MFT1500/2, MFT1552 and MFT1553 Series
Multifunction Tester
USER MANUAL
Page 2
GSAFETY WARNINGS
■ Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.
■ The circuit under test must be switched off, de-energised and isolated before test connections are made when carrying out insulation and continuity
tests.
■ Continuity of protective conductors and earthed equipotential bonding of new or modified installations must be verified before carrying out an earth
fault loop impedance test, or RCD test.
■ Circuit connections and exposed metalwork of an installation or equipment under test must not be touched.
■ The live circuit warning and Automatic discharge are additional safety features and should not be regarded as a substitute for normal safe working
practices.
■ Do not change the rotary switch positions while a test is in progress.
■ The LCD ‘neon’ voltage indicators cannot reveal a Neutral - Earth reversal. They cannot be relied upon to identify circuit correctness and are for
guidance only.
■ After insulation tests, capacitive circuits must be allowed to discharge before disconnecting test leads.
■ The instrument should not be used if any part of it is damaged.
■ Test leads, probes and crocodile clips must be in good order, clean and with no broken or cracked insulation.
■ Ensure that hands remain behind guards of probes/clips when testing.
■ UK Safety Authorities recommend the use of fused test leads when measuring voltage on high energy systems.
■ Replacement fuses must be of the correct type and rating.
Failure to fit the correctly rated fuse will result in damage to the instrument in the event of an overload.
■ The battery cover must be in place whilst conducting tests.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS.
Users of this equipment and/or their employers are reminded that Health and Safety Legislation requires them to carry out valid risk assessments of all
electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent short circuits. Where the assessments
show that the risk is significant then the use of fused test leads constructed in accordance with the HSE guidance note GS38 'Electrical Test Equipment for
use by Electricians' should be used.
2
Page 3
CONTENTS
Safety Warnings2
Description4
Overview of MFT1500 Series4
Instrument layout4
Display4
Control panel4
Front switch panel4
Connection panel4
Test leads4
Battery /fuse warning, fitting and replacement5
Setup5
Operation6
General operation6
Live circuit warning 6
Test button lock6
Backlight (MFT1502/1552 and 1553 only)6
Auto shut-off6
Polarity indication6
Illuminated switched probe6
Operation6
Voltage measurement (V)7
Continuity7
Continuity measurement7
Lead null8
Continuity buzzer8
Buzzer threshold8
Insulation8
Insulation resistance8
Insulation voltage ranges8
Test lock9
Loop impedance9
NO TRIP (15 mA) loop test10
High Current loop test10
P-N and P-P loop test11
PFC12
Residual current device (RCD testing)14
1/2I, I, 5I, 0 & 180°14
RCD auto test sequence (MFT1552 only)15
Ramp testing 15
DC Sensitive RCDs16
Bluetooth downloading (MFT1553 only)17
Technical specification21
Accessories24
Repair and warranty25
Appendix - Additional Bluetooth information
(Attaching a Dongle)26
Symbols used on the instrument are:
FCaution: risk of electric shock
GCaution: refer to accompanying notes
tEquipment protected throughout by Double
Insulation (Class II)
cEquipment complies with current EU directives.
>500V
G
Max 300 V
CAT III
Maximum nominal system voltage of 500 V
Maximum 300 V a.c. CAT III to Earth
g
3
Page 4
DESCRIPTION
Thank you for purchasing the MFT1500 Multifunction Tester. The
MFT1500 series of tester is compact and designed to perform all of the
functions required by the electrical contractor to fully test domestic,
commercial and industrial wiring. Specially designed to comply with UK,
European and other International wiring regulations and standards, the
MFT may be used on all single and three phase systems with rated voltages
up to 300 Volts a.c. rms to earth/ground.
All test leads supplied with the MFT form part of the measuring circuit of
the instrument and must not be modified or changed in any way, or be
used with any other electrical instrument or appliance.
A plug severed from the power cord
MUST be destroyed, as a plug
with bare conductors is hazardous in a live socket outlet.
OVERVIEW OF MFT SERIES
BLUE (RCD)
ORANGE (BUZZER THRESHOLD)
BLACK (BACKLIGHT)
(1502/1552/1553 ONLY)
YELLOW (TEST BUTTON)
RED (TEST LOCK)
(BLUETOOTH)
Connection
indicators
Ohms
Null
Warning
Continuity and
insulation
connections
Switched probe
Test selection
Display
ContactNoise warning
Battery cover (side panel)
RCD range
selection
Fuse warning
Battery status
Temperature
warning
LOOP & RCD
connections
Mains plug test
lead
4
Page 5
REPLACING FUSES AND BATTERIES
Battery and Fuse fitting/Replacement
Battery type: 8 x 1.5 V alkaline LR6 (AA). Rechargeable batteries must not
be used.
Fuse type: 500 mA (F) HBC 10 kA 500 V
Low battery warning symbol
Fuse blown symbol
Battery charge indication
The battery charge level is automatically indicated when the MFT is turned
on.
To replace batteries
Switch off the instrument and disconnect (the instrument) from any
electrical circuits.
Remove the battery cover.
Slide out the battery clip and remove the dead cells.
Refit new batteries following correct polarity as marked on the battery
holder.
Replace the battery holder and cover.
Note:- Incorrect battery cell polarity can cause electrolyte leakage,
resulting in damage to the instrument.
To replace the fuse
Should the main fuse fail, the symbol fwill be displayed.
Disconnect the instrument from any circuits.
Remove the battery cover as above.
The blown fuse should be replaced with a 500 mA (F) HBC 10 kA 500 V
fuse (Megger part no.25950-039)
f
b
Replace the battery cover.
Setup
RCD Touch voltage selection (to select either 25 V or 50 V)
1. With the instrument turned OFF, hold down the YELLOW test button
and turn the left hand rotary switch to any ON position.
2. Keep the button held down until the instrument displays the ‘SET’
warning.
3. Now release the TEST button.
4. Press the TEST button again to view the current setting for the touch
voltage.
The display shows the touch voltage limit, either ‘25 V’ or ‘50 V’.
Note: The MFT can also display the measured Touch Voltage on a bargraph display.
If the touch voltage display is active, a bar-graph display will also
appear.
5. Press the ORANGE (buzzer) button to change the touch voltage limit
setting.
6. Press the BLUE (RCD) button to turn the bar-graph display ON or
OFF.
7. Press the TEST button to exit from the set-up menu.
5
Page 6
OPERATION
GENERAL OPERATION
Note: These functions are generally applied and not limited to an
individual test function.
Live circuit warning - Test inhibit
Testing is automatically inhibited if:
During insulation testing - an external voltage >55 V is
present on the terminals
During continuity testing - a voltage >10 V is present on the
terminals
During RCD or No-Trip loop testing - a voltage >270 V is
present
During Loop testing - a voltage >480 V is present
Test button lock
To lock the test button hold down the RED L test lock button whilst
holding down the YELLOW TEST button.
Intelligent backlight (MFT1502/1552/1553 only)
Both the display and range knobs have a backlight. To activate, press the
BLACK Jbutton.
To disable the Intelligent backlight function, press the BLACK
and the RED Llock button together.
Repeat to enable the intelligent backlight.
Instrument auto shut-off
Automatically activated after 5 minutes of instrument inactivity.
To restore operation press the RED lock button or switch the instrument
off and on.
J
button
Polarity indication
If connected to a single-phase power supply by a plug or by the 3-wire lead
set, three LCD ‘neons‘ marked L-PE, N-PE and L-N respectively will indicate
supply polarity.
If a voltage is detected between their respective two wires, the ‘neon’(s)
will activate.
L-PE N-PE L-N
Correct supply indication
Live –neutral swapped
Any other combinations should be investigated further. However the LCD
'NEONS' cannot be relied upon to identify circuit correctness and are for
guidance only.
Note:- The presence of a voltage between phase and earth does not prove
earth continuity, as the earth could have a high resistance and a voltage
would still be measured. To test earth continuity refer to the sections on
loop resistance or RCD testing.
Warning: The LCD 'Neons' are invalid when using the two wire lead-set
and should be ignored.
The Illuminated switched probe accessory replaces the RED 4 mm test
lead. It can be used anywhere that the 4 mm lead set is specified in this
user guide, and it will also add extra resistance to a loop test measurement.
Operation (SPL1000)
The YELLOW button duplicates the function of the TEST key on the
instrument, allowing quick and easy testing.
6
Page 7
The BLACK switch operates a white LED, which illuminates the probe tip
for use when testing under low light levels.
There is also a visual indication via a red/green LED to notify the user of
the display status, the meanings are as follows:
Green :A valid result is present on the display or the
continuity buzzer is buzzing.
Red: A warning is being shown on the display, testing
will be inhibited.
VOLTAGE MEASUREMENT [V]
TEST LEAD CONNECTION
OPTION 1
2 wire lead
set
BLACK
RED
BLACK
PROBE
OPTION 2
Switched
probe
OPTION 3
Mains plug
test lead L-E
PLUG
OR Using the mains plug lead set (OPTION3)
Voltage between the L and E pins is displayed
Note:- When connected to the circuit under test the instrument will
automatically display AC or DC voltage measurement up to 500 V.
Warning: The voltage measurement range should not be used for
verifying power has been removed (isolated) from a circuit for testing of
documentation, a test lamp should be used.
This function will continue to work if the fuse is blown.
CONTINUITY
Z
Warning: Prior to any continuity testing, ensure the circuits under test are
isolated and not live
TEST LEAD CONNECTION
OPTION 1
2 wire lead
set
BLACK
RED
OPTION 2
Switched
probe
BLACK
Set the Rotary range knob to the [V] range
(The position of the right hand ‘mA’ rotary range knob does not matter)
Two wire lead set or Switched Probe connection
Using the 2-wire lead set OPTION 1 or OPTION 2
1. Connect the test leads as shown.
2. DC Voltage (V) or AC Voltage (V~) is automatically displayed.
PROBE
Set the left hand rotary range knob to the range required.
(The position of the right hand rotary range knob does not matter).
Continuity measurement can be made using one of the 2 options shown
above.
A continuity measurement is made automatically when the test leads
7
Page 8
are connected to the circuit under test. The contact symbol on the
display closes when a resistance of approximately 200 kΩ or less is
detected.
Lead null (up to 9.99 Ω)
Short test probes or clips together and press the YELLOW TEST button on
the instrument (or on the switched probe if fitted). The
displayed to indicate lead null is active.
This null value is stored until the YELLOW TEST button is pressed
again.
To cancel the LEAD NULL, press the YELLOW TEST button.
Continuity Buzzer
Test leads OPTIONS 1 or 2 above
The MFT buzzer will sound continuously if the resistance between the
leads is less than a set limit (Default value 2 Ω).
If being used with the illuminated switched probe (OPTION 2) continuity
is also indicated by a GREEN LED on the probe.
To turn off the buzzer press the TEST button whilst in BUZZER mode. The
display will indicate ON or OFF status.
Buzzer threshold
The resistance at which the buzzer stops sounding can be changed to
meet individual test requirements. Press the ORANGE Zbutton to select
the resistance limit.
Selectable limits of 2 Ω, 5 Ω, 10 Ω, 20 Ω, 50 Ω and 100 Ω.
This setting is stored even when the instrument is switched off.
Z
z
will be
Notes:Method of measurement
The 2-wire lead set must be used for this measurement. The instrument
produces a d.c. voltage of nominally 4,5 V with a current limit of at least
200 mA when measuring 2 Ω.
Possible sources of error
Measurement results can be affected by the following:
■ The impedance of operating circuits connected in parallel.
■ Impedance such as inductors that vary during the measurement.
■ A poor connection to the circuit under test, which can give readings as
much as 100 mΩ (0,10 Ω) high. The best way to avoid this error is to
use sharp prods and press these firmly into the conductors being
measured.
Warning: Prior to any insulation testing, ensure the circuits under test are
isolated and not live.
TEST LEAD CONNECTION
OPTION 1
2 wire lead
set
BLACK
RED
OPTION 2
Switched
probe
BLACK
PROBE
8
Page 9
Set the left hand rotary range knob to the required INSULATION Range.
250 V Insulation measurement to 99.9 MΩ
500 V Insulation measurement to 299 MΩ
1000 V Insulation measurement to 499 MΩ
(The position of the right hand rotary range knob does not matter.)
To initiate insulation testing press and hold the YELLOW TEST button on
the instrument or the switched probe if connected.
Release the test button after the displayed reading has settled.
TEST LOCK
To lock down the test button press the YELLOW TEST button followed by
the RED LOCK L button.
A warning triangle
Press the YELLOW TEST button to stop the test.
Note:- A 1000 V warning is displayed whenever the 1000 V range is selected
and the test button pressed
Warning: The test voltage will be permanently present on the test probes
or crocodile clips when in the locked modes.
Notes:- Auto discharge - Auto discharge facility automatically and safely
discharges connected circuit after test via 250 kΩ resistor.
Live circuit warning - operates when connected to Live circuits > 25 V.
Test Inhibited - an audible alarm operates at >55 V. The instrument
will not perform a test until the voltage source has been removed.
G will appear in the display while the test lock is active.
Method of measurement
A current limited (2 mA) d.c source is used, and the resistance is calculated
from measurements of the voltage and current.
The voltage is only present when the test button is pressed or the test lock
is active. A measurement of the terminal voltage is made before the test and
if this exceeds 55 V the test is disabled. The reading is stable with a circuit
capacitance up to 5 µF.
LOOP IMPEDANCE [LOOP] TESTING
Loop impedance measurement can be made via installation sockets using
the plug terminated test lead at any other convenient point on the
installation, using a two/three wire lead set.
The MFT will measure the loop resistance from the supply end of the
standard test leads, allowing for their resistance.
NON TRIPPING LOOP TESTS [NO TRIP]
Set the LEFT rotary range knob to the required LOOP range as
described below:
OPTION 1
3 wire
measurement
BLACK
GREEN
RED
(The position of the right hand rotary range knob does not matter.)
OPTION 2
Mains plug
test lead
PLUG
9
Page 10
[NO TRIP] LOOP-TESTING - SINGLE PHASE TESTING ONLY
The NO TRIP loop test is a high resolution low current earth loop resistance
measurement (Loop L-PE 0.01 Ω) range which does not trip RCDs with a
rated current 30 mA or higher.
[NO TRIP] PHASE TO EARTH LOOP IMPEDANCE MEASUREMENT
(AT A POWER SOCKET)
Test Lead set: OPTION 2
1.Select
NO TRIP Loop test range.
2. Insert the plug into an installation socket.
3. Supply voltage and polarity are displayed.
4. The test will ‘beep’ and automatically start when voltage is
detected.
5.Measured loop value is displayed
If desired the test can be repeated by pressing the YELLOW TEST button.
[NO TRIP] EARTH LOOP IMPEDANCE MEASUREMENT (NOT AT A
POWER SOCKET)
Test Lead set: OPTION 1
1. Firmly connect the GREEN lead to EARTH, the BLACK lead to
NEUTRAL and the RED lead to PHASE.
2.Perform the loop test, as above for power socket.
If desired the test can be repeated by pressing the YELLOW TEST
button.
PFC MEASUREMENT [NO TRIP PFC]
Use Test Lead set OPTION 1 or OPTION 2
1.Select NO TRIP PFC test range.
2.Connect the leads as shown.
3.Supply voltage and polarity are displayed.
4.The test will ‘beep’ and automatically start when sufficient
voltage is detected.
5.The measured PFC result is displayed.
HIGH CURRENT LOOP-TESTING [HI]
Single Phase and Phase to Phase loop testing on circuits that are NOT
protected by RCD
OPTION 1
2 wire lead
set
GREEN
RED
OPTION 2
Mains plug
test lead
PLUG
Set the instrument to the [HI] Loop test range
High current Phase to Earth loop impedance measurement (at a
power socket):
Test Lead set: OPTION 2
1.Insert the plug into an installation socket.
2.Supply voltage and polarity are displayed.
3.The test will ‘beep’ and automatically start when voltage is
detected.
10
Page 11
4.Measured loop value is displayed.
If desired the test can be repeated by pressing the YELLOW
TEST button.
High current Phase-Earth loop impedance (not at a power
socket):
Test Lead set: OPTION 1
1.Connect the GREEN lead to EARTH and the RED lead to PHASE
2. Supply voltage is displayed.
Warning: The LCD 'Neons' are invalid when using the two wire lead-set
and should be ignored.
3.The test will automatically start when voltage is detected.
4.Measured loop value is displayed.
If desired the test can be repeated by pressing the YELLOW
TEST button.
BONDED METALWORK TESTING
Test Lead set: OPTION 1
1.Connect the GREEN lead to the bonded metalwork.
2.Connect the RED lead to PHASE.
3.Supply voltage is displayed.
Warning: The LCD 'Neons' are invalid
and should be ignored.
4.The test will automatically start when voltage is detected.
5.Measured loop value is displayed.
when using the two wire lead-set
If desired the test can be repeated by pressing the YELLOW
TEST button.
PHASE-NEUTRAL OR PHASE-PHASE LOOP IMPEDANCE
Test Lead set: OPTION 1
1.Connect the GREEN lead to NEUTRAL and the RED lead to
PHASE (or the 2nd PHASE for Phase to Phase loop
measurement).
2.The supply voltage is displayed.
Warning: The LCD 'Neons' are invalid when using the two wire lead-set
and should be ignored.
3.The test will automatically start when voltage is detected.
4.Measured loop resistance is displayed.
If desired the test can be repeated by pressing the YELLOW
TEST button.
11
Page 12
PROSPECTIVE FAULT CURRENT [PFC HI]
OPTION 1
2 wire measurement
GREEN
RED
OPTION 2
Mains plug
test lead
PLUG
Set the instrument to the [PFC Hi] range
Hi current PFC is a 25 A two wire test.
PHASE TO EARTH PFC
Test Lead set: OPTION 1,2
1.For Single phase measurement connect the test leads as
shown above.
For Phase to Phase measurement connect the GREEN lead
to the 2nd Phase.
2.Supply voltage and polarity are displayed.
3.The test will ‘beep’ and automatically start when voltage is
detected.
4.Measured PFC value is displayed.
If desired the test can be repeated by pressing the YELLOW
TEST button.
PHASE TO NEUTRAL PFC
As for the 25 A Phase to Earth PFC test but with the following test lead
connections:
1.Connect the GREEN lead to the NEUTRAL and the RED lead to
PHASE.
2.The test will ‘beep’ and automatically start when voltage is
detected.
3.Measured PFC value is displayed.
Notes:The PSCC of a circuit is the largest Prospective Fault Current (PFC). In a
single phase system, this would be the larger of the earth loop PFC and
the neutral loop PFC. In a multi-phase system phase-phase loops also need
to be considered and these can be measured using the Loop 25 A switch
position.
The PFC is calculated by using the sum:-
Nominal supply voltage
PFC =
Loop resistance
The supply voltage used in the calculation depends on the measured
voltage. The instrument uses the following voltage values:-
Actual measured voltageNominal voltage
> 45 V and < 80 V55 V
>80 V and <150 V110 V
>150 V and <300 V230 V
>300 V400 V
12
Page 13
PFC measurement accuracy
An accurate PFC measurement requires an accurate measurement of the
loop resistance. The difference of a few digits in the loop resistance
measured will have a large effect on the PFC displayed.
Noise Indication
The symbol is displayed when excessive noise caused by other
equipment exists on the circuit under test. This noise can effect the
accuracy of the loop measurement. The operator is advised to repeat the
measurement or, if the noise symbol continually appears, investigate the
cause.
Method of measurement
The phase-earth, phase-neutral or phase-phase loop resistance can be
measured. The instrument takes a current from the supply and measures
the difference between the unloaded and loaded supply voltages. From this
difference it is possible to calculate the loop resistance. The test duration
will depend on the loop resistance value and the presence of noise on the
supply.
The NO TRIP loop test range performs a test with a current of up to 25 A
flowing Line to Neutral to measure the resistance of the source and line
wires, followed by a current of 15 mA flowing Line to Earth to measure the
resistance of the earth wire .
Possible sources of error
The reading depends on a measurement of the supply voltage and
therefore noise or transients caused by other equipment during the test
could cause an error in the reading. One way to check for these is to do
two tests and look for any difference in value. The instrument will detect
some sources of noise and warn the user, where other instruments may
give an incorrect reading. Any leakage current as a consequence of other
appliances connected to the supply under test may affect the reading. If the
Phase-Earth loop is being measured, this leakage may be due to filter
capacitors, etc.
Test results may be adversely affected by supply voltage fluctuations or
electrical ‘noise’ during a measurement. It is recommended that tests are
repeated and the results verified, if measurement results are considered
abnormal.
Errors can be reduced by:-
■ The two-wire lead set with prods and make a firm connection
to clean conductors.
■ Several tests and take the average value.
■ Ensure that potential sources of noise in the installation are isolated
(switched off), eg: automatically switched loads or motor controllers
■ Ensuring that the instrument is calibrated.
Thermal Protection
To protect the MFT from overheating during Loop testing, thermal
protection is fitted. If the message ‘HOT’ appears in the display when loop
testing, the instrument must be allowed to cool down before further
attempts are made at loop testing.
13
Page 14
RESIDUAL CURRENT DEVICE [RCD] TESTING
OPTION 1
2 wire lead
set
GREEN
RED
OPTION 2
Switched
probe
OPTION 3
Mains plug
test lead
GREEN
PROBE
The MFT can perform the following RCD tests:
1/2INon-tripping test at half the rated RCD trip current for 2
seconds, during which the RCD should not trip.
ITripping test at the rated RCD trip current. The trip time will
be displayed.
5ITripping test at 5 x the rated RCD trip current. The trip time
will be displayed in milliseconds.
DC1/2I, I and 5I tests can be performed as DC tests.
0 or 180°
Some RCDs are sensitive to the polarity of the supply, i.e
whether the test current is applied with the instantaneous
voltage rising or falling. Trip tests should therefore be
performed with both polarities 0° and 180° and the
maximum time recorded.
Ramp Test
Used to check the trip current of an RCD.
PLUG
Note: The Breaker symbol indicates whether the test
function selected is a NON-TRIPPING or TRIPPING test:
CLOSED = NON-TRIPPING test
OPEN = TRIPPING test
1/2 I RCD Testing
Set the LEFT [RCD] rotary range knob to the [ 1/2I ] RCD test range.
Set the RIGHT [mA] rotary range knob to current rating of the RCD under
test.
Test lead set: OPTION 1, 2 or 3
1. Ensure the right hand Rotary knob is set to the correct range
for the RCD under test.
2.Press the YELLOW TEST button.
3.After 2 seconds the message >1999 ms is displayed.
4.If enabled, the touch voltage is displayed on the bar-graph
display.
If the RCD trips unexpectedly the message ‘trP’ will be
displayed.
1 x I RCD Testing
Set the LEFT [RCD] rotary range knob to the [ I ] RCD test range.
1.Press the YELLOW TEST button.
2.The RCD trip time is displayed.
3.If enabled, the touch voltage is displayed on the bar-graph
display.
14
Page 15
4.If the RCD fails to trip, >400 ms is displayed (indicating a
failed test).
5 x I RCD Testing
Set the LEFT [RCD] rotary range knob to the [ 5I ] test range.
1.Press the YELLOW TEST button.
2. The trip time will be displayed.
3.If enabled, the touch voltage will be displayed on the bargraph display.
4. If the RCD fails to trip, >40 ms is displayed (indicating a failed
test).
Note:- The instrument can only test up to 1 A a.c. or 300 mA d.c. Any tests
that exceed these limits are disabled.
0 or 180° testing
0° or 180° is selected by pressing the BLUE button on the side of the MFT
on either the I or 5I RCD test.
The
I, and 5I RCD tests should be performed at 0° and 180° and the
greater trip time recorded.
AUTO RCD TEST SEQUENCE (MFT1552 AND MFT1553 ONLY)
The AUTO test function will run the 1/2I, I, and 5I plus 0º and 180º tests
automatically, and store the test results, while the operator stands by the
RCD to reset it when it trips.
To start the RCD AUTO-test:
1.Connect the RED test lead to the “Live” terminal of the RCD and
GREEN and BLACK test leads to the earth conductor.
Alternatively connect the mains plug test lead to a supply outlet.
2.Select the AUTO RCD TEST function on the main range knob,
and the appropriate RCD current rating on the small range
knob.
3.Press the TEST button to start the test. The display will show
‘t1’ to ‘t5’ to indicate the current test.
t1 =
1/2I, t2 = I at 0º, t3 = I at 180º, t4 = 5I at 0º and t5
= 5I at 180º
4.Reset the RCD each time it trips.
5. On completion of testing the results can be recalled by
repeatedly pressing the lock button. To indicate each test result,
segments of the bar graph are displayed as below:
NO BARS =
ONE BAR =
FIVE BARS =
Example shows a 13.9 ms trip time at
RAMP TEST
The RCD trip current is measured by applying a test current of half the
rated trip current and increasing this every 200 ms. When the RCD trips,
the current flowing is recorded and displayed in mA.
To determine the trip current of an RCD.
1. Select the appropriate RCD rated current on the right hand
rotary switch.
2. Select the RAMPtest on the left hand range knob.
1/2 I test
I test
5I test
5I on 180º.
15
Page 16
3. Press the YELLOW TEST button
4. The trip current is displayed.
5. If the RCD fails to trip, ">***mA" will be displayed, where
*** indicates the last test current applied.
DC SENSITIVE RCD TESTING
D.C. sensitive RCDs are tested with a pulsed waveform. The RMS current is
√2 x the rated operating current of the RCD. As with the normal RCDs,
these should be tested with 0° and 180° polarity.
1.Select the appropriate RCD rated current on the right hand
rotary switch.
2. Select the [
1/2I, I, or 5I] test on the left hand range knob
3.Use the BLUE button to cycle through the test options,
selecting DC and the required polarity.
4.Press the YELLOW TEST button
5. The trip time will be displayed in ms.
6.If enabled, the touch voltage will be displayed on the bargraph display.
7. If the RCD fails to trip, ">400 ms" will be displayed.
TIME DELAYED (SELECTIVE) RCDS
The selective RCD testing is enabled by a long press on the blue degree
button. As selective RCD test mode is enabled the MFT will emit a long
beep and the display will show the exclamation mark (!) symbol. Once the
selective RCD mode is chosen, testing of the RCDs can be performed in
the same way as normal RCDs (see above for Residual Current Device
(RCD) Testing, ). To disable selective RCD mode press the degree button
for two seconds.
Method of measurement
The two wire lead or plug should be used for this measurement. A
constant current source is connected across the supply and the time taken
for the supply to trip is measured by the instrument in ms.
Possible sources of error
Measurement results can be affected by the following:
■ Significant operating errors can occur if loads, particularly rotating
machinery and capacitive loads are left connected during tests.
■ A poor connection to the circuit under test.
Thermal Protection T
The RCD circuit has thermal protection fitted to prevent overheating in
the event of multiple ramp tests being performed. The T symbol or the
message "Hot" will be displayed. Allow the instrument time to cool down
before continuing.
16
Page 17
BLUETOOTH DOWNLOADING
Bluetooth Pairing (PC or Laptop)
1. Set the MFT Range knob to the Bluetooth SET UP position.
2. Press the Bluetooth (Lock) button on the MFT, the MFT will show
‘- - -‘ if no pairing exists or the last three digits of a paired identity if
already paired.
If these three digits are the last three digits of your Bluetooth identity
code (e.g. 963) then you are already paired with it. If you don’t
recognise them or are unsure then continue with the pairing process.
3. Push the Bluetooth (Lock) button again to start the pairing process, the
MFT will display ‘<> - - - -‘
4. Activate the “Add Bluetooth Devices” tool on your PC or mobile device
to search for Bluetooth devices.
5. Your PC or mobile device will prompt for an “access key”. When this
happens enter 1234.
6. The MFT will display the last three digits of your Bluetooth identity
code when a successful pairing has been achieved (e.g. <>963).
Bluetooth Pairing (Windows CE)
1. Set the MFT Range knob to the Bluetooth SET UP position.
2. Press the Bluetooth (Lock) button on the MFT, the MFT will show
‘- - -‘ if no pairing exists or the last three digits of a paired identity if
already paired. If these three digits are the last three digits of your
Bluetooth identity code (e.g. 963) then you are already paired with it. If
you don’t recognise them or are unsure then continue with the pairing
process.
3. (i)Turn on your PDA and select ‘Start’ then ‘Settings’.
(ii)Select the ‘Connections’ Tab.
(iii)Select the ‘Bluetooth’ symbol and select ‘Turn on’.
(iv)Select ‘Use Bluetooth Manager’ option.
(v)Select ‘Menu’ and ‘Paired Devices’
(vi)If there are no paired MFTs shown then select ‘Add’.
Note:If there is a MFT symbol present check that it has the serial
number displayed as your MFT. If this isn’t the case then delete the MFT
from the PDA and continue with the pairing procedure.
(vii) Select the Magnifying Glass symbol to start the pairing process.
4. Push the Bluetooth (Lock) button again to start the pairing process, the
MFT will display ‘<> - - - -‘
5. Once paired double click the MFT symbol on the PDA and enter the
access key code 1234.
6. The MFT will display the last three digits of your Bluetooth identity
code when a successful pairing has been achieved (e.g. <>963).
Bluetooth Pairing (Windows Mobile 5 Smartphone)
1. Set the MFT Range knob to the Bluetooth SET UP position.
2. Press the Bluetooth (Lock) button on the MFT, the MFT will show
‘- - -‘ if no pairing exists or the last three digits of a paired identity if
already paired. If these three digits are the last three digits of your
Bluetooth identity code (e.g. 963) then you are already paired with it.
If you don’t recognise them or are unsure then continue with the
pairing process.
17
Page 18
3. (i)Turn on your mobile and press the left hand button to select
‘Start’ menu.
(ii)Select the ‘Connections’ symbol.
(iii) Select the ‘Bluetooth’ symbol.
(iv) Press the right hand Menu button.
(v)Select the Devices symbol.
(vi)Select the ‘Menu’ symbol and the select the ‘New’ symbol.
(vii) If there are no paired MFTs shown then select ‘Add’.
Note:If there is a MFT symbol present check that it has the serial
number displayed as your MFT. If this isn’t the case then delete the MFT
from the PDA and continue with the pairing procedure.
4. Push the Bluetooth (Lock) button again to start the pairing process,
the MFT will display ‘<> - - - -‘
5. On the Windows Mobile 5 once paired select the MFT symbol on the
mobile and enter the access key code 1234.
6. The MFT will display the last three digits of your Bluetooth identity
code when a successful pairing has been achieved (e.g. <>963).
7. On the Windows Mobile 5 press the left hand menu button four times
to select the following in sequence; ‘Next’, ‘OK’, ‘Next’ and ‘Done’.
8. Continue to press the left hand button until you return to the
Windows Desktop display.
18
Bluetooth Pairing (Palm v5)
1. Set the MFT Range knob to the Bluetooth SET UP position.
2. Press the Bluetooth (Lock) button on the MFT, the MFT will show
‘- - -‘ if no pairing exists or the last three digits of a paired identity if
already paired.
If these three digits are the last three digits of your Bluetooth identity
code (e.g. 963) then you are already paired with it. If you don’t
recognise them or are unsure then continue with the pairing process.
3. (i)Select ‘Bluetooth’ from the main Palm desktop and make sue
that it is turned on..
(ii)Select the ‘Setup Devices’ symbol.
(iii)Select the ‘Trusted Devices’ symbol.
(iv)Select the ‘Add Devices’ symbol.
Note:If there is a MFT symbol present check that it has the serial
number displayed as your MFT. If this isn’t the case then delete the MFT
from the Palm and continue with the pairing procedure.
4. Push the Bluetooth (Lock) button again to start the pairing process, the
MFT will display ‘<> - - - -‘
5. On the Palm device once paired select the MFT symbol on the display
and select ‘OK’.
6. Enter the access and select key code ‘1234’ and select the top left hand
menu button ‘OK’.
7. The MFT will display the last three digits of your Bluetooth identity
code when a successful pairing has been achieved (e.g. <>963).
8. On the Palm device select the ‘Done’ twice to get back to the Bluetooth
Page 19
screen.
9. Select the ‘Home’ button to return to the main Palm desktop.
Bluetooth Pairing (Symbian S60 Version 3)
1. Set the MFT Range knob to the Bluetooth SET UP position.
2. Press the Bluetooth (Lock) button on the MFT, the MFT will
show ‘- - -‘ if no pairing exists or the last three digits of a paired
identity if already paired.
If these three digits are the last three digits of your Bluetooth identity
code (e.g. 963) then you are already paired with it. If you don’t recognise
them or are unsure then continue with the pairing process.
3. (i)Select ‘Bluetooth’ from the main Symbian desktop and make sue
that it is turned on..
(ii)Select the right hand Tab to show paired devices..
(iii)Select the top left hand menu button then the ‘New Paired
devices’ symbol.
Note:If there is a MFT symbol present check that it has the serial
number displayed as your MFT. If this isn’t the case then delete the MFT
from the Symbian and continue with the pairing procedure.
4. Push the Bluetooth (Lock) button again to start the pairing process, the
MFT will display ‘<> - - - -‘
5. Once paired select the MFT symbol on the display and select ‘OK’.
6. Enter the access and select key code ‘1234’ and select ‘OK’.
7. The MFT will display the last three digits of your Bluetooth identity code
when a successful pairing has been achieved (e.g. <>963).
8. On the Symbian device select the top left hand menu button’Yes’ to
authorise the Symbian device to make the connection automatically.
9. Select ‘Exit’ to return to the main Symbian desktop.
Downloading Test Results
Table of Symbols
SymbolDefinition
L - ELive to Earth Test
L – nLive to Neutral Test
n – ENeutral to Earth Test
L - LLive to Live Test
r1Circuit Protective Conductor
r2R1 + R2
r12Live
rr1Ring Circuit Phase-Phase
rr2Ring Circuit CPC-CPC
rrnRing Circuit Neutral-Neutral
19
Page 20
TESTING WITH A PAIRED MFT1553
Insulation Testing
1. Perform a Insulation test described previously
2. Press the Bluetooth (Lock) button once to display the various options; LE, L-n, n-E and L-L.
3. Press the Bluetooth (Lock) button repeatedly to scroll through these
options until the one you need is reached.
4. Press and hold the Bluetooth (Lock) button again to send the test result
to your PC or mobile device. The MFT test result will flash whilst the
result is transmitted.
5. The test results will now appear in the correct box in the certificate open
on your PC or mobile device.
Continuity Testing
1. Perform a Continuity test described previously
2. Press the Bluetooth (Lock) button once to display the various options;
r2, r12, r1, rr1 and rr2.
3. Press the Bluetooth (Lock) button repeatedly to scroll through these
options until the one you need is reached.
4. Press the Bluetooth (Lock) button again to send the test result to your
PC or mobile device. The MFT test result will flash whilst the result is
transmitted.
5. The test results will now appear in the correct box in the certificate open
on your PC or mobile device.
Loop Testing
1. Perform a Loop test described previously
2. Press the Bluetooth (Lock) button once to display the various options; Ln, L-E and L-L.
3. Press the Bluetooth (Lock) button repeatedly to scroll through these
options until the one you need is reached.
4. Press the Bluetooth (Lock) button again to send the test result to your
PC or mobile device. The MFT test result will flash whilst the result is
transmitted.
5. The test results will now appear in the correct box in the certificate open
on your PC or mobile device.
RCD Testing
1. Perform a RCD test described previously
2. Press and hold the Bluetooth (Lock) button again to send the test result
to your PC or mobile device. The MFT test result will flash whilst the
result is transmitted.
3. The test results will now appear in the correct box in the certificate open
on your PC or mobile device.
4. Each of the RCD tests (1/2I, I @ 0° & 180° and 5 x I @ 0° & 180°) will
automatically be sent to the correct box when the Bluetooth (Lock)
button is pushed and held.
5. For Auto RCD tests all results are automatically transmitted to the correct
boxes on the certificate (the appropriate value must be selected on the
PC or mobile device for each box when prompted) when the Bluetooth
(Lock) button is pushed and held on the MFT.
To force a test result into a specific certificate box double click the box
within the certificate and then push and hold the Bluetooth (Lock) button.
20
Page 21
TECHNICAL SPECIFICATIONS
Electrical specification
Voltage range
The voltage will enable the user to ascertain if a system is live prior to
testing.
Accuracy ±2% ±2 digits
Voltage a.c. - 000 V - 500 V 50/60Hz
Voltage d.c. - 000 V - 500 V (Indication of polarity above 10 V)
Insulation ranges (to EN 61557-2)
Accuracy ±2% ±2 digits up to 99 MΩ
Short circuit current <2 mA
1 mA at min. pass value of insulation specified in BS7671, HD384 and
IEC364
250 V 0.01 - 99.9 MΩ
500 V 0.01 - 299 MΩ
1000 V 0.01 - 499 MΩ
250 V, 500 V and 1 kV into 1 mA load
Output voltage+20% - 0% at rated load or less.
Auto discharge facility safely discharges connected circuit after test.
Live circuit warning/inhibit when connected to live circuits (Threshold
55 V)
I tripA ramp test that displays actual trip current .
DC sensitiveA DC test current at I current.
Current accuracy 1/2I -8% to -2%
I +2% to +8%
5I +2% to +8%
Intrinsic Accuracy of ramp test current ±3%
Trip time
accuracy±1% ±1 ms
Touch (Fault) Voltage
Displayed range
Remote Probe MFT1502 only (Optional on MFT1501)
Torch feature
SafetyCLASS 1 LED to IEC 60825:2001
Interchangeable tips
Lengths 30 mm GS38
Battery9 V PP3
0 V - 100 V
Error +5% to +15%
±0.5V
5 mm White LED
1500 mcd
112 mm GS38
Page 23
Red/Green LED
RED
indicates that the instrument is displaying a warning (eg volts
on an insulation range)
GREEN indicates that the display on the instrument is valid or that
the Continuity Buzzer on the instrument is sounding.
Power Supply
Instrument8 x 1.5 V Alkaline cells type LR6 (AA cells)
Note: Rechargeable batteries must not be used
Illuminated switched Probe 1 x 9 V Alkaline cell type PP3 (6LR61)
Fuses
Instrument:- Replaceable 500 mA (F) HBC 10 kA 500 V
Non-replaceable 7 A (SIBA 70-065-63) x 2
Non-replaceable 1 A
Probe:-Non-replaceable 7 A (SIBA 70-065-63)
Safety
Double insulated to IEC1010-1:2001, Installation Category III, 300 V phase to
earth, 500 V phase to phase.
In addition Probe designed to meet IEC 1010-031:2002, Double insulated to
Installation Category III, 300 V phase to earth, 500V phase to phase.
EMC
In accordance with IEC61326 including amendment No. 1
Environmental
Operating range -5 to +40ºC
Operating Humidity 90% RH at 40ºC max
Storage temperature -25 to 65ºC
Maximum altitude 2000 m
Dust and water protection: Instrument IP54, Probe no rating.
IEC61557
Complies with the following parts of 61557, Electrical safety in low voltage
systems up to 1000 V a.c. and 1500 V d.c.- Equipment for
testing, measuring or monitoring of protective measures:-
Part 1 - General requirements
Part 2 - Insulation resistance
Part 3 - Loop resistance
Part 4 - Continuity
Part 5 - Earth test
Part 6 - Residual current devices (RCD)
Part 10 - Combined measuring equipment
23
Page 24
ACCESSORIES
ProductOrder Code
Multifunction tester standardMFT1501
Multifunction tester with illuminated
switched probe MFT1502
Multifunction tester with automatic RCD testingMFT1552
Multifunction tester with
Bluetooth®DownloadingMFT1553
PowerSuite On-site software6111-777
Accessories included with MFT1501
Quick start guide
3 wire test lead
Crocodile clips (red, black and green)
Probes (red, black)
Mains plug (BS1363) test lead
CD (including full user guide)
Additional accessories with MFT1502/MFT1552/MFT1553
As MFT1501 plus:
Illuminated switched probe
Instrument/document carry case
Optional accessoriesOrder code
Replacement 3 wire test lead set6220-796
Fused prod and clip set6180-405
Standard switched probe6220-836
Illuminated switched probe6311-089
Test lead with Schuko plug6231-593
Test lead with UK mains plug6231-601
Test lead with USA mains plug6220-643
Earth bond test lead set6231-586
Instrument/Document carry case6420-143
Replacement Probe Tip Set (for SPL1000)6121-562
MFT1501/2E / MFT1502/2E
As MFT1501/MFT1502 but supplied with a Schuko mains lead plug
(6231-593) instead of a BS plug.
The Bluetooth word mark and logo are owned by Bluetooth SIG. Inc. and
any use of such marks by Megger is under licence.
24
Page 25
REPAIR AND WARRANTY
The instrument contains static sensitive devices, and care must be taken in
handling the printed circuit board. If an instrument’s protection has been
impaired it should not be used, but sent for repair by suitably trained and
qualified personnel.
The protection is likely to be impaired if for example; it shows visible
damage; fails to perform the intended measurements; has been subjected to
prolonged storage under unfavourable conditions, or has been subjected to
severe transport stresses.
NEW INSTRUMENTS ARE WARRANTED FOR 3 YEARS FROM THE
DATE OF PURCHASE BY THE USER.
NOTE: Any unauthorized prior repair or adjustment will automatically
invalidate the Warranty.
CALIBRATION, REPAIR AND SPARE PARTS
For service requirements for Megger Instruments contact:
Megger LimitedorMegger
Archcliffe Road Valley Forge Corporate Centre
Dover 2621 Van Buren Avenue
Kent CT17 9ENNorristown PA 19403
England.U.S.A.
Tel: +44 (0) 1304 502 243Tel: +1 610 676 8579
Fax: +44 (0) 1304 207 342 Fax: +1 610 676 8625
Megger operate fully traceable calibration and repair facilities, ensuring your
instrument continues to provide the high standard of performance and
workmanship you expect. These facilities are complemented by a worldwide
network of approved repair and calibration companies to offer excellent inservice care for your Megger products.
Returning your product to Megger - UK and USA service
centres
1. When an instrument requires recalibration, or in the event of a repair
being necessary, a Returns Authorisation (RA) number must first be
obtained from one of the addresses shown. You will be asked to
provide the following information to enable the Service Department to
prepare in advance for receipt of your instrument, and to provide the
best possible service to you.
■ Model, e.g. MFT1501
■ Serial number, (e.g. 61110357050305/1234)
■ Reason for return, (e.g. calibration required, or repair)
■ Details of the fault (if the instrument is to be repaired)
2. Make a note of the RA number. A returns label can be emailed or faxed
to you if you wish.
3. Pack the instrument carefully with plenty of padding, but no pressure on
window or glass.
4. Ensure the returns label is attached, or that the RA number is clearly
marked on the outside of the package and on any correspondence,
before sending the instrument, carriage paid, to Megger.
5. You make track the progress of your return on line by accessing the
Service/Support facilities at www.megger.com
Approved Service Centres
A list of Approved Service Centres may be obtained from the UK address
shown. If outside UK/USA please consult your distributor for the most
convenient Service Organisation.
25
Page 26
ADDITIONAL BLUETOOTH INFORMATION (ATTACHING A DONGLE)
Megger MFT1553 Bluetooth Procedure
This guide provides detailed methods of attaching a Bluetooth Dongle to a
laptop or PC.
1. Initial Installation and setup
Installation of “Bluetooth Dongle”
Unless previously installed or built in you must first install a third party
“Bluetooth Dongle” on your computer. There are three common “Bluetooth
Stacks” employed by third party dongles. This will not normally be stated on
the dongle packaging but each will install slightly differently. A brief
summary of the common types will follow but follow any instructions
supplied with the product.
Some machines have Bluetooth communications built in but not enabled by
default. The IBM T43 laptop series are such an example where you need to
hold down the “Fn” key and press the “F5” key to enable “Bluetooth”
operation.
It is vital that you reboot you computer after the installation is complete and
before running “Megger Download Manager” for the first time.
2. Typical install process for A Widcomm Driver (Belkin in this
case)
The install process starts when the vendor CD is placed in the drive.
This message may appear
…..Click OK.
Plug the Dongle in when requested.
…..Click OK.
Click “Finish”
The “Bluetooth Drivers are only partially setup at this stage. To finish the
setup “Right Click” on the “Bluetooth” icon in the system tray.
26
Click Next,
The Following box will appear.
Page 27
Click Next.
Click Next.
Confirm ticks are shown in the boxes shown……Click Next.
This will be confirmed with a message balloon as shown.
MUST Click Skip at this Stage
You
Click Finish and you must reboot the computer.
3. Typical install process for A Bluesoleil Driver.
The install process starts when the vendor CD is placed in the drive.
27
Page 28
Click OK.
Click Next.
Click “I Accept…” and Next.
Accept the default settings and Next.
To start Install, Click on Install.
Click on Finish.
Accept the default settings and Next.
28
Page 29
4. Typical install process for Microsoft Drivers.
Click on “Open
Bluetooth
Settings”.
Click “Add”
Click on “Com
Ports” Tab
Plug “Bluetooth” Dongle into computer.
you must reboot the computer.
Plug the Dongle in when requested.
Switch Security level from Medium by removing the “Tick”. This driver
exhibits unusual behaviour when set to “Medium” but “High” or “Low” work
correctly.
Auto detect and install will now start.
Right Click on “Bluetooth” icon
in the system tray.
29
Page 30
Incoming should be selected by default.
Click on “Turn
Discovery On”
Click on
“Options” tab.
If not click on radio button. Click OK.
Click Finish and you must reboot the computer.
30
Page 31
31
Page 32
M
Megger Limited
Archcliffe Road, Dover
Kent CT17 9EN England
T +44 (0)1 304 502101
F +44 (0)1 304 207342
E uksales@megger.com
Megger products are distributed in 146 countries worldwide.
This instrument is manufactured in the United Kingdom.
The company reserves the right to change the specification or design without prior notice.
Megger is a registered trademark
Part No. 6172-914 V08 Printed in England 0307
www.megger.com
Megger
4271 Bronze Way, Dallas,
Texas 75237-1019 USA
T +1 800 723 2861 (USA ONLY)
T +1 214 333 3201
F +1 214 331 7399
E ussales@megger.com
Megger
Z.A. Du Buisson de la Couldre
23 rue Eugène Henaff
78190 TRAPPES France
T +33 (0)1 30.16.08.90
F +33 (0)1 34.61.23.77
E infos@megger.com
Megger Pty Limited
Unit 26 9 Hudson Avenue
Castle Hill
Sydney NSW 2125 Australia
T +61 (0)2 9659 2005
F +61 (0)2 9659 2201
E ausales@megger.com
Megger Limited
110 Milner Avenue Unit 1
Scarborough Ontario M1S 3R2
Canada
T +1 416 298 9688 (Canada only)
T +1 416 298 6770
F +1 416 298 0848
E casales@megger.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.