person.
TO REPLACE DAMAGED GLASS
Using an 1/8” drill bit, drill through 3 rivets on each side of glass frame. Remove glass retainer brackets and the damaged glass and gasket material. Clean the inner surface of the glass frame. Assemble new gasket on glass edge starting with the bottom left corner. The adhesive on the gasket should make contact with the glass surface. Use tracer lines in gasket to determine where the glass should sit on the gasket surface. Place glass and gasket assembly in glass frame. Carefully attach glass retainer brackets to sides of glass frame using new 1/8” Aluminum rivets.
The glass frame assembly and its individual components are available through Johnson Gas Appliance Company. Contact
your dealer for more detailed ordering information.
ITEM PART NUMBER DESCRIPTION 1 HA-41-00313 GLASS FRAME, DXV45
2 65-02-00103 3 65-06-00658 GLASS, CERAMIC, DXV45
25
Page 27
DXV45-
DT3 LOG SET PARTS IDENTIFICATION
Also included but not sho wn here are a 24 oz. bag of small c oa ls and one bag of
Inswool.
DXV45 COAL BED AND LOGS INSTALLATION
Carefully unpack the shipping boxes containing the coal bed sections and logs and remove them gently from the foam packing. 10 Log pieces, one 24 oz bag of small coals and one bag of inswool/Rockwool are included.
Lay out the log pieces on a soft flat surface and arrange them according to the diagram, below, to aid you in through the installation process.
26
Page 28
1. Locate Fiber Coal Bed “A”. This Fiber Coal Bed installs
between the front burner and the front of
the rear burner tube as shown below.
2. The Fiber Coal Bed “A” is placed directly behind the front burner. The Coal Bed
‘s front
edge must touch back edge of front burner tube.
3. Slide Fiber Coal Bed “A” to the left as far as possible. The left edge of this Coal Bed shall touch propagation leg of front burner tube.
FIBER COAL BED “A”
A
Left Edge of Coal Bed “A ” shall touch right edge of T- Propagation tube.
Front Edge of Coal Bed “A ” shall touch back edge of Front Burner
DXV45-DT3 LOG SET INSTALLATION INSTRUCTIONS
LOG “B”
Log “B” installed correctly
7. MAKE SURE THERE IS NO AIR SPACE DIRECTLY UNDER THIS LOG.
8. While pushing log “B” down, put your fingers behind the top of log “B” to get a slight angle forward of about 10 degrees.
4. Locate Log “B” - Back right log.
5. Locate holes on bottom of log.
6. Place log “B” onto the 2 pins on right side behind the rear burner as shown.
Holes in bottom of Log “B”.
B
27
Page 29
9. Identify Log “C”. Back left log.
10. Locate holes on bottom of log.
11. Place log “C ” onto the 2 pins on left-side behind the rear burner as shown.
LOG “C”
C
Holes in bottom of Log “C” .
12. Identify L og “D”. This log will be installed between the front and back of the rear burner tube as shown below.
13. Note that on the left end of log “D” is a curvature [along the bottom edge].
14. The curvature on the bottom left side sits on top of the rear burner’s inlet tube.
15. Log “D” will be tipped slightly forward to a maximum of a 10 degree angle once logs “G” & “H” are installed.
Push log “D” up against inside curve of burner.
LOG “D”
D
28
Page 30
18. Identify Log “G” and locate the hole at its bottom surface. Log “G” will be installed on the left side of the fireplace, with the hole on the bottom of the log setting on the left pin in log “D”.
19.
The front end of log “G” is notched. The notch will
rest on the
left-most grate bar.
16. Identify Log “E” and Log “F”. Log “E” rests on left side of the T-propagation tube . Log “E”’s left edge rests against the front burner inlet tube, at floor level.
17. Log “F” sits on the firebox floor and against the left side of the inlet tube on the front burner. Push this log back as far as possible.
Log “G” position on front grate
F
E
G
HOLE IN LOG “G” IS LOCATED UNDER HERE!
NOTCH
HOLE
20. Identify Log “H”. Log “H” will be installed on the right side of the fireplace, with the hole on the bottom of the log setting on the right pin in log “D”.
21. The front end of log “H” will be resting to the right end of the front burner tube as shown.
Log “H” front tip sits on flat crimp of front burner
H
HOLE IN
LOG “H”.
29
Page 31
22. Identify Log “I”. Log “I” will be installed in the middle of the fireplace, with the hole on the bottom of the log setting on the middle pin in log “D”.
23.
Once Log “I” is pinned to the middle pin in Log “D”, rotate FRONT –MOST TIP of Log “I” so that it is 2 inches to the left of the Right-Most Grate Bar.
2” gap
I
24.
Identify Log “J”. This log is designed to hide the pilot light flames and also to aid in the front ember-bed glow effect and realism.
25. Place Log “J” as shown here. You will find that it sits down well and “self­positions” on the ember bed. You may rotate the position of this log as it suites your taste. Exact position is not critical.
30
Page 32
Place small coals between Firebox Front and front Burner. Pile the coals higher near the Front burner to build height. A ny excess coals should be spread on the far left and far right sides of firebox to extend the coal bed effect. A couple of coals may be place behind front burner tube on Ember Bed “A” but sparsely. Avoid covering front burner tube’s gas ports.
Hold a clump of Inswool/ Rockwool in one f ist tightl y with a sma ll portion protr udi ng out. Brush Inswool/Rockwool over top of front burner tube , over Ember B e d “A” and over entire log ass e mbly. Brus he d Inswooldeposits sho uld be a thin layer but enough to hide the front burner tube. Brus h generously over front ember bed and a ll lo gs . Als o br ush lightly o ver c e nter burner tube a nd rear bur ner tube. B e carefuly when brushing o n middle and rear burner tubes . D o not deposit la rge chunks of inswoolon middle or rear burners. Attempt to break inswool i nto s mal l f ibe rs a s you brus h.
31
Page 33
FINAL LOG SET, COALS AND INSWOOL LAY OU T R EC OMMEN DED PATTERN
Note: Some minor adjustment to coals locations may me necessary o n LP gas units. Also, so me
adjustment to brushed inswoolthickness may be necessary if inswoolbrushed over middle or
rear burner are too t hick and heavy and impede combustion air flow to burner.
COMPLETED LOGS AND COAL BED ASSEMBLY EVALUATION
See the picture, shown above. This picture shows the recommended log positions. Slight variations in the position of each log is allowed. However, if any log position is significantly out of position in comparison to the diagram above and if any flames are floating off the burner surface (Ghosting) af­ter 10 minutes of starting the fireplace, turn off the fireplace and contact your installer or fireplace dealer. Have the Installer/Dealer adjust the log positions of the logs and coals and also conduct a thorough evaluation of the venting configuration to make certain that the venting configuration con­forms to Mendota’s venting requirements, which are listed in this Installation and Operations Manual.
32
Page 34
The following Check Off Lists must be completed prior to final operation of the Fireplace. Failure to do so may result in abnormal function or dangerous operation. Ignorance of these guidelines can lead to property damage, personal injury or death and the manufacturer’s warranty and liabilities will be voided: Keep a record of these Check OFF guidelines for fu­ture reference. Mendota may request a certified copy of these Check OFF lists to verify compliance to these printed guide­lines.
INSTALLATION CHECK OFF LIST
Co-axial vent rigid pipe, wall vent cap or roof vent cap must be installed by a Mendota ap-
q
q
proved person in accordance with instructions. All joints must be secured, "twist-locked" and leak-proof. 1000ºF sealant use is recommended on the inner pipe joints of DuraVent pipe sections.
Horizontal or vertical vent cap must be installed "right-side-up" and tightly sealed to structure per instructions. Vent Caps must Horizontal Vent Caps.
be Mendota approved. Heat Shield must be installed on
q Clearances to combustibles requirements must be strictly adhered to. q
Proper exterior and interior clearances for vent systems and locations for wall vent cap/roof vent cap must be maintained.
q Carefully check for correct gas pressure, proper size gas lines and for gas leaks. q
LIGHTING CHECK OFF LIST
120 V electrical service and gas supply must be installed in accordance with instructions and local and national codes.
q All items on "Installation Check Off List" (see above) must be completed. q Check air shutter opening - 1/16" to 1/8" Nat. gas or 1/4" Min. LP gas.
q Carefully follow all Lighting and Log Installation Instructions.
Make certain that burner lights immediately and flame runs promptly around "curve" in burner
q
q
and lights entire burner. DO NOT proceed with operation unless burner cycles "on/off" with­out delays.
Make certain that the flame is "stable" and does not "lift" off burner. If flame lifts off burner, turn unit off and check that all vent pipes are "twist locked" and leak proof, the vent cap is "right side up". DO NOT proceed with operation if flame is "lifting off" burner. Note: do not separate telescoping sections. They must be used as complete assemblies.
q Make certain glass door is in properly closed and "centered" in firebox opening.
33
Page 35
SMART
ON
OFF
SMART
MODE
NORMAL
THERMOSTAT
MANUAL
MODE
68
Hi
MAXMAX
Hi
OFF
76°
F F
76°
ON SMART
76°
F
BEFORE YOU BEGIN
Read this entire manual before you use your new fireplace (especially the section “Safety Precautions” on page 2). Failure to follow the instructions may result in property damage, bodily injury, or even death.
An Optional Wall Holder (#HA-78-00205) for the Remote Transmitter is available. Contact you dealer.
Remote Control Transmitter F u nctions
NOTE: The Receiver will “beep” once every time a Remote Transmitter Key is pressed, signaling that the command has been received.
Identify the four function buttons on the Remote Transmitter:
1. ON/OFF KEY: This button turns the system ON or OFF. When this button is pressed and the system is OFF, the pilot light will stay ON if the “Standing Pilot Switch” is in
the ON position.
2. THERMOSTAT KEY: This button, when pressed after the ON/OFF KEY is pressed and the system is ON, will allow the selection of three modes: Manual Operation, Normal Thermostat and Smart Thermostat.
1. Manual Mode: In this mode, the room temperature is ignored and the fireplace can be turned ON indefinitely.
The room temperature rise has no effect on this mode. All other functions such as fan speed control, flame height control, secondary burner On/OFF control and Accent Light ON/OFF controls will be manually control­lable.
2. Normal Thermostat: In this mode, the fireplace will
stay functioning until the room temperature in­creases 1
o
F above the Set Point Temperature. To increase the Set Point Temperature, Press the UP button until the desired temperature is displayed in the SET POINT TEMPERATURE window. The fan will turn on 5 minutes after fireplace startup and will turn off 12-1/2 minutes after the flames turn off, in this mode. The flame height can be adjusted while the fireplace is functioning, fan speed can be ad­justed after 5 minutes of startup. Secondary burner can be turned On or Off at any time after startup. The Accent Light can be turned on or off any time after startup.
3. Smart Thermostat: In this mode, all other func- tions except the flame height adjustment are allowed. Manual flame height adjustment is not allowed in this mode. The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actual room temperature. As the room temperature gets closer to the set point temperature, the Smart Function automatically modulates the flame down.
3. UP/DOWN KEY: This key is used to increase or decrease the Set Point Temperatures, Flame Height and Fan Speed and to toggle between Accent Light ON/OFF and Secondary Burner ON/OFF.
4. MODE SELECTION KEY: This key is used to toggle between the various function icons : Flame Height, Fan Speed, Accent Light Dimmer and Secondary Burner On/Off.
34
Page 36
REMOTE TRANSMITTER OPERATING INSTRUCTIONS
TO TURN ON THE APPLIANCE:
1. Press the ON/OFF button. The transmitter display will show all active icons on the screen.
2. Select the Thermostat Mode by pressing the Thermostat Key: OFF (meaning Manual Mode), ON (meaning normal Thermostat) or Smart (meaning Smart Mode). a. In OFF (Manual Mode), the appliance will ignite and start on HI. b. In ON (Normal Thermostat Mode), the appliance will only ignite if the Set Temperature
is greater than the Room Temperature.
c. In SMART (Smart Mode), the appliance will only ignite if the Set Temperature is greater
than the Room Temperature.
TO TURN OFF THE APPLIANCE, press the ON/OFF button.
MODE KEY: Pressing the MODE KEY toggles between the
various available functions: Flame Height, Fan Speed, Accent Light Dimmer and Secondary Burner On/Off.
Flame Height: 6 flame height Levels are available. While the Flame
Height Icon is displayed, pressing the Up or Down button once will increase or decrease the flame height by 1 of 6 increments. If the flame height is at Level 1 and the Down button is pressed, all burners will turn OFF. If in IPI mode, the pilot light will also extinguish. If in Standing Pilot Mode, the pilot light will
remain ON. Note: If in SMART model, the flame height function is not available for manual adjustment. In SMART mode, the flame height regulates automatically.
Fan Speed Control: The fan speed can be adjusted through six (6) speeds
and OFF. To activate this function, press the MODE Key to index to the fan control icon. Use the UP/Down Arrow Key to turn ON, OFF or adjust the fan speed. A single “beep” will confirm reception of the command. Once you set the desired fan control, the system will remember your selected fan speed until you manually change it.
Accent-Light Dimmer:
tions. Pressing the UP key in this mode will TURN ON the Accent Light and allow you to control the brightness of the Accent Light in 6 steps. A single “beep” will confirm reception of the command. Once you set the desired light brightness, the system will remember your selected brightness level until you manually change it.
This function controls the Mendota Accent Light func-
Secondary Burner: This function controls the Secondary Burner’s ON/OFF
feature. Pressing the UP Key in this mode will TURN ON the Sec­ondary Burner and Pressing the DOWN Key will TURN OFF the Secondary Burner. The flame level will not change when you turn the Secondary Burner On or Off. The flame level can only be changed in the Flame Level mode.
35
Page 37
TEMPERATURE INDICATOR (oF or oC)
1. Press the ON/OFF Key and Turn Off the Fireplace.
2. Simultaneously, Press both the MODE Key and the Thermostat
Key.
3. Look at the LCD display to verify that your desired indicator (
o
C) is being displayed. If not, repeat step 2.
o
F or
KEY LOCK FUNCTION
To prevent unsupervised children from operating the fireplace, a KEY LOCK function is pro­vided with this remote control system. To activate the KEY LOCK function, simultaneously press the “MODE KEY” and the “UP KEY”. To deactivate the KEY LOCK function, simulta­neously press the “MODE KEY” and the “UP KEY”. During KEY LOCK mode, none of the Keys will function. You must DEACTIVATE the system before you can use the Re­mote Transmitter.
LOW BATTERY POWER DETECTION
1. Transmitter Batteries: The life span of the remote control transmitter batteries depends
on various factors: quality of the batteries used the number of ignitions of the appliance, the number of changes to the room thermostat set point, etc. When the Transmitter bat­teries are low, a Battery Icon will appear on the LCD display of the Transmitter before all battery power is lost. When the batteries are replaced, this icon will disappear.
OPERATING DURING POWER OUTAGES
This electronic ignition system utilizes the supplied 110VAC power when it is available for all functions of this system. If the AC power is interrupted during a power outage, plug in the battery pack (supplied with this fireplace on the right s ide of the courtesy panel)..
During the power outage, the appliance’s bur ners will function. In addition, Flam e Height adjus tm ent and Secondary Burn­er ON/OFF functions will be available. The F an and Accent Light, which are wholly dependent on 110VAC power, will not function.
The fireplace is designed to operate during power outages for 1-1/2 continuous hours, Maximum. The blower will not op­erate, but natural convection can be improved by removing the upper grill and opening the screen doors (depending on the type of optional front installed). After 1-1/2 continuous hours of operation, during the power outage, turn off the burners for 1 hour and allow the fireplace to cool down. Consecutive 1-1/2 hour burn and 1 hour cool down cycles are allowed.
36
Page 38
REMOTE TRANSMITTER
BLUE LCD DISPLAY
MODE SELECTION KEY
UP/DOWN SELECTION KEY
THERMOSTAT
SELECTION KEY
ON/OFF KEY
“FIRST TIME” PILOT LIGHTING INSTRUCTIONS
IMPORTANT: Be sure all items on "INSTALLATION CHECK OFF LIST" in the Installation Manual have been completed! CAUTION: If the pilot goes out, be sure to wait a minimum of five minutes before attempting to relight the pilot.
1. Make certain that any manual gas supply shut-off valves located upstream of
fireplace are open and the Master On/Off switch is toggled to the ON position.
2. Make certain that 110VAC power is connected to Electrical Junction Box on left
side of Fireplace and that the Electrical Power is “ON”.
3. Insert Batteries in the Remote Transmitter. Note the polarity of batteries and
insert as indicated on the battery compartment cover.
4. For the “First Time Lighting”, Remove the Glass Door. This is required to purge
the gas line of air and to inspect the pilot lighting spark.
5. Press OFF on the remote Transmitter. Press MODE button on Transmitter.
Press UP for “CPI” (standing pilot mode). Press MODE button again to exit. You will hear a series of clicks and after a few seconds, you will hear sparking at the pilot spark electrode.
6. Allow adequate time for the air in the gas-line to purge. The control system will stop sparking after 30 seconds if the
pilot light does not light. After a 30 second delay the control system will start sparking again for 30 seconds more. If the pilot light does not light after the third 30 second spark event, the system will enter “Lock-out” mode. To unlock from “Lock-out” mode, Press the ON/OFF button on Transmitter then Press ON/OFF button on the transmitter again so the Transmitter display turns off. Wait 30 seconds. Turn OFF the Master Switch. Wait 30 seconds and Turn Master Switch ON again. Repeat this sequence until the pilot flame lights and the pilot is burning steadily.
7. Once the pilot flame is lit and well-established, close glass door. WARNING: NEVER IGNITE MAIN BURNERS WITH
GLASS DOOR REMOVED OR OPEN. Doing so will lead to damage to pilot flame sensor and spark el ectrode wire leads.
8. Press the ON/OFF button on Transmitter to “ON”. All burners should ignite
and run at “high-fire”. Toggle through other functions of the Fireplace (Flame Height, Fan Speed and Accent Light brightness) to verify all func­tions.
9. Perform gas inlet and outlet pressure tests and leak tests on field installed
gas fittings and factory installed fittings in the gas valve compartment, at this time. Note: Burners must be ON to check outlet pressures and to leak test gas train fittings upstream of main gas valve.
INITIALIZING THE REMOTE CONTROL SYSTEM
MASTER SWITCH: Remote Transmitter WILL NOT communicate to receiver unless the Master Switch is ON. The master switch when OFF disable all functions and acts as a Master Safety Shutoff Switch.
(Synchronizing Receiver and Transmitter)
Master Switch and Sync Switch are located beneath the Glass Frame.
1. Toggle Master Switch to ON (pull toward front of unit). Remote Transmitter
WI LL NOT communicate to receiver unless the Master Switch is ON.
2. Locate Sync Switch (directly above Master Switch). Press the Sync Button.
The receiver will beep 3 times indicating that it is ready to synchronize with a Remote Transmitter.
3. Push the “ON” key on the Remote Transmitter. The receiver will beep 4
times to indicate that the Transmitter’s command is accepted and sets to the particular code of that Transmitter. The system is now initialized.
NOTE: Once synchronized, the Transmitter and Receivers will communicate permanently and no further Synchronizing steps are necessary unless either the Transmitter or Receiver is replaced.
37
Page 39
ATTENTION!
Supply voltage
4.5V (three 1.5V AAA batteries)
Ambient temperature ratings
32 – 122 oF (0 – 50 oC)
Radio Frequency
315 MHz
IPI/STANDING PILOT SYSTEM INFORMATION
The transmitter and receiver are RADIO FREQUENCY DEVICES.
Turn off the main gas supply of the appliance during installation or maintenance of the receiver.
Toggle the Master Switch to OFF during installation or maintenance.
During appliance installation/maintenance or in case of remote control malfunction, turn off electrical sup-
ply to this appliance and remove the Backup batteries. Contact technical service.
REMOTE CONTROL
Intermittent Pilot Light and Standing Pilot Light Features
This gas fireplace is equipped with an electronic ignition System that first lights a pilot light then uses the pilot light to ignite the main burners. The pilot light can be set in the CPI (Standing Pilot) mode to allow the pilot light to remain on indefinitely by setting the Remote Transmitter to CPI mode. If the remote transmitter is set to the IPI (Intermittent Pilot) mode, the pilot light will only light and remain ON while the main fireplace burners are operating.
IPI Mode: This mode turns the pilot light “OFF” when the fireplace is not functioning and only lights the pilot light automat­ically when a call for heat is made by the remote control.
(CPI) Standing Pilot Mode: If set to CPI Mode, the pilot light will ignite and remain ON at all times.
Setting to IPI versus CPI mode:
With the remote transmitter OFF, press the MODE button. You will see either “CPI” or “IPI” displayed on the transmitter screen. Press the UP arrow but­ton to set “CPI” mode and press the DOWN arrow button to set “IPI” mode. One set to the desired setting, press On/Off button to activate the fire­place.
NOTE: Mendota Fireplaces recommends that the (CPI) Standing Pilot Mode be used during the winter months when the average daily high temperature falls below 50
excessive condensation of exhaust vapors on the door glass. Further, leaving the fireplace in the Standing Pilot Mode will keep the fireplace body warm and eliminate cold drafts and heat loss to the cold air that is trapped inside the firebox.
38
o
F. This will keep the fireplace chimney heated for proper updraft during burner ignition and it will also eliminate
Page 40
Backup Batteries
Backup Batteries are to be installed in the Battery Pack located on the right side of the Courtesy Panel beneath the glass frame. The life span of the backup batteries depends on the quality of the batteries used and how long the batteries have been installed in the Battery Pack. With good quality batteries, you can expect proper operation for periods in excess of 2 weeks.
These batteries are only utilized during power outages. Replace these batteries every heating season even if you have not experienced any power outages. Batteries drain slowly even when not in use. This is a normal characteristic of all batter­ies. To prevent the batteries from bleeding while not in use, you may choose to remove the backup batteries and install them only when they are needed.
OPERATING DURING POWER OUTAGES
This electronic ignition system utilizes the supplied 120VAC power when it is available for all functions of this system. If the AC power is interrupted during a power outage, this system utilizes the batteries (installed in the Battery Pack) as back-up batteries. During the power outage, the appliance’s burners will function. In addition, Flame Height adjustment and Sec­ondary Burner ON/OFF functions will be available. The Fan and Accent Light, which are wholly dependent on 110VAC power, will not function.
The fireplace is designed to operate during power outages for 1-1/2 continuous hours, Maximum. The blower will not op­erate, but natural convection can be improved by removing the upper grill and opening the screen doors (depending on the type of optional front installed). After 1-1/2 continuous hours of operation, during the power outage, turn off the burners for 1 hour and allow the fireplace to cool down. Consecutive 1-1/2 hour burn and 1 hour cool down cycles are allowed.
39
Page 41
BLOWER OPERATION AND WIRING
WARNING: The Electrical Junction box within this appliance must be connected to a grounded LIVE power circuit. No
switches, Light Dimmers or Fan Speed Control Devices are allowed within the same electric circuit as this appliance. Connect only to a LIVE electrical power supply that is not controlled by any other switching device.
Dual blowers are provided as standard equipment with this DXV45 DT3 Fireplace. The dual blowers have an air output rating of 210 CFM (in free air). This Fireplace is designed to operate with the blowers turned ON when the appliance is running and hot. The blowers increase the overall efficiency of this fireplace and aid in distributing and circulating heat to the room this Insert is installed in.
BLOWER BREAK-IN PERIOD: The integrated blowers in this Insert may exhibit some bearing noise and electrical stat­ic noise during the first few hours of operation. This is normal during the break-in period. It is recommended that follow­ing the Paint Curing Cycle, the blowers be run at their maximum speed for two 3-hour periods. The blowers in a few units may take longer to break-in and may require additional operation time before all extraneous noise is eliminated. Please allow adequate operational time (a minimum of 2 weeks) for the blowers to break-in before you contact your dealer for service.
WARNING: Label all wires prior to disconnection when se rvicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
BLOWER OPERATION
This Fireplace is designed so the blower operates at all times the fireplace is operating. The blower output can be regulated with the Remote Control. NOTE: There will be a time delay in blower operation during "heat-up" (approx. 10 minutes) and extended blower operation during "cool-down" of unit. (Approx. ½ hour). NOTE: Power supply to blower must be continuous. DO NOT use a switch or variable speed control in the power supplied to fireplace.
OPERATION DURING POWER OUTAGES
The fireplace is designed to operate during power outages for 1-1/2 continuous hours, Maximum. The blower will not operate, but natural convection can be improved by removing the upper grill and opening the screen doors (depending on the type of optional front installed). After 1-1/2 continuous hours of operation, during the power outage, turn off the burners for 1 hour and allow the fireplace to cool down. Consecutive 1-1/2 hour burn and 1 hour cool down cycles are allowed on if fired on the maximum HIGH FIRE setting. If only the FRONT BURNER is fired, you may run this fireplace indefinitely during a power outage at this LOW FIRE setting.
40
Page 42
SYMPTOM
PROBABLE CAUSES
CORRECTIVE ACTION
glass with cloth or paper towel.
flame will reduce the heat output of the unit.
NEVER BLOCK AIR INTAKE OR OUTLET VENTS.
Pull Out Opens,
TROUBLESHOOTING MENDOTA GAS DXV FIREPLACE
1. Thin black coating (soot) forms on viewing glass.
2. Humming or whistling coming from Fireplace.
3. A change in flame ap­pearance or burner operation.
MAIN BURNER GAS FLAME ADJUSTMENT
During initial installation the burner should be removed and veri­fied that the air shutter opening is set correctly at 1/8" to 1/4"
open for Natural gas and 1/4” - 1/2" minimum open for L.P. gas. NOTE: For altitudes above 5,000 ft., some variations may be required.
A. Incorrect gas pressure
B. Not enough combustion air
A. Normal operating noise. (See "Quiet Oper­ation" pg. 25)
A. A change in gas pressure.
B. Carbon dirt or lint.
Have gas supplier check for correct gas pressure (7" W.C. Nat. Gas; 11" W.C. LP Gas). If sooting continues open-air shutter on burner (see "Gas Flame Adjustment" below). If sooting still continues, shut off unit and call Mendo­ta service person. NOTE: To clean glass - remove glass and wipe
Some noise is normal. It is caused by the gas supply flowing through the gas orifice. It is expected from any gas fireplace. The noise can be reduced by turn­ing the Hi/Lo Knob on the control. Turning down the
Have your gas supplier check for correct gas 7" W.C. Nat. Gas; 11" W.C. LP Gas). If flame still needs adjustment see "Flame Adjustment" below. Clean out carbon, spider webs, lint, etc. from shutter area. Logs and burner.
REAR BURNER SHUTTER KNOB
Be sure burner and logs are properly installed. After burner has been properly installed and operated for two to three hours, small additional adjustments to the air shutter may be necessary for final flame appearance. These small shutter adjustments can be made by the following procedure:
NOTE: Very small changes in shutter settings make major changes in flame appearance.
Air shutter knob is located behind the lower grill. If flame is too "blue" slowly push air shutter control knob in small 1/16" increments until flame turns desired realistic "orange." If flame is too "orange" or is causing sooting on viewing glass or on logs, pull air shutter control knob outward in 1/16" increments until sooting stops. IF SOOTING DOES NOT STOP, TURN OFF UNIT AND CALL YOUR MENDOTA SERVICE PERSON. The front coal bed burner is pre-set at 1/8" open. Normally, no adjustment is required. For LPG applications, a slightly larger (greater than 1/8” opening in the front burner air shutter may be required if soot deposits on front logs or on coal chunks). IMPORTANT: Try each new shutter setting approx. ½ hour before making additional changes. NOTE: Changes in front burner flame can be made by re-arranging the coals. CAUTION: Any changes in pilot flame must be made by qualified person and checked with voltmeter.
41
Push in Closes.
Page 43
CUSTOMER INFORMATION AND TROUBLE-SHOOTING
MAXIMUM ALLOWABLE SURFACE TEMPERATURES
Mendota Fireplaces comply with UL Standards for maximum surface temperatures on exposed and embedded combus­tible surfaces adjacent to the unit. The Maximum allowable surface temperature is 117° F. over ambient (room) tempera­ture on exposed surfaces. Thus, if a room is 70° – 80° the exposed combustible surfaces immediately surrounding the Fireplace can have a surface temperature as high as 187° F. – 197° F. (too hot to touch). The continuous blower opera­tion automatically keeps temperatures within these safety limits. During Power Outages, remove upper grills on Millennia Fronts, open doors on Andover and Prairie Fronts and remove upper grills, remove Victoria and Tuscany Upper Face. This will increase convection air flow and prevent overheating.
OVER FIRING OF BURNER
NEVER "over fire" tions. Over firing can cause permanent damage to firebox and deterioration of parts and void warranty.
MAINTAINING CORRECT PILOT FLAME - PILOT OUTAGE & RELIGHTING
Never lower (reduce) pilot flame length less than 1 inch long. If pilot goes out, be sure and wait a minimum of 5 minutes before attempting to e-light the pilot flame.
CLEANING VIEWING GLASS CAUTION: Do Not use oven cleaner to clean glass. The viewing glass should be cleaned periodically. Exterior glass may
be cleaned with cleaner as desired. Interior glass - use soap and water, Kel Kem Glass Cleaner or equivalent. NOTE: Additives that are put in gas (both natural and propane) to make it smell, can be harmful to glass and can leave a
white film deposit on the glass. This deposit can be removed with cleaners such as KEL KEM “Polish Plus” or comparable product (See your dealer).
In some cases (especially propane) additives can cause “crazing” or etching on the glass. Although this is not normal, it is not covered under the warranty. The solution may be to change propane suppliers.
units by adjusting gas pressure or drilling out the orifice to increase BTUH above nameplate specifica-
SOOTING
Sooting is caused by improper installation or improper burner air shutter operations. However, some small areas of soot deposits on log surfaces are deemed acceptable. Open the burner air shutters if you observe sooting. If you observe large soot areas (larger than 1”x2”) on log surfaces or signs of sooting on the door glass (usually a thin black film on the Fire­place viewing glass or on the outside of the home around the vent cap), open both burner air shutters fully. If sooting con­tinues, the unit must correct "sooting" problems, but Mendota and their dealers are not that has not been immediately brought to their attention.
OPERATION DURING POWER FAILURE
The fireplace is designed to operate during power outages for 1-1/2 continuous hours, Maximum. The blower will not operate, but natural convection can be improved by removing the upper grill and opening the screen doors (depending on the type of optional front installed). After 1-1/2 continuous hours of operation, during the power outage, turn off the burners for 1 hour and allow the fireplace to cool down. Consecutive 1-1/2 hour burn and 1 hour cool down cycles are allowed on if fired on the maximum HIGH FIRE setting. If only the FRONT BURNER is fired, you may run this fireplace indefinitely during a power outage at this LOW FIRE setting.
Hot air convection may be improved by removing upper grill of the Millennia and Deerfield Fronts, opening the doors on the Andover and Prairie Fronts and opening the screen on the Wellington Front.
Replace these parts for operation after the unit has cooled completely and power is restored.
be immediately turned off and the local Mendota dealer promptly informed. Mendota dealers will
responsible for damage caused by excessive sooting
42
Page 44
MAINTENANCE
ANNUAL MAINTENANCE OF THIS MENDOTA FIREPLACE IS REQUIRED.
The following procedures must be performed each year by a Mendota approved service person. NOTE: Any adjust­ments to burner, pilot or logs must
A. Replace backup batteries at least 2 times annually. Replace them when the Day Light Savings Time changes. B. Clean all lint and dust build-up around the control. Inspect the condition of any wiring under the burner for
melting or damage.
C. Remove logs & coals and clean away any foreign matter (lint, Carbon, etc.) on the burner and logs. Be sure
the burner ports are "open". Clean the pilot and under side of the logs for any Carbon deposits. NOTE: Logs should be visually checked for Carbon "build-up". If c arbon depos its are visible on logs, unit s hould be turned
off and Mendota service person contacted. Be sure logs are re-installed per instructions. D. Check condition of glass door gasket, gasket must seal tightly over firebox, replace if necessary. E. Periodically check to verify that the vent system and vent cap are open and free of blockage. F. Before re-installing glass, have qualified service person check the operation of the pilot
G. The viewing glass should be c leaned periodically. Exterior glass surface may be cleaned with cleaner as desired.
To clean Interior glass surface, use Kel Kem
oven cleaner or abrasive cleaners to clean glass. Do not clean when glass is hot
H. Periodic visual check of pilot flames and the pilot ignition spark system is required. Pilot lighting Spark must origi-
nate on Pilot Spark Rod Tip and end at Pilot Hood every time the system initiates a spark. Pilot flame must ignite
within 5 sparks once gas flows out of pilot hood. Pilot Flame must be at least 1-inch long and must overlap Flame
Sensor and burner ignition ports at all times.
be done by a qualified Mendota service person.
“polish plus" (part # 65-06-00455) or comparable product. Do not use
.
Periodic visual check of main burner’s rear and front flames is required.
43
Page 45
WIRING SCHEMATICS
Note: The DXV45 DT3 ignition system utilizes Transformed DC power for normal ignition functions. In the event of a power outage, the Battery Pack power is utilized.
IGNITION SYSTEM WIRING SCHEMATIC
44
Page 46
Burner Orifices
#65-14-00053[53 DRILL]
#65-14-00364[3/64 DRILL]
Motorized
LP Pressure
Regulator
[10.0-5.5"WC]
# 907.012
53
364
NATURAL TO LP GAS CONVERSION INSTRUCTIONS
Kit # HA-42-00302 Mendota Model DXV45-DT3-LX
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the infor­mation in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsi­ble for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the owner instructions supplied with the kit.
Caution: The electrical supply to the fireplace must be turned off prior to performing the conversion. The gas supply must be shut off prior to disconnecting the electrical power.
ORIFICE SIZES REQUIREMENT:
LP Conversion Kit # HA-42-00225 contains the following parts: One Motorizedl LP Pressure Regulator #907.012, one Cap Orifices #65-14­00364(drill #3/64”), one Cap Orifice #65-14-00053 (drill #53) and an L-shaped Torx wrench.
RECOMMENDED PROCEDURE TO CONVERT THIS FIREPLACE TO BURN LPG
This Fireplace Insert arrives from the factory ready to burn Natural Gas. If you intend to burn LPG, it is highly recommend­ed that you convert this fireplace and its Pressure Regulator, Pilot Orifice Clip and Burner Orifices prior to placing this fire­place in its fireplace cavity.
See diagrams, on this page, and follow these instructions to prepare this fireplace for conversion to LPG.
1. Using a ¼” Hex Driver, remove screws that secure the Rear and Front burners to the Burner Airbox.
2. Pull forward and remove Front Burner.
3. Loosen Front Burner Air Shutter Screw and rotate air shutter open ¼” minimum. Secure Air Shutter Screw. Set burner aside.
4. Pull Rear Burner forward about 1” and lift up and remove from Firebox.
45
Page 47
5. Using a ½” deep well socket wrench, remove Front and Rear Orifices.
HINT: PACK SOME SOFT PAPER OR INSWOOL INSIDE DEEP WELL SOCKET TO STOP CAP ORIFICE FROM SLIDING TOO FAR INTO THE SOCKET.
6. Thread a new 3/64” drilled orifice to the Front Orifice mounting brass fitting and new #53 drilled orifice to the Rear Ori­fice mounting brass fitting. Tighten down orifices.
7. Locate Pilot Light on left side of firebox. While holding the pilot base body with large vice grips tightly, loosen Pilot Light’s hex shape base using a ½” open end wrench. Rotate counter clock-wise ¼ turn to loosen.
8. Pilot arrives from the factory set for NG. Push NG/LP Adjustment Clip inward all the way to set it for LP. See detail view, below. If you see “NAT” printing on the Adjustment Clip, this indicates that the pilot is set to burn NG. Push Clip in so that “NAT” is not visible.
9. Tighten down Hex shaped base of pilot using a ½” open end wrench.
46
Page 48
.
10. Before reinstalling burners, loosen the screw that secures the rotary air shutter on the Front Burner. Rotate the air shutter open to ¼” minimum.
11. Install both rear and front burners in their original locations and positions and secure down using screws you removed earlier.
12. Make certain front and rear burners are running parallel to front face of unit and positioned properly so that the pilot light flames are pointed properly towards the burner’s flame propagation ports.
BURNER MOUNTING SCREWS
47
Page 49
INSTALLING THE LP PRESSURE REGULATOR
WARNING: READ AND UNDERSTAND ALL INSTRUCTIONS PACKAGED WITH LP PRESSURE REGULATOR BODY BEFORE YOU ATTEMPT THE CONVERSION. FAILURE TO FOLLOW ALL INSTRUCTIONS WILL RESULT IN A LEAK OR OVERFIRING OF THE APPLIANCE AND CAN LEAD TO AN EXPLOSION OR A FIRE HAZARD.
1. Remove the Courtesy Access Panel mounted behind the lower grill and lay down gently without disconnecting any
wires of internal components. WARNING: DO NOT FORCE. EXCESSIVE FORCE MAY DAMAGE INTERNAL WIRING COMPONENTS!
2. Follow Instructions given below directly from SIT Controls. Replace Extension Knob as the final step.
48
Page 50
INLET TAP
LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from the outer left side of the fireplace. A qualified installer shall take pressure measurements at these ports to verify and set the correct gas pressures during the LP Kit installation and before fascia materials are installed over the front of this fireplace. Manifold pressure must burner operating by a qualified installer.
be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the "INLET PRESSURE" tap with the
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS 11.0" W.C.
(2.75 kPa)
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
11" W.C.
(2.75 kPa)
13.0" W.C. (3.24 kPa)
10.0" W.C. (2.5 kPa)
1/4" OPEN MIN.
(5 mm)
LPG PROPER INPUT RATES
With the proper orifices installed, as specified above, this fireplace utilizing LP Gas will have a maximum input rate of 31,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process, check for gas leaks with soap and water solution at all plumbing joints prior to placing this appliance into operation. It is recommended that all gas-plumbing joints, factory installed and field installed are checked for leaks.
PILOT FLAME AND MAIN BURNER RELATIONSHIP
OUTLET T AP
VERIFICATION
Prior to completing the conversion process, the qualified service technician must, light the pilot light and verify the relationship between the pilot light flames and the main burners. The pilot light flames di­rected towards the propagation ports on the rear and front burner must overlap the propagation ports on the burners. The pilot light flames must be a minimum of ¾” long and must overlap the propagation ports on both the rear and front burners as shown in the diagram, below. Verify that the burner tubes ignite quickly and the burner flames propagate smoothly along the entire length of the burners.
Figure 5: Pressure Test Port
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short and the system does not maintain a standing pilot, a qualified installer may in­crease the length of the pilot light flames to meet the two requirements: Minimum pilot light length to maintain a standing pilot light and the pilot light flames must be long enough to overlap the front and rear burner ports, 1 inch long minimum.
CHECKING FOR NORMAL BURNER(S) IGNITION CHARACTERISTICS
Once the conversion to LPG and all the above steps have been completed, light the main burners. Turn Gas Dial counterclockwise to "ON" then set Thermostat or push Main Burner ON/OFF switch to turn on burners.
Main burner should now light IMMEDIATELY and flame should not "lift" off burner. If there is any delay in ignition or if flame is "lifting off" burner, turn off burner and carefully check for proper installation of logs/coals, vent system and proper pilot flame impingement on burner and thermopile. Logs or coals must not block pilot flame or main burner flame. Vent system must be leak proof.
GAS LEAK TEST REQUIREMENT: It is the responsibility of the installer/service person to assure that each and
every gas connection and supply tubing that are a part of this fireplace are leak proof. The qualified/ certified individual connecting the gas supply line, performing pressure tests or performing any service to this fireplace is required to perform a THOROUGH LEAK TEST on ALL gas fittings that are a part of this appliance or the gas supply line connection using soap-water solution or a calibrated combustible gas detector. Failure to perform this leak test may lead to a house fire and/or an explosion. Mendota is not responsible for any damages due to an Installer’s failure to conduct a leak test and verify that all connections and supply lines are leak proof.
WARNING: Do not operate appliances with glass front removed, cracked, or broken. Re­placement of glass should be done a licensed or qualified service person.
49
Page 51
65-02-00103
GLASS GASKET
05-04-00065
PILOT ASS'Y. NAT.
65-06-00658
GLASS - FLAT
HA-42-00210
DOOR FRAME ASS'Y. – FLAT
HA-42-00302
LP KIT
65-14-00038
REAR ORIFICE (Nat. Gas) # 38
35-01-00320
LOG SET
65-14-00044
FRONT ORIFICE (NAT. Gas) # 44
65-14-00053
REAR ORIFICE (LP Gas) # 53
35-01-00239
GLOWING INSWOOL
65-14-00364
FRONT ORIFICE (LP Gas) # 3/64
35-01-00302
FIREBRICK KIT
35-01-00304
EMBER FLOOR SET
05-01-00157
SNAP-DISC (FAN TEMP SENSOR)
10-01-00003
RHEOSTAT
05-02-00364
VALVE NAT. GAS
15-02-00064
RIGHT HAND BLOWER - ONLY
HA-42-00011
MAIN BURNER TUBE WELDMENT
15-02-00065
LEFT HAND BLOWER - ONLY
70-01-00080
FRONT BURNER
REPLACEMENT PARTS MENDOTA DXV-45 DT3 FIREPLACE
PART NO DESCRIPTION PART NO DESCRIPTION
WARNING: Use only authorized parts and materials obtained from Johnson Gas Appliance when replacing any defective
or damaged parts.
DO NOT substitute other manufacturer's materials or components. DO NOT operate unit with cracked, broken or missing glass.
50
Page 52
NATURAL GAS (Gaz Naturel)
PROPANE GAS (Gaz de petrole liquefie (GPL))
Input Rating (Btu/hr) 0 - 610 m (Entrée nominale)
45,000
40,000
Min. Input Rating (Btu/hr) 0 - 610 m (Minimale En­trée nominale)
6,500
5,000 Orifice 0 - 610 m (Orifice)
Front #44 Rear #38
Front 3/64" Rear #52
Orifice 610 - 1370 m (Orifice)
Front #45 Rear #38
Front 3/64" Rear #53
Maximum output (Btu/hr) (Sortie maximale)
32,400
28,800
Manifold Pressure (in w.c./kPa) (Pression au collecteur)
3.5/0.87
10.0/2.5
Manifold Pressure, low (in w.c./kPa) Pression d'entrée minimale)
1.7/0.42
3.6/0.90 d'entrée minimale)
LISTING LABEL, RATING PLATE REPSENTATION
LISTED DIRECT VENT GAS FIREPLACE HEATER POÊLE AU GAZ HOMOLOGUE’, A AÉRATION DIRECTE NOT FOR USE WITH SOLID FUEL (NE DOIT PASÉ UTILISÉ AVEC UN COMBUSIBLE SOLIDE)
Manufactured by (Fabriqué par): JOHNSON GAS APPLIANCE CO. CEDAR RAPIDS, IOWA CERTIFIED FOR CANADA HOMOLOGUÉ POUR LE CANADA Tested to (Testé aux normes) ANSI Z21.88-2005 CSA 2.33-2005 CAN/CGA 2.17-M91 and ANSI Z21.50-1996.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, or loss of life. Refer to the owner's information manual provided with this appliance. Installation and service must be performed by a qualified installer, service agency or the gas supplier. For use with glass doors certified with the appli­ance only. Do not operate with glass panel(s) removed, cracked, or broken. This vented gas fireplace heater is not for use with air filters. Register kit may be used.
MISE EN GARDE: Installation, réglage, modification, entretien ou depannage non appropriés pourront causer des blessures ou des dommages materiels. Réferéz-vous au manuel du proprietaire fourni avac cet appariel. Pour assistance ou renseignements complémentaires, veuillez consulter un installateur expérimenté, une agence dé depannage/entreitien ou cotre compagnie gaziére. Pour utilisation avec les portes en verre certifiée l'appareil suelement. Ne pas opérer avec le verriére enlever, craquelure, brise.
Minimum Inlet Pressure (in w.c./kPa) (Pression
This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an afrtermarket, permanently located manufactured (mobile) home where prohibited by local codes. See owner's manual for details. This appliance is not convertible for use with other gases, unless a certified kit is used. Cet appareil sera installé conformémént avec les codes locaux, le cas écheant. Si aucun code n'existe, suivez la norme ANSI Z223.1 ou la norme CAN/CGA (ACNOR)-B149.
MINIMUM CLEARANCES TO COMBUSTIBLE CONSTRUCTION Unit to adjacent sidewall 10 in. (254mm) Unit to floor 0 in. (0mm) Vent to enclosed top 3 in. (76.2mm) Unit to enclosure sidewall 1 in. (25 mm) Vent to enclosed side 14-3/4 in. (375mm) Unit to enclosure back wall 1/2 in. (13mm) Wall Pass-Through to framing 0 in. (0mm) Unit top to ceiling 14-1/4 in. (374mm) Mantle above discharge air opening 13 in. (330mm)
CAUTION: Hot while in operation. Do not touch. Keep children, clothing, furniture, and flammable liquids or vapors away. ATTENTION: L'appareil est chaud lorsqu'il fonctionne. Ne pas toucher l'appareil. Survieller les enfants. Garder les vétements, les meubles, l'essence ou autres liquides a capeur inflammables loin de l'appareil. Electrical Rating (Courant nominal): 120 volts 60 hertz 1.5 amperes DO NOT REMOVE OR COVER THIS LABEL VEILLEZ Á NE JAMAIS ENLEVER NI DISSIMULER CETTE ÉTIQUETTE MODEL: DXV-45
WH# __________________
51
5.0/1.25 11.0/2.75
Page 53
THIS PAGE LEFT BLANK I NT ENTIONALLY
52
Page 54
MENDOTA WARRANTY QUALIFICATION & SERVICE REFERENCE FORM
As a part of Mendota's on-going program of customer satisfaction, this Form verifies proper installation and operation. It is important as a reference for future service. It insures long life and trouble-free operation of Mendota fireplaces & stoves and qualifies the owner for Mendota's lifetime limited warranty. Owner should sign Form when completed and mail a copy along with Warranty Registration to Mendota. OPTIONALLY, PLEASE REGISTER AT OUR WEBSITE AT: WWW.JOHNSONGAS.COM/MENDOTA-REGISTRATION.ASP
HOME OWNER: ____________________________ DEALER: _____________________________ ADDRESS: ________________________________ ADDRESS: ____________________________ CITY/STATE/ZIP: ___________________________ CITY/STATE/ZIP: _______________________ SIGNATURE: ______________________________ PHONE: ______________________________
MODEL #: DXV-45DT3LX __________________ SERIAL #: _____________________________ DATE INSTALLED: _____ ___________________ Mendota direct vent fireplaces are sophisticated, hi-tech gas appliances. All installation and operating instructions must be
carefully followed. The DXV fireplace must
REF: MENDOTA DXV45-DT3-PF2-LX INSTALLATION MANUAL
q APPROVED VENT PIPES AND VENT CAP INSTALLED - Per Manual.
Vent pipes must be fully twist-locked and leak proof.
Check minimum and maximum vertical / horizontal and vent runs.
q CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES & VENT LOCATIONS - Per Manual
be installed and serviced by a qualified Mendota approved service person.
q INSTALL PROPER SIZE GAS LINES - CHECK FOR GAS LEAKS - Per Manual q CHECK FOR CORRECT GAS PRESSURE AT MANIFOLD - Per Manual
a. 3.5 Inches Water Column Maximum - Nat. Gas (1/8” WC variation is allowed) b. 10.0 Inches Water Column Maximum - L.P. Gas (1/8” WC variation is allowed)
q CYCLE BURNERS ON/OFF FOR PROMPT IGNITION - Per "LIGHTING INSTRUCTIONS"
Burner must light IMMEDIATELY - Flame must travel promptly around "curve" & light burner.
q INSTALL LOGS AND ADJUST FLAME - Per Manual
Proper pilot flame impingement on flame sensor & burner - Air shutter opening: 1/16" - 1/8" Nat. Gas - 1/4" LP
Check that flame is "stable" and is not "lifting" off burner
q BRIEF OWNER ON OPERATION AND MAINTENANCE OF UNIT
Light Pilot Operate Burner Explain blower "delay" operation
WARRANTY REGISTRATION Your Name ________________________________________________________________ Address ___________________________________________________________________ City _____________________________________ State ____ Zip ____________________ Dealer (Place of Purchase) ___________________________________________________ City _____________________________________ State ____ Zip ____________________ Date of Purchase ___________________ Serial Number ___________________________ Purchaser's Signature _______________________________________________________
MENDOTA DXV-45DT3 DIRECT VENT FIREPLACE
CUT OUT PAGE AND MAIL TO: JOHNSON GAS APPLIANCE CO., 520 E AVE. N.W., CEDAR RAPIDS, IOWA 52405
PLEASE REGISTER AT OUR WEBSITE AT: WWW.JOHNSONGAS.COM/MENDOTA-REGISTRATION.ASP
53
Page 55
TAPE SHUT
--------------------------------------------------------------------------------------------------------------------------------------------------------
POSTAGE
NEEDED
JOHNSON GAS APPLIANCE COMPANY
54
520 E AVENUE N.W.
CEDAR RAPIDS, IA 52405
Page 56
MENDOTA EXTENDED PROTECTION AND LIMITED WARRANTY
MENDOTA DXV45 DIRECT VENT FIREPLACE INSERT
Mendota Division of Johnson Gas Appl i ance Company, 520 E Avenue N.W. Cedar Rapids, Iowa 52405, extends this Extended Protection and Limited Warranty to the original purchaser of a Mendota F V 46 F i repl ace, which is limit ed and us ed under normal home conditions .
STANDARD WARRANTY:
JOHNSON GAS APPLIANCE CO., MENDOTA DIVISION, WARRANTS THAT YOUR NEW MENDOTA FIREPLACE AND ALL ITS COMPONENTS ARE FREE FROM MANUFACTURING AND MATERIAL DEFECTS FOR A PERIOD OF ONE YEAR FROM THE DATE OF INSTALLATION. SUBJECT TO PRO OF OF PURCHASE AND THE CONDITIONS AND LIMI T ATIONS OUTLINED, BELOW.
EXTENDED WARRANTY:
THE MAIN BURNER ASSEMBLIES ARE WARRANTED FOR A PERIOD OF 2-YEARS TO THE ORIGINAL OWNER, FROM THE DATE OF PURCHASE. SUBJECT TO PROOF OF P URCHASE AND THE CONDITIONS AND LIMITATIONS OUTLINED, BE L OW. THE HEAT EXCHANGER, COMB USTION CHAMBER AND OUTE R SHIELD OF THE MENDOTA FV46 FIREPLACE ARE WARRA NT ED FOR 10-YEARS TO THE ORIGINAL OWNER. SUBJECT TO PROOF OF PURCHASE AND THE CONDITIONS A ND L IMITATIONS OUTLINED, BELOW.
1) This new Mendota Fireplace must be install ed & serviced by a competent, authorized service contractor. It must be inst al l ed and op­erated at all times i n accordance with the installat i on and operat i ng i nstructions furnished with t he F i repl ace. All adjustments to logs, coals or burner must be m ade by an authorized Mendota person. Any alteration, willful abuse, accident or misuse of the product shall nullify this warranty. This warranty does not c over gl ass or log breakage.
This li mited warranty does not cover the cost of service calls, the cost of labor to remove or i ns tall parts covered by this limited warran-
ty, freight or other transportat i on expenses , which may be incurred in connection with obtaining performances under thi s l i mited war­ranty. The remedy for damages as the result of any defects i n this product which have been warranted herein is limited to replacement parts and does not include any inci dent al , indirect or consequential damages or expenses sustained in c onnection with the product, in­cluding damages to property, except as provided by law.
2) This warranty is non-transferable and is made to the original retail purchaser, provided t he purchase was made through an authorized Mendota dealer.
Mendota is not responsible for any dam age to or malfunction of the Fireplace unless caus ed by a defect in material or workmanship from normal home use. Damage caused by abuse, improper installation, i mproper servicing, and instal l ation by unqualified personnel or breech of conditions of thi s limited warranty will excuse Mendota from perf ormance of any part of this limited warranty. Mendota has the right to investigate and inspect the exact, original Firepl ac e and entire installation (without any alt erations or tampering) in the event a claim is m ade t o determine whether the claimed damage or malfuncti on was caused by abuse, improper installation or other cause outside this warranty. Mendota is not res ponsible for any repairs or material purchases that have not received prior written approval from Mendota.
NOTE: Minor warping of certain parts or discoloration is normal and is not a defect covered by this warranty. Major warping of parts can be caused by over-firing of your Mendota Fireplace. O ver-fi ri ng above rat ed nameplate specific ation is as contrary to the manufac­turer's instructions and m ay void this warranty. This warranty may not be extended by our representatives or any third part y in any manner. The company neither assumes, nor au­thorizes any third party to assum e, on its behalf, any other liabi l i t i es with respect to the sale of t hi s Mendota product.
3) Mendota may at its discreti on, fully discharge all obligat i ons of this warranty by refunding the wholesale price of t he defective part(s).
4) All other warranties - expressed or implied - with respect to the product, its c omponents and accessori es , or any obligation/liabiliti es on the part of the company are hereby expressly excluded. P roduc ts made by other manufac turers, sold with the Fireplace or t hereafter, are not covered by this limit ed warranty. T he us e of unauthorized components will make this warranty null and void.
5) It remains the full respons i bi l i t y of the owner to operate this appliance within the guidelines provided in the Install ation Manual and the Operating Instruct i ons Manual accompanying this appli anc e. Further, the owner shall bear full respon­sibility to enforce cl earances to combusti bl es requirements and cautioni ng oth­ers about hot glass surfaces and hot metal surf ac es. Owner, by operating this appliance, accepts t hat this is a heat producing appli ance which has glass and steel parts that are hot enough t o cause severe burns. Owner accepts that this appliance requires close m oni toring of children and vulnerable individuals who are in the vicinity of this appl i ance when this appliance is in operation. Mendota does not assume or acc ept any liability claims for burns or other physical or material damages res ul ting from touching hot gl ass surfaces and hot metal sur­faces that are part of thi s appliance or other adjacent object such as hearth pads and mantels that may heat up during operation of this appl i anc e.
This warranty shall be effective only if the original purchaser of the Mendota appl i­ance is registered with Mendota Division within thirty (30) days of the date of pur­chase. Such registrat i on or the failure to register shall not be deemed to create any obligation or liability by the manufacturer and this warranty with its c ondi tions and lim­itations shall be the only proc edure for obtaining any rights against t he manufacturer and expresses the sole obligation and respons i bi l i ties of the manufacturer which are offered to the original purchaser and ac cepted upon purchase of the appliance.
Mendota Division, reserves the right t o make changes at any time without notice, in design, material, specif i cations, prices and t he right to discontinue styles and products. Some states do not al l ow the exclus i on of l i mitation of inci dent al or consequential damages or li mitations on how long an impli ed warranty lasts, so the above limitation or exclusion m ay not appl y t o you. T hi s warranty gives you specific legal rights and you may also have other rights which vary from state t o state.
55
Page 57
Johnson Gas Appliance Company 520 E Avenue N.W. - Cedar Rapids, IA 52405 Mendota Hearth Division www.johnsongas.com or www.mendotahearth.com
85-03-00893
56
Loading...