Before connecting or disconnecting any wires, ensure that all power supplies have been switched off and
all wires are potential-free to prevent equipment damage and avoid electrical shock.
Do not run wiring close to transformers or high frequency generating equipment. Complete and verify all
wiring connections before applying power to the controller to which the module is connected.
Wiring
Notes:
For a heat pump system with no heat elements, leave terminals “W1” and “W2” free.
For a heat pump system with one heat element, leave terminal “W2” free.
For system with one compressor, leave terminal “Y2” free.
RC-RH, - When using one transformer, RC,RH terminals must be shorted.
RCRHC
W1
B/O
W2TTGY1
Fan (0.5A)
Heat element 2 (0.5A)
Heat element 1 (0.5A)
External sensor (option)
Main supply 24VAC
External sensor Connection (option)
Important: The external sensor must be Meitav-tec type only!
Res. KΩ 115.8 100.9 88.1 77.1 67.7 59.6 52.5 46.4 41.2 36.6
Connecting the external sensor
Disconnect power to the thermostat.
Move switch 5 to ON position and switches 1 and 6 to OFF position.
Connect the temperature sensor to the T-T terminals.
Reconnect power to the thermostat.
Notes:
The wire length for the external sensor can be up to 100 feet (30 meters) with standard cable.
If the distance is greater than 100 feet the wire MUST be shielded.
The external sensor must be Meitav-tec type.
There is a wide range of sensors for different applications, duct, rooms, etc. There are also options for
averaging the temperature. For details please contact our technical line or visit our web site.
ON
123456
Temp °F 45 50 55 60 65 70 75 80 85 90
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
ETN24-SUPER-FP-PROG-F
Owner’s manual & Technnician Settings
RCRHC
W1
B/O
W2TTGY1
Compressor 1 (0.5A)
Fan (0.5A)
Heat element (0.5A)
Heat pump (0.5A)
External sensor (option)
Main supply 24VAC
System without heat pump
(heat elements only)
System with heat pump
Y2 Y2
Compressor 2 (0.5A)
Compressor 1 (0.5A)
Compressor 2 (0.5A)