It is recommended to mount the thermostat between 1.5 & 1.8 meters from the floor where possible.
Separate the base from the cover by pressing the tongue (pic.1).
Line the back panel up against the wall and drill the appropriate fixing holes (pic.3).
Insert screws so they extend approx. 3/16" (3 mm) from the wall. Align the back panel against these screws, pushing it forward, allowing it to slide downwards to lock into position.
Make electrical connections to terminals on the back panel. Refer to the “Wiring Connections” section.
Reconnect the quick connector.
Change the JUMPERS position according to the system configuration. Refer to the “Jumper Configuration” section.
Attach the cover to the base, first the two shafts and then the spring.
Connect 24Vac to the thermostat; verify that LCD display is ON.
Do not install battery before power is applied.
Remove battery from back panel by sliding it to the left and out from its white retaining clip and mount it in black holder on front panel; insert it from the top, gently pressing downwards until it snaps into place and is held under the top clip of the holder. The '+' engraved on battery should be visible (pic. 4).
Be careful - the top clip of the battery holder is fragile.
Reassemble front and back cover.
Connect at top first then at bottom.
Installation Instructions
Pic.3
Battery Ho lder
Back panel Front panel
+
Pic.4
Quick connector
Shafts
Pic.2
Spring tongue
Spring tongue
Pic.1
Wiring Connections
Terminal Function HC11 HC22 HC32 HP22 HP32
T0,T0
T1,T1
AUX
Y1
Y2
W1
W2
W3
G1
G2
AL,AL
Rc
Rh
C
14,15,16
Not in use
External sensor (option)
Not in use
Compressor 1
Compressor 2
Heat Element 1 / Heat Pump
Heat Element 2
Heat Element 3
Fan
Not in use
Not in use
24Vac Phase (red)
24Vac (jumpered to Rc terminal)
24Vac Common
Another IR Receiver (option)
-
-
+
-
H.E 1
-
-
+
-
-
+
+ +
-
-
+ +
H.E 1
+
-
+
-
-
+
+ +
-
-
+ +
H.E 1
+ + +
-
-
+
+ +
-
-
+
H.P
-
+
-
-
+
+ +
-
-
+ +
H.P
+
-
-
+
+ +
OPT
-
Not in use
+
Connect
Heat element 1
H.E 1
Heat Pump
H.P
Option
OPT
Jumpers Configuration
Disconnect power, remove battery and wait 5 minutes* before changing the jumpers position.
*No need to wait if the unit wasn’t connected to power (1
st
Install).
Important: When changing the jumpers configuration, all information stored in the memory will be lost including the weekly program.
HC Electric
JP6 JP7
OPEN
SHORTHC Oil/Gas
HP energized in HEAT
HP energized in COOL
OPEN
OPEN
SHORT
OPEN
SHORT
SHORT
Internal sensor
JP1
A Position
External sensor B Position
4 minutes delay
JP3
OPEN
No delay (for test only !) SHORT
HC / HP Configuration
Temperature Sensor
Compressor Delay
24 Hours
JP4
OPEN
12 Hours (AM/PM) SHORT
Clock Mode
Celsius
JP5
OPENFahrenheit
SHORT
Temperature Scale
Default from factory
JP3
JP4
JP5
JP6
JP7
JP1
A
B
External Sensor Connection
Installation Procedure
Disconnect power to the thermostat. Move JP1 to “B” position and connect the sensor to “T1” terminals. Reconnect power.
Important: The sensor must be MEITAV-TEC type.
NTC Sensor: Temperature ~ Resistance Characteristics
Temperature (oC)
Resistance (KΩ)
7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2
115.8 100.9 88.1 77.1 67.7 59.6 52.5 46.4 41.2 36.6
- -
+
+
OPT OPT OPT OPT
OPT OPT OPT OPT OPT
HP11
-
-
+
H.P
-
+
-
-
+
+ +
-
OPT
OPT
-
File: bdir-operating maual.vsd | Date: February 1, 2007 | Rev. 3 All rights reserved to Meitav-tec Ltd. © 2007
Page 2
Real Time Clock
BDIR – Owner’s Manual
Meitav-tec Ltd (Contel group) Tel: +972 (3) 962 6462 Fax: +972 (3) 962 6620 www.meitavtec.com - support@meitavtec.com
General
The BDIR thermostat can be controlled using an IR remote control.
This remote control unit is Infra-red; It must be pointed at the thermostat to operate. Every time you change a parameter in the Remote Control, you must send it to the thermostat by pressing the ON/SEND button.
When the thermostat receives the information it will beep.
In normal display, the LCD alternates between a real time clock and Set & Room Temperatures.
CLOCK
SUN
AM
SET TEMP
HEAT
LCD Screen
Real time clock
Set & Room
temperatures
On/Off & Send Information
Press the ON/SEND button to turn the thermostat ON and/or send information from the remote to the thermostat.
Press the OFF button to turn the thermostat OFF and/or send information from the remote to the thermostat.
Autofan On/Off
Press the FAN button to switch between:
AUTOFAN OFF………………......
The fan will work continuously.
AUTOFAN ON…………………....
The fan will only work when there is demand for COOL or HEAT.
Press the ON/SEND button to send information.
Mode
Press the MODE button to switch between:
COOL……………………………...
HEAT……………………………..
AUTO CHANGE-OVER………
FAN ONLY……………………….
Press the ON/SEND button to send information.
Temperature Set-Point
When remote control in HEAT mode:
Press the (+) or (-) buttons – “HEAT" & set-point
temperature will flash.
Using the (+) or (-) buttons adjust the set-
point temperature for heat.
Press the ON/SEND button to send Information.
When remote control in COOL mode:
Press the (+) or (-) buttons – “COOL" & set-point
temperature will flash.
Using the (+) or (-) buttons adjust the set-
point temperature for cool.
Press the ON/SEND button to send Information.
When remote control in AUTO CHANGE-OVER mode:
Press the (+) or (-) buttons – “COOL" & set-point
temperature will flash.
Using the (+) or (-) buttons adjust the set-
point temperature for cool.
Press the SELECT button – “HEAT" & set-point
temperature will flash.
Using the (+) or (-) buttons adjust the set-
point temperature for heat.
Press the ON/SEND button to send Information.
The controller keeps a safety differential of at least 1 degree between set-point temperature for cool and set­point temperature for heat (heat is always less than cool).
Weekly Program
The thermostat can be programmed with up to 12 different programs: Four different programs for the weekdays (Monday to Friday); Four different programs for Saturday and four different programs for Sunday (The daily programs are numbered 1, 2, 3 & 4).
Press & Hold the SELECT button to enter programming – the word “PROGRAM” will flash.
Use the SELECT button here to quickly switch between Weekdays, Saturday & Sunday.
Press the (+) button – “PROGRAM 1” & “START” will flash.
Use the SELECT button here to quickly switch between Programs 1, 2, 3 & 4.
Press the (+) button again – the hour will flash. Using the (+) and (-) buttons adjust the START TIME - HOURS for PROGRAM 1 (weekdays).
Press the SELECT button again - the minutes will flash Using the (+) and (-) buttons adjust the START TIME - MINUTES for PROGRAM 1 (weekdays).
Press the SELECT button again – “COOL” and set-point temperature will flash. Using the (+) and (-) buttons adjust the SET-POINT TEMPERATURE FOR COOL (11oC = OFF).
Press the SELECT button again – “HEAT” and set-point temperature will flash. Using the (+) and (-) buttons adjust the SET-POINT TEMPERATURE FOR HEAT.
Press the SELECT button again to set PROGRAM 2 and repeat the procedure.
Press the SELECT button – the words “CLOCK” &
“SET” will flash.
Press the (+) button – the hour will flash. Using the (+) and (-) buttons adjust the HOURS.
Press the SELECT button again - the minutes will flash. Using the (+) and (-) buttons adjust the MINUTES.
Press the SELECT button again - the day will flash. Using the (+) and (-) buttons adjust the DAY.
Press the SELECT button again to exit.
Programming notes:
Every time the word “SEND” flashes, press the ON/SEND button to send information to the thermostat.
When the icon flashes, use the (+) and (-) buttons to switch between:
Activate program……...…. Deactivate program & keep it in memory….
The display will automatically return to normal if no button is pressed for a few seconds.
To turn the thermostat OFF at a specific time, use one of the programs, adjust the time & change the set-point temperature for cool to be 11
o
C. The unit
will switch back on at the start of the next program.