Megger MOM200A, MOM600A User Manual

WWW.MEGGER.COM
User’s Manual
Art No.
ZP-BB04E
Doc.
BB0141NE V06 2015
Micro-ohmmeters
Micro-ohmmeters
NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS
© 2013, Megger Sweden AB. All rights reserved.
The contents of this manual are the property of Megger Sweden AB. No part of this work may be reproduced or transmitted in any form or by any means, except as permitted in written license agreement with Megger Sweden AB. Megger Sweden AB has made every reasonable attempt to ensure the completeness and accuracy of this document. However, the information contained in this manual is subject to change without notice, and does not represent a commitment on the part of Megger Sweden AB. Any attached hardware schematics and technical descriptions, or software listings that disclose source code, are for informational purposes only. Reproduction in whole or in part to create working hardware or software for other than Megger Sweden AB products is strictly prohibited, except as permitted by written license agreement with Megger Sweden AB.
TRADEMARK NOTICES
Megger® and Programma® are trademarks registered in the U.S. and other countries. All other brand and product names mentioned in this document are trademarks or registered trademarks of their respective companies.
Megger Sweden AB is certified according to ISO 9001 and 14001.
User’s Manual
Postal address:
Megger Sweden AB Box 724 SE-182 17 DANDERYD SWEDEN
T +46 8 510 195 00 F +46 8 510 195 95
seinfo@megger.com www.megger.com
Visiting address:
Megger Sweden AB Rinkebyvägen 19 SE-182 36 DANDERYD SWEDEN
BB0141NE ZP-BB04E MOM200A/600A
3
4 MOM200A/600A ZP-BB04E BB0141NE
Contents
1 Introduction
............................................................. 6
General ..............................................................6
Function description ...........................................6
2 Safety
............................................................. 8
General ..............................................................8
Symbols on the instrument ...................................... 8
Safety instructions ..............................................8
3 Control panels
........................................................... 10
Control panel – MOM200A .............................10
Control panel – MOM600A .............................11
4 Operating instructions
........................................................... 12
External measuring instrument............................... 13
Troubleshooting ..................................................... 13
5 Application examples
........................................................... 14
Measuring resistance in a breaker ....................14
Measuring resistance at bus-bar joints ..............15
Expanded measuring range ..............................16
Application example .............................................. 16
6 Specifications
........................................................... 18
Specifications MOM200A ................................18
Specifications MOM600A ................................18
BB0141NE ZP-BB04E MOM200A/600A
5
6 MOM200A/600A ZP-BB04E BB0141NE
1 INTRODUCTION
1
Introduction
General
This manual is for the MOM200A, and MOM600A micro-ohmmeters.
The micro-ohmmeter is designed to measure the resistances of breaker contacts, bus-bar joints, contact elements in bus-bars and other high-current links.
When contact resistance rises because of oxidation, loosened or improperly tightened threaded joints, temperatures rise abnormally at the points of contact. This abnormal heating reduces conductivity thereby accelerating the rise in temperature — and this often leads to serious trouble.
The micro-ohmmeter can be used to detect such pro­blems early so that they can be remedied long before trouble starts. Checking contact resistance at regular intervals provides a clear indication of the state of your system.
Function description
Connect the instrument to the object being tested.
After you have adjusted the instrument to provide the desired current through the test object (100 A for ex­ample), the actual voltage drop across the test object will be measured automatically, and all you have to do is press a button to display the actual resistance.
High current is generated and sent out by the instru­ment during measurement. A miniature circuit breaker and a thermal cut-out are provided to make certain this current doesn’t generate excessive heat inside the instrument.
The instrument is equipped with a device that guards against induction. A relay short-circuits the sensing input when the instrument’s ON/OFF switch is off and also when the instrument is in the m mode. To protect against external overvoltages, both the current output and the sensing input are decoupled to ground.
MOM200A is used for currents up to 200 A.
MOM600A can provide an output current of up to 600 A, and it can be set to six different measuring ranges.
Full-wave rectified current is used for measuring.