Memmert HPP 108-749 User Manual

OPERATING MANUAL
HPP 108/749
Constant climate chamber with Peltier cooling
Manufacturer and customer service
MEMMERT GmbH + Co. KG PO Box 17 20 91107 Schwabach, Germany
Äußere Rittersbacherstr. 38 91126 Schwabach Germany
Phone: +49 (0) 09122 / 925-0 Fax: +49 (0) 09122 / 14585 E-mail: sales@memmert.com Internet: www.memmert.com
Customer service: Phone: +49 (0) 09122/925-128 and: +49 (0) 09122/925-126 E-mail: service@memmert.com
For service enquiries, please always specify the appliance number on the nameplate (see page 14 ).
© 2011 Memmert GmbH + Co. KG Date 02/2011 We reserve the right to make changes.
About this manual
About this manual
Purpose and target group
This manual describes the setup, function, transport, operation and maintenance of constant climate chambers of types HPP 108 and HPP 749. It is intended for use by accordingly trained staff of the operator who are in charge of operating and / or maintaining the constant climate chamber.
If you as the user intend to work with the constant climate chamber, you should read this manual carefully before starting work with the unit. Familiarise yourself with the safety regula­tions. Only perform the work that is described in this manual. If there is something you do not understand, or certain information is missing, ask your superior or get in touch with the manufacturer. Do not do anything without authorisation.
Optional equipment
The constant climate chamber can be optionally equipped with an LED interior light to simu­late daylight. In this manual, information related to this is marked with the word “optional”. This means that this information is only relevant for appliances that include this function.
Other documents to be observed:
► for service and repair work (see page 57 ) – a separate service manual ► for controlling the constant climate chamber with the Memmert computer software “Cel-
sius” (see page 38 ) of the separate manual for this
► calibration documents
Storage and transfer
This instruction manual for the constant climate chamber should always be kept in a place where those working with the constant climate chamber have access to it. It is the respon­sibility of the operator to ensure that persons who are working with or will work with the constant climate chamber are informed as to the whereabouts of this instruction manual. We recommend that it is always kept in a safe space close to the constant climate chamber. Make sure that the instruction manual is not damaged by heat or humidity. If the constant climate chamber is sold on or transported and then set up again at a different location, this instruc­tion manual must also go with it.
3
Content
Contents
1. Safety regulations 6
1.1 Terms and icons used .......................................................................................................... 6
1.1.1 Terms used .................................................................................................................... 6
1.1.2 Icons used ...................................................................................................................... 6
1.2 Product safety and dangers ................................................................................................ 7
1.3 Requirements of the operating personnel .......................................................................... 7
1.4 Responsibility of the owner ................................................................................................. 7
1.5 Changes and conversions ....................................................................................................8
1.6 Behaviour in case of malfunctions and irregularities ..........................................................8
1.7 Switching off the constant climate chamber in an emergency .......................................... 8
2. Design and description 9
2.1 Construction ........................................................................................................................ 9
2.2 Description .........................................................................................................................10
2.3 Working range ................................................................................................................... 10
2.4 Basic equipment ................................................................................................................ 11
2.5 Material.............................................................................................................................. 12
2.6 Intended use ...................................................................................................................... 12
2.7 EC declaration of conformity ............................................................................................13
2.8 Designation (nameplate) ................................................................................................... 14
2.9 Technical data .................................................................................................................... 14
2.10 Ambient conditions ........................................................................................................... 16
2.11 Electrical connection ..........................................................................................................16
2.12 Standard accessories ......................................................................................................... 16
3. Delivery, transport and setting up 17
3.1 Safety regulations .............................................................................................................. 17
3.2 Delivery .............................................................................................................................. 17
3.2.1 Unpacking ...................................................................................................................17
3.2.2 Checking for completeness and transport damage....................................................17
3.2.3 Disposal of packaging material ................................................................................... 17
3.3 Storage after delivery ........................................................................................................17
3.4 Setup.................................................................................................................................. 17
3.4.1 Setting up options .......................................................................................................19
4. Putting into operation 20
4.1 Checking ............................................................................................................................ 20
4.1.1 Check the door and adjust if necessary ......................................................................20
4.1.2 Checking the temperature sensor ...............................................................................20
4.2 Fill up and connect the water tank ...................................................................................20
4.3 Electrical connections ........................................................................................................ 21
4.4 Switching on ...................................................................................................................... 21
5. Operation and control 22
5.1 Operating personnel.......................................................................................................... 22
5.2 Opening the door .............................................................................................................. 22
5.3 Loading the constant climate chamber ............................................................................ 22
4
Content
5.4 Basic information on operation ........................................................................................23
5.4.1 Switching appliance on and off .................................................................................. 23
5.4.2 User interface/controller ..............................................................................................23
5.4.3 Basic operation ............................................................................................................ 24
5.4.4 Setting parameters ...................................................................................................... 24
5.5 Operating modes ...............................................................................................................24
5.6 Operating mode settings ..................................................................................................25
5.6.1 Normal mode ..............................................................................................................25
5.6.2 Settings example normal mode .................................................................................. 26
5.6.3 Week time switch ........................................................................................................ 27
5.6.4 Settings example week time switch ............................................................................ 28
5.6.5 Programme mode ...................................................................................................... 29
5.6.6 Close statements for ramp segments .........................................................................32
5.6.7 Settings example programming mode ....................................................................... 34
5.6.8 Operation with computer/laptop (optional) ...............................................................38
5.7 Ending operation ............................................................................................................... 38
6. Malfunctions, warning and error messages 39
6.1 Warning messages temperature monitoring/humidification ........................................... 39
6.2 Power failure ......................................................................................................................40
7. Advanced functions 41
7.1 Printer ............................................................................................................................... 41
7.2 Basic appliance settings (Setup) ........................................................................................ 41
7.3 Temperature monitoring and safety equipment ...............................................................43
7.3.1 Electronic temperature monitoring (TWW) ................................................................44
7.3.2 Automatic temperature monitor (ASF) ...................................................................... 45
7.3.3 Warning messages ......................................................................................................46
7.4 Heat output distribution (BALANCE) ................................................................................. 47
7.5 Calibration ......................................................................................................................... 48
7.5.1 Temperature calibration ..............................................................................................48
7.5.2 Humidity calibration .................................................................................................... 49
7.6 Communication interfaces ................................................................................................ 50
7.6.1 USB interface .............................................................................................................50
7.6.2 Communication interfaces RS232/RS485 (optional) ................................................... 51
7.6.3 Connecting test chambers to a network with Ethernet interface .............................. 52
7.6.4 Log memory ...............................................................................................................52
7.6.5 Memory card MEMoryCard XL .................................................................................... 53
7.6.6 User ID card (optionally available as an accessory) ..................................................... 55
8. Maintenance and servicing 56
8.1 Cleaning .............................................................................................................................56
8.1.1 Cleaning the Peltier cooling modules ..........................................................................56
8.2 Regular maintenance.........................................................................................................56
8.3 Adjusting door ................................................................................................................... 57
8.4 Repairs and service ............................................................................................................57
9. Storage and disposal 58
9.1 Storage .............................................................................................................................. 58
9.2 Disposal ............................................................................................................................. 58
Index 59
5
Safety regulations
1. Safety regulations
1.1 Terms and icons used
In this manual, certain common terms and icons are used to warn you of dangers or to give you hints that are important in avoiding injury or damage. Observe and follow these hints and regulations to avoid accidents and damage. These terms and icons are explained below.
1.1.1 Terms used
“Warning“ is always used whenever you or somebody else could be injured if you do
not observe the accompanying safety regulation.
“Caution” is used for information that is important for avoiding damage.
1.1.2 Icons used
Prohibition sign (forbidding an action)
Do not tilt appliance
Warning icons (warning of a danger)
Danger of electrical shock
Regulation signs (stipulate an action)
Disconnect the mains plug
Observe information in separate manual
Other icons
Do not lift appliance without assistance
Explosive atmosphere
Wear gloves
Dangerous gases/vapours
Wear safety shoes
Important or useful additional information
6
Safety regulations
1.2 Product safety and dangers
Constant climate chambers of types HPP 108 and HPP 749 are technically well-developed, manufactured using high-quality materials and are tested for many hours in the factory. They contain the latest technology and comply with recognised technical safety regulations. But there are still dangers involved, even when the appliance is used as intended. These dangers are described below.
Warning! After removing covers, live parts may be exposed. You may receive an electric shock if you touch these parts. Disconnect the mains plug before removing any covers. Any work inside the unit may only be performed by qualified electricians.
Warning! When loading the chamber with an unsuitable load, poisonous or explosive vapours or gases may be produced. This could cause the chamber to explode and people could be badly injured or poisoned. The chamber may only be loaded with materials/test objects which do not form any poisonous or explosive vapours when heated up (see also chapter Intended use on page 12 ).
1.3 Requirements of the operating personnel
The constant climate chamber may only be operated and maintained by persons who are of legal age and who have received instructions for the constant climate chamber. Personnel who are to be trained, instructed or who are undergoing general training may only work on the constant climate chamber under the continuous supervision of an experienced person.
Repairs may only be performed by qualified electricians. In this case, the regulations in the separate service manual must be observed.
1.4 Responsibility of the owner
The owner of the constant climate chamber
► is responsible for the flawless condition of the constant climate chamber and for the con-
stant climate chamber being operated in accordance with its intended use (see page 12);
► is responsible for ensuring that persons who are to operate or service the constant climate
chamber are qualified to do this, have received instructions about the constant climate chamber and are familiar with this operating manual;
► must know about the applicable regulations, requirements and work protection regula-
tions and train staff acordingly;
► is responsible for ensuring that unauthorised persons have no access to the constant
climate chamber;
► is responsible for ensurting that the maintenance plan is adhered to and that maintenance
work is properly carried out (see page 56 );
► ensures, for example through corresponding instructions and inspections, that the con-
stant climate chamber and its surroundings are kept clean and tidy;
► is responsible for ensuring that personal protective clothing is worn by operating person-
nel, e.g. work clothes, safety shoes, protective gloves.
7
Safety regulations
1.5 Changes and conversions
No independent conversions or alterations may be made to the constant climate chamber. No parts may be added or inserted which have not been approved by the manufacturer.
Independent conversions or alterations result in the EC declaration of conformity (see page 13 ) losing its validity, and the constant climate chamber may no longer be operated.
The manufaturer is not liable for any damage, danger or injuries that result from independent conversions or alterations, or from non-observation of the regulations in this manual.
1.6 Behaviour in case of malfunctions and irregularities
The constant climate chamber may only be used when in a flawless condition. If you as the opertor notice irregularities, malfunctions or damage, immediately put the constant climate chamber out of service and inform your superiors.
You can find information on eliminating malfunctions from page 39 .
1.7 Switching off the constant climate chamber in an emergency
Push main switch on front side of appliance ( Fig. 1 ). This causes the constant climate chamber to switch off.
Fig. 1 Switch off constant climate chamber by pressing main switch
8
2. Design and description
2.1 Construction
1
Design and description
2 3
4
5
6 7
11
10
8
Fig. 2 HPP Constant climate chamber 1 Controller/user interface (see page 23 ) 2 Set key 3 Main switch / push-turn control (see page 23 ) 4 Door seal 5 Interior seal 6 Chamber fan 7 Sliding shelf 8 Heating ribs 9 Nameplate (underneath door) 10 Door knob 11 Card reader
9
9
Design and description
2.2 Description
The constant climate chamber can heat the interior up to 70 ºC and cool it down to 5ºC. For this purpose, low-noise, long-life and energy-saving Peltier cooling and heating technology is used. In heating operation, a part of the required energy is extracted from the surroundings (heat pump principle).
Humidity in the interior can be regulated between 10 and 90 % rh (rh = relative humidity). The humidity is increased by water from a tank being evaporated and fed into the interior, and is reduced through condensation on a Peltier module.
2.3 Working range
The temperature-humidity diagram ( Fig. 3 ) specifies at what range of temperature and humid­ity a permanent, condensation-free operation is possible.
Caution:
If the appliance is in operation at the upper level or outside the working range for long periods, puddles of water may form inside the chamber and water may force its way out of the door seal.
100
90
80
70
60
50
Humidity % rH
40
30
20
10
C
B
A
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
Fig. 3 Temperature-humidity working range
10
Temperature °C
Design and description
Range A:
In this range, temperature and humidity can be combined as you please, without resulting in any significant condensation. If there are extreme ambient conditions, the working range may be restricted.
Range B:
If the specified range is exceeded upwards, e.g. 80 % rh at 60°C, the hot steam fed in will im­mediately condense, due to the dew-point, at the coldest point in the appliance.
Range C:
At low temperatures and low relative air humidity, the effective range is heavily dependent on the degree of humidity of the chamber load.
2.4 Basic equipment
► Low-noise, long-life and energy-saving Peltier cooling and heating technology (in heat-
ing mode, part of the energy required is extracted from the surroundings = heat pump principle)
► Electronic fuzzy-supported PID process controller with permanent performance adjust-
ments and time-saving self-diagnosis system to quickly locate errors (see pages 38 and 45)
► Alphanumeric text display ► Control of the appliance and logging the actual values with a preformatted empty
MEMoryCard XL (storage capacity 32 kByte, reprogrammable for up to 40 ramp segments and in addition 135 hours of log memory for temperature and humidity with a scanning interval of 1 minute)
► Programme sequence control for up to 40 ramp segments ► Integrated week time switch with group function (e.g. all working days) ► Retracting push-turn control for simple operation ► Optical alarm display ► Integrated horn as alarm if limit values are crossed, as acoustic signal when programme
ends and to confirm input (button click)
► Digital monitoring control for overtemperature, undertemperature and automatic tem-
perature monitor (ASF)
► Two separate Pt100 temperature sensors DIN class A in a 4-wire circuit for control and
monitoring
► Parallel printer port (PCL3-compatible) ► USB interface for computer-based temperature control programmes and to read out the
controller’s internal log memory
► MEMMERT software "Celsius" for remote control of the chamber via computer (see page
37) and to read out the internal controller log memory
► As an optional accessory, external card reader for MEMory-Card XL for connection to the
PC-USB interface, printer cable (parallel, shielded)- 25-pin
► Language setting (German, English, French, Spanish, Italian) ► Capacitive humidity sensor ► Active humidity control guarantees that setpoint humidity is quickly achieved, with short
recovery times, and avoiding condensation formation
11
Design and description
► 7 different ramp close statements for sophisticated temperature-control tasks ► Acoustic and visual signals if temperature or humidity limits are crossed, and if water tank
is empty
► Internal log memory with 1024 kB as a ring memory for all temperature and humidity
values, errors and settings with realtime and date, logging for approx. 3 months with a 1-minute logging interval
► Calibration possible without separate computer: 3-point calibration on controller for tem-
perature and 2-point calibration for humidity at 20 % rh and 90 % rh
► LED interior light ( light panels) in various light colours (optional)
2.5 Material
For the outer housing, MEMMERT uses stainless steel (W.St.No. 1.4016 = ASTM 430), for the interior, stainless steel (W.St.No. 1.4301= ASTM 304) is used, which stands out through its high stability, optimal hygienic properties and corrosion-resistance towards many (but not all!) chemical compounds (caution for example with chlorine compounds).
The chamber load for the appliance must be carefully checked with respect to chemical com­patibility with the materials mentioned.
A resistance table for all these materials can be requested from the MEMMERT.
2.6 Intended use
Constant climate chambers HPP may be used exclusively for temperature and climate testing of materials and substances in the context of the procedures and specifications described in this manual. Any other use is improper, and may result in hazards and damage.
The test chambers are not explosion-proof (they do not comply with workplace health & safety regulation VBG 24). The chambers may only be loaded with materials and substances which cannot produce any toxic or explosive vapours at temperature ranges up to 70 ºC, and which themselves cannot explode, burst or ignite.
The test chambers may not be used for drying, vaporising and branding paints or similar ma­terials, the solvents of which could form an explosive mixture when combined with air. If there is any doubt as to the composition of materials, they must not be loaded into the constant climate chamber. Potentially explosive gas-air mixtures must not be produced, either in the interior of the chamber or in the direct vicinity of the appliance.
12
Design and description
2.7 EC declaration of conformity
EC Declaration of Conformity
Manufacturer´s name and address: MEMMERT GmbH + Co. KG
Äußere Rittersbacher Straße 38
D-91126 Schwabach Product: Constant-Climate-Chamber Type: HPP … Sizes:  Nominal voltage:
The designated product is in conformity with the European EMC-Directive
Council Directive of 03 May 1989 on the approximation of the laws of the Member States relating to
electromagnetic compatibility.
Full compliance with the standards listed below proves the conformity of the designated product with the essential protection requirements of the above-mentioned EC Directive:
DIN EN 61326-1:2006-10 EN 61326-1:2006 DIN EN 61000-3-11:2001-04 EN 61000-3-11 :2000
The designated product is in conformity with the European Low Voltage Directive
Council Directive on the approximation of the laws of the Member States relating to Electrical
equipment for use within certain voltage limits.
Full compliance with the standards listed below proves the conformity of the designated product with the essential protection requirements of the above-mentioned EC Directive:
DIN EN 61 010-1 (VDE 0411 part 1):2002-08 EN 61 010-1:2001 DIN EN 61 010-2-010 (VDE 0411 part 2-010):2004-06 EN 61 010-2-010:2003
Schwabach, 23.07.08
______________________________
(Legally binding signature of the issuer)
This declaration certifies compliance with the above mentioned directives but does not include a property assurance. The safety note given in the product documentation which are part of the supply, must be observed.
AC 230 V 50 / 60Hz
alternative AC 115 V 50/60 Hz
2004/108/EEC
including amendments
2006/95/EEC
including amendments
Modelljahr 2003 D10633 / 23.07.08
13
Design and description
2.8 Designation ( nameplate)
The nameplate provides information about the appliance model, manufacturer and technical data. It is attached to the front of the appliance, on the right beneath the door (see page 9 ).
1
2
3
4
5
6
Fig. 4 Nameplate 1 Type designation
2 Connection values 3 Applied standard 4 Protection type 5 CE conformity
9
8
7
6 Address of manufacturer 7 Disposal note 8 Nominal temperature range 9 Factory number
2.9 Technical data
Model HPP 108 HPP 746
Chamber width A* [mm]
Chamber height B* [mm]
Chamber depth C* [mm]
Appliance width D* [mm]
Appliance depth F* [mm]
Appliance height E* [mm]
Chamber volume [litres]
Weight [kg]
Performance [W]
Max. number of sliding shelves
560 1040
480 1200
400 600
710 1190
640 825
760 1620
108 749
66/70 218/278
350 1050
514
* see Fig. 5 on page 16 .
14
Design and description
Model HPP 108 HPP 746
Max. load per sliding shelf [kg] 30 30 Max. load per appliance [kg]
60 160
Electrical equipment
Operating voltage
Current consumption
Protection class
Protection type
Interference-suppressed
Fuses Appliance: 250 V/15 A (appliance)
Temperature
see nameplate
see nameplate
1 (acc. to EN 61010)
IP 20 (EN 60529)
Class B acc. to EN 55011
Controller: 100 mA (230 V) or 200 mA (115 V)
► Temperature recording: Pt100 in a 4-wire
circuit
► Adjustment range: 0 °C to 70 °C
Adjustment precision: 0.1 °C
► Working temperature range: 5 °C to 70 °C ► Temperature variation (time): ±0.1 °C ► Spatial deviation: max. ±0.3 °C bei 37°
Monitoring
► Temperature recording: Pt100 in a 4-wire
circuit
► Settings range -5 °C to +75 °C ► Adjustment precision: 0.1 °C
Humidity The relative humidity in the chamber is
measured by a capacitive humidity sensor and displayed digitally in percent
► Measurement precision of the humidity
sensor: 0.5 % rh
► Adjustment range: 10 bis 90 % rh, off* ► Adjustment precision: 1 % rh ► Display range: 1 bis 98 % rh ► Temperature variation (time): max. ±1.5
% rh
* Setting off: Humidity control disabled
* see Fig. 5 on page 16 .
15
Design and description
D
A75 75
E
302
12
Fig. 5 Dimensions of constant climate chambers HPP
2.10 Ambient conditions
38F
C
10
B 19771
► The constant climate chamber may only be used in enclosed rooms and under the follow-
ing environmental conditions: Ambient temperature: 16 ºC to 28ºC Humidity: max. 70 % not condensing Degree of pollution: 2 Altitude of installation: max. 2,000 m above sea level
► The constant climate chamber may not be used in areas where there is a risk of explosions.
The ambient air must not contain any explosive dusts, gases, vapours or gas-air mixtures. The constant climate chamber is not explosion-proof.
► Heavy dust production or aggressive vapours in the vicinity of the appliance could lead to
sedimentation in the chamber interior and as a consequence, could result in short circuits or damage to electrical parts. For this reason, sufficient measures should be taken to pre­vent large clouds of dust or aggressive vapours from developing.
2.11 Electrical connection
Observe the country-specific regulations when making connections (e.g. in Germany DIN VDE 0100 with residual current device).
This appliance is intended for operation on an electrical power system with a system imped­ance Z must ensure that the constant climate chamber is operated only on an electrical power system that meets these requirements. You can ask your local energy supply company what the sys­tem impedance is.
at the point of transfer (service line) of a maximum of 0.292 ohm. The operator
max
2.12 Standard accessories
► Sliding shelf ► Water tank with connection hose
16
Delivery, Transport and Setting Up
3. Delivery, transport and setting up
3.1 Safety regulations
Warning! You may get your hands or feet squashed when transport­ing and installing the constant climate chamber. You should wear protective gloves and work shoes.
Warning! Because of the weight of the constant climate chamber, you could cause yourself an injury if you try to lift it. At least two people are needed to carry the constant climate chamber HPP 108, and four for the constant climate chamber HPP 749.
Warning! The constant climate chamber could fall over and seriously injure you. Never tilt the constant climate chamber and only transport it in an upright position.
3.2 Delivery
The constant climate chamber can be packaged in cardboard or in a box, and is delivered on a wooden pallet.
3.2.1 Unpacking
Remove the cardboard packaging by pulling upwards or cutting carefully along an edge.
3.2.2 Checking for completeness and transport damage
► Check the delivery note to ensure that the delivery is complete. ► Check the constant climate chamber for damage.
If you notice deviations from the delivery note, damage or irregularities, do not put the constant climate chamber into operation, but inform the haulage company and the manufac­turer.
3.2.3 Disposal of packaging material
Dispose of the packaging material (cardboard, wood) in accordance with the appropriate regulations for the material in your country.
3.3 Storage after delivery
If the constant climate chamber is initially to be stored after delivery: Read the storage condi­tions from page 58 .
3.4 Setup
The installation site must be flat and horizontal and must be able to reliably bear the weight of the constant climate chamber (see chapter Technical data on page 14 ). Do not place the appliance on a flammable surface.
An 230 V/16 A/115 V power connection (see nameplate) must be available at the installation site.
17
Delivery, Transport and Setting Up
The distance between the wall and the rear of the chamber must be at least 15 cm. The clear­ance from the ceiling must not be less than 20 cm and the side clearance from the wall must not be less than 8 cm ( Fig. 6
). Sufficient air circulation in the vicinity of the chamber must be
guaranteed at all times.
FP
FP
FP
Fig. 6 Minimum clearance from walls and ceiling
FP
18
Delivery, Transport and Setting Up
3.4.1 Setting up options
Read the assembly instructions for the respective accessory part.
Floor/table
The chambers may be placed on the floor. Constant climate chambers HPP 108 may be placed on a table (work surface), if the table is flat and horizontal and able to bear the weight of the constant climate chamber.
Base
The chamber can be placed on a base (available as an accessory) ( Fig. 7 ).
Stackable model (HPP 108 only)
Two constant climate chambers HPP 108 can be placed on top of one another. Please ensure that the chamber with the lower working temperature is always used as the lower chamber:
Warning! Danger through contact with electrical voltage. Remove the mains plug if the chamber is already connected to the power supply.
1. Remove the housing cover from the lower chamber.
2. Insert the drilling template (supplied with the foot alignment) into the overturned lid.
3. Mark the drilling point and drill with a 4.2 mm diameter drill bit.
4. Screw the foot alignments to the top of the lid with the screws and nuts supplied ( Fig. 8 ).
5. Put the covers back on.
Fig. 7 Base
Fig. 8 Attaching the foot alignments when two chambers are placed on top of one another
19
Putting into Operation
4. Putting into operation
4.1 Checking
4.1.1 Check the door and adjust if necessary
The door may have been twisted during transport. You should therefore check whether the door closes properly and the seals are in the correct position. Adjust door if necessary (descrip­tion on page 57 ).
4.1.2 Checking the temperature sensor
Due to strong vibrations during transport, the temperature sensors could have moved out of position in their holders in the ceiling of the working chamber.
Before operating for the first time, check the temperature sensor for its correct posi­tioning and if necessary adjust its position in the holder ( Fig. 9 ). Open the door to do this (see page 22 )
Fig. 9 Temperature sensor on the ceiling of the interior
4.2 Fill up and connect the water tank
Fill the water tank supplied with water and connect it with the enclosed tube to the "H2O" connection on the rear of the chamber ( Fig. 10 ).
Water specification
To generate steam, only either
► steam-distilled water (aqua dest) may be used
or
► demineralised/desalinated water (aqua dem) in accord-
ance with VDE 0510/DIN EN 50272, provided the regula­tions are strictly maintained (conductivityof production 10 μS/cm). Battery water inaccorance with VDE 0510 can be obtained in all large chemist's, supermarkets, DIY stores and wholesalers. VDE 0510/DIN EN 50272 must be explicitly marked on the label.
Otherwise, limescale in the steam generators, steam piping and tube pumps may impair the the functionality of the appliance.
The water used must have a pH value of > 5 and < 7.
Fig. 10 Water connection
20
Putting into Operation
4.3 Electrical connections
Caution:
Observe the country-specific regulations when making connections (e.g. in Germany DIN VDE 0100 with residual current device (RCD)). Remember the connected loads and power values (see nameplate and also chapter " Technical data " on page 14 ).
The constant climate chamber is intended for operation on an electrical power system with a system impedance Z The operator must ensure that the constant climate chamber is operated only on an electrical power system that meets these requirements. If necessary, you can ask your local energy sup­ply company what the system impedance is.
Only appliances may be connected to external connections whose interfaces comply with the requirements for safety extra-low voltage (e.g. computer, printer).
at the point of transfer (service line) of a maximum of 0.292 ohm.
max
4.4 Switching on
To switch on the appliance, press the main switch on the front of the appliance ( Fig. 11 ).
Caution:
The first time the appliance is oper­ated, it must not be left unattended until it has reached the steady state.
Fig. 11 Switching on the constant climate chamber
21
Operation and control
5. Operation and control
5.1 Operating personnel
The constant climate chamber may only be operated by persons who are of legal age, and who have received instructions for the constant climate chamber. Personnel who are to be trained, instructed or who are undergoing general training may only work with the constant climate chamber under the continuous supervision of an experienced person.
5.2 Opening the door
► To open the door, turn the handle to the right ( Fig. 12 ). ► To close, press in the door knob.
5.3 Loading the constant climate chamber
Warning When loading the chamber with an unsuitable load, poisonous or explosive vapours or gases may be produced. This could cause the chamber to explode, and people could be badly injured or poi­soned. The chamber may only be loaded with materials/test objects which do not form any toxic or explosive vapours when heated up and cannot ignite (see also chapter " Intended use " on page 12 ). If there is any doubt as to the composition of materials, they must not be loaded into the constant climate chamber.
Caution:
Check the chamber load for chemical compatibility with the materials of the constant climate chamber (see page 12 ).
Replacing sliding shelf/shelves. The maximum quantity, and load capacity of the sliding shelves can be found in table in chapter " Technical data " on page 14 .
The chamber must not be loaded too tightly, so that proper air circulation in the working chamber is guaran­teed. Do not place any of the chamber load on the floor, touching the side walls or right below the ceiling of the working chamber ( Fig. 13 , see also the "correct loading" sticker on the appliance).
close
open
Fig. 12 Opening and clos­ing the door
If the load is unfavourable (too close together) it may take longer than normal to reach the set temperature under some circumstances.
22
Fig. 13 Correct placement of the chamber load
Operation and control
N
5.4 Basic information on operation
5.4.1 Switching appliance on and off
The constant climate chamber is switched on and off by pressing the main switch / push-turn control on the front of the appliance:
► Switching on: press the main switch so that it comes out of the appliance ( Fig. 14 ). ► Switching off: press the main switch so that it retracts back into the appliance ( Fig. 15 ).
Fig. 14 Switching on the constant climate chamber
Fig. 15 Switching off the constant climate chamber
5.4.2 User interface/ controller
In normal and programme modes, the desired parameters are entered on the operating panel of the controller on the front of the appliance ( Fig. 16 ). Basic settings, as well as those for time and printing, can also be made here. In addition, programmed and current parameters are displayed, as well as warning messages:
12435678910
IN 1
OUT
IN 2
rh
%
mb
card
DEFROSTERI
°C
MIN
°C
MAX
AUTO
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
set
t3
t2
t4
PRINT
on
off
SETUP
4
3
loop
2
1
push
IN 1
I
Fig. 16 Operating panel
1 Time display 2 Programme mode display (see page 29 ) 3 Interior lighting active (optional) 4 Display: Appliance locked with user-ID
card (see page 55 ) 5 Display: appliance is heating up 6 Temperature display 7 Display: appliance is cooling down 8 Temperature monitoring warning (see
page 43 ) 9 Temperature monitoring (see page 43 )
1315161718
111214
10 Humidity display 11 Display: Appliance is humidified 12 Warning: Water tank empty 13 Interior light (optional) 14 Chipcard reader 15 Operating mode display (see page 24 ) 16 Main switch /push-turn control 17 Set key 18 Alphanumeric text display for error and
status messages
23
Operation and control
5.4.3 Basic operation
set
set
All settings are selected by turning the push/turn control to the left or right ...
...and adjusted by turning it with the SET key held down.
5.4.4 Setting parameters
Normally, all setting actions on the operating panel described on the following pages are made in the same way:
set
set
set
1. Select the desired parameter with the push/turn control (menu item, e.g. temperature); then all other parameters go dark and the selected one flashes.
2. With the SET key held down, set the desired value (e.g. 58.0°C) with the push/ turn control.
3. Release the SET key, and the programme is started. The display briefly shows the value set, flashing. Then the current temperature is displayed and the constant climate chamber begins to heat up or cool down to the set tem­perature.
4. Settings for other parameters are made in the same way.
The control returns automatically to the main menu if the push/turn key or SET key is not used for approx. 30 seconds.
5.5 Operating modes
Constant climate chambers HPP can be operated in four different ways:
► Normal mode: The constant climate chamber runs in permanent operation at the temper-
ature and humidity values set on the operating panel. Operation in this mode is described from page 25 .
► Week time switch: The constant climate chamber runs at the set values only at certain
times. Operation in this mode is described from page 27 .
► Programme mode: Time sequences of temperature and humidity and fan values are
programmed (so-called ramps), which the test chamber automatically works through one after another. Operation in this mode is described from page 29 .
► Interface mode with computer/laptop (optional, see page 38 ).
PRINT
SETUP
Normal mode (see page 25 )
Fig. 17 Operating modes
24
Week time
switch
(see page 27 )
Programme
mode
(see page 29 )
Printer
(see page 41 )
Basic appliance
settings
(see page 41 )
Operation and control
5.6 Operating mode settings
1. Switch on the appliance by pressing the main switch (main switch comes out of appliance, see page 23 ).
set
2. Keep the SET key depressed for approx. three seconds and the selected mode starts flashing.
3. Select the desired operating mode/function (normal mode, week time switch,
set
programming mode, printer or basic appliance settings) by turning control with SET key held down.
set
4. Release the SET key, and the selected operating mode is saved.
5.6.1 Normal mode
In this operating mode, the constant climate chamber runs in permanent operation at the values set on the operating panel (see above). Example of settings: See next chapter 5.6.2 .
1. Load the constant climate chamber (see page 22 ).
2. Switch on appliance. To do this, press the push-turn control on the operating panel so that it comes out of the appliance (see page 23 ).
3. Select the normal operating mode with the push/turn control:
PRINT
SETUP
4. As described above, set the individual parameters with the push-turn control and the SET key:
Temperature setpoint Adjustment range: 0°C to 70°C
Interior light (optional)
t2
°C
Adjustment range: 0 % to 100 % in steps of 10%
The interior lighting can only be acti­vated at a working temperature of up to 40 ºC.
Temperature monitoring Adjustment range:
MIN MAX AUTO
°C
(see also page 43 )
MIN
AUTO
MAX
Humidity setpoint
rh
Adjustment range: 10 to 90 %rh,
%
off
Not all combinations of temperature and humidity are possible (see also page 10 ).
25
Operation and control
5.6.2 Settings example normal mode
At a humidity of 70 % rh and 60 % light intensity (optional), the climate chamber should heat up to 37 °C ( Fig. 18 ).
100 %
70 °C 60 °C
40 °C
20 °C
t
80 %
60 %
40 %
20 %
t
Fig. 18 Example for normal mode
1. Setting the normal operating mode:
Keep the SET key depressed for approx. 3 seconds and the cur­rent operating mode then begins to flash.
Select the operating mode
with the push-turn control, while the SET key is held down. After you let go of the SET key, the control is in the normal operating mode.
2. Setting the temperature setpoint: Hold down the SET key and set the desired temperature set-
point of 37.0 °C with the push-turn control.
100 %
80 %
60 %
40 %
20 %
PRINT
°C
t
SETUP
Release the SET key; the appliance will briefly flash, showing the temperature setpoint. Then the current temperature appears on the display and the controller begins to move to the set temperature of 37.0 °C.
► Heating up is indicated by the icon. ► Cooling down is indicated by the green cooling symbol .
3. Adjusting the light intensity (optional): Turn the push-turn control to the right until the lighting display
flashes. With the SET key held down, set the light intensity to 60 % with the push-turn control (six bars light up). Release the SET key. The interior light is now at 60 % intensity.
4. Setting the monitoring temperature: Turn the push-turn control to the right until the monitoring
temperature and the MIN- or MAX-icon flashes. Hold down the SET key and with the push-turn control set the overtemper­ature limit to 38.5 °C and the undertemperature limit to
35.5 °C. Turn the push-turn control to the right until the moni­toring temperature and the AUTO icons flash. Hold down the SET key and set to on with the push-turn control.
°C
MAX
MIN
AUTO
The tolerance band is set in the SETUP menu (see page 42 ).
26
5. Setting the humidity setpoint: Turn the push-turn control to the right until the humidity
display flashes. Hold down the SET key and set the desired humidity setpoint of 70.0 % rh with the push-turn control. After releasing the SET key the humidity setpoint briefly flashes. Then the current humidity value appears on the display and the con­troller begins to move to the set value.
Operation and control
rh
%
The humidification process is indicated by the
symbol.
The constant climate chamber is now running in permanent operation with the set values.
5.6.3 Week time switch
In this operating mode, the week time switch is active and the constant climate chamber switches on and
PRINT
off at the time programmed. During the OFF phase of the week time switch, the constant climate chamber is in standby
mode. The heating and cooling functions are switched off and the controller display shows the time, dimmed. During the ON phase, the constant climate chamber works with the set values for temperature and humidity.
The sequence of the week time switch repeats itself each week. In total, a maximum of nine time blocks can be programmed,
consisting of the switching on and switching off times:
Mo
on
off
Tu
We
Th
By turning the push/turn control, the following parameters can be selected and altered, as described in the chapter " Basic information on operation " on page 23 :
SETUP
Fr
Sa
h
Su
Weekday Adjustment range: Monday to Sunday
Day groups Adjustment range: Working days Mo–Fr Weekend Sat–Sun
No switch on time: ---­Appliance not switched on on this day
Switch on time (on) Adjustment range: 00:00 to 23:59 hours
Switch off time (off) Adjustment range: One minute beyond the
switch on time up to 24:00
Mo
Mo Mo
on
off
on
off
on
off
Tu
Tu Tu
We
We We
Th
Th Th
Fr
Fr Fr
h
h
Sa
Sa Sa
Su
Su Su
27
Operation and control
By turning further to the right, parameters (temperature setpoint etc.) can be selected as in the normal operating mode.
If no settings (temperature setpoint etc.) are made for the ON phase, the values from the normal operating mode are used by the controller.
For reasons of safety, you should always check that only one switch on time is programmed in the desired time blocks and days.
Direct setting of the temperature setpoint:
If the controller is in standby mode or the week time switch is in the ON phase, the tempera­ture setpoint can be directly accessed by briefly pressing the SET key. By turning the control to the right, you are returned to temperature monitoring and humidity. By turning to the left, you come back to the settings for the individual time blocks.
5.6.4 Settings example week time switch
The constant climate chamber should be switched on at 07.30 from Monday to Friday (work­ing day group) and switched off at 18.00. In addition, it should operate on Saturdays from
10.00 to 14.00 ( Fig. 19 ).
Mo
Fig. 19 Operation with week time switch (example)
1. Setting the week time switch operating mode Hold the SET key down for approx. three seconds; the
current operating mode then begins to flash. Select the week time switch operating mode with the push-turn control, while the SET key is held down.
Release the SET key, the control is now in the week time switch operating mode.
28
Tu
We
Thu
Fr
Sa
Su
PRINT
SETUP
Operation and control
2. Switch on Mo-Fr at 07.30 Turning the push/turn control to the left and select “Mo-
Fr on“ (group working days). Hold down the SET key and set the desired switch-on
time with the push/turn switch to 7:30.
3. Switch off Mo–Fr at 18.00 Select “Mo–Fr off“ (group working days) with the push/
turn control. Hold down the SET key and set the desired switch-off
time with the push/turn switch to 18:00.
4. Switch on Saturday at 10:00 With the push/turn control, select the “Sat on” icon. Hold down the SET key and set the desired switch-on
time with the push-turn switch to 10:00.
Mo
Mo
Mo
on
off
on
off
on
off
Tu
We
Th
Fr
Sa
Su
h
Tu
We
Th
Fr
Sa
Su
h
Tu
We
Th
Sa
Su
Fr
h
5. Switch off on Sa at 14:00 With the push/turn control, select the “Sat off” anwäh-
len.
Tu
on
off
We
Th
Fr
Mo
Hold down the SET key and set the desired switch-off time with the push-turn switch to 14:00.
5.6.5 Programme mode
In this operating mode, up to 40 freely progammable sequences (ramps) can be set with various combinations of temperature and humidity, which the constant climate chamber then processes automatically one after another.
Not all combinations of temperature and humidity are possible (see also page 10 ).
PRINT
Setting the programming operating mode
1. Press the SET key and keep it held down.
2. Select the programming mode with the push/turn
control, while the SET key is held down.
3. Select the EDIT
function with the push-turn
control.
PRINT
Sa
Su
h
SETUP
SETUP
29
Operation and control
Sa
F
r
S
D
O
You can now select and modify the following parameters in turn (see also the adjustment example on page 34 ):
STERI
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
°C
MIN
°C
MAX
AUTO
IN 1
IN 2
OUT
%rh
mb
4. Delayed programme start: Switch-on day Adjustment range: Monday to Sunday, workdays Mo-Fr, weekends Sa-Sun, every day Mon-Sun
or no days. If no week day is set, the appliance starts immediately ( instant start ) after the start of the programme. In the example shown: Switch-on day Monday.
STERI
Tu
Mo
We
on
off
Sa Su
Fr
Th
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
°C
MIN
°C
MAX
AUTO
IN 1
IN 2
OUT
%rh
mb
5. Delayed programme start: Switch-on time Adjustment range: 00:00 to 23:59 (shown: Switch-on time 8:00)
If no switch-on day is shown, then no switch-on time can be selected, and the pro­gramme starts immediately ( instant start ). In the example shown: Switch-on time 8:00.
STERI
Sa Su
Tu
Mo
We
on
off
a
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
MIN
°C
MAX
AUTO
IN 1
IN 2
OUT
mb
6. Duration of first ramp segment Adjustment range: 1 minute to 999 hours. In the example shown: Duration of first ramp seg-
ment: 1:00 hour.
STERI
ERI
DEFRO
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
EFR
°C
MIN
°C
MAX
AUTO
7. Setpoint temperature/temperature to end of ramp segment Adjustment range: 5 °C ... 70 °C. In the example shown: temperature 37.0 ºC.
30
Operation and control
2
OUT
STERI
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
°C
MIN
°C
MAX
AUTO
IN 1
IN 2
OUT
%rh
mb
8. Light intensity during the first ramp segment (optional): Adjustment range: 0 % to 100 % in steps of 10%. In the example shown: Light intensity 60 %
(six bars are lit up).
The interior lighting can only be activated at a working temperature of up to 40 ºC.
STERI
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
°C
MIN
°C
MAX
AUTO
IN 1
IN 2
IN
OUT
%rh
mb
9. Setpoint humidity/humidity to end of ramp segment Adjustment range: 10 to 90 % rh. In the example shown: humidity 80.0 % rh.
Each ramp must be completed with a close statement connecting the ramp to the next one. These commands thus control the programme sequence:
STERI
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
°C
MIN
°C
MAX
AUTO
IN 1
IN 2
OUT
%rh
mb
10. Close statement of the ramp segment Setting: NEXT, SPWT (T), SPWT (H), SPWT (TH), LOOP, HOLD, END (shown: command end, see also
chapter 5.6.6 " Close statements for ramp segments ").
STERI
Tu
Mo
We
on
off
Sa Su
Fr
Th
h
t1
t3
PRINT
t4
SETUP
t2
loop
4
3
2
1
DEFRO
°C
MIN
°C
MAX
AUTO
IN 1
IN 2
OUT
%rh
mb
11. Programme write mode Leave EDIT
Turn push/turn control to the right until EXIT appears in the display, and press the SET key briefly to confirm.
31
Operation and control
After releasing the SET key ...
► ... a new programme can be created
as described above, or an existing one be edited
EDIT
► ... the programme can be stopped STOP
► ... the programme can be started START
5.6.6 Close statements for ramp segments
Each ramp must be completed with a close statement connecting the ramp to the next one. These commands thus control the programme sequence:
NEXT Connect the next programme segment.
SET-POINT WAIT (T – temperature) Wait until setpoint has been reached. Appliance starts the next programme segment only when the programmed setpoint temperature has been reached, even if the set heating up time has already elapsed.
SET-POINT WAIT (H – humidity) Wait until setpoint humidity has been reached. Appliance starts the next programme segment only when the programmed setpoint humidity has been reached, even if the set heating up time has already elapsed.
SET-POINT WAIT (TH – temperatur and humidity) Wait until the setpoint temperature and setpoint humidity has been reached. Appliance starts the next programme segment only when the programmed setpoint temperature and programmed setpoint humidity have been reached, even if the set heating up time has already elapsed.
Ramp repeat function The programme entered is repeated after all programmed seg­ments have been run.
1-99 = repeats cont = endless loop repeat function
32
Programme end while maintaining the temperature and humidity of last programme ramp
Programme end, switching off the heating /cooling function and humidity
Operation and control
Close
command
ramp
segment
No. 4
next
Segment5
°C
Delayed
programme start
Close
command
ramp
segment
No. 1
spwt (t)
Segment1
Close
command
ramp
segment
No. 2
Segment2
next
Close
command
ramp
segment
No. 3
spwt (tH)
Segment4
Segment3
Fig. 20 Schematic example of the use of ramp segment close statements
Close
command
ramp
segment
No. 5
end
t=time
33
Operation and control
5.6.7 Settings example programming mode
On Monday at 8:00, the constant climate chamber should heat up to 37 °C, with 50 % light intensity (optional), as quickly as possible and reach a relative humidity of 70 % rh. Once the temperature and humidity have been reached, the constant climate chamber should retain the setpoint values for 45 minutes at 80 % light intensity and then cool down within one hour, at a light intensity of 30 %, to a humidity of 50 % rh and 15 °C ( Fig. 21 ).
Ramp 1 Ramp 2 Ramp 3
60 °C
40 °C
20 °C
80 %
50 %
30 %
70 % rh
50 % rh
0.01 h
Mo 8.00 h
0.45 h
1.00 h
t
Fig. 21 Settings example programming mode
Before programming ramp sequences, especially before programming complicated ones, it is recommended that you prepare a similar plan to ensure that you enter the required ramp commands correctly, as described below. For better orientation, it is recommended that you programme large programmes graphically on the computer using the "Celsius" software.
34
Operation and control
1. Setting the programme operating mode: Hold the SET key down for approx. three seconds; the current operating mode then begins to flash. Select the programme operating mode with the push/turn control while holding down the Set key. After releasing the SET key, the controller is in the pro­gramme mode.
2. Edit programme: Select EDIT with the push/turn control while holding down the SET key. After releasing the SET key, the controller is in the pro­gramme write mode.
3. Weekday for delayed programme start: Set the start day MO by turning the push-turn control while the SET key is held down.
4. Set the time for delayed programme start: Select the time display with the push/turn control. Hold down the SET key and adjust the time to 8:00 with the push/turn control.
Mo
PRINT
h
SETUP
5. Set the duration of the first ramp segment: Turn the push/turn control to the right until the time display flashes. Hold down the SET key and adjust the time to 0:01 with the push/turn control.
6. Set the temperature of the first ramp segment: Turn the push/turn control to the right until the tempera­ture display flashes. Hold down the SET key and set the desired temperature setpoint to 37.0 °C with the push/turn control.
7. Setting the light intensity of the first ramp segment (optional): Turn the push-turn control to the right until the lighting display flashes. Hold down the SET key and set the desired light intensity of 50 % (five bars are lit up).
8. Set the relative humidity of the first ramp segment: Turn the push/turn control to the right until the humidity display flashes. Hold down the SET key and set the desired humidity setpoint to 70.0 %rh with the push/turn control.
h
°C
%rh
35
Operation and control
9. Set the close statement of the first ramp segment: Turn the push/turn control to the right until a segment close statement, e.g. end, appears. Hold down the SET key and set the close statement SPWT [TH] with the push/turn control.
10. Set the duration of the second ramp segment: Turn the push/turn control to the right until the time display flashes. Hold down the SET key and adjust the time to 0:45 with the push/turn control.
11. Set the temperature of the second ramp segment: Turn the push/turn control to the right until the tem­perature display flashes. Hold down the SET key and set the desired temperature setpoint to 37.0 °C with the push/turn control.
h
°C
12. Setting the light intensity of the second ramp segment (optional): Turn the push-turn control to the right until the lighting display flashes. Hold down the SET key and set the desired light intensity of 80 % (eight bars are lit up).
13. Set the relative humidity of the second ramp segment: Turn the push/turn control to the right until the humidity display flashes. Hold down the SET key and set the desired humidity setpoint to 70.0 % rh with the push/turn control.
14. Set the close statement of the second ramp segment: Turn the push/turn control to the right until a segment close statement, e.g. end, appears. Hold down the SET key and set the close statement next with the push/turn control.
15. Set the time for the third ramp segment: Select the time display with the push/turn control. Hold down the SET key and set the time 1:00 with the push/turn control.
%rh
h
16. Set the temperature of the third ramp segment: Turn the push/turn control to the right until the tem­perature display flashes. Hold down the SET key and set to 15.0 °C with the push/ turn control.
36
°C
17. Setting the light intensity of the third ramp segment (optional): Turn the push-turn control to the right until the lighting display flashes. Hold down the SET key and set the desired light intensity of 30 % with the push-turn control (three bars are lit up).
18. Set the relative humidity of the third ramp segment: Turn the push/turn control to the right until the humidity display flashes. DHold down the SET key and set the desired humidity setpoint to 50.0 % rh with the push/turn control.
19. Adjust the close statement of the third ramp segment: Turn push/turn control to the right until a close state­ment appears in the display, e.g. end, and press the SET key briefly to confirm.
20. Leave the EDIT programme write mode: Turn push/turn control to the right until EXIT appears in the display, and press the SET key briefly to confirm.
Operation and control
%rh
21. Set temperature monitoring: Turn the push-turn control to the right and adjust the temperature monitoring (for more detailed information on this, see page 43 ).
22. Start programme: Turn the push/turn control to the right until the stop icon
flashes. Hold down the SET key and select the start icon the push-turn control. Release the SET key, and the pro­gramme is started.
with
MIN
°C
MAX
AUTO
37
Operation and control
5.6.8 Operation with computer/ laptop (optional)
The constant climate chamber can optionally be used, controlled and programmed with a computer/laptop. It has corresponding communication interfaces on the rear side for this purpose (see page 50 ).
The control of the appliance with the “Celsius“ software is described in its own separate manual.
5.7 Ending operation
1. Switch off appliance. To do this, press the main switch on the operating panel so that it clicks home into the appliance (see Fig. 22 ).
2. Open the door
3. Remove the chamber load.
4. Check the freshwater tank and fill up if necessary (see page 21 ).
Fig. 22 Switching off the constant climate chamber
38
Malfunctions, warning and error messages
6. Malfunctions, warning and error messages
Warning! After removing covers, live parts may be exposed. You may receive an electric shock if you touch these parts. Malfunctions requiring in­tervention inside the appliance may only be rectified by electricians. You must read the separate service manual for this.
Do not try and solve the error yourself, but contact an authorised customer service point for MEMMERT appliances or contact the MEMMERT customer services department directly (see page 2 ).
In case of enquiries, please always specify the model and appliance number on the nameplate (see page 14 ).
6.1 Warning messages temperature monitoring/humidification
See page 46 .
Error description Cause of error Rectifying errors See
General faults Controller display does
not light up
Appliance cannot be operated
Error messages in monitoring display Caution icon
flashes Monitoring controller has
Power supply interrupted
Miniature fuse or appliance fuse faulty
Mainboard faulty Replace
Appliance locked by UserID card
Push/turn control faulty Replace main switch
switched off heater, since temperature difference between operating and monitoring controller is too small
Check power supply
Check fuse, replace if necessary
power module
Undo lock with UserID card
module with push/turn control
Increase temperature difference between monitoring temperature and working tempera­ture.
Replace Pt100 tem­perature sensor of monitoring controller if necessary
Service manual
Service manual
page 55
Service manual
page 44
Service manual
Malfunctions in humidification/dehumidification Humidification
doesn't work
Dehumidification doesn't work
No water supply Fill water tank, check
Fault in the dehumidifica­tion system
page 20 that tube is correctly connected
Service
manual
39
Malfunctions, warning and error messages
For malfunctions that are not listed here or for error messages on the display (e.g. E-3), please read the service manual for the appliance or contact the MEMMERT customer service if the error correction suggested here is not successful.
6.2 Power failure
In case of a power failure, the constant climate chamber operates as follows:
In normal and week time switch operating modes
After the power supply has been restored, operation is continued with the parameters set. The time and the duration of the power failure is documented in the log memory (see page 52 ).
In programming mode
► After a power failure of less than 60 minutes, the current programme is continued from
the point at which it was interrupted. The time and the duration of the power failure is documented in the log memory (see page 52 ).
► For a power failure of more than 60 minutes, the constant climate chamber starts in
manual operating mode for safety reasons and all setpoint values are changed to safe default values (see table below).
For remote (computer) operation
If there is a power failure in remote operation, the constant climate chamber starts in manual operating mode for safety reasons and all setpoint values are changed to safe default values (see table). The programme can only be continued from the computer. The time and the dura-
tion of the power failure is documented in the log memory (see page 52 ).
Parameters Default value
Temperature
Humidity 20 % rh
20 ºC
40
Advanced functions
7. Advanced functions
7.1 Printer
The constant climate chamber is equipped with a parallel printer port as standard, just as used in computers.
A standard PCL3-compatible inkjet printer which has a parallel port interface (e.g. HP DeskJet 5550 or HP DeskJet 9xx) can be connected to the printer port on the rear of the appliance (see page 10).
Make sure that a shielded interface cable is used. The shielding must be connected to the plug casing.
The controller has an internal log memory (see page 52 ). The log data can be printed out in this mode via the connected printer.
If a colour printer is connected, the various graphs are printed out in colour. On a printout, the GLP header is also printed automatically, and contains the following details:
► Date of printout ► Period of log ► Consecutive page numbers ► Serial numbers and appliance name
By turning the push/turn control and holding down the SET key, the following parameters can be selected and altered one after another, as described in the chapter " Basic information on operation " on page 23 :
Querying the date of the first print page
Querying the date of the last print page
Starting graphical printout
Printing programme and configuration page
Leaving the print menu and returning to the main menu
7.2 Basic appliance settings (Setup)
In this operating mode, the basic settings for the appliance can be made.
By turning the push/turn control, the following parameters can be selected and altered while the SET key is held down, as described in the chapter " Basic information on operation " on page 23 :
Clock time in 24 hr. format
Conversion to summer time is not automatic, but must be done manually.
PRINT SETUP
41
Advanced functions
Date The controller contains a calendar which automatically
accounts for the different lengths of months, and for leap years.
Weekday
Year Adjustment range: from 2000 to 2100
Acoustic signal at programme end
ENDSOUND
Setting: OFF or ON
Acoustic Signal for alarm, e.g. over/undertemperature
ALARM sound Setting: OFF or ON
Tu
Communication address Adjustment range: 0 to 15 (see chapter „ Communication
interfaces “ on page 50 )
Ratio between upper and lower heat (only for constant cli­mate chambers HPP 749)
Adjustment range: -50% to +50% (see also chapter Heat output distribution (BALANCE) on page 47 )
Tolerance band ASF Adjustment range: 2 to 20 °C (see page 45 )
Language Setting: GERMAN, English, franCAIS, ESPANOL and italIANO
Compensation correction values (CAL 1-3, rh20, RH90) for customer-side calibration of temperature and humidity (see chapter “ Heat output distribution (BALANCE) “ on page 47 ).
Close setup Save all settings and leave the SETUP mode
42
Advanced functions
The realtime clock, which is set in the SETUP, contains the date and clock time. The realtime clock is used for logging purposes in accordance with GLP. Date and clock time are specified on the log printout. On graphical printouts, the time axis is labeled with the realtime. The clock is battery-buffered and is independent of the mains connection. The integrated Lithium battery of the type CR 2032 has a lifetime of approx. 10 years.
7.3 Temperature monitoring and safety equipment
The monitoring temperature is measured via a separate Pt100 temperature sensor in the chamber interior (see Fig. 9 on page 20 ). The monitoring unit is used to protect the chamber load and as a protection for the appliance and surroundings.
Temperature monitoring can be adjusted independently of the operating modes.
In ramp operation mode, the monitoring temperature must always be set at least 3 K above the maximum working temperature.
6
1
MAX
2
Fig. 23 Temperature monitoring display 1 Visual alarm icon
lit up: TB alarm
flashing: TWW alarm, TWB alarm, ASF alarm 2 Undertemperature protection 3 automatic temperature monitor (ASF, see page 45 ) 4 Overtemperature protection (TWW, TWB, see below) 5 Response temperature 6 Acoustic alarm icon
MIN
AUTO
5
°C
4
3
43
Advanced functions
°C
7.3.1 Electronic temperature monitoring (TWW)
Overtemperature protection Adjustment range: -5 ... +75 °C Setting: Select the Hold down the SET key and adjust the temperature limits with the
push/turn control.
MAX
icon with the push-turn control.
MIN
AUTO
Undertemperature protection Adjustment range: -5 ... +75 °C Setting: Select the
MIN
icon with the push/turn control. Hold down the
MIN
SET key and adjust the temperature limits with the push/turn con­trol.
The lower alarm limit value cannot be set higher than the top one. If no undertemperature protection is required, set the low­est temperature.
The manually set monitoring temperature
MIN
and
MAX
of the overtemperature control is monitored by an adjustable over/undertemperature controller (TWW) protection class 3.3 acc. to DIN 12880.
MAX
°C
MAX
If the manually set monitoring temperature
MAX
is exceeded, the TWW takes over tempera­ture control and begins to regulate the monitoring temperature ( Fig. 24 ). The alarm icon flashes as a warning
.
If the acoustic alarm is switched on in the SETUP (see page 42 ), the TWW alarm is additionally signalled by an interval sound. If the SET key is pressed, the acoustic signal can be temporarily switched off until the next alarm event occurs.
°C
Emergency operation
Setting MAX
Set temperature
Controller error
t
Fig. 24 Schematic diagram of how the TWW temperature monitoring functions
44
Advanced functions
7.3.2 Automatic temperature monitor (ASF)
ASF is a monitoring device that automatically follows the set temperature setpoint within an adjustable tolerance band ( Fig. 25 ).
The ASF is activated – if switched on – automatically if the actual temperature value reaches 50% of the set tolerance band of the setpoint (in the example 50°C ± 1°C) is reached for the first time (section A). The activation of the ASF is shown by the brightly lit
When the temperature moves outside the set tolerance band around the setpoint (in the example in Fig. 25 : 50°C ± 2°C) – e.g. if the door is opened during operation (section B of il­lustration) – the alarm is set off. This is shown by the flashing
AUTO
and icons.
If the acoustic alarm is switched on in the SETUP (see page 42 ), the ASF alarm is additionally signalled by an interval sound. If the SET key is pressed, the acoustic signal can be temporarily switched off until the next alarm event occurs.
The ASF alarm goes off automatically as soon as 50% of the set tolerance band of the setpoint (in the example 50°C ± 1°C) is reached again (section C).
If the temperature setpoint is altered, the ASF is automatically disabled temporarily (see in the example: The setpoint is changed from 50 °C auf 25 °C, section D) until it has reached the tolerance range of the new temperature setpoint (section E).
AUTO
icon.
°C
40 °C
ABCDE
40 °C
37 °C
34 °C
34 °C
33 °C
27 °C
ASF active
AUTO AUTO AUTO
ASF alarm
ASF active ASF active
Fig. 25 Schematic diagram of how the ASF temperature monitoring functions
t
45
Advanced functions
Switching on the automatic temperature monitor: Select the AUTO icon with the push/turn control. Hold down the SET key and set to on
with the push-turn control.
Switching off the automatic temperature monitor: Select the AUTO icon with the push/turn control. Hold down the SET key and set to off with the push/turn control.
The tolerance band for the ASF can be adjusted in the SETUP (see page 42 ).
7.3.3 Warning messages
MIN
MIN
°C
MAX
AUTO
°C
MAX
AUTO
A repeated acoustic signal indicates an error in the temperature control system or in the hu­midification system. It is set off in the following cases:
Overtemperature protection is triggered. Check the MAX set­ting and increase if necessary (see Chapter 7.3.1 ).
Undertemperature protection is triggered. Check the MIN set­ting and reduce if necessary (see Chapter 7.3.1 ).
Automatic monitoring function is triggered. Check the toler­ance value ASF-Set set in the SETUP menu (see page 42 ).
Water tank empty. Fill up with water (see page 20 ).
Humidity exceeds the preset setpoint for longer than 30 minutes. Open door for 30 sec. and wait to see if the control­ler steadily adjusts to the setpoint. If the error occurs again, contact the customer service.
This monitoring function only begins to work after the humidity setpoint has been reached. The acoustic alarm can be temporarily switched off by pressing the SET key.
46
Advanced functions
7.4 Heat output distribution ( BALANCE)
For constant climate chambers HPP 749, application-specific correction of the heat output distribution (BALANCE) is possible between the upper and lower heating groups in the SETUP (setting: see page 42 ). The adjustment range is from –50 % to +50 %.
Setting 0 % restores the heating output distribution factory settings.
upper heat output upper heat output
lower heat output
-20%
Fig. 26 Left: The –20 % setting causes the lower heating groups to emit 20 % less heat than the upper heating groups. Right: The +30 % setting causes the lower heating groups to emit 30 % more heat than the upper heating groups.
lower heat output
+30%
47
Advanced functions
7.5 Calibration
7.5.1 Temperature calibration
The constante climate chamber can be calibrated customer-specifically using three calibration temperatures of your choice:
► CAL.1 temperature calibration at low temperature ► CAL.2 temperature calibration at medium temperature ► CAL.3 temperature calibration at high temperature
For each selected balance point ( Fig. 27 ) a positive or negative compensation correction value can be set between –4.9 ºC and +4.9 ºC. There must be a difference of at least 10 K between the individual balance points.
CAL 3
+0,8°C
factory
calibration
CAL 1
+0,5°C
5°C
0°C
CAL 2
-0,4°C
37°C
20°C
Fig. 27 Temperature calibration (example)
Setting:
1. Set the desired compensation temperature in the SETUP (see page 42 ) and set the accom-
panying compensation correction value to 0.0 °C.
2. With a reference instrument, measure the deviation in the stationary state in the selected
compensation temperature.
3. Set the compensation correction value in the SETUP. If the measured reference tempera-
ture is too low, the compensation correction value must be set with a negative sign.
4. Perform a control measurement with the reference instrument.
5. Repeat the procedure for the other two balance points if necessary.
48
Advanced functions
°C
°C
Example: Temperature deviation at 30 °C should be corrected.
1. Set compensation temperature CAL.2 in the SETUP to 30.0°C and set accompanying
compensation correction value to 0.0°C:
h
°C
°C
2. With a calibrated reference instrument and at a set setpoint temperature of 30 °C in nor-
mal operation, an actual temperature of 29.6 °C is measured.
3. Set the compensation correction value for CAL.2 in the SETUP to - 0.4°C:
h
°C
°C
4. After the calibration procedure, the reference instrument should now display 30°C.
5. With CAL.1, another compensation temperature below CAL.2 can be programmed in the
same way, and with CAL.3, one lying above this.
If all compensation correction values are set to 0.0°C, the factory calibration settings are restored.
7.5.2 Humidity calibration
The constant climate chamber can be calibrated for the individual customer by means of two balance points at 20 and at 90 % relative humidity. For each selected balance point, a positive or negative compensation correction value can be set between and –10 % and +10 % ( Fig. 28 ).
rh 90
-2,0 %
rh 20
+3,0 %
Default calibration
80% 100%
Fig. 28 Humidity calibration (example)
49
Advanced functions
rh
%
%
IN 2
OU
Setting:
1. Set the desired humidity balance point in the SETUP (see page 42 ) and set the accompa-
nying compensation correction value to 0.0 %rh.
2. With a reference instrument, measure the deviation in the stationary state in the selected
humidity balance point.
3. Set the compensation correction value in the SETUP. If the measured reference humidity is
too low, the compensation correction value must be set with a negative sign.
4. Perform a control measurement with the reference instrument. The procedure can be performed with humidity balance points of 20 % rh and 90 % rh. Example: Humidity deviation at 90 % should be corrected.
1. Set humidity balance point in the SETUP to RH 90 and set the accompanying compensation
correction value to 0.0 % rh:
Tu
Mo
We
on
off
Sa Su
Fr
Th
t1
t3
t2
t4
PRINT
SETUP
4
3
loop
2
1
STERI DEFRO
°C
rh
°C
MAX
MIN
AUTO
%
mb
IN 1
OUT
IN 2
2
CO
mb
2. With a calibrated reference instrument, an actual humidity of 88 % rh is measured at nor-
mal operation, with a set setpoint humidity of 90 % rh.
3. Set the compensation correction value in the SETUP for RH 90 to –2.0 % rh:
OUT
T
Tu
Mo
We
on
off
Sa Su
Fr
Th
t1
t3
t2
t4
PRINT
SETUP
4
3
loop
2
1
STERI DEFRO
°C
°C
MAX
MIN
AUTO
IN 2
rh
%
mb
IN 1
OUT
IN 2
2
CO
mb
4. The reference instrument should display 90.0 % rh after the calibration procedure. With RH 20, a further comparison can be programmed at 20 % relative humidity.
If all compensation correction values are set to 0.0 % rh, the factory calibration settings are restored.
7.6 Communication interfaces
Depending on the model, the constant climate chamber can be fitted with different commu­nication interfaces (USB, RS 232/485, Ethernet). These are located on the rear of the appliance.
7.6.1 USB interface
The chamber is fitted by default with a USB interface in accordance with the USB specification. With this interface it is possible to control and log the chamber remotely from the computer. For this, the “Celsius“ software is used.
The chamber must be given a unique device address in the SETUP submenu, menu item AD- DRESS, via which the computer communicates with the oven (see page 42 ). The default setting is ADDRess 0. Using this, the appropriate incubator can be selected and programmed from the computer.
If several chambers are to be connected to a computer via USB interface, an appropriate inter­face on the computer and a separate cable are required for each chamber.
The maximum cable length is 5 m.
50
Advanced functions
7.6.2 Communication interfaces RS232/RS485 (optional)
The chamber can be optionally equipped with a RS232 serial communication interface in ac­cordance with DIN 12900-1 or a RS485 interface, instead of a USB interface ( Fig. 29 and Fig. 30 ).
► With the RS232 interface, it is possible to control and log the chamber remotely from the
computer. If several chambers are to be connected to a computet via RS232 interface, an appropriate interface on the computet and a separate cable are required for each cham­ber. The maximum cable length is 15 m.
► The RS485 interface enables the networking of several chambers (up to 16) with one
computer via a shared two-wire cable. The computer needs to be equipped with either a RS485 interface or with an RS232/RS485 adapter.
Connecting the wires is done individually with a shielded cable, depending on the installa-
tion site. The maximum total cable length is 150 m.
Interface converter
RS232
RS485
Fig. 29 PC RS 485 connection with adapter Fig. 30 PC RS 232 connection
In both cases, each chamber must be given a unique device address in the SETUP submenu, menu item ADDRESS (see page 42 ), via which the computer communicates with the chamber. The default setting is ADDRess 0. Using this address, the appropriate oven can be selected and programmed from the computer.
The chamber can be connected to the computer using a shielded interface cable. The shield­ing must be connected to the plug casing.
If the serial port is not used, put on the cover included.
51
Advanced functions
7.6.3 Connecting test chambers to a network with Ethernet interface
The constant climate chamber can optionally be equipped with an Ethernet instead of a USB interface.
192.168.1.216
LAN 1: 192.168.1.233
LAN 2: 192.168.1.215
LAN 3: 192.168.1.241
Fig. 31 Connecting one or more test chambers to a network using an Ethernet interface (schematic diagram)
For identification purposes, each appliance connected must have its own unique IP address. Each chamber is delivered by default with the IP address 192.168.100.100. The programme “ XTADMIN“, which can be found on the “Celsius“ CD-ROM, can be used to change the IP address.
How the IP address is changed and the oven is logged on is described in the ”Celsius“ manual.
7.6.4 Log memory
The controller continually logs all relevant measured values, settings and error messages at 1-minute intervals.
The internal log memory is listed as a ring memory, i.e. the oldest log data are always over­written automatically with new data.
The logging function cannot be switched off, but is always active. The measured data are stored in the controller, safe from manipulation. For documentation purposes the controller memory can be read out via the Celsius control software. Each dataset is stored with a unique timestamp.
The internal log memory has a size of 1024 kB. This corresponds to a storage capacity for about three months in permanent operation.
Since large amounts of data are stored during ramp mode, this can reduce the maximum logging time.
52
Advanced functions
If the power supply is interrupted, the time of the power cut and the return of voltage are stored in the controller.
Reading in the log memory to the computer via USB interface
Using the “Celsius“ progamme, the log memory of the controller can be read out to a com­puter and from there be displayed graphically, printed out and stored. The log memory of the controller is not modified or deleted by the reading out.
Printing out log memory
(see also chapter " Printer " on page 41 ) For a printout, the GLP header is also printed automatically, and contains the following details:
► Date of printout ► Period of log ► Consecutive page numbers ► Serial numbers and appliance name
If the printer is not ready (e.g. ink cartridge or paper tray empty), no log data will be lost. Multiple printouts can also be made, since the log memory is not deleted after printing.
7.6.5 Memory card MEMoryCard XL
On the MEMoryCard XL ( Fig. 32 ), a temperature control programme with up to 40 ramp segments can be programmed. This can be programmed directly on the controller or via the “Celsius“ programme.
To programme the MEMoryCard XL with the computer and the “Cel­sius“ software, please read the user manual for “Celsius“ or the online help.
For the sake of keeping an overview, it is recommended that you programme large programmes graphically on the computer. If a MEMoryCard XL is programmed, it can only be read in in the same type of chamber for which it was programmed.
The text field of the MEMoryCard XL can be filled individually with text or diagrams.
Fig. 32 MEMoryCard XL
Directly programming the MEMoryCard XL via the constant climate chamber
1. Push the MEMoryCard XL into the card reader in the appliance operating panel (see Fig. 2
on page 9 ).
2. Programming the chamber as described in the " Programme mode " Chapter from page
29 . The chosen settings are written directly to the card and stored on it. After the card is removed, the programme stored internally in the controller is activated again.
Programming the MEMoryCard XL on the computer via the constant climate chamber
1. Connect the computer with an interface cable to the USB interface of the chamber (see
" USB interface " Chapter on page 50 ).
2. Push the MEMoryCard XL into the card reader in the appliance operating panel (see Fig. 2
on page 9 ).
53
Advanced functions
3. Programme the chamber on the computer. The chosen settings are written and stored on
the card.
Via the “Celsius“ software, the MEMoryCard XL can be provided with write protection. The programme on the card can then no longer be altered on the controller.
Programme alterations via the controller are only possible if the write protection has been disabled from the computer with the “Celsius“ software.
Programming the MEMoryCard XL from the computer with the read-write device
Using the read-write device which can be purchased separately ( Fig. 33 ), the MEMoryCard XL can be programmed offline on the computer with “Celsius“ without the need for a constant climate chamber being connected. When you do this, make sure that the contacts on the MEMoryCard XL are pointing upwards to the markings on the read-write device.
Fig. 33 Read-write device
The programme remains stored on the MEMory-Card XL even after it is removed from the appliance. It can also be overwritten at any time with “Celsius“ via the computer.
Logging on the MEMoryCard XL
During a programme sequence running from the chip card, the humidity and temperature setpoints are continually logged on the memory card. These can be read in via “Celsius” after the programme is finished and printed out. This is described in the “Celsius“ user manual.
There is a certain amount of storage space available for logging, depending on the pro­gramme duration. The scanning rate is set automatically by the controller, depending on the programme duration.
The actual value can be logged on the MEMoryCard XL at one minute intervals for a programme lasting up to 135 hours. For programmes lasting longer, the scanning rate is lengthened to a maximum of 30 min.
At each programme start, the logging is restarted and old log data is overwritten.
54
7.6.6 User ID card (optionally available as an accessory)
access authority card
Name:
ID:
_____________________
_____________________
The device number of the appliance and an unique user number are stored in encrypted form on the User-ID card ( Fig. 34 ). The User-ID card therefore works only in the appliance with the corresponding serial number.
Every login process with the User-ID card is logged in the internal Flash memory of the controller.
If the User-ID card has been inserted, the menu item ID-LOCK also appears in the " Basic appliance settings (Setup) ” from page 41 ). If the setting is set to ON, the constant climate chamber is locked against all alterations once the chip card is removed.
SETUP
menu (see
Fig. 34 User ID Card
Advanced functions
The lock via the User-ID card is displayed via the flashing key icon
on the operating
panel (see page 9 ).
If the constant climate chamber is locked via the User-ID card, no programme operation with the MEMoryCard XL is possible, since this card could be removed at any time and modified externally.
55
Maintenance and Servicing
8. Maintenance and servicing
Warning! Disconnect the mains plug before any cleaning or maintenance work.
8.1 Cleaning
Regular cleaning of the easy to clean chamber interior prevents build up of material remains, which over time could impair the appearance and functionality of the stainless steel chamber.
The metal surfaces of the chamber can be cleaned with normal stainless steel cleaning agents. Make sure that no rusty objects come into contact with the working chamber or with the stainless steel housing. Rust deposits lead to an infection of the stainless steel.
If rust spots should appear on the surface of the working chamber, due to impurities, immedi­ately clean and polish the affected area.
Do not clean the operating panel, the plastic input module and other plastic parts of the chamber with caustic or solvent-based cleaning agents.
8.1.1 Cleaning the Peltier cooling modules
In order to guarantee the perfect function and long lifetime of your Peltier cooling modules, it is absolutely essential that you remove dust deposits from the heat sink on the rear of the appliance (with a vacuum cleaner, paintbrush or bottle brush, depending on the amount).
To make cleaning easier, the cover can be removed after the screws have been loosened ( Fig. 35 ).
8.2 Regular maintenance
Every three months if in permanent operation
► Grease the moving parts of the doors (hinges
and lock) with thin silicon grease and check that the hinge screws are not loose.
► Check that door seals fit tightly, adjust door if
necessary (see chapter 8.3 ).
Annually:
► Grease the moving parts of the doors (hinges and lock) with thin silicon grease and check
that the hinge screws are not loose.
Fig. 35 Cover of the Peltier cooling modules on the rear of the appliance
► Check that door seals fit tightly, adjust door if necessary (see chapter 8.3 ).
56
Maintenance and Servicing
8.3 Adjusting door
A well-closing door is indispensable for climate chambers. On Memmert appliances, the tight closing of the door is optimally guaranteed by a chamber seal and a door seal. In permanent operation, it is possible that the flexible seal material will begin to sag. To ensure that the door closes exactly, however, an adjustment may be necessary:
1. Undo mounting bolts ( Fig. 36 , 2) at the top and bottom of door.
2. The top section of the door hinge (1) can now be moved slightly in the direction of the
arrow.
3. After undoing the Allen set screw (5), the door can be adjusted by turning the eccentric (3)
with a screwdriver. The Allen set screw (5) is fixed with lock washer varnish. It can be undone with a jolting
motion using a 2 mm Allen key.
4. Apply lock washer varnish to the Allen set screw (5) and screw tight the set screw.
5. Tighten the mounting bolts (2) again. The locking plate (7) can also be adjusted in the direction of the arrows after undoing the
screws (6) ( Fig. 37 ). Afterwards, screw the locking plate back firmly.
2
Fig. 36 Adjusting the door 1 Upper section of the door hinge 2 Mounting bolts 3 Eccentric tappet 4 Eccentric socket 5 Allen set screw
8.4 Repairs and service
Warning! After removing covers, live parts may be exposed. You may receive an electric shock if you touch these parts. Disconnect the mains plug before removing any covers. Any work inside the unit may only be performed by qualified electricians.
1
3 4
5
Fig. 37 Adjusting the locking plate 6 Screw 7 Locking plate
6 7
Repairs and service work are described in a separate service manual.
57
Storage and disposal
9. Storage and disposal
9.1 Storage
The constant climate chamber may only be stored under the following conditions.
► dry and in an enclosed, dust-free room ► frost-free ► disconnected from the power supply
Before storage, remove the water tube and empty the water tank (see page 21 ).
9.2 Disposal
This product is subject to the directive 2002/96/EC on Waste Electrical and Electronic Equipment (WEEE) of the European Parliament and of the EU Council of Ministers. This appliance has been brought to market after 13th August 2005 in countries which have already integreated this directive into their national laws. It may not be disposed of in normal household waste. To dispose, please contact your dealer or manufacturer. Any appliances that are infected, infectious or contami­nated with materials that are a hazard to health are excluded from being taken back. Please observe the other regulations in this context.
Note for Germany: The appliance may not be left at public or communal recycling or col-
lection points.
58
Index
Index
A
Acoustic signal 42 Adjusting door 57 Ambient conditions 16
B
BALANCE 47 Base 19 Basic operation 24
C
Chamber load 22 Cleaning 56 Clock time 41 Close statements 32 Communication address 42 Computer 38 Construction 9 Controller 23 Corrective values 42 Current consumption 15 Customer service 2
D
Dangers 7 Delivery 17 Description 9, 10 Design 9 Dimensions 16 Disposal 58 Disposal of packaging mate-
rial 17
E
EC declaration of conform-
ity 13 Electrical connection 16 Electrical equipment 15 Emergency 8 Ending operation 38 Equipment 11 Error messages 39
F
Floor/table 19
H
Heat output distribution 47
I
Intended use 12 Interior light 3, 12, 26 Irregularities 8, 17
L
Laptop 38 LED 3, 12 Light 3, 12, 23, 25, 26, 34,
35, 36, 37, 39 Light intensity 31 Load 15 Loading 22
M
Maintenance 56 Malfunctions 8, 39, 40 Manufacturer 2 MEMoryCard XL 53 Minimum clearances 18
N
Nameplate 14 Normal mode 24, 25
O
Opening the door 22 Operating modes 24 Operating mode settings 25 Operating panel 23 Operating personnel 7 Operating voltage 15 Operation 22 Optional equipment 3
P
Packaging material 17 Peltier cooling modules 56 PH value 20 Power failure 40 Product safety 7 Programme mode 29 Protecion class 15 Putting into operation 20
R
Read-write device 54 Regular maintenance 56 Repairs 57
S
Safety regulations 6 Service 57 Servicing 56 Setting parameters 24 Settings example normal
mode 26
Settings example program-
ming mode 34
Settings example week time
switch 28 Setting up 17 Setting up options 19 Setup 17 Sliding shelves 14, 22 Standard accessories 16 Storage 58 Storage after delivery 17 Switching on 21
T
Technical data 14 Temperature-humidity work-
ing range 10 Temperature sensor 20 Transport 17 Transport damage 17
U
Unpacking 17 User ID card 55 User interface 23
W
Water connection 20 Water specification 20 Water tank 20 Week time switch 27 Working range 10
59
Memmert GmbH + Co KG | Postfach 1720 | D-91107 Schwabach | Tel. +49 (0) 9122-925-0 | Fax +49 (0) 9122-145-85 | E-Mail: service@memmert.com | www.memmert.com
27.01.2011
HPP englisch
D10621
Loading...