Megger MIT1020-2, MIT510-2 Application Note

APPLICATION NOTE
BE ON GUARD FOR EFFECTIVE TESTING
What does a GUARD terminal do? How does it work? Why does Megger specify GUARD performance? Where does this fit in with other instrument specifications? Testing transformers? Testing Cables? Testing bushings on outdoor oil circuit breaker? What are the real benefits of using the GUARD terminal?
Introduction:
The development of the insulation tester by Evershed & Vignoles is part of our electrical history. Insulation testers produced by Megger Instruments in Dover dates back to before to 1897.
Voltage outputs are now available up to 10 kV to suit all industrial and commercial applications. On the higher voltage testers (2.5 – 10 kV), which incorporate very high insulation ranges, is where the GUARD TERMINAL becomes a major benefit, when testing various devices that have long surface leakage areas of insulation.
What does a GUARD terminal do?
During insulation testing we are often so preoccupied with the resistance of the actual insulator we forget the resistance path on the outer surface of the insulation material. However this resistance path is very much a part of our measurement and can dramatically effect our measurements. For example if dirt is present on the outer surface of a bush the surface leakage current can be up to ten times that flowing through the actual insulation.
The surface leakage is essentially a resistance in parallel with the true insulation resistance of the material being tested. By using the guard terminal, performing a so-called three terminal test, the surface leakage current is ignored. This may be important when high values of resistance are expected such as when testing high voltage components like insulators, bushings and cable. These tend to have large surface areas that get exposed to contamination resulting in high surface leakage currents across them.
These include:
Larger diameter cables Porcelain bushings Power transformers H.V. circuit breakers
Such products exhibit long creepage paths across their insulation by the nature of their size. This will cause the unwanted surface leakage resistance to introduce errors, and is the reason the Guard terminal is used to enhance the accuracy of the measurement.
The total current that flows during an insulation resistance test is made up of three main components:
1. The charging current, which is charging up the objects capacitance.
2. An absorption current is the current which is being drawn into the insulation by the polarising of the electrons, initially high but drops over time, but at a slower rate than the charging current
3. The conduction or leakage current which is the small steady state current which divides into two parts:
a. The conduction path through the
insulation
b. The current flowing over the surface* of
the insulation.
*Surface leakage is the component of the insulation we do not want to measure if we just want to measure the insulation resistance of the material. By using the guard terminal, which is available on most HV insulation testers, the surface leakage can be excluded from the measurement.
1
Guard Terminal Application Note
5_kV_and_10_kV_IR_ap_en_v01
In applications with lower insulation resistance values (<100MW), such as in L.V. building wiring applications, this is not necessary, but with values of insulation above
How does it work?
Here we have a typical application for the GUARD terminal, testing an HV bushing. Without the GUARD terminal means that the leakage current flowing though
HV BUSHING UNDE R T EST
Leakage
Current
Through
Bushing
Surface
Leakage
Current
the 100MW as found in H.V. insulation applications the use of the guard terminal is often very important.
the bushing and across the surface is combined and therefore measured together by the instrument.
Now with the GUARD terminal now in use:
HV BUSHI NG UNDER TEST
Leakage
Current
Through
Bushing
Surface
Leakage
Current
Wire has been wrapped around the bushing and connected to the GUARD terminal, now the surface leakage flows to the GUARD terminal. Current flowing into the GUARD terminal is NOT measured by the instrument and so is ignored by the insulation resistance measurement.
Surface
Leakage
Current n ow
not being
measured
To better understand what is actually happening within the instrument we can look at the following diagram. Put simply the insulation tester has three main elements; the H.V. d.c. current source, the H.V. voltmeter and the current meter. The insulation resistance measurement is simply ohms law, measured voltage divided by the measured current. The GUARD terminal allows leakage current to bypass the current measurement, and so be ignored in the measurement.
Guard Terminal Application Note
2
5_kV_and_10_kV_IR_ap_en_v01
INST RUM ENT CIR CUIT SIM P LIFIED
Instrument
Terminal
BUSHING EQ UIVALENT CIRCUI T
Through Bushing Measured
-
0 .
2
CURRENT ME TER – ONLY
MEASURES C URRENT
THROUGH INSULATION
HV DC
CURRENT
SOURCE
Instrument
Terminal
G
Surface
Leakage
Current Ignored
5 M
o h m
0 .
2 5 M
o h m
+
Instrument
Terminal
However the story doesn’t end there, as you can see we have added example values to the above diagram. In this circumstance any instrument in the Megger MIT or S1 range of insulation testers will provide measurements with no more than 2% additional error. This is an important part of the comprehensive specification these
MIT and S1 5 kV and 10 kV range specify the GUARD terminal performance as:
2% Error guarding 500 kW leakage with 100 MW load
instruments provide.
Why does Megger specify GUARD performance?
To put it simply it is part of the uncertainty of the measurement. The more leakage current bypassing the current measurement means less left to measure. This then becomes a real test of the instruments ability to accurately measure this remaining test current and therefore give an accurate measurement of the insulation resistance.
The Megger specification reassures the user of its ability to cope under these conditions and provide meaningful results, and therefore properly diagnose the true condition of the insulation. Remember effective predictive maintenance relies on reliable trending of test results to provide early indication of failure. Time taken to carefully compensate for temperature variation can easily be wasted by poor results due to surface leakage not being correctly guarded.
Where does this fit in with other instrument specifications?
Safety?
These days we are more and more recognising the importance of test instrument safety. Insulation testers are not an exception. The complete range of Megger MIT and S1 5 kV and 10 kV insulation testers are CATIV 600 V to give the user maximum confidence.
So how does this relate to the performance of the GUARD terminal? Well, to be able to meet the stringent requirement of CATIV 600 V set out in IEC1010-1: 2001 the instrument has to be protected against 8 kV high-energy impulses on ALL terminals. The challenge is to maintain both impulse protection and the test performance of the instrument.
MAX ERROR 2 %
Leakage Curre nt
100M ohm
3
Guard Terminal Application Note
5_kV_and_10_kV_IR_ap_en_v01
Loading...
+ 5 hidden pages