Megger PAT32 User Manual

M
PAT32 Series P o rtable Appliance Testers
USER GUIDE
GUIDE DE L’UTILISATEUR
GEBRAUCHSANLEITUNG
SAFETY WARNINGS
rectified before testing. Re-testing must commence from the start of the sequence.
Replacement fuses must be of the correct size, type and rating. See 'Specification' section. The instrument must not be used in damp conditions or if any part of it is damaged.
Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed
during use.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS
.
Symbols used on the instrument
Evaluate display reading against appliance details and refer to this User Guide Caution: Refer to accompanying notes. Equipment complies with relevant EU Directives
User Guide
Safety Warnings 2 General Description 4 Features and Controls 6 Test Mode Summary 7
Performing tests – General 9 Appliance Testing 10 Extension lead testing (UK) 14
Specifications 15
Accessories 18
Repair and Warranty 19
Guide de l’utilisateur
Avertissments de Securité 22 Description génerale 23 Dispositifs et Commandes 25 Sommaire de Mode d’essai 23 Exécution des essais – Géneralitiés 26
Mise à l’essai de l’appareil 29 Mise à l’essai de la Rallonge 33 Spécification 34 Accessoires 37 Réparation et Garantie 38
Gebrauchsanleitung
Sicherheitswarnung 42 Allgemeine Beschreibung 43 Funktionen und Steuerelemente 45 Zusammenfassung des Testmodus 46 Durchführung von Tests 48 Testen von Geräte 49 Verlängerrungskabeltest 53 Spezifikation 54 Zubehör 57 Reparaturen und Garantie 58
Contents
3
Introduction
Megger PAT 32 series are designed to check the electrical safety of any product fitted with an appropriate mains plug, including information technology (IT) equipment, domestic appliances, industrial appliances and power tools.
The following tests are available:
Circuit check
Fuse check
Earth Continuity test
10 Amp Earth Bond test
25 Amp Earth Bond test
Insulation test
Extension lead tests (ELT1 or ELT2
required)
- Polarity (UK only)
- Earth Bond
- Insulation
Tests are effected by plugging the portable appliance or extension lead into the relevant socket and pressing the relevant Test switch. The readings from each test are shown on the unique analogue / digital liquid crystal display.The measurement scale for Earth Bond is marked with pass bands. This provides a rapid indication of a test Pass or Failure and allows proper test results to be kept.
Applications
Appliances and electrical equipment with Safety Class I, Class II and Safety Class III insulation may be tested. These classes of safety are defined in various IEC and BS safety specifications, and in general are:-
Class I Appliances which have functional
insulation throughout and an earth connected body i.e. an ‘Earthed‘ appliance.
Class II Appliances which have both functional
and additional insulation, and where any metal parts cannot become ‘Live’ under fault conditions. This is ‘Double
Insulation’ indicated by .
Class I / II Appliances having part of the
enclosure which meets Class I requirements and part which meets Class II.
Class III Appliance where protection against
electric shock is provided by an SELV supply. Class III construction is indicated by the mark.
General Description
4
III
Typical uses for Megger PAT 32 are:
Periodic tests of equipment used in Factories, Offices, Local Education Authorities, Hospitals etc.
Routine tests before and after hiring electrical equipment.
Basic tests following equipment repair.
Tests by manufacturers and distributors.
Specifications
The Megger PAT 32 may be used to test equipment originally manufactured to a range of specifications such as:
IEC 335 -1 / BS3456
BS 2769
BS 4533
BS415
BS 7002
Power cord
The colour code of the cord is:
Phase Brown
Protective Earth Yellow / Green
Neutral Blue
If using a fused plug, a 3 Amp fuse to BS 1362 should be fitted.
Note: A plug severed from the power cord should be destroyed, as a plug with bare conductors is hazardous in a live socket outlet.
5
Features and Controls
6
Fuse test terminals
110 Volt Socket to BS4343 /IEC309
230 V Socket to BS1362
230 V Belgian / French socket
230 V
Circuit Test switch
10 A Earth Bond Test switch
25 A Earth Bond Test switch
Insulation Test switch
Earth Bond Test
Earth Continuity Test terminal
Analogue / Digital LCD
Test Sequence
For safety reasons, it is important that appliance tests are carried out in the correct sequence:-
Circuit Test
Fuse Test (if necessary)
Earth Continuity Test
and / or
Earth Bond Test
Insulation Test
If a fault on an appliance is detected, testing must be stopped and the fault rectified. Testing must then re­commence from the beginning of the test sequence.
Circuit Test
A low voltage d.c. Resistance test of the Phase to Neutral circuit.
FuseTest (if supply or appliance fuse is suspect) Checks the continuity of most types of fuses when removed from the appliance.
Earth Continuity Test
The earth continuity test may only be performed on
Class I (Earthed) appliances.The test checks protective
conductor continuity and the earth connection to the metal parts of the appliance at a current of 100 mA. This test is used where a higher current Earth Bond test may cause damage to the appliance. Avery low voltage
(100 mV) is established between the main supply plug earth pin and the metal parts of the appliance. The low voltage of this test is designed to reveal bad connections by not breaking down any oxide films.
Earth Bond Test
The Earth Bond test may only be carried out on Class I (earthed) appliances.
The test checks protective conductor continuity and the earth connection (or Bonding) to the metal parts of the appliance. Avery low voltage is established between the main supply plug earth pin and the metal parts of the appliance.
A choice of two Earth Bond tests is available:­i) Passing a current of 10 Amp. Used for
appliances and equipment fused at 5 Amp or less.
ii) Passing a current of 25 Amp. Used for
equipment fused at greater than 5 Amp.
Test Mode Summary
7
Insulation Test
Checks the integrity of the insulation. For class I appliances, the test voltage is applied to the main supply plug between Phase and Neutral (shorted together) and the Earth pin, which is held at earth potential. For Class II appliances, the Earth Bond lead is used to make the return connection from the appliance to the instrument earth bond terminal.
The PAT 32 develops 500 V d.c. into 0.5 M and complies with the 1mA load current requirement.
Caution:- If an Insulation test fails, there will be a leakage path to earth somewhere on the appliance. Any metal parts of the appliance could become ‘Live’ and give the user an electric shock. Do not touch the appliance when applying the test.
Extension Lead Test
Using the Megger ELT1 or ELT2 optional accessory, the PAT 32 checks Continuity, Earth Bond and Insulation of both 230 V and 110 V extension leads. (110 V adaptor required). ELT1 (UK version) also checks the Polarity of the extension lead connections.
Error displays
Internal faults within the instrument are indicated by error messages consisting of the letter ‘ followed by a 2 digit
number. Continuous testing on the Earth bond ranges may cause the display of , and the analogue pointer
to move off the left hand end of the scale. Cease testing and allow the instrument to cool for about 15 minutes. If any error message displays, and the instrument will not re-set itself, return the instrument for service. See Repair
and Warranty.
Test Mode Summary
8
Appliance Visual Checks
Before carrying out PAT32 electrical tests, the appliance and its accessories must be given a visual inspection to identify any physical faults that may not be revealed by
electrical testing.
Visually examine and check the condition of the:-
Supply plug
Plug fuse type and rating (if applicable)
Mains cord
Cord connection grommet (if applicable)
Mains On /Off switch
Auxiliary switches
Conducting / Insulated parts of the outer case
Removable covers which must be in place.
Any significant faults or defects must be rectified before proceeding with the PAT 32 electrical tests.
Auto Nulling and Self check
When not being operated, PAT 32 will periodically carry out measurement nulling. The word is displayed. Press any Test switch to override this function.
A self check function is also continuously performed on
the selected test range.
If testing is interrupted, for instance due to the appliance not being switched On, or the mains fuse being ruptured, testing must be repeated from the start of the test sequence in the corrected condition. i.e. with a sound fuse and with the appliance switched On.
Performing Tests – General
9
Tests must be performed with the appliance
switched On and with good fuse(s) fitted.
Preliminary Testing Procedure
1. Plug the PAT32 into the 230 V mains power supply, and switch the supply on. Full screen details are displayed, and a self check is carried out. On completion, the ‘Home’ screen is displayed.
2. Determine the Class / type of the appliance to be tested.
Class I Earthed appliance
Class II Double insulated appliance
Class III - S.E.L.V appliance
3. Plug the appliance into the appropriate socket on the instrument front panel and switch the appliance On.
Appliance Testing Procedure
Circuit Test
1. Press and hold the Circuit Test switch. The Circuit screen is displayed.
2. Phase to Neutral resistance is displayed directly in k .
Note:- Readings of approximately 0,01 k can be expected from appliances incorporating large wound components such as large transformers and motors. Heating appliances may give readings of approximately 0,02 k.
3. Release the Test switch.
Appliance Testing
10
Tests must follow the given sequence
If fault(s) are indicated, cease testing and rectify. Re-commence testing from the start of the test sequence.
Note:- During the test, a display of indicates Open circuit. Check that the appliance is switched On, that any fuses fitted are good, the continuity of the power cord is good and that the appliance itself is not open circuit. Appliances with a switch mode power supply may indicate Open circuit. In this case, omit the Circuit test.
Note:- If the appliance circuit appears to be Open circuit, fuses (if applicable) may be checked as follows:
Fuse Check
1. Remove the suspect fuse from the appliance. With the ‘Home‘ screen displayed (no switches pressed) press the suspect fuse across the contacts.
A good fuse is indicated by the display of
accompanied by a continuous beep note.
Earth Continuity Test (Class I appliances only)
1. With the ‘Home‘ screen displayed (no switches pressed) connect the Earth Bond test lead to the 100mA terminal.
2. Firmly connect the crocodile clip to the metalwork of the appliance.
3. Earth continuity resistance is displayed directly in m .
4. Disconnect the Earth Bond test lead.
Earth Bond Test (Class I appliances only)
1. With the ‘Home‘ screen displayed (no switches pressed) connect the Earth Bond test lead to the 10A/25A terminal.
2. Firmly connect the crocodile clip to the metalwork of the appliance.
3. Press and hold either the 10A or the 25A test switch. The Earth Bond screen is displayed.
4. Earth Bond resistance is displayed directly in m .
5. Release the Test switch.
6. Disconnect the Earth Bond test lead.
A successful test is indicated on the solid scale line and the word PASS is displayed.
As a general rule, an appliances should have an Earth Bond resistance of less than 100 m. Appliances with long supply leads will give higher readings due to conductor resistance. Corrections may be applied if lead
11
resistance figures are available and lead length is measured. A reading of between 100 m and 500 m will be indicated on the broken scale line together with the display of . Refer to the appliance manufacturer. Readings greater than 500 m are indicated by t h e flashing display of the word FAIL.
On the 10 Amp range, the flashing display of w i l l appear for resistance greater than 600 m, indicating that the test current is below a satisfactory test level. It is suggested that the 25 A m p range should then be used.
Insulation Te s t
Class I Appliance
1. Press and hold the Insulation Test switch. The Insulation screen is displayed.
2. Insulation resistance value is displayed directly in M .
3. Release the Test switch.
As a general rule, Class I appliances should have an insulation resistance value greater than 1 M . A reading of less than 0.25 M is indicated with the word
FAIL.
Class II Appliance
1. Connect the Earth Bond test lead (or probe if available) to the 10A/25A terminal.
2. Press and hold the Insulation Test switch. The Insulation screen is displayed.
3. Using the crocodile clip, probe areas of likely leakage around the insulation areas. i.e. joins / apertures / metal parts.
4. Release the Test switch.
5. Disconnect the Earth Bond test lead.
As a general rule, Class II appliances should have an insulation resistance value greater than 2 M .
A reading of greater than 2 M is indicated on the solid scale line together with the word PASS.
A reading of less than 0.25 M is indicated with the word
FAIL.
Appliance Testing
12
Between 0.25 M and 2 M , the is displayed. In this instance, the user must judge whether to PA S S or FA I L the test, depending upon the insulation class of the a p p l i a n c e .
Appliance Testing
13
Plug the extension lead into the appropriate socket on the instrument front panel.
Circuit Test
1. Press and hold the Circuit Test switch. The Circuit screen is displayed.
For an unterminated extension lead a reading of should be displayed. Any other reading indicates a faulty lead and must be investigated.
2. Release the Test switch.
Polarity Test
Plug Extension Lead Tester ELT1 into the socket end of the Extension lead (use the adaptor for 110 V leads).
1. Press the Circuit Test switch twice.
2. Check the polarity of the extension lead against the following display options:
- Polarity Correct
- Connections reversed
- Short Circuit
- Open Circuit
Earth Bond Test
1. Connect the Earth Bond test lead to the 2 5 A terminal.
2. Firmly connect the crocodile clip to the E LT1 metal stud.
3. Press and hold the 25A Test switch. The Earth Bond screen is displayed.
4. Earth Bond resistance is displayed directly in m .
5. Release the Test switch.
6. Disconnect the Earth Bond test lead.
Insulation Test (Class I leads only)
1. Press and hold the Insulation Test switch. The Insulation screen is displayed.
2. Insulation resistance value is displayed directly in M .
3. Release the Test switch.
Extension Lead Testing (UK)
– ELT1 Required
14
Do not plug the ELT1 into a live circuit
If fault(s) are indicated, cease testing and rectify. Re-commence testing from the start of the test sequence.
Circuit Test
Meter reading range: 0 to 9,9 k
Range Resolution Accuracy
0 to 1 k 0,01 k 2,5% of reading ± 0,02 k 1 k to 2 k 0,02 k 2,5% of reading ± 0,02 k 2 k to 5 k 0,05 k 2,5% of reading ± 0,05 k
5 k to 9,9 k 0,1 k 2,5% of reading ± 0,1 k Open Circuit Voltage: 4,5 V d.c. Short Circuit Current: 1 mA d.c.
Fuse Check
5 V. d.c. 0,5 mA Typical
Earth Continuity Test
Range Resolution Accuracy
0 to 999 m 1 m 2,5% of reading ±5 m
900 m to1990 m 10 m 2,5% of reading ±10 m Open Circuit Voltage: Typically 100 mV d.c.
Constant Current: Typically 100 mA into <1
10A Earth Bond Test
Meter reading range: 0 to 1990 m
Range Resolution Accuracy
0 to 600 m 1 m 2,5% of reading ±5 m
600 to 999 m 1 m Current below level for
900-1990 m 10 m satisfactory Bond test.
Transfer to 25A test
Pass Band Limits: 100 and 500 m Open Circuit Voltage: Typically 3 V rms a.c. 50 Hz
Specification
15
Specification
Spec Point Current 10A into 100 m at 240 V. 8,7 A into 100 m at 230 V. Short Circuit Current Typically 12 A
25A Earth Bond Test
Meter reading range: 0 to 1990 m
Range Resolution Accuracy
0 to 999 m 1 m 2,5% of reading ±5 m
900-1990 m 10 m 2,5% of reading ±10 m Pass Band Limits: 100 and 500 m
Open Circuit Voltage: Typically 6 V rms a.c. 50 Hz Spec Point Current: Typically 25A into 100 m (10A into 500 m) Short Circuit Current Typically 36.5 A
Insulation Test
Meter reading range: 0-99 M
Range Resolution Accuracy
0 to 10 M 0,1 M 2,5% of reading ± 0,1 M
10M to 20 M 0,2 M 5% of reading ± 0,2 M
20M to 50 M 0,5 M 5% of reading ± 0,5 M
50M to 99 M 1 M Indication only Pass Band limit: 2 M (Class I) – 7 M (Class II)
Open Circuit Voltage: 600 V d.c. Spec Point Voltage 500 V d.c. into 0.5 M Short Circuit Current: < 2 mA
General
Temperature Range
Operating: 5 ˚C to +40˚ C Storage: -25˚C to +65˚ C
16
Humidity Range
Operating: 90% RH at 25˚C
Supply 230 V(+10% -6%) 50 Hz 300 VA Safety Meets the requirements for double insulation to IEC 1010 (1995) EN
61010 (1995)
Fuses 2 x 2 A (F) 20 mm x 5 mm HBC, IEC 127/1
2 x 250 mA (F) mm x 5 mm HBC, IEC 127/1
Mains power cord fused plug (as applicable) – 3 Afuse to BS1362
EMC In accordance with IEC61326 including amendment No.1 Dimensions 314 mm x 152 mm x 206 mm (12,5” x 6” x 8”) Weight 3,75 kg (8,25 lb approx.) Cleaning: Wipe the disconnected instrument with a clean cloth dampened with
soapy water or Isopropyl Alcohol (IPA).
Specification
17
Supplied Part Number
User Guide 6172-265 Accessory Pouch 6420-108 Earth Bond test lead with crocodile clip 6280-043
Optional Extras
Extension lead tester ELT1 (UK) 6111-130 Extension lead tester ELT2 (France & Germany) 6111-320 Earth Bond lead and Probe EP1 6320-225 Bare wire adaptor lead with 3 pin plug to BS1363/A 6111-230 Appliance safety log book (complete) 6131-813 Log book test sheets (pack of 30 sheets) 6171-417 Log book test stickers (Pack of 3 sheets [72 stickers]) 6171-418
Training Media
VHS Video: ‘Portable Appliance Testing‘ 6131-999
Accessories
18
Loading...
+ 41 hidden pages