DB100
DECONTACTOR™– 100A
Switch Rated Plugs & Receptacles
Ratings
• Voltage
600 VAC, 250 VDC
• Switch Ratings (AC)
ranch Circuit & Motor Circuit
B
Disconnect Switching
• Horsepower ratings
1Ø 7 1/2 hp
120V
1Ø 10 hp
240V
3Ø 30 hp
208V
3Ø 30 hp
240V
3Ø 60 hp
480V
3Ø 60 hp
600V
• Short Circuit Rating
100kA Close & Withstand
Testing was performed with 250A
K1 fuses, so the 100kA rating
R
applies up to 60 hp @ 600, 40 hp @
480V and 20 hp @ 240V and 208V.
• Environmental Ratings
IP67
• Temperature Range
Min -40°F/Max 140°F
See pg 194 for temps below -15°F.
• Wiring Capacity
Min 1/0* AWG Max 2/0 AWG
Aux Contacts - Max 14 AWG
Smaller conductors can be retained
in the terminal, but may result in a
temperature rise greater than the 30°
max allowed in UL & CSA standards.
• Listings
UL, CSA, IEC, CE*
* Contact Customer Service
Receptacle (female) Inlet (male)
on’t forget to
D
dd installation
a
accessories to
our order
y
Voltage Polarity Voltage Polarity
120/208V
125V
1
25/250V
208V
208V
250V
250V
277V
277/480V
347/600V
480V
480V
600V
600V
Other voltage configurations are available – contact customer service at 800.433.7642.
3P+N+E 89-94167 3P+N+E 89-98167
1P+N+E 89-94075 1P+N+E 89-98075
2P+N+E 89-94076 2P+N+E 89-98076
2P+E 89-94162 2P+E 89-98162
3P+E 89-94163 3P+E 89-98163
2P+E 89-94072 2P+E 89-98072
3P+E 89-94073 3P+E 89-98073
1P+N+E 89-94045 1P+N+E 89-98045
3P+N+E 89-94047 3P+N+E 89-98047
3P+N+E 89-94147 3P+N+E 89-98147
2P+E 89-94042 2P+E 89-98042
3P+E 89-94043 3P+E 89-98043
2P+E
3P+E 89-94143 3P+E 89-98143
Part # Part #
Metal Metal
120/208V
125V
1
25/250V
208V
208V
250V
250V
277V
277/480V
347/600V
480V
480V
89-94142 2P+E 89-98142
600V
600V
Main Options
Series Switch Rated Plugs & Receptacles
TM
See pgs 171-180 for detailed
information on these options
DECONTACTOR
59
Auxiliary/Pilot
Contacts
Receptacle Options Suffix # Inlet Options Suffix #
With 4 Auxiliary/Pilot Contacts Recept # - 174** With 4 Auxiliary/Pilot Contacts Inlet # - 174**
/pilot contacts are not UL/CSA listed
DB100 devices with auxiliar
*
** Auxiliary / Pilot Contacts are not available on DB devices with 1P+N+E, 2P+N+E or 3P+N+E polarity
y
DB100 Order Example:
To order 4 auxiliary/pilot contacts on an inlet and
eceptacle add
r
DB100 Metal inlet 3P+E=89-98043
DB100 Metal receptacle 3P+E=89-94043
Appr
included on the order.
-174
opriate accessory part numbers must also be
to the par
t numbers.
-174
-174
Installation Accessories
Handles
DB100
NPT Cable Range
3/4” 9PH34 9H34 1.25 - 1.375 9PM622
1” 9PH1 9H1 1.438 - 1.562 9PM625
1 1/4” 9PH114 9H114 1.562 - 1.688 9PM627
1 1/2” 9PH112 9H112 1.688 - 1.812 9PM629
2” 9PH2 9H2
Poly Metal* Poly Handle
Handle Handle w/Clamp & Bushing
Angles
Metal 30° Metal 70° Metal Angle Metal Straight
Angle Angle Oversized 30° Adapter
MA10 89-9A027 MA110 MS10
Junction Boxes
NPT Guidelines
Cable Range NPT
.187 - .75 3/4”
.437 - 1.10 1”
.750 - 1.375 1 1/4”
.890 - 1.650 1 1/2”
1.125 - 2.438 2”
NPT sizes are deter
cable diameter and thir
cord grip.
mined by the
d party
NPT
1 1/4” MB10114 89-9A053-080-114
1 1/2”
2” MB102 89-9A053-080-2
Metal Metal Box with
Box Metal Angle
MB10112
89-9A053-080-112
Miscellaneous Accessories
For Male
Devices Only
Protective
Cap with Mesh
89-9A126 see pgs 167-168
Cord Grip
Order Example
A typical order should include an inlet
part number, a receptacle part number
AND the matching handles, angles or
other required accessories.
Male Inlet with Handle (Plug)
89-98043 + 9PM622
Female Receptacle with Angle Adapter
89-94043 + 89-9A027
DECONT
ACTOR
TM
Series Switch Rated Plugs & Receptacles
60