Meltric DR50 Catalog Page

DR50 Hazardous Location Plugs & Receptacles – 50 A
Devices rated for hazardous locations are not returnable.
Ratings
Voltage 600 VAC
Current Interruption Capability
Not for current interrupting
Short Circuit Rating 100kA Withstand
Testing was performed with RK1 current limiting fuses sized at 100%of the devices ampacity rating.
Environmental Ratings Type 4X
Temperature Range Min -40°F/Max 104°F
See pg 258 for temps below -15°F.
Wiring Capacity Min 14 AWG Max 4 AWG Aux Contacts - Max 14 AWG
on THHN wire sizes
Applicable Standards CSA C22.2 No. 182.1-07 C22.2 No. 213-M1987
Hazardous Ratings
Class I, Division 2, Groups ABCD, T6 Class I, Zone 2, IIC
Receptacle
(female)
Don’t forget to add installation accessories to your order
!
Voltage Polarity
120V
120 208V
Based
125V
125 250V
208V
208V
250V
250V
277V
277 480V
347 600V
480V
480V
600V
600V
The xxx represents any and all device options; if no options are needed, the xxx suffix should be omitted.
1P+N+G 35-34235-K16-xxx-HAZ 35-38235-K16-xxx-HAZ
3P+N+G 35-34237-K16-xxx-HAZ 35-38237-K16-xxx-HAZ
1P+N+G 35-34175-K07-xxx-HAZ 35-38175-K07-xxx-HAZ
2P+N+G 35-34176-K07-xxx-HAZ 35-38176-K07-xxx-HAZ
2P+G 35-34232-K16-xxx-HAZ 35-38232-K16-xxx-HAZ
3P+G 35-34233-K16-xxx-HAZ 35-38233-K16-xxx-HAZ
2P+G 35-34172-K07-xxx-HAZ 35-38172-K07-xxx-HAZ
3P+G 35-34173-K07-xxx-HAZ 35-38173-K07-xxx-HAZ
1P+N+G 35-34245-K04-xxx-HAZ 35-38245-K04-xxx-HAZ
3P+N+G 35-34247-K04-xxx-HAZ 35-38247-K04-xxx-HAZ
3P+N+G 35-34187-K14-xxx-HAZ 35-38187-K14-xxx-HAZ
2P+G 35-34242-K04-xxx-HAZ 35-38242-K04-xxx-HAZ
3P+G 35-34243-K04-xxx-HAZ 35-38243-K04-xxx-HAZ
2P+G 35-34182-K14-xxx-HAZ 35-38182-K14-xxx-HAZ
3P+G 35-34183-K14-xxx-HAZ 35-38183-K14-xxx-HAZ
Part # Part #
Poly Poly
Inlet
(male)
Standard locking pawl
Hazardous Location DR50 lid is normally closed
Part Number Example
480V DR50 + 2 aux contacts
DR50 recept 3P+G = 35-34243-K04-972-HAZ
480V DR50 with no options
DR50 recept 3P+G = 35-34243-K04-HAZ
See pages 235-244 for detailed information on these options
!
207
Receptacle Options Suffix # Inlet Options Suffix #
With 2 Auxiliary/Pilot Contacts
With 3 Auxiliary/Pilot Contacts
With 4 Auxiliary/Pilot Contacts
Open Lid Configuration
Recept # - 972
Recept # - 973
Recept # - 974
Recept # - NO
With 2 Auxiliary/Pilot Contacts
With 3 Auxiliary/Pilot Contacts
With 4 Auxiliary/Pilot Contacts
With No Lockout Hole
Feature Spotlight – Screw-Type Locking Pawl
Listing Requirement
Users must tighten screw to lock the plug in the mated position
Zone 2/Division 2 DR50 receptacles feature a standard screw-type locking pawl. This required feature allows the user to lock the plug to the receptacle by tightening a screw on the pawl.
For added security, a lockout hole is included on the receptacle that enables the user to insert a 5/16” lock or locking pin to prevent the plug from being disconnected or to lock the receptacle lid closed.
5/16” hole for added security
Inlet # - 972
Inlet # - 973
Inlet # - 974
Inlet # - A155
INSTALLATION ACCESSORIES – SIZE 3
Accessories rated for hazardous locations are not returnable.
DR50
HANDLE w/NPT Part # Poly Part # Metal
1/2” 553P0N05 5K3P0N05
HANDLESANGLES
poly
metal
3/4” 553P0N07 5K3P0N07
1” 553P0N10 5K3P0N10
1 1/4”
553P0N12 5K3P0N12
For available cord grips, see pg 168.
POLY HANDLE w/Cable Range
.39 - 1.18" 553P0D30
Cable Range NPT Cable Range NPT
.312 - .625” 1/2” .660 - 1.000” 1”
.438 - .812” 3/4” .875 - 1.375” 1 1/4”
NPT sizes are determined by the cable diameter and third party cord grip.
POLY ANGLE WITH METAL BOX w/NPT
BOXES
* 29.6 in
METAL ANGLE WITH METAL BOX w/NPT
* 29.6 in
POLY ANGLE WITH LARGER METAL BOX w/NPT
* 170.0 in
METAL ANGLE WITH METAL BOX w/NPT
* 27.7 in
30° 1/2” 753C3N05
30° 3/4” 753C3N07
30° 1” 753C3N10
3
30° 1 1/4” 753C3N12
30°
30° 3/4” 7K3C3N07
30° 1” 7K3C3N10
3
30° 1 1/4” 7K3C3N12
70° 1/2” 753C7N05
70° 3/4” 753C7N07
70° 1” 753C7N10
70° 1 1/4” 753C7N12
3
70° 1 1/2” 753C7N15
70°
70° 3/4” 7K3C7N07
70° 1” 7K3C7N10
3
70° 1 1/4” 7K3C7N12
1/2”
1/2”
* Interior volume with
receptacle installed.
7K3C3N05
* Interior volume with
receptacle installed.
* Interior volume with
receptacle installed.
7K3C7N05
* Interior volume with
receptacle installed.
POLY ANGLE
METAL ANGLE
30° 553M3
5K3M0
30° 5K3M3
70° 5K3M7
NPT on top or bottom (if rotated). For other NPT configurations, contact customer service.
FINGER DRAWPLATES
61-6A346
PROTECTIVE INLET/PLUG CAP
31-3A426 For Inlets/Plugs Only.
RECEPTACLE LOCKING PIN
LP-843
Set of Two (2) Recommended for easier connector closure.
MISCELLANEOUS ACCESSORIES
LOCATION
HAZARDOUS
Notes: For Zone 2 DR dimensions refer to DR dimensions on pgs 101-102.
208