Mitsubishi Electric Corporation Nagoya Works is a factory certified for ISO14001 (standards for
environmental management systems) and ISO9001 (standards for quality assurance management systems).
EC97J1113
Page 2
Evolution of the inverter for fan and pump applications,
Evolution of the inverter for fan and pump applications,
A
V
S
I
N
E
G
R
S
O
!
M
energy savings for buildings and factories as a whole
energy savings for buildings and factories as a whole
BEST
MATCH
Features
1
(1)
Upgrade of the renown Optimum Excitation Control!!
•Achieved a higher level of energy savings during acc./dec. to say
nothing of during constant speed.
[Ex. of Blower Operation Characteristics]
100
Commercial
power
operation
80
60
40
20
Power Consumption (%)
01020304050 60
V/F control
Optimum
excitation
control
Frequency (Hz)
Easy replacement with
the cooling fan cassette!!
[Ratio of Motor Power Consumption during Acc./Dec.]
Driving of the Mitsubishi 400V 4 poles
45kW motors comparison
100
90
Power Consumption Ratio (%)
RS-485 communication is
C
possible with PU connector
Conventional model(FR-F500)
6%
12%
FR-F700
0 1020304050
Motor Lord Torque (%)
H
(2)
The effect of energy savings is obvious
•The effect of energy savings can be confirmed using the
operation panel, output terminal (FM, AM terminal) and
via networks with the newly developed energy saving
monitor.
Ex. of Power Savings
Monitor Display
[Energy Saving Monitor List]
Power saving monitor (kW)
Power saving rate (%)
Power saving amount (kWh)
Power saving amount charge ($)
Power saving average value (kW)
Power saving rate average value (%)
Power saving charge average value ($)
Annual power saving amount (kWh)
Annual power saving amount charge ($)
Easy operation
A
A
with the setting
dial of the
operation panel
(1) Adjustable 5 points V/F
•Possible to set the torque
pattern that is optimum for the
machine's characteristic
•Possible to expect even more
energy savings with optimum
excitation control and optimum
V/F pattern working together
(2) Enhanced PID function
•
Energy savings in low speed region ... PID shutoff (sleep control) function
•
Shorter PID startup time ... PID automatic switchover function
•
Monitor of set point/measured value/deviation possible ... PID monitor
•
Convenient for HVAC usage ... forward/reverse operation switchover
is simple with an external signal
•
Corresponds to a wide range of detectors ... set point and measured value
for PID input can either be voltage (0 to 5V/0 to 10 V) or current (4 to 20mA)
(3)
Adoption of the original operation continuation
at instantaneous power failure function
•Operation continues without
the motor coasting when an
instantaneous power failure
occurred in fan and blower
applications.
*The inverter may trip and the motor may
coast depending on the load condition.
Input
Power Supply
Voltage
V/F3
V/F2
V/F5
V/F4
Torque
characteristic
curves
IPF
Reacceleration
Base
Voltage
Frequency
V/F
pattern
V/F1
0
V/F Characteristic
When power is restored during deceleration
Output
Frequency
Deceleration
Base
Frequency
(4) Restart after instantaneous
•Restart can be made without stopping the
motor when the motor is coasting due to an
instantaneous power failure.
(5) Flying start
Frequency
•Smoothly restarts a motor that is rotating even in
the opposite direction due to the windmill effect.
(6)
•
Possible to avoid regeneration overvoltage alarm by
automatically increasing the frequency and continue
operation if the fan happens to rotate faster due to
the effect of another fan in the same duct.
(7) PTC thermistor input
•Protection of the motor can be certain since the
built-in PTC of the motor can be input directly in
addition to the electronic thermal relay function.
PTC thermistor input…Positive Temperature Coefficient Thermistor
(8) Commercial power-supply
•
Switchover to commercial power-supply operation is
simple using R1 and S1 terminals of the control circuit
and commercial power-supply switchover sequence.
power failure function
Regeneration avoidance function
I
switchover sequence
Connection with
Peripheral Devices
Why can the inverter
save energy?
Adoption of newly developed long life cooling fan (design life of 10 years*1)
Longer operating life is further enhanced with the use of ON/OFF control of cooling fan.
•Adoption of long life capacitor (design life of 10 years*
A capacitor with specification of 5000 hours at 105˚C ambient temperature is adapted.
*1
Ambient temperature: yearly average 40˚C (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Since the design life is a calculated value, it is not a guaranteed value.
*2 Output current: 80% of the rated current of Mitsubishi standard 4P motor
(2)
State of the art longevity diagnostic method
•
Degrees of deterioration of main circuit capacitor, control circuit
capacitor or inrush current limit circuit can be diagnosed by monitor.
•Trouble can be avoided with the self-diagnostic alarms* that is
I
output when the life span is near.
*Any of alarm for main circuit capacitor, control circuit capacitor, inrush current limit
circuit and cooling fan can be output.
1, 2
)
(3) Maintenance timer
•Maintenance timer output function can also inform of
maintenance time for peripheral equipments.
Average output current value and maintenance timer value are output as pulses.
•
(5) Improved workability
Easy replacement of cooling fan
D
Removable terminal block
B
Photo:FR-F740-5.5K
•
¥The installation position of the cooling fan is in the
upper portion of the inverter.
Fan replacement is easily done without having to
remove the main circuit wires.
Wiring is easy with the combed shaped wiring cover
•
¥Wiring cover can be reinstalled after wiring.
(200V class 22K or less, 400V class 30K or less)
C
D
(4) Update is also easy
•Removable terminal block
¥When exchanging the inverter, the control
circuit terminals can be exchanged.
The removable terminal block of the FRF500 series can be used.
(The terminal block of the FR-F700 series is compatible with
that of the FR-F500 series.
Note that some functions of the FR-F700 series are restricted
when using the terminal block of the FR-F500 series.)
FR-F500 series
•
Possible to copy parameters with operation panel
¥Parameter setting for multiple inverters is simple by
copy with the operation panel.
•Alarm history
¥
Alarm history (alarm details and frequency, current, voltage
and cumulative energization time at time of alarm
occurrence) can be displayed on the operation panel and
the cause of a trouble can be checked.(up to 8 past alarms)
B
FR-F700 series
A
Option and
Peripheral Devices
Precautions for
Operation/Selection
Precautions for Peripheral
Device Selection
Application to Motor
Main differences and
compatibilities with
the FR-F500(L) series
Warranty
International FA center
47
49
59
63
64
65
66
21
Page 3
Full of attractive features!
(1)
(1)
Reduction of electromagnetic noises
EF
•Inverter noises have been reduced with the adoption of new technologies.
•Newly developed noise filter (EMC filter)
¥Because of the built-in EMC filter, the inverter itself can
comply with the EMC Directive (2nd environment*
setting the connector to "with filter"(*
[FR-F740-37K Conducted noise data]
130
[dBuV]
120
110
100
90
80
70
60
50
40
30
20
10
0
.15 .2 .3.5 .7 12 35 7 1020 30
*1:
Refer to the EMC instruction manual for compliance conditions.
*2: Leakage current will increase when the EMC filter is selected.
*3: Since the leakage current when using the EMC filter for the 200V class 0.75K and
1.5K is small, the filter is always valid (a setting connector is not provided).
¥
Because of the built-in capacitive filter and zero-phase reactor (55K or less),
2,*3
).
EN61800-3
second Environment QP level
QP value
1
Frequency [MHz]
) by
connecting the optional DC reactor to the inverter will comply with the
electric installation work common specification and machine installation
work common specification (2001) written under the general editorship of
the Japanese Ministry of land, infrastructure and transportation.
Capacitive filter
55K or less
75K or more
(2)
Countermeasures for harmonic current output
Standard (Built-in)
Standard (Built-in)
Zero-phase reactor
Standard (Built-in)
Option (Sell separately)
DC reactor
Option (Sell separately)
Standard (supplied)
•Small AC reactor (FR-HAL)/DC reactor (FR-HEL)
¥
AC reactor and DC reactor options for the control of
harmonics current output has been miniaturized.
(DC reactor is supplied with the 75K or more as standard.)
•
Connection with high power factor converter (FR-HC/MT-HC) is possible
¥Connection is possible to high power-factor converter for effective
suppressions of power-supply harmonics (coefficient K5=0).
(3)
Equipped with inrush current limit circuit
•
Because of the built-in inrush current limit circuit, the current
at power on is restricted.
Equipped with operation panel with the popular setting dial
•Operation is easy with the popular setting dial.
¥Frequency and parameters can be set without frustrations.
¥
Settings can be made quickly or slowly depending on fast
the dial is being turned.
¥
Settings are certain due to the "clicking" sensation and notch on dial.
Example of parameter change
•Operation panel is detachable and can be installed on the
front cover. (Cable connector
option is required.)
•PU/EXT (operation mode)
switchover key is available.
•Dial/key operation lock
function is available.
(2) FR Configurator (setup software)
•
From start up to maintenance of the inverter is simple.
•
Possible to save and print parameter setting file making
parameter management simple
(Possible to use communications connecting to any of PU connector and RS-485 terminals)
AGH
(1)
RS-485 terminal is standard equipped
(1)
Complies with UL, cUL, EN (LVD) standards
•RS-485 terminals are available in addition to the PU.
connector. RS-485 communication can be performed using
the operation panel or parameter unit. Since terminals for
input and output are provided separately, multi-drop
connection is easily done.
(2)
•Modbus-RTU (Binary) protocol has been added for
communications in addition to computer link.
Possible to switch sink/source with one-touch
Possible to switch the logic of I/O terminals. Possible to use in
•
all regions
(2)
Possible to correspond with major networks
(3)Wide voltage range
•
Accommodate both 240V power supply (55K or less) and
480V power supply as standard
(1) Remote output function
•You can utilize the on/off of the inverter's output signals
instead of the remote output function of the programmable
logic controller.
(2) Enhanced I/O is standard
PU/EXT
Example of
operation mode
•Possible to connect with LONWORKS, CC-Link Ver.1.1 and Ver.2.0,
TM
DeviceNet
and Profibus-DP when used with communication
options
Power
supply
unit
Terminating
resistor
CPU
Master
CC-Link
dedicated cable
Inverter
Up to 42 units can
be connected
when connections
( )
are inverter only
FR-A7NCFR-A7NC
CC-Link network
Network management
computer
Inverter
Terminating
resistor
•12 contact inputs, 3 analog inputs, 5 open collector outputs, 2
Inverter
Air-conditioner
Inverter
Pump
relay outputs, analog output and pulse output are all standard.
•Possible to assign variety of functions to contact inputs, open
collector outputs and relay outputs
Possible to switch between voltage and current for the analog input.
•
FR-A7NL
LONWORKS
Network
Free
Topology
NodeNode
FR-A7NL
•Possible to display the ON/OFF status of the I/O terminals on
the operation panel
(3)
Simple magnetic flux vector control is possible
•High torque in low speed region is possible with simple
magnetic flux vector control
(120% torque is possible at 3Hz with slip compensation)
Peripheral devices necessary for driving the FR-F700 series inverter are indicated below.
Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter.
(Refer to page 7.)
Moulded case circuit
breaker (MCCB)
or earth leakage circuit
breaker (ELB), fuse
The breaker must be selected carefully since
an in-rush current flows in the inverter at
power on.
(Refer to page 57.)
Magnetic contactor(MC)
Install the magnetic contactor to ensure safety.
Do not use this magnetic contactor to start and
stop the inverter.
Doing so will cause the inverter life to be shorten.
(Refer to page 57.).
Reactor (FR-HAL, FR-HEL)
Reactors (option) should be used when power
harmonics measures are taken, the power factor
is to be improved or the inverter is installed near a
large power supply system (1000kVA or more).
The inverter may be damaged if you do not use
reactors.
Select the reactor according to the model.
For the 55K or less, remove the jumpers across
terminals P/+-P1 to connect to the DC reactor.
(Refer to page 51.).
PLC
RS-485 terminal block
The inverter can be
connected with computers
such as PLC.
It supports Mitsubishi inverter
protocol and Modbus-RTU
(binary) protocol.
Inverter (FR-F700)
The life of the inverter is influenced by ambient temperature.
The ambient temperature should be as low as possible within
the permissible range. (Refer to page 8.) This must be noted
especially when the inverter is installed in an enclosure.
Wrong wiring might lead to damage of the inverter. The control
signal lines must be kept fully away from the main circuit to
protect them from noise.
AC reactor
(FR-HAL)
(Refer to page 51.)
Noise filter
(FR-BLF)
It is not necessary
for the 55K or less.
High power factor
converter
*1, MT-HC*2)
(FR-HC
Power supply harmonics
can be greatly suppressed.
Install this as required.
*1 Compatible with the 55K or less.
*2 Compatible with the 75K or more.
Refer to page 49 for the option list and details.
DC reactor
(FR-HEL)
For the 75K or more, a DC
reactor is supplied.
Always install the reactor.
(Refer to page 51.)
Power regeneration
common converter
*1)
(FR-CV
Power regeneration
converter (MT-RC
Greater braking capability
is obtained.
Install this as required.
*2)
R/L1 S/L2 T/L3
P/+
P1
Brake unit
*1, MT-BU5*2)
(FR-BU
PR
P/+
P/+
PR
Resistor unit
*1, MT-BR5*2)
(FR-BR
The regenerative braking
capability of the inverter can be
exhibited fully.
Install this as required.
Noise filter
(FR-BSF01, FR-BLF)
N/-P/+
Earth
(Ground)
UVW
Install a noise filter to reduce
the electromagnetic noise
generated from the inverter.
Effective in the range from
about 1MHz to 10MHz.
When more wires are passed
through, a more effective result
can be obtained.
Earth
(Ground)
Devices connected to the output
Do not install a power factor correction capacitor,
surge suppressor or radio noise filter on the output
side of the inverter.
When installing a moulded case circuit breaker on the
output side of the inverter, contact each manufacturer
for selection of the moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth
(ground) the motor and inverter.
Motor
5
Page 5
Why Can the Inverter Save Energy?
The load torque of a motor-driven machine generally changes depending on speed. On the other hand, motor output is
proportional to the product of load torque and speed as indicated in the following formula, and therefore, necessary motor
output varies with speed.
Motor output P = T
× N/(9550 × η) [kW]
T : Motor shaft-equivalent load torque [N·m]
N : Motor speed [r/min]
η : Machine efficiency
When this motor is operated by the inverter, the inverter output provides the frequency f appropriate to the motor speed,
and the then output voltage V is determined by a "V/f = constant" pattern in the case of a constant-torque load.
For example, when the motor is operated at middle speed, f, i.e. output voltage V, decreases, and therefore, the inverter
output power V × I reduces if the output current I is constant.
Proportionately, the inverter input current decreases and the power consumption reduces. Namely, when the motor output
reduces, the input power of the inverter also decreases as a matter of course.
The fundamental principle of energy saving by the inverter is to eliminate wasted power consumption by minimizing loss
caused by the other devices and minimizing the motor output as compared to the other system (for example, commercial
power supply operation or secondary resistance control of wound-rotor motor). A maximum energy saving effect is
produced on a fan, pump or like by the variable-torque load characteristic that reduces load torque as speed decreases.
Motor speed control enables substantial energy-saving operation as compared to commercial power supply operation.
Damper control (discharge side)
100
80
For example, when a 15kW motor is operated at 60% air volume and
the power charge is 17 yen/kW·h, the power charge as much as below
can be saved in a year.
Overload current rating*4120% 60s, 150% 3s (inverse time characteristics)
Voltage*5Three-phase 380 to 480V
Rated input AC voltage/frequencyThree-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation323 to 528V 50Hz/60Hz
Permissible frequency fluctuation±5%
Power supply system capacity (kVA)*6 110137165198247275329366416464520586659733833
Power supply
Protective structure (JEM 1030)*8Open type (IP00)
Cooling systemForced air cooling
Approx. mass (kg)375057727211011 0220220220260260370370370
*1. The applied motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2. The rated output capacity indicated assumes that the output voltage is 220V for 200V class and 440V for 400V class.
*3. When operating the inverter with the carrier frequency set to 3kHz or more, the carrier frequency automatically decreases if the inverter output
current exceeds the value in parenthesis of the rated current. This may cause the motor noise to increase.
*4. The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.
*5. The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply.
*6. The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
*7. When the hook of the inverter front cover is cut off for installation of the plug-in option, the inverter changes to an open type (IP00).
*8. FR-DU07 : IP40 (Except for the PU connector).
7590110132160185220250280315355400450500560
144
180
216
260
325
361
432
481
547
610
683
770
866
(122)
(153)
(183)
(221)
(276)
(306)
(367)
(408)
(464)
2
(518)
(580)
(654)
(736)
962
(817)
1094
(929)
7
Page 7
Common specifications
Control systemHigh carrier frequency PWM control (V/F control)/optimum excitation control/simple magnetic flux vector control
Output frequency range0.5 to 400Hz
0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12bit)
Frequency
Analog input
setting resolution
Digital input0.01Hz
Frequency
accuracy
Analog inputWithin ±0.2% of the max. output frequency (25°C ± 10°C)
Digital inputWithin 0.01% of the set output frequency
Voltage/frequency characteristics
Starting torque120% (3Hz) when set to simple magnetic flux vector control and slip compensation
Control specifications
Acceleration/deceleration time setting
DC injection brakeOperation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) variable
Stall prevention operation levelOperation current level can be set (0 to 150% adjustable), whether to use the function or not can be selected
Frequency
setting signal
Analog input
Digital inputFour-digit BCD or16-bit binary using the setting dial of the operation panel (when used with the option FR-A7AX)
Start signal
Input signals
Operational functions
Operation specifications
Operating status
Output signals
When used with the
FR-A7AY, FR-A7AR
(option)
Pulse/analog output
PU
(FR-DU07/
FR-PU04)
Display
Operating status
Alarm definition
Interactive guidanceOperation guide/trouble shooting with a help function*2
*1. Can be displayed only on the operation panel (FR-DU07).
*2. Can be displayed only on the parameter unit (FR-PU04).
*3. Temperature applicable for a short period in transit, etc.
*4. Only the 75K or more functions.
2
*5. 2.9m/s
or less for the 185K or more.
0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/11bit, terminal 1: -10V to +10V/11bit)
0.06Hz/0 to 60Hz (terminal 1: 0 to ±5V/10bit)
Base frequency can be set from 0 to 400Hz Constant torque/variable torque pattern or adjustable 5 points V/F can
be selected
0 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode
can be selected.
Terminal 2, 4: 0 to 10V, 0 to 5V, 4 to 20mA can be selected
Terminal 1: -10 to +10V, -5 to 5V can be selected
Available individually for forward rotation and reverse rotation. Start signal automatic self-holding input (3-wire input)
can be selected.
You can select any twelve signals using Pr.178 to Pr.189 (input terminal function selection) from among multi speed
selection, second function selection, terminal 4 input selection, JOG operation selection, selection of automatic
restart after instantaneous power failure, external thermal relay input, HC connection (inverter operation enable
signal), HC connection (instantaneous power failure detection), PU operation/external inter lock signal , PID control
enable terminal, PU operation, external operation switchover, output stop, start self-holding selection, forward
rotation command, reverse rotation command, inverter reset, PTC thermistor input, PID forward reverse operation
switchover, PU-NET operation switchover, NET-external operation switchover, command source switchover.
Maximum and minimum frequency settings, frequency jump operation, external thermal relay input selection, polarity
reversible operation, automatic restart after instantaneous power failure operation, original operation continuation at
instantaneous power failure, commercial power supply-inverter switchover operation, forward/reverse rotation
prevention, operation mode selection, PID control, computer link operation (RS-485).
You can select any seven signals using Pr.190 to Pr.196 (output terminal function selection) from among inverter
running, up-to-speed, instantaneous power failure /undervoltage, overload warning, output frequency detection, second
output frequency detection, regenerative brake prealarm
mode, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit, PID
*4, electronic thermal relay function pre-alarm, PU operation
forward rotation reverse rotation output, commercial power supply-inverter switchover MC1, commercial power supplyinverter switchover MC2, commercial power supply-inverter switchover MC3, fan fault output, heatsink overheat prealarm, inverter running start command on, deceleration at an instantaneous power failure, PID control activated, during
retry, during PID output suspension, life alarm, alarm output 3 (power-off signal), power savings average value update
timing, current average monitor, alarm output 2, maintenance timer alarm, remote output, minor failure output, alarm
output. Open collector output (5 points), relay output (2 points) and alarm code of the inverter can be output (4 bit) from
the open collector.
You can select any seven signals using Pr.313 to Pr. 319 (extension output terminal function selection) from among
control circuit capacitor life, main circuit capacitor life, cooling fan life, inrush current limit circuit life and the above
stated signals. (Only positive logic can be set for terminals of the FR-A7AR.)
Selection can be made from output frequency, motor current (steady or peak value), output voltage, frequency setting
value, running speed, converter output voltage (steady or peak value), electronic thermal relay function load factor,
input power, output power, load meter, reference voltage output, motor load factor, power saving effect, regenerative
brake duty
Pr.158 "AM terminal function selection (analog output)".
*4, PID set value, PID measured value using Pr.54 "FM terminal function selection (pulse train output)" and
Output frequency, motor current (steady or peak value), output voltage, frequency setting, running speed, converter
output voltage (steady or peak value), electronic thermal relay function load factor, input power, output power, load
meter, cumulative energization time, actual operation time, motor load factor, cumulative energization power, power
saving effect, cumulative saving power, regenerative brake duty
value, inverter I/O terminal monitor, input terminal option monitor
status monitor
*2, terminal assignment status*2
*4, PID set point, PID measured value, PID deviation
Alarm definition is displayed when the protective function is activated, the output voltage/current/frequency/cumulative
energization time right before the protection function was activated and the past 8 alarm definitions are stored
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage
during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal
operation, motor protection thermal operation, heatsink overheat, instantaneous power failure occurrence,
undervoltage, input phase failure, motor overload, output side earth (ground) fault overcurrent, output phase failure,
external thermal relay operation, PTC thermistor operation, option alarm, parameter error, PU disconnection, retry
count excess, CPU alarm, operation panel power supply short circuit, 24VDC power output short circuit, output
current detection value excess, inrush resistance overheat, communication alarm (inverter), analog input alarm,
internal circuit alarm (15V power supply), fan fault, overcurrent stall prevention, overvoltage stall prevention,
electronic thermal relay function prealarm, PU stop, maintenance timer alarm
To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
⋅
⋅ Be sure to use the inverter and motor after grounding (earthing) them.
⋅ This connection diagram assumes that the control circuit is sink logic (initial setting). Refer to the instruction manual for the
connection in the case of source logic.
16
Page 16
Terminal Specification Explanation
Typ eTerminal SymbolTerminal NameDescription
R/L1, S/L2, T/L3AC power inputConnect to the commercial power supply.
Main circuit
Contact input
Control circuit input signal
Frequency setting
U, V, WInverter outputConnect a three-phase squirrel-cage motor.
R1/L11, S1/L21
P/+, N/-Brake unit connection
P/+, P1DC reactor connection
PR, PXPlease do not remove or use terminals PR and PX or the jumper connected.
STFForward rotation start
STRReverse rotation start
STOP
RH, RM, RLMulti-speed selectionMulti-speed can be selected according to the combination of RH, RM and RL signals.
JOGJog mode selection
RT
MRSOutput stop
RESReset
AU
CS
SD
PC
10E
10
2
4
1
5
Power supply for control
circuit
Earth (Ground)For earthing (grounding) the inverter chassis. Must be earthed (grounded).
Start self-holding
selection
Second acceleration/
deceleration time
selection
Terminal 4 input selection
PTC input
Selection of automatic
restart after
instantaneous power
failure
Contact input common
(sink)
External transistor
common,
24VDC power supply,
contact input common
(source)
Frequency setting power
supply
Frequency setting
(voltage)
Frequency setting
(current)
Frequency setting
auxiliary
Frequency setting
common
Connected to the AC power supply terminals R/L1 and S/L2. To retain the alarm display and
alarm output, apply external power to this terminal.
Connect the brake unit (FR-BU, BU, MT-BU5), power regeneration common converter (FRCV), power regeneration converter (MT-RC) or high power factor converter (FR-HC, MT-HC).
For the 55K or less, remove the jumper across terminals P/+ - P1 and connect the DC reactor.
(For the 75K or more, a DC reactor is supplied as standard.)
Turn on the STF signal to start forward rotation and turn it off to
stop.
Turn on the STR signal to start reverse rotation and turn it off to
stop.
Turn on the STOP signal to self-hold the start signal.
Turn on the JOG signal to select Jog operation (initial setting) and turn on the start signal (STF
or STR) to start Jog operation.
Turn on the RT signal to select second acceleration/deceleration time.
When the second function such as "second torque boost" and "second V/F (base frequency)"
are set, turning on the RT signal selects these functions.
Turn on the MRS signal (20ms or more) to stop the inverter output.
Use to shut off the inverter output when stopping the motor by electromagnetic brake.
Used to reset alarm output provided when protective function is activated. Turn on the RES
signal for more than 0.1s, then turn it off.
Recover about 1s after reset is cancelled.
Terminal 4 is made valid only when the AU signal is turned on. (The frequency setting signal
can be set between 4 and 20mADC.)
Turning the AU signal on makes terminal 2 (voltage input) invalid.
AU terminal is used as PTC input terminal (thermal protection of the motor). When using it as
PTC input terminal, set the AU/PTC switch to PTC.
When the CS signal is left on, the inverter restarts automatically at power restoration. Note that
restart setting is necessary for this operation. In the initial setting, a restart is disabled.
Common terminal for contact input terminal (sink logic) and terminal FM. Common output
terminal for 24VDC 0.1A power supply (PC terminal). Isolated from terminals 5 and SE.
When connecting the transistor output (open collector output), such as a programmable
controller (PLC), when sink logic is selected, connect the external power supply common for
transistor output to this terminal to prevent a malfunction caused by undesirable currents. Can
be used as 24VDC 0.1A power supply. When source logic has been selected, this terminal
serves as a contact input common.
When connecting the frequency setting potentiometer at an initial
status, connect it to terminal 10.
Change the input specifications when connecting it to terminal 10E.
Inputting 0 to 5VDC (or 0 to 10V, 4 to 20mA) provides the maximum output frequency at 5V
(10V, 20mA) and makes input and output proportional. Use Pr.73 to switch from among input 0
to 5VDC (initial setting), 0 to 10VDC, and 4 to 20mA.
Voltage input: Input resistance 10kΩ ± 1kΩ Maximum permissible voltage 20VDC
Current input: Input resistance 250Ω ± 2% Maximum permissible current 30mA
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the maximum output frequency at 20mA
(5V, 10V) makes input and output proportional. This input signal is valid only when the AU
signal is on (terminal 2 input is invalid). Use Pr.267 to switch between the input 4 to 20mA and 0
to 5VDC, 0 to 10VDC (initial setting).
Voltage input: Input resistance 10kΩ ± 1kΩ Maximum permissible voltage 20VDC
Current input: Input resistance 250Ω ± 2% Maximum permissible current 30mA
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal 2 or 4 frequency setting
signal. Use Pr.73 to switch between the input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Input resistance 10kΩ ± 1kΩ, Maximum permissible voltage ± 20VDC
Common terminal for frequency setting signal (terminal 2, 1 or 4) and analog output terminal
AM. Do not earth (ground).
When the STF and STR
signals are turned on
simultaneously, the stop
command is given.
10VDC, permissible load
current 10mA.
5VDC, Permissible load
current 10mA.
17
Page 17
Typ eTerminal SymbolTerminal NameDescription
Changeover contact output indicates that the inverter protective function has activated and the
Relay
A1, B1, C1
Relay output 1 (alarm
output)
output stopped. Abnormal: No conduction across B-C (Across A-C Continuity), Normal: Across
B-C Continuity (No conduction across A-C) Contact capacity: 230VAC 0.3A (Power factor=0.4)
30VDC 0.3A
Switched low when the inverter output frequency is equal to or
RUNInverter running
SUUp to frequency
OLOverload alarm
Open collector
IPF
Instantaneous power
failure
higher than the starting frequency (initial value 0.5Hz). Switched
high during stop or DC injection brake operation.
*1
Switched low when the output frequency reaches within the range
of ±10% (initial value) of the set frequency. Switched high during
acceleration/deceleration and at a stop.
*1
Switched low when stall prevention is activated by the stall
prevention function. Switched high when stall prevention is
cancelled.
*1
Switched low when an instantaneous power failure and under
voltage protections are activated.
*1
Permissible load 24VDC
0.1A
(a voltage drop is 3.4V
maximum when the signal
is on)
Alarm code (4bit) output
(Refer to page 36)
Switched low when the inverter output frequency is equal to or
FUFrequency detection
SE
Open collector output
common
Control circuitoutput signal
Pulse
FMFor meter
AMAnalog signal output
Analog
higher than the preset detected frequency and high when less than
the preset detected frequency.
*1
Common terminal for terminals RUN, SU, OL, IPF, FU
Select one e.g. output frequency from monitor items. *2
The output signal is proportional to the magnitude of the
corresponding monitoring item.
Output item:
Output frequency (initial
setting)
Permissible load current
2mA
1440 pulses/s at 60Hz
Output item:
Output frequency (initial
setting)
Output signal 0 to 10VDC
Permissible load current
1mA (load impedance
10kΩ or more) Resolution
8 bit
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
PU connector PU connector
. Conforming standard: EIA-485(RS-485)
. Transmission format: Multidrop
. Communication speed : 4800 to 38400bps
. Overall length: 500m
With the RS-485 terminal, communication can be made through RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed : 300 to 38400bps
Overall length: 500m
CAUTION
⋅
The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.
⋅ indicates that terminal functions can be selected fromPr. 178 to Pr. 196 (I/O terminal function selection)
*1. Low indicates that the open collector output transistor is on (conducts). High indicates that the transistor is off (does not conduct).
*2. Not output during inverter reset.
PU: Lit to indicate PU operation mode.
EXT: Lit to indicate external operation mode.
NET: Lit to indicate network operation mode.
Rotation direction indication
FWD: Lit during forward rotation
REV: Lit during reverse rotation
On: Forward/reverse operation
Unit indication
· Hz: Lit to indicate frequency.
· A: Lit to indicate current.
· V: Lit to indicate voltage.
(Flicker when the set frequency monitor is
displayed.)
Flickering: When the frequency command is
not given even if the
forward/reverse command is given.
Monitor indication
Lit to indicate monitoring mode.
Monitor(4-digit LED)
Shows the frequency, parameter
number, etc.
Setting dial
(Setting dial: Mitsubishi inverter
dial)
Used to change the
frequency setting and
parameter values.
Mode
switchover
Used to change
each setting mode.
No function
Operation command
forward rotation
Operation command
reverse rotation
Stop operation
Alarms can be reset
Used to set each setting.
If pressed during operation, monitor
changes as below;
Running
frequency
* Energy saving monitor is displayed when the
energy saving monitor of Pr. 52 is set.
Output
current
Output
voltage
*
19
Operation mode switchover
Used to switch between the PU and external operation mode.
When using the external operation mode (operation using a separately
connected frequency setting potentiometer and start signal), press this key to
light up the EXT indication. (Change the Pr.79 value to use the combined mode.)
PU: PU operation mode
EXT: External operation mode
Page 19
Basic operation
Operation mode switchover
At powering on (external operation mode)
PU operation mode
(output frequency monitor)
Monitor/frequency setting
PU Jog operation mode
Value change
Output current monitor
(Example)
and frequency flicker.
Frequency setting has been
written and completed!!
Output voltage monitor
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Diagram
Explanation
Terminal Connection
Terminal Specification
Panel
Operation
List
Parameter
Parameter setting mode
Parameter settingAlarm history
Value change
Parameter clearAll parameter
clear
[Operation for displaying alarm history]
Past eight alarms can be displayed.
(The latest alarm is ended by ".".)
When no alarm history exists, is displayed.
Display the current
setting
(Example)
Parameter and a setting value
flicker alternately.
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel (FR-DU07). For details of parameters, refer to the instruction manual.
POINT
Only simple mode parameters are displayed by the initial setting of Pr.160 User group read selection. Set Pr.160
User group read selection as required.
Simple mode parameter
Parameter
Number
0Torque boost0 to 30%0.1%6/4/3/2/1.5/1%*228
1Maximum frequency0 to 120Hz0.01Hz120/60Hz*128
2Minimum frequency0 to 120Hz0.01Hz0Hz28
3Base frequency0 to 400Hz0.01Hz60Hz28
4Multi-speed setting (high speed)0 to 400Hz0.01Hz60Hz28
5Multi-speed setting (middle speed)0 to 400Hz0.01Hz30Hz28
6Multi-speed setting (low speed)0 to 400Hz0.01Hz10Hz28
7Acceleration time0 to 3600/ 360s0.1/0.01s5s/15s*328
8Deceleration time0 to 3600/ 360s0.1/0.01s10s/30s*328
9Electronic thermal O/L relay 0 to 500/ 0 to 3600A*10.01/0.1A*1
60Energy saving control selection0, 4, 91034
79Operation mode selection0, 1, 2, 3, 4, 6, 71037
125Terminal 2 frequency setting gain frequency 0 to 400Hz0.01Hz60Hz39
126Terminal 4 frequency setting gain frequency 0 to 400Hz0.01Hz60Hz39
160User group read selection0, 1, 99991999940
NameRangeIncrementsInitial Value
Rated inverter
output current
Extended mode parameter
Remarks
⋅ The parameters marked with indicate simple mode parameters.
⋅ The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in
Parameter write selection.
Refer to
page
29
Pr. 77
Function
Basic functions
Brake
Parameters
0
1
2
3
4
5
6
7
8
9
10
11
12
NameSetting RangeIncrementsInitial Value
Torque boost0 to 30%0.1%6/4/3/2/1.5/1%*228
Maximum frequency0 to 120Hz0.01Hz120/60Hz*128
Minimum frequency0 to 120Hz0.01Hz0Hz28
Base frequency0 to 400Hz0.01Hz60Hz28
Multi-speed setting (high speed)0 to 400Hz0.01Hz60Hz28
Multi-speed setting (middle speed)0 to 400Hz0.01Hz30Hz28
Multi-speed setting (low speed)0 to 400Hz0.01Hz10Hz28
Acceleration time0 to 3600/ 360s0.1/0.01s5s/15s*328
Deceleration time0 to 3600/ 360s0.1/0.01s10s/30s*328
Electronic thermal O/L relay 0 to 500/ 0 to 3600A*10.01/0.1A*1
DC injection brake operation frequency0 to 120Hz, 99990.01Hz3Hz29
DC injection brake operation time0 to 10s0.1s0.5s29
DC injection brake operation voltage0 to 30%0.1%4/2/1%*429
DC Injection
13
14
15
Jog
16
Starting frequency0 to 60Hz0.01Hz0.5Hz29
Load pattern selection0, 11129
Jog frequency0 to 400Hz0.01Hz5Hz29
Jog acceleration/deceleration time0 to 3600/360s0.1/0.01s0.5s29
operation
*1 Differ according to capacities. (55K or less/75K or more)
*2 Differ according to capacities. (0.75K/1.5K to 3.7K/5.5K, 7.5K/11K to 37K/45K, 55K/75K or more)
*3 Differ according to capacities. (7.5K or less/11K or more)
*4 Differ according to capacities. (7.5K or less/11K to 55K/75K or more)
Rated inverter
output current
Refer to
page
29
21
Page 21
Function
17
18
19
Parameters
20
NameSetting RangeIncrementsInitial Value
MRS input selection0, 21029
High speed maximum frequency120 to 400Hz0.01Hz120/60Hz*128
Base frequency voltage0 to 1000V, 8888, 99990.1V999928
Acceleration/deceleration reference
frequency
1 to 400Hz0.01Hz60Hz28
Refer to
page
Features
and
times
deceleration
Acceleration
Stall
prevention
setting
Multi-speed
28
29
30
Frequency jump
37
detection
Frequency
Second functions
Monitor functions
21
22
23
24 to 27
31
32
33
34
35
36
41
42
43
44
45
46
47
48
49
50
51
52
54
55
56
57
Acceleration/deceleration time
increments
Stall prevention operation level0 to 150%, 99990.1%120%30
Stall prevention operation level
compensation factor at double speed
Multi-speed setting 4 speed to 7 speed0 to 400Hz, 99990.01Hz999928
Multi-speed input compensation
selection
Acceleration/deceleration pattern
selection
Regenerative function selection0, 2/0, 1, 2*11031
Frequency jump 1A0 to 400Hz, 99990.01Hz999931
Frequency jump 1B0 to 400Hz, 99990.01Hz999931
Frequency jump 2A0 to 400Hz, 99990.01Hz999931
Frequency jump 2B0 to 400Hz, 99990.01Hz999931
Frequency jump 3A0 to 400Hz, 99990.01Hz999931
Frequency jump 3B0 to 400Hz, 99990.01Hz999931
Speed display0, 1 to 99981031
Up-to-frequency sensitivity 0 to 100%0.1%10%31
Output frequency detection 0 to 400Hz0.01Hz6Hz31
Output frequency detection for reverse
rotation
Second acceleration/deceleration time0 to 3600/360s0.1/0.01s5s28
Second deceleration time0 to 3600/360s, 99990.1/0.01s999928
Second torque boost0 to 30%, 99990.1%999928
Second V/F (base frequency)0 to 400Hz, 99990.01Hz999928
Second stall prevention operation
current
Second stall prevention operation
frequency
Second output frequency detection 0 to 400Hz0.01Hz30Hz31
Second electronic thermal O/L relay
DU/PU main display data selection
FM terminal function selection
Frequency monitoring reference0 to 400Hz0.01Hz60Hz32
Current monitoring reference0 to 500/0 to 3600A*10.01/0.1A*1
Regeneration avoidance operation level300 to 800V0.1V380V/760V*145
Regeneration avoidance at deceleration
detection sensitivity
Regeneration avoidance compensation
frequency limit value
Regeneration avoidance voltage gain 0 to 200%0.1%100%45
Free parameter 1 0 to 99991999945
0, 11045
0 to 51045
0 to 10Hz, 99990.01Hz6Hz45
Refer to
page
Free
889
Free parameter 2 0 to 99991999945
parameter
891
892
893
894
895
896
Energy saving monitor
897
898
899
C0
(900)
C1
(901)
C2
(902)
C3
(902)
125
(903)
C4
(903)
C5
Calibration parameters
(904)
C6
(904)
126
(905)
C7
(905)
989
990
PU
991
Pr.CL
ALLC
Clear
*1 The initial value differs according to the voltage class. (200V class / 400V class)
*2 Differ according to capacities. (55K or less/75K or more)
Er.CL
PCPY
parameters
Cumulative power monitor digit shifted
times
Load factor30 to 150%0.1%100%45
Energy saving monitor reference (motor
capacity)
Control selection during commercial
power-supply operation
Power saving rate reference value0, 1, 99991999945
Power unit cost 0 to 500, 99990.01999945
Power saving monitor average time0, 1 to 1000h, 99991999945
Power saving cumulative monitor clear0, 1, 10, 99991999945
Operation time rate (estimated value) 0 to 100%, 99990.1%999945
FM terminal calibration
AM terminal calibration
Terminal 2 frequency setting bias
frequency
Terminal 2 frequency setting bias 0 to 300%0.1%0%39
Terminal 2 frequency setting gain
frequency
Terminal 2 frequency setting gain 0 to 300%0.1%100%39
Terminal 4 frequency setting bias
frequency
Terminal 4 frequency setting bias 0 to 300%0.1%20%39
Terminal 4 frequency setting gain
frequency
Terminal 4 frequency setting gain 0 to 300%0.1%100%39
Parameter copy alarm release10/100110/100*2-
PU buzzer control0, 11146
PU contrast adjustment0 to 6315846
Parameter clear0, 11046
All parameter clear0, 11046
Alarm history clear0, 11046
Parameter copy0, 1, 2, 31046
0 to 4, 99991999932
0.1 to 55/0 to 3600kW*20.01/0.1kW*2
0, 1, 2, 31045
0 to 400Hz0.01Hz0Hz39
0 to 400Hz0.01Hz60Hz39
0 to 400Hz0.01Hz0Hz39
0 to 400Hz0.01Hz60Hz39
Inverter rated
capacity
45
46
46
27
Page 27
P
P
y
Explanations of Parameters
Pr.0Pr.
Pr.0 Torque boost
Manual torque boost
46
Pr.46 Second torque boost
You can compensate for a voltage drop in the low-frequency region
to improve motor torque reduction in the low-speed region.
Motor torque in the low-frequency range can be adjusted to the
load to increase the starting motor torque.
The starting torque boost can be changed by switching terminal RT.
When simple magnetic flux vector control is selected in Pr. 80, the
settings of Pr. 0 and Pr. 46 are invalid.
When using
the constant
torque motor
r.0
r.46
Pr.
Output
voltage
Setting
range
1, 2
100%
0
Pr.
Output frequency(Hz)
Maximum/minimum
18
frequency
Pr.0 Initial
Valu e
0.75K6%←
1.5K to 3.7K 4%←
5.5K, 7.5K 3%2%*
11K to 3 7K 2%←
45K, 55K 1.5%←
75K or more 1%←
Base
* If the initial set Pr. 71 value
frequenc
is changed to the setting
for use with a constanttorque motor, the Pr. 0
setting changes to the
corresponding value in
above.
Pr.1 Maximum frequencyPr.2 Minimum frequency
Pr.18 High speed maximum frequency
You can limit the motor speed.
Clamp the upper and lower limits of the output frequency.
When you want to perform operation above 120Hz, set the upper
limit of the output frequency to Pr. 18 .
(When Pr. 18 is set, Pr. 1 automatically switches to the frequency
of Pr. 18. When Pr. 1 is set, Pr. 18 is automatically changed to the
frequency set in Pr. 1.)
Clamped at the
Output frequency
(Hz)
Pr.1
Pr.18
Clamped at the
minimum frequency
Pr.3Pr.
Pr.2
19, 47
0
(4mA)
Base frequency, voltage
maximum frequency
Frequency setting
5, 10V
(20mA)
Pr.3 Base frequency
Pr.19 Base frequency voltagePr.47 Second V/F (base frequency)
Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
When operating a standard motor, generally set the rated frequency of
the motor to Pr. 3 Base frequency. When running the motor using
commercial power supply-inverter switch-over operation, set Pr. 3 to
the same value as the power supply frequency.
When you want to change the base frequency when switching multiple
motors with one inverter, use the Pr. 47 Second base frequency.
Use Pr. 19 Base frequency voltage to set the base voltage (e.g. rated
Can be used to change the preset speed in the parameter with
the contact signals.
Any speed can be selected by merely turning on-off the contact
signals (RH, RM, RL, REX signals).
The inverter operates at frequencies set in Pr. 4 when RH signal is
on, Pr. 5 when RM signal is on and Pr. 6 when RL signal is on.
Frequency from speed 4 to speed 15 can be set according to the
combination of the RH, RM, RL and REX signals. Set the running
frequencies to Pr. 24 to Pr. 27, Pr. 232 to Pr. 239. (In the initial value
setting, speed 4 to 15 are unavailable.)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Output frequency (Hz)
ONON ON ON
RH
RM
RL
ON
Speed 5
Speed 4
ONON
Speed 6
Speed 7
ON
ONONON
Time
Output frequency
RH
RM
RL
REX
*1 When turning RH, RM and RL off and REX on with "9999" set in Pr. 232
"multi speed setting (8 speed), the inverter operates at frequency set in
Pr. 6.
Pr.
7, 8
Pr.
20, 21, 44, 45
Speed 10
Speed 11
Speed 9
Speed 8
(Hz)
ON ONON ON
ON ON ON ON
ONON ON ON ON ON ON ON
*1
Speed 12
Speed 13
Speed 14
ON ON ON ON
Speed 15
Time
Acceleration/deceleration time setting
Pr.7 Acceleration timePr.8 Deceleration time
Pr.20 Acceleration/deceleration reference frequency
Pr.21 Acceleration/deceleration time incrementsPr.44 Second acceleration/deceleration time
Pr.45 Second deceleration time
Used to set motor acceleration/deceleration time.
Set a larger value for a slower speed increase/decrease or a
smaller value for a faster speed increase/decrease.
Use Pr. 7 Acceleration time to set the acceleration time required to
reach Pr. 20 Acceleration/deceleration reference frequency from 0Hz.
Use Pr. 8 Deceleration time to set the deceleration time required to
stop from the Pr. 20 Acceleration/deceleration reference frequency.
Pr.20
(60Hz)
(Hz)
Output
frequency
Acceleration
time
Pr.7
Deceleration
time
Running
frequency
Time
Pr.8
Pr.21
Setting
0
(initial value)
1
Description
Increments:
0.1s
Range:
0 to 3600s
Increments:
0.01s
Range:
0 to 360s
Increments and
setting range of
acceleration/
deceleration
time setting can
be changed.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Output frequency
(Hz)
Pr.3
Pr.47
28
Page 28
Pr.9Pr.
y
Pr.9 Electronic thermal O/L relay
Motor protection from overheat
51
(electronic thermal relay function)
Pr.51 Second electronic thermal O/L relay
Set the current of the electronic overcurrent protection to protect
the motor from overheat.This feature provides the optimum
protective characteristics, including reduced motor cooling
capability, at low speed.
This function detects the overload (overheat) of the motor, stops
the operation of the inverter's output transistor, and stops the
output.
Set the rated current [A] of the motor in Pr.9.
When using a motor with an external thermal relay, etc., set “0” in
Pr. 9 to make the electronic thermal relay function invalid. (Note
that the output transistor protection of the inverter (E.THT)
functions.)
When using the Mitsubishi constant-torque motor
1) Set “1” in Pr.71 .
(This provides a 100% continuous torque characteristic in the
low-speed range.)
2) Set the rated motor current in Pr. 9.
When the RT signal is on, thermal protection is provided based on
the Pr. 51 setting.
Use this function when rotating two motors of different rated
currents individually by a single inverter.
together, use external thermal relays.)
Pr.
10 to 12
Pr.10 DC injection brake operation frequency
Pr.12 DC injection brake operation voltage
DC injection brake
Pr.11 DC injection brake operation time
(When rotating two motors
The DC injection brake can be operated at a motor stop to adjust
the stop timing and braking torque.
DC injection
brake
voltage
Output frequency (Hz)
Pr.12
Operation
voltage
Pr.11 Operation time
When
4%
2%
1%
Using the
Mitsubish
Constant
Torque
Motor
Pr.12 Initial
Val ue
Pr.10 Operation
frequency
Time
3.7K or less
5.5K to 7.5K 4%2% *3%
Time
11K or mor e
75K or more
* If the Pr. 71 initial value is changed
to the setting for use with a
constant-torque motor, the Pr. 12
setting changes to the
corresponding value in the above
table.
When
Using
the
Energy
Saving
Motor
←←
←←
←←
Pr.
Pr. 14 Load pattern selection
V/F pattern matching applications
14
You can select the optimum output characteristic (V/F
characteristic) for the application and load characteristics.
Setting “0”
For constant-torque load
100%
Output voltage
Pr.3Base frequency
Output frequency (Hz)
Pr.
15, 16
Pr.15 Jog frequencyPr.16 Jog acceleration/deceleration time
Jog operation
Setting “1” (initial value)
For variable-torque load
100%
Output voltage
Pr.3 Base frequenc
Output frequency (Hz)
You can set the frequency and acceleration/decelertion time for
jog operation. Jog operation can be performed from either the
outside or PU.
Can be used for conveyor positioning, test operation, etc.
Output
frequency
(Hz)
Pr.20
Jog frequency
setting range
Pr.
Pr.17 MRS input selection
Logic selection of output stop
17
signal (MRS)
Pr.15
JOG signal
Forward
rotation STF
Reverse
rotation STR
Forward
rotation
Pr.16
ON
ON
Reverse
rotation
ON
Time
The inverter output can be shut off by the MRS signal. The logic
of the MRS signal can also be selected.
Inverter
MRS
SD (PC)
(Initial
value)
Setting value "2"
Output
stop
Inverter
MRS
SD (PC)
Motor coasts
to stop
Time
Setting value "0"
Output
stop
Pr.
13, 571
Pr.13 Starting frequencyPr.571 Holding time at a start
Starting frequency
You can set the starting frequency and hold the set starting
frequency for a certain period of time.
Set these functions when you need the starting torque or want
smooth motor drive at a start.
Output
frequency
(Hz)
60
Pr.13
Setting range
29
0
Forward
rotationON
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.571 setting time
Pr.
Time
MRS signal
STF (STR)
signal
Pr.
18
Pr.
19
Pr.
20, 21
ON
ON
Refer to the section about Pr.1, Pr.2
Refer to the section about Pr. 3.
Refer to the section about Pr.7, Pr.8
Page 29
)
P
e
Pr. 49 SettingOperation
Pr.
22, 23, 48, 49, 66, 148, 149, 154, 156, 157
Stall prevention operation
Pr.22 Stall prevention operation level
Pr.23 Stall prevention operation level compensation factor at double speed
Pr.48 Second stall prevention operation currentPr.49 Second stall prevention operation frequency
Pr.66 Stall prevention operation reduction starting frequency
Pr.148 Stall prevention level at 0V input.
Pr.154 Voltage reduction selection during stall prevention operation
Pr.156 Stall prevention operation selection
This function monitors the output current and automatically changes
the output frequency to prevent the inverter from coming to an alarm
stop due to overcurrent, overvoltage, etc. It can also limit stall
prevention and fast-response current limit operation during
acceleration/deceleration, driving or regeneration.
Stall prevention
If the output current exceeds the limit value, the output frequency
of the inverter is automatically varied to reduce the output current.
Also the second stall prevention function can restrict the output
frequency range in which the stall prevention function is valid.
(Pr.49)
Fast-response current limit
If the current exceeds the limit value, the output of the inverter is
Pr.149 Stall prevention level at 10V input.
Pr.157 OL signal output timer
0 (initial value) Second stall prevention function is not activated
If the output frequency is less than the frequency set in
0.01Hz to 400Hz
Pr. 49, the second stall prevention operation function is
activated. (during constant speed or deceleration)
The second stall prevention function is performed according to
9999
the RT signal.
RT signal on ....... Stall level Pr. 48
RT signal off ....... Stall level Pr. 22
Stall prevention operation and fast response current restriction function
can be restricted according to the operation condition using Pr. 156.
Pr.
24 to 27
Pr.
28
Pr.28 Multi-speed input compensation selection
Refer to the section about Pr.4 to Pr.6
Input compensation of multispeed and remote setting
By inputting the frequency setting compensation signal (terminal 1,
2), the speed (frequency) can be compensated for relative to the
multi-speed setting or the speed setting by remote setting function.
Pr. 28 SettingDefinition
0 (initial value)Without compensation
1With compensation
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Diagram
Explanation
Terminal Connection
Terminal Specification
shut off to prevent an overcurrent.
Set in Pr. 22 the ratio of the output current to the rated inverter
current at which stall prevention operation will be performed.
Normally set this parameter to120% (initial value).
When “9999” is set in Pr. 22, stall prevention operation level can be
changed by the signal to the auxiliary input terminal (terminal 1). For
the adjustment of bias/gain of analog signal, use Pr. 148 and Pr. 149.
During high-speed operation above the rated motor frequency,
acceleration may not be made because the motor current does
not increase. If operation is performed in a high frequency range,
the current at motor lockup becomes smaller than the rated output
current of the inverter, and the protective function (OL) is not
executed if the motor is at a stop.
To improve the operating characteristics of the motor in this case,
the stall prevention level can be reduced in the high frequency
region. This function is effective for performing operation up to the
high speed region on a centrifugal separator etc. Normally, set
60Hz in Pr. 66 and 100% in Pr. 23.
By setting "9999" (initial value) in Pr. 23 Stall prevention operation
level compensation factor at double speed, the stall preventionoperation level is constant at the Pr. 22 setting up to 400Hz.
r.2 2
When Pr.23=9999
Pr.
29, 140 to 143
Pr.29 Acceleration/deceleration pattern selection Pr.140 Backlash acceleration stopping frequency
Pr.141 Backlash acceleration stopping timePr.142 Backlash deceleration stopping frequency
Pr.143 Backlash deceleration stopping time
You can set the acceleration/deceleration pattern suitable for
application.
You can also set the backlash measures that stop acceleration/
deceleration once at the parameter-set frequency and time
during acceleration/deceleration.
Setting value "0"
[Linear acceleration
/ deceleration]
Output frequency
(Hz)
Setting value "1"
Time
[S-pattern acceleration
/deceleration A]
Acceleration/ deceleration pattern
and back lash measures
Linear acceleration/deceleration
(setting "0", initial value)
⋅ When the frequency is changed for
acceleration, deceleration, etc. in
inverter operation, the output
frequency is changed linearly (linear
acceleration/deceleration) to reach
the set frequency without straining
the motor and inverter.
Setting "9999" in Pr. 49 Second stall prevention operation frequency
and turning the RT signal on make Pr. 48 Second stall preventionoperation current valid.
The stall prevention operation level from 0Hz to the output
frequency set in Pr. 49 can be set in Pr. 48.
Set frequency exceeds Pr. 49
Output
frequency (Hz)
Set
frequency
Pr.49
Stall
prevention
level
Pr. 22
used
Output
frequency
Time
Pr. 48
used
Set frequency is Pr. 49 or less
Output
frequency (Hz)
Pr.49
Set
frequency
Pr. 22
used
Output
frequency
Pr. 48
used
Tim
Set frequency
(Hz)
f1
f2
Output frequency
(Hz)
Setting value "3"
[Anti-backlash measure
function]
f1
Pr.140
Output frequency (Hz)
t1
Pr.141
Pr.143
Time
t2
f2
Pr.142
Time
Use when acceleration/deceleration
must be made in a short time to a
high-speed region of not lower than
base frequency.
S-pattern acceleration/deceleration B
(setting "2")
⋅ For prevention of load shifting in
conveyor and other applications
Since acceleration/deceleration is
always made in an S shape from
current frequency (f2) to target
frequency (f1), this function eases
shock produced at acceleration/
deceleration and is effective for load
collapse prevention, etc.
Backlash measures (setting "3", Pr.140
to Pr.143 )
⋅ To avoid backlash, acceleration/
deceleration is temporarily stopped.
Set the acceleration/deceleration
stopping frequency and time in Pr. 140 to Pr. 143.
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
30
Page 30
Pr.
0
30, 70
Pr.30 Regenerative function selectionPr.70 Special regenerative brake duty *
Selection of
regeneration unit
Use the high power factor converter (FR-HC) to reduce
harmonics, improve the power factor, or continuously use the
regenerative mode.
For the 75K or more, use the brake unit MT-BU5 or BR5 when the
regenerative brake duty is need to be increased due to frequent
starts and stops. Use the high power factor converter MT-HC to
reduce harmonics, improve the power factor, or continuously use
the regenerative mode.
<55K or less>
Pr.30 SettingRegeneration Unit
0 (initial value)Brake unit (FR-BU, BU)
2
High power factor converter (FR-HC),
power regeneration common converter (FR-CV)
<75K or more>
Pr.30 Setting Pr.70 Setting *Regeneration Unit
0 (initial value)Not used
1
2High power factor converter (MT-HC)
* Pr.70Special regenerative brake dutycan be set for the 75K or more inverter.
Pr.
31 to 36
Pr.31 Frequency jump 1APr.32 Frequency jump 1B
Pr.33 Frequency jump 2APr.34 Frequency jump 2B
Pr.35 Frequency jump 3APr.36 Frequency jump 3B
When it is desired to
avoid resonance
attributable to the
natural frequency of a
mechanical system,
these parameters allow
You can change the PU (FR-DU07) monitor display or frequency
setting to motor speed or machine speed.
When the running speed monitor is selected, each monitor and
setting are determined according to the combination of Pr. 37 andPr. 144. (The units within the thick frame are the initial values.)
31
Pr. 37
Setting
Pr. 144
Setting
2 to 10HzHzr/min *1Hz
0
102 to
110
1 to
2 to 10
9998
102 to
110
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Output
Frequency
Monitor
0HzHzr/min *1Hz
r/min *1r/min *1r/min *1r/min *1
0HzHz
Machine
speed
*1
HzHzr/min *1Hz
Set
Frequency
Monitor
Machine
speed
*1
Pr.
Running
Speed
Monitor
Machine
speed
Machine
speed
*1
*1
Frequency
Setting
Parameter
Setting
Hz
Machine
speed
*1
*1 Motor speed r/min conversion formula
....... Frequency × 120/number of motor poles (Pr. 144)
Machine speed conversion formula
...... Pr. 37 × frequency/60Hz
For Pr. 144 in the above formula, the value is “Pr. 144-100” when “102 to
110” is set in Pr. 144 and the value is “4” when Pr. 37=0 and Pr.144=0.
*2 The increments for Hz are 0.01Hz, machine speed are 1m/min and r/min
are 1r/min
.
Pr.
41 to 43, 50
Pr.41 Up-to-frequency sensitivityPr.42 Output frequency detection
Pr.43 Output frequency detection for reverse rotation
Pr.50 Second output frequency detection
Detection of output frequency (SU,
FU, FU2 signal)
The inverter output frequency is detected and output at the
output signals.
If the set frequency is considered as 100%, output frequency can
be adjusted between ±1% and ±100% with Pr. 41.
This parameter can be used to ensure that the running frequency
has been reached to provide the operation start signal etc. for
related equipment.
Running frequencyAdjustment
Output frequency
(Hz)
SU
ON
range
OFFOFF
Pr.41
Time
When the output frequency reaches or exceeds the setting of Pr.
42, the output frequency detection signal (FU) is output.
This function can be used for electromagnetic brake operation,
open signal, etc.
When the detection frequency is set in Pr. 43, frequency detection
for reverse rotation use only can also be set. This function is
effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation
(fall) during vertical lift operation, etc.
When outputting a frequency detection signal besides the FU
signal, set the detection frequency to Pr. 50 . The FU2 signal is
output when the output frequency reaches or exceeds the Pr. 50
setting.
OFF
Pr.42
Pr.50
Reverse
rotation
Time
Pr.43
Pr.5
OFFOFF
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
Forward
rotation
(Hz)
Output frequency
Output
frequency
FU
FU2
44, 45
46
47
48, 49
50
51
Refer to the section about Pr.7, Pr.8
Refer to the section about Pr. 0.
Refer to the section about Pr. 3.
Refer to the section about Pr. 22 and other
relevant parameters.
Refer to the section about Pr. 41 and other
relevant parameters.
Refer to the section about Pr. 9.
ONON
OFFOFFOFF
ONON
Page 31
Pr.
52, 54, 158, 170, 171, 268, 563, 564, 867, 891
Change of DU/PU monitor descriptions Cumulative monitor clear
Pr.52
DU/PU main display data selection
Pr.158 AM terminal function selection Pr.170 Cumulative power meter clear
Pr.171 Operation hour meter clearPr.268 Monitor decimal digits selection
Pr.563 Energization time carrying-over timesPr.564 Operating time carrying-over times
Pr.867 AM output filter
Pr.891 Cumulative power monitor digit shifted times
The monitor to be displayed on the main screen of the operation
panel (FR-DU07) / parameter unit (FR-PU04) can be selected.
Types of Monitor
Output frequency
Output current
Output voltage
Alarm display
Frequency setting
Running speed
Converter output
voltage
Regenerative brake
*5
duty
Electronic thermal
relay function load
factor
Output current peak
value
Converter output
voltage peak value
Input power
Output power
Input terminal status
Output terminal
status
Option input
terminal status
Option output
terminal status
Load meter
Reference voltage
output
Cumulative
energization time
Actual operation
time
*2, 3
Motor load factor
Cumulative power
Power saving effect
Cumulative saving
power
PID set point
PID measured value
PID deviation value
Increments
0.01Hz0/1001Pr.55
0.01A/
0.1A
0.1V0/1003
0/100
0.01Hz5
1(r/min)6
0.1V8
0.1%9
0.1%10
0.01A/
0.1A
0.1V12
0.01kW/
0.1kW
0.01kW/
0.1kW
56×
57×
0.1%1717Pr.56
21
1h20
*2
1h23
0.1%2424200%
0.01kWh/
0.1kWh
Variable
according
to
parameters
0.1%5252100%
0.1%5353100%
0.1%54
Pr.54 FM terminal function selection
Pr.52 Parameter
Setting Value
DU
PU main
LED
monitor
*6
*6
*6
*6
*4, *6
0/1002Pr.56
*1
*1
*1
*1
*1
11
13
14
55
*1
*1
*1
*1
*1
*1
25
5050
51
Pr.54
(FM)
Pr.158
(AM)
Setting
200V
class : 400V
400V
class : 800V
5Pr.55
Val ue of Pr. 55
represented in
6
terms of Pr. 37
value
200V
class : 400V
8
400V
class : 800V
Brake duty set
in Pr. 30 and
9
Pr. 70
Electronic
thermal relay
10
function
operation level
11Pr.56
200V
class : 400V
12
400V
class : 800V
Rated inverter
13
power × 2
Rated inverter
14
power × 2
Inverter
capacity
Full Scale
Val ue
*1 Selected by the parameter unit(FR-PU04)
*2 The cumulative energization time and actual operation time are
accumulated from 0 to 65535 hours, then cleared, and accumulated again
from 0.
When the operation panel (FR-DU07) is used, up to 65.53 (65530h) is
displayed as 1h=0.001 and then accumulated from 0.
*3 The actual operation time is not added up if the cumulative operation time
before power supply-off is less than 1h.
*4 When using the parameter unit (FR-PU04), “kW” is displayed.
*5 Setting can be made for the 75K or more.
*6 The setting depends on the inverter capacity.(55K or less/75K or more)⋅
⋅ The cumulative power monitor value digit can be shifted to the
right by the number set in Pr. 891.
⋅ By setting “0” in Pr. 170, the cumulative power monitor can be
cleared.
⋅ You can check the numbers of cumulative energization time
monitor exceeded 65535h with Pr. 563 and the numbers of actual
operation time monitor exceeded 65535h with Pr. 564.
⋅ Writing "0" in Pr. 171 clears the actual operation time monitor.
Pr. 268 SettingDescription
9999 (initial value) No function
When 1 or 2 decimal places (0.1 increments or 0.01
increments) are monitored, the decimal places are
0
1
dropped and the monitor displays an integer value (1
increments).
The monitor value of 0.99 or less is displayed as 0.
When 2 decimal places (0.01 increments) are
monitored, the 0.01 decimal place is dropped and the
monitor displays the first decimal place (0.1
increments).
When the monitor display digit is originally in 1
increments, it is displayed unchanged in 1
increments.
⋅ When Pr. 52 is set to "100", the set frequency monitor is displayed
during a stop and the output frequency monitor is displayed during
operation. (LED of Hz flickers during stop and is lit during
operation.)
Pr.52
0100
Output
frequency
Output
current
Output
voltage
Alarm
display
During
operation/stop
Output frequencySet frequencyOutput frequency
During stop
Output current
Output voltage
Alarm display
During
running
⋅ Using Pr. 867 , the output voltage response of the terminal AM can
be adjusted within the range 0 to 5s.
Pr.
55, 56
Pr.55 Frequency monitoring reference Pr.56 Current monitoring reference
Change of the monitor output
from terminal FM and AM
Set the full-scale value to output the output frequency monitor
value to terminal FM and AM.
Set the full-scale value to output the output current monitor value
to terminal FM and AM in Pr. 56.
Pulse speed(terminal FM)
2400
pulse/s
1440
pulse/s
Output frequency
reference
Output current
reference
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
32
Page 32
Pr.
57, 58, 162 to 165, 299, 611
Restart operation after instantaneous power failure / Flying start
Pr.57 Restart coasting timePr.58 Restart cushion time
Pr.162 Automatic restart after instantaneous power failure selection
Pr.163 First cushion time for restart
Pr.164 First cushion voltage for restart
Pr.299 Rotation direction detection selection at restarting
Pr.611 Acceleration time at a restart
You can restart the inverter without stopping the motor in the
following cases.
⋅ when commercial power supply operation is switched to inverter
operation
⋅ when power comes back on after an instantaneous power failure
⋅ when motor is coasting at start
Pr.
Number
57
580 to 60sSet a voltage starting time at restart.
162
1630 to 20sSet a voltage starting time at restart.
1640 to 100%
1650 to 150%
299
611
*The setting range varies according to the inverter capacity. (55K or less/
75K or more)
Setting RangeDescription
0
0.1 to 5s/
0.1 to 30s
*
9999 (initial value) No restart
0 (initial value)With frequency search
1
10Frequency search at every start
11Reduced voltage system at every start
0Without rotation direction detection
1With rotation direction detection
9999
0 to 3600s
9999
<Connection diagram>
MCCB
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
When “0 (initial value) or 10” is set in Pr. 162, the inverter smoothly
starts after detecting the motor speed upon power restoration.
Even when the motor is rotating in the opposite direction, the
inverter can be restarted smoothly as the direction of rotation is
detected. (You can select whether to make rotation direction
detection or not with Pr. 299 Rotation direction detection selection atrestar ting. )
Pr.165 Stall prevention operation level for restart
1.5K or less..........0.5s,
2.2K to 7.5K .........1s,
11K or more ........3.0s
75K or more ........5.0s
The above times are coasting time.
Set the waiting time for inverter-triggered
restart after an instantaneous power
failure.
Without frequency search (reduced
voltage system)
Consider using these parameters
according to the load (inertia moment,
torque) magnitude.
Consider the rated inverter current as
100% and set the stall prevention
operation level during restart operation.
When Pr. 78 =0, the rotation direction is
detected.
Pr. 78 =1,2, the rotation direction is
When
not detected.
Set the acceleration time to reach the set
frequency at restart.
Acceleration time for restart is the normal
acceleration time (e.g. Pr. 7).
MC2
MC3
U
V
W
STF
CS
SD
For use for only
CS
automatic restart
SD
after instantaneous
power failure or flying start,
short CS-SD in advance.
MC
switchover
sequence
IM
When Pr. 162 = 0, 10 (with frequency search)
Power supply
(R/L1,S/L2,T/L3)
Motor
speed N (r/min)
Inverter
output frequency
f (Hz)
Inverter
output voltage
E (V)
Coasting
time (Pr.57)
* The output shut off timing differs according
to the load condition.
Instantaneous (power failure) time
*
Restart cushion
Speed
+
detection time
time (Pr. 58 setting)
Acceleration time
at a restart
(Pr. 611 setting)
When Pr. 162 = "1" or "11", automatic restart operation is
performed in a reduced voltage system, where the voltage is
gradually risen with the output frequency unchanged from prior to
an instantaneous power failure independently of the coasting
speed of the motor.
When Pr. 162 = 1, 11 (without frequency search)
Instantaneous (power failure) time
*
Coasting time
Pr. 57 setting
Restart cushion
time
Pr. 58 setting
Pr.
Power supply
(R/L1,S/L2,T/L3)
Motor speed N
(r/min)
Inverter
output frequency
f (Hz)
Inverter
output voltage
E (V)
* The output shut off timing differs according
to the load condition.
Remote setting function
59
Pr.59 Remote function selection
Even if the operation panel is located away from the enclosure,
you can use contact signals to perform continuous variable-speed
operation, without using analog signals.
By merely setting this parameter, you can use the acceleration,
deceleration and setting clear functions of the motorized speed
setter (FR-FK).
* External runnning frequency (other than multi-speed operation) or PU
0Hz
running frequency
RH, RM, RL signal
ON
ON
ON
ON
function
ON
When Pr. 59 = 1, 2
When Pr. 59 = 3
ON
ON
Frequency setting
storage function
No
(Turning STF/STR off
clears remotely-set
frequency.)
When Pr. 59 = 1
When Pr. 59 = 2, 3
ON
ON
Time
ON
ON
33
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Page 33
Pr.
Energy saving control selection
60
Pr.60 Energy saving control
Without a fine parameter setting, the inverter automatically
performs energy saving operation.
This inverter is optimum for fan and pump applications.
Pr. 60 SettingDescription
0 (initial value)Normal operation mode
Energy saving operation mode
In the energy saving operation mode, the inverter
automatically controls the output voltage to
minimize the inverter output voltage during a
constant operation.
Optimum excitation control mode
The optimum excitation control mode is a control
system which controls excitation current to
improve the motor efficiency to maximum and
determines output voltage as an energy saving
system.
Retry function at alarm
occurrence
Pr.67 Number of retries at alarm occurrence
If an alarm occurs, the inverter resets itself automatically to
restart. You can also select the alarm description for a retry.
When selection of automatic restart after instantaneous power
failure is selected (Pr. 57 Restart coasting time, restart operation is
performed at retry operation as at an instantaneous power
failure.)
Use Pr. 65 to select the alarm to be activated for retries.
"" indicates the alarms selected for retry.
Alarm Indication
for Retry
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.BE
E. GF
E.OHT
E.OLT
E.OPT
E.OP1
E. PE
E.PTC
E.CDO
E.SER
E.ILF
012345
Pr.65 Setting
Set the number of retries at alarm occurrence in Pr. 67.
Pr. 67 SettingDescription
0 (initial value)No retry function
Set the number of retries at alarm occurrence.
1 to 10
101 to 110
An alarm output is not provided during retry
operation.
Set the number of retries at alarm occurrence.
(The setting value of minus 100 is the number
of retries.)
An alarm output is provided during retry
operation.
Use Pr. 68 to set the waiting time from when an inverter alarm
occurs until a retry is made in the range 0 to 10s.
Reading the Pr. 69 value provides the cumulative number of
successful restart times made by retry.
Pr.
Pr.
Pr.
Pr.
Pr.71 Applied motor
Refer to the section about Pr. 22 and other
66
relevant parameters.
67 to 69
70
Refer to the section about Pr. 65 and
other relevant parameters.
Refer to the section about Pr. 30 and
other relevant parameters.
Use the constant torque motor
71
(applied motor)
Setting of the used motor selects the thermal characteristic
appropriate for the motor.
Setting is necessary when using a constant-torque motor.
Thermal characteristic of the electronic thermal relay function
suitable for the motor is set.
Motor
Pr.71
Setting
0
(initial
value)
1
2
20
Thermal Characteristic of the
Electronic Thermal Relay
Function
Thermal characteristics of a standard
motor
Thermal characteristics of the Mitsubishi
constant-torque motor
Thermal characteristics of a standard
motor
Adjustable 5 points V/F
Mitsubishi standard motor SF-JR4P
(1.5kW or less)
(: Motor used)
Standard
(SF-JR,
etc.)
(SF-HRCA,
Constant
torque
etc.)
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection
brake operation voltage settings are automatically changedaccording to the Pr. 71 setting as follows.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
34
Page 34
Pr.
P
P
72, 240, 260
Carrier frequency and SoftPWM selection
Pr.72 PWM frequency selectionPr.240 Soft-PWM operation selection
Pr.260 PWM frequency automatic switchover
You can change the motor sound.
Pr.
Number
72
240
260
* The setting range varies according to the inverter capacity. (55K or less/75K
or more).
(Note)When Pr. 260="1 (initial value)", if continuous operation is performed at
Pr.
Setting
Range
0 to 15/
0 to 6, 25 *
You can change the PWM carrier frequency. The
setting displayed is in [kHz].
Note that 0 indicates 0.7kHz, 15 indicates
Description
14.5kHz and 25 indicates 2.5kHz.
0Soft-PWM is invalid
When "0 to 5" ("0 to 4" for the 75K or more) is set
1
in Pr. 72, Soft-PWM is valid
PWM carrier frequency is constant independently
of load. When the carrier frequency is set to 3kHz
0
or more (Pr. 72≥ 3), perform continuous operation
at less than 85% of the rated inverter current.
Decreases PWM carrier frequency automatically
1
when load increases.
85% or more of the rated inverter current with Pr. 72 value set to “3”
(3kHz) or more, the carrier frequency is automatically reduced. This
may cause the motor noise to increase.
You can select the function that switches between forward rotation
and reverse rotation according to the analog input polarity, the
override function and the input signal specifications.
For the terminals 1, 2, 4 used for analog input, voltage input (0 to
5V, 0 to 10V) or current input (4 to 20mA) can be selected.
The additional compensation and fixed ratio of analog
compensation (override) using terminal 2 as an auxiliary input can
be made to multi-speed operation or the speed setting signal
(main speed) of the terminal 2 or terminal 4.
(indicates the main speed setting)
Compensation
Pr. 73
Setting
0
1
(Initial
value)
2
3
4
5
6
7
10
11
12
13
14
15
16
17
Terminal 2
Input
Ter mi nal 1
Input
0 to 10V 0 to ±10V
0 to 5V 0 to ±10V
0 to 10V 0 to ±5V
0 to 5V0 to ±5V
0 to 10V 0 to ±10V
0 to 5V0 to ±5V
4 to 20mA 0 to ±10V
4 to 20mA 0 to ±5V
0 to 10V 0 to ±10V
0 to 5V 0 to ±10V
0 to 10V 0 to ±5V
0 to 5V0 to ±5V
0 to 10V 0 to ±10V
0 to 5V0 to ±5V
4 to 20mA 0 to ±10V
4 to 20mA 0 to ±5V
Terminal 4 Input
When the AU
signal is off
×
Input Terminal
and
Compensation
Method
Termi na l 1
added
compensation
Termi na l 2
override
Termi na l 1
added
compensation
Termi na l 2
override
Termi na l 1
added
compensation
Polarity Reversible
Not function
(Indicates that
a frequency
command
signal of
negative
polarity is not
accepted. )
Function
Compensation
Pr. 73
Setting
0
1
(Initial
value)
2
3
4
5
6
7
10
11
12
13
14
15
16
17
Terminal 2
Input
Terminal 1
Input
0 to 10V 0 to ±10V
0 to ±10V
×
0 to ±5V
0 to ±5V
0 to 10V
0 to 5V
×
×
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±10V
×
0 to ±5V
0 to ±5V
0 to 10V
0 to 5V
×
×
0 to ±10V
0 to ±5V
Terminal 4 Input
When the AU
signal is on
According to the
Pr. 267 setting
(Initial value)
1:0 to 5V
2:0 to 10V
Input Terminal
and
Compensation
Method
Termi na l 1
added
compensation
Termi na l 2
override
Termi na l 1
added
compensation
Termi na l 2
override
Termi na l 1
added
compensation
Polarity Reversible
Not function
(Indicates that
a frequency
command
signal of
negative
polarity is not
accepted. )
Function
(1) Added compensation (Pr.242, Pr.243)
⋅ A compensation signal can be added to the main speed
setting for synchronous operation, etc.
Output frequency
When voltage across
terminals 2-5 is 2.5V
(5V)
0
-2.5V
-5V
(-10V)
STF
(a) When Pr. 73 setting is 0 to 5
(-5V)
+2.5V
(+5V)
Forward rotation
Forward rotation
+5V
(+10V)
When voltage
across terminals
2-5 is 0V
Terminal 1
Reverse rotation
STF
Reverse rotation
Output frequency
When voltage across
terminals 2-5 is 2.5V
(5V)
0
-2.5V
-5V
(-10V)
(b) When Pr. 73 setting is 10 to 15
(-5V)
Forward rotation
+2.5V
(+5V)
Forward rotation
+5V
(+10V)
When voltage
across terminals
2-5 is 0V
Terminal 1
⋅ The terminal 1 (frequency setting auxiliary input) signal is added
to the main speed setting signal of the terminal 2 or 4.
(2) Override function (Pr.252, Pr.253)
⋅ When an override is selected, the terminal 1 or 4 is used for
the main speed setting and the terminal 2 for the override
signal. (When the main speed of the terminal 1 or terminal 4
is not input, compensation by the terminal 2 is invalid.)
200
150
r.252
100
r.253
Override value (%)
50
0
0V
2.5V
(5V)
Voltage across terminals 2-5
⋅ When an override is selected, the terminal 1 or 4 is used for the
main speed setting and the terminal 2 for the override signal (50%
to 150% at 0 to 5V or 0 to 10V). (When the main speed of the
terminal 1 or 4 is not input, compensation by the terminal 2 is
invalid.)
⋅ When Pr. 22 Stall prevention operation level = "9999", the value of
the terminal 1 is as set to the stall prevention operation level.
Initial value
(50% to 150%)
5V
(10V)
35
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Page 35
Pr.
Pr.74 Input filter time constant
Noise elimination at the analog
74
input
The time constant of the primary delay filter relative to external
frequency command (analog input (terminal 1, 2, 4) signal) can
be set.
Valid for eliminating noise of the frequency setting circuit.
Increase the filter time constant if steady operation cannot be
performed due to noise.
A larger setting results in slower response. (The time constant can
be set between approximately 10ms to 1s with the setting of 0 to 8.)
Pr.
Pr.75 Reset selection/disconnected PU detection/PU stop selection
Reset selection, disconnected PU
75
detection
You can select the reset input acceptance, disconnected PU
(FR-DU07) connector detection function and PU stop function.
Pr.75
Setting
0
1
2
3
14
(initial
value)
15
16
17
Reset Selection
Reset input normally
enabled.
Reset input enabled
only when the prote ctive
function is activated.
Reset input normally
enabled.
Reset input enabled
only when the prote ctive
function is activated.
Reset input normally
enabled.
Reset input enabled
only when the prote ctive
function is activated.
Reset input normally
enabled.
Reset input enabled
only when the prote ctive
function is activated.
Disconnected
PU Detection
If the PU is
disconnected,
operation will be
continued as-is.
When the PU is
disconnected,
the inverter
output is shut
off.
If the PU is
disconnected,
operation will be
continued as-is.
When the PU is
disconnected,
the inverter
output is shut
off.
PU Stop
Selection
Pressing
decelerates the
motor to a stop only
in the PU operation
mode.
Pressing
decelerates the
motor to a stop in
any of the PU,
external and
communication
operation modes.
Pr.
Pr.76 Alarm code output selection
Output function of alarm code
76
At alarm occurrence, its description can be output as a 4-bit
digital signal from the open collector output terminals.
The alarm code can be read by a programmable controller, etc.,
and its corrective action can be shown on a display, etc.
Pr.76 SettingDescription
0 (initial value)Without alarm code output
1With alarm code output (Refer to the following table)
2
Alarm code output at alarm occurrence only (Refer to
the following table)
The following table indicates alarm codes to be output. (0: output
transistor off, 1: output transistor on)
Operation Panel
Indication
(FR-DU07)
Normal *00000
E.OC100011
E.OC200102
E.OC300113
E.OV1 to E.OV301004
E.THM01015
E.THT01106
E.IPF01117
E.UVT10008
E.FIN10019
E.BE1010A
E. GF1011B
E.OHT1100C
E.OLT1101D
E.OPT1110E
E.OP11110E
Other than the
above
* When Pr. 76 = "2", the output terminals output the signals assigned to
190 to Pr. 196.
Output of Output Terminals
SUIPFOLFU
1111F
Alarm Code
Pr.
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Diagram
Explanation
Terminal Connection
Terminal Specification
Panel
Operation
List
Parameter
of
Parameters
Explanations
Functions
Protective
Reset selection
⋅ You can select the operation timing of reset function (RES
signal, reset command through communication) input
Disconnected PU detection
⋅ This function detects that the PU (FR-DU07/FR-PU04) has
been disconnected from the inverter for longer than 1s and
causes the inverter to provide an alarm output (E.PUE) and
come to an alarm stop.
PU stop selection
⋅ In any of the PU operation, external operation and network
operation modes, the motor can be stopped by pressing
the PU.
of
Pr.
Pr.77 Parameter write selection
Prevention of parameter rewrite
77
You can select whether write to various parameters can be
performed or not. Use this function to prevent parameter values
from being rewritten by misoperation.
Pr. 77 SettingDescription
0 (initial value)Write is enabled only during a stop
1Parameter write is not enabled.
2
Pr.
Pr.78 Reverse rotation prevention selection
Prevention of reverse rotation of
78
the motor
Parameter write is enabled in any operation
mode regardless of operation status.
This function can prevent reverse rotation fault resulting from the
incorrect input of the start signal.
Pr.78 SettingDescription
0 (initial value)Both forward and reverse rotations allowed
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
36
Page 36
Pr.79Pr.
Pr.79 Operation mode selection
Operation mode selection
340
Pr.340 Communication startup mode selection
Used to select the operation mode of the inverter.
You can freely change between operation by external signal
(external operation), operation by PU (FR-DU07) (PU operation),
operation by combination of PU operation and external operation
(external/PU combined operation) and network operation (when
RS-485 terminals or a communication option is used).
Pr.79
Setting
External/PU switchover mode ( Press
0
(initial
value)
external operation mode.)
External operation mode at power-on
1Fixed to PU operation mode
Fixed to external operation mode
Operation can be performed by switching
2
between the external and Net operation
mode.
External/PU combined operation mode 1
Running frequencyStart signal
PU (FR-DU07 /
FR-PU04) setting
or external signal
3
input (multi-speed
setting, across
terminals 4-5 (valid
when AU signal
turns on))
Switch-over mode
Switch among PU operation, external
6
operation, and NET operation while
keeping the same operation status.
External operation mode (PU operation
interlock)
X12 signal ON
7
Operation mode can be switched to the
PU operation mode.
(output stop during external operation)
X12 signal OFF
Operation mode can not be switched to
the PU operation mode.
Description
to switch between the PU and
External signal
input (terminal STF,
STR)
Input from the PU
(FR-DU07 / FRPU04)
(, )
LED Indication
:Off
:On
External operation
mode
PU EXT NET
PU operation mode
PU EXT NET
PU EXT NET
External operation
mode
PU EXT NET
NET operation
mode
PU EXT NET
PU EXT NET
PU operation mode
PU EXT NET
External operation
mode
PU EXT NET
NET operation
mode
PU EXT NET
PU operation mode
PU EXT NET
External operation
mode
PU EXT NET
Specify operation mode at power on (Pr.340)
⋅
When power is switched on or when power comes back on after
instantaneous power failure, the inverter can be started up in the
network operation mode.
After the inverter has started up in the network operation mode,
parameter write and operation can be performed from a program.
Set this mode for communication operation using the inverter RS485 terminals or communication option.
⋅ You can set the operation mode at power on (reset) according
to the Pr. 79 and Pr. 340 settings.
Pr. 340
Setting
(initial
value)
1, 2*1
10, 12
*1 The Pr. 340 setting "2" or "12" is mainly used for communication
*2 The operation mode cannot be switched directly between the PU
*3 Operation mode can be changed between the PU operation mode and
Pr.
Pr.80 Motor capacity (simple magnetic flux vector control)
Pr.90 Motor constant (R1)
Pr.79
Setting
0
As set in Pr. 79.
3, 4
3, 4
*1
operation using the inverter RS-485 terminals.
When a value other than "9999" (selection of automatic restart after
instantaneous power failure) is set in Pr. 57 Restart coasting time, the
inverter will resume the same operation state which was in before after
power has been restored from an instantaneous power failure.
operation mode and network operation mode.
network operation mode with key of the operation panel (FR-
DU07) and X65 signal.
80, 90
Operation mode at
Power On, Power
Restoration, Reset
0NET operation mode
1PU operation modeFixed to PU operation mode
2NET operation mode
External/PU combined
operation mode
6NET operation mode
X12 (MRS) signal ON
.. NET operation mode
7
X12(MRS)signal OFF
.. External operation
mode
0NET operation mode
1PU operation modeFixed to PU operation mode
2NEToperation modeFixed to NET operation mode
External/PU combined
operation mode
6NET operation mode
External operation
7
mode
Operation Mode
Switchover
Can be switched to external,
PU or NET operation mode
Can be switched to external
or NET operation mode
Switching to PU operation
mode disabled
Operation mode switching
disabled
Can be switched to external,
PU or NET operation mode
with operation continued
Can be switched to external,
PU or NET operation mode
Fixed to external operation
mode (Forcibly switched to
external operation mode.)
Can be switched to PU or
NET operation mode
Operation mode switching is
disallowed
Can be switched to PU or
NET operation mode with
operation continued
Fixed to external operation
mode (Forcibly switched to
external operation mode.)
*3
*3
Simple magnetic flux vector
control
*2
*2
Providing optimum excitation to the motor can also produce high
torque in a low-speed region. (simple magnetic flux vector control)
⋅ Set the used motor capacity (equal to or one rank higher than the
inveter capacity) in Pr. 80.
⋅ The number of motor poles should be any of 2, 4 and 6 poles.
⋅ Single-motor operation (one motor for one inverter)
⋅ Wiring length from inverter to motor should be within 30m.
⋅ When simple magnetic flux vector control is not used, set "9999"
(initial value) in Pr. 80.
⋅ For Pr. 90 Motor constant (R1), normally setting is not necessary.
When you need more torque under simple magnetic flux vector
control for other manufacturer's motor, set the motor primary
resistance value (R1) for connection in Pr. 90
37
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
A dedicated V/F pattern can be made by freely setting the V/F
characteristic between a startup and the base frequency and
base voltage under V/F control (frequency voltage/frequency).
Possible to set the torque pattern that is optimum for the
machine’s characteristic
Voltage
ase frequency
voltage
Pr.19
Torque boost
Pr.0
0
⋅ Adjustable 5 points V/F will not function under simple magnetic
flux vector control.
⋅ When Pr. 19 Base frequency voltage = "8888" or "9999", Pr. 71 cannot be
set to "2". To set Pr. 71 to "2", set the rated voltage value to Pr. 19
⋅ When the frequency values of the points are the same, a write
inhibit error () occurs.
⋅ Set the points (frequencies, voltages) of Pr. 100 to Pr. 109 within
the ranges of Pr. 3 Base frequency and Pr. 19 Base frequency voltage .
⋅ When “2” is set in Pr. 71, Pr. 47 Second V/F (base frequency) will not
function.
⋅ When “2” is set in Pr. 71, thermal characteristic of the electronic
thermal relay function changes to thermal characteristics of a
standard motor.
Pr.
117 to 124, 331 to 337, 341 to 343, 549
Pr.101 V/F1 (first frequency voltage)
Pr.103 V/F2 (second frequency voltage)
Pr.105 V/F3 (third frequency voltage)
Pr.107 V/F4 (fourth frequency voltage)
Pr.109 V/F5 (fifth frequency voltage)
V/F5
V/F4
V/F3
V/F1
V/F2
V/F Characteristic
Base frequency
Pr.3
Frequency
Communication initial setting
Pr.117 PU communication stationPr.118 PU communication speed
Pr.119
PU communication stop bit length.
Pr.121
Number of PU communication retries
Pr.123 PU communication waiting time setting
Pr.124 PU communication CR/LF presence/absence selection
Pr.331 RS-485 communication stationPr.332 RS-485 communication speed
Pr.333
RS-485 communication stop bit length
Pr.334 RS-485 communication parity check selection
Pr.335 RS-485 communication number of retries Pr.336 RS-485 communication check time interval
Pr.337 RS-485 communication waiting time setting
Pr.341 RS-485 communication CR/LF selectionPr.342 Communication EEPROM write selection
Pr.343 Communication error countPr.549 Protocol selection
(1) Initial settings and specifications of RS-485
communication (Pr.117 to Pr.124, Pr.331 to Pr.337, Pr.341)
Used to perform required settings for RS-485 communication
between the inverter and personal computer.
There are two different communications: communication
using the PU connector of the inverter and communication
Pr.120 PU communication parity check
Pr.122 PU communication check time interval
Pr.
Number
117
331
118
332
Setting RangeDescription
0 to 31
(0 to 247)
48, 96, 192, 384
(3, 6, 12, 24)
Specify the inverter station number.
Set the inverter station numbers when two
or more inverters are connected to one
*1
personal computer.
Set the communication speed.
The setting value × 100 equals the
communication speed.
*2
For example, the communication speed is
19200bps when the setting value is "192".
Stop bit lengthData length
119
333
120
334
121
335
122
336
123
337
124
341
*1 When making communication through Modbus-RTU protocol with the RS-
485 terminals, the setting range of Pr. 331 within parenthesis is applied.
*2 The values in parenthesis are added to the setting range of Pr. 332.
01bit
1 (initial value)2bit
101bit
112bit
0Without parity check
1With odd parity check
2 (initial value)With even parity check
Set the permissible number of retries at
occurrence of a data receive error. If the
0 to 10
9999
0
0.1 to 999.8s
9999 (initial value) No communication check
0 to 150ms
9999 (initial value) Set with communication data.
0Without CR/LF
1 (initial value)With CR
2With CR/LF
number of consecutive errors exceeds the
permissible value, the inverter will come to
an alarm stop.
If a communication error occurs, the
inverter will not come to an alarm stop.
No PU connector communication
Communication with RS-485 terminal can
be made, but the inverter will come to an
alarm stop in the NET operation mode.
Set the interval of communication check
time.
If a no-communication state persists for
longer than the permissible time, the
inverter will come to an alarm stop.
Set the waiting time between data
transmission to the inverter and response.
8bit
7bit
(2) Communication EEPROM write selection (Pr.342)
Parameters written via the inverter's PU connector or RS-485
terminals or from the communication option can be written to
the RAM. When performing parameter change frequently, set
"1" in Pr. 342.
(3) Modbus-RTU communication specifications (Pr.343,
Pr.549)
* The Modbus-RTU protocol is valid for only communication from the RS-485
terminals.
Pr. Number
343
549
Setting
Range
Display the number of communication
errors during Modbus-RTU communication.
Reading only
You can perform parameter setting, monitor, etc. using the
Mitsubishi inverter protocol or Modbus-RTU protocol.
To make communication between the personal computer and
inverter, initialization of the communication specifications
must be made to the inverter.
Data communication cannot be made if the initial settings
are not made or there is any setting error.
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
38
Page 38
Pr.
7
125
Pr.
126
Pr.
241, C2(902) to C7(905)
Analog input frequency change and voltage, current input and
frequency adjustment (calibration)
Pr.125 Terminal 2 frequency setting gain frequency
Pr.126 Terminal 4 frequency setting gain frequency
Pr. 241 Analog input display unit switchover
C2(Pr.902) Terminal 2 frequency setting bias frequency
C3(Pr.902)
C5(Pr.904) Terminal 4 frequency setting bias frequency
C6(Pr.904)
You can set the magnitude (slope) of the output frequency as
(1)Change the frequency at maximum analog input.
(2) Analog input bias/gain calibration
(3) Analog input display unit changing (Pr. 241)
Terminal 2 frequency setting bias
Terminal 4 frequency setting bias
C4(Pr.903)
C7(Pr.905)
Terminal 2 frequency setting gain
Terminal 4 frequency setting gain
desired in relation to the frequency setting signal (0 to 5VDC, 0 to
10V or 4 to 20mA).
Pr.125, Pr.126
(
)
Set a value in Pr. 125 (Pr. 126) when changing only the
frequency setting (gain) of the maximum analog input power
(current). (C2 (Pr. 902) to C7 (Pr. 905) setting need not be
changed)
60Hz
(Hz)
Output frequency
Bias
C2
(Pr.902)
60Hz
(Hz)
Output frequency
Bias
C5
(Pr.904)
0
05V
Frequency setting signal
0
C3C4
(Pr.902)(Pr.903)
0
020420mA
(Pr.904)(Pr.905)
C6
Initial value
Initial value
Frequency setting signal
100%
10V
100%
C7
Gain
Gain
Pr.125
Pr.126
(C2(Pr.902) to C7(Pr.905))
⋅ The "bias" and "gain" functions are used to adjust the
relationship between the input signal entered from outside
the inverter to set the output frequency, e.g. 0 to 5V, 0 to 10V
or 4 to 20mADC, and the output frequency.
⋅ Set the bias frequency of terminal 2 input using C2(Pr. 902).
(Factory-set to the frequency at 0V)
⋅ Using Pr. 125 , set the output frequency relative to the
frequency command voltage (current) set in Pr. 73 Analoginput selection.
⋅ Set the bias frequency of the terminal 4 input using C5(Pr.
904).
(Factory-set to the frequency at 4mA)
⋅ Using Pr. 126 , set the output frequency relative to 20mA of
the frequency command current (4 to 20mA).
⋅ You can change the analog input display unit (%/V/mA) for
analog input bias/gain calibration.
Pr.
127 to 134, 575 to 57
PID control
Pr.127 PID control automatic switchover freqeuncy
Pr.128 PID action selectionPr.129 PID proportional band
Pr.130 PID integral timePr.131 PID upper limit
Pr.132 PID lower limitPr.133 PID action set point
Pr.134 PID differential timePr.575
Pr.576
Output interruption detection level
Output interruption detection time
Pr.577 Output interruption release level
The inverter can be used to exercise process control, e.g. flow
rate, air volume or pressure.
The terminal 2 input signal or parameter setting is used as a set point
and the terminal 4 input signal used as a feedback value to constitute
a feedback system for PID control.
⋅ Pr.128 ="10, 11" (Deviation value signal input)
Set point
Inverter circuit
Deviation signal
+
-
Terminal 1
0 to 10VDC
To outside
(0 to 5V)
Feedback signal (measured value)
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
PID operation
1+
Kp
Ti S
1
+Td S
Manipulated
variable
Motor
IM
⋅ Pr.128 ="20, 21" (Measured value input)
Pr. 133 or
terminal 2
Set point
0 to 5VDC
(0 to 10V, 4 to 20mA)
Pr.
135 to 139, 159
+
-
Terminal 4
Feedback signal (measured value)
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
Inverter circuit
PID operation
1
Kp 1+ +Td S
Ti S
4 to 20mADC (0 to 5V, 0 to 10V)
Switch between the inverter operation and
commercial power-supply operation to use
Pr.135 Commercial power-supply switchover sequence output terminal selection
Pr.136 MC switchover interlock timePr.137 Waiting time at a start
Pr.138 Commercial power-supply operation switchover selection at an alarm
Pr.139 Automatic switchover frequency between inverter and commercial power-supply operation
Pr.159 Automatic switchover ON range between commercial power-supply and inverter operation
Manipulated
variable
Motor
IM
The complicated sequence circuit for commercial power supplyinverter switchover is built in the inverter. Hence, merely
inputting the start, stop or automatic switchover selection signal
facilitates the interlock operation of the switchover magnetic
contactor.
*1 Take caution for the capacity of the sequence output terminal.
*2 When connecting a DC power supply, insert a protective diode.
*3 The used terminal changes depending on the setting of Pr. 180 to Pr. 189
(input terminal function selection).
Pr.
Pr.
140 to 143
144
Refer to the section about Pr. 29 and
other relevant parameters.
Refer to the section about Pr. 37 and other
relevant parameters.
39
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Page 39
Pr.
7
e
Pr.145
PU display language selection
Parameter unit display language
145
selection
You can switch the display language of the parameter unit (FRPU04) to another.
Pr.145 SettingDescription
0 (initial value)Japanese
1English
2German
3French
4Spanish
5Italian
6Swedish
7Finnish
Pr.
148, 149
Pr.
150 to 153, 166, 16
Refer to the section about Pr. 22 and
other relevant parameters.
Detection of output current (Y12 signal) detection
of zero current (Y13 signal)
Pr.150 Output current detection level
Pr.152 Zero current detection levelPr.153 Zero current detection time
Pr.166 Output current detection signal retention time
Pr.167 Output current detection operation selection
The output current during inverter running can be detected and
output to the output terminal.
(1) Output current detection
(Y12 signal, Pr. 150, Pr. 151, Pr. 166, Pr. 167)
⋅ The output current detection function can be used for
excessive torque detection, etc.
⋅ If the output current remains higher than the Pr. 150 setting
during inverter operation for longer than the time set in Pr.151, the output current detection signal (Y12) is output from
the inverter's open collector or relay output terminal.
Pr.166 9999, Pr.167 = 0
Pr.150
Output current
Output current
detection signal
(Y12)
(2) Zero current detection (Y13 signal, Pr. 152, Pr. 153)
⋅ If the output current remains lower than the Pr. 152 setting
during inverter operation for longer than the time set in Pr.153, the zero current detection (Y13) signal is output from
the inverter's open collector or relay output terminal.
Output
current
Pr.152
0[A]
OFF ON
* Once turned on, the zero current detection time
(Y13) signal is held on for at least 100ms.
Pr.
154
Start signal
Zero current
detection time
(Y13)
Refer to the section about Pr. 22 and other
relevant parameters.
Pr.151 Output current detection signal delay time
Pr.151
OFF
Pr.152
OFF
Pr. 153
Detection time
Pr.166
Minimum 100ms
(initial value)
ON
ON
100ms
OFF
Pr. 153
Detection time
Time
OFF
*
Tim
ON
Pr.
Pr.155 RT signal reflection time selection
Selection of action conditions of
155
the second function signal (RT)
You can select the second function using the external terminal
(RT signal).
You can also set the RT signal operation condition (reflection time).
Pr.155 SettingDescription
0 (initial value)
10
This function is immediately made valid with on
of the RT signal.
This function is valid only during the RT signal
is on and constant speed operation. (invalid
during acceleration/deceleration)
Refer to the section about Pr. 54 and other
relevant parameters.
Refer to the section about Pr. 135 and other
relevant parameters.
Pr.
160
First Function
Parameter Number
Pr.9Pr.51
Refer to the section about Pr. 22 and
other relevant parameters.
172 to 174
Second Function
Parameter Number
Display of applied parameters and user group function
Pr.160 User group read selection
Pr.172 User group registered display/batch clear
Pr.173 User group registrationPr.174 User group clear
Parameter which can be read from the operation panel and parameter
unit can be restricted.
In the initial setting, only the simple mode parameters are displayed.
Pr. 160
Setting
9999
(initial
value)
Only the simple mode parameters can be displayed.
0Simple mode+extended parameters can be displayed.
1Only parameters registered to the user group can be displayed.
(1)Display of simple mode parameters and extended
Pr.160
parameters (
)
⋅ When Pr. 160 = "9999" (initial value), only the simple mode
parameters can be displayed on the operation panel (FRDU07) and parameter unit (FR-PU04).
⋅ When “0” is set in Pr. 160, simple mode parameters and
extended parameters can be displayed.
(2) User group function (Pr.160, Pr.172 to Pr.174)
⋅ The user group function is designed to display only the
parameters necessary for setting.
⋅ From among all parameters, a maximum of 16 parameters can
be registered to a user group. When Pr. 160 is set in "1", only the
parameters registered to the user group can be accessed. (The
parameters not registered to the user group cannot be read.)
⋅ To register a parameter to the user group, set its parameter
number to Pr. 173.
⋅ To delete a parameter from the user group, set its parameter
number to Pr. 174. To batch-delete the registered parameters, setPr. 172 in "9999".
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
40
Page 40
Pr.
9
6
Pr.161 Frequency setting/key lock operation selection
Operation selection of the
161
operation panel
You can use the setting dial of the operation panel (FR-DU07)
like a potentiometer to perform operation.
The key operation of the operation panel can be disabled.
Pr.161 SettingDescription
0 (initial value)Setting dial frequency setting mode
Pr.178 STF terminal function selection Pr.179 STR terminal function selection
Pr.180 RL terminal function selectionPr.181 RM terminal function selection
Pr.182 RH terminal function selection Pr.183 RT terminal function selection
Pr.184 AU terminal function selectionPr.185 JOG terminal function selection
Pr.186 CS terminal function selectionPr.187 MRS terminal function selection
Pr.188
STOP terminal function selection
Refer to the section about Pr. 57 and
other relevant parameters.
Refer to the section about Pr. 150 and
other relevant parameters.
Parameter for manufacturer setting. Do not set.
Refer to the section about Pr. 52 and
other relevant parameters.
Refer to the section about Pr. 160 and
other relevant parameters.
Function assignment of
input terminal
Pr.189 RES terminal function selection
Key lock mode
invalid
Key lock mode
valid
Use these parameters to select/change the input terminal functions.
Selection of automatic restart after instantaneous
power failure, flying start
15 speed selection
(combination with three speeds RL, RM, RH)
Inverter operation enable signal
(FR-HC, FR-CV connection)
FR-HC connection, instantaneous power failure
detection
Forward rotation command
(assigned to STF terminal (Pr. 178) only)
Reverse rotation command
(assigned to STR terminal (Pr. 179) only)
PTC thermistor input
(assigned to AU terminal (Pr. 184) only)
Function
Low speed operation command
Middle speed operation
command
High speed operation command
Pr.
190 to 19
Pr.190 RUN terminal function selection Pr.191 SU terminal function selection
Pr.192 IPF terminal function selection Pr.193 OL terminal function selection
Pr.194 FU terminal function selectionPr.195
Pr.196
ABC2 terminal function selection
Terminal assignment of
output terminal
ABC1 terminal function selection
You can change the functions of the open collector output
terminal and relay output terminal.
Pr.190 to Pr.196
Setting
Positive
logic
Negative
logic
0100RUNInverter running
1101SUUp to frequency
2102IPF
3103OLOverload alarm
4104FUOutput frequency detection
5105FU2
5105FU2
7107RBPRegenerative brake prealarm *
10110PUPU operation mode
11111RYInverter operation ready
12112Y12Output current detection
13113Y13Zero current detection
14114FDNPID lower limit
15115FUPPID upper limit
16116RL
17MC1
18MC2
19MC3
25125FANFan fault output
26126FINHeatsink overheat pre-alarm
45145RUN3
46146Y46
47147PIDDuring PID control activated
64164Y64During retry
70170SLEEPDuring PID output suspension
90190Y90Life alarm
91191Y91Alarm output 3 (power-off signal)
92192Y92
93193Y93Current average monitor signal
94194ALM2Alarm output 2
95195Y95Maintenance timer signal
96196REMRemote output
98198LFMinor fault output
99199ALMAlarm output
9999No function
Signal
Name
Function
Instantaneous power failure/
undervoltage
Second output frequency
detection
Second output frequency
detection
PID forward/reverse rotation
output
Commercial power-supply
switchover MC1
Commercial power-supply
switchover MC2
Commercial power-supply
switchover MC3
During inverter running and start
command is on
During deceleration at
occurrence of power failure
(retained until release)
Energy saving average value
updated timing
* Setting can be made for the 75K or more.
Pr.
Pr.
Pr.
Pr.
232 to 239
240
241
242, 243
Refer to the section about Pr.4 to Pr.6
Refer to the section about Pr. 72 and other
relevant parameters.
Refer to the section about Pr. 125, Pr.126
Refer to the section about Pr. 73 and
other relevant parameters.
41
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Page 41
Pr.
7
Pr.244 Cooling fan operation selection
Increase cooling fan life
244
You can control the operation of the cooling fan (200V class
2.2K or more, 400V class 3.7K or more) built in the inverter.
Pr. 244 SettingDescription
0
1 (initial value)
The cooling fan operates at power on.
Cooling fan on/off control invalid (The cooling
fan is always on at power on)
Cooling fan on/off control valid
The fan is normally on during inverter
operation. The fan switches on/off according to
the temperature during a stop of the inverter
whose status is monitored.
Pr.
251, 872
Pr.251 Output phase failure protection selection
Input/output phase failure
protection selection
Pr.872 Input phase failure protection selection
You can disable the output phase failure protection function that
stops the inverter output if one of the inverter output side (load
side) three phases (U, V, W) opens.
The input phase failure protection selection of the inverter input
side (R/L1, S/L2, T/L3) can be made valid.
Pr.245 Rated slipPr.246 Slip compensation time constant
Pr.247 Constant-output region slip compensation selection
Slip compensation
The inverter output current may be used to assume motor slip to
keep the motor speed constant.
Pr.
Pr.250 Stop selection
Selection of motor stopping
250
method and start signal
Used to select the stopping method (deceleration to a stop or
coasting) when the start signal turns off.
Used to stop the motor with a mechanical brake, etc. together
with switching off of the start signal.
You can also select the operations of the start signals (STF/STR).
Pr.250
Setting
0 to 100s
1000s to 1100s
9999
8888
Start signal
(STF/STR)
STF signal: Foward
STR signal: Reverse
STF signal: Start signal
STR signal: Forward/
STF signal: Foward
STR signal: Reverse
STF signal: Start signal
STR signal: Forward/
Description
rotation start
rotation start
reverse
rotation signal
rotation start
rotation start
reverse
rotation signal
Stop operation
The motor is coasted to a
stop when the preset time
elapses after the start
signal is turned off. The
motor is coasted to a stop
(Pr. 250 - 1000)s after the
start signal is turned off.
When the start signal is
turned off, the motor
decelerates to stop.
When Pr. 250 is set to "9999" (initial value) or "8888".
Deceleration starts
when start signal turns off
Deceleration time
(Time set in Pr. 8, etc.)
OFF
DC brake
Time
Output frequency
(Hz)
Start
signal
RUN
signal
ON
OFF
ON
When Pr. 250 is set to values other than "9999" (initial value) or "8888".
Output is shut off when set
time elapses after start signal
turned off
Pr.250
Output frequency
Start signal
RUN signal
(Hz)
ON
ON
Motor coasts to stop
OFF
O
Time
FF
Pr.
252, 253
Pr.
255 to 259
Pr.255 Life alarm status displayPr.256
Pr.257
Control circuit capacitor life display
Pr.259 Main circuit capacitor life measuring
Refer to the section about Pr. 73 and
other relevant parameters.
Display of the life of the
inverter parts
Inrush current limit circuit life display
Pr.258
Main circuit capacitor life display
Degrees of deterioration of main circuit capacitor, control circuit
capacitor or inrush current limit circuit and cooling fan can be
diagnosed by monitor.
When any part has approached the end of its life, an alarm can
be output by self diagnosis to prevent a fault.
(Use the life check of this function as a guideline since the life
except the main circuit capacitor is calculated theoretically.)
Pr.
Number
255(0 to 15)
256(0 to 100%)
257(0 to 100%)
258(0 to 100%)
259
Pr.
260
Setting
Range
0, 1
(2, 3, 8, 9)
Display whether the control circuit capacitor,
main circuit capacitor, cooling fan, and each
parts of the inrush current limit circuit has
reached the life alarm output level or not.
Reading only
Display the deterioration degree of the inrush
current limit circuit. Reading only
Display the deterioration degree of the control
circuit capacitor. Reading only
Display the deterioration degree of the main
circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Setting "1" and turning off the power starts the
measurement of the main circuit capacitor life.
When the Pr. 259 value is "3" after powering on
again, the measuring is completed. Read the
deterioration degree in Pr. 258.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
42
Page 42
Pr.
6
f
P
261 to 26
Operation at instantaneous
power failure
Pr.261 Power failure stop selection
Pr.262 Subtracted frequency at deceleration start
Pr.263 Subtraction starting frequencyPr.264 Power-failure deceleration time 1
Pr.265 Power-failure deceleration time 2
Pr.266 Power failure deceleration time switchover frequency
When a power failure or undervoltage occurs, the inverter can
be decelerated to a stop or can be decelerated and reaccelerated to the set frequency.
Pr.
Number
261
262 0 to 20Hz
263
264 0 to 3600/ 360s *
265
266 0 to 400Hz
* When the setting of Pr. 21 Acceleration/deceleration time increments is "0"
(initial value), the setting range is "0 to 3600s" and the setting increments
are "0.1s", and when the setting is "1", the setting range is "0 to 360s" and
the setting increments are "0.01s"
Setting RangeDescription
Coasting to stop
0 (initial value)
When undervoltage or power failure
occurs, the inverter output is shut off.
When undervoltage or a power failure
1
occurs, the inverter can be decelerated
to a stop.
When undervoltage or a power failure
occurs, the inverter can be decelerated
2
to a stop.
If power is restored during a power
failure, the inverter accelerates again.
Normally operation can be performed
with the initial value unchanged. But
adjust the frequency according to the
magnitude of the load specifications
(moment of inertia, torque).
When output frequency ≥ Pr. 263
Decelerate from the speed obtained
0 to 120Hz
from output frequency minus Pr. 262.
When output frequency < Pr. 263
Decelerate from output frequency
9999
Decelerate from the speed obtained
from output frequency minus Pr. 262.
Set a deceleration slope down to the
frequency set in Pr. 266.
0 to 3600/ 360s *
Set a deceleration slope below the
frequency set in Pr. 266.
9999Same slope as in Pr. 264
Set the frequency at which the
deceleration slope is switched from the
Pr. 264 setting to the Pr. 265 setting.
Power supply
Output
frequency
Power-failure
deceleration
time switchover
requency
r.266
Subtracted
frequency at
deceleration start
Pr.262
Pr.264
Power-failure
deceleration time 1
Time
Pr.265
Power-failure
deceleration
time 2
(1) Power failure stop mode (Pr.261 = “1”)
⋅ If power is restored during power failure deceleration,
deceleration to a stop is continued and the inverter remains
stopped.To restart, turn off the start signal once, then turn it
on again.
Pr.261 = 1
supply
Power
Output frequency
STF
Y46
During deceleration at
occurrence of power failure
During stop at
occurrence of
power failure
Time
Turn off STF once to make acceleration again
(2) Instantaneous power failure-time operation
continuation function (Pr.261 = “2”)
⋅ When power is restored during deceleration after an
instantaneous power failure, acceleration is made again up
to the set frequency.
⋅ When this function is used in combination with the automatic
restart after instantaneous power failure operation,
deceleration can be made at a power failure and
acceleration can be made again after power restoration.
When power is restored after a stop by deceleration at an
instantaneous power failure, automatic restart operation is
performed if automatic restart after instantaneous power
failure has been selected (Pr. 57 ≠ "9999")
When power is restored during
Pr.261 = 2
deceleration
IPF
Reacceleration
When used with automatic restart
after instantaneous power failure
During power failure
Reset time + Pr.57
Time
Automatic restart
after instantaneous
power failure
Time
Pr.
Pr.
Pr.
Pr.
Pr.
Power
supply
Output
frequency
During deceleration
at occurrence of
power failure
Y46
Pr.261 = 2, Pr.57 9999
Power
supply
Output
frequency
267
268
269
299
331 to 337
During deceleration
at occurrence of
power failure
Y46
Refer to the section about Pr. 73 and other
relevant parameters.
Refer to the section about Pr. 52 and other
relevant parameters.
Parameter for manufacturer setting. Do not set.
Refer to the section about Pr. 57 and other
relevant parameters.
Refer to the section about Pr. 117 and
other relevant parameters.
Pr.
43
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Page 43
Pr.
7
4
7
338, 339, 550, 551
Operation command source and speed command
source during communication operation
Pr.338 Communication operation command source
Pr.339 Communication speed command source
Pr.550 NET mode operation command source selection
Pr.551 PU mode operation command source selection
When the RS-485 terminals or communication option is used,
the external operation command and speed command can be
made valid. Also, the control command source in the PU
operation mode can be selected.
Pr.
Number
338
339
550
551
* Pr. 550 and Pr. 551 are always write-enabled.
Pr.
Pr.
Pr.
Pr.495 Remote output selectionPr.496 Remote output data 1
Pr.497 Remote output data 2
You can utilize the on/off of the inverter's output signals instead
of the remote output terminal of the programmable logic
controller.
*
*
340
341 to 343
495 to 49
Setting
Range
0
(initial
value)
(initial
value)
9999
(initial
value)
(initial
value)
Operation command source communication
1Operation command source external
0
Speed command source communication
Speed command source external (Frequency
setting from communication is invalid, terminal 2
1
and 1 setting from external is valid)
Speed command source external (Frequency
setting from communication is valid, terminal 2 and
2
1 setting from external is invalid)
0Communication option valid
1Inverter RS-485 terminal valid
Automatic communication option recognition
Normally, the RS-485 terminals are valid. When
the communication option is fitted, the
communication option is valid.
Select the RS-485 terminals as the PU operation
1
mode control source.
2
Select the PU connector as the PU operation
mode control source.
Description
Refer to the section about Pr. 79.
Refer to the section about Pr. 117 and
other relevant parameters.
Remote output function
(REM signal)
Pr.
503 to 50
Pr.503 Maintenance timer
To determine the
maintenance time of parts.
Pr.504 Maintenance timer alarm output set time
When the cumulative energization time of the inverter reaches
the parameter set time, the maintenance timer output signal
(Y95) is output. (MT) is displayed on the operation panel
(FR-DU07)
This can be used as a guideline for the maintenance time of
peripheral devices.
First powerON
9998
Maintenance
timer
(Pr. 503)
Y95 signal
MT display
(999800h)
Pr.504
Set "0" in Pr.503
OFFON
ON
Time
The cumulative energization time of the inverter is stored into the
EEPROM every hour and indicated in Pr. 503 Maintenance timer in
100h increments. Pr. 503 is clamped at 9998 (999800h).
Pr.
549
Pr.
550 to 551
Pr.
Pr.555 Current average timePr.556 Data output mask time
Pr.557 Current average value monitor signal output reference current
Refer to the section about Pr.117 to Pr. 124.
Refer to the section about
Current average value
555 to 55
monitor signal
Pr. 338, Pr.339
The average value of the output current during constant speed
operation and the maintenance timer value are output as a pulse to
the current average value monitor signal (Y93).
The pulse width output to the I/O module of the PLC or the like can
be used as a guideline due to abrasion of machines and elongation
of belt and for aged deterioration of devices to know the
maintenance time.
The current average value monitor signal (Y93) is output as
pulse for 20s as 1 cycle and repeatedly output during constant
speed operation.
From acceleration to constant speed operation
Output
frequency
Next cycle
5) End pulse
output as low pulse
shape for 1 to 16.5s
40000h
Time
5s
1) Data output mask time
When the speed has changed to constant
from acceleration/deceleration, Y93 signal is
not output for Pr.556 time.
2) Start pulse
Output as Hi pulse shape for 1s (fixed)
Time and output current set in Pr.555 are averaged
3) Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9s (10 to 180%) during start bit output.
Signal output time=
Y93 signal
output current average value (A)
Pr.557 (A)
1 cycle (20s)
4) Maintenance timer pulse
The maintenance timer value (Pr.503) is output
as Hi output pulse shape for 2 to 9s (16000h to
72000h).
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Refer to the section about Pr. 13 and other
relevant parameters.
Refer to the section about Pr. 127 and
other relevant parameters.
Refer to the section about Pr. 57 and other
relevant parameters.
Refer to the section about Pr. 251 and other
relevant parameters.
44
Page 44
Pr.
6
9
882 to 88
Pr.882 Regeneration avoidance operation selection
Pr.883 Regeneration avoidance operation level
Pr.884 Regeneration avoidance at deceleration detection sensitivity
Pr.885 Regeneration avoidance compensation frequency limit value
Pr.886 Regeneration avoidance voltage gain
Regeneration avoidance
function
This function detects a regeneration status and increases the
frequency to avoid the regeneration status.
Possible to avoid regeneration by automatically increasing the
frequency and continue operation if the fan happens to rotate
faster than the set speed due to the effect of another fan in the
same duct.
Pr.
Number
882
883
884
885
886 0 to 200%
Pr.
Pr.888 Free parameter 1Pr.889 Free parameter 2
Setting
Range
0
(initial
value)
300 to
800V
(initial
value)
1 to 5
0 to 10Hz
9999Frequency limit invalid
888, 889
Regeneration avoidance function invalid
1Regeneration avoidance function valid
Set the bus voltage level at which regeneration
avoidance operates. When the bus voltage level
is set to low, overvoltage error will be less apt to
occur. However, the actual deceleration time
increases. The set value must be higher than the
power supply valtage × .
0
Regeneration avoidance by bus voltage change
ratio is invalid
Set sensitivity to detect the bus voltage change
Setting 1
Detection sensitivity lowhigh
Set the limit value of frequency which rises at
activation of regeneration avoidance function.
Adjust responsiveness at activation of
regeneration avoidance. A larger setting will
improve responsiveness to the bus voltage
change. However, the output frequency could
become unstable.
Free parameter
Description
2
5
Parameters you can use for your own purposes.
You can input any number within the setting range 0 to 9999.
For example, the number can be used:
⋅ As a unit number when multiple units are used.
⋅ As a pattern number for each operation application when
multiple units are used.
⋅ As the year and month of introduction or inspection.
Pr.
891
Refer to the section about Pr. 52 and other
relevant parameters.
Pr.
892 to 89
Pr.892 Load factor
Pr.893 Energy saving monitor reference (motor capacity)
Pr.894 Control selection during commercial power-supply operation
Pr.895 Power saving rate reference value
Pr.896 Power unit cost
Pr.897
Power saving monitor average time
Pr.898
Power saving cumulative monitor clear
Pr.899
Operation time rate (estimated value)
Energy saving monitor
From the power consumption estimated value during
commercial power supply operation, the energy saving effect by
use of the inverter can be monitored/output.
⋅ The following provides the items that can be monitored by the
power saving monitor (Pr. 52, Pr. 54, Pr. 158 = "50").
(Only power saving and power saving average value can be output to Pr. 54
(terminal FM) and Pr. 158 (terminal AM))
Energy
Saving
Monitor
Item
Power
saving
Power
saving
rate
Power
saving
average
value
Power
saving
rate
reference
value
Power
saving
charge
average
value
Difference between the estimated value of
power necessary for commercial power supply
operation and the input power calculated by the
inverter
Power during commercial power supply
operation - input power monitor
Ratio of power saving on the assumption that
power during commercial power supply
operation is 100%
Power during commercial power supply operation
Ratio of power saving on the assumption that
Pr. 893 is 100%
Average value of power saving amount per hour
during predetermined time (Pr. 897)
Ratio of power saving average value on the
assumption that the value during commercial
power supply operation is 100%
Ratio of power saving average value on the
assumption that Pr. 893 is 100%
Power saving average value
Power saving average value represented in
terms of charge
Power saving average value ×Pr. 896
Description and FormulaIncrements
Power saving
Power saving
Pr.893
Σ (Power saving × ∆t)
Σ (Power saving × ∆t)
Pr.897
Pr.897
×100
Pr.893
×100
×100
× 100
0.01kW/
0.1kW*
0.1%
0.01kWh/
0.1kWh*
0.1%
0.01/0.1*
45
Pr.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Page 45
⋅ The following gives the items which can be monitored by the
cumulative saving power monitor (Pr. 52 = "51").
(The cumulative power monitor data digit can be shifted to the
right by the number set in Pr. 891 Cumulative power monitor digitshifted times.)
Energy
Saving
Monitor
Item
Power
saving
amount
Power
saving
amount
charge
Annual
power
saving
amount
Annual
power
saving
amount
charge
* The increments vary according to the inverter capacity. (55K or less/75K or
more)
Power saving is added up per hour.
Σ (Power saving × ∆t)
Power saving amount represented in terms of
charge
Power saving amount × Pr. 896
Estimated value of annual power saving amount
Annual power saving amount represented in
terms of charge
Annual power saving amount × Pr. 896
Description and FormulaIncrements
Power saving amount
Operation time during
power saving totalization
× 24 × 365 ×
Pr.899
100
0.01kWh/
0.1kWh*
0.01/0.1*
0.01kWh/
0.1kWh*
0.01/0.1*
Pr.
Pr.990 PU buzzer control
Buzzer control of the operation panel
990
You can make the buzzer "beep" when you press key of the
operation panel (FR-DU07) and parameter unit (FR-PU04).
Pr.990 SettingDescription
0Without buzzer
1(initial value)With buzzer
Pr.
Pr.991 PU contrast adjustment
PU contrast adjustment
991
Contrast adjustment of the LCD of the parameter unit (FRPU04) can be performed.
Decreasing the setting value makes contrast light.
Pr.991 SettingDescription
0 to 63
0 : Light
↓
63 : Dark
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Diagram
Explanation
Terminal Connection
Terminal Specification
Pr.
C0(900), C1(901)
C0(Pr.900) FM terminal calibrationC1(Pr.901) AM terminal calibration
Adjustment of terminal FM
and AM (calibration)
The operation panel and parameter unit can be used to calibrate
the full scales of the terminals FM and AM.
(1) FM terminal calibration (C0(Pr.900))
⋅ The terminal FM is preset to output pulses. By setting the
Calibraton parameter C0 (Pr. 900), the meter connected to the
inverter can be calibrated by parameter setting without use
of a calibration resistor.
⋅ Using the pulse train output of the terminal FM, a digital
display can be provided by a digital counter. The monitor
value is 1440 pulses/s output at the full-scale value of Pr. 54FM terminal function selection.
Indicator
1mA full-scale
analog meter
FM
SD
*1 Not needed when the operation panel (FR-DU07) or parameter unit (FR-
PU04) is used for calibration.
Used when calibration must be made near the frequency meter for such a
reason as a remote frequency meter.
However, the frequency meter needle may not deflect to full-scale if the
calibration resistor is connected. In this case, use this resistor and
operation panel or parameter unit together.
1mA
(+)
Calibration
*1
resistor
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr. 55 (frequency monitor)
(-)
Set with Pr.56 (current monitor)
8VDC
T1
T2
FM
SD
1440 pulse/s(+)
(Digital indicator)
(-)
(2) AM terminal calibration (C1(Pr.901))
⋅ The AM terminal is factory-set to output 10VDC in the full-
scale state of each monitor item. By setting the calibrationparameter C1 (Pr. 901), the ratio (gain) of the output voltage
can be adjusted to the meter scale. Note that the maximum
output voltage is 10VDC.
Pr.
989, CL, ALLC, Er.CL, PCPY
Parameter clear, parameter copy
Pr.989 Parameter copy alarm release
Pr.CL Parameter clearALLC All parameter clear
Er.CL Alarm history clearPCPY Parameter copy
Set “1” in Pr.CL Parameter clear to initialize all parameters.
(Calibration parameters are not cleared.)*
Set “1” in ALLC All parameter clear to initialize all parameters. *
Set “1” in Er.CL Alarm history clear to clear alarm history. *
Parameter settings can be copied to multiple inverters by using
PCPY.
When parameters are copied to the 75K or more inverter from
the 55K or less inverter or vice versa, an alarm appears on
the operation panel.
For the parameters whose setting range differ, set
below after reset.
55K or less75K or more
Pr.989 setting
PCPY
Setting
0Cancel
1Copy the source parameters in the operation panel.
Write the parameters copied to the operation panel to the
2
destination inverter.
3Verify parameters in the inverter and operation panel.
* Parameters are not cleared when "1" is set in Pr.77 Parameter write selection.
indicates simple mode parameters and indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Refer to the section about
Pr.
Pr. 125, Pr. 126
46
Page 46
Protective Functions
When an alarm occurs in the inverter, the protective function is activated bringing the inverter to an alarm stop and the PU
display automatically changes to any of the following error (alarm) indications.
Function NameDescriptionIndication
Operation panel lockAppears when operation is tried during operation panel lock.
*2
Parameter write errorAppears when an error occurs at parameter writing.
to
Copy operation errorAppears when an error occurs at parameter copying.
Error message
Error
Stall Prevention
(overcurrent)
Stall prevention
(overvoltage)
Appears when the RES signal is on or the PU and inverter can not make normal
communication.
Appears during overcurrent stall prevention.
Appears during overvoltage stall prevention
Appears while the regeneration avoidance function is activated.
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "special
Regenerative brake
*3
prealarm
regenerative brake duty" value. If the regenerative brake duty reaches 100%, a
regenerative overvoltage (E. OV_) occurs.
(displayed only for the 75K or more)
Electronic thermal relay
function prealarm
Warnings
PU Stop
Maintenance signal output
Parameter copy
*4
Fan fault
Minor
fault
Overcurrent shut-off during
acceleration
Overcurrent shut-off during
constant speed
Overcurrent shut-off during
deceleration or stop
Regenerative overvoltage
shutoff during acceleration
Appears when the electronic thermal O/L relay has reached 85% of the specified
value.
Appears whenon the operation panel was pressed during external operation.
Appears when the cumulative energization time has exceeded the maintenance
output timer set value.
Appears when parameters are copied between models with capacities of 55K or
less and 75K or more.
Appears when the cooling fan remains stopped when operation is required or when the speed
has decreased.
Appears when an overcurrent occurred during acceleration.
Appears when an overcurrent occurred during constant speed operation.
Appears when an overcurrent occurred during deceleration and at a stop.
Appears when an overvoltage occurred during acceleration.
Regenerative overvoltage
shut-off during constant
Appears when an overvoltage occurred during constant speed operation.
speed
Regenerative overvoltage shut-
off during deceleration or stop
Inverter overload shut-off
(electronic thermal relay
function)
*1
Motor overload shut-off
(electronic thermal relay
function)
*5
*1
Appears when an overvoltage occurred during deceleration and at a stop.
Appears when the electronic thermal relay function for inverter element protection
was activated.
Appears when the electronic thermal relay function for motor protection was
activated.
Fin overheatAppears when the heatsink overheated.
Instantaneous power failure
protection
Appears when an instantaneous power failure occurred at an input power supply.
Undervoltage protectionAppears when the main circuit DC voltage became low.
Major failures
Input phase failureAppears if one of the three phases on the inverter input side opened.
Stall prevention
Output side earth (ground)
fault overcurrent protection
Output phase failure
protection
External thermal relay
operation
*6
PTC thermistor operation
Appears when the output frequency drops to 0.5Hz as a result of deceleration due to
the excess motor load.
Appears when an earth (ground) fault occurred on the inverter's output side.
Appears if one of the three phases on the inverter output side opened.
Appears when the external thermal relay connected to the terminal OH operated.
Appears when the motor overheat status is detected for 10s or more by the external
PTC thermistor input connected to the terminal AU.
Appears when an alarm occurred in the option card or an AC power supply is
Option alarm
connected to the R/L1, S/L2, T/L3 when the high power factor converter connection
is set.
Option slot alarmAppears when a communication error occurred in the communication option.
Option alarmAppears when a functional error occurred in the plug-in option.
Parameter storage devide
alarm
Appears when operation of the element where parameters are stored became
abnormal. (control circuit board)
to
47
Page 47
Function NameDescriptionIndication
Appears when a communication error between the PU and inverter occurred, the
PU disconnection
communication interval exceeded the permissible time during the RS-485
communication with the PU connecter, or communication errors exceeded the
number of retries during the RS-485 communication.
Retry count excessAppears when the operation was not restarted within the set number of retries.
Parameter storage devide
alarm
Appears when operation of the element where parameters stored became
abnormal. (main circuit board)
CPU errorAppears during the CPU and peripheral circuit errors.
Operation panel power
*5
supply short circuit
RS-485 terminals power
Appears when the RS-485 terminal power supply or operation panel power supply
was shorted.
supply short circuit
24VDC power output short
circuit
Major failures
Output current detection
value exceeded
Appears when terminals PC-SD were shorted.
Appears when output current exceeded the output current detection level set by the
parameter.
Inrush resistor overheatAppears when the resistor of the inrush current limit circuit overheated.
Communication error
(inverter)
Analog input error
Appears when a communication error occurred during the RS-485 communication
with the RS-485 terminals.
Appears when 30mA or more is input or a voltage (7.5V or more) is input with the
terminal 2/4 set to current input.
Internal circuit errorAppears when an internal circuit error occurred.
Brake transistor alarm
detection
*1 Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.
*2 The error message shows an operational error. The inverter output is not shut off.
*3 Warnings are messages given before major failures occur. The inverter output is not shut off.
*4 Minor faults warn the operator of failures with output signals. The inverter output is not shut off.
*5 When major failures occur, the protective functions are activated to shut off the inverter output and output the alarms.
*6 The external thermal operates only when the OH signal is set in Pr. 178 to Pr. 189 (input terminal function selection).
This function stops the inverter output if an alarm occurs in the brake circuit, e.g.
damaged brake transistors. In this case, the inverter must be powered off
immediately. (Internal circuit error for the model 55K or less)
By fitting the following options to the inverter, the inverter is provided with more functions.
One plug-in option can be fitted.
NameTypeApplications, Specifications, etc.
16-bit digital inputFR-A7AX
Digital output
extension analog output
Relay outputFR-A7AR
FR-A7AY
Plug-in Type
CC-LINKFR-A7NC
LONWORKSFR-A7NL
Communication
Parameter unit (Eightlanguages)
Parameter unit connection cable
Operation panel connection
connector
Intercompatibility attachment
AC reactor
DC reactor
Line noise filter
BU type brake unit
Brake unit
Resistor unit
Power regeneration common
converter
Dedicated stand-alone reactor
for the FR-CV
Stand-alone Shared
Power regeneration converter
High power factor converter
Surge voltage suppression filter
Reactor
filter
Capacitor
Sine wave
FR-PU04Interactive parameter unit with LCD display
FR-CB20
FR-ADP
FR-AAT
FR-A5AT
FR-HAL
FR-HEL
FR- BSF01
FR- BLF
BU
FR-BU
MT-BU5
FR-BR
MT-BR5
FR-CV
FR-CVL
MT-RC
FR-HC
MT-HC
FR-ASFFilter for suppressing surge voltage on motor
MT-BSL
MT-BSC
⋅ This input interface sets the high frequency accuracy of the
inverter using an external BCD or binary digital signal.
BCD code 3 digits (maximum 999)
BCD code 4 digits (maximum 9999)
Binary 12 bits (maximum FFFH)
Binary 16 bits (maximum FFFFH)
⋅ This option provides the inverter with open collector outputs
selected from among the standard output signals.
⋅ This option adds two different signals that can be
monitored at the terminals FM and AM, such as the output
frequency, output voltage and output current.
⋅ 20mADC or 5VDC (10V) meter can be connected.
⋅ Output any three output signals available with the inverter
as standard from the relay contact terminals
⋅ This option allows the inverter to be operated or monitored
or the parameter setting to be changed from a computer or
PLC.
* For the FR-A7NC (CC-Link), the above operations can be done from the PLC
only.
Cable for connection of operation panel or parameter unit
indicates a cable length. (1m, 3m, 5m)
Connector to connect the operation panel (FR-DU07) and
connection cable
Attachment for replacing with the F700 series using the
installation holes of the FR-F500.
Attachment for replacing with the F700 series using the
installation holes of the FR-A100<Excellent> and FRA200<Excellent>
For harmonic current reduction and inverter input power factor
improvement (total power factor approx. 88%)
For harmonic current reduction and inverter input power factor
improvement (total power factor approx. 93%)
For line noise reduction
For increasing the braking capability of the inverter (for highinertia load or negative load)
For increasing the braking capability of the inverter (for highinertia load or negative load)
Brake unit and resistor unit are used in combination
Unit which can return motor-generated braking energy back
to the power supply in common converter system
Energy saving type high performance brake unit which can
regenerate the braking energy generated by the motor to the
power supply.
The high power factor converter switches the converter
section on/off to reshape an input current waveform into a
sine wave, greatly suppressing harmonics. (Used in
combination with the standard accessory.)
Reduce the motor noise during inverter driving
Use in combination with a reactor and a capacitor
Applicable
Inverter
Shared among all
models
Shared among all
models
According to
capacities
For 200V class
55K or less, 400V
class 75K or less
For the 55K or
less
Shared among all
models
For the 55K or
less
According to
capacities
For the 55K or
less
For the 75K or
more
According to
capacities
For 400V class
55K or less
For the 75K or
more
49
Page 49
NameTypeApplications, Specifications, etc.
Manual controller
DC tach. follower
Three speed selector
Motorized speed setter
Ratio setter
PG follower
Master controller
Soft starter
Deviation detector
FR-AX
FR-AL
FR-AT
FR-FK
FR-FH
FR-FP
FR-FG
FR-FC
FR-FD
For independent operation. With frequency meter, frequency
setting potentiometer and start switch.
For synchronous operation (1.5VA) by external signal (0 to
5V, 0 to 10V DC)
*
For three speed switching, among high, middle and low
speed operation (1.5VA)
*
For remote operation. Allows operation to be controlled from
several places (5VA)
*
For ratio operation. Allows ratios to be set to five inverters.
*
(3VA)
For tracking operation by a pilot generator (PG) signal (3VA)
*
Master controller (5VA) for parallel operation of multiple
(maximum 35) inverters.
*
For soft start and stop. Enables acceleration/deceleration in
parallel operation (3VA)
*
For continuous speed control operation. Used in combination
with a deviation sensor or synchro (5VA)
*
Applicable
Inverter
Shared among all
models
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Preamplifier
FR Series Manual Controller/Speed Controller
Pilot generator
Deviation sensor
Frequency setting potentiometer
Frequency meter
Others
Calibration resistor
Inverter setup software
(FR Configrator)
*Rated power consumption. The power supply specifications of the FR series manual controllers and speed controllers are 200VAC 50Hz, 220V/
220VAC 60Hz, and 115VAC 60Hz.
FR-FAUsed as an A/V converter or arithmetic amplifier (3VA) *
The FR-F700 series inverter can be installed using installation holes of the conventional FR-F500 series with this attachment.This attachment is useful for replacing the conventional model with the FR-F700 series.
Since the installation size of the 400V class 0.75K to 3.7K, 7.5K, 22K, 37K to 55K are the same, an intercompatibility attachment is not necessary
* The depth increases after installation of the inverter when the attachment is used.
Typ eApplied Inverter
FR-AAT22
FR-AAT24
FR-AAT27
Typ eApplied Inverter
FR-A5AT02
FR-A5AT03
FR-A5AT04
FR-A5AT05
Typ eWDH
135 59.61151.5
135 59.61151.5
135 59.61151.5
135 59.61151.5
135 70.61152.5
160721423.5
160911425.0
160911466.0
2201051959.0
2201702159.0
2201702159.5
22017021511
22017021412.5
28016524515
28017024518
20520817020
4
0
0
V
H0.4K
H0.75K
H1.5K
H2.2K
H3.7K
H5.5K
H7.5K
H11K
H15K
H18.5K
H22K
H30K
H37K
H45K
H55K
H75K
Intercompatibility
attachment
FR-AAT
FR-A5AT
AC reactor
(for power coordination)
FR-HAL-(H)K
FR-AAT
Inverter
12
FR-A100E and FR-A200E series installation intercompatibility attachment
The FR-F700 series inverter can be installed using installation holes of the conventional FR-A100E and FR-A200E series with this attachment. This
attachment is useful for replacing the conventional model with the FR-F700 series.
* The depth increases after installation of the inverter when the attachment is used
FR-A5AT
Inverter
12
Outline dimension
Typ eWDH
10472990.6
0.4K
0.75K
2
0
0
V
18.5K
10474990.8
10477991.1
1.5K
2.2K
3.7K
5.5K
7.5K
1157 711 51 .5
1158 311 52 .2
1158 311 52 .3
1301001354.2
1601111645.2
11K
1601261677.0
15K
1601751287.1
1851581509.0
22K
1851681509.7
30K
210174175 12.9
37K
210191175 16.4
45K
210201175 17.4
55K
Mass
(kg)
FR-F740-5.5K
FR-F740-15K, 18.5K
FR-F740-30K
FR-F740-0.75K to 3.7K
FR-F740-5.5K to 11K
FR-F740-15K to 22K
FR-F740- 45K, 55K
(Unit: mm)
Mass
(kg)
(Note) 1. Make selection according to the applied
Less than D
H
W
motor capacity. (When the inverter
capacity is larger than the motor
capacity, make selection according to the
motor capacity)
2. Power factor improving reactor (FR-BAL)
can be used.
Power factor improving effect
FR-BAL : approx. 90%
FR-HAL : approx. 88%
DC reactor
(for power coordination)
FR-HEL-(H)K
Outline dimension
Typ eWDH
0.4K
0.75K
1.5K
2.2K
3.7K
5.5K
2
7.5K
0
11K
0
15K
V
18.5K
22K
30K
37K
45K
55K
7061710.4
8561810.5
8570810.8
8570810.9
7782921.5
7792921.9
86981132.5
1051121333.3
1051151334.1
105165934.7
105175935.6
1142001007.8
13319511710
13320511711
15320913212.6
Mass
(kg)
Typ eWDH
9060780.6
66701000.8
66801001
76801101.3
86951202.3
961001283
961051283.5
1051101374.5
1051251525
1141201625
1331201786
1331201786.5
1331551878.5
13317018710
15217020611.5
V
4
0
0
H0.4K
H0.75K
H1.5K
H2.2K
H3.7K
H5.5K
H7.5K
H11K
H15K
H18.5K
H22K
H30K
H37K
H45K
H55K
(Unit: mm)
Mass
(kg)
Less than D
H
W
(Note) 1.Be sure to remove the jumper across
terminals P/+ - P1 of the inverter. (A
failure to do so will produce no power
factor im proving eff ect)
2. The wiring length between the reactor and
inverter should be within 5m.
3. The size of the cables used should be equal
to or larger than that of the power supply
cables (R/L1, S/L2, T/L3).
4. Make selection according to the motor
capacity.
(When the inverter c apacity is larger than
the motor capacity, make selection
according to the motor capacity)
5. Power factor improving reactor (FR-BEL)
can be used.
Power factor improving effect
FR-BEL : approx. 95%
FR-HEL : approx. 93%
51
Page 51
Name (type)Specifications, Structure, etc.
r
Outline dimension
FR-BSF01FR-BLF
Line noise filter
FR-BSF01...for small
capacities
FR-BLF
Brake unit
BU-(H)
Electrical-discharge
resistor GZG type
GRZG type
110
95
2-
φ
5
22.5
65
33
65
4.5
A brake unit is an option that fully enhances the regenerative braking capability of the inverter, and should be used with an electrical-discharge resistor.
Brake units should be selected according to the required braking torque.
Brake unit selection table
Motor(kW)
Braking
Vol tage
torque
50%30sBU-1500BU-3700BU-7.5KBU-15K2×BU-15K3×BU-15K
200V
100%30s
output
50%30s*BU-H7.5KB U-H15KBU-H30K2×BU-H30K
100%30s*BU-H7.5KBU-H15KBU-H30K2×BU-H30K3×BU-H30K
400V
output
* The inverter of 1.5K or less with 400V output can not be used in combination with a brake unit.
To use in combination with a brake unit, use the inverter of 2.2K or more.
0.751.52.23.75.57.5111518.52230374555
BU-
BU-
1500
3700
Combination of brake unit and electrical discharge resistor
Brake unitResistor typeCable (P, N)
Vol ta ge
BU-1500GZG300W-50Ω(one)
BU-3700
BU-7.5K
200V output
BU-15K
GRZG200-10Ω
(three in series)
GRZG300-5Ω
(four in series)
GRZG400-2Ω
(six in series)
Brake unit
31.5
φ
7
130
35
2mm
2mm
3.5mm
3.5mm
160
180
Vol ta ge
2
2
400V
2
2
output
2.380
BU-7.5KBU-15K2×BU-15K3×BU-15K
Discharge resistor
MCCB
Power
supply
7
Line noise filter
(Note) 1. Each phase should be wound at least 3
times (4T, 4 turns) in the same direction.
(The greater the number of turns, the more
efficient.)
2. When the thickness of the wire prevents
winding, use at least 4 in series and ensure
that the current passes through each phase
in the same direction.
3. Can be used on the output side in the same
way as the input side.
4. Please use FR-BSF01 for inverters with
small capacities of 3.7K or less. Thick wires
(38mm2 or more) can not be used. In such
cases, use the FR-BLF.
4×
BU-15K5×BU-15K6×BU-15K7×BU-15K
Brake unitResistor typeCable (P, N)
BU-H7.5K
BU-H15K
BU-H30K
GRZG200-10Ω
(six in series)
GRZG300-5Ω
(eight in series)
GRZG400-2Ω
(twelve in series)
Inverte
R/L1
S/L2
T/L3
2mm
3.5mm
3.5mm
BU-15K
4×BU-
H30K
2
2
2
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Diagram
Explanation
Terminal Connection
4×
Terminal Specification
Panel
Operation
List
Parameter
of
Parameters
Explanations
Functions
Protective
H
W
W
BU-1500, 3700, 7.5K, 15K100 128 240
BU-H7.5K, H15K, H30K160 145 240
(Note) 1. Connect so that the terminal symbols are the same for both inverter and brake unit. Incorrect connection will damage the inverter.
2. Minimize the cable length between the inverter and brake unit and between the discharging resistor and brake unit. Use a twisted cable whe n
the wiring length exceeds 2m.
(If twisted cables are used, the wiring length should be within 5m.)
Handling precautions
1. The thermal relay in the brake unit will trip if the rated torque is continuously output. After a trip, reset the inverter and increase its deceleration time
seting.
2. The maximum temperature rise of the discharging resistor is 100 °C. Use heat-resistant wires and wire to avoid contact with resistors.
The brake unit and resistor unit are options that will fully exhibit the regenerative braking capability of the inverter and are always used as a set.
There are six different brake units as in the following table, from which make selection according to the necessary braking torque and deceleration
time.
The brake unit is equipped with a seven-segment LED that displays the duty (%ED) and alarm.
Brake unit selection table
Brake unit
FR-BU-(H)K
Resistor unit
FR-BR-(H)K
%ED at short-time rating when braking torque is 100%
(Note) 1. The temperature rise of the resistor unit is about a
maximum of 100°C. Therefore, use heat-resistant wires
(such as glass wires).
*3
ON
MC
TH1
TH2
OFF
HA
HB
HC
Inverter
P/+
N/-
Inverter
P/+
N/-
*3. Minimize the cable length between the inverter and brake
unit and the resistor unit and brake unit. Use a twisted
cable when the wiring length exceeds 5m. (If twisted
wires are used, the distance should be within 10m.) Use
the wires of the above recommended size or larger.
FR-BU
P/+ P/+P
PRN/-
Within
5m
TwistTwist
Within 10m
FR-BU
P/+ P/+P
Within
5m
PRN/-
Brake unit
FR-BR
PR
Within 10m
FR-BR
PR
53
Page 53
Name (type)Specifications, Structure, etc.
The brake unit and resistor unit are options that will fully exhibit the regenerative braking capability of the inverter. Use them as a set.
There are six different brake units as in the following table, from which make selection according to the deceleration time.
When the brake unit duty (%ED) excess and an alarm occur, errors appear in the inverter.
Brake unit selection table
Brake unit
MT-BU5-(H)K
Resistor unit
MT-BR5-(H)K
%ED at short-time rating when braking torque is 100%
Motor Capacity
Inverter
MT-BU5-55K
2
0
0
V
M T - B U 5 - 1 1 0 K2 0151 0------ ------------------ ------------
(Caution 1) Be sure to select the well-ventilated place for installa-
(Caution 2) The temperature rise of the discharging resistor is
(Caution 3) The temperature of the resistor unit abnormally
* The resistor unit is provided with a thermostat (a contact) as
overheat protection. If this protective device is activated under
normal operation, it is assumed that the deceleration time is too
short. In such a case, increase the deceleration time setting of
the inverter.
85
MT-BU5-
H220K
MT-BU5-
H280K
MT-BU5-
H375K
tion of the resistor unit. Ventilation is necessary when
installing the resistor in a place, e.g. enclosure, where
heat is not well diffused.
300deg. Therefore, wire the cable so as not to touch
the resistor. In addition, separate the parts with low
heat resistance and the resistor by at least 40 to
50cm.
increases if the brake unit is operated exceeding the
specified duty. Since the resistor unit may result in
overheat if the temperature of the brake unit is left
unchanged, switch off the inverter.
The wiring length should be 10m
maximum when wires are twisted
and 5m maximum when wires are
not twisted.
IM
P
PR
P
PR
Brake unit
MT-BU5
TH1TH2
P
PR
P
PR
Resistor unit
MT-BR5
(Caution 1) For wiring of the brake unit and inverter, use
(Caution 2) The brake unit which uses multiple resistor
an accessory cable supplied with the brake
unit. Connect the main circuit cable to the terminals P/+ and N/- and connect the control circuit cable to the connector (CN8) inside by
making cuts in the rubber bush at the top of
the inverter.
units has terminals equal to the number of
resistor units. Connect one resistor unit to one
pair of terminals (P, PR).
XY Z
Resistor unit
type
200V
MT-BR5-55K2.0Ω50kg
class
MT-BR5-
400V
class
H75K
Resistance
value
6.5Ω70kg
Brake unit
mass
Inverter
54
Page 54
Name (type)Specifications, Structure, etc.
Enables 100%-torque continuous regeneration to support continuous regenerative
operation for line control, etc.
Eliminates the need to use a brake unit with each inverter, reducing total space and total
cost.
Saves energy since regeneration energy is used for the other inverters and excess
energy is returned to the power supply.
Power regeneration
common converter
FR-CV-(H)K
High power factor
converter
FR-HC- (H)K
Connection example
Dedicated stand-alone
reactor (FR-CVL)
MC1
MCCB
Three-phase
AC power
supply
*1. Remove the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 of the inverter, and
connect the control circuit power supply across terminals R1/L11-S1/L21. Always keep
the power input terminals R/L1, S/L2, T/L3 open. Incorrect connection will damage the
inverter. Opposite polarity of terminals N/-, P/+ will damage the inverter.
*2. Do not insert an NFB between the terminals P/+-N/- (between P/L+-P/+, between N/
L--N/-).
*3. Assign the terminal for X10 signal using any of Pr. 178 to Pr. 189 (input terminal
function selection).
*4. Be sure to connect the power supply and terminals R/L11, S/L21, T/MC1. If the inverter is
operated without connection, the power regeneration common converter will be damaged.
Substantially suppresses power harmonics to realize the equivalent
capacity conversion coefficient K5=0 in the "Harmonic suppression
guideline for specific consumers".
R/L11
S/L21
T/L31
R2/L12
S2/L22
T2/L32
FR-CV type
Power regeneration
common converter
R2/L1
S2/L2
T2/L3
R/L11
S/L21
*4
RDYA
T/MC1
RDYB
Specifications
Inverter Type
FR-HC
Applied inverter capacity (*1)
Rated input voltage/
frequency
7.5K15K30K55KH7.5K H15KH30KH55K
3.7K to 7.5K 7.5K to 15K 15 K to 30K 30K to 55K 3.7K to 7 .5K 7.5K to 15K 15K t o 30K 30K to 55K
For the FR-F700 series (75K or more) inverter, the motor voltage and current can be made to nearly sine wave shaped by providing a sine wave filter
on the output side.
1) Low noise
2) Surgeless
3) Motor loss reduction (use of standard motor)
Application condition
The following conditions have to be satisfied to install the sine wave filter.
1) Change the Pr. 72 setting to "25". (The initial value is "2".)
The carrier frequency changes to 2.5KHz. (The sine wave filter is designed on condition that the carrier frequency is 2.5KHz. Be sure to change
the setting properly.) If the inverter is operated with Pr.72 set to other than "25", the inverter and sine wave filter may be damaged.
2) The sine wave filter can be used only for 60 Hz or less inverter frequency.
Note that the filter can not be used for the higher frequency operation than this. (Otherwise the filter loss will increase. )
3) Use the inverter with capacity one rank higher. *2
4) Install an external thermal relay of the motor.
Sine wave filter
MT-BSL-(H)K
MT-BSC-(H)K
Circuit configuration and connection
FR-F700
Inverter
(Carrier 2.5kHz)
+
0
Inverter output
voltage
wave form
Reactor for sine wave filter Capacitor for sine wave filter
For a capacitor cable, use a cable
with size larger than indicated in the
table below "recommended cable
size ".
Rating plate
Terminal H
WZVYU
X
C
B
A
F
capacity
200V
class
400V
class
voltage
current
IM
Motor
Wave form at a
motor terminal
*1 For the 2 ×, connect capacitors in parallel as in the connection
*2 If the rated motor current × (1.05 to 1.1) is less than 80% of the
D
E
Mass
(kg)
200V
class
400V
class
* Leave more than 25mm space between capacitors.
Recommended cable size
The cable sizes between the Inverter and MT-BSL and between the MTBSL and IM depend on U, V, W of "Peripheral devices list" (page 57)
The cable size to the MT-BSC is as table below.
MT-BSC-75KMT-BSC-90KMT-BSC-H75KMT-BSC-H110K
Motor
Reactor for filterCapacitor for filter
(kW)
75 MT-BSL-75K1×MT-BSC-75KFR-F720-90K
90 MT-BSL-90K1×MT-BSC-90KFR-F720-110K
75 MT-BSL-H75K1×MT-BSC-H75KFR-F740-90K
90 MT-BSL-H110K1×M T-BSC-H110KFR-F740-110K
110 MT-BSL-H110K1×MT-BSC-H110KFR-F740-132K
132 MT-BSL-H150K2×MT-BSC-H75KFR-F740-160K
160 MT-BSL-H220K2×MT-BSC-H110KFR-F740-185K
185 MT-BSL-H220K2×MT-BSC-H110KFR-F740-220K
220 MT-BSL-H220K2×MT-BSC-H110KFR-F740-250K
250 MT-BSL-H280K3×MT-BSC-H110KFR-F740-280K
280 MT-BSL-H280K3×MT-BSC-H110KFR-F740-315K
Inverter type
Applied Inverter
(*2)
diagram.
inverter rated current, an inverter with same kW with a motor
can be used.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to the Instruction Manual (basics).)
*3The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is used for emergency stop during motor driving, the electrical durability is 25
times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class AC-3 rated
current for the motor rated current.
*4Cable
For the 55K or less, the recommended cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature
of 75°C. Assumes that the ambient temperature is 50°C or less and the wiring distance is 20m or less.
For the 75K or more, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable) etc.) with continuous
maximum permissible temperature of 90°C or more. Assumes that the ambient temperature is 50°C or less and wiring is performed in an enclosure.
MCCBINV
MCCBINV
57
IM
IM
Page 57
Selection of rated sensitivity current of
r
W
earth (ground) leakage breaker
When using the earth leakage circuit breaker with the inverter
circuit, select its rated sensitivity current as follows,
independently of the PWM carrier frequency:
⋅ Breaker designed for harmonic and surge suppression
Ig1, Ig2 : Leakage currents in wire path during commercial power supply
Ign: Leakage current of inverter input side noise filter
Igm: Leakage current of motor during commercial power supply operation
Igi: Inverter unit leakage current
example
operation
Example of leakage current
per 1km during the commercial
power supply operation when
the CV cable is routed in
metal conduit
For " " connection, the amount of leakage current is 1/3
5.5mm
ELB
Noise
filter
5.5
2 ×
5m5.5mm
Inverter
8142230386080
Ig1Ign
Leakage current example of
Three-phase induction moto
during the commercial
power supply operation
(Totally-enclosed fan-cooled
type motor 400V60Hz)
2. 0
1. 0
0. 7
0. 5
0. 3
0. 2
100
2 ×
150
0. 1
leakage currents (mA)
60m
3φ
IM
400V
2.2k
Ig2Igm
Igi
1. 5 3.7
7. 5 152211373055
2. 2
Motor capacity (kW)
455.5 18. 5
(Note)1. Install the earth leakage breaker (ELB) on the input side
of the inverter.
2. In the connection earthed-neutral system, the
sensitivity current is purified against an earth (ground)
fault in the inverter output side. Earthing (Grounding)
must conform to the requirements of national and local
safety regulations and electrical codes. (JIS, NEC
section 250, IEC 536 class 1 and other applicable
standards)
Selection example (in the case of the left figure)
Leakage current
Ig1 (mA)
Leakage current
Ign (mA)
Leakage current Igi
(mA)
Leakage current
Ig2(mA)
Motor leakage
current Igm (mA)
Total leakage
current (mA)
Rated sensitivity
current (mA)(≥ Ig ×
10)
Breaker Designed for
Harmonic and Surge
Suppression
1
× 66 ×
31000m
0 (without noise filter)
Refer to the following table for the leakage current of the
1 (Without EMC filter)
inverter
1
× 66 ×
31000m
2.796.15
30100
5m
60m
0.36
Standard Breaker
= 0.11
= 1.32
Inverter leakage current (with and without EMC filter)
Input power conditions
(200V class : 220V/60Hz, 400V class : 440V/60Hz,
power supply unbalance within 3%)
EMC Filter
ON (mA)OFF (mA)
Phase
grounding
Earthed-neutral
system
Vol tag e
(V)
20022(1) *1
400301
40011
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
Outline
Drawings
Dimension
Diagram
Explanation
Terminal Connection
Terminal Specification
Panel
Operation
List
Parameter
of
Parameters
Explanations
Functions
Protective
* For the 200V class 0.75K and 1.5K, the EMC filter is always valid.
Precautions for use of the inverterPrecautions for selection
Safety Precautions
To operate the inverter correctly and safely, be sure to
read the "instruction manual" before starting operation.
This product has not been designed or manufactured
for use with any equipment or system operated under
life-threatening conditions.
Please contact our sales office when you are
considering using this product in special applications
such as passenger mobile, medical, aerospace,
nuclear, power or undersea relay equipment or system.
Although this product is manufactured under strict
quality control, safety devices should be installed when
a serious accident or loss is expected by a failure of
this product.
The load used should be a three-phase induction motor only.
Operation
A magnetic contactor (MC) provided on the primary
side should not be used to make frequent starts and
stops. It could cause the inverter to fail.
However, at this time, the motor cannot be brought to a
sudden stop. Hence, provide a mechanical stopping/
holding mechanism for the machine/equipment which
requires an emergency stop.
It will take time for the capacitor to discharge after
shutoff of the inverter power supply. When accessing
the inverter for inspection, wait for at least 10 minutes
after the power supply has been switched off, and
check to make sure that there are no residual voltage
using a tester or the like.
Wiring
Application of power to the output terminals (U, V, W) of
the inverter will damage the inverter. Therefore, fully
check the wiring and sequence to ensure that wiring is
correct, etc. before powering on.
The terminals P/+, P1, N/- are provided for connection of a
dedicated option. Connect only a dedicated option. Do not
short the frequency setting power supply terminal 10 and
common terminal 5 or the terminal PC and terminal SD.
Do not wire the maker-dedicated terminal PR/PX.
Installation
Avoid hostile environment where oil mist, fluff, dust particles,
etc. are suspended in the air, and install the inverter in a clean
place or put it in an ingress-protected "enclosed" panel. When
placing the inverter in a panel, determine the cooling system
and panel dimensions so that the ambient temperature of the
inverter is within the permissble value. (refer to page 8 for the
specified value)
Do not install the inverter on wood or other combustible
material as it will be hot locally.
Install the inverter in the vertical orientation.
Setting
The inverter can be operated as fast as a maximum of
400Hz by parameter setting. Therefore, incorrect
setting can cause a danger. Set the upper limit using
the maximum frequency limit setting function.
A setting higher than the initial value of DC injection
brake operation voltage or operation time can cause
motor overheat (electronic thermal relay trip).
Inverter capacity selection
When operating a special motor or more than one motor in
parallel with a single inverter, select the inverter capacity so
that 1.1 times the total rated motor current is less than the
rated output current of the inverter.
Starting torque of the motor
The start and acceleration characteristics of the motor
driven by the inverter are restricted by the overload
current rating of that inverter. Generally the torque
characteristic is less than when the motor is started by
a commercial power supply. When torque boost
adjustment or simple magnetic flux vector cannot
provide enough starting torque, select the inverter of
one rank higher capacity or increase the capacities of
both the motor and inverter.
Acceleration and deceleration times
The acceleration/deceleration time of the motor depends
on the motor-generated torque, load torque and moment
of inertia of the load (GD
When the current limit function or stall prevention function is
activated during acceleration/deceleration, increase the
acceleration/deceleration time as the actual time may
become longer.
To decrease the acceleration/deceleration time,
increase the torque boost value (setting of a too large
value may activate the stall prevention function at a
start, longer the acceleration time), use the simple
magnetic flux vector control, or increase the inverter
and motor capacities. To decrease the deceleration
time, it is necessary to add the brake unit (FR-BU, MTBU5), power regeneration common converter (FR-CV),
power regeneration unit (MT-RC) or a similar device to
absorb braking energy.
2
).
Power transfer mechanism
(gear, belt, chain, etc.)
When an oil-lubricated gear box, speed change gear or
similar device is used in the power transfer system,
note that continuous operation at low decelerated
speed only may deteriorate oil lubrication, causing
seizure. When performing fast operation at higher than
60Hz, fully note that such operation will cause strength
shortage due to the noise, life or centrifugal force of the
power transfer mechanism.
Instructions for overload operation
When performing operation of frequent start/stop of the
inverter, rise/fall in the temperature of the transistor
element of the inverter will repeat due to a continuous
flow of large current, shortening the life from thermal
fatigue. Since thermal fatigue is related to the amount
of current, the life can be increased by reducing bound
current, starting current, etc. Decreasing current may
increase the life. However, decreasing current will
result in insufficient torque and the inverter may not
start. Therefore, increase the inverter capacity to have
enough allowance for current.
59
Page 59
Precautions for Peripheral Device Selection
Installation and selection of moulded case
circuit breaker
Install a moulded case circuit breaker (MCCB) on the power
receiving side to protect the wiring of the inverter primary
side. For MCCB selection, refer to page 57 since it depends
on the inverter power supply side power factor (which
changes depending on the power supply voltage, output
frequency and load). Note that the operation characteristics
of the completely electromagnetic MCCB changes
according to the higher harmonic current, so a larger
capacity must be selected. (Check it in the data of the
corresponding breaker.) As an earth (ground) leakage
breaker, use the Mitsubishi earth (ground) leakage breaker
designed for harmonics and surges. (Refer to page 58.)
When installing a moulded case circuit breaker on the
secondary side of the inverter, contact each manufacturer
for selection of the moulded case circuit breaker.
Handling of primary side magnetic contactor
For operation via external terminal (terminal STF or STR
used), provide a primary side MC to prevent an accident
caused by a natural restart at power recovery after a power
failure, such as an instantaneous power failure, and to
ensure safety for maintenance work. Do not use this
magnetic contactor to make frequent starts and stops. (The
switching life of the inverter input circuit is about 1,000,000
times.) For parameter unit operation, an automatic restart
after power failure is not made and the MC cannot be used
to make a start. Note that the primary side MC can stop the
operation, but the regenerative brake specific to the inverter
does not operate and the motor coasts to stop.
Handling of secondary side magnetic contactor
Switch the magnetic contactor between the inverter and
motor only when both the inverter and motor are at a
stop. When the magnetic contactor is turned on while the
inverter is operating, overcurrent protection of the inverter
and such will activate. When an MC is provided to switch
to a commercial power supply, for example, it is
recommended to use commercial power supply-inverter
switchover operation Pr. 135 to 139.
Thermal relay installation
The inverter has an electronic thermal relay function to
protect the motor from overheating. However, when running
multiple motors with one inverter or operating a multi-pole
motor, provide a thermal relay (OCR) between the inverter
and motor. In this case, set the electronic thermal relay
function of the inverter to 0A. And for the setting of the
thermal relay, add the line-to-line leakage current (refer topage 61) to the current value on the motor rating plate.
For low-speed operation where the cooling capability of
the motor reduces, it is recommended to use a thermal
protector or thermistor-incorporated motor.
Secondary side measuring instrument
When the wiring length between the inverter and motor is
long, select the device that has enough current rating.
Otherwise the measuring instrument or CT which is used
especially for the 400V class small-capacity inverter may
generate heat due to the influence of line leakage current.
To measure and display the output voltage and output
current of the inverter, it is recommended to use the
terminal AM-5 output function of the inverter.
Disuse of power factor improving capacitor
(power capacitor)
The power factor improving capacitor and surge suppressor
on the inverter output side may be overheated or damaged by
the harmonic components of the inverter output. Also, since
an excessive current flows in the inverter to activate
overcurrent protection, do not install a capacitor or surge
suppressor. For power factor improvement, use the power
factor improving DC reactor (see page 51).
Wire thickness and wiring distance
When the wiring length between the inverter and motor is
long, use thick wires so that the voltage drop of the main
circuit cable is 2% or less especially at low frequency
output. (A selection example for the wiring distance of
20m is shown on page 57)
Especially at a long wiring distance, the maximum wiring
length should be within 500m since the overcurrent
protection function may be misactivated by the influence of a
charging current due to the stray capacitances of the wiring.
(The overall wiring length for connection of multiple motors
should be within the value in the table below.)
Pr. 72 PWM frequency
selection setting
(carrier frequency)
2300m500m500m
3 to 15200m300m500m
0.75K1.5K2.2K or more
Use the recommended connection cable when installing
the operation panel away from the inverter unit or when
connecting the parameter unit.
For remote operation via analog signal, wire the control
cable between the operation box or operation signal and
inverter within 30m and away from the power circuits
(main circuit and relay sequence circuit) to prevent
induction from other devices.
When using the external potentiometer instead of the
parameter unit to set the frequency, use a shielded or
twisted cable, and do not earth (ground) the shield, but
connect it to terminal 5 as shown below.
Frequency setting
potentiometer
(3)
(2)
(1)
Frequency setting
potentiometer
(3)
(2)
(1)
Twisted cable
Shielded cable
10 (10E)
2
5
10 (10E)
2
5
Earth (Ground)
When the inverter is run in the low acoustic noise mode,
more leakage currents occur than in the non-low acoustic
noise mode due to high-speed switching operation. Be
sure to use the inverter and motor after grounding
(earthing) them. In addition, always use the earth
(ground) terminal of the inverter to earth (ground) the
inverter. (Do not use the case and chassis)
When performing low-noise operation at higher carrier
frequency, electromagnetic noise tends to increase.
Therefore, refer to the following measure example and
consider taking the measures. Depending on the
installation condition, the inverter may be affected by
noise in a non-low noise (initial) status.
The noise level can be reduced by decreasing the
carrier frequency (Pr. 72).
As measures against AM radio broadcasting noise and
sensor malfunction, turning on the built-in noise
reduction filter produces an effect. (For the switching
method, refer to the instruction manual.)
As measures against induction noise from the power
cable of the inverter, an effect is produced by putting a
distance of 30cm (at least 10cm) or more and using a
twisted pair shielded cable as a signal cable. Do not
earth (ground) shield but connect it to signal common
cable.
Noise reduction examples
Install filter (FR-BLF,
Enclosure Decrease carrier frequency
Inverter
power
supply
Separate inverter and
power line by more than
30cm (at least 10cm)
from sensor circuit.
Control
power
supply
Do not earth (ground)
enclosure directly.
Do not earth (ground) control cable.
EMC
filter
Power
supply for
sensor
FR-
Inverter
BLF
Do not earth (ground) shield but
connect it to signal common cable.
FR-BSF01) on
inverter output side.
IM
Use 4-core cable for motor
power cable and use one cable
as earth (ground) cable.
Use a twisted pair shielded cable
Sensor
Motor
Line leakage current
Typ eInfluence and Measures
⋅ This leakage current flows via a static capacitance between
the inverter output cables.
⋅ The external thermal relay may be operated unnecessarily
by the harmonics of the leakage current.When the wiring
length is long (50m or more) for the 400V class smallcapacity model (7.5kW or less), the external thermal relay is
Influence
and
measures
Undesirable
current path
likely to operate unnecessarily because the ratio of the
leakage current to the rated motor current increases.
Countermeasures
⋅ Use Pr. 9 Electronic thermal O/L relay.
⋅ If the carrier frequency setting is high, decrease the Pr. 72
PWM frequency selection setting.
Note that motor noise increases. Select Pr. 240 Soft-PWM operation selection to make the sound inoffensive.
To ensure that the motor is protected against line-to-line
leakage currents, it is recommended to use a temperature
sensor to directly detect motor temperature.
MCCBMC
Power
supply
Inverter
Thermal relay
line-to-line static
capacitances
Line-to-line leakage currents path
Motor
IM
Leakage currents
Capacitances exist between the inverter I/O cables, other
cables and earth and in the motor, through which a
leakage current flows. Since its value depends on the
capacitances, carrier frequency, etc., low acoustic noise
operation at the increased carrier frequency of the
inverter will increase the leakage current. Therefore, take
the following measures. Select the earth leakage breaker
according to its rated sensitivity current, independently of
the carrier frequency setting.
To-earth (ground) leakage currents
Typ eInfluence and Measures
⋅ Leakage currents may flow not only into the inverter's own
line but also into the other lines through the earth (ground)
cable, etc.These leakage currents may operate earth
(ground) leakage circuit breakers and earth leakage relays
unnecessarily.
Influence
and
measures
Undesirable
current path
Countermeasures
⋅ If the carrier frequency setting is high , decrease the Pr. 72
PWM frequency selection setting.Note that motor noise increases.Select Pr. 240 Soft-PWM
operation selection to make the sound inoffensive.
⋅ By using earth leakage circuit breake rs designed for
harmonic and surge suppression in the inverter's own line
and other line, operation can be performed with the carrier
frequency kept high (with low noise).
Power
supply
NV1
Leakage
breaker
NV2
Leakage
breaker
Inverter
Motor
C
C
Motor
C
61
Page 61
Harmonic suppression guideline
Harmonic currents flow from the inverter to a power
receiving point via a power transformer.The harmonic
suppression guidelines were established to protect other
consumers from these outgoing harmonic currents.
The three-phase 200V input specifications 3.7kW or less
are previously covered by "Harmonic suppression
guideline for household appliances and general-purpose
products" and other models are covered by "Harmonic
suppression guideline for consumers who receive high
voltage or special high voltage". However, the generalpurpose inverter has been excluded from the target
products covered by "Harmonic suppression guideline for
household appliances and general-purpose products" in
January 2004 and all capacities of all models are now
target products of "Harmonic suppression guideline for
consumers who receive high voltage or special high
voltage".
⋅ Harmonic suppression guideline for consumers who
receive high voltage or special high voltage
This guideline sets forth the maximum values of
harmonic currents outgoing from a high-voltage or
especially high-voltage consumer who will install,
add or renew harmonic generating equipment. If any
of the maximum values is exceeded, this guideline
requires that consumer to take certain suppression
measures.
Users who use models other than the target models are
not covered by the guideline. However, we ask to connect
an AC reactor and a DC reactor as before.
For compliance to the "Harmonic suppression guideline
for consumers who receive high voltage or special high
voltage"
Input
Power
Supply
Three-
phase 200V
Three-
phase 400V
Tar ge t
Capacity
All
capacities
Measures
Make a judgment based on "Harmonic
suppression guideline for consumers who receive
high voltage or special high voltage" issued by the
Japanese Ministry of Economy, Trade and Industry
(formerly Ministry of International Trade and
Industry) in September 1994 and take measures if
necessary. For calculation method of power supply
harmonics, refer to materials below.
Reference materials
⋅ "Harmonic suppression measures of the
general-purpose inverter"
Jan., 2004 Japan Electrical Manufacturer's
Association
⋅ "Calculation method of harmonic current of the
general-purpose inverter used by specific
consumers"
JEM-TR201 (Revised in December 2003) :
Japan Electrical Manufacturer's Association
For compliance to "Harmonic suppression guideline of
the general-purpose inverter (input current of 20A or less)
for consumers other than specific consumers" published
by JEMA
Input
Power
Supply
Three-
phase 200V
Tar get
Capacity
3.7kW
or less
Measures
Connect the AC reactor or DC reactor
recommended in a catalog or an instruction manual.
Reference materials
⋅ "Harmonic suppression guideline of the general-
purpose inverter (input current of 20A or less)"
JEM-TR226 (Revised in December 2003) :
Japan Electrical Manufacturer's Association
Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converterd from
received power voltage) × operation ratio × harmonic content
⋅ Operation ratio: Operation ratio = actual load factor × operation time ratio
during 30 minutes
⋅ Harmonic content: Found in Table.
Table 1: Harmonic content (Values of the fundamental current is 100%)
Reactor5th 7th 11 th 13th 17th 19th 23rd 25th
Not used65418.57.74.33.12.61.8
Used (AC side)38 14.5 7.43.43.21.91.71.3
Used (DC side)30138.45.04.73.23.02.2
Used (AC, DC sides) 289.17.24.13.22.41.61.4
Table 2: Rated capacities and outgoing harmonic currents of inverter-driven motors
When the Mitsubishi standard squirrel-cage motor (SFJR, 4-pole) and inverter of the same capacity are used,
the torque characteristics are as shown below.
Output characteristics
60Hz torque reference
120
110
100
100
90
80
80
70
63
Continuous output torque (%)
Short time maximum torque (%)
50
45
30
20
10
0 1 3 620 3060
Short time maximum torque*1
Continuous operation torque
(*6 to 8)
220V
200V
120
Output
frequency (Hz)
*2*4*5*3
50Hz torque reference
*2*4*5*3
104
95
85
80
75
67
65
Continuous output torque (%)
Short time maximum torque (%)
53
45
38
2525
9
0 1 3 620 3050
*1 The 60Hz torque reference indicates that the rated torque of the motor running at
60Hz is 100%, and the 50Hz torque reference indicates that the rated torque of the
motor running at 50Hz is 100%
*2 Torque boost minimum (0%)
*3 Torque boost standard (initial value)
*4 Torque boost large (0.75 K... 10%, 1.5K to 3.7 K... 7%, 5.5K, 7.5K... 6%, 11K or more... 4%)
*5 Enabled for torque boost adjustment (3.7kW or less) or simple magnetic flux vector
control (slip compensation setting)
*6 A general-purpose, squirrel-cage motor must be used at lower continuous operating
torque in rated operation as shown in the chart since the cooling capability of the fan
installed on the rotor reduces at a lower speed. (Instantaneous torque occurs)
*7 200/220V 60Hz or 200V 50Hz in the chart indicates a motor torque standard (base
frequency set in Pr. 3 of the inverter) and is not the frequency of the power supply.
You can also set 60Hz in a 50Hz power supply area.
*8 As shown in the chart, the 60Hz torque reference setting allows you to use the motor
more efficiently as it can bring out the 100% torque of the motor continuously.
*9 This chart shows the characteristic available when a constant-torque load is selected
for load pattern selection (Pr. 14).
Short time maximum torque*1
Continuous operation torque
(*6 to 8)
120
Output
frequency (Hz)
Motor loss and temperature rise
The motor operated by the inverter has a limit on the
continuous operating torque since it is slightly higher in
temperature rise than the one operated by a commercial
power supply. At a low speed, reduce the output torque of
the motor since the cooling effect decreases. When
100% torque is needed continuously at low speed,
consider using a constant-torque motor.
Torque characteristic
The motor operated by the inverter may be less in motor
torque (especially starting torque) than the one driven by
the commercial power supply. It is necessary to fully
check the load torque characteristic of the machine.
Vibration
The machine-installed motor operated by the inverter
may be slightly greater in vibration than the one driven by
the commercial power supply. The possible causes of
vibration are as follows.
1.Vibration due to imbalance of the rotator itself including the
machine
2.Resonance due to the natural oscillation of the
mechanical system. Caution is required especially
when the machine used at constant speed is operated
at variable speed. The frequency jump function allows
resonance points to be avoided during operation.
(During acceleration/deceleration, the frequency within
the setting range is passed through.) An effect is also
produced if the PWM carrier frequency in Pr. 72 is
changed. When a two-pole motor is operated at higher
than 60Hz, caution should be taken since such
operation may cause abnormal vibration.
Inverter-driven 400V class motor
When driving a 400V class motor by the inverter, surge
voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor. In
such a case, consider taking the following measures.
(1) Rectifying the motor insulation
1. Use a "400V class inverter driven insulationenhanced motor".
Note: The four poles of the Mitsubishi standard
motor (SF-JR, SB-JR) have the 400V class
inverter driving insulation-enhanced feature.
2. For the dedicated motor such as the constant-torque
motor and low-vibration motor, use the "inverterdriven, dedicated motor".
(2) Suppressing the surge voltage on the inverter side
Connect a filter on the secondary side of the inverter to
suppress a surge voltage so that the terminal voltage of the
motor is 850V or less. When driving by the Mitsubishi
inverter, connect an optional surge voltage suppression filter
(FR-ASF-H) for the 55K or less and an optional sine wave
filter (MT-BSL, BSC) for the 75K or more on the inverter
output side.
Application to constant-torque motor
Since a constant-torque motor is greater in current than the
standard motor, the inverter capacity may be one rank higher.
For a constant-torque motor, decrease the torque boost setting.
Recommended value 0.75kW... 6%, 1.5 to 3.7kW... 4%,
5.5 to 7.5kW...3%, 11 to 37kW...2%,
45 to 55kW...1.5%, 75k or more...1%
When two or more motors are operated synchronously,
torque imbalance is likely to occur as motor slip is smaller
than that of the standard motor.
Application to special motors
Pole changing motor
As this motor differs in rated current from the standard
motor, confirm the maximum current of the motor and
select the inverter. Be sure to change the number of
poles after the motor has stopped. If the number of poles
is changed during rotation, the regenerative overvoltage
protecion circuit may be activated to cause an inverter
alarm, coasting the motor to a stop.
Geared motor
The continuous operating rotation range of this motor
changes depending on the lubrication system and maker.
Especially in the case of oil lubrication, continuous operation
in the low speed range only can cause gear seizure. For fast
operation at higher than 60Hz, please consult the maker.
Synchronous motor
This motor is not suitable for applications of large load
variation or impact, where out-of-sync is likely to occur.
Please contact us when using this motor because its starting
current and rated current are greater than those of the
standard motor and will not rotate stably at low speed.
63
Page 63
Main Differences and Compatibilities with the FR-F500(L) Series
FR-F740-0.75K to 3.7K, 7.5K, 22K, 37K to 55K are compatible in mounting dimensions
For other capacities, an optional intercompatibility attachment (FR-AAT) is necessary.
Dedicated plug-in option (not compatible)
(When the torque boost value of the FR-F500 series
used was the initial value, it is not necessary to change
the torque boost value from the initial value when
replacing with the FR-F700 series.)
User group (16) only
Setting methods were partially changed
(Pr. 160, Pr. 172 to Pr. 173)
"User initial value setting" (Pr. 199) was cleared
Substitutable with the copy function of the operation
panel (FR-DU07)
DC injection brake function with terminal was cleared
Start in reverse rotation is possible with flying start
function (frequency search of automatic restart after
instantaneous power failure function)
Setting is not necessary
(Pr. 240 settings "10" and "11" were cleared)
Function was cleared
For deceleration time, overvoltage alarm can be avoided
with regeneration avoidance function (Pr. 882 to Pr. 885).
Automatic torque boost was cleared because of addition
of "Simple magnetic flux vector" (Pr. 80)
Removable terminal block
Priority compatibility (Terminal block of the F500 can be
mounted)
FR-DU07
FR-DU04 unavailable (Partly restricted when the FR-
Note that an installation period of less than one year after installation in your company or your customer’s premises or a
period of less than18 months (counted from the date of production) after shipment from our company, whichever is
shorter, is selected.
[Coverage]
(1) Diagnosis of failure
As a general rule, diagnosis of failure is done on site by the customer.
However, Mitsubishi or Mitsubishi service network can perform this service for an agreed upon fee upon the
customer’s request.
There will be no charges if the cause of the breakdown is found to be the fault of Mitsubishi.
(2) Breakdown repairs
There will be a charge for breakdown repairs, exchange replacements and on site visits for the following four
conditions, otherwise there will be a charge.
1) Breakdowns due to improper storage, handling, careless accident, software or hardware design by the
customer.
2) Breakdowns due to modifications of the product without the consent of the manufacturer.
3) Breakdowns resulting from using the product outside the specified specifications of the product.
4) Breakdowns that are outside the terms of warranty.
Since the above services are limited to Japan, diagnosis of failures, etc. are not performed abroad.
If you desire the after service abroad, please register with Mitsubishi. For details, consult us in advance.
2. Exclusion of chance loss from warranty liability
Regardless of the gratis warranty term, compensation to chance losses incurred to your company or your
customers by failures of Mitsubishi products and compensation for damages to products other than Mitsubishi
products and other services are not covered under warranty.
3. Repair period after production is discontinued
Mitsubishi shall accept product repairs for seven years after production of the product is discontinued.
4. Terms of delivery
In regard to the standard product, Mitsubishi shall deliver the standard product without application settings or
adjustments to the customer and Mitsubishi is not liable for on site adjustment or test run of the product.
65
Page 65
International FA center
FA Center in England
FA Center in Europe
FA Center in Beijing
FA Center in Tianjin
FA Center in Shanghai
FA Center in Hong Kong
FA Center
in Korea
FA Center in Taiwan
FA Center in North America
Features
savings?
Why energy
Peripheral Devices
Standard
Specifications
FA Center in ASEAN
• FA Center in North America
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway. Vernon Hills, IL60061
TEL. +1-847-478-2100FAX. +1-847-478-2396
Mitsubishi Electric Automation Korea Co.,Ltd
DongSeo Game Channel BLD. 2F 660-11, DeungChon- Dong,
Kangseo-ku, Seoul, 157-030 Korea
TEL. +82-2-3660-9607FAX. +82-2-3663-0475
• FA Center in Shanghai
Mitsubishi Electric Automation(Shanghai)Ltd.
2F Block 5 Building, Automation Instrumentation Plaza, 103 Cao
Bao Rd., Shanghai 200233
TEL. +86-21-6484-9360FAX. +86-21-6484-9361
• FA Center in ASEAN
Mitsubishi Electric Asia Pte, Ltd.(Factory Automation Center )
307 Alexandra road #05-01/02 Mitsubishi Electric Building
Singapore 159943
TEL. +65-6473-2308FAX. +65-6476-7439
• FA Center in Hong Kong
Mitsubishi Electric Automation (Hong Kong) Ltd. FA Division
10/F., Manulife Tower, 169 Electric Road,North Point,Hong Kong
TEL.+852-2887-8870FAX. +852-2887-7984
Mitsubishi Electric Automation (Shanghai) Ltd. Beijing Office
Unit 917-918,9/F Office Tower1,Henderson Center,18
Jianguomennei Dajie,Dongcheng District,Beijing 100005
TEL. +86-10-6518-8830FAX. +86-10-6518-8030
• FA Center in Tianjin
Mitsubishi Electric Automation (Shanghai) Ltd.Tianjin Office
Room No. 909,Great Ocean Building ,No.200 Shi Zilin
Avenue,Hebei District,Tianjin 300143
TEL +86-22-2635-9090FAX. +86-22-2635-9050
• FA Center in Europe
Mitsubishi Electric Europe B.V. German Branch
Gothaer Strasse 8, D-40880Ratingen, Germany
TEL. +49-2102-486-0FAX. +49-2102-486-7170
• FA Center in England
Mitsubishi Electric Europe, B.V.UK Branch (Customer
Technology Centre)
Travellers Lane, Hatfield, Herts. AL10 8XB, UK
TEL. +44-1707-276100FAX. +44-1707-278992
66
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.