Megger PFL22M1500, PFL22M1500INV User Manual

AVTMPFL22M
Rev 1
April 2011
User Guide
PFL22M1500
PFL22M1500INV
HIGH VOLTAGE EQUIPMENT
Read this entire manual before operating.
M
Valley Forge Corporate Center 2621 Van Buren Avenue Norristown, PA 19403-2329 U.S.A.
610-676-8500
www.megger.com
PFL22M1500-XX
PFL22M1500INV-XX
(XX is used to indicate Language specific model)
Megger Portable Cable Fault Locator
Copyright© 2011 by Megger. All rights reserved.
The information presented in this manual is believed to be adequate for the intended use of the product. The products described herein should not be used for purposes other than as specified herein. Specifications are subject to change without notice.
WARRANTY
Products supplied by Megger are warranted against defects in material and workmanship for a period of one year following shipment. Our liability is specifically limited to replacing or repairing, at our option, defective equipment. Equipment returned for repair must be shipped prepaid and insured. Contact your local MEGGER representative for instructions and a return authorization (RA) number. Please indicate all pertinent information, including problem symptoms. Also specify the serial number and the catalog number of the unit. This warranty does not include batteries, lamps or other expendable items, where the original manufacturer’s warranty shall apply. We make no other warranty. The warranty is void in the event of abuse (failure to follow recommended operating procedures) or failure by the customer to perform specific maintenance as indicated in this manual.
Local Megger Offices
Australia Canada France
Megger Pty Limited Unit 1, 11-21 Underwood Road Homebush NSW 2140 T: +61 (0)2 9397 5900 F:+61 (0)2 9397 5911
Germany India Kingdom of Bahrain
Megger GmbH Obere Zeil 2 61440 Oberursel Deutschland
T: 06171-92987-0 F: 06171-92987-19
Kingdom of Saudi Arabia South Africa Sweden
PO Box 1168 Khobar 31952
T: +966 3889 4407 F: +966 3889 4077 mesales@megger.com
Switzerland United Kingdom (Dover)
Megger Schweiz AG Ob. Haselweg 630 5727 Oberkulm Aargau T: +41 62 768 20 30 F: +41 62 768 20 33
United States (Dallas)
4271 Bronze Way, Dallas, Texas 75237-1019 USA
T: 1-800-723-2861 F: 1-214-331-7399
110 Milner Avenue Unit 1 Scarborough Ontario M1S 3R2 Canada
T: 1 416 298 6770 F: 416 298 0848
Megger (India) Pvt Limited 501 Crystal Paradise Mall Off. Veera Desai Road Andheri (W) Mumbai 400053 T: +91 22 26740468 F: +91 22 26740465
PO Box 22300 Glen Ashley 4022 Durban South Africa
T: +27 (031) 5646578 F:+27 (031) 5637990
Megger Limited Archcliffe Road Dover CT17 9EN
T: 01304 502101 F: 01304 207342
United States (Valley Forge)
Valley Forge Corporate Centre 2621 Van Buren Avenue Norristown, PA 19403 USA T: 610 676 8500 F: 610-676-8610
23 rue Eugène Henaff ZA du Buisson de la Couldre 78190 TRAPPES T: 01 30 16 08 90 F: 01 34 61 23 77
P.O. Box 15777 Office 81, Building 298 Road 3306, Block 333 Manama Kingdom of Bahrain. T: +973 177 40 620 F: + 973 177 20 975 mesales@megger.com
Megger Sweden AB Eldarvägen 4 Box 2970 SE-187 29 TÄBY SWEDEN T: +46 8 510 195 00 F: +46 8 510 195 95
United States (College Station)
4064 State Highway 6 South College Station, TX 77845 USA T: 979-690-7925 F: 979-690-0276
Safety
H
Voltages of greater than 50 V applied across dry unbroken human skin are capable of producing heart fibrillation if they produce electric currents in body tissues which happen to pass through the chest area.[citation needed] The electrocution danger is mostly determined by the low conductivity of dry human skin. If skin is wet, or if there are wounds, or if the voltage is applied to electrodes which penetrate the skin, then even voltage sources below 40 V can be lethal if contacted. Additionally research has shown that where the skin has been compromised, very small voltage of up to 3V can kill.
Accidental contact with high voltage supplying sufficient energy will usually result in severe injury or death. This can occur as a person's body provides a path for current flow causing tissue damage and heart failure. Other injuries can include burns from the arc generated by the accidental contact. These can be especially dangerous if the victim's airways are affected. Injuries may also be suffered as a result of the physical forces exerted as people may fall from height or be thrown a considerable distance.
Low-energy exposure to high voltage may be harmless, such as the spark produced in a dry climate when touching a doorknob after walking across a carpeted floor.
Table of Contents
1 SPECIFICATIONS ............................................................................................................................... 1
Supply .............................................................................................................................................. 1
Input Voltage source ..................................................................................................................... 1
High Voltage .................................................................................................................................. 1
Proof / Burn Output .................................................................................................................... 1
Surge Impulse (Voltage Impulse) ............................................................................................... 2
Arc Reflection & Arc Reflection Plus ........................................................................................ 2
Modes of Operation ...................................................................................................................... 2
Low Voltage ................................................................................................................................... 2
MTDR 100 (Time Domain Reflectometer) ............................................................................... 2
Metering .......................................................................................................................................... 3
Environmental ............................................................................................................................... 3
Dimensions & Weights ................................................................................................................. 4
Accessories ..................................................................................................................................... 4
Standard (supplied with instrument) ........................................................................................... 4
Optional (not supplied as standard) .......................................................................................... 5
2 GETTING TO KNOW YOUR PLF22M ......................................................................................... 7
Top Panel Controls ....................................................................................................................... 7
Safety ............................................................................................................................................... 7
Metering .......................................................................................................................................... 9
Controls ........................................................................................................................................ 10
External Connections ................................................................................................................. 12
External Connections ................................................................................................................. 13
Integrated MTDR ........................................................................................................................ 14
3 SAFETY ................................................................................................................................................ 15
General Safety Precautions ........................................................................................................ 15
Safety in Using the PFL .............................................................................................................. 17
4 PREPARING FOR TEST .................................................................................................................. 19
Important Safety Warnings ........................................................................................................ 19
Site Preparation ............................................................................................................................ 20
Making Connections ................................................................................................................... 20
Earth (Ground) the Instrument ................................................................................................ 20
Incoming Supply Lead/Cord ..................................................................................................... 21
HV Interlock blanking plug ....................................................................................................... 21
Connection HV Cable ................................................................................................................ 21
Sheath / Concentric connection ............................................................................................... 21
High Voltage Cable connection ................................................................................................ 21
Safety Zone ................................................................................................................................... 21
Switching On ................................................................................................................................ 22
Connection Diagram ................................................................................................................... 22
AVTMPFL22M Rev 1 April 2011
i
M
5 OPERATION OF THE PFL22M 23
Test Modes ................................................................................................................................... 23
Connections ................................................................................................................................. 23
Switching on the Unit ................................................................................................................. 24
Test Procedures ........................................................................................................................... 24
D.C. Dielectric withstand (Proof) Test .................................................................................... 24
D.C. Dielectric Proof/Burn ....................................................................................................... 25
Arc Reflection : High Voltage Prelocation .............................................................................. 26
Impulse Current (Surge Impulse, I.C.E.) : High Voltage Prelocation ................................. 28
Surge Generation (Surge Impulse): High Voltage Pinpoint Location ................................. 29
6 MAINTENANCE ............................................................................................................................... 31
ADDENDUM 1 MTDR100 User Guide ............................................................................................. 33
Getting to know your MTDR100 ............................................................................................. 35
MTDR100 Specification ............................................................................................................. 36
Modes of Operation .................................................................................................................... 36
Overview of Methods available on the PFL22M1500 ........................................................... 37
TDR / Pulse Reflection .............................................................................................................. 37
Arc Reflection .............................................................................................................................. 37
Arc Reflection Plus...................................................................................................................... 37
Differential Arc Reflection (DART) ......................................................................................... 37
Impulse Current (ICE or Current Impulse) ............................................................................ 37
Display .......................................................................................................................................... 38
Status Bar ...................................................................................................................................... 38
Operator Menu Bar ..................................................................................................................... 39
Single Button Operation ............................................................................................................. 40
Rotary Jog-Dial (item 35) ........................................................................................................... 40
Operation of the MTDR100/300 ............................................................................................. 41
Enabling the MTDR (When Integrated with PFL system) .................................................. 41
Initial Set-up ................................................................................................................................. 41
ADDENDUM 2 ....................................................................................................................................... 51
Specification ................................................................................................................................. 53
Protection ..................................................................................................................................... 54
Operation ...................................................................................................................................... 56
Determine Battery Capacity ....................................................................................................... 56
Connect the Battery Cables ........................................................................................................ 56
Cabling Guidelines ...................................................................................................................... 56
ADDENDUM 3 ....................................................................................................................................... 59
Cable Fault Location Applications Guide ............................................................................... 59
Typical Fault Locating Strategy ................................................................................................. 61
Overview of Fault Prelocation Methods .................................................................................. 63
Description of TDR or Pulse Echo techniques ...................................................................... 63
Description of Arc Reflection ................................................................................................... 64
Description of Impulse Current ................................................................................................ 65
Description of Voltage Decay ................................................................................................... 66
AVTMPFL22M Rev 1 April 2011
ii
UPON RECEIPT OF YOUR DELIVERY
Prior to operation, check for loosened hardware or damage incurred during transit. If these conditions are found, a safety hazard is likely, DO NOT attempt to operate equipment.
Please contact Megger as soon as possible.
Please check your delivery against:
a) your order b) our advice note c) the item delivered, and d) the parts list
any shortages must be reported immediately.
AVTMPFL22M Rev 1 April 2011
iii
M
STANDARD MANUAL CONVENTIONS
This manual uses the following conventions:
Bold indicates emphasis or a heading.
NOTE:
F
G
is used to set off important information from the rest of the text.
A WARNING symbol alerts you to a hazard that may result in equipment damage, personal injury, or death. Carefully read the instructions provided and follow all safety precautions.
A CAUTION symbol alerts you that the system may not operate as expected if instructions are not followed.
AVTMPFL22M Rev 1 April 2011
iv
1
SPECIFICATIONS
Supply
Input Voltage source
PFL22M1500-XX is fitted with automatic voltage switching and as such can
be supplied from either, a) 108 to 135Volts or b) 208 to 265Volts supplies.
The PFL22M1500-XX, maximum power requirement is 1500 VA when used
with AC input. Two-pole three-terminal grounding type connector must be used.
The PFL22M1500INV-XX has a 12V inverter installed allowing operation
from a suitable 12V Supply, connected to the auxiliary connection on the side of the unit.
The PFL22M1500INV-XX maximum power requirement of a 12V.d.c.
power source is 1900 VA (160A), when used with the authorized inverter unit.
High Voltage
Proof / Burn Output
Output voltage 0 to 10kV dc negative wrt earth
Proof Current 0 to 115mA (10V range)
Burn Current 0 to 115mA (10V range)
AVTMPFL22M Rev 1 April 2011
0 to 20kV dc negative wrt earth
0 to 55mA (20kV range)
0 to 55mA (20kV range)
1
M
Surge Impulse (Voltage Impulse)
Ranges Two (2)
Impulse voltage 0 to 8kV
0 to 16kV
Impulse Energy
@ 100% of range
Impulse Repetition Rate
Single Shot
Arc Reflection & Arc Reflection Plus
Voltage
Energy @ 100% of range
Traces:
Modes of Operation
1500joule @ 0 to 8kV 1500joule @ 0 to 16kV
5 to 30seconds
0 to
8kV
0 to 16kV
1500joule @ 0 to 8kV 1500joule @ 0 to 6kV
1024 to 16 (Dependent on range selected)
Low Voltage
High Voltage
Pulse Echo ; Direct; Comparison
Arc Reflection , Arc Reflection Plus (ARP), Differential Arc Reflection (DART) , Impulse Current
Low Voltage
MTDR 100 (Time Domain Reflectometer)
Operation
Modes
Ranges
Single Jog-Dial
Pulse Echo, Direct, Comparison, Arc Reflection, Arc Reflection Plus (ARP), Differential Arc Reflection (DART) Impulse Current
10 ranges: 100m, to 55km ; 328ft to 180,445ft
2
AVTMPFL22M Rev 1 April 2011
SPECIFICATIONS
Pulse Width
Pulse Amplitude
Sampling Rate
Resolution (VP=55%)
Timebase accuracy
Output impedance
Gain
Display
Storage
Metering
Voltmeter
50ns, 100ns, 200ns, 500ns 1μs, 2 μs, 5 μs, 10 μs
25V into 50 Ohms
100Megasamples/sec
0.82m / 2.7ft
200 ppm
50 Ohms
Variable over 60dB in 5dB steps
XGA 1024 x 768 26.5mm (10.4”)
On-board and USB
Analogue 0 to 20kV Accuracy 5%
Ammeter
Environmental
Operating Temp
Storage Temperature
Humidity
Elevation
Analogue 0 to 300mA Accuracy 5%
-20 to 50o C / -4 to 120 oF
-30 to 55o C / -22 to 131oF
5 to 95% RH non-condensing (operating)
1600m (De-rate voltages at higher altitudes)
AVTMPFL22M Rev 1 April 2011
3
M
Dimensions & Weights
Height
Width
Depth
965 mm / 38 inch
536 mm / 21inch
503 mm / 20 inch
Weight (Total) 131kgs / 290lbs
Accessories
Standard (supplied with instrument)
High Voltage Cable
Safety Ground Cable
Input/supply Cable
15m flexible, lightweight,40kV single core HV cable
15m flexible ground cable with ferrules,
line cord/ supply cable (1 x ea)
1001-123:
19265-15:
17032-4 ; North American 17032-5 ; International
Shorting plug
Cable Bag/Satchel
Documentation
Software
17032-12; BS 170032-13; EU SHUKO
Interlock shorting plug qty 1 supplied 10226-1
Cable bag to take all cables 2001-813:
User Guide AVTMPFL22:
Cable Analysis Software CAS01:
4
AVTMPFL22M Rev 1 April 2011
Optional (not supplied as standard)
SPECIFICATIONS
HV Vice Groups
PFL22M Transit Case
HV Discharge stick
12 V External Battery
Discharge Receiver:
Cable Drums
Adjustable HV Vice
18944-2
Grips
Transit Case 2001-289
70kV Discharge stick 222070-62
12V/92Ah Battery 1001-690
Acoustic and
MPP2000 or MPP1001 Electromagnetic pinpoint receiver
Megger have several cable drums and cable drum assemblies which need to be specified dependent on installation and possible combination with other instruments. Another consideration is where the equipment is installed into a vehicle or trailer the available payload must be taken into consideration.
It is recommend that the factory is contacted prior to ordering the optional cable drums or cable drum assemblies
AVTMPFL22M Rev 1 April 2011
5
M
M
6
AVTMPFL22M Rev 1 April 2011
2
GETTING TO KNOW YOUR PLF22M
Top Panel Controls Safety
1. Status Bar: Indicates
HV On / HV Off
2. External Interlock LED
(Yellow): Indicates if External Interlock activated
AVTMPFL22M Rev 1 April 2011
High visibility status bar Indicates Operating status of the PFL22.
Ungrounded / HV On: Two outer segments glow Red indicating earth/ground off and HV active.
Note: HV not active in TDR mode
Grounded / HV Off: Single inner segment glows Green indicating Earths are on with no HV present.
When illuminated indicates that the optional external interlock has been activated, or interlock blanking-plug not in place.
7
M
3. Zero Start Interlock
LED (Yellow) of voltage control not at
: Indicates
zero
4. HV Cable Interlock
LED (Yellow): Indicates HV Cable not connected
5. Range Switch Interlock
LED (Yellow): Indicates if Range Switch not seated
6. Mode Switch Interlock
LED (Yellow): Indicates if Mode Switch not seated
7. Voltage Preview
LED (Blue): Preview of voltage to be applied
When illuminated indicates that the voltage control knob is not at zero, Voltage control must be at zero before commencing any voltage changes. Only active for dc operations.
When illuminated indicates that the HV cable connection to the PFL has not been made correctly.
Illuminates if the Range switch is not properly seated, and a range correctly selected.
Illuminates if the Mode selector switch is not properly seated, and a mode correctly selected.
When illuminated this indicates that the voltage shown on the Kilovolt meter is a preview only, prior to it being
applied to the cable under test. (No HV activated)
8. Emergency Stop This switch acts as an Emergency Stop and also an
On/Off switch. To disengage and turn on the instrument pull this switch. To turn off either in an emergency or when operation complete depress.
9. Zero Start
Voltage control must be at zero before commencing any voltage changes. Only active for dc operations.
8
AVTMPFL22M Rev 1 April 2011
Metering
GETTING TO KNOW YOUR PLF22M
10. Milliampmeter:
0 to 300mA analogue Mili-Amp meter. Indicates the charging current being applied (leakage current).
11. NOT USED
12. NOT USED
13. d.c. KiloVolt meter: 0 to 20 kV analogue kilovolt meter. Indicates applied
voltage (or voltage preview) in Proof/Burn, Surge, Arc Reflection modes.
AVTMPFL22M Rev 1 April 2011
9
M
Controls
14. Surge Repetition Control Knob: Select either single shot or set the desired surge
repetition rate.
15. Arc Reflection Mode Pushbutton
(switch/indicator):
To selected Arc Reflection mode depress the push button switch. Switch will illuminate when Arc Reflection mode selected and active.
16. TDR Mode Pushbutton
switch/indicator:
To select TDR (Pulse Echo) depress the push button switch. Switch will illuminate when TDR mode selected and active.
17. Surge Mode Pushbutton
(switch/indicator):
To select Surge or Impulse Current depress the switch. Switch will illuminate when Surge mode selected and active.
18. Proof/Burn Mode Pushbutton
(switch/indicator):
To select Proof/Burn depress the switch. Switch will illuminate when Proof/Burn mode selected and active.
19. Mode Switch (Filter in/Filter out): Two position rotary selector switch, switch
between the modes that require the arc reflection filter engaged; Arc Reflection & TDR and the modes whereby the needs to be disengaged Surge & Proof/Burn.
10
AVTMPFL22M Rev 1 April 2011
GETTING TO KNOW YOUR PLF22M
20. Voltage Range Switch: Two position rotary selector switch that switches
between the proof/burn ranges of 10 & 20 kV and the surge voltage ranges of 8 & 16 kV.
21. Voltage Control Knob: Rotary Voltage control knob, controlling the
applied voltage in Proof/Burn, Surge or Arc Reflection modes. Control is via a zero start, hence before selecting knob must be at zero. Only active for dc operations.
22. Initiate pushbutton: Push button whereby the HV is activated, whether
in Proof/Burn, Surge or Arc Reflection modes. Switch is illuminated sold green when valid made selected and flashes when HV has been engaged.
AVTMPFL22M Rev 1 April 2011
11
M
External Connections
23. External Battery connection
Positive (+):
24. External Battery connection
Negative (-):
25. Earth/Ground connection:
26. External HV interlock:
27. Warning Beacon connection:
The positive connection point when using the PFL22M from an external 12V supply.
The negative connection point when using the PFL22M from an external 12V supply. Note: When external battery is used the only earth/ground is via the external Earth/Grounding connection (item 27)
The instrument Earthing/Grounding point. For operator safety it is mandatory that the PFL22M is efficiently earthed/grounded. Failure to do so could result in serious injury or in the extreme circumstances death.
To provide additional operator safety an external HV interlock (optional accessory) can be fitted.
Through this connection an external warning beacon (optional accessory) can be fitted. Connection rated at 3A, 220V dc and 250V ac, exceeding this limit will damage the unit
12
AVTMPFL22M Rev 1 April 2011
External Connections
GETTING TO KNOW YOUR PLF22M
28. Rain Flap Closed and secured during transportation to
maintain Instrument IP rating.
29. HV Output Socket
The PFL22M is supplied with a 5m detachable 40kV HV cable. Interlocks built into the receptacle inhibit the use of the unit unless the
30. Fan
31. Supply Socket
HV cable is securely fitted.
(Guard/Cover removed for illustration purposes)
PFL22M1500 is fitted with automatic voltage switching and as such can be supplied from either a) 108 to 135Volts or 210 to 265Volts.
AVTMPFL22M Rev 1 April 2011
13
M
Integrated MTDR
32. MTDR Display Large 21cm (10.4”) LCD display. Displaying all parameters
and the necessary information and traces to achieve rapid accurate fault location.
33. Pneumatic Lid
Rams:
34. USB Port:
Pneumatic support rams provide safe support whilst opening and closing the lid of the PFL22M.
USB port to download/upload memorized traces including all parameters.
35. MTDR Jog Dial:
One-button operation of the MTDR is achieved using the Rotary Jog-Dial control knob. With this jog-dial the operator sets all the preferences, selects modes of operation and undertakes the fault analysis and fault pre­location.
14
AVTMPFL22M Rev 1 April 2011