Megger MFT1500 Quick Start Manual

M
MFT1500 Series
Multifunction Tester
Quick Start Guide
GSAFETY WARNINGS
Safety Warnings and Precautions must be read and understood
before the instrument is used. They must be observed during use.
isolated before test connections are made when carrying out insulation and continuity tests.
Continuity of protective conductors and earthed equipotential bonding
of new or modified installations must be verified before carrying out an earth fault loop impedance test, or RCD test.
Circuit connections and exposed metalwork of an installation or
equipment under test must not be touched.
The live circuit warning and Automatic discharge are additional safety
features and should not be regarded as a substitute for normal safe working practices.
Do not move the rotary switch positions while a test is in progress.
The LCD ‘neon’ voltage indicators cannot reveal a Neutral - Earth
reversal. They cannot be relied upon to identify circuit correctness and are for guidance only.
After insulation tests, capacitive circuits must be allowed to discharge
before disconnecting test leads.
The instrument should not be used if any part of it is damaged.
Test leads, probes and crocodile clips must be in good order, clean
and with no broken or cracked insulation.
Ensure that hands remain behind guards of probes/clips when testing.
U.K. Safety Authorities recommend the use of fused test leads when
measuring voltage on high energy systems.
Replacement fuses must be of the correct type and rating. Failure to fit
the correctly rated fuse will result in damage to the instrument in the event of an overload.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND
COMPETENT PERSONS
Users of this equipment and/or their employers are reminded that Health and Safety Legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent short circuits.
Where the assessments show that the risk is significant then the use of fused test leads constructed in accordance with the HSE guidance note GS38 'Electrical Test Equipment for use by Electricians' should be used.
Symbols used on the instrument are:
F Caution: risk of electric shock G Caution: refer to accompanying notes
t Equipment protected throughout by Double Insulation (Class II) c Equipment complies with current EU directives.
>500V
G
Equipment must not be connected to installations >500 V.
BLUE (0º - 180º) ORANGE (BUZZER)
BLACK (BACKLIGHT) YELLOW (TEST)
RED (LOCK)
Backlight (MFT1502 only)
Intelligent mode - operates automatically. To switch to manual mode, press the RED lock and the BLACK backlight buttons together.
Voltage, Continuity and Insulation testing
BLACK
RED
OPTION 1
2 wire lead set
BLACK
PROBE
OPTION 2
Switched probe
Voltage measurement (V) Range switch set to (V) range
The MFT1500 will automatically display circuit voltage up to 500 V a.c./d.c.
Continuity Measurement [] Range switch set to [] range
Test Lead options 1 or 2
The MFT1500 will automatically display continuity resistance when connected.
Lead Null
Short test leads together and press the YELLOW test button on the instrument or Switched Probe.
Continuity Buzzer (
The buzzer will sound automatically when a circuit is made (default threshold <2 )
Buzzer Threshold (
Select BUZZER range and press the ORANGE button until required range is displayed. Options, 2 , 5 , 10 , 20 , 50 , and 100
Warning: Ensure the circuit to be tested is disconnected and isolated before starting testing.
Z
Z
)
)
Loading...
+ 5 hidden pages