meibes LogoFresh Compact Installation Manual

Page 1
Technical information for installation and operation
Freshwater Station LogoFresh Compact electronically controlled
E]aZ]kKqkl]e%L][`fac
Jaf_kljY¿])0%<%(,0*/?]ja[`k`Yaf%L]d&#,1 (!+,*1*/)+%(%>Yp/)+%-( ooo&e]aZ]k&\]%]%eYad2af^g8e]aZ]k&\]
PR 24002.123 31-03-2011 Subject to technical modifications
Page 2
Contents
Chapter Title Page
1. Safety instructions 2
2. Technical specifications 2
2.1 Performance characteristics 3
3. Equipment and functional description 4
4. Installation 5
4.1 Hydraulic connections 5
4.2 Electrical connections 5
5. Control system 6
5.1 Display description 6
5.2 Operating keys – description 6
5.3 Control menu structure 7
5.3.1 Explanation of menu items 8
5.3.2 Information menu 8
5.3.3 Programming menu 8
5.3.4 Manual operation menu 9
5.3.5 Basic setting menu 9
6. Initial operation and system calibration 11
6.1 Flushing and filling the system 11
6.2 Controller calibration 11
6.3 Calibration procedure 11
6.3.1 Selecting pump capacity 11
6.3.2 Characteristic curve calibration 11
6.3.3 Circulation adjustment 12
6.3.4 Detailed description of characteristic curve calibration 13
7. System examples of controller settings 14
7.1 Freshwater station with circulation in a time slot and 14 with tapping detection
7.2 Freshwater station with circulation only via 14 tapping detection
7.3 Freshwater station without circulation 14
7.4 Freshwater station with reheating and/or activation 15
7.5 Increasing the domestic hot water set temperature 15
7.6 Freshwater stations as cascade connection 16
7.6.1 Initial operation and system calibration of freshwater 16 cascade
7.7 Disinfecting the hot water and circulation pipes 17
8. Releasing operating level for specialist tradesmen 17
9. Trouble-shooting 18
10. Factory setting and personal setting 19
11. Diagrams 20
Page 3
1. Safety instructions
Q
The installation and initial operation of the freshwater station is only to be carried out by a specialist tradesman.
Q The necessary DIN and VDE provisions are to be
observed (e.g. DIN 4751, DIN 4753, DIN 1988 and VDE 0100)
Q The provisions of local energy supply companies are
to be observed
Q Improper installation as well as misuse of the
freshwater station will exclude any liability as regards guarantee claims
Please note:
Q Before operating on the control system and the
circulating pump, they are to be switched at zero potential as prescribed
Q In the event of a power supply interruption, the
preset values are retained
Q In the event of a power failure, the system clock
settings in the control system are retained for approx. 24 hours
Q A menu for basic settings is available which may only
be modified by a specialist tradesman. This ensures the technical functioning and security of the system!
Q All the relevant old as well as recently enforced
provisions and norms as well as provisions and norms not mentioned, but relevant for application in a particular case, are to be followed
Q The legal provisions relating to the prevention of
accidents are to be followed
2. Technical specifications
Heating connections 3/4“ female 3/4“ IG
Plumbing connections 3/4” female 3/4” IG
Heating operating pressure 3 bar
Plumbing operating pressure 6 bar
Maximum allowed temperature 110°C
Controller protection class IP 54
Supply voltage 230VAC / 50Hz
Dimensions (height/length/breadth) in mm 660 x 455 x 215
Page 4
2. Technical specifications
2.1 Performance characteristics
Heating
cold water
K
35 (10 45°C) 50 31 11 30 1350 0,24 0,15 0,12
35 (10 45°C) 55 28 17 42 1350 0,24 0,15 0,28
35 (10 45°C) 60 26 22 53 1350 0,24 0,15 0,46
35 (10 45°C) 65 25 26 62 1350 0,24 0,15 0,64
35 (10 45°C) 70 24 29 71 1350 0,24 0,15 0,80
35 (10 45°C) 75 23 33 80 1350 0,24 0,15 0,04
35 (10 45°C) 80 22 36 88 1350 0,24 0,15 1,25
Heating
cold water
K
40 (10 50°C) 55 33 12 33 1350 0,24 0,15 0,14
40 (10 50°C) 60 31 17 46 1350 0,24 0,15 0,28
40 (10 50°C) 65 29 20 57 1350 0,24 0,15 0,38
40 (10 50°C) 70 27 24 66 1350 0,24 0,15 0,55
40 (10 50°C) 75 26 27 76 1350 0,24 0,15 0,69
40 (10 50°C) 80 25 30 84 1350 0,24 0,15 0,86
Flow
temperature
primary
°C
Flow
temperature
primary
°C
Return
temperature
primary
°C
Return
temperature
primary
°C
Domestic hot
water drawn
amount*
l/min
Domestic hot
water drawn
amount*
l/min
Domestc
hot water
capacity
kW
Domestc
hot water
capacity
kW
Volumetric
flow
primary
l/h
Volumetric
flow
primary
l/h
Pressure loss
primary
bar
Pressure loss
primary
bar
Remaining
discharge
head
primary
bar
Remaining
discharge
head
primary
bar
Pressure loss
secundary
bar
Pressure loss
secundary
bar
Heating
cold water
K
50 (10 60°C) 65 40 11 39 1350 0,24 0,15 0,12
50 (10 60°C) 70 36 15 53 1350 0,24 0,15 0,22
50 (10 60°C) 75 33 19 64 1350 0,24 0,15 0,34
50 (10 60°C) 80 32 22 75 1350 0,24 0,15 0,46
Flow
temperature
primary
°C
Return
temperature
primary
°C
Domestic hot
water drawn
amount*
l/min
Domestc
hot water
capacity
kW
Volumetric
flow
primary
l/h
Pressure loss
primary
bar
Remaining
discharge
head
primary
bar
Pressure loss
secundary
* at a sufficient domestic water system pressure
Please note: For larger drawing amounts, several freshwater stations can be constructed as a cascade. (page 16)
bar
Page 5
3. Equipment and functional description
Q The freshwater station allows for a hygienic and
energy-saving preparation of warm water via a stainless steel plate heat exchanger. It provides fresh hot water for one to two apartment units. The source of supply is a storage tank with a variable tempera­ ture of 60 to 95°C. At very high storage tempera­ tures (up to 95°C) a temperature reduction of the heat transfer media is recommended by admixture. The primary pump P1 is controlled via block modulation in such a way that the desired hot water temperature is kept constant as much as possible. For the control system to calculate the necessary pump capacity, it uses the heat transfer media temperature on the primary side, the inlet tempera­ ture of the cold water and the circulation on the secondary side as well as the current flow.
Q In addition to the preparation of freshwater, the
circulation can also be activated. In the “basic setting” menu the circulation is switched ON or OFF.
Q For circulation, up to 3 time slots can be specified in
the “programming” menu.
Q For the stainless steel plate heat exchanger there
are three modes of operation besides the drawing of hot water: water temperature-cold, water temperature -hot
and water temperature-timed heating
(See 5.3.3).
Q
After-run
Should water temperature-cold be selected, it is possible to set the circulation pump at an after-run, to allow the stainless steel plate heat exchanger to cool down and to prevent calcification. The after-run function is however, only possible and meaningful outside the circulation time!
Q Activating the hot water controller and reheating
With the additional T5 sensor (not included in delivery), it is possible to put the control system in operation only after a specified buffer temperature has been attained. With the T5 sensor it is further­ more possible to activate a boiler for reheating via a potential-free contact. Both functions are deactiva­ ted in the factory setting.
Q Disinfection
With this function it is possible to disinfect the circulation pipes against the danger of legionella. This function is only activated when a circulation pipe is available and the circulation has been switched on.
Q Data logging
With a „data stick” all measured values and the status of pump outputs can be recorded for a specific time period. A special computer programme is used to analyse the measured values at the freshwater station manufacturer.
T1 = Domestic hot water T2 = Heat transfer media flow T3 = Cold water and circulation temperature T4 = Heat transfer media return T5 = Storage tank sensor for „reheating“ and release of the hot water controller and circulation P1 = Primary heat transfer pump P2 = Circulation pump DFZ = Flow rate metre
1 = Heat transfer unit 2 = Return flow preventer 3 = Control 4 = Shut-off valve 5 = Flow rate restrictor 3l 6 = Filling and draining tap
A = Flow heating B = Return heating C = Domestic hot water outlet D = Hot water circulation E = Cold water (domestic water)
Page 6
4. Installation
The freshwater station has been pre-assembled and
Q
pre-wired.
Q Installation should take place on a load-bearing dry
wall.
Q With a pre-formed insulating wall it is possible to
mount the freshwater station directly onto a storage tank (Ø 600mm) using connectable insulation wedges (not included in delivery)
Q The freshwater station should preferably be moun-
ted low so as to be at the same height as the cold area of the stratified storage tank!
Q The piping should be connected according to their
relevant function (see drawing).
Assembly drawing
ADC
65 65 63
50
Please note:
Q Safeguarding the cold water should be done
according to DIN 1988, i.e. with a safety group and if necessary, an expansion tank.
4.1 Hydraulic connections
Heat transfer media side Connection A: Flow heating 3/4“ female Connection B: Return heating 3/4“ female Plumbing Connection C: Domestic hot water outlet 3/4“ female Connection D: Hot water circulation 3/4“ female Connection E: Cold water (domestic water) 3/4“
female
4.2 Electrical connections
580
320
100
410
205
120
B
45
50
E
Wall distance to the centre lines of the connections: 82mm
Connectable insulation wedges for mounting the storage tank
Kindly observe the EVU (energy supply companies) provisions! To prevent the dry running of pumps, the freshwater station may only be switched on once the system has been filled and vented.
The freshwater station is cabled in working order when delivered. The connection at the electrical supply network 230 V/ 50 Hz AC takes place via the installed power supply cable. This circuit is to be secured with a 10 A line protector switch.
Loading capacity of the control outputs:
Triac outputs A1 and A2 for the pumps max. 1A 230 V AC Potential-free contact S1 (changeover contact) max. 4A 230 V AC1
Wiring diagram
Temperature sensor
Potential-free
switch outputs
Fuse
Outputs 230V/AC
Example storage tank mounting
Pump 1
Power supply
Pump 2
Boiler standards
Page 7
5. Control system
5.1 Display description
1 2 3 4
13 12 11 10
1 ,,Info” menu Display of all measured values and system states 2 ,,Programming” menu Contains programming values which can be ad­ justed by the end customer. 3 „Manual Mode“ menu Set/ reset the outputs, determination of the operating points 4 „Basic Setting“ menu Contains all set values,which can only be adjusted after
5
„Release“. 5 Main menus
6
6 Measuring point assignment 7 Value/ units
7
8
9
8 Additional information, e.g. temperature sensor 9 Status indicator 10 „OK“ symbol Confirmation of inputs/ value change/ value reset 11 „Important“ symbol Group error message for all faults 12 „Outputs“ symbol Indicates which switching outputs are active. 13 „Pump“ symbol Indicates that the controller is active.
5.2 Operating keys - description
key Function Description
„up“ „UP“ „+“
„down“ „Open“ „Down“ „-“
„Page left“ „Quit“ „Cancel“ „ESC“
„Page right“ „Select“ „Confirm“ „Enter“
QPage to the next menu QValue change: incremental increase in the displayed
value, if pressed continuously the values increase continuously
QIn the basic menu: Open a main menu QPage to the next menu QValue change: incremental reduction in the displayed value,
if pressed continuously the values decrease continuously
QPage to the left in the main menu QQuit a menu
QQuit a menu item QCancel a value change without saving QPage to the right in the main menu QSelect a menu item QConfirm a value change with save
Page 8
5. Control system
Shutdown 60°C
Flow min 4 l/min
Output min 7 %
Flow middle 8 l/min
Output middle 20 %
Flow max 25 l/min
Output max 76 %
Correction per 5K 10 %
Calibration Heating medium 75°C
Calibration T cold water 15°C
2)
Basic Setting
menu
Information
Softw. version
1.XX Controller On/Off
Pulse generator
Control parameters
Calibration Setpoint 50°C
Characteristic
Sensor T3 or T6
Activation temp 35-55°C 35°C
After run 0-300 s 60s
Circ. Run time 0-600 90s
Circ. Rest time 1-120 min 0 min
Circulation setpoint 10-50°C 40°C
1)
1)
curve
Heat exchanger
On/Off
Circulation
Activation hysteresis 3-10K 3K
1)
1)
1)
On/Off
Reheating
Off/On
Activation T5
Absolute or relative
Accumulator setpoint
6)
Factory
On/Off
Premixer
configuration
Off/On
1)
Release
For maintenance
and settings
5.3 Menu structure of the V1.54 controller
menu
Manual Mode
the menu
Programming
Output 1
heating
Heat exchanger
Cold, hot or timed
WT operating mode
Hot water setpoint 50°C
Scrolling
Output 2
Circulation
Time slot 1
Time slot 2
WT hysteresis 3K
WT setpoint 40°C
Select
Drinking water T1
Output 3
3)
Time slot 3
Confirm
Outputs
Whole test
or
Reheat
15 K spread
65°C SP setpoint
Hot water VL T2
calibration
Characteristic curve
6)
1s to 30s
Data logging
Cold water T3
Single or cyclical
recording Control
Hot water RL T4
Reset
calibration
Circulation
Time
4)
Accumulator T5
Time
C: 14.0 H: 40.5
P: %
D: 5.0 T: 75.0
Date
Within one minute after mains connection or executable using key combination. Access
Can be run with button combination: Basic Setting menu -> Release -> Select with right
Flow l/min
is automatically blocked after 60 minutes!
Only visible if Reheat is active.4) On visible if T5 activation in operation.5) Only visible if a data stick is plugged in.6) Only visible through button combination: Characteristic curve adjustment alternatively
2)
3)
click 2x -> Up, Down and Right button - press simultaneously > 2 s -> „Release On“
appears -> quit with left click.
7)
1)
7)
P1 % WW
Controlled variables
6,0 l/min kW WW
Status
P1: P2:
Only visible through button combination
7)
by hand
Flow status VL
Information menu
Quit
Tapped quantity
Off
Active 50= hot water control
Z – active = circulation
After run
Controller active
Active outputs
Page 9
5. Control system
5.3.1 Explanation of menu items
5.3.2 Information menu
In this menu all the measured values of the temperature sensor, volumetric flow metre as well as the control system (system conditions) are displayed. Status display: Active 50 = Control system on domestic hot water set temperature value of 50°C Z - active 4 = Control system on circulation set temperature value of 40°C After-run = After-run of the circulation pump for cooling down the stainless steel plate heat exchanger (See 5.3.5) Disinfection = Control system on disinfection temperature Off = No control system function active
5.3.3 Programming menu
The programming menu contains values which are to be set by the end customer.
Q Heat transfer unit
Hot water – set value 50°C, adjustment range 45°C to 60°C for domestic hot water. Should this value be increased, the 60°C temperature value of the safety shutdown should also be increased, by going in the basic setting menu, submenu „Controller“. A blending valve should in any event be installed on the freshwater station outlet! Water temperature – operating mode: cold, hot or timed heating.
Water temperature – cold1) No heat exchange media is added to the stainless steel plate heat exchanger after hot water has been drawn off. It remains at the lowest temperature level after drawing off. This results in a favourable control behaviour arising for the drawing off of hot water.
Water temperature – hot plate heat exchanger is continuously kept at a constant operating temperature. When there is a deviation lower than the water temperature set value minus hysteresis, the P1 is activated with a capacity of 25 % until the water temperature set value has been achieved. This happens provided that a tempe­ rature is measured at T2 or at the “reheating” option at T5 which is greater than that of the hold-warm temperature. Should this condition not be fulfilled at T2, the temperature is again requested after a resting period of one hour. Water temperature – timed heating duration of the time slot the stainless steel plate heat exchanger is kept warm.
1) 2)
The stainless steel
1) 2)
For the
Water temperature – set value
range 20°C to 50°C for the hold-warm temperature of the stainless steel plate heat exchanger for water temperature – hot and water temperature – timed heating. Water temperature – Hysteresis 3 K, adjustment range 1 K to 20 K for the water temperature set value. Only visible if water temperature = hot or water temperature = timed heating has been selected!
Note: The water temperature – hot function should be used if the buffer storage is located far from the freshwater station and the system is operated without circulation.
Hot water max. 5K (2 K – 10 K) Hot water min. 5K (2 K – 10 K)
Testing period 5 min (1 min – 30 min)
An error message is displayed when the tempera­ ture exceeds or is lower than the hot water set value. When the threshold values are exceeded or the temperature drops below these values, a fault is generated after the preset monitoring period, and output S2 is switched as a potential-free contact. The output is reset once the temperature is again within the temperature range or it can be reset in the information menu/error message upon actuation of the right key. This monitoring is only valid when drawing off takes place – not during circulation!
Q Time slot
There are tree time slots available to set the circulation. Should the switch-on and the switch-off time be set the same, this time slot is no longer active. For further circulation functions, see 5.3.3. The time slots are also used for the water tempera­ ture - timed heating. (See 5.3.3)
Q Reheating
This menu item is only visible once the reheating function has been activated in the basic setting menu. If „absolute value” has been selected, „65°C storage tank set value” will be displayed. This value is adjustable between 20°C and 90°C. If „relative value” is selected „15 K splay” is displayed here. This value is adjustable between 2 K and 50 K. For further information regarding functions, see points 5.3.5 and 7.4. Storage tank set value = buffer set value
Q Data logging
This menu is only visible if a data stick has been connected to the front side of the control system. Measured values can be recorded on this data stick. In a measurement interval of 1 second (factory setting) measured values for approx. 4.5 hours can be logged. The data can be analysed at the plant with special software.
Q Clock time
Submenu for setting the clock time, date and the day of the week.
2)
40°C, adjustment
Page 10
5. Control system
1)
Based on the physical fact that the existing heat energy in the heat transfer unit has to be controlled by the control system, short-term temperature fluctuations at the start of a hot water tapping cannot be ruled out completely. Favourable control behaviour is achieved with the water temperature – cold function, which results in very short or no reheating time!
2)
The plate heat exchanger is kept hot by the heat exchange media from the buffer. The heat exchange media can take on temperatures of more than 60°C. Please note that such temperatures can result in calcium oxide precipitation!
5.3.4 Manual operation menu
Q The output 1, output 2, output 3 and outputs
„overall test” can be switched on and off manually,
in order to check the functioning of the pumps.
Q Characteristic curve calibration
Here the regulation of the characteristic curve is determined during the initial operation. (See 6.3.2)
Q Circulation adjustment
In this menu item the circulation adjustment is carried out.(See 6.3.3)
5.3.5 Basic setting menu
This menu contains important technical information and parameters for controlling, which may be modified by a specialist tradesman. In order to modify values, the submenu “release” in the basic setting menu has to be activated. (See 8)
Q Informationen
Here information regarding the software and system version is given.
Q Controller ON/OFF
Amongst other things, this menu item contains the safety shutdown for a domestic hot water tempera­ ture of 60°C. Should this temperature be exceeded at T1, pump P1 switches off until the temperature drops to below 60°C. This value should be increased when the hot water – set value is increased. However, a blending valve should additionally be mounted on the domestic hot water outlet of the freshwater station. The other control parameters should not be adjusted!
Q Pulse generator
These values are used to adapt the flow rate
generator at the control system.
Q Characteristic curve
In this menu item the pre-determined operating points of the control system can be read.
3)
2)
2)
In this menu item the pre-determined operating points of the control system can be read. Likewise the default value for flow max. of the characteristic curve calibration can be modified. Should, for example, the 25l/mm for the characteristic curve at flow max. not be reached, the default value for flow max. can be lowered to 15l/mm. (See 6.3.2)
Q Heat transfer unit
After run Outside the circulation time and after a drawing off of hot water, it is possible to keep the circulation pump running afterwards. The stainless steel plate heat exchanger is cooled down and its decalcification is counteracted. The function of the after-run, from an energy point of view, is only meaningful and possible outside the circulation time!
Q Circulation ON/OFF
If this function has been activated, up to three time slots can be set in the „programming” menu. In the time slot, controlling is always based on the circulation temperature. If the time slot has ended, or drawing off takes place or the circulation temperature has been reached, the circulation switches off. It is attached to the circulation rest time. No circulation can be activated in the circulation rest time. To avoid the heat transfer media in the buffer from being mixed, the heat transfer media temperature is checked at the heat transfer media- flow- sensor T2 or with the option at T5 at the start of the circula­ tion process, to ensure that the heat transfer media temperature is greater than the circulation set temperature +2K. This happens at T2 with the following procedure: The heat transfer pump P1 runs for 5 minutes at minimal capacity. Should the circulation set temperature plus 2K not be attained after expiry of the 5 minute run time, the heat transfer pump P1 is switched off – and restarts the process again after a waiting period of one hour. Following this, the flashing message „error message flow temperature” will be seen on the display in the information menu.
Flow increase 5 K
In some cases (high temperature drops in circula­ tion capacity), the circulation return temperature is not reached. The set value of the circulation tempera­ ture (flow increase 5K) can be increased up to 20 K. The input is limited to the hot water set temperature value. Should the hot water set temperature be reduced, the flow increase value for circulation is also reduced!
Example: Circulation set = 35°C, hot water set = 50°C, flow Increase = 15 K possible Circulation set = 40°C, hot water set = 50°C, flow Increase = 10 K possible Circulation set = 40°C, hot water set = 45°C, flow Increase = 5 K possible
2)
Page 11
5. Control system
If a buffer sensor T5 is available as an option for the activation of the reheating function and its temperature is less than the circulation temperature + 2K, the circulation is then discontinued. As a result of the reheating function it is to be assumed that after reheating and for a conceivable period of time thereafter sufficient temperature is available in the buffer. Outside the active time slot, the circulation is always in the “pulse generated” mode, i.e. always when a drawing off of approx. 1 s has been carried out, the circulation pump is switched on for the programmed time in “circulation-running time” and the circulation is then also blocked from being reactivated for the preset “circulation-rest time” period.
Circulation running time = 300 s
From 0 – 600 s adjustable running time of the circulation pump.
Circulation rest time = 5 min
From 0 – 120 min adjustable blocking time for reactivating the circulation.
Circulation hot water set value = 40°C
From 10°C to 50°C adjustable temperature for circulation in the time slot. Sensor TF3 = select sensor T3 or T6 (optional) In the factory setting T3 is used for measuring the circulation temperature. However, an independent sensor T6 (optional) can also be used directly in the circulation pipes for this purpose. Option T5: With an additional sensor T5 (optional), which is installed in the buffer, two further functions can be activated.
Q Activation T5
If the activation T5 = on is selected, it is possible to only put the control system into operation after a specified buffer temperature has been attained. Factory setting = off Switch-on temperature = 35°C temperature (adjustment range 35°C to 55°C) Hysteresis = 3 K (adjustment range 3 K to 10 K)
Q Reheating ON/OFF
Optionally the additional „reheating” function can be activated. When there is a deviation lower than an adjustable set value for the buffer, this function is an external heat source which is activated to reheat the buffer until it reaches the set level. The requirement for this is that the heat source is actually able to supply the desired temperature level. For this purpose the contact S1 on the controller circuit board is used. This contact can be charged with 4 A 230 V AC. The set value for the storage temperature can be defined as an absolute value (fixed value e.g.: 65°C) or as a relative value.
Should the relative value be used, the set value for the buffer temperature is calculated from the programmed hot water – set temperature + the entered value for the „splay”. e.g.: hot water set temperature 50°C + splay 20 K = 70°C buffer temperature. Should the programmed or calculated set value deviate lower by 3 K, the external heat source is kept activated until the set value is reached again. The temperature values needed for this can be set in the programming menu, under the submenu “reheating”. (See 5.3.3)
Q Pre-mixer ON/OFF
As a rule, this selection is not active in this control system!
Q Disinfection
The “disinfection” function can be activated in the basic setting menu, but only if there is a circulation pipe available. The circulation return temperature is controlled, which is measured at the cold water sensor. This temperature must be attained for the preset disinfection time period. Short-term lower temperature deviations are corrected. In total, the actual time that the set temperature was attained, is counted. Should the flow temperature for the control system not be achieved, a corresponding error message is sent to the information menu after 30 minutes. During the disinfection of the hot water and circulation pipes, very high temperatures are achieved. There is therefore a danger of scalding! Qualified personnel should take the necessary precautions for the protection of persons and property!
Q Factory setting ON/OFF
Should the controller be set back to the original factory positions as on delivery, this menu item is to be activated.
Q Release
In order to „unlock“ the controller for different settings, the following should be done: Release by pressing the right key twice and “OFF” will flash. Press UP and DOWN and right key simultaneously for approx. 2s and release changes to „ON“. To subsequently leave the setting, press the left key.
The same operating sequence is used to block access to the controller. Alternatively, this takes place automatically after 60 minutes.
2)
This is executable within one minute after mains connection or by using the key combination. Access is automatically blocked after 60 minutes.
3)
Only possible to activate „release” by using the key combination in the menu. Access is automati­ cally blocked after 60 minutes.
10
Page 12
6. Initial operation and system calibration
6.1 Flushing and filling the system
Q The entire system should be flushed before filling. Q The flat-sealing connections of the freshwater station
should be checked for leakage and the connections should be tightened, if necessary. When tightening the connections, always use the appropriate tools to counter-resist!
Q Air which has accumulated in the heating system
should be removed by opening the vent screw.
Caution:
In doing so, pay attention to the system pressure and refill, if necessary.
6.2 Controller calibration
Why is it necessary to calibrate the controller?
In doing the controller calibration and the subsequent circulation adjustment, the values of the freshwater station is optimised and adapted to the local conditions. In the calibration menu you will be requested to draw hot water three times. In doing so, the operational points are determined for the control system and are independently taken over into the control system. The control system then operates on the characteristic curve so recorded. Under optimal conditions this process takes10 to 15 minutes. The subsequent circulation adjustment connected to this process, serves to log the volumetric flow of the circulation. Note: Please draw off hot water for a longer period before calibration so that stable temperature conditions for cold water and hot water can be set at the fresh­water station.
6.3 Calibration procedure
6.3.1 Selecting pump capacity
UPS15-60 pump stage I for drawn off amounts up to 15 litres UPS15-60 pump stage II for drawn off amounts up 40 litres
Operating at pump stage II is generally recommended for low buffer temperatures.
6.3.2 Characteristic curve calibration
A buffer temperature which lies above the domestic hot water temperature is necessary for the characteristic curve calibration. The relevant amounts are found at 2.1 Performance characteristics!
Determining the control system operating points
1. Select the “manual” menu
2. Select the “characteristic curve calibration” submenu
3. Select using the right key; „OFF“ flashes; Use upper key to go on “ON”; confirm with right key twice and start a 25 litre hot water tapping accor­ding to the menu navigation. After approx. three minutes you will be requested to reduce the hot water discharge volume to 8 litres. After a further approx. three minutes you will again be requested to reduce the hot water discharge volume (4 litres).
4. If thereafter the “characteristic curve calibration on” is displayed again, leave this submenu using the left key. The characteristic curve calibration is now complete and the values are independently logged into the control system.
1. Pump capacity
2. Characteristic curve calibration
3. Circulation adjustment
5. Should it not be possible to draw off a volume of 25l/min, the value for “flow max.” can be reduced to another value e.g. 15l/min. Additionally, a change into the “flow max” is required in the basic setting menu, submenu characteristic curve by using the “UP” or “DOWN” keys, and to select using the right key. The display 25l/min flashes and can be reduced by using the “DOWN” key. Thereafter, confirm this setting by pressing the right key twice.
11
Page 13
6. Initial operation and system calibration
6.3.3 Circulation adjustment
A circulation adjustment is to be undertaken if the freshwater station is fitted with a circulation pump and a circulation pipe is connected to it! For the controller to detect a withdrawal of water, the actual circulation cycle must be known as the flow rate is always measured by the sum of the hot water withdrawal and the overlaying circulation.
Information for a software update:
As of software version V 1.54 the 3 l/min flow rate restrictor can be left out.
A prerequisite for the calibration is that all hot water tapping points are closed.
Procedure to be followed:
Q select: manual menu
Q menu item „circulation adjustment“
Q select by using the right key,
„OFF“ flashes
Q using the „UP“ key change to „ON“
Q confirm twice using the right key
Q the message “flowing” is displayed
Q when the message „Circulation calibration
complete“ is displayed, measuring has been finished. The measured value is displayed and independently logged into the control system.
Q Leave the menu using the left key
12
Page 14
6. Initial operation and system calibration
6.3.4 Detailed description of characteristic curve calibration
1x Leave the info menu using the “escape” key
2x
flashes
5x
Characteristic
curve off calibrate
and then
1x
Determining the operating points of the control system
Q Manual operation menu Q Characteristic curve calibration submenu
Select the menu: manual operation
Select the menu: manual operation
Q select using right key, OFF flashes.
Characteristic
curve on calibrate
Withdrawal
starts
flashes
1x
2x
1x
Q Using the upper key, switch to On and
Q confirm twice with the right key.
Calibration procedure starts.
Kindly follow the menu guidance on the display. Consecutive drawn amounts of 25 litres, 8 litres and 4 litres are required. After the relevant operating points of the pump have been determined and independently logged into the control system, characteristic curve calibration “on” again appears on the display. Leave this submenu using the left key. The characteristic curve calibration is now complete.
13
Page 15
7. System examples
7.1 Freshwater station with circulation in a time-slot and with tapping detection outside the time slot
Q Initial operation and system calibration from point 6 Q Setting the time and date, point 5.3.3 Q Domestic hot Q set value e.g.: 50°C, point
water 5.3.3 and 5.3.5
Q Circulation Q Basic setting menu,
Circulation submenu = select “on”, point 5.3.5
Q In programming menu,
circulation submenu up to 3 select time slot, point 5.3.3
Q Circulation temperature 40°C,
for control in time slot, point 5.3.5
Q Circulation time e.g.: 60 s,
Circulation rest time.: e.g. 10 min, for controlling the circulation through tapping detection outside the time slot, point 5.3.5
Q Heat transfer unit Q WT = cold, point 5.3.3 Q Time lag Q e.g.: 20 s, point 5.3.5
7.3 Freshwater station without circulation
Q Initial operation and system calibration from point 6 Q Setting the time and date, point 5.3.3 Q Domestic hot Q set value e.g.: 50°C, point
water 5.3.3 and 5.3.5
Q Circulation Q Basic setting menu,
Circulation submenu = select “off”, point 5.3.5
Q Heat transfer unit Q WT = cold can be selected,
if the distance between the buffer and the freshwater station is not too great. After-run e.g.: 20 s, point 5.3.5
Q WT = hot can be selected,
if there is a great distance between the buffer and the freshwater station, and the comfort of the “rapid” hot water drawing has been attained. Set the after-run point 5.3.5 on nought, as no circulation pipe is available.
7.2 Freshwater station with circulation only via tapping detection
Q Initial operation and system calibration from point 6 Q Setting the time and date, point 5.3.3 Q Domestic hot Q set value e.g.: 50°C,
water point 5.3.3 and 5.3.5
Q Circulation Q Basic setting menu,
Circulation submenu = select “on”, point 5.3.5
Q In programming menu,
Circulation submenu is the start and stop times within each 3 time slots which are to be set at the same time e.g.: start 6h00 - stop 6h00 point 5.3.3
 Q Circulation time e.g.: 60 s,
Circulation rest time e.g.: 10 min, point 5.3.5
Q Heat transfer unit Q WT = cold, point 5.3.3 Q Time lag Q e.g.: 20 s, point 5.3.5
14
Page 16
7. System examples
7.4 Freshwater station with reheating option and/or activation
The freshwater station with or without circulation can be extended by two functions via an additional temperature sensor T5 (not included in delivery) in the buffer. These functions must be activated in the basic setting menu. Point 5.3.5 The temperature sensor T5 becomes visible in the information menu after activation.
1. A boiler must be requested to reheat the buffer.
For this a potential-free contact S1 on the control circuit board is used. This contact can be charged with 4 A 230 V AC. A description as well as the settings for the reheating option is found under point 5.3.5, reheating menu item.
2. The same temperature sensor T5 can be used to
specify the buffer temperature, from where the hot water regulation and the circulation are activated. This function makes sense if the buffer temperature could at some point take on unfavourably low values as a result of renewable energy sources, and if the freshwater station should not yet run at such low buffer temperatures. A description as well as the settings for the option activation can be found under point 5.3.5, Activation menu item.
re 2. Release the operating level for the specialist tradesmen in the basic setting menu. See point 7. In the programming menu, submenu controller, increase the menu item 60°C deactivation from 60°C to 70°C. To do this, the submenu controller must be selected by pressing the right key once until the bracket goes out. Then press the lower key once. 60°C activate will be displayed. Now select by pressing the right key once until the 60°C flashes. Using the upper key, increase to 70°C and confirm by pressing the right key twice. You have now increased the safety shutdown (scalding protection) of the control system to a higher value and must now re-install a blending valve on the hot water outlet!
re 3. Characteristic curve calibration see point 6.2 to
6.3.2
7.5 Increasing the domestic water set value
The following example is used to show what factors should be taken into account when the domestic hot water temperature is to be increased from 50°C to 60°C:
1. WW – set value increase
2. Increase the electronic safety shutdown and install a
blending valve.
3. Carry out a characteristic curve calibration!
re 1. In the programming menu, submenu heat transfer,
increase the hot water set value from 50°C to 60°C. To do this, select 50°C with the right key. Once 50°C flashes, the value can be increased to 60°C by using the upper key. Thereafter, confirm by pressing the right key twice.
15
Page 17
7. System examples
7.6 Freshwater station as cascade connection
Should larger volumes of hot water be needed, overflow valves allow for the interconnection of two or more freshwater stations as a cascade. Here, the service water circulation module can be left out for the second and other freshwater stations. The circulation is controlled only by the first freshwater station.
Basic circuit diagram:
Second station First station
Domestic water
hot
7.6.1 Initial operation and system calibration of the freshwater cascade
First station
Q Initial operation and system calibration from point 6 Q Setting the time and date, point 5.3.3 Q Domestic hot Q set value e.g.: 50°C, point
water 5.3.3 and 5.3.5
Q Circulation Q Basic setting menu,
Circulation submenu = select “on”, point 5.3.5 Q In programming menu, circulation submenu up to 3 select time slot, point 5.3.3 Q Circulation temperature 40°C, for control in time slot, point 5.3.5 Q Circulation time e.g.: 60 s, Circulation rest time.: e.g. 10 min, for controlling the circulation through tapping detection outside the time slot, point 5.3.5
Q Heat transfer unit Q WT = cold, point 5.3.3 Q Time lag Q e.g.: 20 s, point 5.3.5
Required accessories:
Overflow valve DN 25 for Cascade connection Adjustment range: 100 to 500 mbar Article no.: 69072.9
Domestic water
cold
Second station
Q Initial operation and system calibration:
The determined values of the characteristic curve calibration of the first station are taken over. These values are read in the first control system in the basic setting menu, characteristic curve submenu and in the same menu they are set in the second control system.
Q Setting the time and date, point 5.3.3 Q Domestic hot Q Set value e.g.: 50°C,
water point 5.3.3 and 5.3.5
Q Circulation off Q Heat transfer unit Q WT = cold, point 5.3.3 Q After-run Q e.g.: 20 s, point 5.3.5
Differential pressure-overflow valve
Hot water should be drawn off of e.g.: 35l/min. This domestic water volumetric flow can be read in the control system information menu of the first freshwater station. Set the differential pressure­overflow valve so that the second freshwater station starts operating (determination of opening pressure of the overflow valve). Loosen the locking screw at the differential pressure-overflow valve. Afterwards the opening pressure can be adjusted in stages by turning the hand wheel valve. The selected position should subsequently be checked at the locking screw to ensure it against accidental adjustment.
16
Page 18
7. System examples
7.7 Disinfecting the hot water and circulation pipes
During the disinfection of the hot water and circulation pipes, very high temperatures are generated. There is a danger of scalding! Qualified personnel should take the necessary precautions for the protection of persons and property!
Example for setting the control system:
1. Release the operating level for the specialist tradesmen in the basic setting menu.
2. In the basic setting menu, submenu disinfection, select “in”.
3. Set the hot water set value. Adjustment range 65 - 75°C
4. Select disinfection time (duration of disinfection) Adjustment range 0 - 60 minutes
5. Select the day, week day or daily.
6. Start time (0 - 24 hours)
This function should be deactivated after disinfection! The function is described in
5.3.5!
8. Releasing operating level for specialist
tradesmen!
Q
In the basic setting menu press the „down“ key downwards nine times until submenu release is attained [values].
Q Now press „right” key twice, this causes “off” to
flash.
Q Press the „up“ and „down“ and „right“ keys
simultaneously for approx. 2 s, release switches to “on”.
Q Thereafter leave the menu by using the “left” key.
The releasing of the operating level can be reset again in the same way. Access to the adjustable values is blocked automatically after 60 minutes!
17
Page 19
9. Trouble-shooting
The following is to be checked if the domestic hot water temperature is not reached:
Q System voltage (fuses) Q Buffer temperature Q Vent the freshwater station Q A temperature sensor interruption or a short circuit
is displayed in the information menu by a flashing general error message and is shown individually when requesting each sensor.
Q Carry out characteristic curve calibration, from
point 6.3.2.
Q Carry out a circulation adjustment, point 6.3.3. Q During a hot water withdrawal, the circulation pipe
becomes cold. Cause: The return flow preventer in the connecting nipple above the circulation pump can start leaking due to soiling in the cold water network.
Q Flow rate metre: To check this, a hot water tapping
is required and the flow in litres per minute read in the information menu. An intact flow rate metre should show a relatively constant value. Should fluctuations occur, check whether this comes from the domestic water network, for example in pressure increase systems
Q Set the freshwater station according to the system
examples.
Q A short time after drawing off hot water at the tap
(e.g.: washbasin) the hot water temperature drops sharply even though the control system displays e.g.: 50°C hot water temperature.
Q The return flow preventer should be checked in
the connecting nipple above the circulation pump to see if it leaks as a result of soiling in the cold water system and if cold water has been pressed into the circulation piping.
Q The circulation does not work: Q Carry out circulation adjustment! Q Check time slot! Q The temperature of the heat transfer media
in the buffer is too low. The circulation set temperature + 2 K is not being reached at T2 or at T5, if present. (see point 5.3.5 Circulation) Please ensure that there is a sufficient quantity of heat in the buffer! With option T5 „reheat buffer“, a type of boiler can be activated.
Q The pumps P1 and P2 run alternatively and the status
display in the information menu switches between active 50, after-run and off.
Q Carry out a circulation adjustment, point 6.3.3.
Q After several months of smooth running operation
the hot water capacity is no longer reached.
Q If a dirt filter has been installed in front of the
station, this should be cleaned.
Q Check return flow preventer. Q Vent the buffer and the freshwater station
18
Page 20
10. Factory setting and personal setting
Menu Submenu
Heat transfer unit
Circulation
Circulation
adjustment
Pulse generator 72 lmp. / litre
Characteristic curve
Heat transfer unit After - run 20 s
Circulation
Activation T5
Reheating On/Off Off
Pre-mixer On/Off Off
Disinfection On/Off Off
UPS 15-60
Pump stage 2
Factor
setting
Hot water set value 50°C
Water temperature (WT) operating mode hot / cold / timed heating
Hot water set value 40°C
Water temperature hysteresis 3 K
Hot water max 5 K
Hot water min -5 K
Test time 5 min
Time slot 1 Time slot 2 Time slot 3
Volumetric flow rate Circulation
Flow min 4 l/min
Capacity min 8 %
Flow middle 8 l/min
Capacity middle 20 %
Flow max 25 l/min
Capacity max 76 %
Correction 5 K 10 %
Heat transfer media adjustment 75°C
Temperature - cold water adjustment 15°C
Se value adjustment 50°C
On/Off on
Running time 90 s
Rest time 0 min
Set value 40°C
Flow increase circulation 5 K
Temperature sensor 3 or 6 TF3
On or Off Off
Temperature 35°C
Hysteresis 3 K
absolute or relative absolute
Hot water set value Off
Disinfection time 70°C
Start Monday
Start 1:00
cold
6:00 - 9:00 11:00 - 13:00 16:00 - 20:00
3 l
Personal
setting
19
Page 21
11. Diagrams
LogoFresh Freshwater Station Compact electronically controlled
Pressure loss [bar]
Volumetric current-pressure loss diagram
Primary side
hot water volume flow (I/h)
Characteristic curve Grundfos UPS 15-60
Kennlinie Grundfos UPS 15-60
20
Page 22
11. Diagrams
LogoFresh Freshwater Station Compact electronically controlled
Pressure loss [bar]
Volumetric current-pressure loss diagram
Secondary side
Domestic hot water drawing volume [l/h]
Domestic hot water drawing volume [l/h]
21
Page 23
22
Page 24
23
Loading...