DR50 Hazardous Location Plugs & Receptacles – 50 A
Devices rated for hazardous locations are not returnable.
Ratings
• Voltage
600 VAC
•
Current Interruption Capability
Not for current interrupting
• Short Circuit Rating
100kA Withstand
Testing was performed with RK1
current limiting fuses sized at 100%of
the devices ampacity rating.
• Environmental Ratings
Type 4X
• Temperature Range
Min -40°F/Max 104°F
See pg 258 for temps below -15°F.
• Wiring Capacity
Min 14 AWG Max 4 AWG
Aux Contacts - Max 14 AWG
on THHN wire sizes
• Applicable Standards
CSA C22.2 No. 182.1-07
C22.2 No. 213-M1987
•
Hazardous Ratings
Class I, Division 2, Groups ABCD, T6
Class I, Zone 2, IIC
Receptacle
(female)
Don’t forget to add installation
accessories to your order
!
Voltage Polarity
120V
120 208V
Based
125V
125 250V
208V
208V
250V
250V
277V
277 480V
347 600V
480V
480V
600V
600V
The xxx represents any and all device options; if no options are needed, the xxx suffix should be omitted.
1P+N+G 35-34235-K16-xxx-HAZ 35-38235-K16-xxx-HAZ
3P+N+G 35-34237-K16-xxx-HAZ 35-38237-K16-xxx-HAZ
1P+N+G 35-34175-K07-xxx-HAZ 35-38175-K07-xxx-HAZ
2P+N+G 35-34176-K07-xxx-HAZ 35-38176-K07-xxx-HAZ
2P+G 35-34232-K16-xxx-HAZ 35-38232-K16-xxx-HAZ
3P+G 35-34233-K16-xxx-HAZ 35-38233-K16-xxx-HAZ
2P+G 35-34172-K07-xxx-HAZ 35-38172-K07-xxx-HAZ
3P+G 35-34173-K07-xxx-HAZ 35-38173-K07-xxx-HAZ
1P+N+G 35-34245-K04-xxx-HAZ 35-38245-K04-xxx-HAZ
3P+N+G 35-34247-K04-xxx-HAZ 35-38247-K04-xxx-HAZ
3P+N+G 35-34187-K14-xxx-HAZ 35-38187-K14-xxx-HAZ
2P+G 35-34242-K04-xxx-HAZ 35-38242-K04-xxx-HAZ
3P+G 35-34243-K04-xxx-HAZ 35-38243-K04-xxx-HAZ
2P+G 35-34182-K14-xxx-HAZ 35-38182-K14-xxx-HAZ
3P+G 35-34183-K14-xxx-HAZ 35-38183-K14-xxx-HAZ
Part # Part #
Poly Poly
Inlet
(male)
Standard
locking pawl
Hazardous Location DR50
lid is normally closed
Part Number Example
480V DR50 + 2 aux contacts
DR50 recept 3P+G = 35-34243-K04-972-HAZ
480V DR50 with no options
DR50 recept 3P+G = 35-34243-K04-HAZ
See pages 235-244 for detailed
information on these options
!
207
Receptacle Options Suffix # Inlet Options Suffix #
With 2 Auxiliary/Pilot Contacts
With 3 Auxiliary/Pilot Contacts
With 4 Auxiliary/Pilot Contacts
Open Lid Configuration
Recept # - 972
Recept # - 973
Recept # - 974
Recept # - NO
With 2 Auxiliary/Pilot Contacts
With 3 Auxiliary/Pilot Contacts
With 4 Auxiliary/Pilot Contacts
With No Lockout Hole
Feature Spotlight – Screw-Type Locking Pawl
Listing Requirement
Users must tighten screw to lock
the plug in the mated position
Zone 2/Division 2 DR50 receptacles feature a standard
screw-type locking pawl. This required feature allows the
user to lock the plug to the receptacle by tightening
a screw on the pawl.
For added security, a lockout hole is included on the
receptacle that enables the user to insert a 5/16” lock or
locking pin to prevent the plug from being disconnected
or to lock the receptacle lid closed.
5/16” hole for
added security
Inlet # - 972
Inlet # - 973
Inlet # - 974
Inlet # - A155

INSTALLATION ACCESSORIES – SIZE 3
Accessories rated for hazardous locations are not returnable.
DR50
HANDLE w/NPT Part # Poly Part # Metal
1/2” 553P0N05 5K3P0N05
HANDLESANGLES
poly
metal
3/4” 553P0N07 5K3P0N07
1” 553P0N10 5K3P0N10
1 1/4”
553P0N12 5K3P0N12
For available cord grips, see pg 168.
POLY HANDLE w/Cable Range
.39 - 1.18" 553P0D30
Cable Range NPT Cable Range NPT
.312 - .625” 1/2” .660 - 1.000” 1”
.438 - .812” 3/4” .875 - 1.375” 1 1/4”
NPT sizes are determined by the cable diameter and third party cord grip.
POLY ANGLE WITH METAL BOX w/NPT
BOXES
* 29.6 in
METAL ANGLE WITH METAL BOX w/NPT
* 29.6 in
POLY ANGLE WITH LARGER METAL BOX w/NPT
* 170.0 in
METAL ANGLE WITH METAL BOX w/NPT
* 27.7 in
30° 1/2” 753C3N05
30° 3/4” 753C3N07
30° 1” 753C3N10
3
30° 1 1/4” 753C3N12
30°
30° 3/4” 7K3C3N07
30° 1” 7K3C3N10
3
30° 1 1/4” 7K3C3N12
70° 1/2” 753C7N05
70° 3/4” 753C7N07
70° 1” 753C7N10
70° 1 1/4” 753C7N12
3
70° 1 1/2” 753C7N15
70°
70° 3/4” 7K3C7N07
70° 1” 7K3C7N10
3
70° 1 1/4” 7K3C7N12
1/2”
1/2”
* Interior volume with
receptacle installed.
7K3C3N05
* Interior volume with
receptacle installed.
* Interior volume with
receptacle installed.
7K3C7N05
* Interior volume with
receptacle installed.
POLY ANGLE
METAL ANGLE
30° 553M3
0° 5K3M0
30° 5K3M3
70° 5K3M7
NPT on top or bottom (if rotated). For other NPT configurations, contact customer service.
FINGER DRAWPLATES
61-6A346
PROTECTIVE INLET/PLUG CAP
31-3A426 For Inlets/Plugs Only.
RECEPTACLE LOCKING PIN
LP-843
Set of Two (2)
Recommended for easier connector closure.
MISCELLANEOUS ACCESSORIES
LOCATION
HAZARDOUS
Notes: For Zone 2 DR dimensions refer to DR dimensions on pgs 101-102.
208