Megger MIT415 User Manual

M
Megger Limited Archcliffe Road, Dover Kent CT17 9EN England T +44 (0)1 304 502101 F +44 (0)1 304 207342 E
Megger Z.A. Du Buisson de la Couldre 23 rue Eugène Henaff 78190 TRAPPES France T +33 (0)1 30.16.08.90 F +33 (0)1 34.61.23.77 E infos@megger.com
Megger Pty Limited Unit 26 9 Hudson Avenue Castle Hill Sydney NSW 2125 Australia T +61 (0)2 9659 2005 F +61 (0)2 9659 2201 E ausales@megger.com
Megger Limited 110 Milner Avenue Unit 1 Scarborough Ontario M1S 3R2 Canada T +1 416 298 9688 (Canada only) T +1 416 298 6770 F +1 416 298 0848 E casales@megger.com
Megger products are distributed in 146 countries worldwide.
This instrument is manufactured in the United Kingdom. The company reserves the right to change the specification or design without prior notice.
Megger is a registered trademark
Part No. MIT415_2000-171_V01 1107 www.megger.com
M
MIT415
Insulation and continuity tester
User Guide
G Safety warnings
n Safety Warnings and Precautions must be read and
understood before the instrument is used. They must be observed during use.
n The circuit under test must be switched off, de-energised,
securely isolated and proved dead before test connections are made when carrying out insulation and continuity tests.
n Circuit connections and exposed-conductive-parts and other
metalwork of an installation or equipment under test
must not
be touched during testing.
n The live circuit warning and automatic discharge are additional
safety features, which may fail, and therefore safe working practices
must be observed.
n The voltage function will only work if the instrument is
functional and switched on.
n After insulation tests, capacitive circuits must be allowed to
discharge before disconnecting test leads.
n The instrument should not be used if any part of it is damaged. n All test leads, probes and crocodile clips must be in good order,
clean and with no broken or cracked insulation.
n Ensure that hands remain behind guards of probes/clips when
testing.
n National Safety Authorities may recommend the use of fused test
leads when measuring voltage on high-energy systems.
n Replacement fuses must be of the correct type and rating.
Failure to fit the correctly rated fuse may result in a safety hazard and may cause damage to the instrument in the event of an overload.
n The battery cover must be in place whilst conducting tests.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY
TRAINED AND COMPETENT PERSONS.
Users of this equipment and/or their employers are reminded that National Health and Safety Legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent short circuits. Where the assessments show that the risk is significant then the use of fused test leads may be appropriate.
Symbols used on the instrument:
F Caution: risk of electric shock
G Caution: refer to accompanying notes
Displayed on the LCD during an insulation test, warns that a hazardous voltage may exist at the test lead probes also observe voltage discharges to a safe level.
On battery cover see section 2.0 notes 10 and 11.
At terminals do not exceed rated input voltage.
t Equipment protected throughout by Double Insulation
(Class II)
c Equipment complies with relevant EU Directives
Equipment complies with ‘C tick’ requirements
Do not dispose of in the normal waste stream
Maximum input voltage 600 V rms
>
600V
G
LCD Display
Figure 3 LCD display
In continuity mode, if a voltage greater than 25 V exists, testing will be automatically inhibited and voltage measurement will be displayed.
SP5 Switched probe
The SP5 switch probe allows the user to start a test by pressing the [TEST] button on the probe, instead of on the instrument. This allows for complete hands-free testing and increases user safety.
AC/DC voltage and frequency measurements
Note: Measured voltage must not exceed 600 V phase to earth or Phase to Phase.
Note on TRMS measurement:
IN TRMS mode the MIT415 will measure both AC and DC components of the supply voltage (AC+DC). In DC mode only the DC component is measured.
1. Rotate selector switch to the ‘V’ position.
2. Connect test leads to the circuit under test.
3. Press the [TRMS] button to select DC or return to TRMS.
4. The measured voltage will be displayed on the main digital scale in units of V or mV, as appropriate In TRMS mode, the measured frequency (Hz) will be simultaneously displayed.
Insulation resistance testing - general
Safety note:
Insulation resistance testing is performed at high DC voltages and is
Auxiliary digital display
Continuity indicator
Lock indicator
Warning-refer to user guide
Fuse blown indicator
Out of range indicator
Lead null indicator
Audible alarm indicator
Battery condition indicator
TRMS indicator
Loading...
+ 9 hidden pages