Although these currents are generally considered together as the total test current, they behave
differently.
Total current
Capacitive charging
current
Absorption or
Polarisation current
Conduction or leakage
current
The capacitive charging current starts quite high but drops quickly as the device under test
charges in much the same way as a capacitor.
The absorption or polarisation current also starts high but decays over a longer period of
time as the molecules of the insulation of the device under test line up to oppose the flow of
current, this polarisation may take some time to occur.
Conduction or leakage current normally begins at a low level, settling to a constant value it is
the current that travels through the insulation and flows along the surface.
We see this as one current that can be measured with an ammeter but using Ohms Law we
can represent this as a resistance.
Guide to Motor testing 19
Page 20
Megger Baker MTR105 – The Tests
The IEEE offers the following guidance for insulation resistance test voltages with respect to the
rated line-to-line voltage for three-phase ac machines, line-to-ground voltage for single-phase
machines and rated direct voltage for dc machines or field windings.
Winding rated VoltageTest Voltage (DC)
<1000500
1000 – 2500500 - 1000
2501 – 50001000 - 2500
5001 – 120002500 - 5000
>120005000 - 10000
Table 1: Rated voltage and corresponding test voltage
Spot or Timed insulation resistance test
The Spot test still remains the basic insulation resistance test that most engineers will use to
test equipment although it has evolved over time.
How long does the test last? That is up to the user, but the Spot test usually runs for about 60
seconds. The value of a quick test can’t be under stated but, as we will see, this test combined
with the other types of insulation resistance test provides a more reliable indication of the state
of the motor.
Insulation resistance should be approximately 1 MΩ for each 1,000 volts of operating
voltage, with a minimum value of 1 MΩ. For example, a motor rated at 2,400 volts should
have a minimum insulation resistance of 2.4 MΩ. In practice, the readings are normally are
considerably above this minimum value in new equipment or when insulation is in good
condition.
20 Guide to Motor testing
Page 21
Megger Baker MTR105 – The Tests
Polarisation Index (PI)
This test is similar to the DAR test, but the times at which the readings are taken are much
longer. This allows the device under test to be fully charged and the insulation to be polarised
A
A
B
Insulation
resistance
B
1 Minute10 Minute
Fig 13: Ratio of time resistance readings over 10 minutes
Usually carried out over 10 minutes the PI is calculated in a similar way to DAR.
In this test, the voltage is applied and IR measurements are taken after 1 minute and 10
minutes.
The Polarisation Index or PI is calculated as PI = R10 ÷ R1
Table 2 shows the condition of the insulation.
Polarisation IndexInsulation Condition
<1Dangerous
1.0 – 2.0 ***Questionable
2.0 – 4.0Good
>4 **Excellent
Table 2: Condition of Insulation Indicated by Polarisation Index
*These values must be considered tentative and relative - subject to experience with the timeresistance method over a period of time.
**In some cases, with motors, values approximately 20% higher than shown here indicate
a dry brittle winding which will fail under shock conditions or during starts. For preventive
maintenance, the motor winding should be cleaned,treated and dried to restore winding
flexibility.
***These results would be satisfactory for equipment with very low capacitance such as short
runs of house wiring.
Guide to Motor testing 21
Page 22
Megger Baker MTR105 – The Tests
Why do we need to use this test?
The PI test provides a relative and not absolute measurement. It is a self-contained evaluation
of the condition of the insulation and can be used independently or with historical PI
measurements for trending. It indicates insulation quality in 10 minutes, which is an advantage
when working on large pieces of equipment which can take an hour to charge for an insulation
measurement reading. The PI reading shows up moisture ingress, contamination and insulation
degradation in a specific time-resistance test.
IEEE 43-2000 states “If the R1 value (at 40 °C) is greater than 5000 MΩ, the P.I. may be
ambiguous and can be disregarded”.
Dielectric Absorption Ratio (DAR)
The ratio of two time-resistance readings is called a dielectric absorption ratio. It is useful in
recording information about insulation.
A
B
A
B
Insulation
resistance
30 Seconds60 seconds
Fig 14: Ratio of time resistance readings over 60 seconds
22 Guide to Motor testing
Page 23
Megger Baker MTR105 – The Tests
The dielectric absorption ratio (DAR) is calculated as: DAR = R60 ÷ R30. The ratio is indicative
of the condition of the insulation using Table 3.
DARInsulation Condition
<1Dangerous
1.0 – 1.4Questionable
1.4 – 1.6 **Good
>1.6Excellent
Table 3: Condition of Insulation Indicated by Dielectric Absorption Ratios
*These values must be considered tentative and relative - subject to experience with the timeresistance method over a period of time.
**In some cases, with motors, values approximately 20% higher than shown here indicate
a dry brittle winding which will fail under shock conditions or during starts. For preventive
maintenance, the motor winding should be cleaned,treated and dried to restore winding
flexibility.
Why do we need to use this test?
It is a quick test to determine the health of the insulation and a DAR of 1.4 or greater, in pre-
1970 insulation systems, is considered acceptable. Otherwise, trending is required. Reference
IEEE Std 43-2000.
Used for equipment with “thin” insulation
Used on materials with a low absorption current – e.g. Polyethylene
Guide to Motor testing 23
Page 24
Megger Baker MTR105 – The Tests
Temperature correction
Insulation resistance values differ considerably at various temperatures, so in order to trend
IR values over a long period it is important to correct the IR measurement to a common
Table 4: Temperature correction factors For Rotating Machines
Class A and Class B. Corrected to 20 ϒC for rotating equipment
and transformers; 15.6 ϒC for cable.
Heat Resist. and
Perfrom. GR-S
Ozone resist
0.42
0.14
0.56
0.26
0.73
0.49
1.00
1.00
1.28
1.75
1.68
3.29
2.24
6.20
2.93
11.65
3.85
25.00
5.08
41.40
6.72
78.00
8.83
15.40
20.30
26.60
natural GR-S
Varnished
cambric
0.10
0.20
0.43
1.00
1.94
4.08
8.62
18.20
38.50
81.00
170.00
345.00
755.00 36.00
Impregnated
paper
0.28
0.43
0.64
1.00
1.43
2.17
3.20
4.77
7.15
10.70
16.00
24.00
24 Guide to Motor testing
Page 25
Megger Baker MTR105 – The Tests
Guard Terminal
During insulation testing, the resistance path on the outer surface of the insulation material is
often not considered. However, this resistance path is an important part of the measurement
and can dramatically affect the results. For example, if dirt, contamination or moisture is
present on the outer surface of a motor, the surface leakage current can be up to ten times of
that flowing through the actual insulation.
When conducting an insulation resistance test, we may note a low test result. Before
condemning the item there is one factor that is often not considered, that is surface leakage
due to contamination. This may be dust, dirt, oil, grease, metal filings, food products,
moisture, rust, even some types of paint and ‘protective’ coverings may cause problems
The surface leakage needs to be eliminated from the reading and that is where the Guard
terminal comes into play.
Note: If there is a high or compliant reading there is no need to use the Guard terminal.
The connection below shows an IR test between L1 and L2.
Fig 15: IR test between L1 and L2
If a low phase to phase reading is obtained there is possibly contamination. This is shown here
as a low resistance path between U and V phase to ground, where U is equivalent to L1 and V
is equivalent to L2.
Guide to Motor testing 25
Page 26
Megger Baker MTR105 – The Tests
Fig 16: Low resistance path between U and V to ground
To guard out this low resistance path connect the GUARD (Blue) test lead to ground
Fig 17: Guard connected to ground
If contamination is present the IR reading will increase to the expected level when the GUARD
is connected. If no change is noted with the GUARD connected then the insulation has
degraded.
Unresolved the contamination can lead to insulation failure and flashover
26 Guide to Motor testing
Page 27
Terminal
Megger Baker MTR105 – The Tests
Instrument circuit
simplified
Current meter - Only
measures current
through insulation
HV DC current
source
Instrumental
Terminal
Instrumental
Motor equivalent
circuit
–
Instrumental
Terminal
G
+
0.25 M ohm
100 M ohm
0.25 M ohm
MAX ERROR 2%
Leakage current
through motor
measured
Surface leakage
current ignored
Fig 18: Guard Diagram
The surface leakage is essentially a resistance in parallel with the true insulation resistance of
the material under test. By using the guard terminal to perform a ‘three-terminal test’, the
surface leakage current can be ignored. This may be important when high values of resistance
are expected, such as motors and supply cables. These tend to have large surface areas that
are exposed to contamination, resulting in high surface leakage currents across them.
In addition to the big improvements in the reliability of insulation condition diagnosis and
predictive maintenance discussed, the guard terminal is an important diagnostic tool. To carry
out this test the windings of the motor must be separated and not left connected in a star or
delta configuration.
The amount of current that is surface leakage can be quickly identified simply by performing
two tests; one using the guard terminal and one without, then calculating the difference
between measurements. With the guard terminal connected, if the insulation resistance is
high showing a good level of insulation but considerably lower when the guard terminal is
disconnected, the indication is of a parallel path conducting surface leakage across the outer
facings of the component between the two terminals.
Why we perform this test?
There have been many instances of poor insulation resistance measurements leading to motors
being replaced needlessly, some at huge cost, only to find later, that by employing the guard
terminal, they simply needed a good clean!
Guide to Motor testing 27
Page 28
Megger Baker MTR105 – The Tests
Three phase test
Similar in operation and performance to the spot test the phase to phase test is a standard
test performed on a three phase ac motor to determine the integrity of the insulation of each
phase. This test can only be performed when the motor is NOT configured as Star (Y) or Delta.
All phases must be isolated.
Voltmeter
Voltage and frequency measurements can be made to ensure that the supply is within that
indicated on the nameplate.
Why we perform this test?
Voltage measurements are used to ensure that the supply voltage remains within +/- 10% of
the nameplate voltage.
Phase rotation
Phase rotation can be determined to ensure that the supply is compatible with the motor prior
to connection and energising.
See Motor direction of rotation.
Why do we need to use this test?
The direction of rotation of the three phase supply voltage is determined to ensure that it
matches the direction of rotation of the motor. If the supply direction of rotation does not
match the motor direction of rotation, apparatus under the control of the motor will not
operate as intended e.g. fans won’t blow and pumps won’t pump correctly with the required
operation.
Continuity
The Continuity test is a 2 wire measurement that involves the output current and the voltage
drop measurement combined within the 2 test leads. So the entire resistance of the closed
loop (test leads + test piece) is combined in the resistance measurement. NULLing the test
leads does not eliminate variation in contact resistance, i.e. NULLing the leads across two
points of the test object, then proceeding to test continuity across several other different
test points introduces a variance in the contact resistance for all subsequent test points. The
contact resistance will almost certainly be different for each test point. The measuring circuit
28 Guide to Motor testing
Page 29
Megger Baker MTR105 – The Tests
for a continuity test is low impedance and any variation in the contact resistance will affect the
measurement.
The continuity test can quickly identify an unexpectedly high resistance in a conductor which
may be due to a break in the conductor or a open connection in a supply cable or faulty control
gear.
This is typically performed for each phase i.e. A-a; B-b; C-c;.
Continuity tests are also used as a comparative test to determine phase imbalance by
comparing the results of all three phases. In a star configured motor each phase is measured
i.e. A-Star point; B-Star point; C-Star point. Any significant difference in the resistance
measurement will indicate a phase imbalance.
Why we perform this test?
When do we need to measure low resistance?
Go/No Go
Ensure resistance is correct after motor repairs and before installation
Condition Monitoring
Identify unacceptable increase in resistance
Like Testing
Ensure ‘like’ elements of a system are of similar resistance
Diode test
This test has been included to show the integrity of diodes. It measures the forward and
reverse voltage drop over the device. Diode testing - diodes are not usually found on motors
but are on alternators and help with polarity control of the excitation circuit.
Digital Low Resistance Ohmmeter (DLRO)
When accurate very low resistance readings are required to be taken, the 4 wire ‘kelvin’ test
configuration is recommended.
Simply stated this test applies a current via 2 of the test leads while measuring the voltage with
the other 2 test leads, the result is displayed as a resistance. This test is unaffected by lead
or contact resistance and is particularly useful for measuring low winding resistances and the
contact resistance of control gear or overloads.
The test can be unidirectional or bidirectional. When testing connection built with dissimilar
materials it is recommended to use the bidirectional test.
Guide to Motor testing 29
Page 30
Megger Baker MTR105 – The Tests
Why we perform this test?
The DLRO test is performed where an accurate low resistance measurement is required in the
mΩ range.
Motor Direction of Rotation test
Determining the direction of rotation of a motor in relation to the phase rotation of the
supply is important, if not crucial for some applications where damage to pumps, compressors
or gearboxes can occur. The ‘bump’ test is often used prior to installation. The motor
is momentarily energised and the direction of rotation is noted with regard to the phase
connections.
Sometimes there is confusion as to how clockwise and anticlockwise rotation is perceived.
The answer lies with DIN EN 60034-8 where the direction of rotation of a motor is defined as
follows:
1. The direction of rotation is the direction viewed from the drive end.
2. The drive end is the side with the shaft extension.
3. For machines with two shaft extensions, the drive end is:
3.1. the end with the bigger shaft diameter
3.2. the end on the opposite side to the fan, (if both shaft extensions have the same
diameter).
So motors with clockwise rotation turn the shaft clockwise when viewed from the drive end
(viewing direction from drive end to non-drive end).
Fig 19: Clock wise motor
30 Guide to Motor testing
Page 31
Megger Baker MTR105 – The Tests
Motors with counter-clockwise rotation turn the shaft in a counter-clockwise direction when
viewed from the drive end (viewing direction from drive end to non-drive end).
Fig 20: Counter clock wise motor
As the direction of rotation for the motor and driven machine is defined with reference to the
respective shaft extension, the motor requires the opposite direction of rotation to that of the
driven machine.
That is to say, a counter-clockwise driven machine requires a clockwise-rotating motor and a
clockwise driven machine requires a counter-clockwise-rotating motor.
Why we perform this test?
The direction of rotation of the motor is determined to ensure that it matches the direction
of rotation of three phase supply voltage. If the motor direction of rotation does not match
the supply direction of rotation, apparatus under the control of the motor will not operate as
intended e.g. fans won’t blow and pumps won’t pump correctly.
This test may eliminate the need to perform a ‘bump’ test. Typically this test is performed on
a motor by pressing the start button ON and OFF quickly to determine the motor direction of
rotation. The bump test can cause problems when the motor is coupled to apparatus, which
is being driven by the motor and is not designed to run backwards. Here severe damage can
result to equipment such as screw compressors and some pumps.
Guide to Motor testing 31
Page 32
Megger Baker MTR105 – The Tests
Inductance
Phase-to-phase inductance measurements can be used to identify several conditions:
Poor or incorrect re-work e.g. reversed coil winding leads.
Power cable faults or power circuit main contacts.
Air gap eccentricity problems.
Shorted turns e.g. stator phase-to-phase and coil to coil.
Rotor porosity and lamination damage.
Cracked rotor bars or end rings.
Why we perform this test?
Inductance measurements can be useful in determining stator problems, even in cases where
the resistance measurements do not show a problem. The winding resistance of each phase
can be very low meaning that the amount of resistance per turn may seem negligible. With
such a negligible value it would be easy to see how losing a few turns may not be seen by
simply measuring resistance. Inductance, however, is exponentially affected by turn changes
within windings and therefore provides a more sensitive method to detect changes in stator
windings.
Capacitance
Measurement is trended and values to ground increasing over time indicate surface
contamination, high humidity, high temperature or insulation breakdown.
Temperature measurement
The temperature of the unit under test is measured in order to perform temperature correction.
Before an insulation resistance test can be carried out with temperature compensation enabled,
a temperature measurement must first be taken to establish the temperature of the unit under
test.
32 Guide to Motor testing
Page 33
Megger Baker MTR105 Overview
Megger Baker MTR105 Overview
Description
The MTR105 is a dedicated Static Motor
Tester with Megger’s tried and trusted suite
of insulation resistance tests (IR), plus all the
great traditional features and reliability of
Megger’s testers.
The MTR105 takes the test abilities of Megger’s proven IR test instruments adding DLRO four
wire Kelvin low resistance test, inductance and capacitance tests to provide a versatile motor
tester, all packaged in a robust hand held instrument, which up to now has simply not been
available.
Additionally the MTR105 incorporates temperature measurement and compensation (for IR
tests), motor direction of rotation plus supply phase rotation tests.
These new test abilities make the MTR105 a real world, versatile, hand held motor test
instrument.
The MTR105 comes in an over-moulded case, providing increased protection and robustness,
achieving an IP54 weatherproof rating.
Features
Guard terminal, to eliminate any surface leakage current.
Detachable test leads with interchangeable clips and probes for different applications.
Stores test results for up to 256 motors, which can be downloaded to a USB mass
storage device.
Rotary dial control, full graphic display, simple and easy to use.
Environmental protection to IP54, providing protection against moisture and dust ingress,
including the battery and fuse compartment.
Tough housing: A ‘rubber over moulding’ combines a tough shock absorbing outer
protection with excellent grip, on a strong modified ABS housing, providing a robust
case.
Rechargeable batteries with mains charger kit option.
Guide to Motor testing 33
Page 34
Megger Baker MTR105 Overview
Applications
Production tests for new manufactured motors and generators.
Test repaired and refurbished motors and generators.
Monitoring and maintenance of in service motors (off line) in the field.
Safety
The MTR105 is designed to be exceptionally safe to use. The fast detecting circuitry reduces
the likelihood of damage to the instrument if accidentally connected to live circuits or across
phases.
Meets the international requirements of IEC61010 and IEC61557.
Live circuit detection and test inhibit on all measurements with user notification (except
for direction of rotation measurements).
User selectable insulation test terminal lockout voltage 25 V, 30 V, 50 V, 75 V (default is
50 V).
Detection and inhibit functions when the protection fuse has failed.
Suitable for use on CAT III applications and supply voltages to 600 V.
Insulation resistance tests
Resistance range 100 Ω up to 200 GΩ.
Supports PI, DAR, Timed, Three Phase and Temperature Compensation.
Stabilised insulation test voltage accurate to -0% +2% ±2 V, which provides a more
accurate test voltage without the risk of over-voltage damage to circuits or components.
The output voltage is maintained between 0 and 2% throughout the test range.
Where a non-standard test voltage is required, a variable range allows the exact test
voltage to be selected from 10 V up to 999 V and is subject to the same stabilised output
control.
Dedicated buzzer button either ON, VISUAL or OFF.
Adjustable buzzer for minimum resistance limit (0.5 MΩ up to 1000 MΩ).
Buzzer sounds on test pass.
34 Guide to Motor testing
Page 35
Megger Baker MTR105 Overview
Voltmeter
Measures ac 10 mV up to 1000 V; dc 0 to 1000 V; TRMS (15 Hz up to 400 Hz).
Three phase supply and direction of rotation.
Continuity (Resistance) tests
Single automatic resistance range from 0.01 Ω to 1.0 MΩ.
Automatic test current selection uses the preferred test current for the load resistance
under test (200 mA up to 4 Ω).
Bi-directional tests option automatically reverses the current without reconnecting leads.
Lead resistance compensation (NULL) operates up to 10 Ω of resistance.
Dedicated buzzer switch either ON, VISUAL or OFF.
Adjustable buzzer for maximum resistance limit (1 Ω to 200 Ω in 12 steps).
Buzzer sounds on test pass.
DLRO Four wire Kelvin low resistance
Automatic resistance range from 1 mΩ up to 10 Ω.
Selectable auto or manual test.
Bi-direction or single direction.
Bi-directional tests option automatically reverses the current without reconnecting leads.
200 mA test current.
Motor Direction of Rotation test
Tests the direction of rotation of the motor under test and displays the phase sequence on
screen.
The connected motor is rotated in one direction and the display shows sequence of the phases
of rotation. The motor is next rotated in the opposite direction, the phases are checked again
and shown on the display.
Guide to Motor testing 35
Page 36
Megger Baker MTR105 Overview
Inductance, Capacitance and Resistance meter (LCR)
Auto inductive, capacitive and resistive test. Frequency selectable to 120 Hz or 1000 Hz.
In AUTO mode, the MTR105 automatically determines if the main element of the load is
inductive, capacitive or resistive and displays the result on screen.
Selectable inductance and capacitance test.
Temperature
Temperature measurement of unit under test, via the supplied thermocouple, allows
temperature compensation to be applied in insulation resistance tests.
Temperature measurement of the unit under test, is carried out via a thermocouple,
allowing temperature compensation to be applied to insulation resistance tests. A type “T”
thermocouple is supplied with the MTR but “J” and “K” type thermocouples can also be used.
Display
Full colour graphic display makes the MTR105 simple to understand and easy to use.
Guard Terminal
The Guard Terminal (G) is a third terminal on the connection panel.
Connection of the guard terminal, on certain applications, provides a return path for parallel
leakage currents, which could otherwise create significant errors in the insulation measurement.
This is especially so for surface contamination of equipment or cables.
Storage and download of results
Test results can be downloaded to a USB mass storage device , which can be accessed by
connecting to a PC or a Laptop running PowerDB.
Instrument software updates
Occasional information bulletins and software updates may be issued on the Megger web site.
36 Guide to Motor testing
Page 37
Specifications
Specifications
All quoted accuracies are at 20 °C (68 °F).
Insulation resistance
Volts Accuracy
50 V 10 GΩ ±2% ±2 digits ±4.0% per GΩ
100 V 20 GΩ ±2% ±2 digits ±2.0% per GΩ
250 V 50 GΩ ±2% ±2 digits ±0.8% per GΩ
500 V 100 GΩ ±2% ±2 digits ±0.4% per GΩ
1000 V 200 GΩ ±2% ±2 digits ±0.2% per GΩ
Polarisation index (PI): 10 min / 1 minute ratio
Dielectric absorption
ratio (DAR):
Guard terminal
performance
Resolution 0.1 kΩ
Short circuit/charge
current
Terminal voltage
accuracy
Test current 1 mA at min. pass value of insulation to a max. of 2 mA
Operation range 0.10 MΩ to 1.0 GΩ (IEC61557-2)
Leakage current
display
Voltage display ±3% ±2 digits ±0.5% of rated voltage
Note: Above specifications only apply when high quality silicone leads are being used
- as supplied with the instrument.
User configurable 15 s or 30 s t1 start time with t2 fixed at 60 s
<5% error at 500 kΩ parallel circuit resistance with 100 MΩ load
2 mA +0% -50% (IEC61557-2)
-0% +2% ±2 V
0.1 uA resolution 10% (±3 digits)
Continuity
Measurement 0.01 Ω to 1 MΩ
0 to 1000 kΩ analogue scale)
Accuracy ±3% ±2 digits (0 to 99.9 Ω )
±5% ±2 digits (100 Ω - 500 kΩ)
Test current 200 mA (–0 mA +20 mA)
(0.01 Ω - 4 Ω)
Polarity Single or Dual (factory default) polarity