Megger MJ15 Operating Manual

BM15/MJ15 Insulation Testers
USER GUIDE
GUIDE DE L’UTILISATEUR
GEBRAUCHSANLEITUNG
M
GUÍA DEL USUARIO
Safety Warnings 3
General Description 4
Features and Controls 5
Working with Capacitive Loads 6
Operation
Preliminary Checks 7
Battery Replacement 7
Voltage Measurement 8
Insulation Testing 8
Choice of Test Leads 8
Using the Guard terminal 9
Specification 10
Accessories 12
Repair and Warranty 13
Before using the instrument, follow the separate instructions provided to fit either the locking or non-locking test button.
If the locking button is fitted, extra care must be taken. See page 6.
Symbols used on the instruments
F Risk of electric shock. G Caution, refer to accompanying documents t Equipment protected throughout by Double Insulation
(Class II)
c Equipment complies with current EU Directives
2
GSAFETY WARNINGS
‘Safety Warnings‘ and ‘Working with Capacitive Loads‘ must be read and understood before the instrument is used. Safety
precautions must be observed during use.
The circuit under test must be switched off, de-energised and isolated before any test connections are made.
Circuit connections must not be touched during a test.
On completion of a test, decaying voltage across the terminals is indicated on the display. Capacitive load circuits must be discharged
to below 60 V before disconnecting the test leads.
Capacitive load circuits should be shorted with a shorting link after discharge.
Remove the test leads from the instrument before opening the battery compartment.
Test leads and crocodile clips must be in good order, clean and with no broken or cracked insulation.
The instrument should not be used if any part of it is damaged.
U.K. Safety Authorities recommend the use of fused test leads when measuring voltage on high energy systems. See ‘Choice of Test
Leads‘.
NOTE
The instruments must only be used by suitably trained and competent persons.
NOTE
Users of this equipment and or their employers are reminded that Health and Safety Legislation requires them to carry out valid risk assessments of
all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as from inadvertent short circuits. Where the
assessments show that the risk is significant then the use of fused test leads constructed in accordance with the HSE guidance note GS38 ‘Electrical
Test Equipment for use by Electricians’ should be used. See ‘Choice of Test Leads’.
3
GENERAL DESCRIPTION
BM15, and MJ15 testers are completely self contained instruments designed for high voltage insulation resistance testing in the maintenance and servicing of rotating plant machinery, transformers, switchgear and industrial installations.
Tests can be performed at 500 V, 1000V, 2500 V or 5000 V. Insulation measuring range is 100 kΩ to 20 GΩ and Infinity. Automatic discharge for capacitive circuits under test is provided and decaying voltage displayed.
A guard terminal can be used to minimise the effects of surface leakage when carrying out insulation resistance tests.
Tests are initiated by pressing the BM15 ‘Test’ button (or by turning the MJ15 generator handle). Releasing the ‘Test’ button (or ceasing handle rotation) causes the instrument to default to ac/dc voltmeter mode, with a discharge resistor internally connected across the terminals. This feature will give decaying voltage indication following the testing of equipment possessing capacitance.
The moving coil meter operates a black pointer to display the readings on a single logarithmic black scale on a white scale-plate for clarity of reading. The movement is resiliently mounted for field use.
A slide - in ‘Pass Band‘ overlay can be inserted over the display. Appropriate Pass/Fail bands can be marked on these windows with a permanent marker for ‘Go / No Go’ testing.
BM15 is powered by eight 1,5 V (IEC LR6) cells.
Normal power for the MJ15 is by low voltage, hand cranked, brushless a.c generator. Fitting the battery container supplied, with eight 1,5 V IEC LR6 cells gives the instrument a dual (independent) supply capability. Both instruments are fitted with a battery check range, operated by pressing the ‘Test‘ push button. Cranking the handle too slowly (<180 RPM) results in an unstable
pointer reading. Excess handle speed cannot harm the instrument as the output voltage is electronically regulated.
The case is robust, yet light-weight, made from a flame retardant ABS, with a polycarbonate display window. Mounted on top of the case is a 6 position, rotary, range selection switch and a ‘Test‘ push button.
Three recessed sockets are provided, and marked ‘+’, ‘-’ and ‘G’. These have safety covers which open when the plugs are inserted. When inserted into the sockets, the shrouded test lead plugs lock into position. They are released by twisting the plug a quarter turn and pulling out.
For this reason, only the test leads supplied or suitable Megger replacement ones should be used.
Design safety features include:
External voltage, a.c. or d.c., displayed.
Load automatically discharged at the end of a test, and decaying
voltage displayed.
Test leads can lock into the case to prevent accidental disconnection.
4
FEATURES AND CONTROLS
Rotary Selector
Switch
Non Locking Button
(recommended
option)
Generator Handle (MJ15)
Locking Button
(Extra care must
be taken if this
option is chosen.
See page 6)
- Terminal
Guard Terminal
+ Terminal
TO INSERT TERMINAL PLUGS, PUSH IN - TO RELEASE, TWIST A QUARTER TURN AND PULL OUT
5
WORKING SAFELY WITH CAPACITIVE LOADS
G
Circuit connections and the instrument terminals may become
hazardous when connected to Capacitive loads.
1. These instruments are designed to safely charge and discharge capacitive loads up to 5 µF. To safeguard against malfunction however, you are advised to take your own precautions when working with capacitive loads. Remember that when charged, even low value capacitors can be fatal on contact .
2. Extra care must be taken if the locking Test button is selected.
3. Circuit connections must not be touched when testing.
Do not forget to release a locked Test button and discharge
any capacitance before touching the item under test or
disconnecting the test leads.
4. Care must be taken to prevent capacitive circuits becoming disconnected during a test, leaving the circuit in a charged state.
5. On completion of a test, the instrument indicates circuit decaying voltage. Do not disconnect test leads until the load capacitance has discharged to below 60 V.
6. The voltmeter and automatic discharge feature of the instruments should be regarded as additional safety features and not a substitute for normal safe working practice.
7. If any part of the instrument is damaged, it should not be used, but returned to the manufacturer or an approved service organization for repair.
6
PRELIMINARY CHECKS
Preliminary Performance Checks
The instrument will operate in any position, but best results are achieved when the instrument is face up, on a firm level surface. This is particularly true for hand cranked units to obtain a crank speed of >180 rev/min.
1) If battery cells are fitted, switch to Battery Check range and press the ‘Test‘ push button. Confirm that the pointer settles within the battery symbol portion of the scale.
2) With the test leads disconnected, set the rotary selector switch to the appropriate insulation range, press and hold down the ‘Test‘ button, (or turn the generator handle). The meter pointer should move up the scale briefly and then return to the ‘‘ (infinity) position on the scale. This establishes that there is no leakage through the instrument itself.
3) Check that the test leads and crocodile clips are in good order, clean and with no broken or cracked insulation. Connect two of the test leads to the ‘+’ and ‘-’ terminals and ensure that their clips are not touching anything.
4) Press the ‘Test‘ button again (or turn the generator handle) and observe the meter pointer. The pointer should rest over the ‘∞‘ position on the scale. If it does not, the test leads may be faulty and should be inspected more closely for damage. Replace them if necessary.
5) Connect the test lead clips together, press the ‘Test‘ button (or turn the generator handle) and observe the meter pointer. The meter should read ‘0Ω‘. If it indicates infinity or a high resistance value the leads may be open circuit and should be inspected further. Replace them if necessary. (Shorting the leads together and obtaining a ‘0 Ω‘ reading also indicates that the instrument is working).
Battery Replacement
GWARNING
The battery contacts are not isolated from the test leads. Remove the test
leads from the instrument before opening the battery compartment.
The cells are housed in a battery compartment in the base of the instrument. To change the cells, use a screwdriver to remove the battery cover securing screws and lift off the battery compartment cover. Observing the correct polarity as marked on the battery housing, install 8 replacement IEC LR6 (AA) cells. Replace and secure the battery compartment cover on completion.
7
OPERATION
Voltage measurement
When switched to the ‘V’ position, the instrument measures up to 600 V a.c. to the specified accuracy of the instrument. DC voltage is also indicated on the display, but not to the specified accuracy. When not testing (i.e. in standby mode) and connected to a live circuit, the instruments default to voltmeter (0 to 600 Volts a.c. or d.c.) irrespective of the rotary switch position. Any voltage present will immediately be shown. Thus indication is given that the item has not been completely de-energized. The instrument also monitors circuit discharge when the ‘Test‘ button is released following an insulation test on a capacitive item, e.g. a long cable.
Insulation Testing
After connecting the test leads to the instrument and carrying out the Preliminary Performance Checks:
1) Set the selector switch to the required test voltage. Connect the test leads to the isolated circuit to be tested, as follows:-
(a) For insulation tests to earth (ground):- Connect either test
lead to earth (ground) or the frame of the equipment,and the other lead to that part of the circuit to be tested.
b) For insulation tests between wires:- Connect a lead to the
core of each of the wires.
2) Press the ‘Test‘ button (or turn the generator handle).
3) The meter pointer will indicate the value of insulation resistance on the Ω scale.
If a capacitive circuit is tested, the pointer will initially deflect towards 0 Ω and then gradually rise to its final steady value as the capacitance is charged up to the output voltage of the tester.
If several successive readings of (infinity) are obtained, connect the two
farthest ends of the test leads together and carry out a check on the leads. A 0Ω reading should result which double checks that the leads are not disconnected or broken and therefore, the insulation resistance readings are correct.
Capacitive circuits automatically discharge through the tester when the ‘Test‘ button is released. Decaying discharge voltage will be indicated on the voltage scale. Wait a few moments for the voltage to decay to below 60 V before disconnecting the test leads.
Do not forget to release a locked Test button, and discharge
any capacitance before touching the item under test, or
disconnecting the test leads.
Choice of Test Leads
BM15/MJ15 are supplied with three unfused leads terminated in crocodile clips. These are the best leads to use for insulation tests on non-live circuits. The crocodile clips ensure that any capacitive load remains connected until it is automatically discharged at the end of a test.
GS 38 (UK Safety Authority Guidance Note) advises the use of fused test prods if the instrument is to be used for making voltage measurements on live, high energy circuits. These leads are available as an optional extra. See ‘Accessories’.
Fused prods must not be used for insulation testing. If the fuse should rupture, or the prods lose contact during a test, the system under test would remain charged without any apparent evidence of danger!
8
Using the Guard terminal (G)
For basic insulation tests and where there is little possibility of surface leakage affecting the measurement, it is unnecessary to use the guard terminal (if the insulator is clean and there are unlikely to be any adverse current paths). However in cable testing, there may be surface leakage paths across the insulation between the bare cable and the external sheathing due to the presence of moisture or dirt. Where it is required to remove the effect of this leakage, particularly at high testing voltages, a bare wire may be bound tightly around the insulation and connected via the third test lead to the guard terminal ‘G’.
The guard terminal is at the same potential as the negative terminal. Since the leakage resistance is effectively in parallel with the resistance to be measured, the use of the guard causes the current flowing through surface leakage to be diverted from the measuring circuit. The instrument therefore reads the leakage of the insulator, ignoring leakage across its surface.
Leakage Path
to ‘+’ve terminal
to ‘G’ terminal
Tightly bound bare wire
to ‘-’ve terminal
OPERATION BLOCK DIAGRAM
9
SPECIFICATION
Insulation
Range: 100 kΩ to 20 GΩ (also 0 Ω and ∞ ) Test Voltages (d.c.): 500 V, 1000 V, 2500 V & 5000 V Test Voltage Accuracy: ±5% of nominal test voltages on 20 MΩ load Test Voltage Stability: <±1% (180 r.p.m. to 240 r.p.m. MJ15) Insulation Accuracy see page 11 Short Circuit Current: 1,5 mA ± 0,5 mA Maximum capacitance of load: 5 µF Interference Rejection: 1 mA rms at 50 to 60 Hz Discharge Resistor: <500 kΩ
Voltage
Range: 0 to 600 V a.c. indication of d.c. Accuracy: see page 11
General
Overload rating: 720 V a.c. or d.c. Scale Length: 72 mm (96˚) Power Supply: BM15 8 x LR6 (AA alkaline or rechargeable) cells
MJ15 Low voltage brushless Generator or 8 x LR6 (AA alkaline) cell battery Battery life: Typically 2000 five second tests at 5 kV on 100 MΩ load Battery Indicator: Loaded battery test
10
Safety: IEC 61010-1 Non replaceable Fuse: 1 Amp, 250 V, HBC type (F) (20 mm x 5 mm) to IEC 127/1
This fuse protects the instrument against any faults occurring when using rechargable batteries. E.M.C: IEC 61326-1 Operational uncertainties: Refer to www.megger.com Temperature Range:
Operating: 0˚C to 30˚C (32˚F to 86˚F) at full specification Operating: -20˚C† to 50˚C (-4˚F to 122˚F) to temperature coefficient ±0,1% / ˚C Storage: -25˚C to 65˚C (-13˚F to 149˚F)
Humidity: 90% RH maximum at 40˚C (104˚F)
Dimensions: 220 mm x 160 mm x 115 mm (8,9 in x 6,3 in x 4,5 in) Weight: BM15 Approx 1.2 kg
MJ15 Approx 1,6 kg, or 1,8 kg with battery holder and cells.
Cleaning: Wipe the disconnected instrument with a clean cloth dampened with soapy water or Isopropyl Alcohol (IPA)
***Relates to transient overvoltage likely to be found in fixed installation wiring. *Relates to transient overvoltage likely to be found in special equipment or parts of equipment, telecommunication, electronic etc.
† Note: MJ15 will operate as normal by generator at full temperature range
BM15 will require new healthy battery cells to operate as normal at -20˚C
11
ACCESSORIES
SUPPLIED WITH THE INSTRUMENT PART NUMBER
User Guide 6172-209
Battery of 8 x 1,5 V LR6 (AA Alkaline) cells
3 x 3 m HV leads 8101-181
Test Record Card (5 supplied) 6172-111
(U.S. 210949)
Carrying case with lead storage 6420-117
Slide in Pass Band overlay (5 supplied) 6121-401
AVAILABLE AS AN OPTIONAL EXTRA
5 kV Fused Prod Set 6320-240
5 kV Calibration Box - CB101 6311-077
Test Record Card (Pack of 20) 6111-216
PUBLICATIONS
‘A Stitch In Time’ AVTM21-P8B
’Lowdown on HV d.c. Testing’ AVTM22P-1
12
REPAIR AND WARRANTY
The instrument circuit contains static sensitive devices, and care must be taken in handling the printed circuit board. If the protection of an instrument has been impaired it should not be used, and be sent for repair by suitably trained and qualified personnel. The protection is likely to be impaired if, for example, the instrument shows visible damage, fails to perform the intended measurements, has been subjected to prolonged storage under unfavourable conditions, or has been exposed to severe transport stresses.
New Instruments are Guaranteed for 1 Year from the
Date of Purchase by the User.
Note: Any unauthorized prior repair or adjustment will automatically
invalidate the Warranty.
Instrument Repair and Spare Parts
For service requirements for Megger Instruments contact:
Megger Limited or Megger Archcliffe Road Valley Forge Corporate Center Dover 2621 Van Buren Avenue Kent, CT17 9EN. Norristown, PA 19403 England. U.S.A.
Tel: +44 (0) 1304 502243 Tel: +1 (610) 676-8579
Fax: +44 (0) 1304 207342 Fax: +1 (610) 676-8625
ukenquires@megger.com usenquires@megger.com
or an approved repair company.
Approved Repair Companies
A number of independent instrument repair companies have been approved for repair work on most Megger instruments, using genuine Megger spare parts. Consult the Appointed Distributor / Agent regarding spare parts, repair facilities and advice on the best course of action to take.
Returning an Instrument for Repair
If returning an instrument to the manufacturer for repair, it should be sent freight pre -paid to the appropriate address. A copy of the Invoice and of the packing note should be sent simultaneously by airmail to expedite clearance through Customs. A repair estimate showing freight return and other charges will be submitted to the sender, if required, before work on the instrument commences.
13
GUIDE DE L’UTILISATEUR - TABLE DES MATIÈRES GEBRAUCHSANLEITUNG - S.26 GUÍA DEL USUARIO - P.38
Avertissements relatifs à la sécurité 15
Description Générale 16
Caractéristiques et Commandes 17
Opérations sur des charges capacitive 18
Exploitation
Vérifications Préliminaires 19
Remplacement des piles 19
Mesure des tensions 20
Essai d’isolement 20
Choix des câbles d’essai 20
Utilisation de la borne de protection 21
Spécifications 22
Accessoires 24
Réparation et Garantie 25
Avant d’utiliser l’instrument, suivre les instructions séparées pour monter soit le bouton d’essai verrouillable soit le bouton d’essai non verrouillable. Le bouton d’essai verrouillable exige des soins supplémentaires.
Symboles utilisés sur l'instrument
F Risque de choc électrique G Consulter le Guide de l'utilisateur t Équipement entièrement protégé par un isolement
double (Classe II).
c Équipement conforme aux Directives en vigueur de
l'UE.
14
GAVERTISSEMENTS RELATIFS À LA SÉCURITÉ
Les Avertissements relatifs à la sécurité et les instructions Opérations sur des charges capacitives doivent être lus et compris
avant d’utiliser l’instrument. Les précautions de sécurité doivent être observées pendant l’usage.
Le circuit à tester doit être coupé, désexcité et isolé avant d’effectuer des connexions d’essai quelconques.
Les connexions du circuit ne doivent pas être touchées pendant l’essai
A la fin de l’essai, la tension de déclin aux bornes est indiquée sur l’affichage. Les circuits à charge capacitive doivent être déchargés
en dessous de 60 V avant de déconnecter les câbles d’essai.
Les circuits à charge capacitive doit être court-circuités avec un cavalier de court-circuit après la décharge.
Enlever les câbles d’essai de l’instrument avant d’ouvrir le compartiment des piles.
Les câbles d’essai et les pinces crocodiles doivent être en bon état, propres et avec un isolement sans cassures ni fissures.
L’instrument ne doit pas être utilisé si l’un de ses constituants est endommagé.
Les Services de sécurité Britanniques recommandent l’utilisation de câbles d’essai équipés de fusibles pour lade la mesure de la
tension des systèmes à haute énergie. Voir “Choix des câbles d’essai”.
REMARQUE
Seule une personne düment formée et compétente doit se servir de cet instrument.
NOTE
ll est rappelé aux utilisateurs de cet instrument et/ou à leurs employeurs qu’ils doivent évaluer les risques de tous les travaux électriques de manière à
identifier les sources possibles de danger électrique et les risques de blessure tels que ceux des courts-circuits involontaires. Lorsque ces évaluations indiquent des risques importants, des câbles d’essai équipés de fusibles tels que recommandés par les Services de sécurité Britanniques doivent être
employés. Des sondes équipées de fusibles ne doivent pas être utilisées pour les essais d’isolement. En cas de rupture du fusible ou si les sondes
perdent contact pendant l’essai, le circuit testé peut rester chargé sans aucun signe évident du danger !
15
Loading...
+ 35 hidden pages