Features and Ratings p. 34
DS20 p. 35
DS30 p. 37
DS
DS60 p. 39
DS100C p. 41
DS100 p. 43
DS200 p. 45
Spare parts p. 47
Dimensions p. 49
Switch rated plugs and receptacles
DS Series Decontactors provide a useful combination of capacity and ruggedness. DS are often
y, automotive, and mining industries.
used to connect motors and welders in the metals, quar
e designed for applications r
They ar
achieved as soon as the plug and receptacle are fully engaged, making them an excellent choice
for outdoor applications where rainproof performance is required.
equiring lar
ge wiring capacities. The DS’s NEMA 3R rating is
Main Advantages
t Switch & Hp rated (AC only)
cuit rated*
Series Switch Rated Plugs & Receptacles
TM
DECONTACTOR
33
t 65 kA to 100kA shor
t Up to 5 auxiliary contacts
t Amperage ratings up to 200A
t Metal or Poly constr
* See note under General Ratings on the next page
t cir
uction
r
Highlighted Advantage
Simplify NFP
A 70E Compliance
See pgs 17-18 for
more information
Product Features
Operating
Instructions
Pushbutton Pawl
Provides quick, safe and
easy load break.
Spring Assisted Screw Terminals
Patented design assures “Tighten
and Forget” confidence.
Spring Loaded Butt-Style Contacts
Ensures optimal contact force and
superior electrical performance
over thousands of operations.
Lid
Provides additional
protection from harsh
environments.
General Ratings
Dead Front
Assures safety by preventing
user access to live parts.
Silver-Nickel Contact Material
Solid silver-nickel contact surfaces
provide superior conductivity, durability
and corrosion resistance.
Casing
Fiberglass reinforced thermoplastic polyester material
offers great resistance to
impact, corrosion and harsh
environmental conditions.
Lockout-Tagout Provisions
Allows plug to be easily locked out and
tagged. Optional Padlock Pawl allows
lockout/tagout of the receptacle
1
When the plug and receptacle are latched together,
the circuit is connected.
2
Pressing the pawl causes
the DECONTACTOR to
break the circuit. The
plug is ejected to its rest
position; its contacts are
now dead.
Amperage 20 to 200A
Voltage 600 VAC (480 VAC for DS200) 250 VDC
equency
Fr
Horsepower 1/2 to 25 hp
Short-Circuit
(Make & Withstand)
Environmental
Temperature min -40°F/max 140°F
, 30, 60 & 100C
DS20
*
current limiting fuses sized at 400% of the highest full load motor ampacity
with the devices hp rating.
associated
& 200 are rated 65kA. Testing was performed with RK5 time delay
DS100
*
fuses sized at 100% of the devices rated ampacity.
** IP54 rated when receptacle and plug are mated, when not mated receptacle
alone is IP55 rated provided that the lid is latched closed.
50-400 Hz
65kA to 100kA*
NEMA 3R, IP54/55**
e rated 100kA.
ar
esting was per
T
med with RK1
for
Highlighted Feature
Typical Device Labels
Meltric Corporation
, NEMA 4X
20 hp, 480V
LISTED 49B6
33-64043
SWITCH RATED RECEPTACLE/CONNECTOR
MOTOR CIRCUIT DISCONNECT SWITCH
BRANCH CIRCUIT DISCONNECT SWITCH
DS Decontactors ar
“motor circuit” and “branch circuit” disconnect
switching – up to 25 hp and up to 200A
DS, 60A
e UL & CSA rated for
Listings
Category UL CSA IEC
Plugs and Receptacles UL 1682 C22.2 No. 182.1 60309-1
Branch Circuit Disconnect Switching UL Subject 2682 UL Subject 2682
mance tested to UL 98)
for
(AC only)
Motor Circuit Disconnect Switching UL Subject 2682 UL Subject 2682
(AC only) (Performance tested to UL 508)
CE ratings available upon request
(Per
60947-3, AC22, AC23
04J27
3
Rotating the ‘dead’ plug
30° counterclockwise
closes the safety shutter
and frees the plug to be
withdrawn from the
receptacle.
4
The plug and the receptacle
are separated. The safety
shutter pr
live parts.
rotate 30° clockwise, and
apply inser
events access to
To reconnect, insert
5
plug into receptacle,
tion for
ce.
DECONT
ACTOR
TM
Series Switch Rated Plugs & Receptacles
34