1. General description ............................................................................. 1
2. Installation and wiring ......................................................................... 2
3. Example of safety system configuration ........................................... 5
4. Test and checking failure .................................................................... 8
Compliance with the EU Machinery Directive – Functional Safety
DANGER
Any misuse of safety function could lead to personal injury or death, property damage, or economic loss.
To ensure that the system complies fully with requirement of safety, make a system-level risk assessment.
Mitsubishi Electric Co. cannot assume responsibility for any system to comply with safety directive.
ATTENTION
The information of this manual is merely a guide for proper installation.
Mitsubishi Electric Co. cannot assume responsibility for the compliance or the noncompliance to any code,
national, local or otherwise for the proper installation of this equipment.
A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
DANGER
To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before
performing any work on the drive. Measure the DC bus voltage at the P(+) and N(-) terminals or test points
(refer to your drive’s User Manual for locations and discharging time). The voltage must be zero.
DANGER
The safety stop function do not isolate electrically between drive and motor. To avoid an electric shock
hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before
performing any work on the motor (refer to your drive’s User Manual for discharging time).
ATTENTION
If you are using a FR-D740-EC or FR-D740-CHT with serial number shown below, safety function does not
work according to safety standard. In such case please contact your sales person.
<Europe model : suffixed with ‘-EC’>
D740-012 to 080–EC : Axxxxx, Bxxxxx, Cxxxxx, Dxxxxx, Exxxx and Fxxxxx
D740-120 to 160–EC : Axxxxx, Bxxxxx, Cxxxxx and Dxxxxx
<China model : suffixed with ‘–CHT’>
D740-0.4K to 3.7K–CHT : Axxxxx, Bxxxxx, Cxxxxx, Dxxxxx,Exxxx and Fxxxxx
D740-5.5K to 7.5K–CHT : Axxxxx, Bxxxxx, Cxxxxx and Dxxxxx
1. General description
Features
Mitsubishi FR-D700 safety stop function prevents a drive from supplying rotational energy to motors.
Dual safety channels ‘S1’ and ‘S2’ cut off the gate-drive power for IGBT to turn off.
S2
FR-D700
S1
SC
CPU
Gate
Driver
Gate
Driver
Fig.1 FR-D700 safety stop function diagram
DANGER
The safety stop function doesn’t isolate electrically between drive and motor. To avoid an electric shock
hazard, disconnect power to the drive and verify that the voltage is zero before performing any work on the
motor (refer to your drive’s User Manual for discharging time).
Directives
Mitsubishi FR-D700 safety stop function meets the following directives and categories.
EN954-1 Category 3
IEC60204-1 Stop category 0
DANGER
The misuse of safety function leads to personal injury or death, property damage, or economic loss.
To ensure that the system complies fully with requirement of safety, make a system-level risk assessment.
Mitsubishi Electric Co. cannot assume responsibility for any system to comply with safety directive.
Input power
IGBTs
M
1
2. Installation and wiring
ATTENTION
The following information is merely a guide for proper installation.
Mitsubishi Electric Co. cannot assume responsibility for the compliance or the noncompliance to any code,
national, local or otherwise for the proper installation of this equipment.
A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
ATTENTION
Ensure the safety relay unit and the D700 unit is mounted closely in enclosure meeting IP54 and all
interconnection wiring is short and protected against open and short circuit faults.
Refer EN/ISO13849-2.
Installation
Mitsubishi FR-D700 safety stop function should be used under following condition and environment.
Table.1 The condition and environment for using safety stop function
Item Condition
Operation -10Cto+50C (non-freezing) Temperature
range
Ambient humidity 90%RH maximum (non-condensing)
Vibration 5.9m/s2 or less
Altitude maximum 1000m above sea level
Atmosphere Indoors (without corrosive gas, flammable gas, dust and dirt etc.)
Over voltage category II or less
Pollution degree II or less
Mounting wall mounting / vertical orientation
In order to meet safety stop, an approved safety relay unit to EN954-1 safety category 3 or better shall be used in
conjunction with D700 as shown in example1,2.
In addition, all other components with in the safety stop loop shall be ‘safety approved’ types.
To avoid an electric shock hazard, insert the magnetic contactor (MC) between power source and drive.
Open the contact of MC and keep away from drive for discharging time (refer to your drive’s User Manual
for information) before performing any work on the drive.
And verify that the voltage on the bus capacitors has discharged before Measure the DC bus voltage at the
P(+) and N(-) terminals or test points (refer to your drive’s User Manual for locations). The voltage must be
zero.
To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check
the correct function of the monitor signal. This test shall be carried out at system installation, any software changes,
parameterization changes, and/or at least once per year.
Refer to ‘4. Test and checking failure’.
Storage -20Cto+65C
ATTENTION
DANGER
ATTENTION
2
Wiring
The safety related terminals are described in Table.2 and Table.3
Table.2 The safety related terminals
Terminal
Symbol
S1
S2
SO
SC
RUN
SE
A,C
SD
For input of safety stop channel1.
S1-SC is
Open: In safety stop mode.
Short: Non safety stop mode.
For input of safety stop channel2.
S2-SC is
Open: In safety stop mode.
Short: Non safety stop mode.
As output for safety stop condition.
SO terminal type is ‘Open collector output’.
SO-SC is
OFF(Open) :Drive enabled
ON(Close) :Drive shutoff, no fault
Important: SO terminal should be used for monitoring safety stop
condition only. SO terminal cannot be used for safety function.
Common terminal for S1,S2,SOsignals.
*SC is connected terminal SD internally.
As output for failure detection and alarm. RUN terminal type is ‘Open
collector output’.
RUN-SE is
OFF(Open): Detect failure or Alarm.
ON(Close): No failure detected.
Attention: To use RUN terminal for monitor output of failure
detection, The parameter No.190 should be set 199
(Alarm output).
Note: This terminal can be used for alarm or to prevent restart only,
no other safety function.
Common terminal for safety RUN signal.
As output for failure detection. A,C terminal type is ‘Relay output’.
A-C is
OFF(Open): Detect failure or Alarm.
ON(Close): No failure detected.
Attention: To use A,C terminal for monitor output of failure
detection, The parameter No.192 should be set 199
(Alarm output).
Note: This terminal can be used for alarm or to prevent restart only,
no other safety function.
Signal ground
Description Rating
Input resistance:4.7kOhm
Current : 4 to 6 mA
(In case of shorted to SC)
Voltage : 21 to 26 V
(In case of open from SC)
Load: 24VDC/0.1A max.
Voltage drop: 3.4V max.
(In case of ‘ON’ state)
Load: 24VDC/0.1A max.
Voltage drop: 3.4V max.
(In case of ‘ON’ state)
Load: 30VDC/0.3A max.
Table.3 Truth table of Safety related signals
Input power S1-SC S2-SC Failure SO-SC RUN-SE or A-CDrive state
OFF - - - OFF(Open)OFF(Open) Drive shutoff (Safe state)
0.75 (combined 2 wire) AI TWIN 2 X 0,75-10GY
*Ferrules and tools are distributed by Phoenix Contact.
Jumper cable
The jumper cable between S1,S2 and SC terminal has been installed in the factory as shown in Fig.2.
Before connecting safety input wire to S1,S2 and SC terminal, remove this jumper cable.
AMAM
Fig.2. Short wire
4
3. Example of safety system configuration
Example 1
EM
START
STOP
STF
+24V
COM0 COM1
X0 X1
XS0 XS1 Z10 Z00 Z20
DC24V
Safety
Logic
Circuit
K1
K2
24G
MITSUBISHI MELSEC Safety relay unit
QS90SR2SN-Q
Z11 Z01 Z21
Fig.3 Safety system example 1 – STOP asynchronous with EM and fault detection through A-C output.
For safety stop, configure the wiring as shown in Fig.3 above.
Note: the above wiring is configured to prevent restart in case of a fault.
The parameter No.192 must be set to ‘199’. This setting makes the A-C output to open in case of failure.
After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.
In the above configuration, after reset of EM switch, drive will be in safe-state until START switch is
pressed.
To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.
A
B
C
STF
STOP
PC
S1
S2
SC
RY
SOURCE
ATTENTION
CPU
Gate
Driver
FR-D700
Gate
Driver
RST
IGBTs
UVW
IM
5
EM
START
STOP
STF
STF
STOP
PC
S
RT
A
B
C
RY
SOURCE
CPU
Gate
Driver
Gate
Driver
IGBTs
DC24V
+24V
COM0 COM1
X0 X1
Safety
Logic
Circuit
24G
MITSUBISHI MELSEC Safety relay unit
QS90SR2SN-Q
XS0 XS1Z10 Z00 Z20
K1
K2
STOP
Z11 Z01 Z21
STF
*
*
STF
STOP
PC
S1
S2
SC
FR-D700
A
B
C
RY
SOURCE
CPU
Gate
Driver
Gate
Driver
U V W
IM
RTS
IGBTs
*
S1
*
S2
SC
FR-D700
U V W
IM
* When connecting multiple inverters, use a diode on the each safety input terminal to prevent a malfunction due to
undesirable current.
Fig.4 Example of multiple inverters connected to a safety relay unit
The number of inverters connected to a safety relay unit should be decided under considerations of output
terminal rating of a safety relay unit.
6
Example 2
RUN
DC24V
START
EM
+24V
COM0 COM1
X0 X1
Safety
Logic
Circuit
24G
MITSUBISHI MELSEC Safety relay unit
QS90SR2SN-Q
STF
STOP
XS0 XS1 Z10 Z00 Z20
K1
K2
Z11 Z01 Z21
SE
STF
STOP
S1
S2
SC
SD
SINK
CPU
Gate
Driver
FR-D700
Gate
Driver
Fig.5 Safety system example 2 – STOP synchronous with EM and fault detection through RUN output.
For safety stop, configure the wiring as shown in Fig.4 above.
Note: the above wiring is configured to prevent restart in case of a fault.
XS0 should be connected to RUN terminal and XS1 should be connected to SE, because polarity of XS0 is
positive, XS1 is negative.
The parameter No.190 must be set to ‘199’. This setting makes the RUN output to turn off in case of
failure.
After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.
In the above Fig.4, wired example2, in the event of reset of ‘safe-condition’ the motor rotation will not occur
until STF is pressed.
(for normal ‘non-safety’ STF/STOP function, please refer to your drive’s User Manual)
ATTENTION
To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.
RST
IGBTs
UVW
IM
7
4. Test and checking failure
ATTENTION
To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check
the correct function of the monitor signal. This test shall be carried out at system installation, any software changes,
parameterization changes, and/or at least once per year.
I/O status and failure
FR-D700 safety related I/O status obeys the following truth table.
Table.5 Truth table of Safety related signals
Input power S1-SC S2-SC Failure SO-SC RUN-SE or A-CDrive state
OFF - - - OFF(Open)OFF(Open) Drive shutoff (Safe state)
Short Open DetectedOFF(Open)OFF(Open) Drive shutoff (Safe state)
Open Short Detected OFF(Open)OFF(Open) Drive shutoff (Safe state)
In case of diagnostic or functionality test, check the I/O state whether it is same or not as Table.5.
Diagnostic
If the failure detected, FR-D700 output alarm signal and indicate ‘E.SAF’ at the display.
In case of FR-D700 output the alarm, please take following action.
(1) Check the S1-SC and S2-SC input signal logic is the same. If these are different logic, collect the input
signal and reset the FR-D700.
(2) Disconnect the wire from S1, S2, SC terminal, then reset or power-off and on, If the ‘SA’ letter is
flashed up at display, there is failure in system except FR-D700. But, still ‘E.SAF’ is displayed and
alarm output, there is malfunction on FR-D700.
Self diagnostic test
FR-D700 does the self-diagnostic test on the power-ON.
If FR-D700 output alarm at power-ON, please take the action described in ‘Diagnostic’ at above.
Test procedure for functionality
As depicted ‘ATTENTION’ in above, the test for the functionality is important.
Please do the test following procedure.
(1) Please make each state of S1-SC and S2-SC depicted at Table.5.
(2) If there is any different state from Table.5, FR-D700 has some malfunction.
(3) If there is no different state from Table.5, check the systematic performance, such as, press the
Emergency switch, press the start/restart button at the failure detected (RUN-SE opened), and so on.
(4) Finally clear the error record of the FR-D700 (see the user manual how to clear the error record).
8
BCN-A211508-000-D
REVISIONS
Print Date Manual Number Revision
Aug. 2009 BCN-A211508-000-C First edition
Dec. 2009 BCN-A211508-000-D
Change
Example of Safety stop connection
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.