Melco TG-2000A User Manual

Mitsubishi Electric Air Conditioning Network System
Integrated centralized control software TG-2000A(Ver. 2)
Operation Manual (Site adjustment)
1. Safety Precautions................................1
2. System Requirements............................2
3. System Configuration.............................5
4. Flow of Site Adjustment..........................6
5. Installation .........................................9
6. Part Names and Functions..................... 13
7. Initial Startup and Shutdown................... 20
8. System Setting Procedure..................... 22
8.1 System Setting Screen................... 22
8.2 System Setting Procedure............... 22
8.3 User Set-up................................ 23
8.4 Site Name Set-up .........................25
8.5 G-50A Connection Set-up............... 27
8.6 System Configuration Set-up............ 28
8.7 Monitoring screen Set-up................ 34
8.8 Watt Hour Meter Set-up.................. 40
8.9 Energy monitoring Set-up ................42
8.10 Time Set-up............................... 50
8.11 Password Change........................ 52
9. Charge Data Correction and Remedy ........ 53
9.1 Result of Air - conditioning
Charge Calculation....................... 53
9.2 Maintenance of Charge Data............ 55
9.3 Operation Amount Data Monitoring..... 60
9.4 Charge Parameter Output............... 61
9.5 Charging Remedy ........................ 62
10. Error code list.................................... 74
11. Setting Check List ............................. 78
Appendix 1 Installing Windows XP
Professional ........................ 91
Appendix 2: Auto Log-in Confirmation Method. 93 Appendix 3: Correction to Charge Calcution in the Event of G- 50A
Replacement due to Fault.......... 94
Please read this manual before using the unit.
Please keep this manual for future use. WT03901X01
2002-Sep. (Ver. 2. 00)

Contents

1. Safety Precautions..............................................1
2. System Requirements ..........................................2
2.1 Requirements (system recommendations)............2
2.2 Compatible units..........................................2
2.3 Restrictions................................................3
2.4 Other devices .............................................4
3. System Configuration ...........................................5
3.1 System Configuration Example.........................5
3.2 Hardware Connection Diagram.........................5
4. Flow of Site Adjustment........................................6
4.1 Flow of Site Adjustment ..................................6
4.2 Tools for Site Adjustment................................6
4.3 Step 1: Test operation from central controller
G-50A ............................................7
4.4 Step 2: Initial setting of integrated centralized
control software TG-2000A.....................7
4.5 Step 3: Test operation from integrated centralized
control software TG-2000A.....................8
5. Installation.......................................................9
5.1 Pre-installation Steps ....................................9
5.2 TG-2000A Setup.........................................9
5.2.1 Setup...............................................9
5.2.2 Running TG-2000A Setup (New setup) ......10
5.3 TG-2000A Uninstall.................................... 12
6. Part Names and Functions................................... 13
6.1 Window E lements...................................... 13
6.2 Basic Mouse Operation................................ 14
6.3 Accessing Functions and Moving between
Windows................................................. 14
7. Initial Startup and Shutdown .................................20
7.1 Before startup........................................... 20
7.2 Startup................................................... 20
7.3 Shutdown ................................................21
8. System Setting Procedure ................................... 22
8.1 System Setting Screen................................ 22
8.2 System Setting Procedure............................. 22
8.3 User Set-up ............................................. 23
8.3.1 General Operation.............................. 23
8.3.2 Connection Setting............................. 24
8.3.3 Reliability Function............................. 24
8.3.4 Energy Monitoring Related.................... 25
8.4 Site Name Set-up...................................... 25
8.5 G-50A Connection Set-up............................. 27
8.5.1 Setting Procedure and Restrictions........... 27
8.5.2 Number of G-50A (Step1)..................... 27
8.5.3 G-50A IP Address Set-up (Step 2) ............27
8.6 System Configuration Set-up ..........................28
8.6.1 Setting Procedure and Restrictions........... 28
8.6.2 G-50A Data Collecting (Step 1)............... 29
8.6.3. Unit Composition Set-up (Step 2)............. 29
8.6.4. Set-up of Refrigerant System (Step3) .... 31
8.6.5 Set-up of Group (Step4)....................... 32
8.6.6 Interlocked setting(Step 5)..................... 33
8.7 Monitoring Screen Set-up............................. 34
8.7.1 Configuration Procedure and Restrictions ... 34
8.7.2 Set-up of Model Name (Step1)................ 34
8.7.3 Set- up of the Number of Floors,
and Floor Name (Step2) ....................... 35
8.7.4 Creation of a Plane View (Step 3) ............. 36
8.7.5 Set-up of Floor Name and G-50A(Step 4)... 36
8.7.6 Set-up of IIon arrange and Name (Step 5)... 37
8..7.7 Set-up of Block (Step 6 ).....................................38
8.8 Watt Hour Meter Set-up ................................40
8.8.1 Setting Procedures and Restrictions ......... 40
8.8.2 Watt Hour Meter Setting (Step 1) ............ 40
8.8.3 Set- up for the Name and the Maximium
Integrated Value of WHM (Step 2)............ 41
8.9 Energy Monitoring Set-up............................. 42
8.9.1 Setting Procedures and Restrictions ......... 42
8.9.2 Division Mode (Step 1)......................... 43
8.9.3 Relation between Outdoor Units and
Watt Hour Meter (Step 2) .................... 43
8.9.4 Electrical Specification of Outdoor Units
(Step 3) ........................................ 44
8.9.5 Relation between Indoor Units and
Watt Hour Meter (Step 4) .................... 45
8.9.6 Electrical Specification of Indoor Units
(Step 5) ........................................ 46
8.9.7 Charge Block (Step 6).......................... 46
8.9.8 Currency Unit Set (Step 7)..................... 48
8.9.9 Charge Set (Step 8) ........................... 48
8.9.10 Standard Charge Set........................... 49
8.10 Time Set-up............................................. 50
8.11 Password Change...................................... 52
9. Charge Data Correction and Remedy...................... 53
9.1 Result of Air-conditioning Charge Calculation....... 53
9.2 Maintenance of Charge Data ..........................55
9.2.1 Preparing for Charging Data Maintenance... 55
9.2.2 Maintenance Methods and Restrictions...... 55
9.2.3 Unit Data Maintenance......................... 56
9.2.4 Watt Hour Meter Data Maintenance.......... 59
9.2.5 Verfy Test Operation of Watt Hour Meter.... 60
9.3 Operation Amount Data Monitoring .................. 60
9.4 Charge Parameter Output............................. 61
9.5 Charging Remedy...................................... 62
9.5.1 Preparing to Perform Charging Remedy..... 63
9.5.2 Remedial Apportioning Setting Screen....... 64
9.5.3 Remedy when personal computer HDD
fails (no backup) ............................... 66
9.5.4 Remedy when personal computer HDD
fails (backup).................................... 67
9.5.5 Apportioning method when computer
crashes........................................... 69
9.5.6 Remedy when watt hour meter fails
(monitoring impossible) ....................... 70
9.5.7 Remedy for system information setting error72
10. Error Code List................................................ 74
11. Setting Check List ........................................... 78
11.1 Setting Check List ..................................... 78
11.2 Test Run Check ....................................... 79
11.3 Charging Test Run Check ............................ 82
11.3.1 Charging (No WHM connection)
Test Run Check.................................82
11.3.2 Proportionally Diveded Power Charge
(RS-485 WHM connection) Test Run Check86
Appendix 1: Installing Windows XP Professional ........... 91
Appendix 2: Auto Log-in Confirmation Method............... 93
Appendix 3: Correction to Charge Calcution in the Event
of G-50AReplacement due to Fault............. 94
In this manual, Microsoft® Windows® 2000 Professional is called Windows 2000 and Microsoft® Windows® XP Professional is called Windows XP. In this manual, Microsoft® Excel 2000/XP is called Excel.
Trademarks MS, Microsoft, Microsoft logo, and Windows are registered trademarks and trade names of Microsoft Corporation. Each company may use as registered trademarks and trade names the product names used in this manual.
– Term description –
• “Man-machine”: Indicates a personal computer with integrated centralzed control software TG-2000A. (M an-machine interface abbreviation)
• “G-50A ” : Indicates a central controller G-50A.
On the screen of integrated centralized control software TG-2000A, G-50A is displayed
as "G-50."
- About screen -
• This instruction manual may use the development version screen in some case.

1. Safety Precautions

contract between the customer and Mitsubishi Electric Corporation. By using this
or
if notified by the distributor of the possibility of a certain type of damage.
Please observe the safety precautions detailed in the installation manuals and operation
The customer must not do any wiring or
Have the dealer or a specialist do any wiring or
work. Do not do it yourself. Doing the
result in improper installation
Do not relocate the unit yourself.
Relocating the unit yourself may result in
ic
To relocate the unit, consult the
Do not make any improvements or repairs
electric shock or fire. For repairs, consult
the company from which the unit was purchased.
Read the installation manuals and operat-
for the computer, peripherals
Improper operation could result in fire or damage to the computer or peripherals.
Stop operation immediately if an error
appears on the computer and the
Immediately contact the company from
which the unit was purchased.
Read the installation manual and operation
Improper operation could result in fire or damage
WARNING
Do not use the product for any other
This product is for use with the Mitsubishi
Building Air Conditioning Control
function.
Keep children away from the unit.
let children near the unit
Do not use with other applications.
Use the PC that uses this product with this
Using it with other applications
CAUTION
Please read the Safety Precautions section very carefully before using the unit.
The safety cautions pro vided here are very important for your safety. Please observe them at all times.
The degree of danger involved with incorrect operation of the unit are indicated in this manual using
the following symbols.
WARNING Incorrect operation could result in death or severe injury. CAUTION Incorrect operation could result in injury or damage to property.
After reading this information, please keep this manual together with the operation manual (Management)
in a location where the operator can see it. Also, when changing operators give both of these manuals to the new operator.
Note :
manuals of the other machines such as computers, peripherals, and air conditioners.
electrical work.
electrical work yourself may which may cause electric
for any reason.
Making improper improvements or repairs may cause
message unit stops or is not operating properly.
Failing to do so may result in fire or damage to the unit.
purpose.
Electric System. Do not use it with any other air con­ditioning control system or for any other appli­cation. Doing s o may cause the unit to mal-
product only. may cause faulty operation.
Warning to all users (User Agreement)
This document is a application, you agree to the following conditions and are considered a user.
• Mitsubishi Electric and associated suppliers are not responsible for any collateral, secondary, special damages, even Mitsubishi Electric is not responsible for any rights claimed by a third party.
incorrect installation which may cause electr shock or fire. company from which the unit was purchased.
ion manuals and other machines.
manual for the air conditioner controller.
to the air conditioner controller.
Inspections and maintenance can be dangerous. Do not during these times.
1
(A separate watt hour meter is
Billing is done with
ating/
(A separate watt hour meter is
Billing is done with
(A separate watt hour meter is
Billing is done with
(A separate watt hour meter is
Billing is done with

2. System Requirements

2.1 Requirements (system recommendations)

We recommend the following software and hardware when using this application (TG-2000A).
Item Requirement Recommended
PC PC/AT interchangeable machine Operation check completed, using IBM,
COMPAQ, and DELL
CPU Pentium III 350 MHz or faster :
within 1000 indoor units Pentium III 1GHz or faster :
1001 indoor units or over Memory 128 MB or more 256 MB or more HDD 6 GB or more (2GB or more of C drive free
space necessary) Storage device FDD, CD-ROM drive Devices other than those shown at the left may
Resolution 1024 × 768 or higher, 65536 colors or more Serial port 1 port or more Required when using RS-485 communication WHM LAN Internal LAN (10/100 Mbps) *1 OS Windows XP Professional
Windows 2000 Professional
Service Pack 2 and above
Other Computer must be dedicated for this use
(TG-2000A).
Pentium 4 1.8GHz or faster
4 GB or more of C drive free space necessary
also be installed.
English version only * Personal computer must support each OS.
*1 Purchase the option, or use the equipment recommended for the personal computer when
purchasing the personal computer.

2.2 Compatible Units

The TG -2000A has two main functions: air conditioner controller and cost accounting. However, not all functions are available with all air conditioners.
Table: Compatible units and function list
(¡: supported, : Certain restrictions apply, ×: Not supported)
Function
Model
Y series ¡ ¡ *1 Super Y series ¡ ¡ *1 R2 series ¡ ¡ *1 WR2 series ¡ ¡ *1 WY series ¡ ¡ *1
Multi S series ¡ ¡ *1 Free plan Indoor unit
Free plan LOSSNAY
LOSSNAY with he humidifying
“A” control type ¡
“K” control type ¡
*1 : Can be calculated for each charging block.
May not be available with some older models.
Control/
Maintenance
¡ ¡ *1 ¡ ×
¡ ×
(Adapter required)
(Converter required)
Charging (Billing)
without WHM
×
×
Charging (Billing) with WHM
required. watt-hour units)
required. watt-hour units)
required. watt-hour units)
required. watt-hour units)
2

2.3 Restrictions

The following restrictions apply to the TG -2000A application.
(1) System configuration limits
Number of units Notes
G-50A Max. 40 units G-50A Ver. 2.10 or higher Indoor unit Max. 50 units/G -50A Max. 2000 units (including all IC, KIC, AIC, LC, and FU)
[Symbol]IC: Indoor unit, LC: LOSSNAY, FU: OA processing unit, A IC: “A” controller,
KIC: “K” controller
(2) Group setting restrictions
Item Restrictions Note
Remote controls 2 per group * Other remote controls besides M-NET Number of indoor units
connected to a group
Number of SC and RC connected to a group Groups per floor Max. 50 groups per floor Up to 50A groups can be displayed on
*1 The ME remote controller and MA remote controller cannot be used together for the same group. *2 Set the same function unit for the group.
[Symbol]SC: System controller, RC: Remote controller
(3) Block setting
• The block comes in two types, operation block and charge block.
• The operation block is an aggregate of groups, and it is possible to set a different model group for the same operation block.
• The charge block consists of an aggregate of operation blocks.
(4) Notes on using K control models
When using a K transmission converter (model name: PAC -SC25KA, PAC-SC25KAA(-E)) to manage K control models, take note of the following. See the documentation provided with the K transmission converter for more detail.
• The address of the K transmission converter will be the smallest address of the K control model +
200.
• Set the K control model addresses so that they are larger than the M transmission model addresses.
• When setting a group containing K control models, make the group number the same as the smallest unit address in the group.
(5) Notes on using A control mode
• Use the A/M NET Adapter (model name: PAC-SF48MA(-E)). Set the group to “Group with only A control”.
(6) Countermeasure when an error occurs
• Note that each control or function may not operate properly when rebooting (*1) or when a fault occurs in the centralized Controller G-50A. Since each error is displayed when it occurs, it is recommended to solve the faults quickly.
*1 Indicates that the system is restarting.
1 to 16 * IC, AIC, KIC, or LC cannot be used
4 per group * The number of G-50A is not included
type will not work within the same group. It is not pos-
sible for group settings to span G-50A
one floor of the whole building window.
Group
Block for operation
Block for charging
3
(7) Notes on charge system
485 output of
Necessary when measuring the
F or
att hour meter 2,
Installation is recommended to billing (Charge data) and other
use
• If there is a group that is not set in the charge block, the electric power amount for that group will not be included in the air-conditioning charge. If there are groups which require charging to be divided, set those groups as operation blocks or charge blocks to accomplish this.
• The air conditioning charge can be calculated by block units or by power meter units. Note that even when OA processing unit, LOSSNAY, A control unit or K control unit are included in the block setting, they are not included in the air conditioning charge of the block unit.
• The function for Charge calculation (Without WHM connection) is only applicable to the indoor unit. It does not apply to OA processing unit, LOSSNAY, A control unit, and K control unit, etc.
• Some older M-NET control indoor units are not compatible with the charge function.
• When the system is changed or the air conditioner is extended, which may require address changes, the charge calculation may be affected in some cases. Executing such changes or extensions are recommended after gaining approval from the building owner(s).
(8) Charging (Billing) restrictions
The air conditioning cost calculation method use by this integrated software TG -2000A is the Mitsubishi proprietary general electric power apportioning method. Thus, it is not calculated using watt hour meters installed at the power supply to each unit. Additionally, it cannot be employed in applications demanding calculations based on watt hour meters installed at each unit. Thus when using this unit, we recommend a separate contract be established between the building owner and the tenant that specifies “air conditioning fees will be collected based on proport ional usage (including special considerations for downtime).”
(9) Function description
• The function/specifications may partially change and improvements may be made without any notice.

2.4 Other Devices

Other devices specified or recommended for use with the TG-2000A are listed below.
Name Manufacturer Model Notes
Printer (None specified) (None specified) Supports a page printer only
Watt hour meter 1 Northern Design
RS -232C/ RS -485 converter
UPS (Uninteruptable power supply)
1 POWER RAIL 323 +
(Electronics) Ltd.
2 Elcomponent
Limited 3 CIRCUTOR 4 elcontrol energy
(None specified) (None specified)
(None specified) (None specified)
OPTION Module 2 AEM31D/485 3 CVM-BC-ITF-RS485-
C2 4 ED39din 485
(Must run under the OS used (Windows 2000/XP Professional).)
Only supports RS ­the specified model and manufacturer
electric power. Ex) B&B Electronics Model 485DRJ Black Box Model IC520A ­IC108A * Regarding w
the converter from the manu­facturer may also emit light.
prevent destruction or loss of data. (Any type suitable for
with personal computers)
4

3. System Configuration

controller
G-50A
G-50A
Integrated software

3.1 System Configuration Example

[Image drawing]
HUB
LAN
Integrated software
TG-2000

3.2 Hardware Connection Diagram

(1) LAN connection
Connect the LAN cable to the personal computer. For the location of the LAN connector for the personal computer, refer to the Instruction Manual of the personal computer.
LAN
TG-2000
Note:
• Be sure to use the hub.
• Execute the LAN cascade connection as shown below. For 10BASE-T, the cascade connection is executable up to a maximum of 4 sta ges. For 100BASE-T, the cascade connection is executable up to a maximum of 2 stages.
Power
supply unit
Power
supply u
10BASE-T
straight cable
Outdoor unit
Indoor unit
Remote
HUB
To G-50A
5
ners and controllers
PC connections and settings
-
machine system can correctly operate air conditioner units of all

4. Flow of Site Adjustment

For the test operation method of the air
50A,
that only the air conditioner test
operation has been completed before
Power
G- 50A

4.1 Flow of Site Adjustment

When the task of site adjustment is subdivided into smaller tasks as shown in the figure below, the tasks can be broadly grouped into three steps. The benefit of following these three steps when carrying out the tasks of site adjustment is that if troubles do arise, it will be clear which step caused the problem. This makes it easier to solve problems and this results in a more efficient execution of site adjustment tasks.
Carry out site adjustment, by following the step by step instructions shown below.
Check that the air conditio are correctly configured and that the air con­ditioner works.
Step 2
Connect and set up the software and hard ware on the PC with TG -2000A installed. Check that it is ready for operation.
Check that the TG -2000A man­the managed systems by issuing TG -2000A commands.
Step 1 G-50A test run
Integrated centralized
control software
TG-2000A
Step 2
S tep 3

4.2 Tools for Site Adjustment

You will need the following equipment and reference material in order to easily carry out site adjustment.
<Measurement instruments>
• Tester : to check the wiring and the voltage <Reference material>
• All necessary drawings of the air conditioning control system
• TG-2000A Instruction Manual (Site Adjustment (this manual), Management)
• Operation Manual for each air conditioner unit and controller <Ot her material>
• Floppy disk : used when copying data
• CD-R : used to store generated data and copy it to the site PC.
• Initial setting tool: Personal computer in which this tool is installed
• LAN cable : PAC-YG00FA LAN cable
• Screwdriver kit
• Other usual maintenance tools
*
conditioner and centralized controller G­refer to the relevant installation manuals.
l Check
starting Step 1.
* See Chapter 4 in this booklet for details.
Step 3 TG-2000A system test run
HUB
supply unit
LAN
S tep 1
Step 1
6

4.3 Step 1: Test operation from centralized controller G-50A

Perform only the test operation of the air-conditioning system of the central controller G-50A.
(1) Preliminary check
Check that the test operation of the air conditioner has been completed. Check that the central controller G-50A is set to Group and Interlock.
(The initial setting is executable using the initial setting tool or the G-50A.)
Integrated centralized
control software
TG-2000A
(2) Test operation from central controller G-50A
After supplying power to the central controller G-50A and all air conditioners, perform the test operation from the central controller G-50A, and check the operation state of each unit. * For the test operation method, refer to the installation manual for the air conditioner or the
central controller G-50A.
HUB
Power
supply unit
G-50A
S tep 1

4.4 Step 2: Initial setting of integrated centralized control software TG-2000A

(1) Set -up of integrated centralized control software TG -2000A
Make preparations to allow the personal computer to be operative in order to install the integrated centralized control software TG-2000A. After performing the set-up preparations, set up the integrated centralized control software TG -2000A.
(2) Check the G-50A IP address and personal computer (which uses the integrated centralized control
Note:
• For the set -up procedure, refer to Chapter 5.
• For safety, check the installation state/connection before turning the power ON.
software) Check the G-50A IP address. Check the IP address used for the integrated centralized control software at the same time. Normally, set the sub-net to "255.255.255.0".
For a LAN dedicated to the G-50A system, it is recommended to set the IP address within the following range.
Models IP address range
G-50A main unit [192.168.1.1] to [192.168.1.40] Personal computer for browser [192.168.1.101]to [192.168.1.149] Personal computer
for integrated centralzed control software PLC [192.168.1.151]to [192.168.1.200] Personal computer of initial setting tool [192.168.1.201]
* To connect to the existing LAN, set the IP address and sub-net mask set by the LAN manager.
(3) LAN connection confirmation
Check that the LAN cable is connected to the G-50A, personal computer (using integrated software), and hub, and that power is supplied to the hub.
(4) Initial setting of integrated centralized control software
Start the integrated centralized control software TG -2000A to execute the initial setting.
Note:
• For the initial setting method of the integrated software, refer to Chapters 6 to 8.
[192.168.1.150]
7

4.5 Step 3: Test operation from integrated centralized control software TG-2000A

2000A to
execute the test operation/confirmation. (The test operation function is not included in the
Perform the test operation from the integrated centralized control software TG-2000A to check the operation state and monitor display of the air conditioner. For the operation procedure, refer to the Instruction Manual (Management).
Note:
• For confirmation in the test operation, use the checklist shown in Chapter 11.
• Perform the normal operation from the integrated centralized control software TG­start/stop function.)
8
If not the correct version,
Check that there is at least 128 MB of
Check that there is at least 2GB of free
the C drive. (OS already set
Install the printer driver and check that
For details, refer to the
In the Windows Control Panel, select
Time” and set the date, time
For details, refer to the
At the “display” in the Windows Control
the screen size to 1024 × 768
color to 65536 colors
For details, refer to the
cedure, see Appendix 2
t the network settings have
performed (even if the adapter is
For details, refer to the

5. Installation

2000A will not be started automatically after starting (rebooting) the personal computer
2000A is set

5.1 Pre-installation Steps

Preparing for installation
Before installing the TG -2000A application, do the following checks and preparatory steps.
Steps
1 Check the OS Check the OS Service Pack version.
2 Check the memory
3 Check the HDD free
4 Printer settings
5 Set the date and time
6 Screen size and color
7 Automatic login
8 Network settings Check tha
*1 Check when using the printer. *2 Auto log-in sets the automatic start-up without entering the log-in name or password at the OS
start -up.
Note:
• The TG ­when the TG -2000A is set to Auto reboot, unless the Auto log-in is set. When the TG­to Auto re-boot, be sure to set the Auto log-in.

5.2 TG-2000A Setup

5.2.1 Setup

The following shows the TG-2000A setup disk (CD-ROM) folder configuration and files. However, it only describes the files to be run.
CD-ROM drive \Setup\Step1\MSDEInst.bat \ Step2\DbSetup.bat \ Step3\SetupTG.exe
[Reference] CD-ROM directory structure
readme.txt : Directory structure and setup precautions of this CD-ROM \ Setup : Set -up folder \Tool : Air-conditioning charge calculation support tool (chargecalc.xls) \ Manual : Operation Manual
Action Details How to
space
settings
settings
*
• Windows XP Professional
• Windows 2000 Professional: SP2 and above
RAM (256MB or more is recommended.)
space on up)
printing is possible.
“Date and and region
Panel, set or larger and the (High Color (16-bit)) or more.
Check that the Auto log-in is set. *2 * For the setting check pro-
been not connected).
9
refer to the attached documentation, “Installing
• Windows 2000/XP” and upgrade the OS.
* If necessary, add more
RAM.
* Refer to the Windows
instruction manual for more details.
*
attached instruction manual.
*
Windows users manual.
*
Windows users manual.
Auto Log-in Check Proce ­dure.
*
Windows users manual.

5.2.2 Running TG-2000A Setup (New setup)

Restart the personal computer after completing the
up. Otherwise, Step 2 which follows may
The TG -2000A setup is performed in three stages:
Step 1) MSDE setup Step 2) Database setup Step 3) TG-2000A setup
Note:
Perform the 3 setup steps sequentially. Otherwise, the TG-2000A will not operate properly.
• Be sure to log -in to Windows, using the Auto log-in name and password before executing the set-up. (It is necessary to execute the log-in with a log-in name having administrator rights.)
Step 1) MSDE setup
Run the “MSDEInst.bat” file in the “\Setup\Step1” folder. A DOS window will ope n and the close 2 or 3 minutes later when the process has finished.
When the installation is completed, restart the computer.
Note:
• MSDE set­not be able to be set up properly.
Step 2) Database setup
Run the “DbSetup.bat” file in the “\Setup\Step2” folder. A DOS window will open and the close 10 se cond s later when the process has finished.
Step 3) TG-2000A setup
Run the setup program for TG-2000A. Perform the setup in accordance with the instructions on the screen.
(1) Starting the setup program
1) Starting SetupTG.exe Use Windows Start -Run to execute Run SetupTG.exe in the “\Setup\Step3” folder in the root directory of the Setup CD. The setup start confirmation window appears. Read and check the cautions which appear on the screen.
2) Check the displayed items and click the [Next] button. If there is no problem with the cautions, click the [Next] button to continue on to the next screen. * Click the [Cancel] button to stop the setup.
10
(2) Read the license agreement
Be sure to restart the personal computer after
1) Read the license agreement and click the [Next] button. The license agreement screens will be displayed one at a time. Carefully read all of the agreement and check that you agree with each item before selecting “It agrees” and clicking [Next] to continue.
* If you cannot agree with the license agreement,
click the [Cancel] button and stop the installation of TG-2000A.
(3) Check the installation folder
1) Check the location where the program is to be installed and click the [Next] button. Check the location where the program is to be installed. If the location needs to be changed, set the new location by clicking the [Browse] button. After checking the installation location, click the [Next] button.
* Click the [Cancel] button to stop the installation.
(4) Installation start confirmation
1) Confirm that you want to start the installation and select the [ Next] button. If the [ Next] button is clicked the installation will start.
* Click the [Cancel] button to stop the installation.
(5) TG-2000A setup completion
1) Select [ Finish] button Click [Finish] button on installation screen.
After the installation is completed, restart the computer. When the installation is completed, the program is registered in the start menu and automatically run from the nex t time the computer is started. Store the CD is a safe place.
Note:
• installing TG -2000A.
11

5.3 TG-2000A Uninstall

This section describes how to uninstall an installed “MSDE” and “TG -2000A” program.
(1) TG-2000A uninstall
1) Check to see if TG -2000A has ended Check to see if the TG-2000A program has ended. If it has not ended, end it. * For a description of the ending method, see
Chapter 7.
2) Start “Add/Remove Programs”. Start by clicking Control Panel’s Add/Remove Pro­grams.
3) Select “TG-2000A”, and click [Change/Remove] button. Select “Integrated centralized control software TG-2000A” from the displayed programs, and click the [Change/Remove] button. Uninstallation of the TG -2000A program begins.
Note:
• We recommend that you do not delete all the shared files.
• This uninstall cannot delete some folders and files. (Ex: C: \TG-2000)
4) “Add/Remove Programs” ending When program uninstallation ends, Add/Remove Programs ends.
(2) MSDE uninstall
1) Start the SQL Server Service Manager Start the “SQL Server Service Manager” by right-clicking the MSDE icon on the taskbar.
2) Stop all service To stop all service, make your selection at the Service field and click the [Stop] button.
3) End the SQL Server Service Manager The “SQL Server Service Manager” window closes.
4) Close the MSDE icon Right-click the MSDE icon on the taskbar and select [Exit]. The MSDE icon is removed from the taskbar.
5) Start “Add/Remove Programs”. Start by clicking on the Control Panel’s Add/Remove Programs.
6) Choose “MSDE”, and click the [Change/Remove] button. Select “MSDE“ from the displayed programs, and click the [ Change/Remove] button. Uninstallation of the MSDE program begins.
Note:
• This uninstall cannot delete some folders and files. (Ex: C: \Mssql7)
• When MSDE is used, uninstall is unnecessary.
7) “Add/Remove Programs” ending When program uninstallation ends, “Add/Remove Programs” ends.
MSDE icon
12

6. Part Names and Functions

functions that may be
-
-
Maintenance group:
Shows the title of the
for the
function, site name, and
Exits the Initial window Shows time, warnings,
Equipment state
Displays the system equipment as error or
Display the title of
Message bar:
Display comments
next,

6.1 Window Elements

The window displayed when the power is turned on and no system settings have been made is called the Initial window. The Initial window has the following parts. (The Initial window can be accessed from the menu bar with a password. For details, see section 6.3.)
Title bar:
window
Menu bar:
Shows a list of selected
System setting group:
Sets the group infor mation, monitor dis ­play, charge calcula tion system, etc.
display:
normal.
Click the buttons to display the window associated with that feature. An example is shown below.
Title bar:
the window.
User setting group:
Sets valid/invalid password.
Function to correct the charge calculation, etc.
Exit button:
and moves to the Manage­ment window
Message bar:
and other comments
Initial window
Function display ­operation setting section:
Used to display/set the set­ting contents.
about function dis­play and operation
Displays the operation contents of the [Next], [Back], [Cancel], and [OK] buttons on each setting screen.
Buttons Operation contents
[OK]
Advances to the setting screen with the confirmation contents on the preparation screen determined not to have any problems. Validates the contents set on this display screen to advance to the next setting screen.
[Next] Advances to the next setting screen. [Back] Invalidates the contents set on this display screen to return to the last screen. [Cancel] Invalidates the contents set on this display screen to shift to the initial screen.
System Configuration Options Control Window
13
Next, Back, Cancel, and OK buttons:
Choose to end, return, or cancel the setting of func­tion display and operation settings

6.2 Basic Mouse Operation

First, use of the mouse as a pointing device will be explained. If a device other than a mouse is being used, consult with the manual for that device.
The following is a list of terms used in describing mouse operations.
Click : This refers to pressing and releasing the button one time.
To use this function, click the button Double Click: This refers to pressing and releasing the button twice in quick succession. Drag : This refers to moving the mouse pointer on top of an object on the screen, pressing
and holding down the button to select the object, then, while holding the button down,
moving the mouse pointer, and the object, to a different location. Keyboard : Primarily used when entering password, characters, or numerics.

6.3 Accessing Functions and M oving between Windows

The functions of the TG -2000A can be divided into two general categories.
1) Functions that monitor air conditioner operation status and control functions……Initial window
2) Operation and system initialization and charge data maintenance functions (functions used to
accomplish functions in 1) above)……Control window(Management screen)
This section deals mostly with functions in category 2).
(1) Shift from the initial window to the control window
The following shows the procedure to shift from the initial window to the control window. Shift the screen to the control window after completing the initial setting shown in Chapter 8.
[Procedure]
1) Select [Finish] button. Click the [Finish] button located on the lower right on the initial screen. With the above step, the confirmation screen (asking whether or not to trans ­mit the setting contents to the G-50A) is displayed.
2) Select [OK] button. Click the [OK] button to transmit the initial setting contents to the G-50A.
The start-up display screen is displayed after the screen has been shifted to the control window. The system information set or changed is transmitted to each G-50A to enter upon the start -up processing. It takes approximately 10 to 20 minutes to start-up.
* Note that the setting contents will not be trans-
mitted to the G-50A when the [Cancel] button is clicked. If it is used when only the maintenance group function is operated, it is possible to shorten the time required until the control window resumes.
(2) Shift from the control window to the initial
window
The control window shifts to the initial window when the initial setting contents are changed or when the charge calculation maintenance is performed.
[Procedure]
1) Select [Configuration] and then [System set] in the menu bar. Click the [Configuration] in the menu bar on the control window to select the [System set]. The password confirmation screen is displayed.
Display screen of Shift to setting screen
Screen of confirmation for
transmitting set contents
Start-up display screen
14
2) Enter the password
Manage the password to prevent unauthorized personnel from accessing the system. The
Enter the word “*****” in the password verification box, then click the [OK] button. Doing so returns you to the initial window.
There are two kinds of passwords.
Initialization password: All the items in the initial
window can be used. The initial password is “SYSTEM”.
Maintenance password: The initial window maintenance group and personal password can be
changed. The initial password is “Maintenance”.
Maintenance Tip
• password can be changed.
Password input screen
15
<TG -2000A screen order 1>
turn
]
]
Power On + Start
TG-2000A
System data
No system data
[User setup group]
Exit TG -2000A, shut down the OS, and
the power off
Select [ File]-[End button
[System setup group]
Select [ Exit button
* Range described in this manual
Control window(Management screen) (see separate management manual)
Password input
Return to Initial window
16
Wizard name Primary settings contained in the activated window
User Set -up Set TG -2000A functions
Wizard name Primary settings contained in the activated window
Site Name Set -up Set the product name (site name)
Wizard name Primary settings contained in the activated window
Password change Changes the password to the two types of Initial window
Wizard name Primary settings contained in the activated window
Preparation for the G-50A connection setting
Number of G-50A units setting Sets the number of G-50A units. G-50A IP address setting Sets the IP address for each G-50A.
Wizard name Primary settings contained in the activated window
Preparation for System configurations setup
Collecting G-50A data Collects the setting information for the G-50A during the initial
Unit configurations setup Sets the unit configurations in G-50A. System structure of refrigerant
system Function of each group Set indoor unit and ventilation groups. Ventilation unit grouping Set ventilators and indoor unit groupings .
Wizard name Primary settings contained in the activated window
Preparation for Monitoring screen set -up
Set -up of model name Sets the model name of unit Set -up of the number of floors, and
floor name Creation of a plane view Create a floor plane to be used in the floor window of the Management
Set -up of floor name and G-50A Set floor and G-50A assignment Set -up of icon arrange and name Layout icons on the floor plane, and set names S et-up of block
Wizard name Primary settings contained in the activated window
Time set -up Sets the current time.
Wizard name Primary settings contained in the activated window
Preparation for WHM set -up Check the WHM setting order and notes display . Watt hour meter setting Sets the watt hour meter connection port and watt hour meter
Set -up for the name and the maximum count value of WHM
Checks the step/caution display for the G-50A connection setting.
It is possible to display the optional functions of the G-50A.
Verifies the order of system configuration settings and displays warnings
setting.
Set refrigerant connections .
Verifies the order of monitoring screen settings and displays warnings
Sets the number of floors and floor name.
screen(control window)
Set groups in blocks
address. Sets the WHM name, installation location, and maximum
integrated value.
17
<TG -2000A screen order 2>
No system data
System data
Exit TG -2000A, shut down the OS, and turn the power off
Select [File] - [End] button
Select [Exit] button
* Range described in this manual
[Maintenance setup group]
Control windows(Management screen)
(see separate management manual)
Power On + Start TG -2000A
Password input
Return to Initial window
[System setup group]
18
Wizard name Primary settings contained in the activated window
Preparation for Energy monitoring set -up
Model name Sets the unit model No. Number of floors, and floor name Set floor number and names. Floor plane drawing Create a floor plane to be used in the floor window of the
Relation between floor and G-50A Sets the number of G-50A terminals. Group icon placing and naming Layout icons on the floor plane, and set names. Operation block setting Set groups in blocks.
Wizard name Primary settings contained in the activated window
Maintenance of charge data (Present value monitor)
Maintenance of charge data (Meter maintenance)
Maintenance of charge data (Unit) Data for the last 62 days from indoor units and outdoor units can
Wizard name Primary settings contained in the activated window
Operation amount data monitoring Operation data stored in G-50A can be monitored and saved.
Wizard name Primary settings contained in the activated window
Remedial apportioning setting Remedial apportioning can be tentatively performed when
Verifies the order of billing settings and displays warnings .
Management window.
Dat a for the last 62 days from the watt hour meter, indoor units, and outdoor units can be viewed and edited. (Also, current values for watt hour meters can be monitored.)
Watt hour meter data from the last 62 days can be viewed and edited.
be viewed and edited.
charging trouble occurs.
19

7. Initial Startup and Shutdown

For safety reasons, make a thorough check of
Desktop screen

7.1 Before Startup

Please confirm the following items before starting the TG-2000A application.
(1) A test run of the air conditioning system has been completed. (2) Check that the personal computer, hub, G-50A, power supply unit, and air conditioner power are
turned on. (3) All PC hardware and cables have been connected and the proper software installed. (4) “Date and time” setting are correct.

7.2 Startup

Start the integrated centralized control software TG-2000A
application.
Follow these steps to startup the TG -2000A application. [Procedure]
1) Restart Windows When Windows OS restarts, the user automatically logs on and the TG-2000A program starts. When the startup process begins, the setup screen is displayed. * When Windows OS restarts, the integrated software
TG-2000A application starts automatically.
After the startup screen is displayed, the behavior of the application depends on the existence of System Settings data.
Case 1: Without System Settings data: (the first startup)
The initial screen is displayed. Start with Chapter 8 “Changing System Settings”
Case 2: With system setting data
After the system has been set up once, turning on the power brings up the Management window, and the startup process begins immediately. The startup process takes some time (approx. 10 to 20 minutes). To change the initial settings, go to the initial window. See the procedure in chapter 6.3 “Accessing functions and moving between windows”.
Maintenance Tip
• all equipment and connections.
Startup screen
Initial window
20
2000A application before
turning off the PC. Failing to do so could result in
2000A application is
When the charge
the operation

7.3 Shutdown

TG-2000A Shutdown
Follow these steps to shutdown TG -2000A.
[Procedure]
1) Select the E nd option in the File menu in the Menu Bar Always end the application before turning off the power. Shutdown is done from the initial window. Select the File menu in the Menu Bar and select the End option. * To switch to the Initial window, refer to chapter 6.3.
2) Select [ OK] button. The shutdown confirmation dialog box appears asking to confirm this action. After verifying the content of the dialog box, click the [OK] button to exit the application. * Click the [Cancel] button to return to the Initial window.
Maintenance Tip
• Always exit the TG ­damage.
• Note that when the TG ­exited, the functions used stop. calculation function is used, set mode to 24-hour continuous operation.
Shutting down the OS
Shut down the OS (Windows 2000/XP) after verifying that the TG -2000A application has been exited. Turn off the PC after shutting down the OS.
* Please see the OS or PC owner’s manual for procedures on shutting down the OS and turning
off the PC.
End the application
Shutdown verification
21

8. System Setting Procedure

8.1 System Setting Screen

The following is an explanation of the items found in the System Settings window.
User Set-up
group
System Set-up
group
Initial window
Function group Function Operation details
User set- up Allow or disallow certain functions
[User Set- up group]
[System Set-up group]
Site name set- up Set the building name Password set- up The password can be changed G- 50A connection set-up Sets the number of G-50A units connected and the IP address. System configuration set-up Sets the system configuration, group, interlocking unit, etc. Monitoring screen set-up Executes the model name setting, plane drawing creation, group icon
arrangement, etc.
Watt hour meter set- up Set the watt hour meter serial port and watt hour meter address
Maintenance group
Energy monitoring set-up Set the system billing function Time set- up Set the current time
Maintenance of charge data Proportional billing information can be revised.
[Maintenance group]
Note:
• See Chapter 9 for the maintenance group items.
• The set items that are displayed depend on the functions of the TG -2000A purchased.
Operation amount data monitor
Remedial apportioning setting
Operation amount data stored in G-50A can be monitored and saved.
Remedial apportioning can be tentatively performed when charging trouble occurs.
Displays the operation contents of the select buttons on each setting screen.
Buttons Operation contents
[OK] [Next] Advances to the next setting screen.
[Back] Invalidates the contents set on this display screen to return to the last screen. [Cancel] Invalidates the contents set on this display screen to shift to the initial screen.
Validates the contents set on this display screen to advance to the next setting screen. (Advances to the next setting screen if it is the preparation screen.)

8.2 System Setting Procedure

The following is an explanation of the System Settings performed at the Initial window.
When no System Settings exist
User set -up  Site name set -up G-50A connection set -up  System configuration set -upMonitoring screen set-up  Watt hour meter set-up  Energy monitoring set-up (Password set-up  Time set -up)
22
* Even if the G-50A is not actually connected, it is possible to set it in advance as long as
If the settings are done out of order, some items will not be available and others will have to be
Check the time for each
When filter sign automatic display is deactivated, the filter status is not reflected automatically even
ter status is
, it only possible
information such as system configuration, etc. is available.
Note:
• set again.
• Time set -up and Site name set-up are only performed when necessary. G-50A with “Time set -up”, and set the time when necessary.
When System Settings exist
Make any changes to the settings. Note:
• Changing certain settings affects the status of other settings.
• User set -up in particular affect other settings and functions.
• Changing the settings on the left affects the settings on the right. System configuration set -up > Monitoring screen set -up, Energy monitoring set-up Monitoring screen set -up > Energy monitoring set -up Watt hour meter set -up > Energy monitoring set-up

8.3 User Set-up

Use these settings to allow or disallow TG-2000A general operations, printer, charge (billing), and external I/O functions.
Activating TG-2000A Functions
[Procedure]
1) Click the User set -up button From the Initial window, click the User set-up button in the User set -up group. The User set -up window appears.

8.3.1 General Operation

Set the schedule and summer time and turn on and off the filter sign automatic display function.
Setting general operation options
[Procedure]
1) Click the option button. Set the Schedule Set-up, Summer Time Set-up and Filter sign automatic display setting. To do this, click the option button of the setting.
User set -up window
Schedule Set-up
Off (Deactivate) : Turns the scheduling function off. On (Activate) : Turns the scheduling function on.
(Default)
Summer Time Set-up
Off (Deactivate) : Do not automatically adjust the
G-50A for summer time.
On (Activate) : Automatically adjust the G-50A for
summer time. (Automatic updates take place at 04: 15 AM) (Default)
Filter sign
Off (Deactivate) : Do not automaticaly display. On (Activate) : Automaticaly display . (Default)
Note:
• when the filter sign window is selected. When the View filter button is clicked, the fil reflected.
• To use the Schedule S et-up, it is necessary to register the license number of the annual/weekly schedule separately with the G-50A. When the license is not registered with the G-50A to use the week ly schedule function of the G-50A. In this case, the schedule setting made from the integrated centralized control software TG -2000A is invalidated, resulting in operation failure.
23
General operation set-up

8.3.2 Connection Setting

2000A application and Windows 2000/XP OS on a regular basis
continuously without restarting, system errors may
The automatic restart function serves to insure that the system restart is done on a regular basis.
automatic restart, the system must be restarted manually. Since
it is recommended to periodically restart the
31st
The system configuration, history, and charge data databases are backed up. The trend and
Connection settings
Turn on and off the printer.
Setting connector options
[Procedure]
1) Click the option buttons Use the option button to select the printer an d WHM connection. Available printer options are ON or OFF.
Printer connection
Off (No connection): Turns the printing function off. (Default) On (Connection) : Turns the printing function on.
Note:
• Data cannot be printed if this option is OFF.

8.3.3 Reliability Function

Turn on and off the automatic reboot function as backup and the database backup function.
Setting automatic reboot and database backup function
[Procedure]
1) Click the option button Use the option button to select the Automatic Reboot function and Database Backup function.
Automatic reboot setting
Off (Deactivate) : Does not automatically reboot.
(Default)
On (Activate) : Automatically reboots.
Backup setting
Off (Deactivate) : Do not back up the database. (Default) On (Activate) : Back up the database.
2) Select the reboot interval using the “/ ” buttons . When automatic reboot was set to On, select the automatic reboot day using the “/” buttons. The setting range is the 7th thru 31st day after booting. The initial value is the 31st day.
3) Set the output folder. When database backup was set to On, set the database folder to be backed up using the Browse button. The initial value is “C: \TG2000\databackup”. * Set the folder to be backed up to an HDD drive different from the C: drive.
Maintenance Tip
Manually restart the TG-
(once a week). (Perform the restarting operation during the period from 08:00 to 21:45.)
Note:
• When Windows 2000/XP OS is used accumulate. Thus it is necessary to restart both TG -2000A and the OS.
• If there is an error during the there is a possibility of the error not being detected, system manually.
• When automatic reboot is set to [ON], Windows reboots automatically at 06:35 on the 7th to day after booting. (The number of days depends on the set value.)
• display characters databases are not backed up.
Reliability Function Settings
24

8.3.4 Energy Monitoring Related

auto
In
of
. If the license is not registered with
, the charge calculation function will not operate properly. It is necessary to register
the " Charge calculation function" license with all G-50A units controlled by the TG-2000A.
Follow these steps to energy monitoring functions On or Off , automatically print air conditioning charges, and set printing options.
Energy monitoring functions On or Off
[Procedure]
1) Click the option button Use the option button to select Energy Monitoring function, Automatic Air Conditioning Charges Print, or Air Conditioning Charge Output Processing function setup.
Energy monitoring function
Off (Deactivate) : Deactivates Energy monitoring related
(Default)
On (Activate) : Activates Energy monitoring related
Energy monitoring automatic output
Off (Deactivate) : Do not automatically print air conditioning
charges. (Default)
Printing : Print Energy monitoring auto- matic
printing information auto- matically.
Exporting file : Automatically output air conditioning
charge result as a file.
Printing and : Automatically print and automatically
output air conditioning charges as exporting file a file.
* For file output, set the output destination. The initial output
destination is “C: \TG2000\Chargefile”.
Energy monitoring output format
Standard : Output by standard item. (Default) Unit details : Output detailed air conditioning charges for each unit also. Regular/Off details : Output detailed air conditioning charges for regular hours and off hours also.
W att hour meter connection
Non-connection : Charge calculation function without WHM connected (default) Connection : Charge calculation function with WHM connected
It is possible to select Serial connection. * Note that it is not possible for this version to select the PLC connection.
Note:
• When the printer is not connected, it is unable to set the printing for the "Energy monitoring output".
• When this TG -2000A is not provided with the "Charge function", this screen is not displayed. order to use the charge function, please contact a Mitsubishi official sales office or supplier.
• The charge function can be set only for either WHM or No WHM.
• The filename is “(Month) (Year) *.csv”. (*: B=Block units, W=WHM units)
• When using the " Charge calculation function", it is necessary to register the license number the " Charge calculation function" separately with the G-50A the G-50A

8.4 Site Name Set-up

Set the site name which this integrated centralized control software TG - 2000A is installed.
Set the site name.
[Procedure]
1) Click the [Site name set -up] button. Click the [Site name set-up] button in the User Set -up Group in the Initial window.
Site Name Set -up
25
2) Enter the site name.
up
Enter the name of the site on the site name set -up screen from keyboard.
3) Click the [ OK] button. When finished entering the site name, click the [OK] button. * Click the [Cancel] button, the site name is left unchanged.
Note:
• Site names may contain a maximum of 20 characters. The site name is reflected upon the start ­screen and version confirmation screen display.
26

8.5 G-50 Connection Set-up

Number of G-50A set-up
Set the integrated centralized control software TG-2000A, number of G-50A units connected, and the IP address. It is possible for this setting to monitor and display the option functions state of the G-50A.

8.5.1 Setting Procedure and Restrictions

Confirm the precautions and procedure before setting the G-50A connection.
Perform the check before setting the G-50A connection.
[Procedure]
1) Select the [G-50 connection set -up] button. Click the [G-50 connection set -up] button located in the system setting group on the initial window.
2) Select the [ON] button after confirming the display contents. Check the contents of the alarm displayed. When there are not any problems found, click the [OK] button to advance to the setting. * When the [Cancel] button is clicked, this setting is
terminated to return to the initial screen.
Set the G-50A connection in accordance with the following procedure.
Step 1: Number of G-50 set -up Step 2: IP address of G-50 set -up

8.5.2 Number of G-50A set-up (Step 1)

Set the number of G-50 connected to the system.
Set-up the number of G-50A
[Procedure]
1) Click the “/ “ buttons. Use the “ Number of connectable G-50A units: 1 to 40 units
2) Click [ OK] button. When finished making settings , click the [OK] button. * When the [Cancel] button is clicked, this setting is
terminated to return to the initial window.
/
“ buttons to set the number of G-50A.

8.5.3 IP address of G-50A set-up (Step 2)

Set the data of the G-50A IP address connected to the data of the integrated centralized control software.
Register the G-50A IP address.
[Procedure]
1) Select the G-50 No. with the “/ “ buttons. In this case, use the “/ “ buttons to select the G-50A No. for which the IP address information is registered.
G-50 connection Set -up
27
IP address of G-50A set-up
Loading...
+ 68 hidden pages