30-kV HV Insulation Tester
MIT30
30 kV High Voltage Insulation Tester
n
Specifically designed for ungrounded test
samples only
n
Continuously variable test voltage, 0 - 30kV
n
Test current 0 - 330 µA
n
Output voltage accuracy, + 1.5% (full scale)
n
Built-in adjustable ionization indicator
n
Fail-safe grounding and “zero-start” switches
n
Rugged, compact, lightweight, and portable
MIT30
DESCRIPTION
The Megger MIT30 is a portable 30-kV insulation tester
that has been developed to undertake tests on UST
(ungrounded test samples). It satisfies the demand for a
variety of high voltage, high accuracy, and low current
applications. The MIT30 CANNOT be used on grounded/
earthed test samples. Otherwise, the unit will be damaged.
The MIT30 has a test current of up to 330 µA, and userselectable trip levels from 0 to 360 µA. The MIT30 provides
protection to the test piece against flashovers (arcing) and
further damage in the event of a breakdown. An audible
ionization indicator gives an audio indication of any
electrical discharges present during the test period.
The MIT30 can be used to perform step-voltage and proof
tests which, when incorporated into a routine maintenance
program, can aid in predicting potential failure before
breakdown occurs.
The MIT30 will operate from a wide range of input voltages
and frequencies. The unit will will operate from 85-264 V
ac with a frequency range of 47-440 Hz.
APPLICATIONS
The MIT30 checks the electrical insulation quality and
integrity of a wide variety of insulation material on UST
ungrounded systems.
Due to the unique combination of up to 30-kV high
voltage, high accuracy down to 100 nA, and low current
0-330 µA, the MIT30 has several applications:
n
Acceptance and maintenance testing of electrical plant:
n
Switchgear
n
Buss-bars
n
Capacitors
n
Defense industry
n
Aerospace Industry
n
Rubber safety glove testing
n
Testing of vacuum interrupters
n
Power equipment/plant manufacturers to perform
QA/QC production tests
MIT30
30-kV HV Insulation Tester
FEATURES AND BENEFITS
n
Ergonomic design ensures ease of use, hence subsequent
reduction in instrument learning time. This allows
the operator to undertake accurate safety testing in a
minimum amount of time.
n
Fast charging of high-capacitance samples reduces
testing times.
n
Current guard circuit ensures highly accurate
measurements and test results, thus avoiding external
interferences that could affect the accuracy of any test
results.
n
Highly accurate voltage and current outputs normally
associated with a test bench or laboratory test set, in a
rugged, field-proven case, takes high accuracy into the
field environment.
n
User selectable current trip points provide protection
to the test piece and the operator in the event of a
breakdown in the insulation of the object being tested.
n
Adjustable ionization indicator gives audible indication of
electrical discharges during test.
n
Universal input 85-264 V ac, 47-440 Hz makes the MIT30
suitable for a wide variety of applications.
n
Compact, lightweight and rugged construction makes the
unit ideal for field use.
n
Its rugged, field-proven case has in integrated carry
handle for easy carrying and an air transport pressure
relief value which allows the instrument to be safely
transported without damage.
Safety and Reliability
n
Fail-Safe, gravitationally invariant internal grounding
switch
n
Zero-Start safety provision
n
Cable interlock with bright LED, visible even in direct
sunlight
n
Triaxial HV output cable, with integrated HV, guard,
and current sense
n
Detachable HV output cable, shielded with interlock
provision
n
Output current overload relay
n
Switch control and indicating lights for high-voltage ON/
OFF
n
Protected output for both short/open circuit conditions
n
Fused power inlet module
SPECIFICATIONS
Output
Voltage: 0 to 30 kV dc (variable negative with respect to earth/
ground) 20MΩ minimum
Maximum Current: 330 µA @ 30 kV
Peak-Peak Ripple: <0.4%
Line Regulation: 0.03%
Load Regulation: 0.001%
Current
330 µA continuous @ 30 kV
User selectable trip from 0 to 360 µA
Accuracy
Voltage Meter: ±1.5% (full scale), 10 V resolution
Current Meter: ±1.5% (full scale), 100 nA resolution
Input
Mains: ac: 85 - 264 V ac, 47 - 440 Hz
<75 VA
Mechanical
Dimensions: 360 L x 304 W x 194 D mm (14 L x 12 L x 8 D in.)
Weight: 10 kg (22 lb)
Environmental
Operating Temperature: 14o F to 131o F (-10o C to +55o C)
Storage Temperature: -4o F to +158o F (-20o C to +70o C)
Humidity: 0 to 90% RH (non-condensing)
Maximum Altitude (full rating): 1600 m (MSL)
IP Rating
IP67 when closed for transport (Def Stan 81-41/STANAG 4280)
IP52 when in use
ORDERING INFORMATION
Item [Qty] Cat. No.
30-kV high-voltage insulation tester MIT30
Included Accessories
HV triaxial output cable, 3 m P1000-921
Input power cord, 120 V 17032
Input power cord, 230 V 17032-12
Instruction manual AVTMMIT30-EN
Optional Accessories
High-voltage resistance discharge stick 222070-62
“The Lowdown on High-Voltage
DC Testing” Guide AVTM22P-1
UK
Archcliffe Road, Dover
CT17 9EN England
T (0) 1 304 502101
F (0) 1 304 207342
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1019 USA
T 1 800 723 2861
T 1 214 333 3201
F 1 214 331 7399
OTHER TECHNICAL SALES OFFICES
Valley Forge USA, College Station USA,
Sydney AUSTRALIA, Täby SWEDEN, Ontario
CANADA, Trappes FRANCE, Oberursel
GERMANY, Aargau SWITZERLAND, Kingdom
of BAHRAIN, Mumbai INDIA, Johannesburg
SOUTH AFRICA, and Chonburi THAILAND
ISO STATEMENT
Registered to ISO 9001:2000 Cert. no. 10006.01
MIT30_DS_USen_V05
www.megger.com
Megger is a registered trademark