Megger MFT1500/2 series, MFT1552, MFT1553, MFT1552 series, MFT1553 series user Manual

M
MFT1500/2, MFT1552 and MFT1553 Series Multifunction Tester
USER MANUAL
GSAFETY WARNINGS
Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.
The circuit under test must be switched off, de-energised and isolated before test connections are made when carrying out insulation and continuity
tests.
fault loop impedance test, or RCD test.
Circuit connections and exposed metalwork of an installation or equipment under test must not be touched.
The live circuit warning and Automatic discharge are additional safety features and should not be regarded as a substitute for normal safe working
practices.
Do not change the rotary switch positions while a test is in progress.
The LCD ‘neon’ voltage indicators cannot reveal a Neutral - Earth reversal. They cannot be relied upon to identify circuit correctness and are for
guidance only.
After insulation tests, capacitive circuits must be allowed to discharge before disconnecting test leads.
The instrument should not be used if any part of it is damaged.
Test leads, probes and crocodile clips must be in good order, clean and with no broken or cracked insulation.
Ensure that hands remain behind guards of probes/clips when testing.
UK Safety Authorities recommend the use of fused test leads when measuring voltage on high energy systems.
Replacement fuses must be of the correct type and rating.
Failure to fit the correctly rated fuse will result in damage to the instrument in the event of an overload.
The battery cover must be in place whilst conducting tests.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS.
Users of this equipment and/or their employers are reminded that Health and Safety Legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent short circuits. Where the assessments show that the risk is significant then the use of fused test leads constructed in accordance with the HSE guidance note GS38 'Electrical Test Equipment for use by Electricians' should be used.
2
CONTENTS
Safety Warnings 2 Description 4
Overview of MFT1500 Series 4
Instrument layout 4 Display 4 Control panel 4 Front switch panel 4 Connection panel 4
Test leads 4 Battery /fuse warning, fitting and replacement 5 Setup 5 Operation 6
General operation 6
Live circuit warning 6
Test button lock 6
Backlight (MFT1502/1552 and 1553 only) 6
Auto shut-off 6
Polarity indication 6
Illuminated switched probe 6
Operation 6
Voltage measurement (V) 7 Continuity 7
Continuity measurement 7
Lead null 8
Continuity buzzer 8
Buzzer threshold 8 Insulation 8
Insulation resistance 8
Insulation voltage ranges 8
Test lock 9 Loop impedance 9
NO TRIP (15 mA) loop test 10
High Current loop test 10
P-N and P-P loop test 11 PFC 12 Residual current device (RCD testing) 14
1/2I, I, 5I, 0 & 180° 14 RCD auto test sequence (MFT1552 only) 15
Ramp testing 15 DC Sensitive RCDs 16 Bluetooth downloading (MFT1553 only) 17 Technical specification 21 Accessories 24 Repair and warranty 25
Appendix - Additional Bluetooth information (Attaching a Dongle) 26
Symbols used on the instrument are:
F Caution: risk of electric shock G Caution: refer to accompanying notes t Equipment protected throughout by Double
Insulation (Class II)
c Equipment complies with current EU directives.
>500V
G
Max 300 V CAT III
Maximum nominal system voltage of 500 V
Maximum 300 V a.c. CAT III to Earth
g
3
DESCRIPTION
Thank you for purchasing the MFT1500 Multifunction Tester. The MFT1500 series of tester is compact and designed to perform all of the functions required by the electrical contractor to fully test domestic, commercial and industrial wiring. Specially designed to comply with UK, European and other International wiring regulations and standards, the MFT may be used on all single and three phase systems with rated voltages up to 300 Volts a.c. rms to earth/ground.
All test leads supplied with the MFT form part of the measuring circuit of the instrument and must not be modified or changed in any way, or be used with any other electrical instrument or appliance.
A plug severed from the power cord
MUST be destroyed, as a plug
with bare conductors is hazardous in a live socket outlet.
OVERVIEW OF MFT SERIES
BLUE (RCD)
ORANGE (BUZZER THRESHOLD)
BLACK (BACKLIGHT) (1502/1552/1553 ONLY)
YELLOW (TEST BUTTON)
RED (TEST LOCK) (BLUETOOTH)
Connection
indicators
Ohms
Null
Warning
Continuity and insulation connections
Switched probe
Test selection
Display
Contact Noise warning
Battery cover (side panel)
RCD range
selection
Fuse warning
Battery status
Temperature
warning
LOOP & RCD connections
Mains plug test lead
4
REPLACING FUSES AND BATTERIES
Battery and Fuse fitting/Replacement
Battery type: 8 x 1.5 V alkaline LR6 (AA). Rechargeable batteries must not be used. Fuse type: 500 mA (F) HBC 10 kA 500 V Low battery warning symbol Fuse blown symbol
Battery charge indication
The battery charge level is automatically indicated when the MFT is turned on.
To replace batteries
Switch off the instrument and disconnect (the instrument) from any electrical circuits.
Remove the battery cover.
Slide out the battery clip and remove the dead cells.
Refit new batteries following correct polarity as marked on the battery holder.
Replace the battery holder and cover.
Note:- Incorrect battery cell polarity can cause electrolyte leakage, resulting in damage to the instrument.
To replace the fuse
Should the main fuse fail, the symbol fwill be displayed.
Disconnect the instrument from any circuits.
Remove the battery cover as above.
The blown fuse should be replaced with a 500 mA (F) HBC 10 kA 500 V fuse (Megger part no.25950-039)
f
b
Replace the battery cover.
Setup RCD Touch voltage selection (to select either 25 V or 50 V)
1. With the instrument turned OFF, hold down the YELLOW test button
and turn the left hand rotary switch to any ON position.
2. Keep the button held down until the instrument displays the ‘SET’
warning.
3. Now release the TEST button.
4. Press the TEST button again to view the current setting for the touch
voltage.
The display shows the touch voltage limit, either ‘25 V’ or ‘50 V’.
Note: The MFT can also display the measured Touch Voltage on a bar­graph display.
If the touch voltage display is active, a bar-graph display will also appear.
5. Press the ORANGE (buzzer) button to change the touch voltage limit
setting.
6. Press the BLUE (RCD) button to turn the bar-graph display ON or
OFF.
7. Press the TEST button to exit from the set-up menu.
5
OPERATION
GENERAL OPERATION
Note: These functions are generally applied and not limited to an individual test function.
Live circuit warning - Test inhibit
Testing is automatically inhibited if:
During insulation testing - an external voltage >55 V is present on the terminals
During continuity testing - a voltage >10 V is present on the terminals
During RCD or No-Trip loop testing - a voltage >270 V is present
During Loop testing - a voltage >480 V is present
Test button lock
To lock the test button hold down the RED L test lock button whilst
holding down the YELLOW TEST button.
Intelligent backlight (MFT1502/1552/1553 only)
Both the display and range knobs have a backlight. To activate, press the BLACK Jbutton.
To disable the Intelligent backlight function, press the BLACK and the RED Llock button together.
Repeat to enable the intelligent backlight.
Instrument auto shut-off
Automatically activated after 5 minutes of instrument inactivity.
To restore operation press the RED lock button or switch the instrument off and on.
J
button
Polarity indication
If connected to a single-phase power supply by a plug or by the 3-wire lead set, three LCD ‘neons‘ marked L-PE, N-PE and L-N respectively will indicate supply polarity.
If a voltage is detected between their respective two wires, the ‘neon’(s) will activate.
L-PE N-PE L-N
Correct supply indication
Live –neutral swapped
Any other combinations should be investigated further. However the LCD 'NEONS' cannot be relied upon to identify circuit correctness and are for guidance only.
Note:- The presence of a voltage between phase and earth does not prove earth continuity, as the earth could have a high resistance and a voltage would still be measured. To test earth continuity refer to the sections on loop resistance or RCD testing.
Warning: The LCD 'Neons' are invalid when using the two wire lead-set and should be ignored.
ILLUMINATED SWITCHED PROBE SPL1000 (MFT1502/1552/1553 ONLY)
The Illuminated switched probe accessory replaces the RED 4 mm test lead. It can be used anywhere that the 4 mm lead set is specified in this user guide, and it will also add extra resistance to a loop test measurement.
Operation (SPL1000)
The YELLOW button duplicates the function of the TEST key on the instrument, allowing quick and easy testing.
6
The BLACK switch operates a white LED, which illuminates the probe tip for use when testing under low light levels.
There is also a visual indication via a red/green LED to notify the user of the display status, the meanings are as follows:
Green : A valid result is present on the display or the
continuity buzzer is buzzing.
Red: A warning is being shown on the display, testing
will be inhibited.
VOLTAGE MEASUREMENT [V] TEST LEAD CONNECTION
OPTION 1
2 wire lead set
BLACK
RED
BLACK
PROBE
OPTION 2
Switched probe
OPTION 3
Mains plug test lead L-E
PLUG
OR Using the mains plug lead set (OPTION3)
Voltage between the L and E pins is displayed
Note:- When connected to the circuit under test the instrument will automatically display AC or DC voltage measurement up to 500 V.
Warning: The voltage measurement range should not be used for verifying power has been removed (isolated) from a circuit for testing of documentation, a test lamp should be used.
This function will continue to work if the fuse is blown.
CONTINUITY
Z
Warning: Prior to any continuity testing, ensure the circuits under test are isolated and not live
TEST LEAD CONNECTION
OPTION 1
2 wire lead set
BLACK
RED
OPTION 2
Switched probe
BLACK
Set the Rotary range knob to the [V] range
(The position of the right hand ‘mA’ rotary range knob does not matter)
Two wire lead set or Switched Probe connection
Using the 2-wire lead set OPTION 1 or OPTION 2
1. Connect the test leads as shown.
2. DC Voltage (V) or AC Voltage (V~) is automatically displayed.
PROBE
Set the left hand rotary range knob to the range required. (The position of the right hand rotary range knob does not matter).
Continuity measurement can be made using one of the 2 options shown above.
A continuity measurement is made automatically when the test leads
7
are connected to the circuit under test. The contact symbol on the display closes when a resistance of approximately 200 kor less is detected.
Lead null (up to 9.99 )
Short test probes or clips together and press the YELLOW TEST button on the instrument (or on the switched probe if fitted). The displayed to indicate lead null is active.
This null value is stored until the YELLOW TEST button is pressed again.
To cancel the LEAD NULL, press the YELLOW TEST button.
Continuity Buzzer
Test leads OPTIONS 1 or 2 above
The MFT buzzer will sound continuously if the resistance between the leads is less than a set limit (Default value 2 ).
If being used with the illuminated switched probe (OPTION 2) continuity is also indicated by a GREEN LED on the probe.
To turn off the buzzer press the TEST button whilst in BUZZER mode. The display will indicate ON or OFF status.
Buzzer threshold
The resistance at which the buzzer stops sounding can be changed to meet individual test requirements. Press the ORANGE Zbutton to select the resistance limit.
Selectable limits of 2 , 5 , 10 , 20 , 50 and 100 .
This setting is stored even when the instrument is switched off.
Z
z
will be
Notes:­Method of measurement
The 2-wire lead set must be used for this measurement. The instrument produces a d.c. voltage of nominally 4,5 V with a current limit of at least 200 mA when measuring 2 .
Possible sources of error
Measurement results can be affected by the following:
The impedance of operating circuits connected in parallel.
Impedance such as inductors that vary during the measurement.
A poor connection to the circuit under test, which can give readings as
much as 100 m(0,10 ) high. The best way to avoid this error is to use sharp prods and press these firmly into the conductors being measured.
INSULATION RESISTANCE [M] [250 V] [500 V] [1000 V]
Warning: Prior to any insulation testing, ensure the circuits under test are isolated and not live.
TEST LEAD CONNECTION
OPTION 1
2 wire lead set
BLACK
RED
OPTION 2
Switched probe
BLACK
PROBE
8
Set the left hand rotary range knob to the required INSULATION Range.
250 V Insulation measurement to 99.9 M
500 V Insulation measurement to 299 M
1000 V Insulation measurement to 499 M
(The position of the right hand rotary range knob does not matter.)
To initiate insulation testing press and hold the YELLOW TEST button on the instrument or the switched probe if connected.
Release the test button after the displayed reading has settled.
TEST LOCK
To lock down the test button press the YELLOW TEST button followed by the RED LOCK L button.
A warning triangle
Press the YELLOW TEST button to stop the test.
Note:- A 1000 V warning is displayed whenever the 1000 V range is selected and the test button pressed
Warning: The test voltage will be permanently present on the test probes or crocodile clips when in the locked modes.
Notes:- Auto discharge - Auto discharge facility automatically and safely discharges connected circuit after test via 250 kresistor.
Live circuit warning - operates when connected to Live circuits > 25 V.
Test Inhibited - an audible alarm operates at >55 V. The instrument will not perform a test until the voltage source has been removed.
G will appear in the display while the test lock is active.
Method of measurement
A current limited (2 mA) d.c source is used, and the resistance is calculated from measurements of the voltage and current.
The voltage is only present when the test button is pressed or the test lock is active. A measurement of the terminal voltage is made before the test and if this exceeds 55 V the test is disabled. The reading is stable with a circuit capacitance up to 5 µF.
LOOP IMPEDANCE [LOOP] TESTING
Loop impedance measurement can be made via installation sockets using the plug terminated test lead at any other convenient point on the installation, using a two/three wire lead set.
The MFT will measure the loop resistance from the supply end of the standard test leads, allowing for their resistance.
NON TRIPPING LOOP TESTS [NO TRIP]
Set the LEFT rotary range knob to the required LOOP range as described below:
OPTION 1
3 wire measurement
BLACK GREEN
RED
(The position of the right hand rotary range knob does not matter.)
OPTION 2
Mains plug test lead
PLUG
9
[NO TRIP] LOOP-TESTING - SINGLE PHASE TESTING ONLY
The NO TRIP loop test is a high resolution low current earth loop resistance measurement (Loop L-PE 0.01 ) range which does not trip RCDs with a rated current 30 mA or higher.
[NO TRIP] PHASE TO EARTH LOOP IMPEDANCE MEASUREMENT (AT A POWER SOCKET)
Test Lead set: OPTION 2
1. Select
NO TRIP Loop test range.
2. Insert the plug into an installation socket.
3. Supply voltage and polarity are displayed.
4. The test will ‘beep’ and automatically start when voltage is detected.
5. Measured loop value is displayed
If desired the test can be repeated by pressing the YELLOW TEST button.
[NO TRIP] EARTH LOOP IMPEDANCE MEASUREMENT (NOT AT A POWER SOCKET)
Test Lead set: OPTION 1
1. Firmly connect the GREEN lead to EARTH, the BLACK lead to NEUTRAL and the RED lead to PHASE.
2. Perform the loop test, as above for power socket.
If desired the test can be repeated by pressing the YELLOW TEST button.
PFC MEASUREMENT [NO TRIP PFC]
Use Test Lead set OPTION 1 or OPTION 2
1. Select NO TRIP PFC test range.
2. Connect the leads as shown.
3. Supply voltage and polarity are displayed.
4. The test will ‘beep’ and automatically start when sufficient voltage is detected.
5. The measured PFC result is displayed.
HIGH CURRENT LOOP-TESTING [HI]
Single Phase and Phase to Phase loop testing on circuits that are NOT protected by RCD
OPTION 1
2 wire lead set
GREEN
RED
OPTION 2
Mains plug test lead
PLUG
Set the instrument to the [HI] Loop test range
High current Phase to Earth loop impedance measurement (at a power socket):
Test Lead set: OPTION 2
1. Insert the plug into an installation socket.
2. Supply voltage and polarity are displayed.
3. The test will ‘beep’ and automatically start when voltage is detected.
10
Loading...
+ 22 hidden pages