Melco QA6ADP User Manual

QA6ADP QA Conversion
Adapter Module
User’s Manual
Thank you for buying the Mitsubishi general-purpose programmable logic controller MELSEC-Q Series
Prior to use, please read both this manual and detailed manual thoroughly and familiarize yourself with the product.
© 2007 MITSUBISHI ELECTRIC CORPORATION
MODEL QA6ADP-U-JE MODEL
CODE
IB(NA)-0800402-B(0803)MEE
13JY50

Revisions

* The manual number is noted at the lower right of the top cover.
Print Date *Manual Number Revision Aug., 2007 IB(NA)-0800402-A First printing Mar., 2008 IB(NA)-0800402-B
Partial correction Section 2.2, 6.1
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual
© 2007 MITSUBISHI ELECTRIC CORPORATION
1

CONTENTS

1. OVERVIEW....................................................................................................3
1.1 Overview ...............................................................................................3
1.2 Included Parts .......................................................................................3
2. SYSTEM CONFIGURATION .........................................................................4
2.1 System Configuration ............................................................................4
2.2 Configuration Device List.......................................................................5
3. SPECIFICATIONS .........................................................................................7
3.1 General Specifications...........................................................................7
3.2 Performance Specifications...................................................................8
4. PART NAMES AND SETTING.......................................................................9
4.1 Part Names ...........................................................................................9
4.2 Extension Stage Number Setting......................................................... 10
5. IMPLEMENTATION AND INSTALLATION...................................................11
5.1 Mounting/Removal of QA6ADP ...........................................................11
5.2 Connection/Disconnection of Extension Cable ....................................13
6. PRECAUTION FOR USING QA6ADP..........................................................16
6.1 Current Consumption of QA6ADP.......................................................16
6.2 Voltage Drop of Extension Cable.........................................................17
7. EXTERNAL DIMENSIONS...........................................................................18

GENERIC TERMS AND ABBREVIATIONS

Unless otherwise specified, this manual uses the following generic terms and abbreviations to explain the QA conversion adapter module.
Generic term/Abbreviation Description
Generic term for A52B, A55B, and A58B extension base units on which A series I/O
A5 B
module and special function module can be mounted without power supply. Generic term for A62B, A65B, and A68B extension base units on which A series I/O
A6 B
module and special function module can be mounted. Abbreviation for QA6ADP QA conversion
QA6ADP
adapter module. Abbreviation for A large type extension base unit
QA6ADP+A5 B/A6 B
on which QA6ADP is mounted.
2

1. OVERVIEW

1.1 Overview

This user’s manual describes the specifications, configuration device, part names and setting, and implementation and installation of the QA6ADP QA conversion adapter module. For contents that are not described in this manual such as safety precautions, EMC and low voltage directives, or error code list, refer to QCPU User’s Manual (Hardware Design, Maintenance and Inspection) (SH-080483). The QA6ADP is the adapter module connecting the A (large type) series extension base unit to the Q series main base unit.
Q3 B
A3 B
Replace the main base unit (A3 B)
with the extension base unit (QA6 B)
A6 B
Replace CPU with QCPU
Mount the QA6ADP on the extension base unit (A6 B)
QA6 B
A6 B
QA6ADP
POINT
The QA6ADP is CE-compliant. To meet the EMC directive, the extension base unit and module to be used in combination with the QA6ADP should be CE-compliant.
When using a control line or communication cable, keep it away from the main circuit or power line 100mm or more. Failure to do so may cause malfunction due to noise.

1.2 Included Parts

This section describes parts included with this module.
Product name Model Quantity Remarks QA6ADP QA conversion adapter module QA6ADP 1 --­Adapter module mounting bracket --- 1 --­Mounting bracket fixing screw --- 1 --­Boa rd f ix ing sc r ew --- 1 --­This manual --- 1 ---
3

2. SYSTEM CONFIGURATION

2.1 System Configuration

This section describes the system configuration and restrictions when the QA6ADP is used.
(1) The QA6ADP+A5 B/A6 B is only applicable for the High Performance
model QCPU (Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU).
(2) Mount the Q5
from the nearest position of the main base unit. The QA6ADP cannot be used in combination with the QA1S6
(3) The number of slots of the QA6ADP+A5
slots, regardless of the number of slots of the extension base unit to be used in combination with the QA6ADP. Assign the I/O number of a module, putting each series in block and in order of "Q series Failure to do so may cause an error (SP.UNITLAY ERR). In addition, do not duplicate the I/O number.
(4) For the extension stage number setting of the extension base unit, set
stage number (the first to seventh stages) to extension stages from the one nearest to the main base unit.
(5) An extension cable connectable to the QA6ADP is the Q series extension
cable only.
(6) Set the same stage number to both the stage number setting connector of
the extension base unit and that of the QA6ADP.
(7) The QA6ADP+A5
remote I/O station.
(8) The bus connection with GOT is not available for the QA6ADP+A5
B.
A6
[Extension stage number setting] Stage number setting connector
B/Q6 B, QA6 B, and QA6ADP+A5 B/A6 B in order
B.
B/A6 B is always displayed in 8
A series" or "A series Q series".
B/A6 B cannot be used as the MELSECNET/H
B/
High Performance model QCPU
01234567
Power
supply
1
2
8 9 10 11 12 13 14 15
Power
supply
16 17 18 19 20 21 22 23
Power
supply
24325 26 27 28 29 30 31
Power
supply
QA6ADP
Q38B
Q68B
QA68B
A68B
Main base unit
Q series compatible extension base unit (The Q5 B/Q6 B is connected to the main base unit or the Q5 B/Q6 B.)
A series compatible extension base unit (The QA6 B is connected to the main base unit, the end of the Q5 B/Q6 B, or the QA6 B.)
A series compatible extension base unit (The QA6ADP+A5 B/A6 B is connected to the main base unit, the end of the Q5 B/Q6 B/QA6 B, or the QA6ADP +A5 B/A6 B.)
4

2.2 Configuration Device List

(1) Extension base unit mountable on the QA6ADP
The following shows extension base units that can be mounted on the QA6ADP.
Product name Model Remarks
Extension base unit (Power supply module not
A52B, A55B, A58B,
A55B-UL, A58B-UL ---­mounting type) Extension base unit (Power supply module
A62B, A65B, A68B,
A65B-UL, A68B-UL ---­mounting type)
(2) Module mountable on the extension base unit where the QA6ADP is
mounted The following shows modules that can be mounted on the extension base unit where the QA6ADP is mounted.
Product name Model Remarks
Power supply module A61P, A61PN, A62P,
----
A63P, A61PEU, A62PEU Power supply module
A68P
----
(I/O slot mounting type) AC input module AX10, AX11, AX11EU,
*6
AX20, AX21, AX21EU AC/DC input module AX31, AX31-S1 ---­DC input module AX40, AX41, AX41-S1,
AX42, AX42-S1, AX50-S1,
AX60-S1, AX70, AX71,
----
AX80, AX80E, AX81,
AX81-S1, AX81-S2, AX81-S3,
AX81B, AX82 Contact output module AY10, AY10A, AY11,
AY11A, AY11E, AY11AEU,
----
AY11EEU, AY13, AY13E,
AY13EU, AY15EU Triac output module AY22, AY23 ---­Transistor output module AY40, AY40A, AY41,
AY42, AY42-S1, AY42-S2,
AY42-S3, AY42-S4, AY50,
AY51, AY51-S1, AY60,
---­AY60S, AY60E, AY70, AY71, AY72, AY80, AY81, AY82EP
Dynamic I/O module A42XY ---­Combined I/O module AH42 ----
5
Product name Model Remarks
High-speed counter
AD61, AD61S1
*1
module A/D converter module A68AD, A68AD-S2, A68ADN,
----
A616AD
D/A converter module A62DA, A62DA-S1, A68DAV,
----
A68DAI-S1, A616DAV, A616DAI
Temperature-digital
A68RD3N, A68RD4N, A616TD,
----
converter module
A60MX, A60MXRN, A60MXTN
Interrupt module AI61, AI61-S1 *2
AD70, AD72 ---- Positioning module AD75M1, AD75M2, AD75M3,
*1
AD75P1-S3, AD75P2-S3, AD75P3-S3
A-A1S module conversion
A1ADP-XY, A1ADP-SP
*3 *4
adapter MELSECNET/MINI-S3
AJ71PT32-S3,
*1
master module Intelligent communication
AJ71T32-S3 AD51, AD51-S3, AD51H,
*2
module
AD51H-S3 PC fault detection module AS91 ---­MELSEC-I/OLINK module AJ51T64 ---­B/NET interface module AJ71B62-S3 ---­Blank cover AG60 ---­Dummy module AG62 ----
*1: The dedicated instructions used in the QnA/A series program cannot be used in the
QCPU. Replace the dedicated instructions with the FROM/TO instructions.
*2: There is restriction on the number of mountable modules.
Product name Model
No. of mountable
modules
Intelligent communication
AD51, AD51-S3,
6
module
AD51H, AD51H-S3 Interrupt module AI61, AI61-S1 1 *5
*3: Using the A-A1S module conversion adapter enables to use modules equivalent to the
AnS module by the module shown in the table. For the mountable modules, refer to
A-A1S Module Conversion Adapter User's Manual (IB-0800352). *4: Only the multidrop link function can be used with the A1SJ71UC24-R4+A1ADP. *5: The interrupt module can use only one out of the QI60 (when mounted on the Q3 B,
Q5 B or Q6 B), AI61, and AI61-S1. *6: The normal operation of A series AC input module can be guaranteed only when the base
unit on which the A series power supply module is mounted exists in the system.
Make sure that the following condition is satisfied when A series AC input module is used.
y A series AC input module is mounted on the QA6 B or QA6ADP+A6 B. y A series AC input module is mounted on the QA6ADP+A5 B. However, A series
compatible extension base unit, QA6 B or QA6ADP+A6 B, exists in the system.
6

3. SPECIFICATIONS

3.1 General Specifications

This section describes general specifications of the QA6ADP.
Item Specifications
Operating ambient temperature Storage ambient temperature Operating ambient humidity Storage ambient humidity
Conforming Vibration resistance
Shock resistance
Operation ambiance Operating elevation *3 Installation location Overvoltage category *1 Pollution degree *2 2 max. Equipment category
to
JIS B 3502,
IEC 61131-2
Under intermittent vibration Under continuous vibration
(147 m/s2, 3 times in each of 3 directions XYZ)
10 to 90 % RH, No-condensing
10 to 90 % RH, No-condensing
Frequency
Conforming to JIS B 3502, IEC 61131-2
2000 m (6562 ft.) or less
*1: This indicates the section of the power supply to which the equipment is assumed
to be connected between the public electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*2: This index indicates the degree to which conductive material is generated in terms
of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected occasionally.
*3: Do not use or store the PLC in the environment when the pressure is higher than
the atmospheric pressure at sea level. Otherwise, malfunction may result. To use the PLC in high-pressure environment, please contact your local Mitsubishi Repress entative.
0 to 55
-20 to 75
Accelera
-tion
10 to 57 Hz ---- 0.075 mm
57 to 150 Hz 9.8 m/s
10 to 57 Hz ----
57 to 150 Hz 4.9 m/s
No corrosive gasses
Control panel
II max.
Class I
Amplitude
2
2
----
00.35 mm (0.001 in.)
----
Sweep
count
10 times
each in
X, Y, Z
directions
(for 80
min).
7

3.2 Performance Specifications

This section describes performance specifications of the QA6ADP.
Item Specifications
5VDC internal current consumption
130 mm (5.11 inch) (H) 73.5 mm (2.89 inch)
External dimensions *1
74 (2.91 inch) mm (D) Weight 0.2 kg Adapter mounting screw
(M3) torque Board fixing screw
torque
*1: The external dimensions show values in a status where the QA6ADP is
mounted on the extension base unit.
110 mA
(W)
0.36 to 0.48 N•m
0.61 to 0.82 N•m
8

4. PART NAMES AND SETTING

4.1 Part Names

This section describes part names of the QA6ADP.
9) 8)
3)
1)
7)
4)
5)
3)
6)
2)
No. Name Application
Extension cable
1) connector
Stage number
2) setting connector
Adapter module
3)
mounting screw (M3 screw)
Adapter module
4) mounting bracket
Mounting bracket
5) fixing screw
Base side stage
6)
number setting connector window Extension base unit
7) mounting connector
8) Board fixing screw
Connector for sending/receiving signals to the main base unit or the other extension base unit and connecting an extension cable.
Connector for setting the number of extension stages.
Screw for mounting this adapter module on the extension base unit.
Bracket for mounting this adapter module on the extension base unit. Utilize screws used in the extension base unit. (Included parts) Screw for mounting an adapter module mounting bracket on the extension base unit. (Included parts)
Window is transparent so that a stage number setting connecter of the extension base unit side can be seen.
Connector to be connected to the A extension cable I/O connecter of the extension base unit. Screw for mounting this adapter module on the extension base unit. (Included parts) Guide for positioning an extension base unit mounting
9) Mounting guide
connector by inserting this into a cover fixing square hole of the extension base unit at the time of mounting.
9

4.2 Extension Stage Number Setting

Set the number of extension stages to both the QA6ADP and the extension base unit. The same stage number should be set to both the stage number setting connector of the extension base unit and that of the QA6ADP.
POINT Set any number of 1 to 7 which matches to the number of extension stages for the stage number setting connector setting. If the stage number setting of the QA6ADP and that of the extension base unit is different, the two or more settings are made to one stage, the same stage number is duplicated, or no setting is made to the number of stages, incorrect input or incorrect output will occur.
(1) Extension stage number setting of the QA6ADP
The following describes how to set the number of extension stages of the QA6ADP.
Extension stage number setting
st
1
stage
2nd
stage
3rd
stage
4th
stage
5th
stage
Stage number setting connector setting
(2) Extension stage number setting of the extension base unit
Remove a base cover from the extension base unit.
Insert a connector pin into the place of the stage number selected from 1 to 7 of the connector (CON3) at bottom left of the base unit.
6th
stage
7th
stage
Stage number setting connector setting
Completed
st
1
stage
2nd
stage
Extension stage number setting
3rd
stage
10
Stage number setting connector
4th
stage
5th
stage
6th
stage
7th
stage

5. LOADING AND INSTALLATION

5.1 Mounting/Removal of QA6ADP

(1) Mounting of the QA6ADP
The following shows procedures for mounting the QA6ADP on the extension base unit.
Disconnect the A series extension cable from the extension base unit.
Remove a base cover from the extension base unit.
Set the stage number setting connector of the extension base unit.
Set the stage number setting connector of the QA6ADP. (The setting should be same as that of the stage number setting connector of the extension base unit.)
A)
In case of the A5 B, disconnect a lead of the FG terminal (right side).
Among screws fixing a board of the extension base unit, remove two at the left. (Screws A and B shown in the figure.)
Utilize a mounting bracket fixing screw to mount the adapter module mounting bracket of the QA6ADP into a screw hole (B) at the bottom left of the board.
Mount a board fixing screw of the QA6ADP to a screw hole (A) at top left of the board.
Connect an extension base unit mounting connector of the QA6ADP to the IN side of an extension connector of the extension base unit.
Tighten the adapter module mounting screws of the QA6ADP at two parts (top and bottom), placing a mounting guide.
Mount an upper mounting screw to a board fixing screw (at top left) of the extension base unit. Mount a lower mounting screw to the
adapter module mounting bracket.
Extension base unit IN side connector
Adapter module mounting bracket
B)
Board fixing screw
Mounting guide
Adapter module mounting screw
In case of the A5 B, connect the disconnected lead of the FG terminal (right side).
Connect the Q series extension cable to the QA6ADP and the upper/lower base unit.
Completed
ounting bracket
M fixing screw
11
Adapter module
QA6ADP
mounting screw
(2) Removal of the QA6ADP
The following shows procedures for removing the QA6ADP from the extension base unit.
Disconnect an extension cable form the QA6ADP.
Remove the adapter module mounting screws of the QA6ADP at two parts (top and bottom).
Remove the QA6ADP main body from the extension base unit.
Remove a board fixing screw and an adapter module mounting bracket of the QA6ADP.
Mount a screw fixing the board of the extension base unit at two parts on the left.
Board fixing screw
Extension base unit IN side connector
Adapter module mounting bracket
ounting bracket fixing screw
M
Mounting guide
Adapter module mounting screw
Please a base cover over the extension base unit.
Completed
Adapter module mounting screw
QA6ADP
12
t

5.2 Connection/Disconnection of Extension Cable

(1) Precautions for handling an extension cable
Do not step on an extension cable.
When laying an extension cable, the minimum bend radius of the cable
should be 55 mm (2.17 inch) or more. If it is less than 55 mm (2.17 inch), malfunction may occur due to characteristic deterioration, wire break etc.
When connecting or disconnecting an extension cable, do not hold ferrite cores mounted at both ends of the cable. In case of connecting/disconnecting a cable, hold the connector part of the cable.
Extension base uni
Holding a ferrite core may cause cable break inside the connector. Also, if the ferrite core is shifted, the characteristic will change. When handling the cable, take care not to change position of the ferrite core.
(2) Connection of extension cable
The following shows extension cables connectable to the QA6ADP.
Model Remarks QC05B 0.45m cable QC06B 0.6m cable QC12B 1.2m cable QC30B 3m cable QC50B 5m cable
QC100B 10m cable
Ferrite core
Extension
cable
Connector
POINT When connecting the base unit of the previous stage and the QA6ADP with an extension cable, be sure to connect the OUT side connector of the base unit of the previous stage and the IN side connector of the QA6ADP. If an extension cable is connected in the wrong way (IN
OUT), the system will not operate normally.
IN
IN, OUT OUT or
13
t
t
To connect an extension cable to the QA6ADP, remove a sticker on the IN side connector.
Base cover
IN side
QA6ADP
Sticker
Extension base uni
To connect an extension cable to the OUT side connector of the QA6ADP, remove the portion (lid) under the characters "OUT" by tools such as a flathead screwdriver (5.5
75, 6 100).
Extension base uni
QA6ADP
Base cover
OUT side
Flathead screwdriver
Cutting one
thin-walled part
14
r
Hold the connector part of an extension cable when connecting the extension cable to the QA6ADP.
Extension base unit
QA6ADP
Connector
Extension cable
Make sure to tighten fixing screws of the extension cable connector after connecting the extension cable. (Tightening torque: 0.20 Nm)
Extension base unit
Flathead screwdrive
QA6ADP
Fixing screw
(3) Disconnection of extension cable
When disconnecting an extension cable, hold and pull the connector part of the extension cable after making sure that fixing screws have been completely removed.
15

6. PRECAUTION FOR USING QA6ADP

6.1 Current Consumption of QA6ADP

Since 5VDC is supplied to the QA6ADP from the power supply module of the main base unit, take the current consumption of the QA6ADP into consideration when selecting the power supply module for the main base unit.
Current consumption of CPU
and I/O of main base unit
Current consumption
of I/O of Q5 B
Current consumption
of I/O of A5 B
n: Quantity of QA6ADP in system*1
Current consumption
of QA6ADP n
*1The quantity of the QA6ADP includes the QA6ADP when the A6B is used.
The following shows the concept of the current consumption of the power supply module mounted on the main base unit.
Main base unit
Power supply
module
I0
Extension base unit (QA6 B)
Power supply
module
I1
Extension base unit (A5 B)
IA
I2
First extension stage
Second extension stage
Extension base unit (A5 B)
IA
I3
Extension base unit (A6 B)
IA
Power supply
module
I4
Third extension stage
Fourth extension stage
Symbol Description
I Rated current of power supply module on the main base unit
I0
I1 to I4
Current consumption of CPU and I/O modules mounted on the main base unit Current consumption of I/O mounted on the extension base unit in first to fourth stages
IA Current consumption of the QA6ADP
In case of the above system, use the QA6ADP when the current consumption of the power supply module mounted on the main base unit meets the following formula.
[Calculating formula]
I I0 I2 I3 IA 3
16

6.2 Voltage Drop of Extension Cable

Since 5VDC is supplied to the QA6ADP from the power supply module mounted on the main base unit, the voltage drop will be caused in the extension cable. If the specified voltage (4.75VDC or more) is not supplied to the IN side connector of the QA6ADP+A5
B/A6 B, wrong input/output may occur. When using the QA6ADP, check that the IN side connector of the QA6ADP+A5
B/A6 B has 4.75VDC or more.
The following shows an example regarding how to calculate the voltage drop.
Main base unit
Power supply
module
R1V1
R2V2
Extension base unit (QA6 B)
Power
supply
module
I1
Extension base unit (A5 B)
IA
First extension stage
Model
QC05B 0.044 QC06B 0.051 QC12B 0.082
Conductor
resistance value
QC30B 0.172
I2
Second extension stage
QC50B 0.273
QC100B 0.530
R3V3
Extension base unit (A6 B)
IA
Power supply
module
I3
Third extension stage
Symbol Description
V Sum of voltage drop
V1
Vn
R1
Rn
I1 to I3 5VDC current consumption in the first to third stages *1
IA Current consumption of the QA6ADP
Voltage drop due to an extension cable between the main base unit and the QA6
B Voltage drop due to an extension cable between the extension base unit (n-1th extension stage) and the extension base unit (nth extension stage) Resistance value of a cable between the main base unit and the extension base unit QA6
B Resistance value of an extension cable between the extension base unit (n-1th extension stage) and the extension base unit (nth extension stage)
*1: Since the current consumptions I1 to I3 vary depending on modules to be
mounted, refer to the manual for the module to be mounted.
[Calculating formula]
V V1 V2 V3 R1 ( I2 IA 2 ) R2 ( I2 IA 2 ) R3 IA
The minimum value of the 5VDC output voltage of the power supply module mounted on the main base unit is set to 4.90VDC. Therefore, the voltage of the IN side connector of the QA6ADP+A5
B/A6 B in the final stage is 4.75VDC or
more only when the sum (V) of voltage drop is 0.15V or less.
17

7. COMPATIBLE MODELS LIST

This chapter describes external dimensions of the QA6ADP.
A series extension base unit that you have already had
130 (5.11)
QA6ADP QA conversion adapter module
Handle
74 (2.91)
2 6-M4 screw
(for mounting module)
4- 6mounting hole
(M5 mounting screw)
I/OPOWER I/OI/OI/OI/O
200 (7.87)
73.5 (2.89)
Power supply module, Extension cable
Power supply module
Extension cable
250 (9.84)
9 (0.35)
121 (4.76)
172 (6.77)
Unit: mm (inch)
18

Warranty

Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
For safe use
y This product has been manufactured as a general-purpose part for general industries, and
has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
y Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
y This product has been manufactured under strict quality control. However, when installing
the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A Mitsubishi Electric Automation Inc. 500 Corporate Woods Parkway Vernon Hills, IL 60061, U.S.A. Tel : +1-847-478-2100 Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda. Rua Correia Dias, 184, Edificio Paraiso Trade Center-8 andar Paraiso, Sao Paulo, SP Brazil Tel : +55-11-5908-8331 Germany Mitsubishi Electric Europe B.V. German Branch Gothaer Strasse 8 D-40880 Ratingen, GERMANY Tel : +49-2102-486-0 U.K Mitsubishi Electric Europe B.V. UK Branch Travellers Lane, Hatfield, Hertfordshire., AL10 8XB, U.K. Tel : +44-1707-276100 Italy Mitsubishi Electric Europe B.V. Italian Branch Centro Dir. Colleoni, Pal. Perseo-Ingr.2 Via Paracelso 12, I-20041 Agrate Brianza., Milano, Italy Tel : +39-039-60531 Spain Mitsubishi Electric Europe B.V. Spanish Branch Carretera de Rubi 76-80, E-08190 Sant Cugat del Valles, Barcelona, Spain Tel : +34-93-565-3131 France Mitsubishi Electric Europe B.V. French Branch 25, Boulevard des Bouvets, F-92741 Nanterre Cedex, France TEL: +33-1-5568-5568 South Africa Circuit Breaker Industries Ltd. Private Bag 2016, ZA-1600 Isando, South Africa Tel : +27-11-928-2000
Country/Region Sales office/Tel
Hong Kong Mitsubishi Electric Automation (Hong Kong) Ltd. 10th Floor, Manulife Tower, 169 Electric Road, North Point, Hong Kong Tel : +852-2887-8870 China Mitsubishi Electric Automation (Shanghai) Ltd. 4/F Zhi Fu Plazz, No.80 Xin Chang Road, Shanghai 200003, China Tel : +86-21-6120-0808 Taiwan Setsuyo Enterprise Co., Ltd. 6F No.105 Wu-Kung 3rd.Rd, Wu-Ku Hsiang, Taipei Hsine, Taiwan Tel : +886-2-2299-2499 Korea Mitsubishi Electric Automation Korea Co., Ltd. 1480-6, Gayang-dong, Gangseo-ku Seoul 157-200, Korea Tel : +82-2-3660-9552 Singapore Mitsubishi Electric Asia Pte, Ltd. 307 Alexandra Road #05-01/02, Mitsubishi Electric Building, Singapore 159943 Tel : +65-6470-2460 Thailand Mitsubishi Electric Automation (Thailand) Co., Ltd. Bang-Chan Industrial Estate No.111 Moo 4, Serithai Rd, T.Kannayao, A.Kannayao, Bangkok 10230 Thailand Tel : +66-2-517-1326 Indonesia P.T. Autoteknindo Sumber Makmur Muara Karang Selatan, Block A/Utara No.1 Kav. No.11 Kawasan Industri Pergudangan Jakarta - Utara 14440, P.O.Box 5045 Jakarta, 11050 Indonesia Tel : +62-21-6630833 India Messung Systems Pvt, Ltd. Electronic Sadan NO:III Unit No15, M.I.D.C Bhosari, Pune-411026, India Tel : +91-20-2712-3130 Australia Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, Rydalmere, N.S.W 2116, Australia Tel : +61-2-9684-7777
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORK S : 1-14, YA DA-MINAMI 5-C HOME, HIGASHI -KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan on recycled paper.
Loading...